- UFC 400 ultrasonic flow converter (Modbus RTU)
Sensor (ultrasonic flowmeter) · Modbus register map
KROHNE UFC 400 ultrasonic flow converter (Modbus RTU) Modbus register map
Updated 17 November 2026
The UFC 400 is KROHNE's signal converter for ultrasonic flowmeters. With the Modbus option it is an RS-485 Modbus RTU slave. This map covers flow velocity, volume and mass flow, sound velocity, gain and SNR (overall and per path), NAMUR NE 107 status bytes, the totalisers, process input parameters, serial settings and the control coils.
This page lists 89 Modbus registers for the KROHNE UFC 400 ultrasonic flow converter (Modbus RTU) — 49 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from KROHNE’s own free documentation (linked below) and checked against it.
- Manufacturer
- KROHNE
- Model
- UFC 400 ultrasonic flow converter (Modbus RTU)
- Equipment type
- Sensor (ultrasonic flowmeter)
- Registers
- 89 (49 writable)
- Transport
- Modbus RTU
- Default unit ID
- 1
- Default serial
- 19200 baud, 8E1
- Documented addressing
- 0-based (the number printed is the address on the wire)
- 32-bit word order
- ABCD high word first (big-endian)
- Firmware
- ER 2.2.0_ / Modbus 2.1.0_
- Also known as
- UFC400, KROHNE UFC 400, UFC 400 Modbus
Integration notes: KROHNE UFC 400 ultrasonic flow converter (Modbus RTU)
Read input registers 30000-30015 (function 04) for flow and acoustic values and 30500-30507 for their NE 107 status bytes. Totalisers are doubles at 32000/32004.
Minimum registers to map
Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.
| Register | Name | Type | Why | Access |
|---|---|---|---|---|
| IR 30002 | Volume flow | FLOAT32 ABCD | Volume flow | Read |
| IR 30000 | Flow velocity | FLOAT32 ABCD | Flow velocity | Read |
| IR 30006 | Velocity of sound | FLOAT32 ABCD | Velocity of sound | Read |
| IR 30501 | NE 107 status of volume flow | BITMAP16 | Volume flow status | Read |
| IR 32000 | Totaliser 1 value (double) | FLOAT64 ABCD | Totaliser 1 | Read |
| IR 39100 | NE 107 device status | BITMAP16 | Device status | Read |
Enable Modbus control & writes
Set slave address, baud rate, parity, data format, delay and stop bits in display menu C5.8.
Byte order & addressing
- Protocol addresses are sent as printed.
- Write holding registers with FC16, then apply with coil 1002.
- Pipe temperature is entered in kelvin.
Network setup
- Defaults: address 1, 19200 bps, even parity, 1 stop bit, Big Endian.
Watch out for
- Discrete input 10001 = 1 means written changes are still pending.
KROHNE UFC 400 ultrasonic flow converter (Modbus RTU) Modbus registers
Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.
| Table | Address | Name | Description | Type | Order | Scale | Units | Access | Values / bits |
|---|---|---|---|---|---|---|---|---|---|
| CO | 1000 | Restart device | Write 1 to restart the converter. | BIT | Write | ||||
| CO | 1001 | Reset errors | Clears the system error flags. | BIT | Write | ||||
| CO | 1002 | Apply changes | Write 1 to apply pending configuration changes. | BIT | Write | ||||
| CO | 1003 | Discard changes | Discard changes since the last apply. | BIT | Write | ||||
| CO | 1004 | Reset to factory data | BIT | Write | |||||
| CO | 2000 | Zero calibration start | Write 1 to start zero calibration. | BIT | Read/write | ||||
| CO | 3000 | Totaliser 1 start/stop | 0 = stop, 1 = start. | BIT | Read/write | ||||
| CO | 3001 | Totaliser 2 start/stop | 0 = stop, 1 = start. | BIT | Read/write | ||||
| CO | 3002 | Totaliser 3 start/stop (modular carrier only) | 0 = stop, 1 = start. | BIT | Read/write | ||||
| CO | 3003 | Totaliser 1 reset | Write 1 to set the totaliser to zero. | BIT | Write | ||||
| CO | 3004 | Totaliser 2 reset | Write 1 to set the totaliser to zero. | BIT | Write | ||||
| CO | 3005 | Totaliser 3 reset (modular carrier only) | Write 1 to set the totaliser to zero. | BIT | Write | ||||
| DI | 10001 | Unsaved changes pending | 1 = unapplied configuration changes exist. | BIT | Read | ||||
| IR | 20000 | Zero calibration result | UINT16 | Read | 0 = Not OK; 1 = OK | ||||
| IR | 30000 | Flow velocity | FLOAT32 | ABCD | m/s | Read | |||
| IR | 30002 | Volume flow | FLOAT32 | ABCD | m3/s | Read | |||
| IR | 30004 | Mass flow | FLOAT32 | ABCD | kg/s | Read | |||
| IR | 30006 | Velocity of sound | FLOAT32 | ABCD | m/s | Read | |||
| IR | 30008 | Gain | FLOAT32 | ABCD | dB | Read | |||
| IR | 30010 | Signal-to-noise ratio | FLOAT32 | ABCD | dB | Read | |||
| IR | 30012 | Diagnosis 1 | Value chosen by selector 41002. | FLOAT32 | ABCD | m/s | Read | ||
| IR | 30014 | Diagnosis 2 | Value chosen by selector 41003. | FLOAT32 | ABCD | dB | Read | ||
| IR | 30500 | NE 107 status of flow velocity | No bit set = no status message. | BITMAP16 | Read | bit 0 = Value too small, limited; bit 1 = Value too large, limited; bit 2 = Maintenance required (M); bit 3 = Initial value; bit 4 = Function check (C); bit 5 = Out of specification (S); bit 7 = Failure (F) | |||
| IR | 30501 | NE 107 status of volume flow | No bit set = no status message. | BITMAP16 | Read | bit 0 = Value too small, limited; bit 1 = Value too large, limited; bit 2 = Maintenance required (M); bit 3 = Initial value; bit 4 = Function check (C); bit 5 = Out of specification (S); bit 7 = Failure (F) | |||
| IR | 30502 | NE 107 status of mass flow | No bit set = no status message. | BITMAP16 | Read | bit 0 = Value too small, limited; bit 1 = Value too large, limited; bit 2 = Maintenance required (M); bit 3 = Initial value; bit 4 = Function check (C); bit 5 = Out of specification (S); bit 7 = Failure (F) | |||
| IR | 30503 | NE 107 status of velocity of sound | No bit set = no status message. | BITMAP16 | Read | bit 0 = Value too small, limited; bit 1 = Value too large, limited; bit 2 = Maintenance required (M); bit 3 = Initial value; bit 4 = Function check (C); bit 5 = Out of specification (S); bit 7 = Failure (F) | |||
| IR | 30504 | NE 107 status of gain | No bit set = no status message. | BITMAP16 | Read | bit 0 = Value too small, limited; bit 1 = Value too large, limited; bit 2 = Maintenance required (M); bit 3 = Initial value; bit 4 = Function check (C); bit 5 = Out of specification (S); bit 7 = Failure (F) | |||
| IR | 30505 | NE 107 status of signal-to-noise ratio | No bit set = no status message. | BITMAP16 | Read | bit 0 = Value too small, limited; bit 1 = Value too large, limited; bit 2 = Maintenance required (M); bit 3 = Initial value; bit 4 = Function check (C); bit 5 = Out of specification (S); bit 7 = Failure (F) | |||
| IR | 30506 | NE 107 status of diagnosis 1 | No bit set = no status message. | BITMAP16 | Read | bit 0 = Value too small, limited; bit 1 = Value too large, limited; bit 2 = Maintenance required (M); bit 3 = Initial value; bit 4 = Function check (C); bit 5 = Out of specification (S); bit 7 = Failure (F) | |||
| IR | 30507 | NE 107 status of diagnosis 2 | No bit set = no status message. | BITMAP16 | Read | bit 0 = Value too small, limited; bit 1 = Value too large, limited; bit 2 = Maintenance required (M); bit 3 = Initial value; bit 4 = Function check (C); bit 5 = Out of specification (S); bit 7 = Failure (F) | |||
| IR | 31000 | Velocity of sound path 1 | FLOAT32 | ABCD | m/s | Read | |||
| IR | 31002 | Velocity of sound path 2 | FLOAT32 | ABCD | m/s | Read | |||
| IR | 31004 | Velocity of sound path 3 | FLOAT32 | ABCD | m/s | Read | |||
| IR | 31006 | Flow speed path 1 | FLOAT32 | ABCD | m/s | Read | |||
| IR | 31008 | Flow speed path 2 | FLOAT32 | ABCD | m/s | Read | |||
| IR | 31010 | Flow speed path 3 | FLOAT32 | ABCD | m/s | Read | |||
| IR | 31012 | Gain path 1 | FLOAT32 | ABCD | dB | Read | |||
| IR | 31014 | Gain path 2 | FLOAT32 | ABCD | dB | Read | |||
| IR | 31016 | Gain path 3 | FLOAT32 | ABCD | dB | Read | |||
| IR | 31018 | SNR path 1 | FLOAT32 | ABCD | dB | Read | |||
| IR | 31020 | SNR path 2 | FLOAT32 | ABCD | dB | Read | |||
| IR | 31022 | SNR path 3 | FLOAT32 | ABCD | dB | Read | |||
| IR | 31024 | Reynolds number | FLOAT32 | ABCD | Read | ||||
| IR | 31026 | Reynolds correction | FLOAT32 | ABCD | Read | ||||
| IR | 32000 | Totaliser 1 value (double) | m3 or kg. | FLOAT64 | ABCD | Read | |||
| IR | 32004 | Totaliser 2 value (double) | m3 or kg. | FLOAT64 | ABCD | Read | |||
| IR | 32008 | Totaliser 3 value (double) (modular carrier only) | m3 or kg. | FLOAT64 | ABCD | Read | |||
| IR | 32100 | Totaliser 1 value (single) | m3 or kg. | FLOAT32 | ABCD | Read | |||
| IR | 32102 | Totaliser 2 value (single) | m3 or kg. | FLOAT32 | ABCD | Read | |||
| IR | 32104 | Totaliser 3 value (single) (modular carrier only) | m3 or kg. | FLOAT32 | ABCD | Read | |||
| IR | 39002 | Device operation time | FLOAT32 | ABCD | s | Read | |||
| IR | 39100 | NE 107 device status | BITMAP16 | Read | bit 0 = Information (I); bit 2 = Maintenance required (M); bit 4 = Function check (C); bit 5 = Out of specification (S); bit 7 = Failure (F) | ||||
| HR | 40000 | Totaliser 1 function | UINT16 | Read/write | 0 = Off; 1 = Absolute total; 2 = Increment; 3 = Decrement | ||||
| HR | 40001 | Totaliser 1 measurement | UINT16 | Read/write | 0 = Volume flow; 2 = Mass flow | ||||
| HR | 40002 | Totaliser 2 function | UINT16 | Read/write | 0 = Off; 1 = Absolute total; 2 = Increment; 3 = Decrement | ||||
| HR | 40003 | Totaliser 2 measurement | UINT16 | Read/write | 0 = Volume flow; 2 = Mass flow | ||||
| HR | 40004 | Totaliser 3 function (modular carrier only) | UINT16 | Read/write | 0 = Off; 1 = Absolute total; 2 = Increment; 3 = Decrement | ||||
| HR | 40005 | Totaliser 3 measurement (modular carrier only) | UINT16 | Read/write | 0 = Volume flow; 2 = Mass flow | ||||
| HR | 40500 | Totaliser 1 low flow cut-off | m3/s or kg/s. | FLOAT32 | ABCD | Read/write | |||
| HR | 40502 | Totaliser 1 time constant | 0-100 s. | FLOAT32 | ABCD | s | Read/write | ||
| HR | 40504 | Totaliser 1 set or read value | m3 or kg. | FLOAT32 | ABCD | Read/write | |||
| HR | 40506 | Totaliser 1 preset | m3 or kg. | FLOAT32 | ABCD | Read/write | |||
| HR | 40508 | Totaliser 2 low flow cut-off | m3/s or kg/s. | FLOAT32 | ABCD | Read/write | |||
| HR | 40510 | Totaliser 2 time constant | 0-100 s. | FLOAT32 | ABCD | s | Read/write | ||
| HR | 40512 | Totaliser 2 set or read value | m3 or kg. | FLOAT32 | ABCD | Read/write | |||
| HR | 40514 | Totaliser 2 preset | m3 or kg. | FLOAT32 | ABCD | Read/write | |||
| HR | 40516 | Totaliser 3 low flow cut-off (modular carrier only) | m3/s or kg/s. | FLOAT32 | ABCD | Read/write | |||
| HR | 40518 | Totaliser 3 time constant (modular carrier only) | 0-100 s. | FLOAT32 | ABCD | s | Read/write | ||
| HR | 40520 | Totaliser 3 set or read value (modular carrier only) | m3 or kg. | FLOAT32 | ABCD | Read/write | |||
| HR | 40522 | Totaliser 3 preset (modular carrier only) | m3 or kg. | FLOAT32 | ABCD | Read/write | |||
| HR | 41000 | Flow direction | UINT16 | Read/write | 0 = Normal; 1 = Reverse | ||||
| HR | 41001 | Linearization | UINT16 | Read/write | 0 = Off; 1 = On | ||||
| HR | 41004 | Plausibility counter decrease | 1-99. | UINT16 | Read/write | ||||
| HR | 41005 | Plausibility counter limit | 0-999. | UINT16 | Read/write | ||||
| HR | 41502 | GK | FLOAT32 | ABCD | Read/write | ||||
| HR | 41504 | Limitation min | FLOAT32 | ABCD | m/s | Read/write | |||
| HR | 41506 | Limitation max | FLOAT32 | ABCD | m/s | Read/write | |||
| HR | 41508 | Time constant | FLOAT32 | ABCD | s | Read/write | |||
| HR | 41510 | Low flow cut-off threshold | FLOAT32 | ABCD | m/s | Read/write | |||
| HR | 41512 | Low flow cut-off hysteresis | FLOAT32 | ABCD | m/s | Read/write | |||
| HR | 41514 | Plausibility error limit | FLOAT32 | ABCD | % | Read/write | |||
| HR | 41516 | Dynamic viscosity | FLOAT32 | ABCD | kg/ms | Read/write | |||
| HR | 41518 | Pipe temperature | FLOAT32 | ABCD | K | Read/write | |||
| HR | 41520 | Density | FLOAT32 | ABCD | kg/m3 | Read/write | |||
| HR | 50000 | Baud rate | 1200-115200; default 19200. | UINT32 | ABCD | bps | Read/write | ||
| HR | 50004 | Slave address | 1-247, default 1. | UINT16 | Read/write | ||||
| HR | 50005 | Parity | UINT16 | Read/write | 0 = Even (default); 1 = Odd; 3 = Off | ||||
| HR | 50006 | Register format | UINT16 | Read/write | 0 = Little endian; 1 = Big endian (default) | ||||
| HR | 50007 | Stop bits | UINT16 | Read/write | 1 = 1 stop bit (default); 2 = 2 stop bits |
Notes on this map
- This is an unaltered copy of the KROHNE document hosted by distributor Instrumart; no public KROHNE URL for this revision was found in the time available.
- Data representation (pp. 9-10): 16-bit values are MSB first; 32- and 64-bit values follow the 'Register Format' setting (holding 50006). Big Endian, the default, puts the most significant word in the first register (ABCD); the manual's Little Endian diagram keeps bytes in order inside each register but reverses the registers (CDAB).
- Holding registers are written with function 16 (0x10). Configuration changes take effect only after 'Apply Changes' (coil 1002).
- Totaliser 3 registers are footnoted in the manual as available only on signal converters with the 'modular carrier'.
- Left out: NE 107 status groups (39004, Long), diagnostics selectors 41002/41003 (long code lists), NE 107 event-group signal registers 52000+, and device identification via function 43.
- Byte-type parameters each occupy one register and are listed as UINT16.
- Left out: transmission delay 50002 (Float), because the table gives its unit as ms while the range is printed as 0...0.04.
Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.
Questions about the KROHNE UFC 400 ultrasonic flow converter (Modbus RTU)
What Modbus registers does the KROHNE UFC 400 ultrasonic flow converter (Modbus RTU) have?
This map lists 89 registers: 12 coils, 1 discrete input, 39 input registers, 37 holding registers. 49 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.
Are the KROHNE UFC 400 ultrasonic flow converter (Modbus RTU) Modbus addresses 0-based or 1-based?
The manufacturer's document numbers registers 0-based (the number printed is the address on the wire). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. The manual lists protocol addresses that go into the request unchanged: input register 30006 is requested as 30006 (0x7536); each row also prints the hex value. Register numbers, if a tool wants them, are the address + 1.
What byte order does the KROHNE UFC 400 ultrasonic flow converter (Modbus RTU) use for 32-bit values?
Multi-register values in this map use ABCD (high word first (big-endian)). Set your client to this order for every 32/64-bit value in the table.
What are the minimum Modbus registers to integrate the KROHNE UFC 400 ultrasonic flow converter (Modbus RTU)?
Start with IR 30002 Volume flow (Volume flow); IR 30000 Flow velocity (Flow velocity); IR 30006 Velocity of sound (Velocity of sound); IR 30501 NE 107 status of volume flow (Volume flow status); IR 32000 Totaliser 1 value (double) (Totaliser 1); IR 39100 NE 107 device status (Device status).
How do I enable Modbus control of the KROHNE UFC 400 ultrasonic flow converter (Modbus RTU)?
Set slave address, baud rate, parity, data format, delay and stop bits in display menu C5.8.
Where is the official KROHNE UFC 400 ultrasonic flow converter (Modbus RTU) Modbus documentation?
The source is UFC 400 Supplementary instructions - Signal converter for ultrasonic flowmeters - Description of Modbus interface (4002744801 R01), revision 2013-05. KROHNE doesn't publish it on its own website, so this map was re-typed from a free copy at https://core.instrumart.com/assets/Krohne-UFC-400-Modbus-Manual.pdf. It may be an older revision, so check it against the live unit.
More KROHNE Modbus register maps
- Sensor (battery-powered electromagnetic water flowmeter)
KROHNE IFC 070 signal converter (Modbus)
IFC 070 electronic revision 5.1.0, Modbus version 1.1.1 (battery) and 1.1.0 (FlexPower), per AD IFC 070 Modbus R02.
Also known as: WATERFLUX 3070, IFC070, IFC 070 FlexPower - Sensor (electromagnetic flowmeter)
KROHNE IFC 100 electromagnetic flow converter (Modbus RTU)
IFC 100 signal converter with the Modbus option, supplementary instructions 4001410101 R01 (08/2014).
Also known as: IFC100, IFC 100 Modbus, KROHNE IFC 100 - Sensor (Coriolis mass flowmeter)
KROHNE MFC 300 Coriolis mass flow converter (Modbus RTU)
MFC 300 converter with the Modbus option, supplementary instructions 4000744801 R01 (11/2009).
Also known as: MFC300, KROHNE MFC 300
Other power & energy meters register maps
- Power meter (panel network parameter meter)
Lumel ND20LITE network parameter meter
Lumel ND20LITE 96x96 panel meter with RS-485 Modbus RTU (not the ND20 or ND20CT, which have their own maps).
Also known as: ND20LITE - Energy meter
Measurlogic DTS family energy sub-meters (DTS 101/105/305/310/SMX/SKT/DC)
Measurlogic DTS AC and DC sub-meters and transducers with Modbus RTU or Modbus TCP, per DTS Modbus Map version 2.7U (Oct 2012). Registers depend on model and wiring.
Also known as: DTS 101, DTS 105, DTS 305, DTS 310, DTS SMX, DTS SKT, DTS DC - Energy meter
Panasonic KW7M Eco-POWER METER
Panasonic KW7M (AKW7111 / AKW7111B) with Modbus RTU selected, user manual ARCT1F434E-6.
Also known as: AKW7111, AKW7111B - Sensor (counter / rate panel meter)
Red Lion PAXI counter / rate panel meter (Modbus)
PAXI counter/rate meters with a Modbus serial card, per register table LP0897A (revised 7/10/12).
Also known as: PAXI, PAX I, Red Lion PAXI counter - Energy meter
Rishabh Instruments RISH ED11XX / EC11XX / ER11XX single-phase DIN-rail energy meters
Rishabh RISH ED11XX (direct), EC11XX (CT) and ER11XX (RJ12 CT) single-phase DIN-rail meters in their Modbus (x1) versions, per operating manual DMAN-00IM-1071 Rev. M.
Also known as: RISH ED11X1, RISH EC11X1, RISH ER11X1, ED1111, EC1111, ER1111, RISH ED11XX, RISH EC11XX, RISH ER11XX - Energy meter (DC)
Rishabh Instruments RISH EM DC 6001 / 6002 multi-channel DC energy meter
Rishabh RISH EM DC 6001 / 6002 multi-channel DC energy meters with RS-485 Modbus, per interface definition 2-60-006-00-00627 Rev. 0 (10/2015).
Also known as: RISH EM DC 6001, RISH EM DC 6002, EM DC 6001, EM DC 6002
All power & energy meters Modbus register maps →
Source: UFC 400 Supplementary instructions - Signal converter for ultrasonic flowmeters - Description of Modbus interface · 4002744801 R01 · rev. 2013-05 · unofficial copy. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.