- TriStar TS-45 / TS-60 PWM charge, load and diversion controller (Modbus RTU)
Solar charge controller (PWM charge / load / diversion) · Modbus register map
Morningstar TriStar TS-45 / TS-60 PWM charge, load and diversion controller (Modbus RTU) Modbus register map
Updated 17 November 2026
The TriStar TS-45/TS-60 is a PWM controller that runs as a solar charger, a load controller or a diversion regulator. Its RS-232 port speaks Modbus RTU: RAM registers carry battery, array/load voltage and currents, temperatures, Ah counters, control mode/state, alarm and fault bitfields and PWM duty; EEPROM registers hold setpoints, and coils trigger equalize, disconnect, resets and counter clears.
This page lists 45 Modbus registers for the Morningstar TriStar TS-45 / TS-60 PWM charge, load and diversion controller (Modbus RTU) — 22 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Morningstar’s own free documentation (linked below) and checked against it.
- Manufacturer
- Morningstar
- Model
- TriStar TS-45 / TS-60 PWM charge, load and diversion controller (Modbus RTU)
- Equipment type
- Solar charge controller (PWM charge / load / diversion)
- Registers
- 45 (22 writable)
- Transport
- Modbus RTU
- Default unit ID
- 1
- Default serial
- 9600 baud, 8N2
- Documented addressing
- hexadecimal, 0-based
- 32-bit word order
- ABCD high word first (big-endian)
- Firmware
- Alarm_HI (0x001D) needs software newer than 1.04.02; data logger needs firmware v13+.
- Also known as
- TS-45, TS-60, TriStar, TriStar PWM
- Source document
- TriStar MODBUS Specification · V07 · rev. 2020-01-31
Integration notes: Morningstar TriStar TS-45 / TS-60 PWM charge, load and diversion controller (Modbus RTU)
Connect to the RS-232 port at 9600 8N2, ID 1, and read 0x0008-0x001D in one request. Convert voltages with 96.667/32768 (battery) or 139.15/32768 (array/load). Check control mode 0x001A before interpreting control state 0x001B.
Minimum registers to map
Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.
| Register | Name | Type | Why | Access |
|---|---|---|---|---|
| HR 8 | adc_vb_f - battery voltage | UINT16 | Battery voltage | Read |
| HR 10 | adc_vx_f - array / load voltage | UINT16 | Array or load voltage | Read |
| HR 11 | adc_ipv_f - charging current | UINT16 | Charging current | Read |
| HR 26 | Control mode | UINT16 | Control mode | Read |
| HR 27 | Control state | UINT16 | Control state | Read |
| HR 24 | Fault bitfield | BITMAP16 | Fault bitfield | Read |
| CO 1 | Disconnect | BIT | Remote disconnect | Read/write |
Enable Modbus control & writes
Modbus is available on the RS-232 port at the factory settings (address 1); no enable step is described.
Byte order & addressing
- Each analog channel has its own scaling constant; check which applies before converting.
- EEPROM values that need updating are written once every 24 hours; use coil 0x0016 to force it.
- Clearing faults does not clear those that need a power cycle (e.g. DIP switch change).
Network setup
- Serial: 9600 baud, 8 data bits, no parity, 2 stop bits, no flow control, RS-232 only.
Watch out for
- The spec describes Modbus on the RS-232 port only; an RS-485 network needs a converter.
Morningstar TriStar TS-45 / TS-60 PWM charge, load and diversion controller (Modbus RTU) Modbus registers
Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.
| Table | Address | Name | Description | Type | Order | Scale | Units | Access | Values / bits |
|---|---|---|---|---|---|---|---|---|---|
| CO | 0doc 0x0000 | Equalize triggered | Equalizes while 1; set 0 to stop. | BIT | Read/write | ||||
| CO | 1doc 0x0001 | Disconnect | 1 forces DISCONNECT (MOSFETs off); 0 resumes. | BIT | Read/write | ||||
| CO | 16doc 0x0010 | Clear Ah resettable | Set only; reads 0. | BIT | Write | ||||
| CO | 17doc 0x0011 | Clear Ah total | Set only; reads 0. | BIT | Write | ||||
| CO | 18doc 0x0012 | Clear kWh | Set only; reads 0. | BIT | Write | ||||
| CO | 19doc 0x0013 | Reset battery service reminder | Set only. | BIT | Write | ||||
| CO | 20doc 0x0014 | Clear faults | Some faults need 10 s before they can be cleared. | BIT | Write | ||||
| CO | 21doc 0x0015 | Clear alarms | Set only. | BIT | Write | ||||
| CO | 22doc 0x0016 | Force EEPROM update | Writes RAM values to EEPROM. | BIT | Write | ||||
| CO | 23doc 0x0017 | LVD override for one cycle | Load/lighting mode: forces the load back on. | BIT | Write | ||||
| CO | 255doc 0x00FF | Reset control | Reboots the controller software. | BIT | Write | ||||
| HR | 8doc 0x0008 | adc_vb_f - battery voltage | Filtered (about 2.5 s). | UINT16 | × 0.0029500427 | V | Read | ||
| HR | 9doc 0x0009 | adc_vs_f - battery sense voltage | At the battery sense terminals. | UINT16 | × 0.0029500427 | V | Read | ||
| HR | 10doc 0x000A | adc_vx_f - array / load voltage | PV input in charge mode, load terminals in load mode. | UINT16 | × 0.004246521 | V | Read | ||
| HR | 11doc 0x000B | adc_ipv_f - charging current | UINT16 | × 0.0020345154 | A | Read | |||
| HR | 12doc 0x000C | adc_iload_f - load current | UINT16 | × 0.0096640015 | A | Read | |||
| HR | 13doc 0x000D | Vb_f - battery voltage, slow filter | About 25 s filter. | UINT16 | × 0.0029500427 | V | Read | ||
| HR | 14doc 0x000E | T_hs - heatsink temperature | INT16 | °C | Read | ||||
| HR | 15doc 0x000F | T_batt - battery temperature | From the RTS; 0x80 if not connected. | INT16 | °C | Read | |||
| HR | 16doc 0x0010 | V_ref - charge regulation reference | Temperature compensated. | UINT16 | × 0.0029500427 | V | Read | ||
| HR | 17doc 0x0011 | Ah resettable | UINT32 | ABCD | × 0.1 | Ah | Read | ||
| HR | 19doc 0x0013 | Ah total | UINT32 | ABCD | × 0.1 | Ah | Read | ||
| HR | 21doc 0x0015 | Hourmeter | Hours of operation (24-bit range). | UINT32 | ABCD | h | Read | ||
| HR | 23doc 0x0017 | Alarm bitfield LO (bits 0-15) | BITMAP16 | Read | bit 0 = RTS open; bit 1 = RTS shorted; bit 2 = RTS disconnected; bit 3 = Ths disconnected; bit 4 = Ths shorted; bit 5 = TriStar hot; bit 6 = Current limit; bit 7 = Current offset; bit 8 = Battery sense; bit 9 = Battery sense disconnected; bit 10 = Uncalibrated; bit 11 = RTS miswire; bit 12 = HVD; bit 13 = High d (duty); bit 14 = Miswire; bit 15 = FET open | ||||
| HR | 24doc 0x0018 | Fault bitfield | BITMAP16 | Read | bit 0 = External short; bit 1 = Overcurrent; bit 2 = FET short; bit 3 = Software; bit 4 = HVD; bit 5 = TriStar hot; bit 6 = DIP switch changed; bit 7 = Setting edit; bit 8 = Reset?; bit 9 = Miswire; bit 10 = RTS shorted; bit 11 = RTS disconnected | ||||
| HR | 25doc 0x0019 | DIP switch settings | Switch 1-8 at power-on in bits 0-7. | UINT16 | Read | ||||
| HR | 26doc 0x001A | Control mode | UINT16 | Read | 0 = Charge; 1 = Load; 2 = Diversion; 3 = Lighting | ||||
| HR | 27doc 0x001B | Control state | Meaning depends on control mode: charge/diversion name first, load/lighting second. | UINT16 | Read | 0 = START; 1 = NIGHT CHECK / NORMAL (load); 2 = DISCONNECT / LVD WARN (load); 3 = NIGHT / LVD (load); 4 = FAULT; 5 = BULK / DISCONNECT (load); 6 = PWM / NORMAL OFF (lighting); 7 = FLOAT / OVERRIDE LVD (lighting); 8 = EQUALIZE | |||
| HR | 28doc 0x001C | d_filt - PWM duty cycle | 0-255; 230 and above = 100 %. | UINT16 | Read | ||||
| HR | 29doc 0x001D | Alarm bitfield HI (bits 16-23) | Not available on software 1.04.02 or older. | BITMAP16 | Read | bit 0 = P12 (alarm bit 16); bit 1 = Load disconnect (alarm bit 17) | |||
| HR | 57344doc 0xE000 | EV_reg - regulation voltage @25°C | UINT16 | × 0.0029500427 | V | Read/write | |||
| HR | 57345doc 0xE001 | EV_float - float voltage @25°C | 0 disables float. | UINT16 | × 0.0029500427 | V | Read/write | ||
| HR | 57346doc 0xE002 | Et_float - time before float | UINT16 | s | Read/write | ||||
| HR | 57350doc 0xE006 | EV_eq - equalize voltage @25°C | 0 disables equalize. | UINT16 | × 0.0029500427 | V | Read/write | ||
| HR | 57351doc 0xE007 | Et_eqcalendar - days between equalize | UINT16 | days | Read/write | ||||
| HR | 57355doc 0xE00B | EV_hvd - high voltage disconnect | 0 disables HVD. | UINT16 | × 0.0029500427 | V | Read/write | ||
| HR | 57356doc 0xE00C | EV_hvr - high voltage reconnect | UINT16 | × 0.0029500427 | V | Read/write | |||
| HR | 57359doc 0xE00F | EV_lvd - low voltage disconnect (load mode) | UINT16 | × 0.0029500427 | V | Read/write | |||
| HR | 57360doc 0xE010 | EV_lvr - low voltage reconnect (load mode) | UINT16 | × 0.0029500427 | V | Read/write | |||
| HR | 57364doc 0xE014 | Et_lvd_warn - LVD warning timeout | UINT16 | × 0.1 | s | Read/write | |||
| HR | 57384doc 0xE028 | EAh_r - resettable Ah (EEPROM) | LO word at 0xE028, HI at 0xE029. | UINT32 | CDAB | × 0.1 | Ah | Read | |
| HR | 57386doc 0xE02A | EAh_t - total Ah (EEPROM) | LO word at 0xE02A, HI at 0xE02B. | UINT32 | CDAB | × 0.1 | Ah | Read | |
| HR | 57389doc 0xE02D | EVb_min - minimum battery voltage | UINT16 | × 0.0029500427 | V | Read | |||
| HR | 57390doc 0xE02E | EVb_max - maximum battery voltage | UINT16 | × 0.0029500427 | V | Read | |||
| HR | 57408doc 0xE040 | Emb_meterbus_id - MeterBus ID | 1-15. | UINT16 | Read/write |
Notes on this map
- Scaling: formulas n x 96.667 x 2^-15 (battery voltages), n x 139.15 x 2^-15 (array/load voltage), n x 66.667 x 2^-15 (charging current) and n x 316.67 x 2^-15 (load current) are converted to single multipliers. Example from the spec: 0x1007 = 4103 x 96.667 / 32768 = 12.1 V.
- Word order: the RAM table names each pair HI word first (Ah_r_HI 0x0011, Ah_r_LO 0x0012), so these are ABCD. The EEPROM Ah copies are printed LO first (EAh_r_LO 0xE028), so they are CDAB.
- The alarm bitfield is split: bits 0-15 at 0x0017 and bits 16-23 at 0x001D, so it is listed as two 16-bit registers.
- Control state codes mean different things in charge/diversion and in load/lighting mode; both meanings are given in the values.
- Left out: EEPROM kWh 0xE02C (no scaling or unit printed), lighting-mode and diversion EEPROM settings, calibration values and the 0x8000-0x85DF data logger. Registers 0x0000-0x0007 are internal use.
- Both FC 0x03 and FC 0x04 are supported for reading; EEPROM is written with Write Single Register (0x06).
Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.
Questions about the Morningstar TriStar TS-45 / TS-60 PWM charge, load and diversion controller (Modbus RTU)
What Modbus registers does the Morningstar TriStar TS-45 / TS-60 PWM charge, load and diversion controller (Modbus RTU) have?
This map lists 45 registers: 11 coils, 34 holding registers. 22 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.
Are the Morningstar TriStar TS-45 / TS-60 PWM charge, load and diversion controller (Modbus RTU) Modbus addresses 0-based or 1-based?
The manufacturer's document numbers registers hexadecimal, 0-based. Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. Morningstar lists a hex PDU address (used on the wire unchanged) and a logical address one higher. The spec says all listed addresses are request-PDU addresses; its scaling example reads battery voltage at PDU 0x0008.
What byte order does the Morningstar TriStar TS-45 / TS-60 PWM charge, load and diversion controller (Modbus RTU) use for 32-bit values?
Multi-register values in this map use ABCD (high word first (big-endian)) and CDAB (low word first (word-swapped)). Each register's order is in the Order column.
What are the minimum Modbus registers to integrate the Morningstar TriStar TS-45 / TS-60 PWM charge, load and diversion controller (Modbus RTU)?
Start with HR 8 adc_vb_f - battery voltage (Battery voltage); HR 10 adc_vx_f - array / load voltage (Array or load voltage); HR 11 adc_ipv_f - charging current (Charging current); HR 26 Control mode (Control mode); HR 27 Control state (Control state); HR 24 Fault bitfield (Fault bitfield); CO 1 Disconnect (Remote disconnect).
How do I enable Modbus control of the Morningstar TriStar TS-45 / TS-60 PWM charge, load and diversion controller (Modbus RTU)?
Modbus is available on the RS-232 port at the factory settings (address 1); no enable step is described.
Where is the official Morningstar TriStar TS-45 / TS-60 PWM charge, load and diversion controller (Modbus RTU) Modbus documentation?
The source is TriStar MODBUS Specification (V07), revision 2020-01-31, published free by Morningstar at https://www.morningstarcorp.com/wp-content/uploads/technical-doc-tristar-modbus-specification-en.pdf.
More Morningstar Modbus register maps
- Solar charge controller (PWM, dual battery)
Morningstar SunSaver Duo dual-battery PWM charge controller (Modbus RTU via MeterBus)
Morningstar SunSaver Duo through the MSC MeterBus-to-RS-232 adapter; Modbus specification V04 (19 March 2019). 16-bit registers only.
Also known as: SunSaver Duo, SSDuo - Solar charge controller (MPPT, battery charger)
Morningstar SunSaver MPPT solar charge controller (Modbus RTU via MeterBus)
Morningstar SunSaver MPPT through the MSC MeterBus-to-RS-232 adapter; Modbus specification v11.
Also known as: SunSaver MPPT, SS-MPPT - Battery inverter (off-grid sine wave)
Morningstar SureSine-300 off-grid sine-wave inverter (Modbus RTU via MeterBus)
Morningstar SureSine-300 (115 V and 220 V versions) via the MSC MeterBus adapter; Modbus specification V03 (29 Oct 2008).
Also known as: SureSine, SureSine-300
Other solar & battery inverters register maps
- Sensor (battery monitor for Studer systems)
Studer Innotec BSP battery status processor (via Xcom-485i)
Studer BSP-500 and BSP-1200 battery status processors read through an Xcom-485i Modbus RTU gateway, system release R706.
Also known as: BSP-500, BSP-1200, BSP500, BSP1200, Xcom-485i - Solar inverter
Fronius Primo GEN24 / Symo GEN24 (Plus) SunSpec int+SF
Fronius Primo/Symo GEN24 (Plus) rest-of-world variants with a battery configured, SunSpec Model Type int+SF; without a battery the MPPT model has 2 inputs and model 124 is absent.
Also known as: Primo GEN24 Plus, Symo GEN24 Plus, Primo GEN24, Symo GEN24, Symo GEN24 10.0 Plus, Primo GEN24 6.0 Plus - Solar inverter gateway (smart dongle)
Huawei SDongleA smart dongle (Modbus TCP)
Huawei SDongleA WLAN/WLAN-FE/4G dongles with firmware V100R001C00SPC100 or later, per MODBUS Interface Definitions issue 05.
Also known as: SDongleA-01, SDongleA-02-CN, SDongleA-03-EU, SDongleA-03-AU, SDongleA-03-KR, SDongleA-03-JP, SDongleA-03-CN - Solar inverter
Schneider Electric Conext CL three-phase PV inverter 18/20/25 kVA
Conext CL (IEC, PVSCL20E/25E) and Conext CL-NA (PVSCL18NA/25NA) three-phase string inverters, map revision 1.5.
Also known as: Conext CL-NA, Conext CL-E, PVSCL18NA, PVSCL20E, PVSCL25E, PVSCL25NA - Solar inverter (MPPT solar charge controller)
Studer Innotec VarioString MPPT solar charge controller (via Xcom-485i)
Studer VarioString VS-70 and VS-120 MPPT chargers read through an Xcom-485i Modbus RTU gateway, system release R706.
Also known as: VS-70, VS-120, VarioString VS-120, Xcom-485i - Solar inverter
Fronius Primo GEN24 Plus / Symo GEN24 Plus US (SunSpec int+SF with 700-series models)
Fronius Primo/Symo GEN24 (Plus) US variants with a battery configured, SunSpec Model Type int+SF; the US map appends IEEE 1547 models 701-713 after storage model 124.
Also known as: Primo GEN24 Plus US, Symo GEN24 Plus US, Primo GEN24 10.0 208-240, Primo GEN24 3.8 208-240, Primo GEN24 6.0 208-240
All solar & battery inverters Modbus register maps →
Source: TriStar MODBUS Specification · V07 · rev. 2020-01-31. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.