Power meter (power quality analyzer) · Modbus register map
SATEC PM174 powermeter and power quality analyzer Modbus register map
Updated 17 November 2026
The PM174 is a SATEC panel power meter and EN 50160 power quality analyzer with serial (RTU/ASCII) and optional Ethernet/GPRS Modbus ports. Its 32-bit register set carries 1-second phase and total values, demands and energy counters as integers with fixed units, low word first. This map covers volts, amps, power, PF, THD, frequency, unbalance, present demands, energy totals, digital I/O, basic wiring/CT/PT setup, COM port settings, password and clear commands.
This page lists 103 Modbus registers for the SATEC PM174 powermeter and power quality analyzer — 17 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from SATEC’s own free documentation (linked below) and checked against it.
- Manufacturer
- SATEC
- Model
- PM174 powermeter and power quality analyzer
- Equipment type
- Power meter (power quality analyzer)
- Registers
- 103 (17 writable)
- Transport
- Modbus RTU, Modbus ASCII, Modbus TCP
- Default unit ID
- Not stated
- Documented addressing
- 0-based (the number printed is the address on the wire)
- 32-bit word order
- CDAB low word first (word-swapped)
- Firmware
- 24.3.1 or higher
- Also known as
- PM174, SATEC PM174, PM 174
Integration notes: SATEC PM174 powermeter and power quality analyzer
Read 13952-14017 (phase values) and 14336-14361 (totals) with function 03; decode 32-bit integers low word first. Energy totals are at 14720 onward in whole kWh/kvarh.
Minimum registers to map
Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.
| Register | Name | Type | Why | Access |
|---|---|---|---|---|
| HR 13952 | V1/V12 Voltage | UINT32 CDAB | V1/V12 voltage | Read |
| HR 13958 | I1 Current | UINT32 CDAB | I1 current | Read |
| HR 14336 | Total kW | INT32 CDAB | Total kW | Read |
| HR 14342 | Total PF | INT32 CDAB | Total PF | Read |
| HR 14468 | Frequency | UINT32 CDAB | Frequency | Read |
| HR 14720 | kWh import | UINT32 CDAB | kWh import | Read |
| HR 14722 | kWh export | UINT32 CDAB | kWh export | Read |
Enable Modbus control & writes
Choose the port protocol (Modbus RTU/ASCII) and address in the COM setup (2344-2359) or from the front panel; Modbus/TCP runs on the Ethernet option.
Byte order & addressing
- 32-bit values are low word first (CDAB).
- Voltage and power units change from 0.1 V / 1 W to 1 V / 1 kW when a PT ratio above 1 is set.
- 120 user-assignable registers (0-119, mapped by 120-239) let you pack scattered values into one read.
Network setup
- Set wiring mode, PT ratio and CT primary at 2304-2306 first (and the PT ratio factor at 2324 if used).
- Write the password to 2575 if protection is enabled.
Watch out for
- Changing the PT ratio from 1 changes the meaning of every voltage and power register.
- Broadcast (address 0) is not supported.
SATEC PM174 powermeter and power quality analyzer Modbus registers
Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.
| Table | Address | Name | Description | Type | Order | Scale | Units | Access | Values / bits |
|---|---|---|---|---|---|---|---|---|---|
| HR | 2304 | Wiring mode | UINT16 | Read/write | 0 = 3OP2 - 3-wire open delta, 2 CTs; 1 = 4LN3 - 4-wire wye, 3 PTs, L-N readings; 2 = 3DIR2 - 3-wire direct, 2 CTs; 3 = 4LL3 - 4-wire wye, 3 PTs, L-L readings; 4 = 3OP3 - 3-wire open delta, 3 CTs; 5 = 3LN3 - 4-wire wye, 2 PTs, L-N readings; 6 = 3LL3 - 4-wire wye, 2 PTs, L-L readings; 8 = 3BLN3 - 3-wire broken delta, 2 PTs, L-N readings; 9 = 3BLL3 - 3-wire broken delta, 2 PTs, L-L readings | ||||
| HR | 2305 | PT ratio | 10-65000 = 1.0-6500.0; multiplied by the factor at 2324 (x1 or x10). | UINT16 | × 0.1 | Read/write | |||
| HR | 2306 | CT primary current | 1-50000 A. | UINT16 | A | Read/write | |||
| HR | 2315 | Nominal line frequency | 50 or 60. | UINT16 | Hz | Read/write | |||
| HR | 2344 | COM1 protocol | UINT16 | Read/write | 0 = Modbus RTU; 1 = Modbus ASCII; 2 = DNP3.0; 5 = Profibus DP | ||||
| HR | 2345 | COM1 interface | UINT16 | Read/write | 0 = RS-232; 1 = RS-422; 2 = RS-485; 4 = Dial-up modem; 6 = Ethernet; 7 = Profibus; 8 = GSM/GPRS | ||||
| HR | 2346 | COM1 device address | Modbus 1-247. | UINT16 | Read/write | ||||
| HR | 2347 | COM1 baud rate | UINT16 | Read/write | 1 = 300; 2 = 600; 3 = 1200; 4 = 2400; 5 = 4800; 6 = 9600; 7 = 19200; 8 = 38400; 9 = 57600; 10 = 115200 | ||||
| HR | 2348 | COM1 data format | UINT16 | Read/write | 0 = 7 bits, even parity; 1 = 8 bits, no parity; 2 = 8 bits, even parity | ||||
| HR | 2354 | COM2 device address | Modbus 1-247. | UINT16 | Read/write | ||||
| HR | 2355 | COM2 baud rate | UINT16 | Read/write | 1 = 300; 2 = 600; 3 = 1200; 4 = 2400; 5 = 4800; 6 = 9600; 7 = 19200; 8 = 38400; 9 = 57600; 10 = 115200 | ||||
| HR | 2356 | COM2 data format | UINT16 | Read/write | 0 = 7 bits, even parity; 1 = 8 bits, no parity; 2 = 8 bits, even parity | ||||
| HR | 2560 | Warm restart | Write 0xFFFF to restart; reads 0. | UINT16 | Read/write | ||||
| HR | 2565 | Firmware version number | Two high decimal digits = major version, two low = minor. | UINT16 | Read | ||||
| HR | 2575 | Device authorization (password) | Write the 4-digit password before setup writes; reads 0 = allowed, -1 = password needed. | INT16 | Read/write | ||||
| HR | 11906doc 11906-11907 | Phase rotation order | UINT32 | CDAB | Read | 0 = Error; 1 = Positive (ABC); 2 = Negative (CBA) | |||
| HR | 12544doc 12544-12545 | Digital inputs (bitmap) | Bit 0 = DI1, bit 1 = DI2, and so on. | UINT32 | CDAB | Read | |||
| HR | 12800doc 12800-12801 | Relay outputs (bitmap) | Bit 0 = relay 1, bit 1 = relay 2, and so on. | UINT32 | CDAB | Read | |||
| HR | 13952doc 13952-13953 | V1/V12 Voltage | Scale is for PT ratio 1; with PT ratio above 1 the unit is 1 V. | UINT32 | CDAB | × 0.1 | V | Read | |
| HR | 13954doc 13954-13955 | V2/V23 Voltage | Scale is for PT ratio 1; with PT ratio above 1 the unit is 1 V. | UINT32 | CDAB | × 0.1 | V | Read | |
| HR | 13956doc 13956-13957 | V3/V31 Voltage | Scale is for PT ratio 1; with PT ratio above 1 the unit is 1 V. | UINT32 | CDAB | × 0.1 | V | Read | |
| HR | 13958doc 13958-13959 | I1 Current | UINT32 | CDAB | × 0.01 | A | Read | ||
| HR | 13960doc 13960-13961 | I2 Current | UINT32 | CDAB | × 0.01 | A | Read | ||
| HR | 13962doc 13962-13963 | I3 Current | UINT32 | CDAB | × 0.01 | A | Read | ||
| HR | 13964doc 13964-13965 | kW L1 | Scale is for PT ratio 1; with PT ratio above 1 the unit is 1 kW. | INT32 | CDAB | × 0.001 | kW | Read | |
| HR | 13966doc 13966-13967 | kW L2 | Scale is for PT ratio 1; with PT ratio above 1 the unit is 1 kW. | INT32 | CDAB | × 0.001 | kW | Read | |
| HR | 13968doc 13968-13969 | kW L3 | Scale is for PT ratio 1; with PT ratio above 1 the unit is 1 kW. | INT32 | CDAB | × 0.001 | kW | Read | |
| HR | 13970doc 13970-13971 | kvar L1 | Scale is for PT ratio 1; with PT ratio above 1 the unit is 1 kvar. | INT32 | CDAB | × 0.001 | kvar | Read | |
| HR | 13972doc 13972-13973 | kvar L2 | Scale is for PT ratio 1; with PT ratio above 1 the unit is 1 kvar. | INT32 | CDAB | × 0.001 | kvar | Read | |
| HR | 13974doc 13974-13975 | kvar L3 | Scale is for PT ratio 1; with PT ratio above 1 the unit is 1 kvar. | INT32 | CDAB | × 0.001 | kvar | Read | |
| HR | 13976doc 13976-13977 | kVA L1 | Scale is for PT ratio 1; with PT ratio above 1 the unit is 1 kVA. | UINT32 | CDAB | × 0.001 | kVA | Read | |
| HR | 13978doc 13978-13979 | kVA L2 | Scale is for PT ratio 1; with PT ratio above 1 the unit is 1 kVA. | UINT32 | CDAB | × 0.001 | kVA | Read | |
| HR | 13980doc 13980-13981 | kVA L3 | Scale is for PT ratio 1; with PT ratio above 1 the unit is 1 kVA. | UINT32 | CDAB | × 0.001 | kVA | Read | |
| HR | 13982doc 13982-13983 | Power factor L1 | INT32 | CDAB | × 0.001 | Read | |||
| HR | 13984doc 13984-13985 | Power factor L2 | INT32 | CDAB | × 0.001 | Read | |||
| HR | 13986doc 13986-13987 | Power factor L3 | INT32 | CDAB | × 0.001 | Read | |||
| HR | 13988doc 13988-13989 | V1/V12 Voltage THD | UINT32 | CDAB | × 0.1 | % | Read | ||
| HR | 13990doc 13990-13991 | V2/V23 Voltage THD | UINT32 | CDAB | × 0.1 | % | Read | ||
| HR | 13992doc 13992-13993 | V3/V31 Voltage THD | UINT32 | CDAB | × 0.1 | % | Read | ||
| HR | 13994doc 13994-13995 | I1 Current THD | UINT32 | CDAB | × 0.1 | % | Read | ||
| HR | 13996doc 13996-13997 | I2 Current THD | UINT32 | CDAB | × 0.1 | % | Read | ||
| HR | 13998doc 13998-13999 | I3 Current THD | UINT32 | CDAB | × 0.1 | % | Read | ||
| HR | 14000doc 14000-14001 | I1 K-Factor | UINT32 | CDAB | × 0.1 | Read | |||
| HR | 14002doc 14002-14003 | I2 K-Factor | UINT32 | CDAB | × 0.1 | Read | |||
| HR | 14004doc 14004-14005 | I3 K-Factor | UINT32 | CDAB | × 0.1 | Read | |||
| HR | 14006doc 14006-14007 | I1 Current TDD | UINT32 | CDAB | × 0.1 | % | Read | ||
| HR | 14008doc 14008-14009 | I2 Current TDD | UINT32 | CDAB | × 0.1 | % | Read | ||
| HR | 14010doc 14010-14011 | I3 Current TDD | UINT32 | CDAB | × 0.1 | % | Read | ||
| HR | 14012doc 14012-14013 | V12 Voltage | Scale is for PT ratio 1; with PT ratio above 1 the unit is 1 V. | UINT32 | CDAB | × 0.1 | V | Read | |
| HR | 14014doc 14014-14015 | V23 Voltage | Scale is for PT ratio 1; with PT ratio above 1 the unit is 1 V. | UINT32 | CDAB | × 0.1 | V | Read | |
| HR | 14016doc 14016-14017 | V31 Voltage | Scale is for PT ratio 1; with PT ratio above 1 the unit is 1 V. | UINT32 | CDAB | × 0.1 | V | Read | |
| HR | 14336doc 14336-14337 | Total kW | Scale is for PT ratio 1; with PT ratio above 1 the unit is 1 kW. | INT32 | CDAB | × 0.001 | kW | Read | |
| HR | 14338doc 14338-14339 | Total kvar | Scale is for PT ratio 1; with PT ratio above 1 the unit is 1 kvar. | INT32 | CDAB | × 0.001 | kvar | Read | |
| HR | 14340doc 14340-14341 | Total kVA | Scale is for PT ratio 1; with PT ratio above 1 the unit is 1 kVA. | UINT32 | CDAB | × 0.001 | kVA | Read | |
| HR | 14342doc 14342-14343 | Total PF | INT32 | CDAB | × 0.001 | Read | |||
| HR | 14348doc 14348-14349 | Total kW import | Scale is for PT ratio 1; with PT ratio above 1 the unit is 1 kW. | UINT32 | CDAB | × 0.001 | kW | Read | |
| HR | 14350doc 14350-14351 | Total kW export | Scale is for PT ratio 1; with PT ratio above 1 the unit is 1 kW. | UINT32 | CDAB | × 0.001 | kW | Read | |
| HR | 14352doc 14352-14353 | Total kvar import | Scale is for PT ratio 1; with PT ratio above 1 the unit is 1 kvar. | UINT32 | CDAB | × 0.001 | kvar | Read | |
| HR | 14354doc 14354-14355 | Total kvar export | Scale is for PT ratio 1; with PT ratio above 1 the unit is 1 kvar. | UINT32 | CDAB | × 0.001 | kvar | Read | |
| HR | 14356doc 14356-14357 | 3-phase average L-N/L-L voltage | Scale is for PT ratio 1; with PT ratio above 1 the unit is 1 V. | UINT32 | CDAB | × 0.1 | V | Read | |
| HR | 14358doc 14358-14359 | 3-phase average L-L voltage | Scale is for PT ratio 1; with PT ratio above 1 the unit is 1 V. | UINT32 | CDAB | × 0.1 | V | Read | |
| HR | 14360doc 14360-14361 | 3-phase average current | UINT32 | CDAB | × 0.01 | A | Read | ||
| HR | 14466doc 14466-14467 | In (neutral) Current | UINT32 | CDAB | × 0.01 | A | Read | ||
| HR | 14468doc 14468-14469 | Frequency | UINT32 | CDAB | × 0.01 | Hz | Read | ||
| HR | 14470doc 14470-14471 | Voltage unbalance | UINT32 | CDAB | × 0.1 | % | Read | ||
| HR | 14472doc 14472-14473 | Current unbalance | UINT32 | CDAB | × 0.1 | % | Read | ||
| HR | 14592doc 14592-14593 | V1/V12 Volt demand | Scale is for PT ratio 1; with PT ratio above 1 the unit is 1 V. | UINT32 | CDAB | × 0.1 | V | Read | |
| HR | 14594doc 14594-14595 | V2/V23 Volt demand | Scale is for PT ratio 1; with PT ratio above 1 the unit is 1 V. | UINT32 | CDAB | × 0.1 | V | Read | |
| HR | 14596doc 14596-14597 | V3/V31 Volt demand | Scale is for PT ratio 1; with PT ratio above 1 the unit is 1 V. | UINT32 | CDAB | × 0.1 | V | Read | |
| HR | 14598doc 14598-14599 | I1 Ampere demand | UINT32 | CDAB | × 0.01 | A | Read | ||
| HR | 14600doc 14600-14601 | I2 Ampere demand | UINT32 | CDAB | × 0.01 | A | Read | ||
| HR | 14602doc 14602-14603 | I3 Ampere demand | UINT32 | CDAB | × 0.01 | A | Read | ||
| HR | 14604doc 14604-14605 | kW import block demand | Scale is for PT ratio 1; with PT ratio above 1 the unit is 1 kW. | UINT32 | CDAB | × 0.001 | kW | Read | |
| HR | 14606doc 14606-14607 | kvar import block demand | Scale is for PT ratio 1; with PT ratio above 1 the unit is 1 kvar. | UINT32 | CDAB | × 0.001 | kvar | Read | |
| HR | 14608doc 14608-14609 | kVA block demand | Scale is for PT ratio 1; with PT ratio above 1 the unit is 1 kVA. | UINT32 | CDAB | × 0.001 | kVA | Read | |
| HR | 14610doc 14610-14611 | kW import sliding window demand | Scale is for PT ratio 1; with PT ratio above 1 the unit is 1 kW. | UINT32 | CDAB | × 0.001 | kW | Read | |
| HR | 14612doc 14612-14613 | kvar import sliding window demand | Scale is for PT ratio 1; with PT ratio above 1 the unit is 1 kvar. | UINT32 | CDAB | × 0.001 | kvar | Read | |
| HR | 14614doc 14614-14615 | kVA sliding window demand | Scale is for PT ratio 1; with PT ratio above 1 the unit is 1 kVA. | UINT32 | CDAB | × 0.001 | kVA | Read | |
| HR | 14622doc 14622-14623 | kW import accumulated demand | Scale is for PT ratio 1; with PT ratio above 1 the unit is 1 kW. | UINT32 | CDAB | × 0.001 | kW | Read | |
| HR | 14624doc 14624-14625 | kvar import accumulated demand | Scale is for PT ratio 1; with PT ratio above 1 the unit is 1 kvar. | UINT32 | CDAB | × 0.001 | kvar | Read | |
| HR | 14626doc 14626-14627 | kVA accumulated demand | Scale is for PT ratio 1; with PT ratio above 1 the unit is 1 kVA. | UINT32 | CDAB | × 0.001 | kVA | Read | |
| HR | 14628doc 14628-14629 | kW import predicted sliding window demand | Scale is for PT ratio 1; with PT ratio above 1 the unit is 1 kW. | UINT32 | CDAB | × 0.001 | kW | Read | |
| HR | 14630doc 14630-14631 | kvar import predicted sliding window demand | Scale is for PT ratio 1; with PT ratio above 1 the unit is 1 kvar. | UINT32 | CDAB | × 0.001 | kvar | Read | |
| HR | 14632doc 14632-14633 | kVA predicted sliding window demand | Scale is for PT ratio 1; with PT ratio above 1 the unit is 1 kVA. | UINT32 | CDAB | × 0.001 | kVA | Read | |
| HR | 14634doc 14634-14635 | PF (import) at Max. kVA sliding window demand | UINT32 | CDAB | × 0.001 | Read | |||
| HR | 14636doc 14636-14637 | kW export block demand | Scale is for PT ratio 1; with PT ratio above 1 the unit is 1 kW. | UINT32 | CDAB | × 0.001 | kW | Read | |
| HR | 14638doc 14638-14639 | kvar export block demand | Scale is for PT ratio 1; with PT ratio above 1 the unit is 1 kvar. | UINT32 | CDAB | × 0.001 | kvar | Read | |
| HR | 14640doc 14640-14641 | kW export sliding window demand | Scale is for PT ratio 1; with PT ratio above 1 the unit is 1 kW. | UINT32 | CDAB | × 0.001 | kW | Read | |
| HR | 14642doc 14642-14643 | kvar export sliding window demand | Scale is for PT ratio 1; with PT ratio above 1 the unit is 1 kvar. | UINT32 | CDAB | × 0.001 | kvar | Read | |
| HR | 14644doc 14644-14645 | kW export accumulated demand | Scale is for PT ratio 1; with PT ratio above 1 the unit is 1 kW. | UINT32 | CDAB | × 0.001 | kW | Read | |
| HR | 14646doc 14646-14647 | kvar export accumulated demand | Scale is for PT ratio 1; with PT ratio above 1 the unit is 1 kvar. | UINT32 | CDAB | × 0.001 | kvar | Read | |
| HR | 14648doc 14648-14649 | kW export predicted sliding window demand | Scale is for PT ratio 1; with PT ratio above 1 the unit is 1 kW. | UINT32 | CDAB | × 0.001 | kW | Read | |
| HR | 14650doc 14650-14651 | kvar export predicted sliding window demand | Scale is for PT ratio 1; with PT ratio above 1 the unit is 1 kvar. | UINT32 | CDAB | × 0.001 | kvar | Read | |
| HR | 14720doc 14720-14721 | kWh import | UINT32 | CDAB | kWh | Read | |||
| HR | 14722doc 14722-14723 | kWh export | UINT32 | CDAB | kWh | Read | |||
| HR | 14728doc 14728-14729 | kvarh import | UINT32 | CDAB | kvarh | Read | |||
| HR | 14730doc 14730-14731 | kvarh export | UINT32 | CDAB | kvarh | Read | |||
| HR | 14736doc 14736-14737 | kVAh total | UINT32 | CDAB | kVAh | Read | |||
| HR | 44102 | Clear energies | Write 0. | UINT16 | Write | ||||
| HR | 44103 | Clear maximum demands | UINT16 | Write | 0 = Clear all maximum demands; 1 = Clear power demands; 2 = Clear volt, ampere and harmonic demands | ||||
| HR | 44107 | Clear min/max log | Write 0. | UINT16 | Write | ||||
| HR | 46080doc 46080-46081 | Device serial number | UINT32 | CDAB | Read | ||||
| HR | 46082doc 46082-46083 | Device model ID | 17400 for PM174. | UINT32 | CDAB | Read |
Notes on this map
- Addressing: the guide says to add 40001 to a register address to get the Modicon holding-register number (400001 above 9999), so printed addresses are 0-based wire addresses.
- Word order: 32-bit values are sent with the low-order word in the first (even) register and the high-order word in the second, so they are CDAB here.
- Units U1 (voltage) and U3 (power) depend on the PT ratio: with PT ratio = 1 they are 0.1 V and 0.001 kW/kvar/kVA (the scales used here); with PT ratio > 1 they become 1 V and 1 kW/kvar/kVA. U2 (current) is always 0.01 A.
- Function 04 can be used the same way as function 03.
- Voltage rows marked V1/V12 read line-to-neutral in 4LN3, 3LN3 and 3BLN3 wiring and line-to-line otherwise.
- Energy counters are whole kWh/kvarh/kVAh and roll over at the energy roll value set in the device options.
- Left out: 16-bit scaled registers (need per-site HI/LO scale arithmetic), 1-cycle and 1/2-cycle values, harmonics, min/max logs, TOU registers, the total PF lag/lead rows (printed as UINT16 in a two-register slot), setpoint, log and file-transfer registers.
- When password protection is on, write the password to 2575 before any setup or clear command, otherwise writes fail with exception 01.
Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.
Questions about the SATEC PM174 powermeter and power quality analyzer
What Modbus registers does the SATEC PM174 powermeter and power quality analyzer have?
This map lists 103 registers: 103 holding registers. 17 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.
Are the SATEC PM174 powermeter and power quality analyzer Modbus addresses 0-based or 1-based?
The manufacturer's document numbers registers 0-based (the number printed is the address on the wire). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. The guide numbers registers 0-65535 and says to add 40001 (or 400001 above 9999) for Modicon holding-register numbers, so the printed address goes straight into the frame: 13952 is wire address 13952 (Modicon 413953).
What byte order does the SATEC PM174 powermeter and power quality analyzer use for 32-bit values?
Multi-register values in this map use CDAB (low word first (word-swapped)). Set your client to this order for every 32/64-bit value in the table.
What are the minimum Modbus registers to integrate the SATEC PM174 powermeter and power quality analyzer?
Start with HR 13952 V1/V12 Voltage (V1/V12 voltage); HR 13958 I1 Current (I1 current); HR 14336 Total kW (Total kW); HR 14342 Total PF (Total PF); HR 14468 Frequency (Frequency); HR 14720 kWh import (kWh import); HR 14722 kWh export (kWh export).
How do I enable Modbus control of the SATEC PM174 powermeter and power quality analyzer?
Choose the port protocol (Modbus RTU/ASCII) and address in the COM setup (2344-2359) or from the front panel; Modbus/TCP runs on the Ethernet option.
Where is the official SATEC PM174 powermeter and power quality analyzer Modbus documentation?
The source is PM174 Powermeter and Power Quality Analyzer - Modbus Communications Protocol Reference Guide (BG0414 Rev. A7), revision 2013-04, published free by SATEC at https://www.satec-global.com/wp-content/uploads/2023/03/PM174-Modbus.pdf.
More SATEC Modbus register maps
- Power meter (multi-circuit branch feeder monitor)
SATEC BFM-II branch feeder monitor
SATEC BFM-II multi-circuit meter per Modbus reference guide BG0589 Rev. A12 (May 2024); per-submeter 32-bit measurement registers plus shared setup.
Also known as: BFM II, BFM2, SATEC BFM-II - Power meter (multi-circuit branch feeder monitor)
SATEC BFM136/036 branch feeder monitor
SATEC BFM136 and BFM036 multi-circuit meters per Modbus reference guide BG0395 Rev. A8 (July 2024); per-submeter 32-bit measurement registers plus shared setup.
Also known as: BFM136, BFM036, BFM 136, SATEC BFM136 - Energy meter (multifunction)
SATEC EM133-R residential multifunction meter
SATEC EM133-R (and EM133-XM) multifunction meters, per Modbus reference guide BG0520 Rev. A6 (Oct 2018).
Also known as: EM133, EM133-R, EM133-XM, SATEC EM133 - Power meter (revenue / power quality)
SATEC EM235 / PM335 PRO advanced power meter
SATEC EM235 and PM335 PRO advanced power meters, per Modbus reference guide BG0613 Rev. A8 (Sept 2025).
Also known as: EM235, PM335 PRO, PM335PRO, SATEC EM235, SATEC PM335 - Power meter (power quality analyzer)
SATEC PM175 powermeter and power quality analyzer
SATEC PM175 from firmware 25.2.6, per Modbus reference guide BG0416 Rev. A7 (Nov 2009).
Also known as: PM175, SATEC PM175, PM 175 - Power meter (power quality analyzer)
SATEC PM180 expertmeter high performance analyzer
SATEC PM180 expertmeter, per Modbus reference guide BG0527 Rev. A11 (Sep 2024).
Also known as: PM180, expertmeter PM180, SATEC PM180
Other power & energy meters register maps
- Power meter
Seneca T203PM single-phase AC/DC power meter (Modbus RTU)
T203PM100-MU / T203PM300-MU / T203PM600-MU per user manual MI00571-3-EN.
Also known as: T203PM100-MU, T203PM300-MU, T203PM600-MU, T203PM-MU, T-203PM - Power meter (power quality)
Siemens SICAM P850 / P855 power monitoring and PQ device
SICAM P850 / P855 (7KG85x) with Modbus TCP or Modbus RTU, firmware V3.11, per communication manual E50417-C1040-C482-B1 (05.2024).
Also known as: 7KG85, 7KG85X, SICAM P850, SICAM P855 - Power meter (branch circuit monitoring)
ABB CMS-700 circuit monitoring system control unit (Modbus RTU / TCP)
ABB CMS-700 control unit with up to 96 CMS branch current sensors, per the CMS-700 user manual (Modbus and SNMP mapping chapter).
Also known as: CMS-700, CMS700, ABB CMS-700, CMS-700 control unit - Power meter (circuit breaker trip unit)
ABB SACE PR122/P, PR123/P, PR332/P, PR333/P trip units with PR120/D-M or PR330/D-M (Modbus RTU)
ABB SACE PR122/P and PR123/P (Emax) and PR332/P and PR333/P (Emax X1, Tmax T7, Tmax T8) protection releases with the Modbus RTU communication module, per 1SDH000556R0001.
Also known as: PR122/P, PR123/P, PR332/P, PR333/P, PR120/D-M, PR330/D-M, Emax PR122, Emax PR123, Tmax T7 PR332, Emax X1 PR333, Tmax T8 PR332 - Energy meter (thermal / BTU meter)
Belimo Thermal Energy Meter (TEM) DN 15-50, Version 4 (Modbus RTU / TCP)
Belimo Thermal Energy Meter DN 15...50 version 4 (22PE..-1U.., 22PF-..U..), interface description V4.2.0 edition 2025-11.
Also known as: 22PE-1U, 22PEM-1UC, 22PE..-1U.., 22PF, Belimo Thermal Energy Meter, Belimo TEM - Energy meter (energy analyzer)
Carlo Gavazzi EM24-DIN (PFA, PFB and X models)
EM24-DIN three-phase energy analyzers, PFA/PFB (MID) and X models with the RS485 Modbus RTU port (IS option), protocol version 4 revision 0.
Also known as: EM24, EM24DIN, EM24DINAV93XISPFA, EM24DINAV93XISPFB, EM24DINAV93XISX, EM24DINAV53XISX, EM24DINAV23XISX, EM24 DIN AV9, EM24 DIN AV5
All power & energy meters Modbus register maps →
Source: PM174 Powermeter and Power Quality Analyzer - Modbus Communications Protocol Reference Guide · BG0414 Rev. A7 · rev. 2013-04. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.