Sensor (electromagnetic flowmeter) · Modbus register map

KROHNE IFC 100 electromagnetic flow converter (Modbus RTU) Modbus register map

Updated 17 November 2026

Short answer

The IFC 100 is a KROHNE signal converter for electromagnetic flowmeters. With the Modbus option it is an RS-485 Modbus RTU slave. This map covers flow, temperature, conductivity and diagnosis floats, the two double-float totalisers, counter and filter settings, calibration values, serial parameters and the control coils.

This page lists 63 Modbus registers for the KROHNE IFC 100 electromagnetic flow converter (Modbus RTU) — 51 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from KROHNE’s own free documentation (linked below) and checked against it.

Manufacturer
KROHNE
Model
IFC 100 electromagnetic flow converter (Modbus RTU)
Equipment type
Sensor (electromagnetic flowmeter)
Registers
63 (51 writable)
Transport
Modbus RTU
Default unit ID
1
Default serial
19200 baud, 8E1
Documented addressing
0-based (the number printed is the address on the wire)
32-bit word order
ABCD high word first (big-endian)
Firmware
Electronic revision ER 3.0.xx, Modbus version 1.0.xx
Also known as
IFC100, IFC 100 Modbus, KROHNE IFC 100
Source document
IFC 100 Supplementary instructions - Description of Modbus interface · 4001410101 R01 · rev. 2014-08
Download CSV all columns JSON Manufacturer PDF ↗

Integration notes: KROHNE IFC 100 electromagnetic flow converter (Modbus RTU)

Integration in brief

Read input registers 30000-30027 (function 04) in one block for flow speed, volume and mass flow, temperature and the two double-float counters. Use coils (function 05) for counter start/stop/reset and error reset.

Minimum registers to map

Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.

RegisterNameTypeWhyAccess
IR 30002Volume flowFLOAT32 ABCDVolume flowRead
IR 30004Mass flowFLOAT32 ABCDMass flowRead
IR 30000Flow speedFLOAT32 ABCDFlow speedRead
IR 30020Counter 1FLOAT64 ABCDCounter 1Read
IR 30024Counter 2FLOAT64 ABCDCounter 2Read
IR 30006Coil temperatureFLOAT32 ABCDCoil temperatureRead

Enable Modbus control & writes

Set the Modbus slave address, baud rate, parity, data format and stop bits in converter menu C5.8 (or holding registers 50000-50004).

Byte order & addressing

Network setup

Watch out for

KROHNE IFC 100 electromagnetic flow converter (Modbus RTU) Modbus registers

Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.

63 of 63 shown
KROHNE IFC 100 electromagnetic flow converter (Modbus RTU) Modbus register map
TableAddressNameDescriptionTypeOrderScaleUnitsAccessValues / bits
CO1000Cold startWrite 1 to cold-start the converter.BITRead/write
CO1001Warm startWrite 1 to warm-start; also activates new calibration values.BITRead/write
CO1002Error resetWrite 1 to reset errors.BITRead/write
CO2000Zero calibrationWrite 1 to start; reads 1 while running.BITRead/write
CO2001Coil temperature calibrationWrite 1 to start; reads 1 while running.BITRead/write
CO2002Electrode factor calibrationWrite 1 to start; reads 1 while running.BITRead/write
CO3000Counter 1 start/stopWrite 1 start, 0 stop; reads 1 while running.BITRead/write
CO3001Counter 2 start/stopWrite 1 start, 0 stop; reads 1 while running.BITRead/write
CO3003Counter 1 resetWrite 1 to reset.BITRead/write
CO3004Counter 2 resetWrite 1 to reset.BITRead/write
IR20000Calibration resultResult of the last calibration function (first float).FLOAT32ABCDRead
IR30000Flow speedFLOAT32ABCDm/sRead
IR30002Volume flowFLOAT32ABCDm3/sRead
IR30004Mass flowFLOAT32ABCDkg/sRead
IR30006Coil temperatureFLOAT32ABCDKRead
IR30008ConductivityOnly measured when empty-pipe/conductivity function (42003) is on.FLOAT32ABCDS/mRead
IR30010Diagnosis valueMeaning set by 42011: electrode noise (m/s) or terminal 2/3 DC (V).FLOAT32ABCDRead
IR30012Display channel 1First line of the first measurement screen, SI units.FLOAT32ABCDRead
IR30014Display channel 2First line of the second measurement screen, SI units.FLOAT32ABCDRead
IR30016Operating timeFLOAT32ABCDsRead
IR30020Counter 1m3 or kg, per counter 1 measurement.FLOAT64ABCDRead
IR30024Counter 2m3 or kg, per counter 2 measurement.FLOAT64ABCDRead
HR40000Counter 1 functionUINT16Read/write0 = Off; 1 = Sum counter; 2 = + counter; 3 = - counter
HR40001Counter 1 measurementUINT16Read/write21 = Volume flow; 22 = Mass flow
HR40002Counter 2 functionUINT16Read/write0 = Off; 1 = Sum counter; 2 = + counter; 3 = - counter
HR40003Counter 2 measurementUINT16Read/write21 = Volume flow; 22 = Mass flow
HR41000Counter 1 low flow cutoffm3/s or kg/s.FLOAT32ABCDRead/write
HR41002Counter 1 time constantFLOAT32ABCDsRead/write
HR41004Counter 1 value (set/read)m3 or kg.FLOAT32ABCDRead/write
HR41006Counter 2 low flow cutoffm3/s or kg/s.FLOAT32ABCDRead/write
HR41008Counter 2 time constantFLOAT32ABCDsRead/write
HR41010Counter 2 value (set/read)m3 or kg.FLOAT32ABCDRead/write
HR41018Counter 1 presetm3 or kg.FLOAT32ABCDRead/write
HR41020Counter 2 presetm3 or kg.FLOAT32ABCDRead/write
HR42000Flow directionUINT16Read/write0 = Normal; 1 = Reverse
HR42001Pulse filterUINT16Read/write0 = Off; 1 = On; 2 = Automatic
HR42002Noise filterUINT16Read/write0 = Off; 1 = On
HR42003Empty pipe / conductivityUINT16Read/write0 = Off; 1 = Conductivity; 2 = Cond. + empty pipe (S); 3 = Cond. + empty pipe (F); 4 = Cond. + empty pipe (I)
HR42009Electrode noiseUINT16Read/write0 = Off; 1 = On
HR42010Settling of fieldUINT16Read/write0 = Off; 1 = On
HR42011Diagnosis value selectionUINT16Read/write8 = Terminal 2 DC; 9 = Terminal 3 DC; 25 = Off; 31 = Electrode noise
HR43000Limitation lowFLOAT32ABCDm/sRead/write
HR43002Limitation highFLOAT32ABCDm/sRead/write
HR43004Time constantFLOAT32ABCDsRead/write
HR43006Pulse width (pulse filter on)FLOAT32ABCDsRead/write
HR43008Pulse limitationFLOAT32ABCDm/sRead/write
HR43010Noise levelFLOAT32ABCDm/sRead/write
HR43012Noise suppressionFLOAT32ABCDRead/write
HR43014Low flow cutoffFLOAT32ABCDm/sRead/write
HR43016Limit empty pipeFLOAT32ABCDS/mRead/write
HR43022Limit electrode noiseFLOAT32ABCDm/sRead/write
HR43024Zero pointFLOAT32ABCDm/sRead/write
HR43026Coil resistance Rsp,20FLOAT32ABCDOhmRead/write
HR43028Coil temperature calibration pointFLOAT32ABCDKRead/write
HR43030Coil resistance calibration pointFLOAT32ABCDOhmRead/write
HR43032Electrode factor EFFLOAT32ABCDmRead/write
HR43034Conductivity calibration pointFLOAT32ABCDS/mRead/write
HR43036Conductivity calibration point (second copy)Write the same target to 43034 and 43036.FLOAT32ABCDS/mRead/write
HR43038Pulse width (pulse filter automatic)FLOAT32ABCDsRead/write
HR50000Baud rate1200-115200; default 19200.UINT32ABCDbaudRead/write
HR50002Slave address1-247, default 1.UINT16Read/write
HR50003ParityUINT16Read/write0 = Even (default); 1 = Odd; 3 = None
HR50004Data formatUINT16Read/write1 = Big endian; 2 = Little endian

Notes on this map

Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.

Questions about the KROHNE IFC 100 electromagnetic flow converter (Modbus RTU)

What Modbus registers does the KROHNE IFC 100 electromagnetic flow converter (Modbus RTU) have?

This map lists 63 registers: 10 coils, 12 input registers, 41 holding registers. 51 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.

Are the KROHNE IFC 100 electromagnetic flow converter (Modbus RTU) Modbus addresses 0-based or 1-based?

The manufacturer's document numbers registers 0-based (the number printed is the address on the wire). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. The manual lists protocol addresses and says they go into the request unchanged: input register 30006 is requested as start address 30006 (0x7536). The same registers are mirrored lower for masters that cannot use high addresses (30000-38998 -> 0-8998, 20000-20998 -> 9000-9998, 40000-49998 -> 0-9998).

What byte order does the KROHNE IFC 100 electromagnetic flow converter (Modbus RTU) use for 32-bit values?

Multi-register values in this map use ABCD (high word first (big-endian)). Set your client to this order for every 32/64-bit value in the table.

What are the minimum Modbus registers to integrate the KROHNE IFC 100 electromagnetic flow converter (Modbus RTU)?

Start with IR 30002 Volume flow (Volume flow); IR 30004 Mass flow (Mass flow); IR 30000 Flow speed (Flow speed); IR 30020 Counter 1 (Counter 1); IR 30024 Counter 2 (Counter 2); IR 30006 Coil temperature (Coil temperature).

How do I enable Modbus control of the KROHNE IFC 100 electromagnetic flow converter (Modbus RTU)?

Set the Modbus slave address, baud rate, parity, data format and stop bits in converter menu C5.8 (or holding registers 50000-50004).

Where is the official KROHNE IFC 100 electromagnetic flow converter (Modbus RTU) Modbus documentation?

The source is IFC 100 Supplementary instructions - Description of Modbus interface (4001410101 R01), revision 2014-08, published free by KROHNE at https://cdn.krohne.com/archive/AD_IFC100_Modbus_en_140728_4001410101_R01.pdf.

More KROHNE Modbus register maps

Other power & energy meters register maps

All power & energy meters Modbus register maps →

Source: IFC 100 Supplementary instructions - Description of Modbus interface · 4001410101 R01 · rev. 2014-08. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.