KROHNE MFC 300 Coriolis mass flow converter (Modbus RTU) Modbus register map

Updated 17 November 2026

Short answer

The MFC 300 is a KROHNE signal converter for Coriolis mass flowmeters. With the Modbus option it is an RS-485 Modbus RTU slave. This map covers mass and volume flow, density, temperature, concentration and diagnosis floats, the double-float counters, counter and calibration parameters, serial settings and the control coils.

This page lists 68 Modbus registers for the KROHNE MFC 300 Coriolis mass flow converter (Modbus RTU) — 50 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from KROHNE’s own free documentation (linked below) and checked against it.

Manufacturer
KROHNE
Model
MFC 300 Coriolis mass flow converter (Modbus RTU)
Equipment type
Sensor (Coriolis mass flowmeter)
Registers
68 (50 writable)
Transport
Modbus RTU
Default unit ID
1
Default serial
19200 baud, 8E1
Documented addressing
0-based (the number printed is the address on the wire)
32-bit word order
ABCD high word first (big-endian)
Firmware
Electronic revision ER 3.3.xx (SW.REV. 3.3x), Modbus version 1.0.x
Also known as
MFC300, KROHNE MFC 300
Source document
MFC 300 Supplementary instructions - Description of Modbus interface · 4000744801 R01 · rev. 2009-11
Download CSV all columns JSON Manufacturer PDF ↗

Integration notes: KROHNE MFC 300 Coriolis mass flow converter (Modbus RTU)

Integration in brief

Read input registers 30000-30027 (function 04) for flow, density and temperature floats and 30050-30061 for the double-float counters. Use coils 3000-3005 to start, stop and reset counters.

Minimum registers to map

Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.

RegisterNameTypeWhyAccess
IR 30004Mass flowFLOAT32 ABCDMass flowRead
IR 30002Volume flowFLOAT32 ABCDVolume flowRead
IR 30008DensityFLOAT32 ABCDDensityRead
IR 30006TemperatureFLOAT32 ABCDTemperatureRead
IR 30050Counter 1FLOAT64 ABCDCounter 1Read

Enable Modbus control & writes

Set address, baud rate, parity, data format and stop bits in converter menu C6.8.

Byte order & addressing

Network setup

Watch out for

KROHNE MFC 300 Coriolis mass flow converter (Modbus RTU) Modbus registers

Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.

68 of 68 shown
KROHNE MFC 300 Coriolis mass flow converter (Modbus RTU) Modbus register map
TableAddressNameDescriptionTypeOrderScaleUnitsAccessValues / bits
CO1000Cold startWrite 1 to cold-start the converter.BITRead/write
CO1001Warm startWrite 1 to warm-start; activates new calibration values.BITRead/write
CO1002Error resetWrite 1 to reset errors.BITRead/write
CO2000Zero calibrationWrite 1 to start; reads 1 while running.BITRead/write
CO2001Single-point density calibrationWrite 1 to start.BITRead/write
CO2002Two-point density calibration, point 1Write 1 to start.BITRead/write
CO2003Two-point density calibration, point 2Write 1 to start.BITRead/write
CO3000Counter 1 start/stopWrite 1 start, 0 stop.BITRead/write
CO3001Counter 2 start/stopWrite 1 start, 0 stop.BITRead/write
CO3002Counter 3 start/stopIO2 only.BITRead/write
CO3003Counter 1 resetWrite 1 to reset.BITRead/write
CO3004Counter 2 resetWrite 1 to reset.BITRead/write
CO3005Counter 3 resetIO2 only.BITRead/write
IR20000Calibration resultResult of the last calibration function (first float).FLOAT32ABCDRead
IR30000Flow velocityFLOAT32ABCDm/sRead
IR30002Volume flowFLOAT32ABCDm3/sRead
IR30004Mass flowFLOAT32ABCDkg/sRead
IR30006TemperatureFLOAT32ABCDKRead
IR30008DensityFLOAT32ABCDkg/m3Read
IR30010Concentration 1Type chosen in 42000.FLOAT32ABCDRead
IR30012Concentration 2 or diagnosis 3FLOAT32ABCDRead
IR30014Concentration flow 1FLOAT32ABCDRead
IR30016Concentration flow 2FLOAT32ABCDRead
IR30018Diagnosis 1Type chosen in 42002.FLOAT32ABCDRead
IR30020Diagnosis 2Type chosen in 42003.FLOAT32ABCDRead
IR30022Display channel 1First line of the first measurement screen, SI units.FLOAT32ABCDRead
IR30024Display channel 2First line of the second measurement screen, SI units.FLOAT32ABCDRead
IR30026Operating timeFLOAT32ABCDsRead
IR30050Counter 1m3 or kg.FLOAT64ABCDRead
IR30054Counter 2m3 or kg.FLOAT64ABCDRead
IR30058Counter 3m3 or kg; only with IO2.FLOAT64ABCDRead
HR40000Counter 1 functionUINT16Read/write0 = Off; 1 = Sum counter; 2 = + counter; 3 = - counter
HR40001Counter 1 measurementUINT16Read/write21 = Volume flow; 22 = Mass flow; 27 = Concentration flow 1; 28 = Concentration flow 2
HR40002Counter 2 functionUINT16Read/write0 = Off; 1 = Sum counter; 2 = + counter; 3 = - counter
HR40003Counter 2 measurementUINT16Read/write21 = Volume flow; 22 = Mass flow; 27 = Concentration flow 1; 28 = Concentration flow 2
HR40004Counter 3 functionOnly with IO2.UINT16Read/write0 = Off; 1 = Sum counter; 2 = + counter; 3 = - counter
HR40005Counter 3 measurementOnly with IO2.UINT16Read/write21 = Volume flow; 22 = Mass flow; 27 = Concentration flow 1; 28 = Concentration flow 2
HR41000Counter 1 low flow cutoffm3/s or kg/s.FLOAT32ABCDRead/write
HR41002Counter 1 time constantFLOAT32ABCDsRead/write
HR41004Counter 1 value (set/read)m3 or kg.FLOAT32ABCDRead/write
HR41006Counter 2 low flow cutoffm3/s or kg/s.FLOAT32ABCDRead/write
HR41008Counter 2 time constantFLOAT32ABCDsRead/write
HR41010Counter 2 value (set/read)m3 or kg.FLOAT32ABCDRead/write
HR41012Counter 3 low flow cutoffm3/s or kg/s; IO2 only.FLOAT32ABCDRead/write
HR41014Counter 3 time constantIO2 only.FLOAT32ABCDsRead/write
HR41016Counter 3 value (set/read)m3 or kg; IO2 only.FLOAT32ABCDRead/write
HR41018Counter 1 presetm3 or kg.FLOAT32ABCDRead/write
HR41020Counter 2 presetm3 or kg.FLOAT32ABCDRead/write
HR41022Counter 3 presetm3 or kg; IO2 only.FLOAT32ABCDRead/write
HR42000Concentration 1 selectionUINT16Read/write1 = Off; 2 = Brix; 3 = % mass; 4 = Baume 144; 5 = Baume 145; 6 = % NaOH; 7 = Plato; 8 = API; 9 = % volume
HR42001Concentration 2 selectionUINT16Read/write1 = Off; 2 = Brix; 3 = % mass; 4 = Baume 144; 5 = Baume 145; 6 = % NaOH; 7 = Plato; 8 = API; 9 = % volume
HR42002Diagnosis 1 selectionUINT16Read/write9 = Tube frequency [Hz]; 10 = Measuring tube strain [Ohm]; 11 = Inner cylinder strain [Ohm]; 14 = Drive energy [%]; 31 = Sensor average [%]; 32 = Sensor deviation [%]; 255 = Off
HR42003Diagnosis 2 selectionUINT16Read/write9 = Tube frequency [Hz]; 10 = Measuring tube strain [Ohm]; 11 = Inner cylinder strain [Ohm]; 14 = Drive energy [%]; 31 = Sensor average [%]; 32 = Sensor deviation [%]; 255 = Off
HR42004Diagnosis 3 selectionUINT16Read/write9 = Tube frequency [Hz]; 10 = Measuring tube strain [Ohm]; 11 = Inner cylinder strain [Ohm]; 14 = Drive energy [%]; 31 = Sensor average [%]; 32 = Sensor deviation [%]; 255 = Off
HR43000Zero calibration valueFLOAT32ABCDRead/write
HR43002Zero calibration temperatureFLOAT32ABCDRead/write
HR43004DCF2FLOAT32ABCDRead/write
HR43006DCF3FLOAT32ABCDRead/write
HR43008DCF4FLOAT32ABCDRead/write
HR43010DCF6FLOAT32ABCDRead/write
HR43012DCF7FLOAT32ABCDRead/write
HR43014DCF8FLOAT32ABCDRead/write
HR44000Density calibration stateUINT16Read/write0 = First point not done; 1 = First point done
HR44001DCF1 mediumUINT16Read/write0 = Empty; 1 = Pure water; 2 = Town water; 3 = Other
HR44002DCF5 mediumUINT16Read/write0 = Empty; 1 = Pure water; 2 = Town water; 3 = Other
HR50000Baud rate1200-115200; default 19200.UINT32ABCDbaudRead/write
HR50002Slave address1-247, default 1.UINT16Read/write
HR50003ParityUINT16Read/write0 = Even (default); 1 = Odd; 3 = None

Notes on this map

Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.

Questions about the KROHNE MFC 300 Coriolis mass flow converter (Modbus RTU)

What Modbus registers does the KROHNE MFC 300 Coriolis mass flow converter (Modbus RTU) have?

This map lists 68 registers: 13 coils, 18 input registers, 37 holding registers. 50 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.

Are the KROHNE MFC 300 Coriolis mass flow converter (Modbus RTU) Modbus addresses 0-based or 1-based?

The manufacturer's document numbers registers 0-based (the number printed is the address on the wire). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. The manual lists protocol addresses that go into the request unchanged: input register 30006 is requested as start address 30006 (0x7536).

What byte order does the KROHNE MFC 300 Coriolis mass flow converter (Modbus RTU) use for 32-bit values?

Multi-register values in this map use ABCD (high word first (big-endian)). Set your client to this order for every 32/64-bit value in the table.

What are the minimum Modbus registers to integrate the KROHNE MFC 300 Coriolis mass flow converter (Modbus RTU)?

Start with IR 30004 Mass flow (Mass flow); IR 30002 Volume flow (Volume flow); IR 30008 Density (Density); IR 30006 Temperature (Temperature); IR 30050 Counter 1 (Counter 1).

How do I enable Modbus control of the KROHNE MFC 300 Coriolis mass flow converter (Modbus RTU)?

Set address, baud rate, parity, data format and stop bits in converter menu C6.8.

Where is the official KROHNE MFC 300 Coriolis mass flow converter (Modbus RTU) Modbus documentation?

The source is MFC 300 Supplementary instructions - Description of Modbus interface (4000744801 R01), revision 2009-11, published free by KROHNE at https://cdn.krohne.com/archive/AD_MFC300_Modbus_en_091124_4000744801_R01.pdf.

More KROHNE Modbus register maps

Other power & energy meters register maps

All power & energy meters Modbus register maps →

Source: MFC 300 Supplementary instructions - Description of Modbus interface · 4000744801 R01 · rev. 2009-11. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.