Battery inverter (off-grid sine wave) · Modbus register map

Morningstar SureSine-300 off-grid sine-wave inverter (Modbus RTU via MeterBus) Modbus register map

Updated 17 November 2026

Short answer

The SureSine-300 is a Morningstar sine-wave inverter (115 V and 220 V versions). Through its RJ-11 meter port and Morningstar's MSC adapter it speaks Modbus RTU: battery voltage, heatsink temperature, fault/alarm bits, load state and nominal output settings in RAM, a remote-off and reset register, and EEPROM custom disconnect/reconnect voltages.

This page lists 24 Modbus registers for the Morningstar SureSine-300 off-grid sine-wave inverter (Modbus RTU via MeterBus) — 12 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Morningstar’s own free documentation (linked below) and checked against it.

Manufacturer
Morningstar
Model
SureSine-300 off-grid sine-wave inverter (Modbus RTU via MeterBus)
Equipment type
Battery inverter (off-grid sine wave)
Registers
24 (12 writable)
Transport
Modbus RTU
Default unit ID
1
Default serial
9600 baud, 8N2
Documented addressing
hexadecimal, 0-based
Also known as
SureSine, SureSine-300
Source document
SureSine-300 Modbus Specification · V03 · rev. 2008-10-29
Download CSV all columns JSON Manufacturer PDF ↗

Integration notes: Morningstar SureSine-300 off-grid sine-wave inverter (Modbus RTU via MeterBus)

Integration in brief

Via the MSC adapter at 9600 8N2, ID 1, read 0x0000-0x000E: battery voltage (x 16.92/65536), heatsink temperature, faults, alarms and load state. Write a non-zero value to 0x000F to switch the AC output off remotely.

Minimum registers to map

Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.

RegisterNameTypeWhyAccess
HR 4Vb - battery voltage, filteredUINT16Battery voltageRead
HR 11Load stateUINT16Load stateRead
HR 7Fault bitfieldBITMAP16FaultsRead
HR 8Alarm bitfieldBITMAP16AlarmsRead
HR 6Ths - heatsink temperatureINT16Heatsink temperatureRead
HR 15m_disconnect - remote offUINT16Remote AC offRead/write

Enable Modbus control & writes

No enable step; connect a Morningstar MSC MeterBus-to-RS-232 adapter to the meter port.

Byte order & addressing

Network setup

Watch out for

Morningstar SureSine-300 off-grid sine-wave inverter (Modbus RTU via MeterBus) Modbus registers

Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.

24 of 24 shown
Morningstar SureSine-300 off-grid sine-wave inverter (Modbus RTU via MeterBus) Modbus register map
TableAddressNameDescriptionTypeOrderScaleUnitsAccessValues / bits
HR0doc 0x0000adc_vb - battery voltage, unfilteredDC input voltage.UINT16× 0.0002581787VRead
HR4doc 0x0004Vb - battery voltage, filteredDC input voltage with slow filter.UINT16× 0.0002581787VRead
HR6doc 0x0006Ths - heatsink temperature-128 to +127.INT16°CRead
HR7doc 0x0007Fault bitfieldA fault stops the inverter.BITMAP16Readbit 0 = Reset; bit 1 = Over-current; bit 3 = Software; bit 4 = HVD; bit 5 = Hot (heatsink over 95 °C); bit 6 = DIP switch; bit 7 = Settings edit
HR8doc 0x0008Alarm bitfieldAlarms do not stop the inverter.BITMAP16Readbit 0 = Heatsink sensor open; bit 1 = Heatsink sensor shorted; bit 3 = Heatsink hot (above 80 °C)
HR10doc 0x000ADIP switch settingsBITMAP16Readbit 0 = DIP 1 on; bit 1 = DIP 2 on; bit 2 = DIP 3 on; bit 3 = DIP 4 on
HR11doc 0x000BLoad stateUINT16Read0 = Start-up; 1 = Load on; 2 = LVD warning; 3 = LVD; 4 = Fault; 5 = Load disconnected (by meter/Modbus); 6 = Load off; 8 = Standby
HR12doc 0x000CModulation index0xFF = 100 %.UINT16× 0.390625%Read
HR13doc 0x000DOutput voltage settingNominal rating, not a measurement.UINT16VRead
HR14doc 0x000EOutput frequency settingNominal rating, not a measurement.UINT16HzRead
HR15doc 0x000Fm_disconnect - remote offNon-zero turns the AC output off; write 0 to resume.UINT16Read/write
HR16doc 0x0010modbus_reset - software resetNon-zero resets the inverter; returns to 0.UINT16Write
HR57344doc 0xE000EVb_min - minimum battery voltageSince last reset.UINT16× 0.0002581787VRead
HR57345doc 0xE001EVb_max - maximum battery voltageUINT16× 0.0002581787VRead
HR57346doc 0xE002Emodbus_id - Modbus ID1-247, factory 1.UINT16Read/write
HR57347doc 0xE003Emeter_id - MeterBus ID1-15, factory 1.UINT16Read/write
HR57348doc 0xE004Ev_lvd2 - custom low voltage disconnect0 disables.UINT16× 0.0002581787VRead/write
HR57349doc 0xE005Ev_lvr2 - custom low voltage reconnectUINT16× 0.0002581787VRead/write
HR57350doc 0xE006Ev_hvd2 - custom high voltage disconnectUINT16× 0.0002581787VRead/write
HR57351doc 0xE007Ev_hvr2 - custom high voltage reconnectUINT16× 0.0002581787VRead/write
HR57352doc 0xE008Et_lvd_warn2 - LVD warning timerUINT16× 0.1sRead/write
HR57353doc 0xE009Ev_lvdwarn_beep2 - LVD beeper limitUINT16× 0.0002581787VRead/write
HR57354doc 0xE00AEv_lvrwarn_beep2 - LVD beeper reset limitUINT16× 0.0002581787VRead/write
HR57355doc 0xE00BEv_startlvd2 - start-up LVD settingUINT16× 0.0002581787VRead/write

Notes on this map

Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.

Questions about the Morningstar SureSine-300 off-grid sine-wave inverter (Modbus RTU via MeterBus)

What Modbus registers does the Morningstar SureSine-300 off-grid sine-wave inverter (Modbus RTU via MeterBus) have?

This map lists 24 registers: 24 holding registers. 12 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.

Are the Morningstar SureSine-300 off-grid sine-wave inverter (Modbus RTU via MeterBus) Modbus addresses 0-based or 1-based?

The manufacturer's document numbers registers hexadecimal, 0-based. Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. The spec says all listed addresses are request-PDU addresses, so the hex value in the PDU column goes on the wire unchanged (logical address = PDU + 1).

What are the minimum Modbus registers to integrate the Morningstar SureSine-300 off-grid sine-wave inverter (Modbus RTU via MeterBus)?

Start with HR 4 Vb - battery voltage, filtered (Battery voltage); HR 11 Load state (Load state); HR 7 Fault bitfield (Faults); HR 8 Alarm bitfield (Alarms); HR 6 Ths - heatsink temperature (Heatsink temperature); HR 15 m_disconnect - remote off (Remote AC off).

How do I enable Modbus control of the Morningstar SureSine-300 off-grid sine-wave inverter (Modbus RTU via MeterBus)?

No enable step; connect a Morningstar MSC MeterBus-to-RS-232 adapter to the meter port.

Where is the official Morningstar SureSine-300 off-grid sine-wave inverter (Modbus RTU via MeterBus) Modbus documentation?

The source is SureSine-300 Modbus Specification (V03), revision 2008-10-29, published free by Morningstar at https://www.morningstarcorp.com/wp-content/uploads/technical-doc-suresine-modbus-specification-en.pdf.

More Morningstar Modbus register maps

Other solar & battery inverters register maps

All solar & battery inverters Modbus register maps →

Source: SureSine-300 Modbus Specification · V03 · rev. 2008-10-29. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.