- MFC 300 Coriolis mass flow converter (Modbus RTU)
Sensor (Coriolis mass flowmeter) · Modbus register map
KROHNE MFC 300 Coriolis mass flow converter (Modbus RTU) Modbus register map
Updated 17 November 2026
The MFC 300 is a KROHNE signal converter for Coriolis mass flowmeters. With the Modbus option it is an RS-485 Modbus RTU slave. This map covers mass and volume flow, density, temperature, concentration and diagnosis floats, the double-float counters, counter and calibration parameters, serial settings and the control coils.
This page lists 68 Modbus registers for the KROHNE MFC 300 Coriolis mass flow converter (Modbus RTU) — 50 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from KROHNE’s own free documentation (linked below) and checked against it.
- Manufacturer
- KROHNE
- Model
- MFC 300 Coriolis mass flow converter (Modbus RTU)
- Equipment type
- Sensor (Coriolis mass flowmeter)
- Registers
- 68 (50 writable)
- Transport
- Modbus RTU
- Default unit ID
- 1
- Default serial
- 19200 baud, 8E1
- Documented addressing
- 0-based (the number printed is the address on the wire)
- 32-bit word order
- ABCD high word first (big-endian)
- Firmware
- Electronic revision ER 3.3.xx (SW.REV. 3.3x), Modbus version 1.0.x
- Also known as
- MFC300, KROHNE MFC 300
Integration notes: KROHNE MFC 300 Coriolis mass flow converter (Modbus RTU)
Read input registers 30000-30027 (function 04) for flow, density and temperature floats and 30050-30061 for the double-float counters. Use coils 3000-3005 to start, stop and reset counters.
Minimum registers to map
Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.
| Register | Name | Type | Why | Access |
|---|---|---|---|---|
| IR 30004 | Mass flow | FLOAT32 ABCD | Mass flow | Read |
| IR 30002 | Volume flow | FLOAT32 ABCD | Volume flow | Read |
| IR 30008 | Density | FLOAT32 ABCD | Density | Read |
| IR 30006 | Temperature | FLOAT32 ABCD | Temperature | Read |
| IR 30050 | Counter 1 | FLOAT64 ABCD | Counter 1 | Read |
Enable Modbus control & writes
Set address, baud rate, parity, data format and stop bits in converter menu C6.8.
Byte order & addressing
- Protocol addresses are sent as printed.
- Temperature is in kelvin.
- Counters are 64-bit doubles.
Network setup
- Defaults 19200 baud, even parity, 1 stop bit, address 1.
- Bus termination and biasing are off by default; set jumpers X5/X6 on the Modbus board to enable them.
Watch out for
- New calibration values take effect after a warm start (coil 1001).
KROHNE MFC 300 Coriolis mass flow converter (Modbus RTU) Modbus registers
Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.
| Table | Address | Name | Description | Type | Order | Scale | Units | Access | Values / bits |
|---|---|---|---|---|---|---|---|---|---|
| CO | 1000 | Cold start | Write 1 to cold-start the converter. | BIT | Read/write | ||||
| CO | 1001 | Warm start | Write 1 to warm-start; activates new calibration values. | BIT | Read/write | ||||
| CO | 1002 | Error reset | Write 1 to reset errors. | BIT | Read/write | ||||
| CO | 2000 | Zero calibration | Write 1 to start; reads 1 while running. | BIT | Read/write | ||||
| CO | 2001 | Single-point density calibration | Write 1 to start. | BIT | Read/write | ||||
| CO | 2002 | Two-point density calibration, point 1 | Write 1 to start. | BIT | Read/write | ||||
| CO | 2003 | Two-point density calibration, point 2 | Write 1 to start. | BIT | Read/write | ||||
| CO | 3000 | Counter 1 start/stop | Write 1 start, 0 stop. | BIT | Read/write | ||||
| CO | 3001 | Counter 2 start/stop | Write 1 start, 0 stop. | BIT | Read/write | ||||
| CO | 3002 | Counter 3 start/stop | IO2 only. | BIT | Read/write | ||||
| CO | 3003 | Counter 1 reset | Write 1 to reset. | BIT | Read/write | ||||
| CO | 3004 | Counter 2 reset | Write 1 to reset. | BIT | Read/write | ||||
| CO | 3005 | Counter 3 reset | IO2 only. | BIT | Read/write | ||||
| IR | 20000 | Calibration result | Result of the last calibration function (first float). | FLOAT32 | ABCD | Read | |||
| IR | 30000 | Flow velocity | FLOAT32 | ABCD | m/s | Read | |||
| IR | 30002 | Volume flow | FLOAT32 | ABCD | m3/s | Read | |||
| IR | 30004 | Mass flow | FLOAT32 | ABCD | kg/s | Read | |||
| IR | 30006 | Temperature | FLOAT32 | ABCD | K | Read | |||
| IR | 30008 | Density | FLOAT32 | ABCD | kg/m3 | Read | |||
| IR | 30010 | Concentration 1 | Type chosen in 42000. | FLOAT32 | ABCD | Read | |||
| IR | 30012 | Concentration 2 or diagnosis 3 | FLOAT32 | ABCD | Read | ||||
| IR | 30014 | Concentration flow 1 | FLOAT32 | ABCD | Read | ||||
| IR | 30016 | Concentration flow 2 | FLOAT32 | ABCD | Read | ||||
| IR | 30018 | Diagnosis 1 | Type chosen in 42002. | FLOAT32 | ABCD | Read | |||
| IR | 30020 | Diagnosis 2 | Type chosen in 42003. | FLOAT32 | ABCD | Read | |||
| IR | 30022 | Display channel 1 | First line of the first measurement screen, SI units. | FLOAT32 | ABCD | Read | |||
| IR | 30024 | Display channel 2 | First line of the second measurement screen, SI units. | FLOAT32 | ABCD | Read | |||
| IR | 30026 | Operating time | FLOAT32 | ABCD | s | Read | |||
| IR | 30050 | Counter 1 | m3 or kg. | FLOAT64 | ABCD | Read | |||
| IR | 30054 | Counter 2 | m3 or kg. | FLOAT64 | ABCD | Read | |||
| IR | 30058 | Counter 3 | m3 or kg; only with IO2. | FLOAT64 | ABCD | Read | |||
| HR | 40000 | Counter 1 function | UINT16 | Read/write | 0 = Off; 1 = Sum counter; 2 = + counter; 3 = - counter | ||||
| HR | 40001 | Counter 1 measurement | UINT16 | Read/write | 21 = Volume flow; 22 = Mass flow; 27 = Concentration flow 1; 28 = Concentration flow 2 | ||||
| HR | 40002 | Counter 2 function | UINT16 | Read/write | 0 = Off; 1 = Sum counter; 2 = + counter; 3 = - counter | ||||
| HR | 40003 | Counter 2 measurement | UINT16 | Read/write | 21 = Volume flow; 22 = Mass flow; 27 = Concentration flow 1; 28 = Concentration flow 2 | ||||
| HR | 40004 | Counter 3 function | Only with IO2. | UINT16 | Read/write | 0 = Off; 1 = Sum counter; 2 = + counter; 3 = - counter | |||
| HR | 40005 | Counter 3 measurement | Only with IO2. | UINT16 | Read/write | 21 = Volume flow; 22 = Mass flow; 27 = Concentration flow 1; 28 = Concentration flow 2 | |||
| HR | 41000 | Counter 1 low flow cutoff | m3/s or kg/s. | FLOAT32 | ABCD | Read/write | |||
| HR | 41002 | Counter 1 time constant | FLOAT32 | ABCD | s | Read/write | |||
| HR | 41004 | Counter 1 value (set/read) | m3 or kg. | FLOAT32 | ABCD | Read/write | |||
| HR | 41006 | Counter 2 low flow cutoff | m3/s or kg/s. | FLOAT32 | ABCD | Read/write | |||
| HR | 41008 | Counter 2 time constant | FLOAT32 | ABCD | s | Read/write | |||
| HR | 41010 | Counter 2 value (set/read) | m3 or kg. | FLOAT32 | ABCD | Read/write | |||
| HR | 41012 | Counter 3 low flow cutoff | m3/s or kg/s; IO2 only. | FLOAT32 | ABCD | Read/write | |||
| HR | 41014 | Counter 3 time constant | IO2 only. | FLOAT32 | ABCD | s | Read/write | ||
| HR | 41016 | Counter 3 value (set/read) | m3 or kg; IO2 only. | FLOAT32 | ABCD | Read/write | |||
| HR | 41018 | Counter 1 preset | m3 or kg. | FLOAT32 | ABCD | Read/write | |||
| HR | 41020 | Counter 2 preset | m3 or kg. | FLOAT32 | ABCD | Read/write | |||
| HR | 41022 | Counter 3 preset | m3 or kg; IO2 only. | FLOAT32 | ABCD | Read/write | |||
| HR | 42000 | Concentration 1 selection | UINT16 | Read/write | 1 = Off; 2 = Brix; 3 = % mass; 4 = Baume 144; 5 = Baume 145; 6 = % NaOH; 7 = Plato; 8 = API; 9 = % volume | ||||
| HR | 42001 | Concentration 2 selection | UINT16 | Read/write | 1 = Off; 2 = Brix; 3 = % mass; 4 = Baume 144; 5 = Baume 145; 6 = % NaOH; 7 = Plato; 8 = API; 9 = % volume | ||||
| HR | 42002 | Diagnosis 1 selection | UINT16 | Read/write | 9 = Tube frequency [Hz]; 10 = Measuring tube strain [Ohm]; 11 = Inner cylinder strain [Ohm]; 14 = Drive energy [%]; 31 = Sensor average [%]; 32 = Sensor deviation [%]; 255 = Off | ||||
| HR | 42003 | Diagnosis 2 selection | UINT16 | Read/write | 9 = Tube frequency [Hz]; 10 = Measuring tube strain [Ohm]; 11 = Inner cylinder strain [Ohm]; 14 = Drive energy [%]; 31 = Sensor average [%]; 32 = Sensor deviation [%]; 255 = Off | ||||
| HR | 42004 | Diagnosis 3 selection | UINT16 | Read/write | 9 = Tube frequency [Hz]; 10 = Measuring tube strain [Ohm]; 11 = Inner cylinder strain [Ohm]; 14 = Drive energy [%]; 31 = Sensor average [%]; 32 = Sensor deviation [%]; 255 = Off | ||||
| HR | 43000 | Zero calibration value | FLOAT32 | ABCD | Read/write | ||||
| HR | 43002 | Zero calibration temperature | FLOAT32 | ABCD | Read/write | ||||
| HR | 43004 | DCF2 | FLOAT32 | ABCD | Read/write | ||||
| HR | 43006 | DCF3 | FLOAT32 | ABCD | Read/write | ||||
| HR | 43008 | DCF4 | FLOAT32 | ABCD | Read/write | ||||
| HR | 43010 | DCF6 | FLOAT32 | ABCD | Read/write | ||||
| HR | 43012 | DCF7 | FLOAT32 | ABCD | Read/write | ||||
| HR | 43014 | DCF8 | FLOAT32 | ABCD | Read/write | ||||
| HR | 44000 | Density calibration state | UINT16 | Read/write | 0 = First point not done; 1 = First point done | ||||
| HR | 44001 | DCF1 medium | UINT16 | Read/write | 0 = Empty; 1 = Pure water; 2 = Town water; 3 = Other | ||||
| HR | 44002 | DCF5 medium | UINT16 | Read/write | 0 = Empty; 1 = Pure water; 2 = Town water; 3 = Other | ||||
| HR | 50000 | Baud rate | 1200-115200; default 19200. | UINT32 | ABCD | baud | Read/write | ||
| HR | 50002 | Slave address | 1-247, default 1. | UINT16 | Read/write | ||||
| HR | 50003 | Parity | UINT16 | Read/write | 0 = Even (default); 1 = Odd; 3 = None |
Notes on this map
- Data format is selectable in converter menu C6.8; the default is Big Endian, which section 6.2 defines as MSB first, so floats and doubles are listed ABCD. The register table for 50004 pairs the labels the other way round (see below), so check one known value (for example 30000 at zero flow, or the baud rate at 50000) before trusting a new installation.
- Left out: the data-format register 50004, because its printed coding contradicts itself (0 = Little Endian 'MSB first', 1 = Big Endian 'LSB first'); set data format at the converter menu instead.
- Left out: long status sensor/device (30062 / 30064, byte[4]) because their bits are not defined here.
- Counter 3 and its parameters exist only on converters with the IO2 option; writing to a missing counter returns an error.
- Factory serial settings: address 1, 19200 baud, even parity, 1 stop bit.
Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.
Questions about the KROHNE MFC 300 Coriolis mass flow converter (Modbus RTU)
What Modbus registers does the KROHNE MFC 300 Coriolis mass flow converter (Modbus RTU) have?
This map lists 68 registers: 13 coils, 18 input registers, 37 holding registers. 50 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.
Are the KROHNE MFC 300 Coriolis mass flow converter (Modbus RTU) Modbus addresses 0-based or 1-based?
The manufacturer's document numbers registers 0-based (the number printed is the address on the wire). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. The manual lists protocol addresses that go into the request unchanged: input register 30006 is requested as start address 30006 (0x7536).
What byte order does the KROHNE MFC 300 Coriolis mass flow converter (Modbus RTU) use for 32-bit values?
Multi-register values in this map use ABCD (high word first (big-endian)). Set your client to this order for every 32/64-bit value in the table.
What are the minimum Modbus registers to integrate the KROHNE MFC 300 Coriolis mass flow converter (Modbus RTU)?
Start with IR 30004 Mass flow (Mass flow); IR 30002 Volume flow (Volume flow); IR 30008 Density (Density); IR 30006 Temperature (Temperature); IR 30050 Counter 1 (Counter 1).
How do I enable Modbus control of the KROHNE MFC 300 Coriolis mass flow converter (Modbus RTU)?
Set address, baud rate, parity, data format and stop bits in converter menu C6.8.
Where is the official KROHNE MFC 300 Coriolis mass flow converter (Modbus RTU) Modbus documentation?
The source is MFC 300 Supplementary instructions - Description of Modbus interface (4000744801 R01), revision 2009-11, published free by KROHNE at https://cdn.krohne.com/archive/AD_MFC300_Modbus_en_091124_4000744801_R01.pdf.
More KROHNE Modbus register maps
- Sensor (battery-powered electromagnetic water flowmeter)
KROHNE IFC 070 signal converter (Modbus)
IFC 070 electronic revision 5.1.0, Modbus version 1.1.1 (battery) and 1.1.0 (FlexPower), per AD IFC 070 Modbus R02.
Also known as: WATERFLUX 3070, IFC070, IFC 070 FlexPower - Sensor (electromagnetic flowmeter)
KROHNE IFC 100 electromagnetic flow converter (Modbus RTU)
IFC 100 signal converter with the Modbus option, supplementary instructions 4001410101 R01 (08/2014).
Also known as: IFC100, IFC 100 Modbus, KROHNE IFC 100 - Sensor (ultrasonic flowmeter)
KROHNE UFC 400 ultrasonic flow converter (Modbus RTU)
UFC 400 signal converter with Modbus, electronic revision ER 2.2.0_, Modbus version 2.1.0_, supplementary instructions 4002744801 R01 (05/2013).
Also known as: UFC400, KROHNE UFC 400, UFC 400 Modbus
Other power & energy meters register maps
- Power meter (panel network parameter meter)
Lumel ND20 network parameter meter
Lumel ND20 panel meter per the ND20 user's manual; registers 4056-4061 need firmware 1.09 or later and are not listed here.
Also known as: ND20, ND20-xxxx - Power meter (DIN-rail network meter)
Lumel NR30 DIN-rail power network meter
Lumel NR30 rail-mounted 3-phase meter (RS-485 Modbus RTU; Ethernet versions also offer Modbus TCP), per manual NR30-09E_R1.
Also known as: NR30 - Power meter (multi-circuit power monitor)
Omron KM-N3-FLK on-panel power monitor
Omron KM-N3-FLK power monitor (catalog N214-E1-04).
Also known as: KM-N3-FLK, KM-N3 - Sensor (counter / rate panel meter)
Red Lion PAX2D counter / rate panel meter (Modbus)
PAX2D dual counter / rate meter, per register table LP0930A (4/11/13).
Also known as: PAX2D, PAX2 D, Red Lion PAX2D counter - Energy meter
Rishabh Instruments RISH EC43xx / ER43xx DIN-rail energy meters
Rishabh RISH EC43xx and ER43xx DIN-rail digital energy meters with RS-485 Modbus, per interface definition DMAN-00IM-09xx Rev. F (11/25).
Also known as: EC4311, EC4321, ER4311, ER4321, RISH EC43X1, EC43XX, ER43XX - Energy meter (DC)
Rishabh Instruments RISH EM DC 6000 programmable DC energy meter
Rishabh RISH EM DC 6000 single-channel programmable DC energy meters with RS-485 Modbus, per interface definition DMAN-00IM-0862 Rev. 0 (12/2020).
Also known as: RISH EM DC 6000, EMDC 6000, EM DC6000
All power & energy meters Modbus register maps →
Source: MFC 300 Supplementary instructions - Description of Modbus interface · 4000744801 R01 · rev. 2009-11. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.