Energy meter · Modbus register map

Panasonic KW7M Eco-POWER METER Modbus register map

Updated 17 November 2026

Short answer

The KW7M is a small DIN-rail energy meter for single-phase or three-phase three-wire circuits using dedicated or 5 A CTs, with an RS485 port that speaks MEWTOCOL or Modbus RTU. Its Modbus table is short: two phase currents, two line voltages, active power and the metering and alarm settings, all as holding registers.

This page lists 15 Modbus registers for the Panasonic KW7M Eco-POWER METER — 10 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Panasonic’s own free documentation (linked below) and checked against it.

Manufacturer
Panasonic
Model
KW7M Eco-POWER METER
Equipment type
Energy meter
Registers
15 (10 writable)
Transport
Modbus RTU
Default unit ID
1
Default serial
19200 baud, 8O1
Documented addressing
hexadecimal, 0-based
32-bit word order
CDAB low word first (word-swapped)
Also known as
AKW7111, AKW7111B
Source document
KW7M Eco-POWER METER User's Manual · ARCT1F434E-6 · rev. 2016-06
Download CSV all columns JSON Manufacturer PDF ↗

Integration notes: Panasonic KW7M Eco-POWER METER

Integration in brief

Select MODBUS(RTU) in Mode 2 on the front panel, then poll 00B0H (kW x0.01), 006BH/006DH (A x0.1) and 00AAH/00ACH (V x0.1) with function 03. 32-bit values are low word first.

Minimum registers to map

Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.

RegisterNameTypeWhyAccess
HR 176Instantaneous active powerUINT32 CDABInstantaneous active powerRead
HR 107L1 (CT1) phase currentUINT16L1 currentRead
HR 109L2 (CT2) phase currentUINT16L2 currentRead
HR 170Voltage between 1 and 2UINT32 CDABVoltage 1-2Read
HR 172Voltage between 2 and 3UINT32 CDABVoltage 2-3Read

Enable Modbus control & writes

Protocol defaults to MEWTOCOL. In Mode 2 change Protocol to MODBUS(RTU), then set station number, speed, format and response time.

Byte order & addressing

Network setup

Watch out for

Panasonic KW7M Eco-POWER METER Modbus registers

Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.

15 of 15 shown
Panasonic KW7M Eco-POWER METER Modbus register map
TableAddressNameDescriptionTypeOrderScaleUnitsAccessValues / bits
HR50doc 0032HRateElectricity rate per kWh used for the charge display.UINT16× 0.01Read/write
HR60doc 003CHCT typeDedicated CT rating: 5, 50, 100, 250 or 400.UINT16ARead/write
HR61doc 003DHUnit for pulse outputUINT32CDABRead/write1 = 0.001 kWh; 10 = 0.01 kWh; 100 = 0.1 kWh; 333 = Stand-by alarm output (uses 004DH/004EH); 777 = Current alarm output (uses ratio 0045H); 999 = Power alarm output (uses alarm value 0040H); 1000 = 1 kWh; 10000 = 10 kWh; 100000 = 100 kWh
HR63doc 003FHCT primary current (5 A CT)Used with a commercial 5 A secondary CT, 1-4000.UINT16ARead/write
HR64doc 0040HAlarm value (instantaneous power)UINT32CDAB× 0.01kWRead/write
HR66doc 0042HVT ratioUINT16× 0.01Read/write
HR68doc 0044HCut-off currentUINT16× 0.1%Read/write
HR69doc 0045HRatio for current alarmUINT16× 0.1%Read/write
HR77doc 004DHRatio for stand-by currentUINT16× 0.1%Read/write
HR78doc 004EHTime for stand-by alarmUINT16minRead/write
HR107doc 006BHL1 (CT1) phase currentUINT16× 0.1ARead
HR109doc 006DHL2 (CT2) phase currentUINT16× 0.1ARead
HR170doc 00AAHVoltage between 1 and 2UINT32CDAB× 0.1VRead
HR172doc 00ACHVoltage between 2 and 3UINT32CDAB× 0.1VRead
HR176doc 00B0HInstantaneous active powerUINT32CDAB× 0.01kWRead

Notes on this map

Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.

Questions about the Panasonic KW7M Eco-POWER METER

What Modbus registers does the Panasonic KW7M Eco-POWER METER have?

This map lists 15 registers: 15 holding registers. 10 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.

Are the Panasonic KW7M Eco-POWER METER Modbus addresses 0-based or 1-based?

The manufacturer's document numbers registers hexadecimal, 0-based. Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. Addresses are printed in hex (0064H) and go into the request unchanged; the manual's Modbus example resets energy by writing 2 words at data item 0064H. The MEWTOCOL DT number in decimal equals the hex Modbus address.

What byte order does the Panasonic KW7M Eco-POWER METER use for 32-bit values?

Multi-register values in this map use CDAB (low word first (word-swapped)). Set your client to this order for every 32/64-bit value in the table.

What are the minimum Modbus registers to integrate the Panasonic KW7M Eco-POWER METER?

Start with HR 176 Instantaneous active power (Instantaneous active power); HR 107 L1 (CT1) phase current (L1 current); HR 109 L2 (CT2) phase current (L2 current); HR 170 Voltage between 1 and 2 (Voltage 1-2); HR 172 Voltage between 2 and 3 (Voltage 2-3).

How do I enable Modbus control of the Panasonic KW7M Eco-POWER METER?

Protocol defaults to MEWTOCOL. In Mode 2 change Protocol to MODBUS(RTU), then set station number, speed, format and response time.

Where is the official Panasonic KW7M Eco-POWER METER Modbus documentation?

The source is KW7M Eco-POWER METER User's Manual (ARCT1F434E-6), revision 2016-06, published free by Panasonic at https://mediap.industry.panasonic.eu/assets/custom-upload/Factory%20%26%20Automation/Eco-POWER%20METERS/Manuals/mn_kw7m_user_pidsx_en.pdf.

More Panasonic Modbus register maps

Other power & energy meters register maps

All power & energy meters Modbus register maps →

Source: KW7M Eco-POWER METER User's Manual · ARCT1F434E-6 · rev. 2016-06. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.