Battery inverter (off-grid inverter-charger) · Modbus register map

Studer Innotec Xtender XTH / XTM / XTS inverter-charger (via Xcom-485i) Modbus register map

Updated 17 November 2026

Short answer

The Xtender family are Studer's off-grid and backup inverter-chargers. They have no Modbus port of their own: an Xcom-485i on the Studer bus answers Modbus RTU for each unit. This map lists the Xtender user infos (battery, AC input/output, power, energy, relays, state) as input registers and the Xtender parameters as holding registers.

This page lists 469 Modbus registers for the Studer Innotec Xtender XTH / XTM / XTS inverter-charger (via Xcom-485i) — 356 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Studer Innotec’s own free documentation (linked below) and checked against it.

Manufacturer
Studer Innotec
Model
Xtender XTH / XTM / XTS inverter-charger (via Xcom-485i)
Equipment type
Battery inverter (off-grid inverter-charger)
Registers
469 (356 writable)
Transport
Modbus RTU
Default unit ID
11
Default serial
8E1
Documented addressing
0-based (the number printed is the address on the wire)
32-bit word order
ABCD high word first (big-endian)
Firmware
Studer system release R706 (appendix V1.6.44); Xcom-485i protocol V1.1.3
Also known as
XTH, XTM, XTS, Xtender XTH, Xtender XTM, Xtender XTS, Xcom-485i
Source document
Technical specification Studer Modbus RTU Appendix V1.6.44 (with Technical specification Studer Modbus RTU Protocol V1.1.3) · Appendix V1.6.44 (R706); Protocol V1.1.3 · rev. 2025-09-03
Download CSV all columns JSON Manufacturer PDF ↗

Integration notes: Studer Innotec Xtender XTH / XTM / XTS inverter-charger (via Xcom-485i)

Integration in brief

Fit an Xcom-485i on the Studer communication bus and poll it as a Modbus RTU slave. Each Studer device answers at its own unit ID (offset set by DIP switches 1-2); read infos with function 04 and parameters with 03, always 2 registers at a time, and decode as big-endian float.

Minimum registers to map

Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.

RegisterNameTypeWhyAccess
IR 0Battery voltage {3000}FLOAT32 ABCDBattery voltageRead
IR 10Battery charge current {3005}FLOAT32 ABCDBattery charge currentRead
IR 14State of charge {3007}FLOAT32 ABCDState of chargeRead
IR 22Input voltage {3011}FLOAT32 ABCDAC input voltageRead
IR 42Output voltage {3021}FLOAT32 ABCDAC output voltageRead
IR 272Output active power {3136}FLOAT32 ABCDOutput active powerRead
IR 56Operating state {3028}FLOAT32 ABCDOperating stateRead
HR 14Maximum current of AC source (Input limit) {1107}FLOAT32 ABCDAC input current limit (setpoint)Read/write
HR 76Battery charge current {1138}FLOAT32 ABCDBattery charge current (setpoint)Read/write

Enable Modbus control & writes

Install the Xcom-485i on the Studer bus. DIP switches 1-2 set the unit-ID offset (0, 32, 64 or 128) and switches 7-8 set the baud rate (9600, 19200, 38400 or 115200). Frames are 8 data bits, even parity, 1 stop bit.

Byte order & addressing

Network setup

Watch out for

Studer Innotec Xtender XTH / XTM / XTS inverter-charger (via Xcom-485i) Modbus registers

Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.

469 of 469 shown
Studer Innotec Xtender XTH / XTM / XTS inverter-charger (via Xcom-485i) Modbus register map
TableAddressNameDescriptionTypeOrderScaleUnitsAccessValues / bits
IR0Battery voltage {3000}FLOAT32ABCDVRead
IR2Battery temperature {3001}Reads about 32767 when no battery temperature sensor is fitted.FLOAT32ABCD°CRead
IR4Temperature compensation of battery voltage {3002}FLOAT32ABCDRead
IR6Dynamic compensation of battery voltage {3003}FLOAT32ABCDRead
IR8Wanted battery charge current {3004}FLOAT32ABCDARead
IR10Battery charge current {3005}FLOAT32ABCDARead
IR12Battery voltage ripple {3006}FLOAT32ABCDVRead
IR14State of charge {3007}FLOAT32ABCD%Read
IR16Low Voltage Disconect {3008}FLOAT32ABCDVRead
IR20Battery cycle phase {3010}Enumerated state, sent as a float (1.0 = code 1).FLOAT32ABCDRead0 = Invalid value; 1 = Bulk; 2 = Absorpt.; 3 = Equalise; 4 = Floating; 5 = R.float.; 6 = Per.abs.; 7 = Mixing; 8 = Forming
IR22Input voltage {3011}FLOAT32ABCDVRead
IR24Input current {3012}FLOAT32ABCDARead
IR26Input power {3013}FLOAT32ABCDkVARead
IR34Input limit value {3017}FLOAT32ABCDARead
IR36Input limite reached {3018}Enumerated state, sent as a float (1.0 = code 1).FLOAT32ABCDRead0 = Off; 1 = On
IR38Boost active {3019}Enumerated state, sent as a float (1.0 = code 1).FLOAT32ABCDRead0 = Off; 1 = On
IR40State of transfer relay {3020}Enumerated state, sent as a float (1.0 = code 1).FLOAT32ABCDRead0 = Opened; 1 = Closed
IR42Output voltage {3021}FLOAT32ABCDVRead
IR44Output current {3022}FLOAT32ABCDARead
IR46Output power {3023}FLOAT32ABCDkVARead
IR56Operating state {3028}Enumerated state, sent as a float (1.0 = code 1).FLOAT32ABCDRead0 = Invalid value; 1 = Inverter; 2 = Charger; 3 = Boost; 4 = Injection
IR60State of output relay {3030}Enumerated state, sent as a float (1.0 = code 1).FLOAT32ABCDRead0 = Opened; 1 = Closed
IR62State of auxiliary relay 1 {3031}Enumerated state, sent as a float (1.0 = code 1).FLOAT32ABCDRead0 = Opened; 1 = Closed
IR64State of auxiliary relay 2 {3032}Enumerated state, sent as a float (1.0 = code 1).FLOAT32ABCDRead0 = Opened; 1 = Closed
IR90Nbr. of overloads {3045}FLOAT32ABCDRead
IR92Nbr. overtemperature {3046}FLOAT32ABCDRead
IR94Nbr. batterie overvoltage {3047}FLOAT32ABCDRead
IR98State of the inverter {3049}Enumerated state, sent as a float (1.0 = code 1).FLOAT32ABCDRead0 = Off; 1 = On
IR100Number of battery elements {3050}FLOAT32ABCDRead
IR102Search mode state {3051}Enumerated state, sent as a float (1.0 = code 1).FLOAT32ABCDRead0 = Off; 1 = On
IR108Relay aux 1 mode {3054}Enumerated state, sent as a float (1.0 = code 1).FLOAT32ABCDRead0 = Invalid value; 1 = A; 2 = I; 3 = M; 4 = M; 5 = G
IR110Relay aux 2 mode {3055}Enumerated state, sent as a float (1.0 = code 1).FLOAT32ABCDRead0 = Invalid value; 1 = A; 2 = I; 3 = M; 4 = M; 5 = G
IR112Lockings flag {3056}FLOAT32ABCDRead
IR148State of the ground relay {3074}Enumerated state, sent as a float (1.0 = code 1).FLOAT32ABCDRead0 = Opened; 1 = Closed
IR150State of the neutral transfer relay {3075}Enumerated state, sent as a float (1.0 = code 1).FLOAT32ABCDRead0 = Opened; 1 = Closed
IR152Discharge of battery of the previous day {3076}FLOAT32ABCDkWhRead
IR156Discharge of battery of the current day {3078}FLOAT32ABCDkWhRead
IR160Energy AC-In from the previous day {3080}FLOAT32ABCDkWhRead
IR162Energy AC-In from the current day {3081}FLOAT32ABCDkWhRead
IR164Consumers energy of the previous day {3082}FLOAT32ABCDkWhRead
IR166Consumers energy of the current day {3083}FLOAT32ABCDkWhRead
IR168Input frequency {3084}FLOAT32ABCDHzRead
IR170Output frequency {3085}FLOAT32ABCDHzRead
IR172Remote entry state {3086}Enumerated state, sent as a float (1.0 = code 1).FLOAT32ABCDRead0 = RM EN 0; 1 = RM EN 1
IR174Output active power {3087}FLOAT32ABCDWRead
IR176Input active power {3088}FLOAT32ABCDWRead
IR178Defined phase {3089}FLOAT32ABCDRead
IR180Battery voltage (minute min) {3090}FLOAT32ABCDVRead
IR182Battery voltage (minute max) {3091}FLOAT32ABCDVRead
IR184Battery voltage (minute avg) {3092}FLOAT32ABCDVRead
IR186Battery charge current (minute min) {3093}FLOAT32ABCDARead
IR188Battery charge current (minute max) {3094}FLOAT32ABCDARead
IR190Battery charge current (minute avg) {3095}FLOAT32ABCDARead
IR192Output power min (minute min) {3096}FLOAT32ABCDkVARead
IR194Output power (minute max) {3097}FLOAT32ABCDkVARead
IR196Output power (minute avg) {3098}FLOAT32ABCDkVARead
IR198Output active power (minute min) {3099}FLOAT32ABCDkWRead
IR200Output active power (minute max) {3100}FLOAT32ABCDkWRead
IR202Output active power (minute avg) {3101}FLOAT32ABCDkWRead
IR204Electronic temperature 1 (minute min) {3102}FLOAT32ABCD°CRead
IR206Electronic temperature 1 (minute max) {3103}FLOAT32ABCD°CRead
IR208Electronic temperature 1 (minute avg) {3104}FLOAT32ABCD°CRead
IR210Electronic temperature 2 (minute min) {3105}FLOAT32ABCD°CRead
IR212Electronic temperature 2 (minute max) {3106}FLOAT32ABCD°CRead
IR214Electronic temperature 2 (minute avg) {3107}FLOAT32ABCD°CRead
IR216Output frequency (minute min) {3108}FLOAT32ABCDHzRead
IR218Output frequency (minute max) {3109}FLOAT32ABCDHzRead
IR220Output frequency (minute avg) {3110}FLOAT32ABCDHzRead
IR222Input voltage (minute min) {3111}FLOAT32ABCDVRead
IR224Input voltage (minute max) {3112}FLOAT32ABCDVRead
IR226Input voltage (minute avg) {3113}FLOAT32ABCDVRead
IR228Input current (minute min) {3114}FLOAT32ABCDARead
IR230Input current (minute max) {3115}FLOAT32ABCDARead
IR232Input current (minute avg) {3116}FLOAT32ABCDARead
IR234Input active power (minute min) {3117}FLOAT32ABCDkWRead
IR236Input active power (minute max) {3118}FLOAT32ABCDkWRead
IR238Input active power (minute avg) {3119}FLOAT32ABCDkWRead
IR240Input frequency (minute min) {3120}FLOAT32ABCDHzRead
IR242Input frequency (minute max) {3121}FLOAT32ABCDHzRead
IR244Input frequency (minute avg) {3122}FLOAT32ABCDHzRead
IR248ID type {3124}FLOAT32ABCDRead
IR250ID Power {3125}FLOAT32ABCDVARead
IR252ID Uout {3126}FLOAT32ABCDVRead
IR254ID batt voltage {3127}FLOAT32ABCDVRead
IR256ID Iout nom {3128}FLOAT32ABCDARead
IR258ID HW {3129}FLOAT32ABCDRead
IR260ID SOFT msb {3130}Software version word, encoded as in the protocol spec's version section.FLOAT32ABCDRead
IR262ID SOFT lsb {3131}Software version word, encoded as in the protocol spec's version section.FLOAT32ABCDRead
IR264ID HW PWR {3132}FLOAT32ABCDRead
IR266Parameter number (in code) {3133}FLOAT32ABCDRead
IR268Info user number {3134}FLOAT32ABCDRead
IR270ID SID {3135}FLOAT32ABCDRead
IR272Output active power {3136}FLOAT32ABCDkWRead
IR274Input active power {3137}FLOAT32ABCDkWRead
IR276Input power {3138}FLOAT32ABCDkVARead
IR278Output power {3139}FLOAT32ABCDkVARead
IR280System debug 1 {3140}FLOAT32ABCDRead
IR282System debug 2 {3141}FLOAT32ABCDRead
IR284System state machine {3142}FLOAT32ABCDRead
IR308Input frequency {3154}FLOAT32ABCDHzRead
IR310Desired AC injection current {3155}FLOAT32ABCDARead
IR312ID FID msb {3156}Half of the unit's unique FID number.FLOAT32ABCDRead
IR314ID FID lsb {3157}Half of the unit's unique FID number.FLOAT32ABCDRead
IR316Actual freezed current in ARN4105 P(f) {3158}FLOAT32ABCDRead
IR318AC injection current, type of limitation ARN4105 P(f) {3159}Enumerated state, sent as a float (1.0 = code 1).FLOAT32ABCDRead0 = No limit; 1 = FreezeOF; 2 = N_ImaxOF; 3 = FreezeUF; 4 = N_ImaxUF; 5 = N_IMaxST
IR320Source of limitation of the functions charger or injector {3160}Enumerated state, sent as a float (1.0 = code 1).FLOAT32ABCDRead0 = Invalid value; 1 = Ubatt; 2 = Ubattp; 3 = Ubattpp; 4 = Ibatt; 5 = Pchar; 6 = UbattInj; 7 = Iinj; 8 = Imax; 9 = Ilim; 10 = Ithermal; 11 = PchNeg; 12 = ARN f
IR322Battery priority active {3161}Enumerated state, sent as a float (1.0 = code 1).FLOAT32ABCDRead0 = Off; 1 = On
IR324Forced grid feeding active {3162}Enumerated state, sent as a float (1.0 = code 1).FLOAT32ABCDRead0 = Off; 1 = On
IR328Battery voltage target for charger/injection {3164}FLOAT32ABCDRead
IR330Allowed charge current in limited charger mode {3165}FLOAT32ABCDRead
IR332Current on converter output stage DC/AC {3166}FLOAT32ABCDRead
IR334Voltage on converter output stage DC/AC {3167}FLOAT32ABCDRead
IR336Over temperature state {3168}Enumerated state, sent as a float (1.0 = code 1).FLOAT32ABCDRead0 = No Error; 1 = TR.Alarm; 2 = TR.Error; 3 = EL.Error; 4 = EL.Stop
HR14Maximum current of AC source (Input limit) {1107}Basic level. Range 2 to 50, default 32.FLOAT32ABCDAacRead/write
HR16Battery undervoltage level without load {1108}Expert level. Range 36 to 72, default 46.3.FLOAT32ABCDVdcRead/write
HR18Battery undervoltage level at full load {1109}Expert level. Range 36 to 72, default 42.FLOAT32ABCDVdcRead/write
HR20Restart voltage after batteries undervoltage {1110}Expert level. Range 37.9 to 72, default 48.FLOAT32ABCDVdcRead/write
HR22Autostart to the battery connection {1111}Expert level. Float 0.0 = no, 1.0 = yes.FLOAT32ABCDRead/write0 = No; 1 = Yes
HR24Inverter frequency {1112}Expert level. Range 45 to 65, default 50.FLOAT32ABCDHzRead/write
HR42Battery overvoltage level {1121}Expert level. Range 37.9 to 74.4, default 68.2.FLOAT32ABCDVdcRead/write
HR44Restart voltage level after an battery overvoltage {1122}Expert level. Range 37.9 to 72, default 64.8.FLOAT32ABCDVdcRead/write
HR48Inverter allowed {1124}Basic level. Float 0.0 = no, 1.0 = yes.FLOAT32ABCDRead/write0 = No; 1 = Yes
HR50Charger allowed {1125}Expert level. Float 0.0 = no, 1.0 = yes.FLOAT32ABCDRead/write0 = No; 1 = Yes
HR52Smart-Boost allowed {1126}Basic level. Float 0.0 = no, 1.0 = yes.FLOAT32ABCDRead/write0 = No; 1 = Yes
HR54Grid feeding allowed {1127}Expert level. Float 0.0 = no, 1.0 = yes.FLOAT32ABCDRead/write0 = No; 1 = Yes
HR56Transfer relay allowed {1128}Expert level. Float 0.0 = no, 1.0 = yes.FLOAT32ABCDRead/write0 = No; 1 = Yes
HR60After battery undervoltage {1130}Expert level. Float 0.0 = no, 1.0 = yes.FLOAT32ABCDRead/write0 = No; 1 = Yes
HR62After battery overvoltage {1131}Expert level. Float 0.0 = no, 1.0 = yes.FLOAT32ABCDRead/write0 = No; 1 = Yes
HR64After inverter or Smart-Boost overload {1132}Expert level. Float 0.0 = no, 1.0 = yes.FLOAT32ABCDRead/write0 = No; 1 = Yes
HR68After overtemperature {1134}Expert level. Float 0.0 = no, 1.0 = yes.FLOAT32ABCDRead/write0 = No; 1 = Yes
HR76Battery charge current {1138}Basic level. Range 0 to 200, default 60.FLOAT32ABCDAdcRead/write
HR78Temperature compensation {1139}Expert level. Range -8 to 0, default -3.FLOAT32ABCDmV/°C/cellRead/write
HR80Floating voltage {1140}Expert level. Range 37.9 to 72, default 54.4.FLOAT32ABCDVdcRead/write
HR84Force a new cycle {1142}Expert level. Write 1.0 to trigger.FLOAT32ABCDWrite
HR86Voltage level 1 to start a new cycle {1143}Expert level. Range 36 to 72, default 49.9.FLOAT32ABCDVdcRead/write
HR88Time period under voltage level 1 to start a new cycle {1144}Expert level. Range 0 to 240, default 30.FLOAT32ABCDminRead/write
HR90Voltage level 2 to start a new cycle {1145}Expert level. Range 36 to 72, default 49.2.FLOAT32ABCDVdcRead/write
HR92Time period under voltage level 2 to start a new cycle {1146}Expert level. Range 0 to 600, default 60.FLOAT32ABCDsecRead/write
HR94Cycling restricted {1147}Expert level. Float 0.0 = no, 1.0 = yes.FLOAT32ABCDRead/write0 = No; 1 = Yes
HR96Minimal delay between cycles {1148}Expert level. Range 0 to 540, default 3.FLOAT32ABCDhoursRead/write
HR98New cycle priority on absorption and equalization phases {1149}Expert level. Float 0.0 = no, 1.0 = yes.FLOAT32ABCDRead/write0 = No; 1 = Yes
HR110Absorption phase allowed {1155}Expert level. Float 0.0 = no, 1.0 = yes.FLOAT32ABCDRead/write0 = No; 1 = Yes
HR112Absorption voltage {1156}Expert level. Range 37.9 to 72, default 57.6.FLOAT32ABCDVdcRead/write
HR114Absorption duration {1157}Expert level. Range 0 to 18, default 2.FLOAT32ABCDhoursRead/write
HR116End of absorption triggered with current {1158}Expert level. Float 0.0 = no, 1.0 = yes.FLOAT32ABCDRead/write0 = No; 1 = Yes
HR118Current limit to quit the absorption phase {1159}Expert level. Range 1 to 200, default 4.FLOAT32ABCDAdcRead/write
HR120Maximal frequency of absorption control {1160}Expert level. Float 0.0 = no, 1.0 = yes.FLOAT32ABCDRead/write0 = No; 1 = Yes
HR122Minimal delay since last absorption {1161}Expert level. Range 0 to 540, default 2.FLOAT32ABCDhoursRead/write
HR124Force equalization {1162}Expert level. Write 1.0 to trigger.FLOAT32ABCDWrite
HR126Equalization allowed {1163}Expert level. Float 0.0 = no, 1.0 = yes.FLOAT32ABCDRead/write0 = No; 1 = Yes
HR128Equalization voltage {1164}Expert level. Range 37.9 to 72, default 62.4.FLOAT32ABCDVdcRead/write
HR130Equalization duration {1165}Expert level. Range 0.2 to 10, default 0.5.FLOAT32ABCDhoursRead/write
HR132Number of cycles before an equalization {1166}Expert level. Range 0 to 100, default 25.FLOAT32ABCDRead/write
HR136End of equalization triggered with current {1168}Expert level. Float 0.0 = no, 1.0 = yes.FLOAT32ABCDRead/write0 = No; 1 = Yes
HR138Current threshold to end equalization phase {1169}Expert level. Range 1 to 30, default 4.FLOAT32ABCDAdcRead/write
HR140Reduced floating allowed {1170}Expert level. Float 0.0 = no, 1.0 = yes.FLOAT32ABCDRead/write0 = No; 1 = Yes
HR142Floating duration before reduced floating {1171}Expert level. Range 0 to 31, default 1.FLOAT32ABCDdaysRead/write
HR144Reduced floating voltage {1172}Expert level. Range 37.9 to 72, default 52.8.FLOAT32ABCDVdcRead/write
HR146Periodic absorption allowed {1173}Expert level. Float 0.0 = no, 1.0 = yes.FLOAT32ABCDRead/write0 = No; 1 = Yes
HR148Periodic absorption voltage {1174}Expert level. Range 37.9 to 72, default 57.6.FLOAT32ABCDVdcRead/write
HR150Reduced floating duration before periodic absorption {1175}Expert level. Range 0 to 31, default 7.FLOAT32ABCDdaysRead/write
HR152Periodic absorption duration {1176}Expert level. Range 0 to 10, default 0.5.FLOAT32ABCDhoursRead/write
HR174Standby level {1187}Basic level. Range 0 to 100, default 10.FLOAT32ABCD%Read/write
HR176Standby number of pulses {1188}Expert level. Range 1 to 10, default 1.FLOAT32ABCDRead/write
HR178Time delay between standby pulses {1189}Expert level. Range 0.2 to 10, default 0.8.FLOAT32ABCDsecRead/write
HR180Battery undervoltage duration before turn off {1190}Expert level. Range 0 to 60, default 3.FLOAT32ABCDminRead/write
HR182Battery undervoltage dynamic compensation {1191}Expert level. Float 0.0 = no, 1.0 = yes.FLOAT32ABCDRead/write0 = No; 1 = Yes
HR188Battery adaptive low voltage (B.L.O) {1194}Expert level. Float 0.0 = no, 1.0 = yes.FLOAT32ABCDRead/write0 = No; 1 = Yes
HR190Max voltage for adaptive low voltage {1195}Expert level. Range 37.9 to 72, default 49.9.FLOAT32ABCDVdcRead/write
HR196Time delay before opening of transfer relay {1198}Expert level. Range 0 to 30, default 8.FLOAT32ABCDsecRead/write
HR198Input voltage giving an opening of the transfer relay with delay {1199}Expert level. Range 80 to 230, default 200.FLOAT32ABCDVacRead/write
HR200Input voltage giving an immediate opening of the transfer relay (UPS) {1200}Expert level. Range 80 to 230, default 180.FLOAT32ABCDVacRead/write
HR204Operating mode (AUX 1) {1202}Expert level. Option code as a float; one option at a time.FLOAT32ABCDRead/write1 = Automatic; 2 = Reversed automatic; 4 = Manual ON; 8 = Manual OFF
HR210Day of the week (AUX 1) {1205}Expert level. Day bitmask as a float, bit 0 Monday to bit 6 Sunday.FLOAT32ABCDRead/write
HR212Start hour (AUX 1) {1206}Expert level. Minutes after midnight as a float (0-1440).FLOAT32ABCDminRead/write
HR214End hour (AUX 1) {1207}Expert level. Minutes after midnight as a float (0-1440).FLOAT32ABCDminRead/write
HR218Day of the week (AUX 1) {1209}Expert level. Day bitmask as a float, bit 0 Monday to bit 6 Sunday.FLOAT32ABCDRead/write
HR220Start hour (AUX 1) {1210}Expert level. Minutes after midnight as a float (0-1440).FLOAT32ABCDminRead/write
HR222End hour (AUX 1) {1211}Expert level. Minutes after midnight as a float (0-1440).FLOAT32ABCDminRead/write
HR226Day of the week (AUX 1) {1213}Expert level. Day bitmask as a float, bit 0 Monday to bit 6 Sunday.FLOAT32ABCDRead/write
HR228Start hour (AUX 1) {1214}Expert level. Minutes after midnight as a float (0-1440).FLOAT32ABCDminRead/write
HR230End hour (AUX 1) {1215}Expert level. Minutes after midnight as a float (0-1440).FLOAT32ABCDminRead/write
HR234Day of the week (AUX 1) {1217}Installer level. Day bitmask as a float, bit 0 Monday to bit 6 Sunday.FLOAT32ABCDRead/write
HR236Start hour (AUX 1) {1218}Installer level. Minutes after midnight as a float (0-1440).FLOAT32ABCDminRead/write
HR238End hour (AUX 1) {1219}Installer level. Minutes after midnight as a float (0-1440).FLOAT32ABCDminRead/write
HR242Day of the week (AUX 1) {1221}Installer level. Day bitmask as a float, bit 0 Monday to bit 6 Sunday.FLOAT32ABCDRead/write
HR244Start hour (AUX 1) {1222}Installer level. Minutes after midnight as a float (0-1440).FLOAT32ABCDminRead/write
HR246End hour (AUX 1) {1223}Installer level. Minutes after midnight as a float (0-1440).FLOAT32ABCDminRead/write
HR250Xtender is OFF (AUX 1) {1225}Expert level. Float 0.0 = no, 1.0 = yes.FLOAT32ABCDRead/write0 = No; 1 = Yes
HR252Battery undervoltage alarm (AUX 1) {1226}Expert level. Float 0.0 = no, 1.0 = yes.FLOAT32ABCDRead/write0 = No; 1 = Yes
HR254Battery overvoltage (AUX 1) {1227}Expert level. Float 0.0 = no, 1.0 = yes.FLOAT32ABCDRead/write0 = No; 1 = Yes
HR256Inverter overload (AUX 1) {1228}Expert level. Float 0.0 = no, 1.0 = yes.FLOAT32ABCDRead/write0 = No; 1 = Yes
HR258Overtemperature (AUX 1) {1229}Expert level. Float 0.0 = no, 1.0 = yes.FLOAT32ABCDRead/write0 = No; 1 = Yes
HR262Active charger (AUX 1) {1231}Expert level. Float 0.0 = no, 1.0 = yes.FLOAT32ABCDRead/write0 = No; 1 = Yes
HR264Active inverter (AUX 1) {1232}Expert level. Float 0.0 = no, 1.0 = yes.FLOAT32ABCDRead/write0 = No; 1 = Yes
HR266Active Smart-Boost (AUX 1) {1233}Expert level. Float 0.0 = no, 1.0 = yes.FLOAT32ABCDRead/write0 = No; 1 = Yes
HR268AC input presence but with fault (AUX 1) {1234}Expert level. Float 0.0 = no, 1.0 = yes.FLOAT32ABCDRead/write0 = No; 1 = Yes
HR270AC input presence (AUX 1) {1235}Expert level. Float 0.0 = no, 1.0 = yes.FLOAT32ABCDRead/write0 = No; 1 = Yes
HR272Transfer relay ON (AUX 1) {1236}Expert level. Float 0.0 = no, 1.0 = yes.FLOAT32ABCDRead/write0 = No; 1 = Yes
HR274AC out presence (AUX 1) {1237}Expert level. Float 0.0 = no, 1.0 = yes.FLOAT32ABCDRead/write0 = No; 1 = Yes
HR276Bulk charge phase (AUX 1) {1238}Expert level. Float 0.0 = no, 1.0 = yes.FLOAT32ABCDRead/write0 = No; 1 = Yes
HR278Absorption phase (AUX 1) {1239}Expert level. Float 0.0 = no, 1.0 = yes.FLOAT32ABCDRead/write0 = No; 1 = Yes
HR280Equalization phase (AUX 1) {1240}Expert level. Float 0.0 = no, 1.0 = yes.FLOAT32ABCDRead/write0 = No; 1 = Yes
HR284Floating (AUX 1) {1242}Expert level. Float 0.0 = no, 1.0 = yes.FLOAT32ABCDRead/write0 = No; 1 = Yes
HR286Reduced floating (AUX 1) {1243}Expert level. Float 0.0 = no, 1.0 = yes.FLOAT32ABCDRead/write0 = No; 1 = Yes
HR288Periodic absorption (AUX 1) {1244}Expert level. Float 0.0 = no, 1.0 = yes.FLOAT32ABCDRead/write0 = No; 1 = Yes
HR292Battery voltage 1 activate (AUX 1) {1246}Expert level. Float 0.0 = no, 1.0 = yes.FLOAT32ABCDRead/write0 = No; 1 = Yes
HR294Battery voltage 1 (AUX 1) {1247}Expert level. Range 36 to 72, default 46.8.FLOAT32ABCDVdcRead/write
HR296Delay 1 (AUX 1) {1248}Expert level. Range 0 to 60, default 1.FLOAT32ABCDminRead/write
HR298Battery voltage 2 activate (AUX 1) {1249}Expert level. Float 0.0 = no, 1.0 = yes.FLOAT32ABCDRead/write0 = No; 1 = Yes
HR300Battery voltage 2 (AUX 1) {1250}Expert level. Range 36 to 72, default 47.8.FLOAT32ABCDVdcRead/write
HR302Delay 2 (AUX 1) {1251}Expert level. Range 0 to 60, default 10.FLOAT32ABCDminRead/write
HR304Battery voltage 3 activate (AUX 1) {1252}Expert level. Float 0.0 = no, 1.0 = yes.FLOAT32ABCDRead/write0 = No; 1 = Yes
HR306Battery voltage 3 (AUX 1) {1253}Expert level. Range 36 to 72, default 48.5.FLOAT32ABCDVdcRead/write
HR308Delay 3 (AUX 1) {1254}Expert level. Range 0 to 60, default 60.FLOAT32ABCDminRead/write
HR310Battery voltage to deactivate (AUX 1) {1255}Expert level. Range 36 to 72, default 54.FLOAT32ABCDVdcRead/write
HR312Delay to deactivate (AUX 1) {1256}Expert level. Range 0 to 480, default 60.FLOAT32ABCDminRead/write
HR316Inverter power level 1 activate (AUX 1) {1258}Expert level. Float 0.0 = no, 1.0 = yes.FLOAT32ABCDRead/write0 = No; 1 = Yes
HR318Power level 1 (AUX 1) {1259}Expert level. Range 20 to 120, default 120.FLOAT32ABCD% PnomRead/write
HR320Time delay 1 (AUX 1) {1260}Expert level. Range 0 to 60, default 1.FLOAT32ABCDminRead/write
HR322Inverter power level 2 activate (AUX 1) {1261}Expert level. Float 0.0 = no, 1.0 = yes.FLOAT32ABCDRead/write0 = No; 1 = Yes
HR324Power level 2 (AUX 1) {1262}Expert level. Range 20 to 120, default 80.FLOAT32ABCD% PnomRead/write
HR326Time delay 2 (AUX 1) {1263}Expert level. Range 0 to 60, default 5.FLOAT32ABCDminRead/write
HR328Inverter power level 3 activate (AUX 1) {1264}Expert level. Float 0.0 = no, 1.0 = yes.FLOAT32ABCDRead/write0 = No; 1 = Yes
HR330Power level 3 (AUX 1) {1265}Expert level. Range 20 to 120, default 50.FLOAT32ABCD% PnomRead/write
HR332Time delay 3 (AUX 1) {1266}Expert level. Range 0 to 60, default 30.FLOAT32ABCDminRead/write
HR334Inverter power level to deactivate (AUX 1) {1267}Expert level. Range 20 to 120, default 40.FLOAT32ABCD% PnomRead/write
HR336Time delay to deactivate (AUX 1) {1268}Expert level. Range 0 to 60, default 5.FLOAT32ABCDminRead/write
HR342Day of the week (AUX 1) {1271}Expert level. Day bitmask as a float, bit 0 Monday to bit 6 Sunday.FLOAT32ABCDRead/write
HR344Start hour (AUX 1) {1272}Expert level. Minutes after midnight as a float (0-1440).FLOAT32ABCDminRead/write
HR346End hour (AUX 1) {1273}Expert level. Minutes after midnight as a float (0-1440).FLOAT32ABCDminRead/write
HR350Day of the week (AUX 1) {1275}Expert level. Day bitmask as a float, bit 0 Monday to bit 6 Sunday.FLOAT32ABCDRead/write
HR352Start hour (AUX 1) {1276}Expert level. Minutes after midnight as a float (0-1440).FLOAT32ABCDminRead/write
HR354End hour (AUX 1) {1277}Expert level. Minutes after midnight as a float (0-1440).FLOAT32ABCDminRead/write
HR358Day of the week (AUX 1) {1279}Expert level. Day bitmask as a float, bit 0 Monday to bit 6 Sunday.FLOAT32ABCDRead/write
HR360Start hour (AUX 1) {1280}Expert level. Minutes after midnight as a float (0-1440).FLOAT32ABCDminRead/write
HR362End hour (AUX 1) {1281}Expert level. Minutes after midnight as a float (0-1440).FLOAT32ABCDminRead/write
HR366Integral mode {1283}Expert level. Float 0.0 = no, 1.0 = yes.FLOAT32ABCDRead/write0 = No; 1 = Yes
HR368Equalization with fixed interval {1284}Expert level. Float 0.0 = no, 1.0 = yes.FLOAT32ABCDRead/write0 = No; 1 = Yes
HR370Weeks between equalizations {1285}Expert level. Range 1 to 104, default 26.FLOAT32ABCDweeksRead/write
HR372AC Output voltage {1286}Expert level. Range 110 to 280, default 230.FLOAT32ABCDVacRead/write
HR374Restore factory settings {1287}Installer level. Write 1.0 to trigger.FLOAT32ABCDWrite
HR376Use dynamic compensation of battery level (AUX 1) {1288}Expert level. Float 0.0 = no, 1.0 = yes.FLOAT32ABCDRead/write0 = No; 1 = Yes
HR380Equalization current {1290}Expert level. Range 1 to 200, default 60.FLOAT32ABCDAdcRead/write
HR382Equalization before absorption phase {1291}Expert level. Float 0.0 = no, 1.0 = yes.FLOAT32ABCDRead/write0 = No; 1 = Yes
HR390Charge current decrease coef. at voltage limit to turn back in inverter mode {1295}Expert level. Range 0 to 100, default 100.FLOAT32ABCD%Read/write
HR392Batteries priority as energy source (Not recommended in parallel) {1296}Expert level. Float 0.0 = no, 1.0 = yes.FLOAT32ABCDRead/write0 = No; 1 = Yes
HR394Battery priority voltage {1297}Expert level. Range 37.9 to 72, default 51.6.FLOAT32ABCDVdcRead/write
HR396Increment step of the adaptive low voltage {1298}Expert level. Range 0 to 1.4, default 0.5.FLOAT32ABCDVdcRead/write
HR408Number of batteries undervoltage allowed before definitive stop {1304}Expert level. Range 1 to 20, default 3.FLOAT32ABCDRead/write
HR410Number of batteries critical undervoltage allowed before definitive stop {1305}Expert level. Range 1 to 20, default 10.FLOAT32ABCDRead/write
HR414Reset voltage for adaptive correction {1307}Expert level. Range 37.9 to 72, default 52.8.FLOAT32ABCDVdcRead/write
HR418AC input low limit voltage to allow charger function {1309}Expert level. Range 100 to 230, default 180.FLOAT32ABCDVacRead/write
HR422Operating mode (AUX 2) {1311}Expert level. Option code as a float; one option at a time.FLOAT32ABCDRead/write1 = Automatic; 2 = Reversed automatic; 4 = Manual ON; 8 = Manual OFF
HR428Day of the week (AUX 2) {1314}Expert level. Day bitmask as a float, bit 0 Monday to bit 6 Sunday.FLOAT32ABCDRead/write
HR430Start hour (AUX 2) {1315}Expert level. Minutes after midnight as a float (0-1440).FLOAT32ABCDminRead/write
HR432End hour (AUX 2) {1316}Expert level. Minutes after midnight as a float (0-1440).FLOAT32ABCDminRead/write
HR436Day of the week (AUX 2) {1318}Expert level. Day bitmask as a float, bit 0 Monday to bit 6 Sunday.FLOAT32ABCDRead/write
HR438Start hour (AUX 2) {1319}Expert level. Minutes after midnight as a float (0-1440).FLOAT32ABCDminRead/write
HR440End hour (AUX 2) {1320}Expert level. Minutes after midnight as a float (0-1440).FLOAT32ABCDminRead/write
HR444Day of the week (AUX 2) {1322}Expert level. Day bitmask as a float, bit 0 Monday to bit 6 Sunday.FLOAT32ABCDRead/write
HR446Start hour (AUX 2) {1323}Expert level. Minutes after midnight as a float (0-1440).FLOAT32ABCDminRead/write
HR448End hour (AUX 2) {1324}Expert level. Minutes after midnight as a float (0-1440).FLOAT32ABCDminRead/write
HR452Day of the week (AUX 2) {1326}Installer level. Day bitmask as a float, bit 0 Monday to bit 6 Sunday.FLOAT32ABCDRead/write
HR454Start hour (AUX 2) {1327}Installer level. Minutes after midnight as a float (0-1440).FLOAT32ABCDminRead/write
HR456End hour (AUX 2) {1328}Installer level. Minutes after midnight as a float (0-1440).FLOAT32ABCDminRead/write
HR460Day of the week (AUX 2) {1330}Installer level. Day bitmask as a float, bit 0 Monday to bit 6 Sunday.FLOAT32ABCDRead/write
HR462Start hour (AUX 2) {1331}Installer level. Minutes after midnight as a float (0-1440).FLOAT32ABCDminRead/write
HR464End hour (AUX 2) {1332}Installer level. Minutes after midnight as a float (0-1440).FLOAT32ABCDminRead/write
HR466Xtender is OFF (AUX 2) {1333}Expert level. Float 0.0 = no, 1.0 = yes.FLOAT32ABCDRead/write0 = No; 1 = Yes
HR468Battery undervoltage alarm (AUX 2) {1334}Expert level. Float 0.0 = no, 1.0 = yes.FLOAT32ABCDRead/write0 = No; 1 = Yes
HR470Battery overvoltage (AUX 2) {1335}Expert level. Float 0.0 = no, 1.0 = yes.FLOAT32ABCDRead/write0 = No; 1 = Yes
HR472Inverter overload (AUX 2) {1336}Expert level. Float 0.0 = no, 1.0 = yes.FLOAT32ABCDRead/write0 = No; 1 = Yes
HR474Overtemperature (AUX 2) {1337}Expert level. Float 0.0 = no, 1.0 = yes.FLOAT32ABCDRead/write0 = No; 1 = Yes
HR478Active charger (AUX 2) {1339}Expert level. Float 0.0 = no, 1.0 = yes.FLOAT32ABCDRead/write0 = No; 1 = Yes
HR480Active inverter (AUX 2) {1340}Expert level. Float 0.0 = no, 1.0 = yes.FLOAT32ABCDRead/write0 = No; 1 = Yes
HR482Active Smart-Boost (AUX 2) {1341}Expert level. Float 0.0 = no, 1.0 = yes.FLOAT32ABCDRead/write0 = No; 1 = Yes
HR484AC input presence but with fault (AUX 2) {1342}Expert level. Float 0.0 = no, 1.0 = yes.FLOAT32ABCDRead/write0 = No; 1 = Yes
HR486AC input presence (AUX 2) {1343}Expert level. Float 0.0 = no, 1.0 = yes.FLOAT32ABCDRead/write0 = No; 1 = Yes
HR488Transfer contact ON (AUX 2) {1344}Expert level. Float 0.0 = no, 1.0 = yes.FLOAT32ABCDRead/write0 = No; 1 = Yes
HR490AC out presence (AUX 2) {1345}Expert level. Float 0.0 = no, 1.0 = yes.FLOAT32ABCDRead/write0 = No; 1 = Yes
HR492Bulk charge phase (AUX 2) {1346}Expert level. Float 0.0 = no, 1.0 = yes.FLOAT32ABCDRead/write0 = No; 1 = Yes
HR494Absorption phase (AUX 2) {1347}Expert level. Float 0.0 = no, 1.0 = yes.FLOAT32ABCDRead/write0 = No; 1 = Yes
HR496Equalization phase (AUX 2) {1348}Expert level. Float 0.0 = no, 1.0 = yes.FLOAT32ABCDRead/write0 = No; 1 = Yes
HR500Floating (AUX 2) {1350}Expert level. Float 0.0 = no, 1.0 = yes.FLOAT32ABCDRead/write0 = No; 1 = Yes
HR502Reduced floating (AUX 2) {1351}Expert level. Float 0.0 = no, 1.0 = yes.FLOAT32ABCDRead/write0 = No; 1 = Yes
HR504Periodic absorption (AUX 2) {1352}Expert level. Float 0.0 = no, 1.0 = yes.FLOAT32ABCDRead/write0 = No; 1 = Yes
HR508Use dynamic compensation of battery level (AUX 2) {1354}Expert level. Float 0.0 = no, 1.0 = yes.FLOAT32ABCDRead/write0 = No; 1 = Yes
HR510Battery voltage 1 activate (AUX 2) {1355}Expert level. Float 0.0 = no, 1.0 = yes.FLOAT32ABCDRead/write0 = No; 1 = Yes
HR512Battery voltage 1 (AUX 2) {1356}Expert level. Range 36 to 72, default 48.FLOAT32ABCDVdcRead/write
HR514Delay 1 (AUX 2) {1357}Expert level. Range 0 to 60, default 5.FLOAT32ABCDminRead/write
HR516Battery voltage 2 activate (AUX 2) {1358}Expert level. Float 0.0 = no, 1.0 = yes.FLOAT32ABCDRead/write0 = No; 1 = Yes
HR518Battery voltage 2 (AUX 2) {1359}Expert level. Range 36 to 72, default 46.1.FLOAT32ABCDVdcRead/write
HR520Delay 2 (AUX 2) {1360}Expert level. Range 0 to 60, default 5.FLOAT32ABCDminRead/write
HR522Battery voltage 3 activate (AUX 2) {1361}Expert level. Float 0.0 = no, 1.0 = yes.FLOAT32ABCDRead/write0 = No; 1 = Yes
HR524Battery voltage 3 (AUX 2) {1362}Expert level. Range 36 to 72, default 44.2.FLOAT32ABCDVdcRead/write
HR526Delay 3 (AUX 2) {1363}Expert level. Range 0 to 60, default 5.FLOAT32ABCDminRead/write
HR528Battery voltage to deactivate (AUX 2) {1364}Expert level. Range 36 to 72, default 50.4.FLOAT32ABCDVdcRead/write
HR530Delay to deactivate (AUX 2) {1365}Expert level. Range 0 to 480, default 5.FLOAT32ABCDminRead/write
HR534Inverter power level 1 activate (AUX 2) {1367}Expert level. Float 0.0 = no, 1.0 = yes.FLOAT32ABCDRead/write0 = No; 1 = Yes
HR536Power level 1 (AUX 2) {1368}Expert level. Range 20 to 120, default 120.FLOAT32ABCD% PnomRead/write
HR538Time delay 1 (AUX 2) {1369}Expert level. Range 0 to 60, default 0.FLOAT32ABCDminRead/write
HR540Inverter power level 2 activate (AUX 2) {1370}Expert level. Float 0.0 = no, 1.0 = yes.FLOAT32ABCDRead/write0 = No; 1 = Yes
HR542Power level 2 (AUX 2) {1371}Expert level. Range 20 to 120, default 80.FLOAT32ABCD% PnomRead/write
HR544Time delay 2 (AUX 2) {1372}Expert level. Range 0 to 60, default 5.FLOAT32ABCDminRead/write
HR546Inverter power level 3 activate (AUX 2) {1373}Expert level. Float 0.0 = no, 1.0 = yes.FLOAT32ABCDRead/write0 = No; 1 = Yes
HR548Power level 3 (AUX 2) {1374}Expert level. Range 20 to 120, default 50.FLOAT32ABCD% PnomRead/write
HR550Time delay 3 (AUX 2) {1375}Expert level. Range 0 to 60, default 30.FLOAT32ABCDminRead/write
HR552Inverter power level to deactivate (AUX 2) {1376}Expert level. Range 20 to 120, default 40.FLOAT32ABCD% PnomRead/write
HR554Time delay to deactivate (AUX 2) {1377}Expert level. Range 0 to 60, default 5.FLOAT32ABCDminRead/write
HR560Day of the week (AUX 2) {1380}Expert level. Day bitmask as a float, bit 0 Monday to bit 6 Sunday.FLOAT32ABCDRead/write
HR562Start hour (AUX 2) {1381}Expert level. Minutes after midnight as a float (0-1440).FLOAT32ABCDminRead/write
HR564End hour (AUX 2) {1382}Expert level. Minutes after midnight as a float (0-1440).FLOAT32ABCDminRead/write
HR568Day of the week (AUX 2) {1384}Expert level. Day bitmask as a float, bit 0 Monday to bit 6 Sunday.FLOAT32ABCDRead/write
HR570Start hour (AUX 2) {1385}Expert level. Minutes after midnight as a float (0-1440).FLOAT32ABCDminRead/write
HR572End hour (AUX 2) {1386}Expert level. Minutes after midnight as a float (0-1440).FLOAT32ABCDminRead/write
HR576Day of the week (AUX 2) {1388}Expert level. Day bitmask as a float, bit 0 Monday to bit 6 Sunday.FLOAT32ABCDRead/write
HR578Start hour (AUX 2) {1389}Expert level. Minutes after midnight as a float (0-1440).FLOAT32ABCDminRead/write
HR580End hour (AUX 2) {1390}Expert level. Minutes after midnight as a float (0-1440).FLOAT32ABCDminRead/write
HR582Number of days without functionalitie's restrictions {1391}Qualified service level. Range 0 to 1300, default 0.FLOAT32ABCDdaysRead/write
HR590Restore default settings {1395}Basic level. Write 1.0 to trigger.FLOAT32ABCDWrite
HR598OFF of the Xtenders {1399}Installer level. Write 1.0 to trigger.FLOAT32ABCDWrite
HR608Time period for batteries undervoltages counting {1404}Expert level. Range 0 to 3000, default 0.FLOAT32ABCDsecRead/write
HR610Time period for critical batteries undervoltages counting {1405}Expert level. Range 0 to 3000, default 10.FLOAT32ABCDsecRead/write
HR630ON of the Xtenders {1415}Installer level. Write 1.0 to trigger.FLOAT32ABCDWrite
HR664Absolute max limit for input voltage {1432}Installer level. Range 235 to 290, default 270.FLOAT32ABCDVacRead/write
HR666Adaptation range of the input current according to the input voltage {1433}Expert level. Range 4 to 30, default 10.FLOAT32ABCDVacRead/write
HR672Overrun AC source current limit without opening the transfer relay (Input limit) {1436}Expert level. Float 0.0 = no, 1.0 = yes.FLOAT32ABCDRead/write0 = No; 1 = Yes
HR674Minigrid compatible {1437}Installer level. Float 0.0 = no, 1.0 = yes.FLOAT32ABCDRead/write0 = No; 1 = Yes
HR676Solsafe presence Energy source at AC-Out side {1438}Expert level. Float 0.0 = no, 1.0 = yes.FLOAT32ABCDRead/write0 = No; 1 = Yes
HR678Contact activated with the SOC 1 of battery (AUX 1) {1439}Expert level. Float 0.0 = no, 1.0 = yes.FLOAT32ABCDRead/write0 = No; 1 = Yes
HR680Contact activated below SOC 1 (AUX 1) {1440}Expert level. Range 0 to 100, default 50.FLOAT32ABCD% SOCRead/write
HR682Contact deactivated over SOC (AUX 1) {1441}Expert level. Range 0 to 100, default 90.FLOAT32ABCD% SOCRead/write
HR684Contact activated with the SOC 1 of battery (AUX 2) {1442}Expert level. Float 0.0 = no, 1.0 = yes.FLOAT32ABCDRead/write0 = No; 1 = Yes
HR686Contact activated below SOC 1 (AUX 2) {1443}Expert level. Range 0 to 100, default 50.FLOAT32ABCD% SOCRead/write
HR688Contact deactivated over SOC (AUX 2) {1444}Expert level. Range 0 to 100, default 90.FLOAT32ABCD% SOCRead/write
HR692Contact activated with the temperature of battery (AUX 1) {1446}Expert level. Float 0.0 = no, 1.0 = yes.FLOAT32ABCDRead/write0 = No; 1 = Yes
HR694Contact activated over (AUX 1) {1447}Expert level. Range -10 to 50, default 3.FLOAT32ABCD°CRead/write
HR696Contact deactivated below (AUX 1) {1448}Expert level. Range -10 to 50, default 5.FLOAT32ABCD°CRead/write
HR714Contact activated with the temperature of battery (AUX 2) {1457}Expert level. Float 0.0 = no, 1.0 = yes.FLOAT32ABCDRead/write0 = No; 1 = Yes
HR716Contact activated over (AUX 2) {1458}Expert level. Range -10 to 50, default 3.FLOAT32ABCD°CRead/write
HR718Contact deactivated below (AUX 2) {1459}Expert level. Range -10 to 50, default 5.FLOAT32ABCD°CRead/write
HR722Multi inverters allowed {1461}Expert level. Float 0.0 = no, 1.0 = yes.FLOAT32ABCDRead/write0 = No; 1 = Yes
HR724Multi inverters independents. Need reset {1468} {1462}Expert level. Float 0.0 = no, 1.0 = yes.FLOAT32ABCDRead/write0 = No; 1 = Yes
HR734Force phase of floating {1467}Expert level. Write 1.0 to trigger.FLOAT32ABCDWrite
HR736Reset of all the inverters {1468}Expert level. Write 1.0 to trigger.FLOAT32ABCDWrite
HR770Prohibited ground relay {1485}Expert level. Float 0.0 = no, 1.0 = yes.FLOAT32ABCDRead/write0 = No; 1 = Yes
HR772Continuous neutral {1486}Expert level. Float 0.0 = no, 1.0 = yes.FLOAT32ABCDRead/write0 = No; 1 = Yes
HR782Generator control active {1491}Expert level. Float 0.0 = no, 1.0 = yes.FLOAT32ABCDRead/write0 = No; 1 = Yes
HR784Starter pulse duration (with AUX2) {1492}Expert level. Range 1 to 20, default 3.FLOAT32ABCDsecRead/write
HR786Number of starting attempts {1493}Expert level. Range 0 to 20, default 5.FLOAT32ABCDRead/write
HR788Time before a starter pulse {1494}Expert level. Range 1 to 20, default 3.FLOAT32ABCDsecRead/write
HR794Combination of the events for the auxiliary contact (AUX 1) {1497}Expert level. Option code as a float; one option at a time.FLOAT32ABCDRead/write0 = Any (Function OR); 1 = All (Function AND)
HR796Combination of the events for the auxiliary contact (AUX 2) {1498}Expert level. Option code as a float; one option at a time.FLOAT32ABCDRead/write0 = Any (Function OR); 1 = All (Function AND)
HR800Standby of the charger allowed {1500}Qualified service level. Float 0.0 = no, 1.0 = yes.FLOAT32ABCDRead/write0 = No; 1 = Yes
HR810Delta frequency allowed above the standard input frequency {1505}Expert level. Range 0 to 35, default 5.FLOAT32ABCDHzRead/write
HR812Delta frequency allowed under the standard input frequency {1506}Expert level. Range 0 to 15, default 5.FLOAT32ABCDHzRead/write
HR814Duration with frequency error before opening the transfer {1507}Expert level. Range 0 to 5, default 2.FLOAT32ABCDsecRead/write
HR820Tolerance on detection of AC-input loss (tolerant UPS mode) {1510}Expert level. Range 2 to 120, default 100.FLOAT32ABCDRead/write
HR824Security, maximum time of contact (AUX 1) {1512}Expert level. Float 0.0 = no, 1.0 = yes.FLOAT32ABCDRead/write0 = No; 1 = Yes
HR826Security, maximum time of contact (AUX 2) {1513}Expert level. Float 0.0 = no, 1.0 = yes.FLOAT32ABCDRead/write0 = No; 1 = Yes
HR828Maximum time of operation of contact (AUX 1) {1514}Expert level. Range 10 to 1200, default 600.FLOAT32ABCDminRead/write
HR830Maximum time of operation of contact (AUX 2) {1515}Expert level. Range 10 to 1200, default 600.FLOAT32ABCDminRead/write
HR832Deactivate if battery in floating phase (AUX 1) {1516}Expert level. Float 0.0 = no, 1.0 = yes.FLOAT32ABCDRead/write0 = No; 1 = Yes
HR834Deactivate if battery in floating phase (AUX 2) {1517}Expert level. Float 0.0 = no, 1.0 = yes.FLOAT32ABCDRead/write0 = No; 1 = Yes
HR836Xtender ON (AUX 1) {1518}Expert level. Float 0.0 = no, 1.0 = yes.FLOAT32ABCDRead/write0 = No; 1 = Yes
HR838Xtender ON (AUX 2) {1519}Expert level. Float 0.0 = no, 1.0 = yes.FLOAT32ABCDRead/write0 = No; 1 = Yes
HR840No overtemperature (AUX 1) {1520}Expert level. Float 0.0 = no, 1.0 = yes.FLOAT32ABCDRead/write0 = No; 1 = Yes
HR842No overtemperature (AUX 2) {1521}Expert level. Float 0.0 = no, 1.0 = yes.FLOAT32ABCDRead/write0 = No; 1 = Yes
HR846Max grid feeding current {1523}Expert level. Range 0 to 50, default 10.FLOAT32ABCDAacRead/write
HR848Battery voltage target for forced grid feeding {1524}Expert level. Range 37.9 to 72, default 48.FLOAT32ABCDVdcRead/write
HR850Forced grid feeding start time {1525}Expert level. Minutes after midnight as a float (0-1440).FLOAT32ABCDminRead/write
HR852Forced grid feeding stop time {1526}Expert level. Minutes after midnight as a float (0-1440).FLOAT32ABCDminRead/write
HR854Decrease max input limit current with AC-In voltage {1527}Expert level. Float 0.0 = no, 1.0 = yes.FLOAT32ABCDRead/write0 = No; 1 = Yes
HR864Kind of dynamic compensation {1532}Expert level. Option code as a float; one option at a time.FLOAT32ABCDRead/write0 = Manual; 1 = Automatic
HR866Delay to restart after an overload {1533}Expert level. Range 2 to 120, default 5.FLOAT32ABCDsecRead/write
HR868Speed of voltage or frequency change in function of battery {1534}Expert level. Range -4 to 3, default 0.FLOAT32ABCDRead/write
HR872Inverter frequency increase when battery full {1536}Expert level. Float 0.0 = no, 1.0 = yes.FLOAT32ABCDRead/write0 = No; 1 = Yes
HR876Prohibits transfert relay {1538}Expert level. Float 0.0 = no, 1.0 = yes.FLOAT32ABCDRead/write0 = No; 1 = Yes
HR878Prohibits inverter {1539}Expert level. Float 0.0 = no, 1.0 = yes.FLOAT32ABCDRead/write0 = No; 1 = Yes
HR880Prohibits charger {1540}Expert level. Float 0.0 = no, 1.0 = yes.FLOAT32ABCDRead/write0 = No; 1 = Yes
HR882Prohibits Smart-Boost {1541}Expert level. Float 0.0 = no, 1.0 = yes.FLOAT32ABCDRead/write0 = No; 1 = Yes
HR884Prohibits grid feeding {1542}Expert level. Float 0.0 = no, 1.0 = yes.FLOAT32ABCDRead/write0 = No; 1 = Yes
HR886Remote entry (AUX 1) {1543}Expert level. Float 0.0 = no, 1.0 = yes.FLOAT32ABCDRead/write0 = No; 1 = Yes
HR888Remote entry (AUX 2) {1544}Expert level. Float 0.0 = no, 1.0 = yes.FLOAT32ABCDRead/write0 = No; 1 = Yes
HR890Remote entry active {1545}Expert level. Option code as a float; one option at a time.FLOAT32ABCDRead/write0 = Closed; 1 = Open
HR892Max frequency increase {1546}Expert level. Range 0 to 10, default 4.FLOAT32ABCDHzRead/write
HR894Allow slaves standby in multi-Xtender system {1547}Expert level. Float 0.0 = no, 1.0 = yes.FLOAT32ABCDRead/write0 = No; 1 = Yes
HR896AC voltage increase according to battery voltage {1548}Expert level. Float 0.0 = no, 1.0 = yes.FLOAT32ABCDRead/write0 = No; 1 = Yes
HR898Inverter frequency increase according to battery voltage {1549}Expert level. Float 0.0 = no, 1.0 = yes.FLOAT32ABCDRead/write0 = No; 1 = Yes
HR900Parameters saved in flash memory {1550}Installer level. Float 0.0 = no, 1.0 = yes.FLOAT32ABCDRead/write0 = No; 1 = Yes
HR902Basic parameters set by means of the potentiomenter in the XTS {1551}Basic level. Float 0.0 = no, 1.0 = yes.FLOAT32ABCDRead/write0 = No; 1 = Yes
HR904Type of detection of the grid loss (AC-In) {1552}Basic level. Option code as a float; one option at a time.FLOAT32ABCDRead/write1 = Slow; 2 = Tolerant; 4 = Fast
HR906Speed of input limit increase {1553}Expert level. Range 0 to 100, default 50.FLOAT32ABCDRead/write
HR908Decrease of the max. current of the source with input voltage activated by remote entry {1554}Expert level. Float 0.0 = no, 1.0 = yes.FLOAT32ABCDRead/write0 = No; 1 = Yes
HR910Battery cycle synchronized by the master {1555}Expert level. Float 0.0 = no, 1.0 = yes.FLOAT32ABCDRead/write0 = No; 1 = Yes
HR912Is the central inverter in distributed minigrid {1556}Installer level. Float 0.0 = no, 1.0 = yes.FLOAT32ABCDRead/write0 = No; 1 = Yes
HR914Use an energy quota on AC-input {1557}Installer level. Float 0.0 = no, 1.0 = yes.FLOAT32ABCDRead/write0 = No; 1 = Yes
HR916Separated Batteries {1558}Qualified service level. Float 0.0 = no, 1.0 = yes.FLOAT32ABCDRead/write0 = No; 1 = Yes
HR918AC-In energy quota {1559}Installer level. Range 0.5 to 100, default 1.FLOAT32ABCDkWhRead/write
HR920Max AC voltage increase with battery voltage {1560}Expert level. Range 4 to 16, default 10.FLOAT32ABCDVacRead/write
HR922Correction for XTS saturation Reg U {1561}Qualified service level. Range -300 to 300, default 0.FLOAT32ABCDRead/write
HR924Correction for XTS saturation Reg I {1562}Qualified service level. Range -300 to 300, default 0.FLOAT32ABCDRead/write
HR930Buzzer alarm duration {1565}Expert level. Range 0 to 60, default 0.FLOAT32ABCDminRead/write
HR932Using a secondary value for the maximum current of the AC source {1566}Expert level. Float 0.0 = no, 1.0 = yes.FLOAT32ABCDRead/write0 = No; 1 = Yes
HR934Second maximum current of the AC source (Input limit) {1567}Expert level. Range 2 to 50, default 16.FLOAT32ABCDAacRead/write
HR938Reset all settings (AUX 1) {1569}Expert level. Write 1.0 to trigger.FLOAT32ABCDWrite
HR940Reset all settings (AUX 2) {1570}Expert level. Write 1.0 to trigger.FLOAT32ABCDWrite
HR942Splitphase: L2 with 180 degrees phaseshift {1571}Expert level. Float 0.0 = no, 1.0 = yes.FLOAT32ABCDRead/write0 = No; 1 = Yes
HR944Modulator ru_soll {1572}Qualified service level. Float 0.0 = no, 1.0 = yes.FLOAT32ABCDRead/write0 = No; 1 = Yes
HR948Main contact hold/interrupt time {1574}Expert level. Range 0 to 30, default 0.FLOAT32ABCDsecRead/write
HR950AC-IN current active filtering (Not in parallel) {1575}Expert level. Float 0.0 = no, 1.0 = yes.FLOAT32ABCDRead/write0 = No; 1 = Yes
HR952ON/OFF command {1576}Expert level. Float 0.0 = no, 1.0 = yes.FLOAT32ABCDRead/write0 = No; 1 = Yes
HR954Minigrid with shared battery energy {1577}Installer level. Float 0.0 = no, 1.0 = yes.FLOAT32ABCDRead/write0 = No; 1 = Yes
HR956Activated by AUX 1 state {1578}Expert level. Float 0.0 = no, 1.0 = yes.FLOAT32ABCDRead/write0 = No; 1 = Yes
HR958Prohibits battery priority {1579}Expert level. Float 0.0 = no, 1.0 = yes.FLOAT32ABCDRead/write0 = No; 1 = Yes
HR960Delay before closing transfer relay {1580}Expert level. Range 0 to 30, default 0.FLOAT32ABCDminRead/write
HR962Delay 1 (AUX 1) {1581}Expert level. Range 0 to 99, default 12.FLOAT32ABCDhoursRead/write
HR964Contact activated with the SOC 2 of battery (AUX 1) {1582}Expert level. Float 0.0 = no, 1.0 = yes.FLOAT32ABCDRead/write0 = No; 1 = Yes
HR966Contact activated below SOC 2 (AUX 1) {1583}Expert level. Range 0 to 100, default 30.FLOAT32ABCD% SOCRead/write
HR968Delay 2 (AUX 1) {1584}Expert level. Range 0 to 99, default 0.2.FLOAT32ABCDhoursRead/write
HR970Contact activated with the SOC 3 of battery (AUX 1) {1585}Expert level. Float 0.0 = no, 1.0 = yes.FLOAT32ABCDRead/write0 = No; 1 = Yes
HR972Contact activated below SOC 3 (AUX 1) {1586}Expert level. Range 0 to 100, default 20.FLOAT32ABCD% SOCRead/write
HR974Delay 3 (AUX 1) {1587}Expert level. Range 0 to 99, default 0.FLOAT32ABCDhoursRead/write
HR976Delay to deactivate (AUX 1) {1588}Expert level. Range 0 to 10, default 0.2.FLOAT32ABCDhoursRead/write
HR978Deactivate if battery in floating phase (AUX 1) {1589}Expert level. Float 0.0 = no, 1.0 = yes.FLOAT32ABCDRead/write0 = No; 1 = Yes
HR980Delay 1 (AUX 2) {1590}Expert level. Range 0 to 99, default 12.FLOAT32ABCDhoursRead/write
HR982Contact activated with the SOC 2 of battery (AUX 2) {1591}Expert level. Float 0.0 = no, 1.0 = yes.FLOAT32ABCDRead/write0 = No; 1 = Yes
HR984Contact activated below SOC 2 (AUX 2) {1592}Expert level. Range 0 to 100, default 30.FLOAT32ABCD% SOCRead/write
HR986Delay 2 (AUX 2) {1593}Expert level. Range 0 to 99, default 0.2.FLOAT32ABCDhoursRead/write
HR988Contact activated with the SOC 3 of battery (AUX 2) {1594}Expert level. Float 0.0 = no, 1.0 = yes.FLOAT32ABCDRead/write0 = No; 1 = Yes
HR990Contact activated below SOC 3 (AUX 2) {1595}Expert level. Range 0 to 100, default 20.FLOAT32ABCD% SOCRead/write
HR992Delay 3 (AUX 2) {1596}Expert level. Range 0 to 99, default 0.FLOAT32ABCDhoursRead/write
HR994Delay to deactivate (AUX 2) {1597}Expert level. Range 0 to 10, default 0.2.FLOAT32ABCDhoursRead/write
HR996Deactivate if battery in floating phase (AUX 2) {1598}Expert level. Float 0.0 = no, 1.0 = yes.FLOAT32ABCDRead/write0 = No; 1 = Yes
HR998Softstart duration {1599}Expert level. Range 0 to 1, default 0.FLOAT32ABCDsecRead/write
HR1000Disable minigrid mode {1600}Installer level. Float 0.0 = no, 1.0 = yes.FLOAT32ABCDRead/write0 = No; 1 = Yes
HR1002AC-In energy quota (AUX 1) {1601}Installer level. Float 0.0 = no, 1.0 = yes.FLOAT32ABCDRead/write0 = No; 1 = Yes
HR1004AC-In energy quota (AUX 2) {1602}Installer level. Float 0.0 = no, 1.0 = yes.FLOAT32ABCDRead/write0 = No; 1 = Yes
HR1014Limitation of the power Boost {1607}Installer level. Range 0 to 100, default 100.FLOAT32ABCD%Read/write
HR1016Use dynamic compensation of battery level (new cycle) {1608}Installer level. Float 0.0 = no, 1.0 = yes.FLOAT32ABCDRead/write0 = No; 1 = Yes
HR1020Use of the defined phase shift curve for injection {1610}Installer level. Float 0.0 = no, 1.0 = yes.FLOAT32ABCDRead/write0 = No; 1 = Yes
HR1026Power of the second cos phi point in % of Pnom {1613}Installer level. Range 20 to 85, default 50.FLOAT32ABCD%Read/write
HR1030Fast charge/inject regulation {1615}Qualified service level. Float 0.0 = no, 1.0 = yes.FLOAT32ABCDRead/write0 = No; 1 = Yes
HR1032Use of functions limited to a number of days {1616}Qualified service level. Float 0.0 = no, 1.0 = yes.FLOAT32ABCDRead/write0 = No; 1 = Yes
HR1034Transfer relay disabled after timeout {1617}Qualified service level. Float 0.0 = no, 1.0 = yes.FLOAT32ABCDRead/write0 = No; 1 = Yes
HR1036Inverter disabled after timeout {1618}Qualified service level. Float 0.0 = no, 1.0 = yes.FLOAT32ABCDRead/write0 = No; 1 = Yes
HR1038Charger disabled after timeout {1619}Qualified service level. Float 0.0 = no, 1.0 = yes.FLOAT32ABCDRead/write0 = No; 1 = Yes
HR1040Smart-Boost disabled after timeout {1620}Qualified service level. Float 0.0 = no, 1.0 = yes.FLOAT32ABCDRead/write0 = No; 1 = Yes
HR1042Grid feeding disabled after timeout {1621}Qualified service level. Float 0.0 = no, 1.0 = yes.FLOAT32ABCDRead/write0 = No; 1 = Yes
HR1044Cos phi at P = 0% {1622}Installer level. Range -0.1: Inductive 0.90 to +0.1: Capacitive 0.90, default 0: Cos phi 1.FLOAT32ABCDRead/write
HR1046Cos phi at the power defined by param {1613} {1623}Installer level. Range -0.1: Inductive 0.90 to +0.1: Capacitive 0.90, default 0: Cos phi 1.FLOAT32ABCDRead/write
HR1048Cos phi at P = 100% {1624}Installer level. Range -0.1: Inductive 0.90 to +0.1: Capacitive 0.90, default +0.1: Capacitive 0.90.FLOAT32ABCDRead/write
HR1054ARN4105 frequency control enabled {1627}Installer level. Float 0.0 = no, 1.0 = yes.FLOAT32ABCDRead/write0 = No; 1 = Yes
HR1056Xtender watchdog enabled (SCOM) {1628}Installer level. Float 0.0 = no, 1.0 = yes.FLOAT32ABCDRead/write0 = No; 1 = Yes
HR1058Xtender watchdog delay (SCOM) {1629}Installer level. Range 10 to 300, default 60.FLOAT32ABCDsecRead/write
HR1060Delta from user frequency to start derating {1630}Installer level. Range 0 to 3.9, default 1.FLOAT32ABCDHzRead/write
HR1062Delta from user frequency to reach 100% derating {1631}Installer level. Range 0 to 3.9, default 2.FLOAT32ABCDHzRead/write
HR1064Automatic adaptation of dynamic compensation {1632}Qualified service level. Range 0 to 100, default 65.FLOAT32ABCD%Read/write
HR1080Clear AUX2 event partial overload {1640}Qualified service level. Float 0.0 = no, 1.0 = yes.FLOAT32ABCDRead/write0 = No; 1 = Yes
HR1086Partial overload {1643}Qualified service level. Float 0.0 = no, 1.0 = yes.FLOAT32ABCDRead/write0 = No; 1 = Yes
HR1088Activated by AUX2 event partial overload {1644}Qualified service level. Float 0.0 = no, 1.0 = yes.FLOAT32ABCDRead/write0 = No; 1 = Yes
HR1090Pulses cutting regulation for XT (Not XTS) {1645}Qualified service level. Float 0.0 = no, 1.0 = yes.FLOAT32ABCDRead/write0 = No; 1 = Yes
HR1092Charger uses only power from AC-Out {1646}Installer level. Float 0.0 = no, 1.0 = yes.FLOAT32ABCDRead/write0 = No; 1 = Yes
HR1094Prohibits charger using only power from AC-Out {1647}Installer level. Float 0.0 = no, 1.0 = yes.FLOAT32ABCDRead/write0 = No; 1 = Yes
HR1096Imagnet INT level adjustment for correction {1648}Qualified service level. Range -300 to 300, default 0.FLOAT32ABCDRead/write
HR1098Imagnet ERROR level adjustment for correction {1649}Qualified service level. Range -300 to 300, default 0.FLOAT32ABCDRead/write
HR1100Minigrid compatible with lithium battery {1650}Installer level. Float 0.0 = no, 1.0 = yes.FLOAT32ABCDRead/write0 = No; 1 = Yes
HR1102Adjustment by pulse cut-off for smartboost only {1651}Installer level. Float 0.0 = no, 1.0 = yes.FLOAT32ABCDRead/write0 = No; 1 = Yes

Notes on this map

Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.

Questions about the Studer Innotec Xtender XTH / XTM / XTS inverter-charger (via Xcom-485i)

What Modbus registers does the Studer Innotec Xtender XTH / XTM / XTS inverter-charger (via Xcom-485i) have?

This map lists 469 registers: 113 input registers, 356 holding registers. 356 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.

Are the Studer Innotec Xtender XTH / XTM / XTS inverter-charger (via Xcom-485i) Modbus addresses 0-based or 1-based?

The manufacturer's document numbers registers 0-based (the number printed is the address on the wire). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. The appendix lists the register exactly as it goes in the request. The protocol spec's example reads info 3001 from register 2 with start address 0x0002 in the frame, and parameter 1107 from register 14 (0x000E).

What byte order does the Studer Innotec Xtender XTH / XTM / XTS inverter-charger (via Xcom-485i) use for 32-bit values?

Multi-register values in this map use ABCD (high word first (big-endian)). Set your client to this order for every 32/64-bit value in the table.

What are the minimum Modbus registers to integrate the Studer Innotec Xtender XTH / XTM / XTS inverter-charger (via Xcom-485i)?

Start with IR 0 Battery voltage {3000} (Battery voltage); IR 10 Battery charge current {3005} (Battery charge current); IR 14 State of charge {3007} (State of charge); IR 22 Input voltage {3011} (AC input voltage); IR 42 Output voltage {3021} (AC output voltage); IR 272 Output active power {3136} (Output active power); IR 56 Operating state {3028} (Operating state); HR 14 Maximum current of AC source (Input limit) {1107} (AC input current limit (setpoint)); HR 76 Battery charge current {1138} (Battery charge current (setpoint)).

How do I enable Modbus control of the Studer Innotec Xtender XTH / XTM / XTS inverter-charger (via Xcom-485i)?

Install the Xcom-485i on the Studer bus. DIP switches 1-2 set the unit-ID offset (0, 32, 64 or 128) and switches 7-8 set the baud rate (9600, 19200, 38400 or 115200). Frames are 8 data bits, even parity, 1 stop bit.

Where is the official Studer Innotec Xtender XTH / XTM / XTS inverter-charger (via Xcom-485i) Modbus documentation?

The source is Technical specification Studer Modbus RTU Appendix V1.6.44 (with Technical specification Studer Modbus RTU Protocol V1.1.3) (Appendix V1.6.44 (R706); Protocol V1.1.3), revision 2025-09-03, published free by Studer Innotec at https://studer-innotec.com/wp-content/uploads/2025/09/Manuel-xcom-485i-technical-specification.zip.

More Studer Innotec Modbus register maps

Other solar & battery inverters register maps

All solar & battery inverters Modbus register maps →

Source: Technical specification Studer Modbus RTU Appendix V1.6.44 (with Technical specification Studer Modbus RTU Protocol V1.1.3) · Appendix V1.6.44 (R706); Protocol V1.1.3 · rev. 2025-09-03. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.