- IFC 100 electromagnetic flow converter (Modbus RTU)
Sensor (electromagnetic flowmeter) · Modbus register map
KROHNE IFC 100 electromagnetic flow converter (Modbus RTU) Modbus register map
Updated 17 November 2026
The IFC 100 is a KROHNE signal converter for electromagnetic flowmeters. With the Modbus option it is an RS-485 Modbus RTU slave. This map covers flow, temperature, conductivity and diagnosis floats, the two double-float totalisers, counter and filter settings, calibration values, serial parameters and the control coils.
This page lists 63 Modbus registers for the KROHNE IFC 100 electromagnetic flow converter (Modbus RTU) — 51 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from KROHNE’s own free documentation (linked below) and checked against it.
- Manufacturer
- KROHNE
- Model
- IFC 100 electromagnetic flow converter (Modbus RTU)
- Equipment type
- Sensor (electromagnetic flowmeter)
- Registers
- 63 (51 writable)
- Transport
- Modbus RTU
- Default unit ID
- 1
- Default serial
- 19200 baud, 8E1
- Documented addressing
- 0-based (the number printed is the address on the wire)
- 32-bit word order
- ABCD high word first (big-endian)
- Firmware
- Electronic revision ER 3.0.xx, Modbus version 1.0.xx
- Also known as
- IFC100, IFC 100 Modbus, KROHNE IFC 100
Integration notes: KROHNE IFC 100 electromagnetic flow converter (Modbus RTU)
Read input registers 30000-30027 (function 04) in one block for flow speed, volume and mass flow, temperature and the two double-float counters. Use coils (function 05) for counter start/stop/reset and error reset.
Minimum registers to map
Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.
| Register | Name | Type | Why | Access |
|---|---|---|---|---|
| IR 30002 | Volume flow | FLOAT32 ABCD | Volume flow | Read |
| IR 30004 | Mass flow | FLOAT32 ABCD | Mass flow | Read |
| IR 30000 | Flow speed | FLOAT32 ABCD | Flow speed | Read |
| IR 30020 | Counter 1 | FLOAT64 ABCD | Counter 1 | Read |
| IR 30024 | Counter 2 | FLOAT64 ABCD | Counter 2 | Read |
| IR 30006 | Coil temperature | FLOAT32 ABCD | Coil temperature | Read |
Enable Modbus control & writes
Set the Modbus slave address, baud rate, parity, data format and stop bits in converter menu C5.8 (or holding registers 50000-50004).
Byte order & addressing
- Addresses are protocol addresses sent as printed (30000 is sent as 30000).
- Low mirror addresses exist for masters limited to 9999.
- Counters are 64-bit doubles.
Network setup
- Defaults 19200 baud, even parity, 1 stop bit, address 1.
- Terminate both bus ends with 120 Ohm and bias the line at one point.
Watch out for
- New calibration values take effect only after a warm start (coil 1001), which takes up to 5 s.
- Write the conductivity target to both 43034 and 43036.
KROHNE IFC 100 electromagnetic flow converter (Modbus RTU) Modbus registers
Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.
| Table | Address | Name | Description | Type | Order | Scale | Units | Access | Values / bits |
|---|---|---|---|---|---|---|---|---|---|
| CO | 1000 | Cold start | Write 1 to cold-start the converter. | BIT | Read/write | ||||
| CO | 1001 | Warm start | Write 1 to warm-start; also activates new calibration values. | BIT | Read/write | ||||
| CO | 1002 | Error reset | Write 1 to reset errors. | BIT | Read/write | ||||
| CO | 2000 | Zero calibration | Write 1 to start; reads 1 while running. | BIT | Read/write | ||||
| CO | 2001 | Coil temperature calibration | Write 1 to start; reads 1 while running. | BIT | Read/write | ||||
| CO | 2002 | Electrode factor calibration | Write 1 to start; reads 1 while running. | BIT | Read/write | ||||
| CO | 3000 | Counter 1 start/stop | Write 1 start, 0 stop; reads 1 while running. | BIT | Read/write | ||||
| CO | 3001 | Counter 2 start/stop | Write 1 start, 0 stop; reads 1 while running. | BIT | Read/write | ||||
| CO | 3003 | Counter 1 reset | Write 1 to reset. | BIT | Read/write | ||||
| CO | 3004 | Counter 2 reset | Write 1 to reset. | BIT | Read/write | ||||
| IR | 20000 | Calibration result | Result of the last calibration function (first float). | FLOAT32 | ABCD | Read | |||
| IR | 30000 | Flow speed | FLOAT32 | ABCD | m/s | Read | |||
| IR | 30002 | Volume flow | FLOAT32 | ABCD | m3/s | Read | |||
| IR | 30004 | Mass flow | FLOAT32 | ABCD | kg/s | Read | |||
| IR | 30006 | Coil temperature | FLOAT32 | ABCD | K | Read | |||
| IR | 30008 | Conductivity | Only measured when empty-pipe/conductivity function (42003) is on. | FLOAT32 | ABCD | S/m | Read | ||
| IR | 30010 | Diagnosis value | Meaning set by 42011: electrode noise (m/s) or terminal 2/3 DC (V). | FLOAT32 | ABCD | Read | |||
| IR | 30012 | Display channel 1 | First line of the first measurement screen, SI units. | FLOAT32 | ABCD | Read | |||
| IR | 30014 | Display channel 2 | First line of the second measurement screen, SI units. | FLOAT32 | ABCD | Read | |||
| IR | 30016 | Operating time | FLOAT32 | ABCD | s | Read | |||
| IR | 30020 | Counter 1 | m3 or kg, per counter 1 measurement. | FLOAT64 | ABCD | Read | |||
| IR | 30024 | Counter 2 | m3 or kg, per counter 2 measurement. | FLOAT64 | ABCD | Read | |||
| HR | 40000 | Counter 1 function | UINT16 | Read/write | 0 = Off; 1 = Sum counter; 2 = + counter; 3 = - counter | ||||
| HR | 40001 | Counter 1 measurement | UINT16 | Read/write | 21 = Volume flow; 22 = Mass flow | ||||
| HR | 40002 | Counter 2 function | UINT16 | Read/write | 0 = Off; 1 = Sum counter; 2 = + counter; 3 = - counter | ||||
| HR | 40003 | Counter 2 measurement | UINT16 | Read/write | 21 = Volume flow; 22 = Mass flow | ||||
| HR | 41000 | Counter 1 low flow cutoff | m3/s or kg/s. | FLOAT32 | ABCD | Read/write | |||
| HR | 41002 | Counter 1 time constant | FLOAT32 | ABCD | s | Read/write | |||
| HR | 41004 | Counter 1 value (set/read) | m3 or kg. | FLOAT32 | ABCD | Read/write | |||
| HR | 41006 | Counter 2 low flow cutoff | m3/s or kg/s. | FLOAT32 | ABCD | Read/write | |||
| HR | 41008 | Counter 2 time constant | FLOAT32 | ABCD | s | Read/write | |||
| HR | 41010 | Counter 2 value (set/read) | m3 or kg. | FLOAT32 | ABCD | Read/write | |||
| HR | 41018 | Counter 1 preset | m3 or kg. | FLOAT32 | ABCD | Read/write | |||
| HR | 41020 | Counter 2 preset | m3 or kg. | FLOAT32 | ABCD | Read/write | |||
| HR | 42000 | Flow direction | UINT16 | Read/write | 0 = Normal; 1 = Reverse | ||||
| HR | 42001 | Pulse filter | UINT16 | Read/write | 0 = Off; 1 = On; 2 = Automatic | ||||
| HR | 42002 | Noise filter | UINT16 | Read/write | 0 = Off; 1 = On | ||||
| HR | 42003 | Empty pipe / conductivity | UINT16 | Read/write | 0 = Off; 1 = Conductivity; 2 = Cond. + empty pipe (S); 3 = Cond. + empty pipe (F); 4 = Cond. + empty pipe (I) | ||||
| HR | 42009 | Electrode noise | UINT16 | Read/write | 0 = Off; 1 = On | ||||
| HR | 42010 | Settling of field | UINT16 | Read/write | 0 = Off; 1 = On | ||||
| HR | 42011 | Diagnosis value selection | UINT16 | Read/write | 8 = Terminal 2 DC; 9 = Terminal 3 DC; 25 = Off; 31 = Electrode noise | ||||
| HR | 43000 | Limitation low | FLOAT32 | ABCD | m/s | Read/write | |||
| HR | 43002 | Limitation high | FLOAT32 | ABCD | m/s | Read/write | |||
| HR | 43004 | Time constant | FLOAT32 | ABCD | s | Read/write | |||
| HR | 43006 | Pulse width (pulse filter on) | FLOAT32 | ABCD | s | Read/write | |||
| HR | 43008 | Pulse limitation | FLOAT32 | ABCD | m/s | Read/write | |||
| HR | 43010 | Noise level | FLOAT32 | ABCD | m/s | Read/write | |||
| HR | 43012 | Noise suppression | FLOAT32 | ABCD | Read/write | ||||
| HR | 43014 | Low flow cutoff | FLOAT32 | ABCD | m/s | Read/write | |||
| HR | 43016 | Limit empty pipe | FLOAT32 | ABCD | S/m | Read/write | |||
| HR | 43022 | Limit electrode noise | FLOAT32 | ABCD | m/s | Read/write | |||
| HR | 43024 | Zero point | FLOAT32 | ABCD | m/s | Read/write | |||
| HR | 43026 | Coil resistance Rsp,20 | FLOAT32 | ABCD | Ohm | Read/write | |||
| HR | 43028 | Coil temperature calibration point | FLOAT32 | ABCD | K | Read/write | |||
| HR | 43030 | Coil resistance calibration point | FLOAT32 | ABCD | Ohm | Read/write | |||
| HR | 43032 | Electrode factor EF | FLOAT32 | ABCD | m | Read/write | |||
| HR | 43034 | Conductivity calibration point | FLOAT32 | ABCD | S/m | Read/write | |||
| HR | 43036 | Conductivity calibration point (second copy) | Write the same target to 43034 and 43036. | FLOAT32 | ABCD | S/m | Read/write | ||
| HR | 43038 | Pulse width (pulse filter automatic) | FLOAT32 | ABCD | s | Read/write | |||
| HR | 50000 | Baud rate | 1200-115200; default 19200. | UINT32 | ABCD | baud | Read/write | ||
| HR | 50002 | Slave address | 1-247, default 1. | UINT16 | Read/write | ||||
| HR | 50003 | Parity | UINT16 | Read/write | 0 = Even (default); 1 = Odd; 3 = None | ||||
| HR | 50004 | Data format | UINT16 | Read/write | 1 = Big endian; 2 = Little endian |
Notes on this map
- Data format is selectable (C5.8.4 or holding 50004): Big Endian, which the manual defines as MSB first for the data bytes, is the default, so 32-bit floats and 64-bit doubles are listed ABCD. With Little Endian (LSB first) selected the whole value is byte-reversed. The manual gives no worked byte example.
- Input registers 30000-30034 can also be read at 0-34, and holding registers 40000-49998 at 0-9998; only the primary addresses are listed.
- Left out: long status sensor/device (30032 / 30034, byte[4]) because the bit meanings are not given in this document; 'no function' and 'not used' registers.
- Factory serial settings: address 1, 19200 baud, even parity, 1 stop bit, Big Endian, 0 ms response delay.
- byte and word types in the holding tables each occupy one register and are listed as UINT16.
Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.
Questions about the KROHNE IFC 100 electromagnetic flow converter (Modbus RTU)
What Modbus registers does the KROHNE IFC 100 electromagnetic flow converter (Modbus RTU) have?
This map lists 63 registers: 10 coils, 12 input registers, 41 holding registers. 51 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.
Are the KROHNE IFC 100 electromagnetic flow converter (Modbus RTU) Modbus addresses 0-based or 1-based?
The manufacturer's document numbers registers 0-based (the number printed is the address on the wire). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. The manual lists protocol addresses and says they go into the request unchanged: input register 30006 is requested as start address 30006 (0x7536). The same registers are mirrored lower for masters that cannot use high addresses (30000-38998 -> 0-8998, 20000-20998 -> 9000-9998, 40000-49998 -> 0-9998).
What byte order does the KROHNE IFC 100 electromagnetic flow converter (Modbus RTU) use for 32-bit values?
Multi-register values in this map use ABCD (high word first (big-endian)). Set your client to this order for every 32/64-bit value in the table.
What are the minimum Modbus registers to integrate the KROHNE IFC 100 electromagnetic flow converter (Modbus RTU)?
Start with IR 30002 Volume flow (Volume flow); IR 30004 Mass flow (Mass flow); IR 30000 Flow speed (Flow speed); IR 30020 Counter 1 (Counter 1); IR 30024 Counter 2 (Counter 2); IR 30006 Coil temperature (Coil temperature).
How do I enable Modbus control of the KROHNE IFC 100 electromagnetic flow converter (Modbus RTU)?
Set the Modbus slave address, baud rate, parity, data format and stop bits in converter menu C5.8 (or holding registers 50000-50004).
Where is the official KROHNE IFC 100 electromagnetic flow converter (Modbus RTU) Modbus documentation?
The source is IFC 100 Supplementary instructions - Description of Modbus interface (4001410101 R01), revision 2014-08, published free by KROHNE at https://cdn.krohne.com/archive/AD_IFC100_Modbus_en_140728_4001410101_R01.pdf.
More KROHNE Modbus register maps
- Sensor (battery-powered electromagnetic water flowmeter)
KROHNE IFC 070 signal converter (Modbus)
IFC 070 electronic revision 5.1.0, Modbus version 1.1.1 (battery) and 1.1.0 (FlexPower), per AD IFC 070 Modbus R02.
Also known as: WATERFLUX 3070, IFC070, IFC 070 FlexPower - Sensor (Coriolis mass flowmeter)
KROHNE MFC 300 Coriolis mass flow converter (Modbus RTU)
MFC 300 converter with the Modbus option, supplementary instructions 4000744801 R01 (11/2009).
Also known as: MFC300, KROHNE MFC 300 - Sensor (ultrasonic flowmeter)
KROHNE UFC 400 ultrasonic flow converter (Modbus RTU)
UFC 400 signal converter with Modbus, electronic revision ER 2.2.0_, Modbus version 2.1.0_, supplementary instructions 4002744801 R01 (05/2013).
Also known as: UFC400, KROHNE UFC 400, UFC 400 Modbus
Other power & energy meters register maps
- Power meter (power analyzer)
Lovato Electric DMG7000 / DMG7500 / DMG8000 / DMG9000 power analyzers
Lovato DMG7000, DMG7500, DMG8000 and DMG9000 panel power analyzers on any Modbus port (RTU, ASCII or TCP); DMG9000-only rows are marked.
Also known as: DMG7000, DMG7500, DMG8000, DMG9000, DMG 7000, DMG 8000, DMG 9000, Lovato DMG - Energy meter (DIN-rail, single-phase)
Lumel NR10PLUS single-phase energy meter
Lumel NR10PLUS single-phase DIN-rail meter with RS-485 Modbus RTU, per its user manual.
Also known as: NR10PLUS - Power meter (multi-circuit power monitor)
Omron KM-N2-FLK multi-circuit power monitor
Omron KM-N2-FLK power monitor (catalog N200-E1-04).
Also known as: KM-N2-FLK, KM-N2 - Sensor / multi-parameter controller
ProMinent DULCOMETER diaLog DACb multi-parameter controller (Modbus RTU)
diaLog DACb controllers with the Modbus RTU interface option, per software manual BA DM 232 01/19.
Also known as: DACb, diaLog DACb, DULCOMETER DACb - Power meter (demand controller)
Rishabh Instruments RISH DMCi touch-screen demand controller with TOD
Rishabh RISH DMCi 96 x 96 mm touch-screen demand controllers with the optional RS-485 Modbus output, per interface definition DMAN-00IM-0578 Rev. A (09/16).
Also known as: RISH DMCi, DMCi, Rish DMCi demand controller - Energy meter
Rishabh Instruments RISH EM 3490 SS three-phase single-source energy meter
Rishabh RISH EM 3490 SS three-phase energy meters with the optional RS-485 Modbus output, per the 3-phase manual Rev E.
Also known as: RISH EM 3490 SS 3P, EM3490SS 3P, EM 3490 SS three-phase
All power & energy meters Modbus register maps →
Source: IFC 100 Supplementary instructions - Description of Modbus interface · 4001410101 R01 · rev. 2014-08. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.