- ACS800 drive, Standard Control Program 7.x (RMBA-01 Standard Modbus Link)
Variable frequency drive · Modbus register map
ABB ACS800 drive, Standard Control Program 7.x (RMBA-01 Standard Modbus Link) Modbus register map
Updated 17 November 2026
ABB's older industrial AC drive family. Modbus RTU is added with the RMBA-01 adapter module, which the firmware calls the Standard Modbus Link. The drive exposes two three-word data sets in each direction: control word, two references and three auxiliary references from the master, and status word plus five actual values back. This map covers those twelve holding registers with the ABB Drives control and status word bits.
This page lists 12 Modbus registers for the ABB ACS800 drive, Standard Control Program 7.x (RMBA-01 Standard Modbus Link) — 6 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from ABB’s own free documentation (linked below) and checked against it.
- Manufacturer
- ABB
- Model
- ACS800 drive, Standard Control Program 7.x (RMBA-01 Standard Modbus Link)
- Equipment type
- Variable frequency drive
- Registers
- 12 (6 writable)
- Transport
- Modbus RTU
- Default unit ID
- Not stated
- Documented addressing
- Modicon 3xxxx/4xxxx (drop the prefix, subtract 1)
- Firmware
- Standard Control Program 7.x
- Also known as
- ACS800-01, ACS800-02, ACS800-04, ACS800-07, ACS800-11, ACS800-17, ACS800-31, ACS800-37, RMBA-01, ACS800 Standard Control Program
Integration notes: ABB ACS800 drive, Standard Control Program 7.x (RMBA-01 Standard Modbus Link)
Fit the RMBA-01, set 98.02 = STD MODBUS and 98.07 = ABB DRIVES, then set station, baud and parity in group 52. Write the control word and REF1 at 40001/40002 and poll the status word and actual values at 40004-40006; pick what the actuals carry with parameters 92.02-92.06.
Minimum registers to map
Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.
| Register | Name | Type | Why | Access |
|---|---|---|---|---|
| HR 0 | Control Word | BITMAP16 | Control word: start/stop/reset | Read/write |
| HR 1 | Reference 1 | INT16 | Reference 1 (20000 = par. 11.05 for speed/frequency) | Read/write |
| HR 3 | Status Word | BITMAP16 | Status word: ready/running/fault/remote | Read |
| HR 4 | Actual 1 | INT16 | Actual 1 (selected by 92.02) | Read |
| HR 5 | Actual 2 | INT16 | Actual 2 (selected by 92.03) | Read |
Enable Modbus control & writes
Install the RMBA-01 in slot 1 or 2. Set 98.02 Comm. module link = STD MODBUS (this activates group 52) and 98.07 = ABB DRIVES. Set 52.01 station number (1-247), 52.02 baud rate (600-19200) and 52.03 parity. For fieldbus control set the control-location parameters (10.01/10.02 = COMM.CW) and the reference selection (11.03 = COMM.REF1, 11.06 = COMM.REF2). Parameter writes are saved to permanent memory with 16.07 = SAVE.
Communication loss & watchdog
30.18 COMM FAULT FUNC picks the action when the main or auxiliary reference data set stops arriving: FAULT (trip, coast), NO, CONST SP 15 (warning, run at par. 12.16) or LAST SPEED (warning, hold 10 s average speed). 30.19 sets the main data set delay (0.1-60 s), 30.21 the auxiliary data set delay, and 30.20 decides whether fieldbus-driven relay and analogue outputs go to zero or hold their last value.
Byte order & addressing
- Only twelve words exist on the Standard Modbus Link: 40001-40003 and 40007-40009 are written by the master, 40004-40006 and 40010-40012 are read from the drive.
- References and actual values are scaled integers, not engineering units: 20000 equals the maximum set in group 11 for speed/frequency references.
- Status word bits 10, 13 and 14 are user-assignable through parameters 92.07-92.09.
Network setup
- Modbus RTU only; the RMBA-01 does not do Modbus TCP.
- Set 52.01 station number, 52.02 baud and 52.03 parity (NONE1STOPBIT, NONE2STOPBIT, ODD, EVEN) to match the master.
- With 98.02 = CUSTOMISED, 90.04 = 81 and 90.05 = 83 select the Standard Modbus data sets as the main and auxiliary reference sources.
Watch out for
- Bit 10 REMOTE_CMD must be 1 for the fieldbus to command the drive; with it at 0 and a non-zero control word or reference, the drive keeps the last values.
- Starting follows the ABB Drives state machine: first a word with bit 10 set and bits 1-2 set but bit 0 clear (ready to switch on), then bit 0, then bit 3, then bits 4-6 to reach OPERATING.
- REF3 bits 13-15 can drive relay outputs RO1-RO3 (14.01-14.03 = COM.REF3), and REF4/REF5 can drive AO1/AO2 (15.01 = COMM.REF4, 15.06 = COMM.REF5, 20000 = 20 mA).
ABB ACS800 drive, Standard Control Program 7.x (RMBA-01 Standard Modbus Link) Modbus registers
Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.
| Table | Address | Name | Description | Type | Order | Scale | Units | Access | Values / bits |
|---|---|---|---|---|---|---|---|---|---|
| HR | 0doc 40001 | Control Word | Main control word (03.01), ABB Drives profile. | BITMAP16 | Read/write | bit 0 = OFF1 CONTROL: 1 = enter ready to operate, 0 = stop along active deceleration ramp; bit 1 = OFF2 CONTROL: 1 = continue, 0 = emergency off, coast to stop; bit 2 = OFF3 CONTROL: 1 = continue, 0 = emergency stop within par. 22.07 time; bit 3 = INHIBIT_OPERATION: 1 = enable operation (run enable needed), 0 = inhibit; bit 4 = RAMP_OUT_ZERO: 1 = normal, 0 = force ramp output to zero; bit 5 = RAMP_HOLD: 1 = enable ramping, 0 = hold ramp output; bit 6 = RAMP_IN_ZERO: 1 = normal, 0 = force ramp input to zero; bit 7 = RESET: 0 to 1 edge resets an active fault; bit 8 = INCHING_1: not in use; bit 9 = INCHING_2: not in use; bit 10 = REMOTE_CMD: 1 = fieldbus control enabled; bit 11 = EXT CTRL LOC: 1 = select EXT2, 0 = EXT1 (when par. 11.02 = COMM.CW) | |||
| HR | 1doc 40002 | Reference 1 | REF1. Speed/frequency: 20000 = par. 11.05. | INT16 | Read/write | ||||
| HR | 2doc 40003 | Reference 2 | REF2. Speed/frequency: 20000 = par. 11.08; torque/PID per macro. | INT16 | Read/write | ||||
| HR | 3doc 40004 | Status Word | Main status word (03.02), ABB Drives profile. | BITMAP16 | Read | bit 0 = RDY_ON: ready to switch on; bit 1 = RDY_RUN: ready to operate (0 = OFF1 active); bit 2 = RDY_REF: operation enabled; bit 3 = TRIPPED: fault; bit 4 = OFF_2_STA: 1 = OFF2 inactive; bit 5 = OFF_3_STA: 1 = OFF3 inactive; bit 6 = SWC_ON_INHIB: switch-on inhibited; bit 7 = ALARM: warning/alarm active; bit 8 = AT_SETPOINT: actual value within tolerance of reference; bit 9 = REMOTE: 1 = remote (EXT1/EXT2), 0 = local; bit 10 = ABOVE_LIMIT by default; source set by par. 92.07; bit 11 = EXT CTRL LOC: 1 = EXT2 selected; bit 12 = EXT RUN ENABLE: external run enable received; bit 13 = User bit, source set by par. 92.08 (none by default); bit 14 = User bit, source set by par. 92.09 (none by default); bit 15 = Fieldbus adapter (CH0) communication error | |||
| HR | 4doc 40005 | Actual 1 | Signal or parameter chosen by par. 92.02. | INT16 | Read | ||||
| HR | 5doc 40006 | Actual 2 | Signal or parameter chosen by par. 92.03. | INT16 | Read | ||||
| HR | 6doc 40007 | Reference 3 | Written to the parameter chosen by par. 90.01. | INT16 | Read/write | ||||
| HR | 7doc 40008 | Reference 4 | Written to the parameter chosen by par. 90.02. | INT16 | Read/write | ||||
| HR | 8doc 40009 | Reference 5 | Written to the parameter chosen by par. 90.03. | INT16 | Read/write | ||||
| HR | 9doc 40010 | Actual 3 | Signal or parameter chosen by par. 92.04. | INT16 | Read | ||||
| HR | 10doc 40011 | Actual 4 | Signal or parameter chosen by par. 92.05. | INT16 | Read | ||||
| HR | 11doc 40012 | Actual 5 | Signal or parameter chosen by par. 92.06. | INT16 | Read |
Notes on this map
- Only the twelve data-set words that the manual maps to Modicon addresses are listed. The manual gives no Modbus address rule for reaching other drive parameters through the RMBA-01, so none are listed.
- Actual values 1-5 and the destinations of references 3-5 are user-selected through parameters 92.02-92.06 and 90.01-90.03 (format xxyy = group and index), so their meaning and scaling depend on the drive setup and they are left unscaled.
- Control and status word bits are for parameter 98.07 = ABB DRIVES. With the Generic Drive profile the manual says only Rxxx adapters are supported, and with CSA 2.8/3.0 a different word layout applies (not listed).
- REF1/REF2 scaling is the ABB Drives profile scaling: for speed or frequency 20000 corresponds to parameter 11.05 (REF1) or 11.08 (REF2); for torque and PID references the manual gives other end points per macro (10000 or 20000 = par. 11.08).
- Station number, baud rate and parity are set in parameters 52.01-52.03; the manual does not print their factory values, so the defaults are left empty.
Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.
Questions about the ABB ACS800 drive, Standard Control Program 7.x (RMBA-01 Standard Modbus Link)
What Modbus registers does the ABB ACS800 drive, Standard Control Program 7.x (RMBA-01 Standard Modbus Link) have?
This map lists 12 registers: 12 holding registers. 6 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.
Are the ABB ACS800 drive, Standard Control Program 7.x (RMBA-01 Standard Modbus Link) Modbus addresses 0-based or 1-based?
The manufacturer's document numbers registers Modicon 3xxxx/4xxxx (drop the prefix, subtract 1). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. The manual places the data words at Modicon references 40001-40012, so 40001 (control word) is wire address 0 and 40004 (status word) is wire address 3.
What are the minimum Modbus registers to integrate the ABB ACS800 drive, Standard Control Program 7.x (RMBA-01 Standard Modbus Link)?
Start with HR 0 Control Word (Control word: start/stop/reset); HR 1 Reference 1 (Reference 1 (20000 = par. 11.05 for speed/frequency)); HR 3 Status Word (Status word: ready/running/fault/remote); HR 4 Actual 1 (Actual 1 (selected by 92.02)); HR 5 Actual 2 (Actual 2 (selected by 92.03)).
How do I enable Modbus control of the ABB ACS800 drive, Standard Control Program 7.x (RMBA-01 Standard Modbus Link)?
Install the RMBA-01 in slot 1 or 2. Set 98.02 Comm. module link = STD MODBUS (this activates group 52) and 98.07 = ABB DRIVES. Set 52.01 station number (1-247), 52.02 baud rate (600-19200) and 52.03 parity. For fieldbus control set the control-location parameters (10.01/10.02 = COMM.CW) and the reference selection (11.03 = COMM.REF1, 11.06 = COMM.REF2). Parameter writes are saved to permanent memory with 16.07 = SAVE.
What happens when the ABB ACS800 drive, Standard Control Program 7.x (RMBA-01 Standard Modbus Link) loses Modbus communication?
30.18 COMM FAULT FUNC picks the action when the main or auxiliary reference data set stops arriving: FAULT (trip, coast), NO, CONST SP 15 (warning, run at par. 12.16) or LAST SPEED (warning, hold 10 s average speed). 30.19 sets the main data set delay (0.1-60 s), 30.21 the auxiliary data set delay, and 30.20 decides whether fieldbus-driven relay and analogue outputs go to zero or hold their last value.
Where is the official ABB ACS800 drive, Standard Control Program 7.x (RMBA-01 Standard Modbus Link) Modbus documentation?
The source is ACS800 Standard Control Program 7.x Firmware Manual (3AFE64527592 Rev L), revision 2011-08-25, published free by ABB at https://search.abb.com/library/Download.aspx?DocumentID=3AFE64527592&LanguageCode=en&DocumentPartId=1&Action=Launch.
More ABB Modbus register maps
- Variable frequency drive
ABB ACH480 HVAC drive (embedded Modbus RTU)
ACH480 drives running the ACH480 HVAC control program, embedded fieldbus (EFB) Modbus RTU, addressing mode 0 (default); firmware manual 3AXD50000247134 Rev E.
Also known as: ACH480-04, ACH480 HVAC control program - Variable frequency drive
ABB ACH550-UH HVAC drive (embedded Modbus RTU)
ACH550-UH HVAC drives using the embedded fieldbus (EFB) RS-485 port on terminals X1:28-32 with 9802 = STD MODBUS; user's manual 3AUA0000081823 Rev F.
Also known as: ACH550-UH, ACH550 - Variable frequency drive
ABB ACH580 HVAC drive (embedded Modbus RTU)
ACH580 drives running the ACH580 HVAC control program, embedded fieldbus (EFB) set to Modbus RTU, addressing mode 0 (default).
Also known as: ACH580-01, ACH580-07, ACH580-31, ACH580-34, ACH580 HVAC control program - Variable frequency drive
ABB ACQ580 water and wastewater drive (embedded Modbus RTU)
ACQ580 drives running the ACQ580 pump control program, embedded fieldbus (EFB) Modbus RTU, addressing mode 0 (default); firmware manual 3AXD50000035867 Rev H.
Also known as: ACQ580-01, ACQ580-04, ACQ580-07, ACQ580-31, ACQ580-34, ACQ580 pump control program - Variable frequency drive
ABB ACS180 machinery drive (embedded Modbus RTU)
ACS180 drives running the machinery control program, built-in EIA-485 Modbus RTU terminal (embedded fieldbus, EFB), addressing mode 0 (default); firmware manual 3AXD50000467860 Rev D.
Also known as: ACS180-04, ACS180 machinery control program - Variable frequency drive
ABB ACS310 pump and fan drive (embedded Modbus RTU)
ACS310 drives (01E/01U/03E/03U) using the embedded fieldbus: Modbus RTU on the built-in EIA-485 terminals 23-26 or RS-232 on the panel connector; user's manual 3AUA0000044201 Rev D.
Also known as: ACS310-01E, ACS310-01U, ACS310-03E, ACS310-03U - Variable frequency drive
ABB ACS355 machinery drive (embedded Modbus RTU)
ACS355 drives with firmware 5.110 or later using the embedded fieldbus (Modbus RTU) over an FMBA-01 adapter on terminal X3 (EIA-485) or the panel port (RS-232).
Also known as: ACS355-01E, ACS355-03E, ACS355-01U, ACS355-03U, ACS355 with FMBA-01 - Variable frequency drive
ABB ACS380 machinery drive (embedded Modbus RTU)
ACS380 drives running the machinery control program with the BMIO-01 I/O and Modbus RTU module, embedded fieldbus (EFB), addressing mode 0 (default); firmware manual 3AXD50000029275 Rev J.
Also known as: ACS380-04, ACS380 machinery control program, BMIO-01 - Variable frequency drive
ABB ACS480 general purpose drive (embedded Modbus RTU)
ACS480 drives running the ACS480 standard control program, embedded fieldbus (EFB) Modbus RTU, addressing mode 0 (default); firmware manual 3AXD50000047399 Rev G.
Also known as: ACS480-04, ACS480 standard control program - Variable frequency drive
ABB ACS550-01/U1 general purpose drive (embedded Modbus RTU)
ACS550-01 and ACS550-U1 drives (0.75-160 kW / 1-200 hp) using the embedded fieldbus (EFB) RS-485 port on terminals X1:28-32 with 9802 = STD MODBUS; user's manual 3AFE64804588 Rev H.
Also known as: ACS550-01, ACS550-U1 - Variable frequency drive
ABB ACS580 general purpose drive (embedded Modbus RTU)
ACS580 drives running the ACS580 standard control program, embedded fieldbus (EFB) Modbus RTU, addressing mode 0 (default).
Also known as: ACS580-01, ACS580-04, ACS580-07, ACS580 standard control program - Variable frequency drive
ABB ACS880 industrial drive, primary control program (embedded Modbus RTU)
ACS880 drives running the primary control program (AINLX) 3.4x or later, embedded fieldbus (EFB) Modbus RTU on terminal XD2D, 58.33 Addressing mode = Mode 0 (default).
Also known as: ACS880-01, ACS880-04, ACS880-07, ACS880-11, ACS880-17, ACS880-31, ACS880-37, AINLX, ACS880 primary control program - Power meter (branch circuit monitoring)
ABB CMS-700 circuit monitoring system control unit (Modbus RTU / TCP)
ABB CMS-700 control unit with up to 96 CMS branch current sensors, per the CMS-700 user manual (Modbus and SNMP mapping chapter).
Also known as: CMS-700, CMS700, ABB CMS-700, CMS-700 control unit - Variable frequency drive (DC drive)
ABB DCS880 DC drive (embedded Modbus RTU)
DCS880 DC drives, firmware manual revision E, embedded fieldbus (EFB) Modbus RTU on control-board terminal XD2D, ABB Drives profile, 58.33 Addressing mode = Mode 0.
Also known as: DCS880-S01, DCS880-S02, DCS880-H, DCS880-R - Energy meter
ABB EQ meter A41 / A42 (Modbus RTU)
ABB EQ A41 (direct connected) and A42 (transformer connected) DIN meters whose RS-485 port is set to Modbus.
Also known as: A41, A42, EQ A41, EQ A42 - Energy meter
ABB EQ meter A43 / A44 (Modbus RTU)
ABB EQ A43 (direct connected) and A44 (transformer connected) three-phase DIN meters whose RS-485 port is set to Modbus.
Also known as: A43, A44, EQ A43, EQ A44 - Energy meter
ABB EQ meter B21 (Modbus RTU)
ABB EQ B21 single-phase 65 A DIN meter with the RS485 interface set to Modbus.
Also known as: B21, EQ B21 - Energy meter
ABB EQ meter B23 / B24 (Modbus RTU)
ABB EQ B23 (direct, 65 A) and B24 (CT-connected) three-phase DIN meters fitted with the RS485 interface set to Modbus.
Also known as: B23, B24, EQ B23, EQ B24 - Power meter (network analyzer)
ABB M4M 20 / M4M 30 network analyzer
ABB M4M 20 and M4M 30 network analyzers, Modbus RTU and Modbus TCP versions, map v1.3O; items marked M4M 30 only are absent on M4M 20.
Also known as: M4M 20, M4M 30, M4M 20 Modbus, M4M 30 Modbus, M4M 20 Ethernet, M4M 30 Ethernet, M4M 20 I/O, M4M 30 I/O, M4M 2X, M4M 30-M, M4M 32 - Process controller (sensor / PID controller)
ABB Protronic 100/500/550 and Digitric 500 process controllers (Modbus RTU)
ABB Protronic 100/500/550 and Digitric 500 universal process controllers with the RS-485/RS-232 Modbus interface module, interface description 42/62-50040 EN Rev. 04.
Also known as: Protronic 100, Protronic 500, Protronic 550, Digitric 500 - Soft starter (motor control)
ABB PSE softstarter (internal Modbus RTU)
ABB PSE18...PSE370 softstarters using the internal Modbus RTU interface (Modbus RTU adaptor on the front fieldbus connector), document 1SFC132367M0201 Rev B.
Also known as: PSE18, PSE25, PSE30, PSE37, PSE45, PSE60, PSE72, PSE85, PSE105, PSE142, PSE170, PSE210, PSE250, PSE300, PSE370 - Soft starter (motor control)
ABB PSTX softstarter (built-in Modbus RTU)
ABB PSTX30...PSTX1250 softstarters using the built-in Modbus RTU interface on terminals 23/24 (Com3), document 1SFC132089M0201 Rev F.
Also known as: PSTX30, PSTX37, PSTX45, PSTX60, PSTX72, PSTX85, PSTX105, PSTX142, PSTX170, PSTX210, PSTX250, PSTX300, PSTX370, PSTX470, PSTX570, PSTX720, PSTX840, PSTX1050, PSTX1250 - Power meter (DC circuit breaker trip unit)
ABB SACE Emax DC PR122DC / PR123DC trip units with PR120/D-M (Modbus RTU)
ABB SACE PR122DC and PR123DC DC protection trip units with the PR120/D-M communication module, document rev 02 (04/04/2014, SW 3.01 and later).
Also known as: PR122DC, PR123DC, PR120/D-M, Emax DC, SACE Emax DC - Power meter (circuit breaker trip unit)
ABB SACE PR122/P, PR123/P, PR332/P, PR333/P trip units with PR120/D-M or PR330/D-M (Modbus RTU)
ABB SACE PR122/P and PR123/P (Emax) and PR332/P and PR333/P (Emax X1, Tmax T7, Tmax T8) protection releases with the Modbus RTU communication module, per 1SDH000556R0001.
Also known as: PR122/P, PR123/P, PR332/P, PR333/P, PR120/D-M, PR330/D-M, Emax PR122, Emax PR123, Tmax T7 PR332, Emax X1 PR333, Tmax T8 PR332 - Power meter (circuit breaker trip unit)
ABB SACE Tmax PR223DS trip unit (Modbus RTU)
ABB SACE PR223DS electronic trip unit (Tmax moulded-case breakers), software version 02.02, per 1SDH000658R0001.
Also known as: PR223DS, Tmax PR223DS, SACE PR223DS
Other variable frequency drives register maps
- Variable frequency drive
AutomationDirect GS1 series AC drive
All GS1 drives; status addresses and P9.xx serial-communication parameters from chapter 5 of the user manual.
Also known as: GS1-10P2, GS1-10P5, GS1-20P2, GS1-20P5, GS1-21P0, GS1-22P0 - Variable frequency drive
Danfoss VLT AutomationDrive FC 360 (Modbus RTU)
VLT AutomationDrive FC 360 on its built-in RS-485 port with 8-30 Protocol = Modbus RTU and the FC control profile.
Also known as: FC360, FC-360, VLT AutomationDrive FC 360 - Variable frequency drive (HVAC)
Eaton H-Max HVAC drive (embedded Modbus RTU / TCP)
H-Max HVAC drives with the application described in application manual MN04008006E (January 2012).
Also known as: HMX, H-Max HVAC, HMX32, HMX34 - Pump (circulator / E-pump / pump drive)
Grundfos E-pumps (MAGNA3, TPE, CRE, CUE) via CIM 200 / CIM 500
Grundfos E-pumps (CRE/CRNE/CRIE, MTRE, CHIE, CME, TPE, TPE Series 2000, NBE/NKE), CUE drives and MAGNA3 with a CIM/CIU 200, CIM/CIU 500 or built-in SoftCIM.
Also known as: MAGNA3, TPE, TPE Series 2000, CRE, CRNE, CRIE, MTRE, CHIE, CME, NBE, NKE, CUE, MGE, CIM 200, CIU 200, CIM 500, CIU 500, SoftCIM Modbus RTU - Variable frequency drive
Invertek Drives Optidrive E3 IP20 (built-in Modbus RTU)
Invertek Optidrive E3 (ODE-3) IP20 drives on the RJ45 Modbus RTU port, per user guide 82-E3I20-IN V1.05.
Also known as: ODE-3, Optidrive E3, ODE-3 IP20, Optidrive ODE-3 - Variable frequency drive
INVT Goodrive270 (GD270) fan and pump VFD
INVT Goodrive270 fan and pump drives using the built-in RS-485 Modbus RTU port, per the GD270 manual V1.4 (chapter 9).
Also known as: GD270, Goodrive270, GD270 fan and pump drive, GD270 HVAC drive
All variable frequency drives Modbus register maps →
Source: ACS800 Standard Control Program 7.x Firmware Manual · 3AFE64527592 Rev L · rev. 2011-08-25. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.