Solar charge controller (MPPT, battery charger) · Modbus register map
Morningstar SunSaver MPPT solar charge controller (Modbus RTU via MeterBus) Modbus register map
Updated 17 November 2026
The SunSaver MPPT is a Morningstar MPPT solar charge controller with a load output. It speaks Modbus RTU on its RJ-11 meter port through Morningstar's MSC adapter (MeterBus to RS-232). RAM registers give battery, array and load readings, charge and load state and fault bitfields; EEPROM registers hold the charge setpoints and LO-first copies of the Ah and hour counters; coils force load/charge disconnect and clear counters.
This page lists 56 Modbus registers for the Morningstar SunSaver MPPT solar charge controller (Modbus RTU via MeterBus) — 21 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Morningstar’s own free documentation (linked below) and checked against it.
- Manufacturer
- Morningstar
- Model
- SunSaver MPPT solar charge controller (Modbus RTU via MeterBus)
- Equipment type
- Solar charge controller (MPPT, battery charger)
- Registers
- 56 (21 writable)
- Transport
- Modbus RTU
- Default unit ID
- 1
- Default serial
- 9600 baud, 8N2
- Documented addressing
- hexadecimal, 0-based
- 32-bit word order
- CDAB low word first (word-swapped)
- Firmware
- Va_ref_fixed registers need firmware v08 or later.
- Also known as
- SunSaver MPPT, SS-MPPT
- Source document
- SunSaver MPPT MODBUS Specification · v11 · rev. 2017-04-03
Integration notes: Morningstar SunSaver MPPT solar charge controller (Modbus RTU via MeterBus)
Connect through the Morningstar MSC adapter at 9600 8N2, ID 1. Read 0x0008-0x0014 for live data; multiply raw voltages by 100/32768 and currents by 79.16/32768. Use coils 0x0001/0x0002 to switch the load or charger off remotely.
Minimum registers to map
Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.
| Register | Name | Type | Why | Access |
|---|---|---|---|---|
| HR 8 | Adc_vb_f - battery voltage | UINT16 | Battery voltage | Read |
| HR 9 | Adc_va_f - array voltage | UINT16 | Array voltage | Read |
| HR 11 | Adc_ic_f - charging current | UINT16 | Charging current | Read |
| HR 17 | Charge state | UINT16 | Charge state | Read |
| HR 18 | Array fault bitfield | BITMAP16 | Array faults | Read |
| HR 39 | Power_out - charge output power | UINT16 | Charge output power | Read |
| CO 1 | Load disconnect | BIT | Remote load disconnect | Read/write |
Enable Modbus control & writes
Set the comm DIP switch (switch 4, reported as bit 3 of register 0x0025) to MODBUS protocol instead of Meterbus, and connect via the MSC RS-232 adapter.
Byte order & addressing
- Every analog value needs its own formula-derived multiplier; there are no floats.
- Any EEPROM write sets an 'EEPROM changed' fault; reset the controller (coil 0x00FF) to clear it. Writes are not verified.
Network setup
- Serial: 9600 baud, 8 data bits, no parity, 2 stop bits, no flow control.
- Modbus ID is stored in EEPROM at 0xE034 (1-247).
Watch out for
- The MeterBus port is not RS-485; a Morningstar adapter is required.
Morningstar SunSaver MPPT solar charge controller (Modbus RTU via MeterBus) Modbus registers
Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.
| Table | Address | Name | Description | Type | Order | Scale | Units | Access | Values / bits |
|---|---|---|---|---|---|---|---|---|---|
| CO | 0doc 0x0000 | Equalize triggered | BIT | Read/write | |||||
| CO | 1doc 0x0001 | Load disconnect | 1 forces the load output off. | BIT | Read/write | ||||
| CO | 2doc 0x0002 | Charge disconnect | 1 forces the charger off. | BIT | Read/write | ||||
| CO | 16doc 0x0010 | Clear Ah resettable | Set only; reads 0. | BIT | Write | ||||
| CO | 17doc 0x0011 | Clear Ah total | Set only; reads 0. | BIT | Write | ||||
| CO | 18doc 0x0012 | Clear kWh | Set only; reads 0. | BIT | Write | ||||
| CO | 22doc 0x0016 | Force EEPROM update | Set only; reads 0. | BIT | Write | ||||
| CO | 255doc 0x00FF | Reset control | Restarts the controller (needed after EEPROM writes). | BIT | Write | ||||
| HR | 8doc 0x0008 | Adc_vb_f - battery voltage | Filtered (about 1 s). | UINT16 | × 0.0030517578 | V | Read | ||
| HR | 9doc 0x0009 | Adc_va_f - array voltage | Solar input terminal voltage. | UINT16 | × 0.0030517578 | V | Read | ||
| HR | 10doc 0x000A | Adc_vl_f - load voltage | UINT16 | × 0.0030517578 | V | Read | |||
| HR | 11doc 0x000B | Adc_ic_f - charging current | UINT16 | × 0.0024157715 | A | Read | |||
| HR | 12doc 0x000C | Adc_il_f - load current | UINT16 | × 0.0024157715 | A | Read | |||
| HR | 13doc 0x000D | T_hs - heatsink temperature | INT16 | °C | Read | ||||
| HR | 14doc 0x000E | T_batt - battery temperature | Ambient sensor, or RTS if connected. | INT16 | °C | Read | |||
| HR | 15doc 0x000F | T_amb - ambient temperature | INT16 | °C | Read | ||||
| HR | 16doc 0x0010 | T_rts - remote temperature sensor | 0x80 if no RTS is connected. | INT16 | °C | Read | |||
| HR | 17doc 0x0011 | Charge state | UINT16 | Read | 0 = START; 1 = NIGHT_CHECK; 2 = DISCONNECT; 3 = NIGHT; 4 = FAULT; 5 = BULK_CHARGE; 6 = ABSORPTION; 7 = FLOAT; 8 = EQUALIZE | ||||
| HR | 18doc 0x0012 | Array fault bitfield | BITMAP16 | Read | bit 0 = Overcurrent; bit 1 = FETs shorted; bit 2 = Software bug; bit 3 = Battery HVD; bit 4 = Array HVD; bit 5 = EEPROM setting edit (reset required); bit 6 = RTS shorted; bit 7 = RTS was valid, now disconnected; bit 8 = Local temperature sensor failed | ||||
| HR | 19doc 0x0013 | Vb_f - battery voltage, slow filter | About 25 s filter. | UINT16 | × 0.0030517578 | V | Read | ||
| HR | 20doc 0x0014 | Vb_ref - charge target voltage | Temperature-compensated regulation reference. | UINT16 | × 0.0029500427 | V | Read | ||
| HR | 25doc 0x0019 | kWh charge | The spec marks it as possibly resettable. | UINT16 | × 0.1 | kWh | Read | ||
| HR | 26doc 0x001A | Load state | UINT16 | Read | 0 = START; 1 = LOAD_ON; 2 = LVD_WARNING; 3 = LVD; 4 = FAULT; 5 = DISCONNECT | ||||
| HR | 27doc 0x001B | Load fault bitfield | BITMAP16 | Read | bit 0 = External short circuit; bit 1 = Overcurrent; bit 2 = FETs shorted; bit 3 = Software bug; bit 4 = HVD; bit 5 = Heatsink over-temperature; bit 6 = EEPROM setting edit (reset required) | ||||
| HR | 28doc 0x001C | V_lvd - LVD voltage | Current-compensated low voltage disconnect point. | UINT16 | × 0.0030517578 | V | Read | ||
| HR | 37doc 0x0025 | DIP switch settings | BITMAP16 | Read | bit 0 = Custom battery settings; bit 1 = Custom load settings; bit 2 = Equalize enabled; bit 3 = MODBUS protocol selected (else Meterbus) | ||||
| HR | 38doc 0x0026 | LED state | SOC LED pattern code (0-19). | UINT16 | Read | ||||
| HR | 39doc 0x0027 | Power_out - charge output power | UINT16 | × 0.0150985718 | W | Read | |||
| HR | 40doc 0x0028 | Sweep_Vmp - array Vmp | Found during last MPPT sweep. | UINT16 | × 0.0030517578 | V | Read | ||
| HR | 41doc 0x0029 | Sweep_Pmax - array max power | Found during last sweep. | UINT16 | × 0.0150985718 | W | Read | ||
| HR | 42doc 0x002A | Sweep_Voc - array Voc | UINT16 | × 0.0030517578 | V | Read | |||
| HR | 43doc 0x002B | Vb_min_daily | Today's minimum battery voltage. | UINT16 | × 0.0030517578 | V | Read | ||
| HR | 44doc 0x002C | Vb_max_daily | Today's maximum battery voltage. | UINT16 | × 0.0030517578 | V | Read | ||
| HR | 45doc 0x002D | Ahc_daily | Charge Ah today. | UINT16 | × 0.1 | Ah | Read | ||
| HR | 46doc 0x002E | Ahl_daily | Load Ah today. | UINT16 | × 0.1 | Ah | Read | ||
| HR | 47doc 0x002F | Array fault bitfield, daily | Sticky for the day. | BITMAP16 | Read | bit 0 = Overcurrent; bit 1 = FETs shorted; bit 2 = Software bug; bit 3 = Battery HVD; bit 4 = Array HVD; bit 5 = EEPROM setting edit (reset required); bit 6 = RTS shorted; bit 7 = RTS was valid, now disconnected; bit 8 = Local temperature sensor failed | |||
| HR | 48doc 0x0030 | Load fault bitfield, daily | Sticky for the day. | BITMAP16 | Read | bit 0 = External short circuit; bit 1 = Overcurrent; bit 2 = FETs shorted; bit 3 = Software bug; bit 4 = HVD; bit 5 = Heatsink over-temperature; bit 6 = EEPROM setting edit (reset required) | |||
| HR | 51doc 0x0033 | Vb_min - minimum battery voltage | UINT16 | × 0.0030517578 | V | Read | |||
| HR | 52doc 0x0034 | Vb_max - maximum battery voltage | UINT16 | × 0.0030517578 | V | Read | |||
| HR | 57doc 0x0039 | Va_ref_fixed - fixed array voltage | Non-zero stops MPPT and holds this array voltage. FW v08+. | UINT16 | × 0.0030517578 | V | Read/write | ||
| HR | 58doc 0x003A | Va_ref_fixed_pct - array voltage % of Voc | Non-zero holds array at this % of Voc. FW v08+. | UINT16 | × 0.390625 | % | Read/write | ||
| HR | 57344doc 0xE000 | EV_reg - regulation voltage @25°C | UINT16 | × 0.0030517578 | V | Read/write | |||
| HR | 57345doc 0xE001 | EV_float - float voltage @25°C | 0 disables float. | UINT16 | × 0.0030517578 | V | Read/write | ||
| HR | 57346doc 0xE002 | Et_float - absorption time before float | UINT16 | s | Read/write | ||||
| HR | 57351doc 0xE007 | EV_eq - equalize voltage @25°C | 0 disables equalize. | UINT16 | × 0.0030517578 | V | Read/write | ||
| HR | 57352doc 0xE008 | Et_eqcalendar - days between equalize | UINT16 | days | Read/write | ||||
| HR | 57371doc 0xE01B | EV_hvd - high voltage disconnect | 0 disables HVD. | UINT16 | × 0.0030517578 | V | Read/write | ||
| HR | 57372doc 0xE01C | EV_hvr - high voltage reconnect | UINT16 | × 0.0030517578 | V | Read/write | |||
| HR | 57378doc 0xE022 | EV_lvd - load low voltage disconnect | UINT16 | × 0.0030517578 | V | Read/write | |||
| HR | 57379doc 0xE023 | EV_lvr - load low voltage reconnect | UINT16 | × 0.0030517578 | V | Read/write | |||
| HR | 57396doc 0xE034 | Emodbus_id - Modbus ID | 1-247. | UINT16 | Read/write | ||||
| HR | 57400doc 0xE038 | Eic_lim - charge current limit | UINT16 | × 0.0024157715 | A | Read/write | |||
| HR | 57408doc 0xE040 | Ehourmeter (EEPROM copy) | LO word at 0xE040, HI word at 0xE041. | UINT32 | CDAB | h | Read | ||
| HR | 57414doc 0xE046 | EAhc_r - Ah charge resettable (EEPROM) | LO word first. | UINT32 | CDAB | × 0.1 | Ah | Read | |
| HR | 57416doc 0xE048 | EAhc_t - Ah charge total (EEPROM) | LO word first. | UINT32 | CDAB | × 0.1 | Ah | Read | |
| HR | 57418doc 0xE04A | EkWhc - kWh charge (EEPROM) | The spec marks it as possibly resettable. | UINT16 | × 0.1 | kWh | Read |
Notes on this map
- Scaling: Morningstar gives formulas such as n x 100 x 2^-15; these are converted to a single multiplier (e.g. 100/32768 = 0.0030517578125 for voltages, 79.16/32768 for currents, 989.5/65536 for power, 96.667/32768 for Vb_ref). The manual's example: 0x0F96 = 3990 x 100 / 32768 = 12.18 V.
- Word order: the RAM table names each 32-bit pair HI word then LO word (e.g. hourmeter_HI 0x0021, hourmeter_LO 0x0022), but the spec's own two-word example reads the hourmeter LO word at the lower address. Because the document contradicts itself, the RAM 32-bit values (Ah counters 0x0015-0x0020, hourmeter 0x0021, alarm 0x0023 and daily alarm 0x0031) are left out. The EEPROM read-only copies are printed LO word first (Ehourmeter_LO 0xE040, Ehourmeter_HI 0xE041), which matches the example, so those are listed as CDAB.
- The two-word example uses addresses 0x0025/0x0026 for the hourmeter, which do not match the table (0x0021/0x0022).
- Both Read Holding (0x03) and Read Input (0x04) are supported; registers are listed as holding registers. EEPROM is written with Write Single Register (0x06) only.
- Alarm bitfield bits (32-bit value at 0x0023, not listed): 0 RTS open, 1 RTS shorted, 2 RTS disconnected, 3 Ths open, 4 Ths shorted, 5 SSMPPT hot, 6 current limit, 7 current offset, 10 uncalibrated, 11 RTS miswire, 14 miswire, 15 FET open, 16 P12, 17 high Va current limit.
- Not listed: bank-2 charge settings (0xE00D-0xE017), LED thresholds, the data logger (0x8000-0x81FF) and the remaining EEPROM timers.
- Voltages and currents are listed as unsigned raw values; temperatures are signed (-128 to +127).
Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.
Questions about the Morningstar SunSaver MPPT solar charge controller (Modbus RTU via MeterBus)
What Modbus registers does the Morningstar SunSaver MPPT solar charge controller (Modbus RTU via MeterBus) have?
This map lists 56 registers: 8 coils, 48 holding registers. 21 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.
Are the Morningstar SunSaver MPPT solar charge controller (Modbus RTU via MeterBus) Modbus addresses 0-based or 1-based?
The manufacturer's document numbers registers hexadecimal, 0-based. Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. Morningstar prints a PDU address (hex, goes on the wire as-is) and a logical address (PDU + 1). The manual states all listed addresses are request-PDU addresses; its scaling example reads battery voltage at 0x0008.
What byte order does the Morningstar SunSaver MPPT solar charge controller (Modbus RTU via MeterBus) use for 32-bit values?
Multi-register values in this map use CDAB (low word first (word-swapped)). Set your client to this order for every 32/64-bit value in the table.
What are the minimum Modbus registers to integrate the Morningstar SunSaver MPPT solar charge controller (Modbus RTU via MeterBus)?
Start with HR 8 Adc_vb_f - battery voltage (Battery voltage); HR 9 Adc_va_f - array voltage (Array voltage); HR 11 Adc_ic_f - charging current (Charging current); HR 17 Charge state (Charge state); HR 18 Array fault bitfield (Array faults); HR 39 Power_out - charge output power (Charge output power); CO 1 Load disconnect (Remote load disconnect).
How do I enable Modbus control of the Morningstar SunSaver MPPT solar charge controller (Modbus RTU via MeterBus)?
Set the comm DIP switch (switch 4, reported as bit 3 of register 0x0025) to MODBUS protocol instead of Meterbus, and connect via the MSC RS-232 adapter.
Where is the official Morningstar SunSaver MPPT solar charge controller (Modbus RTU via MeterBus) Modbus documentation?
The source is SunSaver MPPT MODBUS Specification (v11), revision 2017-04-03, published free by Morningstar at https://www.morningstarcorp.com/wp-content/uploads/technical-doc-sunsaver-mppt-modbus-specification-en.pdf.
More Morningstar Modbus register maps
- Solar charge controller (PWM, dual battery)
Morningstar SunSaver Duo dual-battery PWM charge controller (Modbus RTU via MeterBus)
Morningstar SunSaver Duo through the MSC MeterBus-to-RS-232 adapter; Modbus specification V04 (19 March 2019). 16-bit registers only.
Also known as: SunSaver Duo, SSDuo - Battery inverter (off-grid sine wave)
Morningstar SureSine-300 off-grid sine-wave inverter (Modbus RTU via MeterBus)
Morningstar SureSine-300 (115 V and 220 V versions) via the MSC MeterBus adapter; Modbus specification V03 (29 Oct 2008).
Also known as: SureSine, SureSine-300 - Solar charge controller (PWM charge / load / diversion)
Morningstar TriStar TS-45 / TS-60 PWM charge, load and diversion controller (Modbus RTU)
Morningstar TriStar TS-45 and TS-60 (non-MPPT) on the RS-232 port; Modbus specification V07 (31 Jan 2020).
Also known as: TS-45, TS-60, TriStar, TriStar PWM
Other solar & battery inverters register maps
- Solar inverter (via Sunny WebBox gateway)
SMA Sunny WebBox Modbus profile - common addresses of SMA devices (unit IDs 3-247)
SMA devices reached through a Sunny WebBox (fw 1.52+) on unit IDs 3-247 whose family uses the common address set; SB n000US and SB nn000TL-US-12 families use their own tables instead.
Also known as: Sunny WebBox device profile, SMA Modbus profile WebBox, Sunny Central via WebBox, Sunny Tripower STP nn000TL-10 via WebBox, Sunny Mini Central via WebBox - Sensor (battery monitoring system)
Vertiv (Alber) Alber MPM-100 and BDS series battery monitors (Modbus ASCII)
Alber MPM-100 (firmware 1.20+) and BDS series (controller firmware 2.20+) battery monitors with BMDM software 4.10+, per protocol document SL-29417 Rev 7.05.
Also known as: Alber MPM-100, Alber BDS, BDS-40, BDS40, MPM100, Vertiv Alber battery monitor, SL-29417 - Battery charger (industrial float charger, UPS-type DC system)
HindlePower AT10.1 / AT30 series battery charger with communications module (Modbus)
HindlePower AT10.1 and AT30 microprocessor-controlled float battery chargers fitted with the AT Series Communications Module (EJ5037-##) set to Modbus, per operating instructions JA0102-04 Rev. 02-2025.
Also known as: AT10.1, AT30, EJ5037, AT Series Communications Module - Solar inverter
SolarEdge SolarEdge inverters (SunSpec logging)
SolarEdge single-, split- and three-phase inverters with SunSpec enabled (SolarEdge Go/SetApp units, or LCD units on firmware 3.xxxx+); meter 1 at the non-Synergy default base.
Also known as: SE5000, Synergy, SolarEdge SunSpec - Battery inverter (GX gateway for inverter/chargers, batteries and solar chargers)
Victron Energy GX device Modbus-TCP (Cerbo GX, Venus GX, Color Control GX)
Victron GX devices running Venus OS with the Modbus-TCP service enabled; register list version 3.81 (document Rev 54). Core system, VE.Bus inverter/charger, battery, solar charger and ESS registers only.
Also known as: Cerbo GX, Cerbo-S GX, Venus GX, Color Control GX, CCGX, Ekrano GX, Octo GX, MultiPlus-II GX, EasySolar-II GX, Venus OS, dbus-modbustcp - Battery charger (industrial float charger, UPS-type DC system)
HindlePower ATevo battery charger (Modbus communications adapter)
HindlePower ATevo battery chargers with the serial or Ethernet communications adapter set to Modbus, per the ATevo Communications online manual version 1.3.
Also known as: ATevo, ATevo Communications
All solar & battery inverters Modbus register maps →
Source: SunSaver MPPT MODBUS Specification · v11 · rev. 2017-04-03. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.