- SunSaver Duo dual-battery PWM charge controller (Modbus RTU via MeterBus)
Solar charge controller (PWM, dual battery) · Modbus register map
Morningstar SunSaver Duo dual-battery PWM charge controller (Modbus RTU via MeterBus) Modbus register map
Updated 17 November 2026
The SunSaver Duo is a PWM solar charge controller that charges two separate batteries. Via its RJ-11 MeterBus port and Morningstar's MSC adapter it speaks Modbus RTU: both battery voltages and charge currents, solar voltage, duty cycles, charge setpoints in use, state and fault bits, plus EEPROM custom settings and a few coils.
This page lists 52 Modbus registers for the Morningstar SunSaver Duo dual-battery PWM charge controller (Modbus RTU via MeterBus) — 14 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Morningstar’s own free documentation (linked below) and checked against it.
- Manufacturer
- Morningstar
- Model
- SunSaver Duo dual-battery PWM charge controller (Modbus RTU via MeterBus)
- Equipment type
- Solar charge controller (PWM, dual battery)
- Registers
- 52 (14 writable)
- Transport
- Modbus RTU
- Default unit ID
- 1
- Default serial
- 9600 baud, 8N2
- Documented addressing
- hexadecimal, 0-based
- Also known as
- SunSaver Duo, SSDuo
- Source document
- SunSaver Duo MODBUS Specification · V04 · rev. 2019-03-19
Integration notes: Morningstar SunSaver Duo dual-battery PWM charge controller (Modbus RTU via MeterBus)
Through the MSC adapter at 9600 8N2, ID 1, read 0x0000-0x0010 for both battery voltages, solar voltage and charge currents, and 0x0108-0x0110 for state, faults and battery states.
Minimum registers to map
Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.
| Register | Name | Type | Why | Access |
|---|---|---|---|---|
| HR 0 | vb1 - battery 1 voltage | UINT16 | Battery 1 voltage | Read |
| HR 1 | vb2 - battery 2 voltage | UINT16 | Battery 2 voltage | Read |
| HR 3 | ia1 - charge current battery 1 | UINT16 | Charge current battery 1 | Read |
| HR 4 | ia2 - charge current battery 2 | UINT16 | Charge current battery 2 | Read |
| HR 264 | state - controller state | UINT16 | Controller state | Read |
| HR 265 | faults - fault bitfield | BITMAP16 | Fault bitfield | Read |
Enable Modbus control & writes
The meter port auto-detects Meterbus or Modbus; connect the MSC adapter and poll. Coil 0x00F1 switches the port back to Meterbus for a remote meter.
Byte order & addressing
- Both FC 0x03 and FC 0x04 are supported for reading.
- EEPROM values that need updating are saved once every 24 hours; coil 0x0016 forces it.
Network setup
- Serial: 9600 baud, 8 data bits, no parity, 2 stop bits, no flow control.
Watch out for
- The RJ-11 port is MeterBus, not RS-485; Morningstar's MSC adapter is needed.
Morningstar SunSaver Duo dual-battery PWM charge controller (Modbus RTU via MeterBus) Modbus registers
Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.
| Table | Address | Name | Description | Type | Order | Scale | Units | Access | Values / bits |
|---|---|---|---|---|---|---|---|---|---|
| CO | 20doc 0x0014 | Clear faults | Some faults need 30 s before they can be cleared. | BIT | Write | ||||
| CO | 22doc 0x0016 | Force EEPROM update | Writes RAM values to EEPROM. | BIT | Write | ||||
| CO | 23doc 0x0017 | Reset min/max volts and amps | Set only; reads 0. | BIT | Write | ||||
| CO | 241doc 0x00F1 | Switch to Meterbus protocol | Hands the port back to the Morningstar remote meter protocol. | BIT | Write | ||||
| CO | 255doc 0x00FF | Reset controller | Reboots the controller software. | BIT | Write | ||||
| HR | 0doc 0x0000 | vb1 - battery 1 voltage | Filtered (about 2.5 s). | UINT16 | × 0.0005555556 | V | Read | ||
| HR | 1doc 0x0001 | vb2 - battery 2 voltage | UINT16 | × 0.0005555556 | V | Read | |||
| HR | 2doc 0x0002 | va - solar voltage | UINT16 | × 0.0009689922 | V | Read | |||
| HR | 3doc 0x0003 | ia1 - charge current battery 1 | UINT16 | × 0.0014858841 | A | Read | |||
| HR | 4doc 0x0004 | ia2 - charge current battery 2 | UINT16 | × 0.0014858841 | A | Read | |||
| HR | 8doc 0x0008 | vref1 - charge reference battery 1 | Temperature-compensated target voltage. | UINT16 | × 0.0005555556 | V | Read | ||
| HR | 9doc 0x0009 | vref2 - charge reference battery 2 | UINT16 | × 0.0005555556 | V | Read | |||
| HR | 10doc 0x000A | dutcyc1 - PWM duty battery 1 | 0-417 = 0-100 %. | UINT16 | × 0.2398081535 | % | Read | ||
| HR | 11doc 0x000B | dutcyc2 - PWM duty battery 2 | UINT16 | × 0.2398081535 | % | Read | |||
| HR | 12doc 0x000C | vmaxb1 - max battery 1 voltage | Since last min/max clear. | UINT16 | × 0.0005555556 | V | Read | ||
| HR | 13doc 0x000D | vminb1 - min battery 1 voltage | UINT16 | × 0.0005555556 | V | Read | |||
| HR | 14doc 0x000E | vmaxb2 - max battery 2 voltage | UINT16 | × 0.0005555556 | V | Read | |||
| HR | 15doc 0x000F | vminb2 - min battery 2 voltage | UINT16 | × 0.0005555556 | V | Read | |||
| HR | 16doc 0x0010 | iamax - max solar current | UINT16 | × 0.0014858841 | A | Read | |||
| HR | 27doc 0x001B | tcompcoef - temperature compensation in use | UINT16 | × 0.0005555556 | V | Read | |||
| HR | 28doc 0x001C | priority - battery 1 charge priority | Share of charge current to battery 1 (0-417 = 0-100 %). | UINT16 | × 0.2398081535 | % | Read | ||
| HR | 29doc 0x001D | vabs1 - absorption voltage battery 1 | UINT16 | × 0.0005555556 | V | Read | |||
| HR | 30doc 0x001E | veql1 - equalize voltage battery 1 | UINT16 | × 0.0005555556 | V | Read | |||
| HR | 31doc 0x001F | vfloat1 - float voltage battery 1 | UINT16 | × 0.0005555556 | V | Read | |||
| HR | 32doc 0x0020 | vclamp1 - max regulation voltage battery 1 | UINT16 | × 0.0005555556 | V | Read | |||
| HR | 33doc 0x0021 | tfloat1 - float timer battery 1 | UINT16 | min | Read | ||||
| HR | 34doc 0x0022 | teq1 - equalize timer battery 1 | UINT16 | min | Read | ||||
| HR | 35doc 0x0023 | vabs2 - absorption voltage battery 2 | UINT16 | × 0.0005555556 | V | Read | |||
| HR | 36doc 0x0024 | veql2 - equalize voltage battery 2 | UINT16 | × 0.0005555556 | V | Read | |||
| HR | 37doc 0x0025 | vfloat2 - float voltage battery 2 | UINT16 | × 0.0005555556 | V | Read | |||
| HR | 38doc 0x0026 | vclamp2 - max regulation voltage battery 2 | UINT16 | × 0.0005555556 | V | Read | |||
| HR | 39doc 0x0027 | tfloat2 - float timer battery 2 | UINT16 | min | Read | ||||
| HR | 40doc 0x0028 | teq2 - equalize timer battery 2 | UINT16 | min | Read | ||||
| HR | 262doc 0x0106 | dc1 - duty cycle battery 1 | Pre-scaled percent. | UINT16 | % | Read | |||
| HR | 263doc 0x0107 | dc2 - duty cycle battery 2 | UINT16 | % | Read | ||||
| HR | 264doc 0x0108 | state - controller state | UINT16 | Read | 1 = NORMAL; 3 = NIGHT; 4 = FAULT | ||||
| HR | 265doc 0x0109 | faults - fault bitfield | BITMAP16 | Read | bit 0 = Reverse polarity solar; bit 1 = Reverse polarity battery 1; bit 2 = Reverse polarity battery 2; bit 3 = Damaged local temperature sensor; bit 4 = Damaged or removed RTS; bit 5 = Over-current; bit 6 = High temperature disconnect; bit 7 = High voltage disconnect | ||||
| HR | 266doc 0x010A | flags - controller flags | BITMAP16 | Read | bit 3 = Regulation; bit 4 = Valid RTS; bit 5 = Alternating; bit 6 = On/off regulation; bit 7 = Started | ||||
| HR | 267doc 0x010B | DIP switch positions | BITMAP16 | Read | bit 0 = DIP 1; bit 1 = DIP 2; bit 2 = DIP 3; bit 3 = DIP 4; bit 4 = DIP 5 | ||||
| HR | 269doc 0x010D | b1_state - battery 1 charge state | UINT16 | Read | 0 = NORMAL; 1 = EQUALIZE; 2 = FLOAT | ||||
| HR | 270doc 0x010E | b2_state - battery 2 charge state | UINT16 | Read | 0 = NORMAL; 1 = EQUALIZE; 2 = FLOAT | ||||
| HR | 271doc 0x010F | b1_detect - battery 1 detected | UINT16 | Read | 0 = Disconnected; 1 = Connected | ||||
| HR | 272doc 0x0110 | b2_detect - battery 2 detected | UINT16 | Read | 0 = Disconnected; 1 = Connected | ||||
| HR | 57346doc 0xE002 | priority_off - battery 1 priority, DIP 3 off | EEPROM custom setting (0-417). | UINT16 | × 0.2398081535 | % | Read/write | ||
| HR | 57347doc 0xE003 | priority_on - battery 1 priority, DIP 3 on | UINT16 | × 0.2398081535 | % | Read/write | |||
| HR | 57348doc 0xE004 | tcompcoef - temperature compensation (EEPROM) | Per 12 V battery per °C; typical 0.030. | UINT16 | × 0.0005555556 | V | Read/write | ||
| HR | 57350doc 0xE006 | Battery 1 (DIP 1 off) absorption voltage | UINT16 | × 0.0005555556 | V | Read/write | |||
| HR | 57351doc 0xE007 | Battery 1 (DIP 1 off) equalize voltage | 0 disables equalize. | UINT16 | × 0.0005555556 | V | Read/write | ||
| HR | 57352doc 0xE008 | Battery 1 (DIP 1 off) float voltage | UINT16 | × 0.0005555556 | V | Read/write | |||
| HR | 57362doc 0xE012 | Battery 2 (DIP 2 off) absorption voltage | UINT16 | × 0.0005555556 | V | Read/write | |||
| HR | 57363doc 0xE013 | Battery 2 (DIP 2 off) equalize voltage | UINT16 | × 0.0005555556 | V | Read/write | |||
| HR | 57364doc 0xE014 | Battery 2 (DIP 2 off) float voltage | UINT16 | × 0.0005555556 | V | Read/write |
Notes on this map
- Left out: the 32-bit hourmeter and amp-hour counters (0x0013-0x001A). The register table puts the HI word first, but the spec's own two-word example reads the hourmeter LO word at 0x0013 and HI at 0x0014, and the revision history says the HI/LO addresses were swapped in an earlier version. The word order cannot be settled from the document.
- Left out: the 'reset amp-hours' coil, because the table gives 0x0010 and the definitions page gives 0x0017 (which is also the min/max reset coil).
- Scaling formulas (n / 1800 for battery voltages, n / 1032 for solar voltage, n / 673 for currents, 0-417 = 0-100 % for duty/priority) are converted to multipliers.
- Left out: the pre-scaled temperatures at 0x0100-0x0105 (F and C copies), because the spec gives no data type or signedness for them and sub-zero readings are expected.
- Only the 'DIP off' custom voltages are listed for each battery; the 'DIP on' set (0xE00C-0xE011, 0xE018-0xE01D) follows the same layout. The two ID registers 0xE000/0xE001 are not listed because the table and the definitions disagree on which range belongs to which ID.
- Battery detect registers follow the register table (0x010F, 0x0110); the definitions page repeats the battery-state addresses for them, which looks like a copy error.
- Any EEPROM write (FC 0x06) sets an 'EEPROM changed' fault that needs a controller reset.
Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.
Questions about the Morningstar SunSaver Duo dual-battery PWM charge controller (Modbus RTU via MeterBus)
What Modbus registers does the Morningstar SunSaver Duo dual-battery PWM charge controller (Modbus RTU via MeterBus) have?
This map lists 52 registers: 5 coils, 47 holding registers. 14 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.
Are the Morningstar SunSaver Duo dual-battery PWM charge controller (Modbus RTU via MeterBus) Modbus addresses 0-based or 1-based?
The manufacturer's document numbers registers hexadecimal, 0-based. Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. The hex PDU address in Morningstar's table is the wire address; the spec says all listed addresses are request-PDU addresses, and its example reads battery 1 voltage at 0x0000 (0x5CD0 = 23760 / 1800 = 13.20 V).
What are the minimum Modbus registers to integrate the Morningstar SunSaver Duo dual-battery PWM charge controller (Modbus RTU via MeterBus)?
Start with HR 0 vb1 - battery 1 voltage (Battery 1 voltage); HR 1 vb2 - battery 2 voltage (Battery 2 voltage); HR 3 ia1 - charge current battery 1 (Charge current battery 1); HR 4 ia2 - charge current battery 2 (Charge current battery 2); HR 264 state - controller state (Controller state); HR 265 faults - fault bitfield (Fault bitfield).
How do I enable Modbus control of the Morningstar SunSaver Duo dual-battery PWM charge controller (Modbus RTU via MeterBus)?
The meter port auto-detects Meterbus or Modbus; connect the MSC adapter and poll. Coil 0x00F1 switches the port back to Meterbus for a remote meter.
Where is the official Morningstar SunSaver Duo dual-battery PWM charge controller (Modbus RTU via MeterBus) Modbus documentation?
The source is SunSaver Duo MODBUS Specification (V04), revision 2019-03-19, published free by Morningstar at https://www.morningstarcorp.com/wp-content/uploads/technical-doc-sunsaver-duo-modbus-specification-en.pdf.
More Morningstar Modbus register maps
- Solar charge controller (MPPT, battery charger)
Morningstar SunSaver MPPT solar charge controller (Modbus RTU via MeterBus)
Morningstar SunSaver MPPT through the MSC MeterBus-to-RS-232 adapter; Modbus specification v11.
Also known as: SunSaver MPPT, SS-MPPT - Battery inverter (off-grid sine wave)
Morningstar SureSine-300 off-grid sine-wave inverter (Modbus RTU via MeterBus)
Morningstar SureSine-300 (115 V and 220 V versions) via the MSC MeterBus adapter; Modbus specification V03 (29 Oct 2008).
Also known as: SureSine, SureSine-300 - Solar charge controller (PWM charge / load / diversion)
Morningstar TriStar TS-45 / TS-60 PWM charge, load and diversion controller (Modbus RTU)
Morningstar TriStar TS-45 and TS-60 (non-MPPT) on the RS-232 port; Modbus specification V07 (31 Jan 2020).
Also known as: TS-45, TS-60, TriStar, TriStar PWM
Other solar & battery inverters register maps
- Solar inverter gateway (PV plant data logger)
SMA Sunny WebBox Modbus gateway (plant and gateway unit IDs 1-2)
Sunny WebBox firmware 1.52 or later with Modbus enabled, SMA Modbus profile as documented in WEBBOX_MODBUS-TB-US-EN-19 v1.9 (legacy product).
Also known as: Sunny WebBox, WebBox, SWEBBOX, Sunny WebBox with Bluetooth - Battery inverter (off-grid inverter-charger)
Studer Innotec Xtender XTH / XTM / XTS inverter-charger (via Xcom-485i)
Studer Xtender XTH, XTM and XTS inverter-chargers read through an Xcom-485i Modbus RTU gateway, system release R706.
Also known as: XTH, XTM, XTS, Xtender XTH, Xtender XTM, Xtender XTS, Xcom-485i - Solar inverter
Fronius Tauro ECO 50-100 (SunSpec int+SF)
Fronius Tauro ECO 50-100 kW commercial inverters (rest-of-world map, single MPPT), SunSpec Model Type int+SF.
Also known as: Fronius Tauro ECO, Tauro ECO 50-3-P, Tauro ECO 99-3-D, Tauro ECO 100-3-P, Tauro ECO 100-3-D - Solar inverter (via Sunny WebBox gateway)
SMA Sunny WebBox Modbus profile - common addresses of SMA devices (unit IDs 3-247)
SMA devices reached through a Sunny WebBox (fw 1.52+) on unit IDs 3-247 whose family uses the common address set; SB n000US and SB nn000TL-US-12 families use their own tables instead.
Also known as: Sunny WebBox device profile, SMA Modbus profile WebBox, Sunny Central via WebBox, Sunny Tripower STP nn000TL-10 via WebBox, Sunny Mini Central via WebBox - Sensor (battery monitoring system)
Vertiv (Alber) Alber MPM-100 and BDS series battery monitors (Modbus ASCII)
Alber MPM-100 (firmware 1.20+) and BDS series (controller firmware 2.20+) battery monitors with BMDM software 4.10+, per protocol document SL-29417 Rev 7.05.
Also known as: Alber MPM-100, Alber BDS, BDS-40, BDS40, MPM100, Vertiv Alber battery monitor, SL-29417 - Battery charger (industrial float charger, UPS-type DC system)
HindlePower AT10.1 / AT30 series battery charger with communications module (Modbus)
HindlePower AT10.1 and AT30 microprocessor-controlled float battery chargers fitted with the AT Series Communications Module (EJ5037-##) set to Modbus, per operating instructions JA0102-04 Rev. 02-2025.
Also known as: AT10.1, AT30, EJ5037, AT Series Communications Module
All solar & battery inverters Modbus register maps →
Source: SunSaver Duo MODBUS Specification · V04 · rev. 2019-03-19. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.