- AT10.1 / AT30 series battery charger with communications module (Modbus)
Battery charger (industrial float charger, UPS-type DC system) · Modbus register map
HindlePower AT10.1 / AT30 series battery charger with communications module (Modbus) Modbus register map
Updated 17 November 2026
HindlePower's AT10.1 and AT30 industrial float battery chargers can carry a communications module that speaks Modbus RTU or ASCII (or DNP3) over RS-232/RS-485, with optional Ethernet. Charger modes are coils, alarms are discrete inputs, measurements are input registers and setpoints are holding registers, all 16-bit with a fixed multiplier. This map covers the full published Modbus register set.
This page lists 33 Modbus registers for the HindlePower AT10.1 / AT30 series battery charger with communications module (Modbus) — 12 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from HindlePower’s own free documentation (linked below) and checked against it.
- Manufacturer
- HindlePower
- Model
- AT10.1 / AT30 series battery charger with communications module (Modbus)
- Registers
- 33 (12 writable)
- Transport
- Modbus RTU, Modbus ASCII, Modbus TCP
- Default unit ID
- Not stated
- Default serial
- 8N1
- TCP port
- 502
- Documented addressing
- Modicon 3xxxx/4xxxx (drop the prefix, subtract 1)
- Firmware
- Charger main control board software Rev. 3.00 or higher
- Also known as
- AT10.1, AT30, EJ5037, AT Series Communications Module
Integration notes: HindlePower AT10.1 / AT30 series battery charger with communications module (Modbus)
Set DIP S1-3 off (Modbus), S1-4 off for RTU (on = ASCII), S1-5 on for RS-485, S1-7 for the baud rate and S2 for the address, press RESET on the A12 board, then poll 30006/30007 for output voltage and current and 10001-10012 for alarms.
Minimum registers to map
Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.
| Register | Name | Type | Why | Access |
|---|---|---|---|---|
| IR 5 | Output voltage | UINT16 | Output voltage, 0.1 V | Read |
| IR 6 | Output current | UINT16 | Output current, 0.1 A | Read |
| DI 6 | CAR (common alarm relay) | BIT | Common alarm | Read |
| DI 3 | AC input failure | BIT | AC input failure | Read |
| DI 2 | DC output failure | BIT | DC output failure | Read |
| HR 0 | Float voltage setpoint | UINT16 | Float voltage setpoint | Read/write |
| CO 0 | Equalize mode | BIT | Equalize / float mode | Read/write |
Enable Modbus control & writes
DIP S1-3 OFF selects Modbus (ON = DNP3); S1-4 OFF = RTU, ON = ASCII; S1-5 ON = RS-485, OFF = RS-232; S1-7 ON = 19200, OFF = 9600; S1-8 enables Ethernet; S1-2 OFF uses factory-default configuration values; S2-1...S2-8 set the address bits b7...b0. Changes take effect after pressing RESET (SW10) on the A12 board or cycling both charger breakers.
Byte order & addressing
- Values are scaled integers: divide by the multiplier (10 for volts and amps, 100 for revisions).
- For telephone-modem links the manual recommends Modbus ASCII because RTU timing is tighter.
Network setup
- Up to 32 chargers per RS-485 segment; 2-wire half-duplex.
- Advanced settings (DNP3, Ethernet, Modbus TCP) need the setup program over RS-232 at 9600 8N1 with S1-1 ON.
Watch out for
- Chargers built before 2003 may need a new or reprogrammed main control board (software 3.00+) before the module works.
HindlePower AT10.1 / AT30 series battery charger with communications module (Modbus) Modbus registers
Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.
| Table | Address | Name | Description | Type | Order | Scale | Units | Access | Values / bits |
|---|---|---|---|---|---|---|---|---|---|
| CO | 0doc 00001 | Equalize mode | 1 = equalize, 0 = float. | BIT | Read/write | ||||
| CO | 1doc 00002 | Manual timer equalize method | Selecting one equalize method turns the other two off. | BIT | Read/write | ||||
| CO | 2doc 00003 | Manual equalize method | BIT | Read/write | |||||
| CO | 3doc 00004 | Auto-equalize timer method | BIT | Read/write | |||||
| CO | 4doc 00005 | HVDC shutdown enable | Enables high-voltage DC shutdown. | BIT | Read/write | ||||
| CO | 5doc 00006 | Battery type | 0 = lead, 1 = NiCd (used for temperature compensation). | BIT | Read/write | ||||
| DI | 0doc 10001 | HVDC alarm | High DC voltage alarm. | BIT | Read | ||||
| DI | 1doc 10002 | LVDC alarm | Low DC voltage alarm. | BIT | Read | ||||
| DI | 2doc 10003 | DC output failure | Charger failure alarm. | BIT | Read | ||||
| DI | 3doc 10004 | AC input failure | BIT | Read | |||||
| DI | 4doc 10005 | Positive ground fault | BIT | Read | |||||
| DI | 5doc 10006 | Negative ground fault | BIT | Read | |||||
| DI | 6doc 10007 | CAR (common alarm relay) | Summary alarm relay active. | BIT | Read | ||||
| DI | 7doc 10008 | HVDC shutdown enabled | BIT | Read | |||||
| DI | 8doc 10009 | LVAC shutdown enabled | BIT | Read | |||||
| DI | 9doc 10010 | Forced load share enabled | BIT | Read | |||||
| DI | 10doc 10011 | Temperature probe installed | BIT | Read | |||||
| DI | 11doc 10012 | Defective temperature probe | BIT | Read | |||||
| IR | 0doc 30001 | Communication firmware revision | Multiplier 100 (e.g. 300 = 3.00). | UINT16 | × 0.01 | Read | |||
| IR | 1doc 30002 | DNP revision | Multiplier 100. | UINT16 | × 0.01 | Read | |||
| IR | 2doc 30003 | AT10.1 firmware revision | Charger software revision, multiplier 100. | UINT16 | × 0.01 | Read | |||
| IR | 3doc 30004 | Voltage rating | Charger nominal voltage rating. | UINT16 | V | Read | |||
| IR | 4doc 30005 | Current rating | Charger current rating. | UINT16 | A | Read | |||
| IR | 5doc 30006 | Output voltage | UINT16 | × 0.1 | V | Read | |||
| IR | 6doc 30007 | Output current | UINT16 | × 0.1 | A | Read | |||
| IR | 7doc 30008 | Equalize time remaining | UINT16 | h | Read | ||||
| IR | 8doc 30009 | Error number | Self-diagnostic error code. | UINT16 | Read | ||||
| HR | 0doc 40001 | Float voltage setpoint | UINT16 | × 0.1 | V | Read/write | |||
| HR | 1doc 40002 | Equalize voltage setpoint | UINT16 | × 0.1 | V | Read/write | |||
| HR | 2doc 40003 | Equalize time | 0-255 hours. | UINT16 | h | Read/write | |||
| HR | 3doc 40004 | Current limit | UINT16 | × 0.1 | A | Read/write | |||
| HR | 4doc 40005 | HVDC alarm setpoint | High DC voltage alarm level. | UINT16 | × 0.1 | V | Read/write | ||
| HR | 5doc 40006 | LVDC alarm setpoint | Low DC voltage alarm level. | UINT16 | × 0.1 | V | Read/write |
Notes on this map
- Scaling: each register has a multiplier; the raw value is divided by it (manual's example: 30006 = 1300 means 130.0 V). Scale = 1 / multiplier.
- Left out: 30010 Battery temperature (°C, multiplier 1): the manual does not say whether below-zero temperatures are sent as signed values.
- Modbus RTU settings: 8 data bits with none/even/odd parity (1 or 2 stop bits with no parity); ASCII uses 7 data bits. Baud is 9600 or 19200 (DIP S1-7). The Modbus address is set in binary on DIP S2. The setup program's factory defaults are no parity and 1 stop bit.
- Modbus over TCP/IP is available with the Ethernet option; it is disabled by default (setup program item 'Enable Modbus over TCP/IP') and its default port is 502. Port 20000 is the default for DNP3 over TCP, not Modbus.
- Only one equalize method coil can be active; switching one on turns the other two off, and the method cannot be switched off.
Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.
Questions about the HindlePower AT10.1 / AT30 series battery charger with communications module (Modbus)
What Modbus registers does the HindlePower AT10.1 / AT30 series battery charger with communications module (Modbus) have?
This map lists 33 registers: 6 coils, 12 discrete inputs, 9 input registers, 6 holding registers. 12 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.
Are the HindlePower AT10.1 / AT30 series battery charger with communications module (Modbus) Modbus addresses 0-based or 1-based?
The manufacturer's document numbers registers Modicon 3xxxx/4xxxx (drop the prefix, subtract 1). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. Registers are printed with Modicon prefixes (00001 coils, 10001 discrete inputs, 30001 input registers, 40001 holding registers) and the implementation follows the Modicon PI-MBUS-300 guide, so 30001 is input register 0 on the wire, 40001 holding register 0, and so on.
What are the minimum Modbus registers to integrate the HindlePower AT10.1 / AT30 series battery charger with communications module (Modbus)?
Start with IR 5 Output voltage (Output voltage, 0.1 V); IR 6 Output current (Output current, 0.1 A); DI 6 CAR (common alarm relay) (Common alarm); DI 3 AC input failure (AC input failure); DI 2 DC output failure (DC output failure); HR 0 Float voltage setpoint (Float voltage setpoint); CO 0 Equalize mode (Equalize / float mode).
How do I enable Modbus control of the HindlePower AT10.1 / AT30 series battery charger with communications module (Modbus)?
DIP S1-3 OFF selects Modbus (ON = DNP3); S1-4 OFF = RTU, ON = ASCII; S1-5 ON = RS-485, OFF = RS-232; S1-7 ON = 19200, OFF = 9600; S1-8 enables Ethernet; S1-2 OFF uses factory-default configuration values; S2-1...S2-8 set the address bits b7...b0. Changes take effect after pressing RESET (SW10) on the A12 board or cycling both charger breakers.
Where is the official HindlePower AT10.1 / AT30 series battery charger with communications module (Modbus) Modbus documentation?
The source is AT10.1/AT30 Series Microprocessor-Controlled Float Battery Charger - Communications Module (DNP3 Level 2 / Modbus Protocols) Operating Instructions (JA0102-04 Rev. 02-2025), revision 2025-02, published free by HindlePower at https://www.hindlepowerinc.com/media/j5mfmli1/ja0102-04.pdf.
More HindlePower Modbus register maps
Other solar & battery inverters register maps
- Battery inverter (off-grid sine wave)
Morningstar SureSine-300 off-grid sine-wave inverter (Modbus RTU via MeterBus)
Morningstar SureSine-300 (115 V and 220 V versions) via the MSC MeterBus adapter; Modbus specification V03 (29 Oct 2008).
Also known as: SureSine, SureSine-300 - Solar inverter
SolarEdge SolarEdge inverters (SunSpec logging)
SolarEdge single-, split- and three-phase inverters with SunSpec enabled (SolarEdge Go/SetApp units, or LCD units on firmware 3.xxxx+); meter 1 at the non-Synergy default base.
Also known as: SE5000, Synergy, SolarEdge SunSpec - Battery inverter (GX gateway for inverter/chargers, batteries and solar chargers)
Victron Energy GX device Modbus-TCP (Cerbo GX, Venus GX, Color Control GX)
Victron GX devices running Venus OS with the Modbus-TCP service enabled; register list version 3.81 (document Rev 54). Core system, VE.Bus inverter/charger, battery, solar charger and ESS registers only.
Also known as: Cerbo GX, Cerbo-S GX, Venus GX, Color Control GX, CCGX, Ekrano GX, Octo GX, MultiPlus-II GX, EasySolar-II GX, Venus OS, dbus-modbustcp - Solar charge controller (PWM charge / load / diversion)
Morningstar TriStar TS-45 / TS-60 PWM charge, load and diversion controller (Modbus RTU)
Morningstar TriStar TS-45 and TS-60 (non-MPPT) on the RS-232 port; Modbus specification V07 (31 Jan 2020).
Also known as: TS-45, TS-60, TriStar, TriStar PWM - Sensor (battery monitor for Studer systems)
Studer Innotec BSP battery status processor (via Xcom-485i)
Studer BSP-500 and BSP-1200 battery status processors read through an Xcom-485i Modbus RTU gateway, system release R706.
Also known as: BSP-500, BSP-1200, BSP500, BSP1200, Xcom-485i - Solar inverter
Fronius Primo GEN24 / Symo GEN24 (Plus) SunSpec int+SF
Fronius Primo/Symo GEN24 (Plus) rest-of-world variants with a battery configured, SunSpec Model Type int+SF; without a battery the MPPT model has 2 inputs and model 124 is absent.
Also known as: Primo GEN24 Plus, Symo GEN24 Plus, Primo GEN24, Symo GEN24, Symo GEN24 10.0 Plus, Primo GEN24 6.0 Plus
All solar & battery inverters Modbus register maps →
Source: AT10.1/AT30 Series Microprocessor-Controlled Float Battery Charger - Communications Module (DNP3 Level 2 / Modbus Protocols) Operating Instructions · JA0102-04 Rev. 02-2025 · rev. 2025-02. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.