- KW7M Eco-POWER METER
Energy meter · Modbus register map
Panasonic KW7M Eco-POWER METER Modbus register map
Updated 17 November 2026
The KW7M is a small DIN-rail energy meter for single-phase or three-phase three-wire circuits using dedicated or 5 A CTs, with an RS485 port that speaks MEWTOCOL or Modbus RTU. Its Modbus table is short: two phase currents, two line voltages, active power and the metering and alarm settings, all as holding registers.
This page lists 15 Modbus registers for the Panasonic KW7M Eco-POWER METER — 10 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Panasonic’s own free documentation (linked below) and checked against it.
- Manufacturer
- Panasonic
- Model
- KW7M Eco-POWER METER
- Equipment type
- Energy meter
- Registers
- 15 (10 writable)
- Transport
- Modbus RTU
- Default unit ID
- 1
- Default serial
- 19200 baud, 8O1
- Documented addressing
- hexadecimal, 0-based
- 32-bit word order
- CDAB low word first (word-swapped)
- Also known as
- AKW7111, AKW7111B
Integration notes: Panasonic KW7M Eco-POWER METER
Select MODBUS(RTU) in Mode 2 on the front panel, then poll 00B0H (kW x0.01), 006BH/006DH (A x0.1) and 00AAH/00ACH (V x0.1) with function 03. 32-bit values are low word first.
Minimum registers to map
Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.
| Register | Name | Type | Why | Access |
|---|---|---|---|---|
| HR 176 | Instantaneous active power | UINT32 CDAB | Instantaneous active power | Read |
| HR 107 | L1 (CT1) phase current | UINT16 | L1 current | Read |
| HR 109 | L2 (CT2) phase current | UINT16 | L2 current | Read |
| HR 170 | Voltage between 1 and 2 | UINT32 CDAB | Voltage 1-2 | Read |
| HR 172 | Voltage between 2 and 3 | UINT32 CDAB | Voltage 2-3 | Read |
Enable Modbus control & writes
Protocol defaults to MEWTOCOL. In Mode 2 change Protocol to MODBUS(RTU), then set station number, speed, format and response time.
Byte order & addressing
- Only 8-bit transmission formats work with Modbus RTU (8bit-o, 8bit-n, 8bit-E); the default 8bit-o is odd parity.
- Writes outside the allowed range are acknowledged but not applied.
Network setup
- Defaults: station 1, 19200 bps, 8bit-o, response time 5 ms.
- Speeds available: 2400, 4800, 9600, 19200, 38400 bps.
- Broadcast address 0 is accepted but gets no reply.
Watch out for
- AKW7111B and AKW7111 are not interchangeable; only AKW4x0xB CTs can be used with the AKW7111B.
- Settings written over Modbus are stored in EEPROM; don't write them in a loop.
Panasonic KW7M Eco-POWER METER Modbus registers
Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.
| Table | Address | Name | Description | Type | Order | Scale | Units | Access | Values / bits |
|---|---|---|---|---|---|---|---|---|---|
| HR | 50doc 0032H | Rate | Electricity rate per kWh used for the charge display. | UINT16 | × 0.01 | Read/write | |||
| HR | 60doc 003CH | CT type | Dedicated CT rating: 5, 50, 100, 250 or 400. | UINT16 | A | Read/write | |||
| HR | 61doc 003DH | Unit for pulse output | UINT32 | CDAB | Read/write | 1 = 0.001 kWh; 10 = 0.01 kWh; 100 = 0.1 kWh; 333 = Stand-by alarm output (uses 004DH/004EH); 777 = Current alarm output (uses ratio 0045H); 999 = Power alarm output (uses alarm value 0040H); 1000 = 1 kWh; 10000 = 10 kWh; 100000 = 100 kWh | |||
| HR | 63doc 003FH | CT primary current (5 A CT) | Used with a commercial 5 A secondary CT, 1-4000. | UINT16 | A | Read/write | |||
| HR | 64doc 0040H | Alarm value (instantaneous power) | UINT32 | CDAB | × 0.01 | kW | Read/write | ||
| HR | 66doc 0042H | VT ratio | UINT16 | × 0.01 | Read/write | ||||
| HR | 68doc 0044H | Cut-off current | UINT16 | × 0.1 | % | Read/write | |||
| HR | 69doc 0045H | Ratio for current alarm | UINT16 | × 0.1 | % | Read/write | |||
| HR | 77doc 004DH | Ratio for stand-by current | UINT16 | × 0.1 | % | Read/write | |||
| HR | 78doc 004EH | Time for stand-by alarm | UINT16 | min | Read/write | ||||
| HR | 107doc 006BH | L1 (CT1) phase current | UINT16 | × 0.1 | A | Read | |||
| HR | 109doc 006DH | L2 (CT2) phase current | UINT16 | × 0.1 | A | Read | |||
| HR | 170doc 00AAH | Voltage between 1 and 2 | UINT32 | CDAB | × 0.1 | V | Read | ||
| HR | 172doc 00ACH | Voltage between 2 and 3 | UINT32 | CDAB | × 0.1 | V | Read | ||
| HR | 176doc 00B0H | Instantaneous active power | UINT32 | CDAB | × 0.01 | kW | Read |
Notes on this map
- Word order: 32-bit rows are printed as two registers marked <LSB> (lower address) and <MSB> (higher address), so the low word comes first (CDAB).
- Integral active energy (0064H/0065H, 0.01 kWh, read/write, writing 0 resets it) is left out: that row has no LSB/MSB mark, so the manual does not state its word order.
- Pulse-output unit codes 999, 777 and 333 turn the output into a power, current or stand-by alarm instead of an energy pulse.
- Registers not listed read 0. Phase/wire system and the communication settings are not in the Modbus table; set them on the front panel.
Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.
Questions about the Panasonic KW7M Eco-POWER METER
What Modbus registers does the Panasonic KW7M Eco-POWER METER have?
This map lists 15 registers: 15 holding registers. 10 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.
Are the Panasonic KW7M Eco-POWER METER Modbus addresses 0-based or 1-based?
The manufacturer's document numbers registers hexadecimal, 0-based. Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. Addresses are printed in hex (0064H) and go into the request unchanged; the manual's Modbus example resets energy by writing 2 words at data item 0064H. The MEWTOCOL DT number in decimal equals the hex Modbus address.
What byte order does the Panasonic KW7M Eco-POWER METER use for 32-bit values?
Multi-register values in this map use CDAB (low word first (word-swapped)). Set your client to this order for every 32/64-bit value in the table.
What are the minimum Modbus registers to integrate the Panasonic KW7M Eco-POWER METER?
Start with HR 176 Instantaneous active power (Instantaneous active power); HR 107 L1 (CT1) phase current (L1 current); HR 109 L2 (CT2) phase current (L2 current); HR 170 Voltage between 1 and 2 (Voltage 1-2); HR 172 Voltage between 2 and 3 (Voltage 2-3).
How do I enable Modbus control of the Panasonic KW7M Eco-POWER METER?
Protocol defaults to MEWTOCOL. In Mode 2 change Protocol to MODBUS(RTU), then set station number, speed, format and response time.
Where is the official Panasonic KW7M Eco-POWER METER Modbus documentation?
The source is KW7M Eco-POWER METER User's Manual (ARCT1F434E-6), revision 2016-06, published free by Panasonic at https://mediap.industry.panasonic.eu/assets/custom-upload/Factory%20%26%20Automation/Eco-POWER%20METERS/Manuals/mn_kw7m_user_pidsx_en.pdf.
More Panasonic Modbus register maps
- Heat pump (air-to-water) Modbus interface
Panasonic CZ-NSMB A2W Modbus PCB for Aquarea air-to-water heat pumps
Panasonic CZ-NSMB Modbus PCB fitted inside Panasonic Air-To-Water control boxes; the manual's compatibility list names the A2W M-Series control module WH-CME8 and the Big A2W 20-30 kW outdoor units WH-WXG20/25/30ME8 with control module WH-CME8L (user manual M02412F0). Some registers carry H/J/K/L-series conditions.
Also known as: CZ-NSMB, A2W Modbus PCB, WH-CME8, WH-CME8L, WH-WXG20ME8, WH-WXG25ME8, WH-WXG30ME8, Aquarea M series Modbus, Big A2W Modbus - Energy meter
Panasonic KW8M Eco-POWER METER
Panasonic KW8M AKW8111 and AKW8111H (logging/demand version) with Modbus RTU selected, manual ARCT1F440E-8.
Also known as: AKW8111, AKW8111H - Energy meter (multi-circuit power monitor)
Panasonic KW9M Eco-POWER METER
Panasonic KW9M (AKW91110) with the Modbus RTU protocol selected, user manual WUME-KW9M-10.
Also known as: AKW91110
Other power & energy meters register maps
- Sensor (counter / rate panel meter)
Red Lion PAXI counter / rate panel meter (Modbus)
PAXI counter/rate meters with a Modbus serial card, per register table LP0897A (revised 7/10/12).
Also known as: PAXI, PAX I, Red Lion PAXI counter - Energy meter
Rishabh Instruments RISH ED11XX / EC11XX / ER11XX single-phase DIN-rail energy meters
Rishabh RISH ED11XX (direct), EC11XX (CT) and ER11XX (RJ12 CT) single-phase DIN-rail meters in their Modbus (x1) versions, per operating manual DMAN-00IM-1071 Rev. M.
Also known as: RISH ED11X1, RISH EC11X1, RISH ER11X1, ED1111, EC1111, ER1111, RISH ED11XX, RISH EC11XX, RISH ER11XX - Energy meter (DC)
Rishabh Instruments RISH EM DC 6001 / 6002 multi-channel DC energy meter
Rishabh RISH EM DC 6001 / 6002 multi-channel DC energy meters with RS-485 Modbus, per interface definition 2-60-006-00-00627 Rev. 0 (10/2015).
Also known as: RISH EM DC 6001, RISH EM DC 6002, EM DC 6001, EM DC 6002 - Power meter (multi-circuit energy meter)
Rishabh Instruments RISH ML 1400 / ML 1410 Multiload Monitor (Modbus RTU)
RISH Multiload Monitor (12 current channels, 4 voltage channels) per interface definition DMAN-00IM-0795 Rev A (08/2020).
Also known as: RISH ML 1400, RISH ML 1410, RISH MLM, Multiload Monitor - Power meter (power quality analyzer)
SATEC PM174 powermeter and power quality analyzer
SATEC PM174 from firmware 24.3.1, per Modbus reference guide BG0414 Rev. A7 (April 2013).
Also known as: PM174, SATEC PM174, PM 174 - Power meter
Seneca T203PM single-phase AC/DC power meter (Modbus RTU)
T203PM100-MU / T203PM300-MU / T203PM600-MU per user manual MI00571-3-EN.
Also known as: T203PM100-MU, T203PM300-MU, T203PM600-MU, T203PM-MU, T-203PM
All power & energy meters Modbus register maps →
Source: KW7M Eco-POWER METER User's Manual · ARCT1F434E-6 · rev. 2016-06. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.