Energy meter · Modbus register map
Measurlogic DTS family energy sub-meters (DTS 101/105/305/310/SMX/SKT/DC) Modbus register map
Updated 17 November 2026
The DTS family are compact DIN-rail, panel and socket energy sub-meters and transducers for single-phase, three-phase and DC circuits. Every value is a signed 32-bit integer in two holding registers, low word first. This map covers voltages, currents, frequency, power, power factor, unbalance, nett and split energy counters, identity and CT/PT ratio registers, and the RS-485 settings.
This page lists 78 Modbus registers for the Measurlogic DTS family energy sub-meters (DTS 101/105/305/310/SMX/SKT/DC) — 8 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Measurlogic’s own free documentation (linked below) and checked against it.
- Manufacturer
- Measurlogic
- Model
- DTS family energy sub-meters (DTS 101/105/305/310/SMX/SKT/DC)
- Equipment type
- Energy meter
- Registers
- 78 (8 writable)
- Transport
- Modbus RTU, Modbus TCP
- Default unit ID
- 100
- Documented addressing
- 1-based (subtract 1 for the wire address)
- 32-bit word order
- CDAB low word first (word-swapped)
- Also known as
- DTS 101, DTS 105, DTS 305, DTS 310, DTS SMX, DTS SKT, DTS DC
Integration notes: Measurlogic DTS family energy sub-meters (DTS 101/105/305/310/SMX/SKT/DC)
Read holding registers in CDAB 32-bit pairs at address 100 (default). Read EnerPowDivider (16045) first and scale power and energy with raw x divider x 0.001.
Minimum registers to map
Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.
| Register | Name | Type | Why | Access |
|---|---|---|---|---|
| HR 11000 | Voltage_LN_1 | INT32 CDAB | Voltage L1-N | Read |
| HR 11024 | Current_1 | INT32 CDAB | Current 1 | Read |
| HR 11054 | PowerP_Total | INT32 CDAB | Total active power (raw) | Read |
| HR 14006 | EnergyP_Total | INT32 CDAB | Total nett active energy (raw) | Read |
| HR 16044 | EnerPowDivider | INT32 CDAB | EnerPowDivider | Read/write |
Enable Modbus control & writes
Modbus is built in (RS-485 RTU or Ethernet TCP depending on model). Communication parameters and address are normally set with Measurlogic's DTSConfig software.
Byte order & addressing
- Every value is 32-bit signed, low word first (CDAB).
- Published addresses are 1-based.
- Power/energy resolution depends on EnerPowDivider.
Network setup
- Default slave address 100.
- RS-485 baud rate 9600 or 19200; change it with DTSConfig rather than by writing registers.
- Do not change the RS-485 registers on Ethernet models.
Watch out for
- Writing wrong values to 16119-16123 can make the meter unreachable.
- Not every register is used on every model or wiring; only connected channels and the Total/Average registers carry valid data.
Measurlogic DTS family energy sub-meters (DTS 101/105/305/310/SMX/SKT/DC) Modbus registers
Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.
| Table | Address | Name | Description | Type | Order | Scale | Units | Access | Values / bits |
|---|---|---|---|---|---|---|---|---|---|
| HR | 10002doc 10003 | DTS_SerialNumber | INT32 | CDAB | Read | ||||
| HR | 10008doc 10009 | DTS_FW_Version | INT32 | CDAB | × 0.0001 | Read | |||
| HR | 10014doc 10015 | DTS_Model_ID | INT32 | CDAB | Read | ||||
| HR | 11000doc 11001 | Voltage_LN_1 | On DTS DC meters 11001 is Voltage_DC. | INT32 | CDAB | × 0.1 | V | Read | |
| HR | 11002doc 11003 | Voltage_LN_2 | INT32 | CDAB | × 0.1 | V | Read | ||
| HR | 11004doc 11005 | Voltage_LN_3 | INT32 | CDAB | × 0.1 | V | Read | ||
| HR | 11006doc 11007 | Voltage_LN_Average | INT32 | CDAB | × 0.1 | V | Read | ||
| HR | 11008doc 11009 | Voltage_LL_12 | INT32 | CDAB | × 0.1 | V | Read | ||
| HR | 11010doc 11011 | Voltage_LL_23 | INT32 | CDAB | × 0.1 | V | Read | ||
| HR | 11012doc 11013 | Voltage_LL_31 | INT32 | CDAB | × 0.1 | V | Read | ||
| HR | 11014doc 11015 | Voltage_LL_Average | INT32 | CDAB | × 0.1 | V | Read | ||
| HR | 11024doc 11025 | Current_1 | On DTS DC meters 11025 is Current_DC. | INT32 | CDAB | × 0.001 | A | Read | |
| HR | 11026doc 11027 | Current_2 | INT32 | CDAB | × 0.001 | A | Read | ||
| HR | 11028doc 11029 | Current_3 | INT32 | CDAB | × 0.001 | A | Read | ||
| HR | 11030doc 11031 | Current_Average | INT32 | CDAB | × 0.001 | A | Read | ||
| HR | 11032doc 11033 | Current_Total | INT32 | CDAB | × 0.001 | A | Read | ||
| HR | 11034doc 11035 | Current_Neutral | INT32 | CDAB | × 0.001 | A | Read | ||
| HR | 11040doc 11041 | Frequency_1 | INT32 | CDAB | × 0.01 | Hz | Read | ||
| HR | 11042doc 11043 | Frequency_2 | INT32 | CDAB | × 0.01 | Hz | Read | ||
| HR | 11044doc 11045 | Frequency_3 | INT32 | CDAB | × 0.01 | Hz | Read | ||
| HR | 11046doc 11047 | Frequency_Average | INT32 | CDAB | × 0.01 | Hz | Read | ||
| HR | 11048doc 11049 | PowerP_1 | Raw; multiply by EnerPowDivider (16045) x 0.001 to get W (11049 is Power_DC on DC meters). | INT32 | CDAB | Read | |||
| HR | 11050doc 11051 | PowerP_2 | Raw; multiply by EnerPowDivider (16045) x 0.001 to get W. | INT32 | CDAB | Read | |||
| HR | 11052doc 11053 | PowerP_3 | Raw; multiply by EnerPowDivider (16045) x 0.001 to get W. | INT32 | CDAB | Read | |||
| HR | 11054doc 11055 | PowerP_Total | Raw; multiply by EnerPowDivider (16045) x 0.001 to get W. | INT32 | CDAB | Read | |||
| HR | 11056doc 11057 | PowerS_1 | Raw; multiply by EnerPowDivider (16045) x 0.001 to get VA. | INT32 | CDAB | Read | |||
| HR | 11058doc 11059 | PowerS_2 | Raw; multiply by EnerPowDivider (16045) x 0.001 to get VA. | INT32 | CDAB | Read | |||
| HR | 11060doc 11061 | PowerS_3 | Raw; multiply by EnerPowDivider (16045) x 0.001 to get VA. | INT32 | CDAB | Read | |||
| HR | 11062doc 11063 | PowerS_Total | Raw; multiply by EnerPowDivider (16045) x 0.001 to get VA. | INT32 | CDAB | Read | |||
| HR | 11064doc 11065 | PowerQ_1 | Raw; multiply by EnerPowDivider (16045) x 0.001 to get var. | INT32 | CDAB | Read | |||
| HR | 11066doc 11067 | PowerQ_2 | Raw; multiply by EnerPowDivider (16045) x 0.001 to get var. | INT32 | CDAB | Read | |||
| HR | 11068doc 11069 | PowerQ_3 | Raw; multiply by EnerPowDivider (16045) x 0.001 to get var. | INT32 | CDAB | Read | |||
| HR | 11070doc 11071 | PowerQ_Total | Raw; multiply by EnerPowDivider (16045) x 0.001 to get var. | INT32 | CDAB | Read | |||
| HR | 11124doc 11125 | ACosPF_1 | Power factor angle. | INT32 | CDAB | × 0.1 | ° | Read | |
| HR | 11126doc 11127 | ACosPF_2 | Power factor angle. | INT32 | CDAB | × 0.1 | ° | Read | |
| HR | 11128doc 11129 | ACosPF_3 | Power factor angle. | INT32 | CDAB | × 0.1 | ° | Read | |
| HR | 11130doc 11131 | ACosPF_Overall | Power factor angle. | INT32 | CDAB | × 0.1 | ° | Read | |
| HR | 11140doc 11141 | Voltage_Unbalance_LN_1 | INT32 | CDAB | × 0.01 | % | Read | ||
| HR | 11142doc 11143 | Voltage_Unbalance_LN_2 | INT32 | CDAB | × 0.01 | % | Read | ||
| HR | 11144doc 11145 | Voltage_Unbalance_LN_3 | INT32 | CDAB | × 0.01 | % | Read | ||
| HR | 11146doc 11147 | Voltage_Unbalance_LN_Worst | INT32 | CDAB | × 0.01 | % | Read | ||
| HR | 11148doc 11149 | Voltage_Unbalance_LL_12 | INT32 | CDAB | × 0.01 | % | Read | ||
| HR | 11150doc 11151 | Voltage_Unbalance_LL_23 | INT32 | CDAB | × 0.01 | % | Read | ||
| HR | 11152doc 11153 | Voltage_Unbalance_LL_31 | INT32 | CDAB | × 0.01 | % | Read | ||
| HR | 11154doc 11155 | Voltage_Unbalance_LL_Worst | INT32 | CDAB | × 0.01 | % | Read | ||
| HR | 11156doc 11157 | Current_Unbalance_1 | INT32 | CDAB | × 0.01 | % | Read | ||
| HR | 11158doc 11159 | Current_Unbalance_2 | INT32 | CDAB | × 0.01 | % | Read | ||
| HR | 11160doc 11161 | Current_Unbalance_3 | INT32 | CDAB | × 0.01 | % | Read | ||
| HR | 11162doc 11163 | Current_Unbalance_Worst | INT32 | CDAB | × 0.01 | % | Read | ||
| HR | 11256doc 11257 | DemandP_Total | Raw; multiply by EnerPowDivider (16045) x 0.001 to get W. | INT32 | CDAB | Read | |||
| HR | 14000doc 14001 | EnergyP_1 | Raw; multiply by EnerPowDivider (16045) x 0.001 to get Wh; nett counters are signed (export negative). | INT32 | CDAB | Read | |||
| HR | 14002doc 14003 | EnergyP_2 | Raw; multiply by EnerPowDivider (16045) x 0.001 to get Wh; nett counters are signed (export negative). | INT32 | CDAB | Read | |||
| HR | 14004doc 14005 | EnergyP_3 | Raw; multiply by EnerPowDivider (16045) x 0.001 to get Wh; nett counters are signed (export negative). | INT32 | CDAB | Read | |||
| HR | 14006doc 14007 | EnergyP_Total | Raw; multiply by EnerPowDivider (16045) x 0.001 to get Wh; nett counters are signed (export negative). | INT32 | CDAB | Read | |||
| HR | 14008doc 14009 | EnergyS_1 | Raw; multiply by EnerPowDivider (16045) x 0.001 to get VAh; nett counters are signed (export negative). | INT32 | CDAB | Read | |||
| HR | 14010doc 14011 | EnergyS_2 | Raw; multiply by EnerPowDivider (16045) x 0.001 to get VAh; nett counters are signed (export negative). | INT32 | CDAB | Read | |||
| HR | 14012doc 14013 | EnergyS_3 | Raw; multiply by EnerPowDivider (16045) x 0.001 to get VAh; nett counters are signed (export negative). | INT32 | CDAB | Read | |||
| HR | 14014doc 14015 | EnergyS_Total | Raw; multiply by EnerPowDivider (16045) x 0.001 to get VAh; nett counters are signed (export negative). | INT32 | CDAB | Read | |||
| HR | 14016doc 14017 | EnergyQ_1 | Raw; multiply by EnerPowDivider (16045) x 0.001 to get varh; nett counters are signed (export negative). | INT32 | CDAB | Read | |||
| HR | 14018doc 14019 | EnergyQ_2 | Raw; multiply by EnerPowDivider (16045) x 0.001 to get varh; nett counters are signed (export negative). | INT32 | CDAB | Read | |||
| HR | 14020doc 14021 | EnergyQ_3 | Raw; multiply by EnerPowDivider (16045) x 0.001 to get varh; nett counters are signed (export negative). | INT32 | CDAB | Read | |||
| HR | 14022doc 14023 | EnergyQ_Total | Raw; multiply by EnerPowDivider (16045) x 0.001 to get varh; nett counters are signed (export negative). | INT32 | CDAB | Read | |||
| HR | 14024doc 14025 | EnergyP_Total_Imp | Raw; multiply by EnerPowDivider (16045) x 0.001 to get Wh. | INT32 | CDAB | Read | |||
| HR | 14026doc 14027 | EnergyP_Total_Exp | Raw; multiply by EnerPowDivider (16045) x 0.001 to get Wh. | INT32 | CDAB | Read | |||
| HR | 14028doc 14029 | EnergyQ_Total_Imp | Raw; multiply by EnerPowDivider (16045) x 0.001 to get varh. | INT32 | CDAB | Read | |||
| HR | 14030doc 14031 | EnergyQ_Total_Exp | Raw; multiply by EnerPowDivider (16045) x 0.001 to get varh. | INT32 | CDAB | Read | |||
| HR | 14080doc 14081 | GeneralCounter1 | General input pulse counter. | INT32 | CDAB | Read | |||
| HR | 14082doc 14083 | GeneralCounter2 | General input pulse counter. | INT32 | CDAB | Read | |||
| HR | 14084doc 14085 | GeneralCounter3 | General input pulse counter. | INT32 | CDAB | Read | |||
| HR | 14086doc 14087 | GeneralCounter4 | General input pulse counter. | INT32 | CDAB | Read | |||
| HR | 16000doc 16001 | VoltagePrimary | PT primary. | INT32 | CDAB | × 0.1 | V | Read/write | |
| HR | 16002doc 16003 | VoltageSecondary | PT secondary. | INT32 | CDAB | × 0.1 | V | Read/write | |
| HR | 16008doc 16009 | CurrentPrimary | CT primary. | INT32 | CDAB | × 0.001 | A | Read/write | |
| HR | 16010doc 16011 | CurrentSecondary | CT secondary. | INT32 | CDAB | × 0.001 | A | Read/write | |
| HR | 16044doc 16045 | EnerPowDivider | Power/energy resolution divider; default 100 = 0.1 W. | INT32 | CDAB | Read/write | |||
| HR | 16118doc 16119 | Rem_Baudrate | RS-485 baud rate (9600 or 19200). | INT32 | CDAB | Read/write | |||
| HR | 16120doc 16121 | Rem_Parity/DataBits/StopBits | Packed bytes: parity (0 none, 1 odd, 2 even), data bits, stop bits, reserved. | INT32 | CDAB | Read/write | |||
| HR | 16122doc 16123 | Rem_Address | RS-485 slave address 1-247. | INT32 | CDAB | Read/write |
Notes on this map
- Measurlogic does not host this map publicly that we could find; this copy is on a distributor's document CDN and is the unaltered Measurlogic document (Measurlogic header and footer on every page).
- All registers are signed 32-bit values with the LO register at the listed address and the HI register next (CDAB).
- Power, demand and energy registers have a variable resolution: engineering value in W / VA / var / Wh = raw x EnerPowDivider (register 16045) x 0.001. Their scale is therefore left at 1 and units blank; read 16045 once and apply the formula.
- Energy registers roll over after 999,999,999 counts.
- Min/max registers (116xx / 122xx), single-cycle currents, I/O channel status/coils (15301+), the output command register 40001 and the SunSpec map at 50001 are left out.
- Default Modbus address is 100 (on Modbus TCP it is always 100).
- Power factor registers (11100-11107) are left out: the manual marks their format 'Special' without defining it.
Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.
Questions about the Measurlogic DTS family energy sub-meters (DTS 101/105/305/310/SMX/SKT/DC)
What Modbus registers does the Measurlogic DTS family energy sub-meters (DTS 101/105/305/310/SMX/SKT/DC) have?
This map lists 78 registers: 78 holding registers. 8 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.
Are the Measurlogic DTS family energy sub-meters (DTS 101/105/305/310/SMX/SKT/DC) Modbus addresses 0-based or 1-based?
The manufacturer's document numbers registers 1-based (subtract 1 for the wire address). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. Section 2.1.1 says the published addresses are 1-based in the 4x region; subtract 1 for the wire address (Voltage_LN_1 11001 -> 11000). Some masters want the 4 prefix (411001).
What byte order does the Measurlogic DTS family energy sub-meters (DTS 101/105/305/310/SMX/SKT/DC) use for 32-bit values?
Multi-register values in this map use CDAB (low word first (word-swapped)). Set your client to this order for every 32/64-bit value in the table.
What are the minimum Modbus registers to integrate the Measurlogic DTS family energy sub-meters (DTS 101/105/305/310/SMX/SKT/DC)?
Start with HR 11000 Voltage_LN_1 (Voltage L1-N); HR 11024 Current_1 (Current 1); HR 11054 PowerP_Total (Total active power (raw)); HR 14006 EnergyP_Total (Total nett active energy (raw)); HR 16044 EnerPowDivider (EnerPowDivider).
How do I enable Modbus control of the Measurlogic DTS family energy sub-meters (DTS 101/105/305/310/SMX/SKT/DC)?
Modbus is built in (RS-485 RTU or Ethernet TCP depending on model). Communication parameters and address are normally set with Measurlogic's DTSConfig software.
Where is the official Measurlogic DTS family energy sub-meters (DTS 101/105/305/310/SMX/SKT/DC) Modbus documentation?
The source is DTS Modbus Map (Version 2.7U), revision 2012-10-17. Measurlogic doesn't publish it on its own website, so this map was re-typed from a free copy at https://cdn.logic-control.com/docs/measurlogic/Measurlogic%20DTS%20Modbus%20Map%20V2.7U.pdf. It may be an older revision, so check it against the live unit.
Other power & energy meters register maps
- Energy meter
Panasonic KW7M Eco-POWER METER
Panasonic KW7M (AKW7111 / AKW7111B) with Modbus RTU selected, user manual ARCT1F434E-6.
Also known as: AKW7111, AKW7111B - Sensor (counter / rate panel meter)
Red Lion PAXI counter / rate panel meter (Modbus)
PAXI counter/rate meters with a Modbus serial card, per register table LP0897A (revised 7/10/12).
Also known as: PAXI, PAX I, Red Lion PAXI counter - Energy meter
Rishabh Instruments RISH ED11XX / EC11XX / ER11XX single-phase DIN-rail energy meters
Rishabh RISH ED11XX (direct), EC11XX (CT) and ER11XX (RJ12 CT) single-phase DIN-rail meters in their Modbus (x1) versions, per operating manual DMAN-00IM-1071 Rev. M.
Also known as: RISH ED11X1, RISH EC11X1, RISH ER11X1, ED1111, EC1111, ER1111, RISH ED11XX, RISH EC11XX, RISH ER11XX - Energy meter (DC)
Rishabh Instruments RISH EM DC 6001 / 6002 multi-channel DC energy meter
Rishabh RISH EM DC 6001 / 6002 multi-channel DC energy meters with RS-485 Modbus, per interface definition 2-60-006-00-00627 Rev. 0 (10/2015).
Also known as: RISH EM DC 6001, RISH EM DC 6002, EM DC 6001, EM DC 6002 - Power meter (multi-circuit energy meter)
Rishabh Instruments RISH ML 1400 / ML 1410 Multiload Monitor (Modbus RTU)
RISH Multiload Monitor (12 current channels, 4 voltage channels) per interface definition DMAN-00IM-0795 Rev A (08/2020).
Also known as: RISH ML 1400, RISH ML 1410, RISH MLM, Multiload Monitor - Power meter (power quality analyzer)
SATEC PM174 powermeter and power quality analyzer
SATEC PM174 from firmware 24.3.1, per Modbus reference guide BG0414 Rev. A7 (April 2013).
Also known as: PM174, SATEC PM174, PM 174
All power & energy meters Modbus register maps →
Source: DTS Modbus Map · Version 2.7U · rev. 2012-10-17 · unofficial copy. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.