  4. SACE PR122/P, PR123/P, PR332/P, PR333/P trip units with PR120/D-M or PR330/D-M (Modbus RTU)

Power meter (circuit breaker trip unit) · Modbus register map

ABB SACE PR122/P, PR123/P, PR332/P, PR333/P trip units with PR120/D-M or PR330/D-M (Modbus RTU) Modbus register map

Updated 19 November 2026

Short answer

ABB's PR12x and PR33x electronic trip units talk Modbus RTU through the PR120/D-M (or PR330/D-M) com module. Run-time measures (currents, voltages, power, energy, frequency) and breaker state are input registers; commands such as open, close and trip reset go to two holding registers. 32-bit values are sent low word first.

This page lists 36 Modbus registers for the ABB SACE PR122/P, PR123/P, PR332/P, PR333/P trip units with PR120/D-M or PR330/D-M (Modbus RTU) — 2 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from ABB’s own free documentation (linked below) and checked against it.

Manufacturer
ABB
Model
SACE PR122/P, PR123/P, PR332/P, PR333/P trip units with PR120/D-M or PR330/D-M (Modbus RTU)
Equipment type
Power meter (circuit breaker trip unit)
Registers
36 (2 writable)
Transport
Modbus RTU
Default unit ID
247
Default serial
19200 baud, 8E1
Documented addressing
Modicon 3xxxx/4xxxx (drop the prefix, subtract 1)
32-bit word order
CDAB low word first (word-swapped)
Also known as
PR122/P, PR123/P, PR332/P, PR333/P, PR120/D-M, PR330/D-M, Emax PR122, Emax PR123, Tmax T7 PR332, Emax X1 PR333, Tmax T8 PR332
Source document
Modbus system Interface for Protection relays PR122/P and PR123/P + communication module PR120/D-M, mounted on CB New Emax; Protection relays PR332/P and PR333/P + communication module PR330/D-M, mounted on CB Emax X1, Tmax T7 and Tmax T8 · 1SDH000556R0001
Download CSV all columns JSON Manufacturer PDF ↗

Integration notes: ABB SACE PR122/P, PR123/P, PR332/P, PR333/P trip units with PR120/D-M or PR330/D-M (Modbus RTU)

Integration in brief

Read input registers 200-264 for measurements and 101/103/107 for breaker state, alarms and trips. Open, close or reset by writing command type and parameter (registers 0-1) together with function 16.

Minimum registers to map

Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.

RegisterNameTypeWhyAccess
IR 101State 2 - flagsBITMAP16CB open/closed, tripped, remoteRead
IR 107State 8 - latched tripsBITMAP16Which protection trippedRead
IR 203L1 currentUINT32 CDABL1 currentRead
IR 219V12 line-to-line voltageUINT16V12 voltageRead
IR 228Total active powerINT32 CDABTotal active powerRead
IR 256Total active energyINT32 CDABTotal active energyRead
HR 0Command typeUINT16Commands (open/close/reset)Write

Enable Modbus control & writes

Fit the PR120/D-M (or PR330/D-M) module and set address, baud and parity on the trip unit. The breaker must be in Remote mode (state 2 bit 9) for open/close commands.

Byte order & addressing

Network setup

Watch out for

ABB SACE PR122/P, PR123/P, PR332/P, PR333/P trip units with PR120/D-M or PR330/D-M (Modbus RTU) Modbus registers

Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.

36 of 36 shown
ABB SACE PR122/P, PR123/P, PR332/P, PR333/P trip units with PR120/D-M or PR330/D-M (Modbus RTU) Modbus register map
TableAddressNameDescriptionTypeOrderScaleUnitsAccessValues / bits
IR5doc 30006 (rel. 5)Contact wear0-65000, 65000 = 100 %.UINT16Read
IR6doc 30007 (rel. 6)Total trip protection numberIncludes failed trips.UINT16Read
IR7doc 30008 (rel. 7)Total operation numberUINT16Read
IR101doc 30102 (rel. 101)State 2 - flagsBreaker position and remote/local.BITMAP16Readbit 0 = Any alarm / timing / warning; bit 1 = Any trip (latched); bit 2 = CB tripped; bit 3 = CB connected (0 = isolated); bit 4 = CB closed (0 = open); bit 5 = CB undefined; bit 6 = No communication on local bus; bit 7 = Springs charged; bit 8 = Trip command fail; bit 9 = Remote mode (0 = local); bit 10 = Programming OK; bit 11 = Programming failed; bit 12 = Internal bus programming session; bit 13 = Test bus programming session; bit 14 = Local bus programming session; bit 15 = System bus programming session
IR103doc 30104 (rel. 103)State 4 - alarmsBITMAP16Readbit 0 = Harmonic distortion > 2.1; bit 1 = Contact wear pre-alarm; bit 2 = Contact wear alarm; bit 3 = L pre-alarm; bit 4 = L timing; bit 5 = S timing; bit 6 = S2 timing; bit 7 = G timing; bit 8 = G alarm (trip blocked); bit 9 = G ext timing; bit 10 = G ext alarm (trip blocked); bit 11 = T pre-alarm; bit 12 = T alarm; bit 13 = T alarm (trip blocked); bit 14 = D timing; bit 15 = U timing
IR107doc 30108 (rel. 107)State 8 - latched tripsCleared by CB reset or trip reset.BITMAP16Readbit 0 = L tripped; bit 1 = S tripped; bit 2 = S2 tripped; bit 3 = I tripped (or MCR); bit 4 = Iinst tripped; bit 5 = G tripped; bit 6 = G ext tripped; bit 7 = T tripped; bit 8 = D tripped; bit 9 = UN tripped; bit 10 = UV tripped; bit 11 = OV tripped; bit 12 = RV tripped; bit 13 = RP tripped; bit 14 = UF tripped; bit 15 = OF tripped
IR200doc 30201-30202 (rel. 200)Maximum current2^32-1 = not available.UINT32CDABARead
IR202doc 30203 (rel. 202)Maximum current phaseUINT16Read0 = Not available; 1 = L1; 2 = L2; 3 = L3; 4 = Ne
IR203doc 30204-30205 (rel. 203)L1 current2^32-1 = not available.UINT32CDABARead
IR205doc 30206-30207 (rel. 205)L2 current2^32-1 = not available.UINT32CDABARead
IR207doc 30208-30209 (rel. 207)L3 current2^32-1 = not available.UINT32CDABARead
IR209doc 30210-30211 (rel. 209)Neutral current2^32-1 = not available.UINT32CDABARead
IR211doc 30212-30213 (rel. 211)Internal ground currentG versions. 2^32-1 = not available.UINT32CDABARead
IR213doc 30214-30215 (rel. 213)External ground currentG versions, 0.01 A units. 2^32-1 = not available.UINT32CDAB× 0.01ARead
IR215doc 30216 (rel. 215)V1 line-to-neutral voltage65535 = not available.UINT16× 0.1VRead
IR216doc 30217 (rel. 216)V2 line-to-neutral voltageUINT16× 0.1VRead
IR217doc 30218 (rel. 217)V3 line-to-neutral voltageUINT16× 0.1VRead
IR219doc 30220 (rel. 219)V12 line-to-line voltageUINT16× 0.1VRead
IR220doc 30221 (rel. 220)V23 line-to-line voltageUINT16× 0.1VRead
IR221doc 30222 (rel. 221)V31 line-to-line voltageUINT16× 0.1VRead
IR222doc 30223-30224 (rel. 222)L1 active powerINT32CDAB× 0.1kWRead
IR224doc 30225-30226 (rel. 224)L2 active powerINT32CDAB× 0.1kWRead
IR226doc 30227-30228 (rel. 226)L3 active powerINT32CDAB× 0.1kWRead
IR228doc 30229-30230 (rel. 228)Total active power2^31-1 = not available.INT32CDAB× 0.1kWRead
IR236doc 30237-30238 (rel. 236)Total reactive powerINT32CDAB× 0.1kVARRead
IR244doc 30245-30246 (rel. 244)Total apparent powerINT32CDAB× 0.1kVARead
IR246doc 30247 (rel. 246)Total power factorSigned, 0.01 steps.INT16× 0.01Read
IR247doc 30248 (rel. 247)FrequencyUINT16× 0.1HzRead
IR252doc 30253-30254 (rel. 252)Positive active energyINT32CDABkWhRead
IR254doc 30255-30256 (rel. 254)Negative active energyINT32CDABkWhRead
IR256doc 30257-30258 (rel. 256)Total active energyINT32CDABkWhRead
IR262doc 30263-30264 (rel. 262)Total reactive energyINT32CDABkVARhRead
IR264doc 30265-30266 (rel. 264)Total apparent energyINT32CDABkVAhRead
IR704doc 30705 (rel. 704)Rated current In100-6300 A.UINT16ARead
HR0doc 40001 (rel. 0)Command typeWrite with the parameter in one function-16 request.UINT16Write0 = Dummy; 1 = Trip reset; 2 = Signalling reset; 3 = Communication statistics reset; 4 = Log events reset; 5 = Start programming session; 6 = Abort programming session; 7 = Stop programming session; 8 = CB open; 9 = CB close; 10 = CB reset; 11 = Wink toggle; 12 = History measure reset; 13 = Energy counters reset; 14 = Data logger trigger restart; 15 = Data logger stop; 16 = Waveform + harmonics acquisition start; 17 = Waveform + harmonics acquisition stop
HR1doc 40002 (rel. 1)Command parameter0 when the command needs none.UINT16Write

Notes on this map

Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.

Questions about the ABB SACE PR122/P, PR123/P, PR332/P, PR333/P trip units with PR120/D-M or PR330/D-M (Modbus RTU)

What Modbus registers does the ABB SACE PR122/P, PR123/P, PR332/P, PR333/P trip units with PR120/D-M or PR330/D-M (Modbus RTU) have?

This map lists 36 registers: 34 input registers, 2 holding registers. 2 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.

Are the ABB SACE PR122/P, PR123/P, PR332/P, PR333/P trip units with PR120/D-M or PR330/D-M (Modbus RTU) Modbus addresses 0-based or 1-based?

The manufacturer's document numbers registers Modicon 3xxxx/4xxxx (drop the prefix, subtract 1). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. The map gives relative addresses with 30001 (input registers, function 4) and 40001 (holding registers) bases; its example says run-time measures at offset 200 are 30201, relative address 200. The relative address is what goes on the wire with the default 'Standard' addressing type.

What byte order does the ABB SACE PR122/P, PR123/P, PR332/P, PR333/P trip units with PR120/D-M or PR330/D-M (Modbus RTU) use for 32-bit values?

Multi-register values in this map use CDAB (low word first (word-swapped)). Set your client to this order for every 32/64-bit value in the table.

What are the minimum Modbus registers to integrate the ABB SACE PR122/P, PR123/P, PR332/P, PR333/P trip units with PR120/D-M or PR330/D-M (Modbus RTU)?

Start with IR 101 State 2 - flags (CB open/closed, tripped, remote); IR 107 State 8 - latched trips (Which protection tripped); IR 203 L1 current (L1 current); IR 219 V12 line-to-line voltage (V12 voltage); IR 228 Total active power (Total active power); IR 256 Total active energy (Total active energy); HR 0 Command type (Commands (open/close/reset)).

How do I enable Modbus control of the ABB SACE PR122/P, PR123/P, PR332/P, PR333/P trip units with PR120/D-M or PR330/D-M (Modbus RTU)?

Fit the PR120/D-M (or PR330/D-M) module and set address, baud and parity on the trip unit. The breaker must be in Remote mode (state 2 bit 9) for open/close commands.

Where is the official ABB SACE PR122/P, PR123/P, PR332/P, PR333/P trip units with PR120/D-M or PR330/D-M (Modbus RTU) Modbus documentation?

The source is Modbus system Interface for Protection relays PR122/P and PR123/P + communication module PR120/D-M, mounted on CB New Emax; Protection relays PR332/P and PR333/P + communication module PR330/D-M, mounted on CB Emax X1, Tmax T7 and Tmax T8 (1SDH000556R0001), published free by ABB at https://library.e.abb.com/public/89aa30f1720540cfaf50e2e1da987829/1SDH000556R0001.pdf.

More ABB Modbus register maps

Other power & energy meters register maps

All power & energy meters Modbus register maps →

Source: Modbus system Interface for Protection relays PR122/P and PR123/P + communication module PR120/D-M, mounted on CB New Emax; Protection relays PR332/P and PR333/P + communication module PR330/D-M, mounted on CB Emax X1, Tmax T7 and Tmax T8 · 1SDH000556R0001. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.