Variable frequency drive · Modbus register map

ABB ACS800 drive, Standard Control Program 7.x (RMBA-01 Standard Modbus Link) Modbus register map

Updated 17 November 2026

Short answer

ABB's older industrial AC drive family. Modbus RTU is added with the RMBA-01 adapter module, which the firmware calls the Standard Modbus Link. The drive exposes two three-word data sets in each direction: control word, two references and three auxiliary references from the master, and status word plus five actual values back. This map covers those twelve holding registers with the ABB Drives control and status word bits.

This page lists 12 Modbus registers for the ABB ACS800 drive, Standard Control Program 7.x (RMBA-01 Standard Modbus Link) — 6 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from ABB’s own free documentation (linked below) and checked against it.

Manufacturer
ABB
Model
ACS800 drive, Standard Control Program 7.x (RMBA-01 Standard Modbus Link)
Equipment type
Variable frequency drive
Registers
12 (6 writable)
Transport
Modbus RTU
Default unit ID
Not stated
Documented addressing
Modicon 3xxxx/4xxxx (drop the prefix, subtract 1)
Firmware
Standard Control Program 7.x
Also known as
ACS800-01, ACS800-02, ACS800-04, ACS800-07, ACS800-11, ACS800-17, ACS800-31, ACS800-37, RMBA-01, ACS800 Standard Control Program
Source document
ACS800 Standard Control Program 7.x Firmware Manual · 3AFE64527592 Rev L · rev. 2011-08-25
Download CSV all columns JSON Manufacturer PDF ↗

Integration notes: ABB ACS800 drive, Standard Control Program 7.x (RMBA-01 Standard Modbus Link)

Integration in brief

Fit the RMBA-01, set 98.02 = STD MODBUS and 98.07 = ABB DRIVES, then set station, baud and parity in group 52. Write the control word and REF1 at 40001/40002 and poll the status word and actual values at 40004-40006; pick what the actuals carry with parameters 92.02-92.06.

Minimum registers to map

Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.

RegisterNameTypeWhyAccess
HR 0Control WordBITMAP16Control word: start/stop/resetRead/write
HR 1Reference 1INT16Reference 1 (20000 = par. 11.05 for speed/frequency)Read/write
HR 3Status WordBITMAP16Status word: ready/running/fault/remoteRead
HR 4Actual 1INT16Actual 1 (selected by 92.02)Read
HR 5Actual 2INT16Actual 2 (selected by 92.03)Read

Enable Modbus control & writes

Install the RMBA-01 in slot 1 or 2. Set 98.02 Comm. module link = STD MODBUS (this activates group 52) and 98.07 = ABB DRIVES. Set 52.01 station number (1-247), 52.02 baud rate (600-19200) and 52.03 parity. For fieldbus control set the control-location parameters (10.01/10.02 = COMM.CW) and the reference selection (11.03 = COMM.REF1, 11.06 = COMM.REF2). Parameter writes are saved to permanent memory with 16.07 = SAVE.

Communication loss & watchdog

30.18 COMM FAULT FUNC picks the action when the main or auxiliary reference data set stops arriving: FAULT (trip, coast), NO, CONST SP 15 (warning, run at par. 12.16) or LAST SPEED (warning, hold 10 s average speed). 30.19 sets the main data set delay (0.1-60 s), 30.21 the auxiliary data set delay, and 30.20 decides whether fieldbus-driven relay and analogue outputs go to zero or hold their last value.

Byte order & addressing

Network setup

Watch out for

ABB ACS800 drive, Standard Control Program 7.x (RMBA-01 Standard Modbus Link) Modbus registers

Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.

12 of 12 shown
ABB ACS800 drive, Standard Control Program 7.x (RMBA-01 Standard Modbus Link) Modbus register map
TableAddressNameDescriptionTypeOrderScaleUnitsAccessValues / bits
HR0doc 40001Control WordMain control word (03.01), ABB Drives profile.BITMAP16Read/writebit 0 = OFF1 CONTROL: 1 = enter ready to operate, 0 = stop along active deceleration ramp; bit 1 = OFF2 CONTROL: 1 = continue, 0 = emergency off, coast to stop; bit 2 = OFF3 CONTROL: 1 = continue, 0 = emergency stop within par. 22.07 time; bit 3 = INHIBIT_OPERATION: 1 = enable operation (run enable needed), 0 = inhibit; bit 4 = RAMP_OUT_ZERO: 1 = normal, 0 = force ramp output to zero; bit 5 = RAMP_HOLD: 1 = enable ramping, 0 = hold ramp output; bit 6 = RAMP_IN_ZERO: 1 = normal, 0 = force ramp input to zero; bit 7 = RESET: 0 to 1 edge resets an active fault; bit 8 = INCHING_1: not in use; bit 9 = INCHING_2: not in use; bit 10 = REMOTE_CMD: 1 = fieldbus control enabled; bit 11 = EXT CTRL LOC: 1 = select EXT2, 0 = EXT1 (when par. 11.02 = COMM.CW)
HR1doc 40002Reference 1REF1. Speed/frequency: 20000 = par. 11.05.INT16Read/write
HR2doc 40003Reference 2REF2. Speed/frequency: 20000 = par. 11.08; torque/PID per macro.INT16Read/write
HR3doc 40004Status WordMain status word (03.02), ABB Drives profile.BITMAP16Readbit 0 = RDY_ON: ready to switch on; bit 1 = RDY_RUN: ready to operate (0 = OFF1 active); bit 2 = RDY_REF: operation enabled; bit 3 = TRIPPED: fault; bit 4 = OFF_2_STA: 1 = OFF2 inactive; bit 5 = OFF_3_STA: 1 = OFF3 inactive; bit 6 = SWC_ON_INHIB: switch-on inhibited; bit 7 = ALARM: warning/alarm active; bit 8 = AT_SETPOINT: actual value within tolerance of reference; bit 9 = REMOTE: 1 = remote (EXT1/EXT2), 0 = local; bit 10 = ABOVE_LIMIT by default; source set by par. 92.07; bit 11 = EXT CTRL LOC: 1 = EXT2 selected; bit 12 = EXT RUN ENABLE: external run enable received; bit 13 = User bit, source set by par. 92.08 (none by default); bit 14 = User bit, source set by par. 92.09 (none by default); bit 15 = Fieldbus adapter (CH0) communication error
HR4doc 40005Actual 1Signal or parameter chosen by par. 92.02.INT16Read
HR5doc 40006Actual 2Signal or parameter chosen by par. 92.03.INT16Read
HR6doc 40007Reference 3Written to the parameter chosen by par. 90.01.INT16Read/write
HR7doc 40008Reference 4Written to the parameter chosen by par. 90.02.INT16Read/write
HR8doc 40009Reference 5Written to the parameter chosen by par. 90.03.INT16Read/write
HR9doc 40010Actual 3Signal or parameter chosen by par. 92.04.INT16Read
HR10doc 40011Actual 4Signal or parameter chosen by par. 92.05.INT16Read
HR11doc 40012Actual 5Signal or parameter chosen by par. 92.06.INT16Read

Notes on this map

Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.

Questions about the ABB ACS800 drive, Standard Control Program 7.x (RMBA-01 Standard Modbus Link)

What Modbus registers does the ABB ACS800 drive, Standard Control Program 7.x (RMBA-01 Standard Modbus Link) have?

This map lists 12 registers: 12 holding registers. 6 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.

Are the ABB ACS800 drive, Standard Control Program 7.x (RMBA-01 Standard Modbus Link) Modbus addresses 0-based or 1-based?

The manufacturer's document numbers registers Modicon 3xxxx/4xxxx (drop the prefix, subtract 1). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. The manual places the data words at Modicon references 40001-40012, so 40001 (control word) is wire address 0 and 40004 (status word) is wire address 3.

What are the minimum Modbus registers to integrate the ABB ACS800 drive, Standard Control Program 7.x (RMBA-01 Standard Modbus Link)?

Start with HR 0 Control Word (Control word: start/stop/reset); HR 1 Reference 1 (Reference 1 (20000 = par. 11.05 for speed/frequency)); HR 3 Status Word (Status word: ready/running/fault/remote); HR 4 Actual 1 (Actual 1 (selected by 92.02)); HR 5 Actual 2 (Actual 2 (selected by 92.03)).

How do I enable Modbus control of the ABB ACS800 drive, Standard Control Program 7.x (RMBA-01 Standard Modbus Link)?

Install the RMBA-01 in slot 1 or 2. Set 98.02 Comm. module link = STD MODBUS (this activates group 52) and 98.07 = ABB DRIVES. Set 52.01 station number (1-247), 52.02 baud rate (600-19200) and 52.03 parity. For fieldbus control set the control-location parameters (10.01/10.02 = COMM.CW) and the reference selection (11.03 = COMM.REF1, 11.06 = COMM.REF2). Parameter writes are saved to permanent memory with 16.07 = SAVE.

What happens when the ABB ACS800 drive, Standard Control Program 7.x (RMBA-01 Standard Modbus Link) loses Modbus communication?

30.18 COMM FAULT FUNC picks the action when the main or auxiliary reference data set stops arriving: FAULT (trip, coast), NO, CONST SP 15 (warning, run at par. 12.16) or LAST SPEED (warning, hold 10 s average speed). 30.19 sets the main data set delay (0.1-60 s), 30.21 the auxiliary data set delay, and 30.20 decides whether fieldbus-driven relay and analogue outputs go to zero or hold their last value.

Where is the official ABB ACS800 drive, Standard Control Program 7.x (RMBA-01 Standard Modbus Link) Modbus documentation?

The source is ACS800 Standard Control Program 7.x Firmware Manual (3AFE64527592 Rev L), revision 2011-08-25, published free by ABB at https://search.abb.com/library/Download.aspx?DocumentID=3AFE64527592&LanguageCode=en&DocumentPartId=1&Action=Launch.

More ABB Modbus register maps

Other variable frequency drives register maps

All variable frequency drives Modbus register maps →

Source: ACS800 Standard Control Program 7.x Firmware Manual · 3AFE64527592 Rev L · rev. 2011-08-25. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.