  3. Eaton
  4. H-Max HVAC drive (embedded Modbus RTU / TCP)

Variable frequency drive (HVAC) · Modbus register map

Eaton H-Max HVAC drive (embedded Modbus RTU / TCP) Modbus register map

Updated 17 November 2026

Short answer

The Eaton H-Max is an HVAC variable frequency drive with built-in RS-485 (Modbus RTU, N2, BACnet MS/TP) and Ethernet (Modbus TCP, BACnet IP). Its Modbus map uses fixed process-data blocks for control and status plus direct access to application IDs. This map covers the control/status words, speed reference, the default process-data outputs, coils/discrete inputs and the RTU settings.

This page lists 36 Modbus registers for the Eaton H-Max HVAC drive (embedded Modbus RTU / TCP) — 16 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Eaton’s own free documentation (linked below) and checked against it.

Manufacturer
Eaton
Model
H-Max HVAC drive (embedded Modbus RTU / TCP)
Equipment type
Variable frequency drive (HVAC)
Registers
36 (16 writable)
Transport
Modbus RTU, Modbus TCP
Default unit ID
1
Default serial
9600 baud, 8N2
TCP port
502
Documented addressing
1-based (subtract 1 for the wire address)
32-bit word order
ABCD high word first (big-endian)
Also known as
HMX, H-Max HVAC, HMX32, HMX34
Source document
H-Max HVAC Drives Application Manual · MN04008006E · rev. 2012-01 · unofficial copy
Download CSV all columns JSON Manufacturer PDF ↗

Integration notes: Eaton H-Max HVAC drive (embedded Modbus RTU / TCP)

Integration in brief

Select Fieldbus as the remote control place, then write the control word to 2000 and the speed reference (0-10000 = 0-100 %) to 2002 in one write. Read status 2100 and process data out 2103-2110 for frequency, current and fault code.

Minimum registers to map

Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.

RegisterNameTypeWhyAccess
HR 2000FB control wordBITMAP16Control word (run, direction, reset)Read/write
HR 2002FB speed referenceUINT16Speed reference 0.01 %Read/write
HR 2100FB status wordBITMAP16Status wordRead
HR 2103Process data out 1 (output frequency)UINT16Output frequency 0.01 HzRead
HR 2105Process data out 3 (motor current)UINT16Motor current 0.1 ARead
HR 2110Process data out 8 (active fault code)UINT16Active fault codeRead

Enable Modbus control & writes

Select Modbus RTU as the RS-485 protocol (P4.7.1.1, ID 2208), set slave address, baud and parity under I/O and Hardware > RS-485, then set the remote control place to Fieldbus control (Basic Parameters > Start Src Auto) and the auto speed reference to fieldbus.

Communication loss & watchdog

P4.7.3.1.4 RTU communication time-out (default 10 s, 0 = not used) and P4.8.2.1.3 for Modbus TCP raise a fieldbus fault when polling stops.

Byte order & addressing

Network setup

Watch out for

Eaton H-Max HVAC drive (embedded Modbus RTU / TCP) Modbus registers

Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.

36 of 36 shown
Eaton H-Max HVAC drive (embedded Modbus RTU / TCP) Modbus register map
TableAddressNameDescriptionTypeOrderScaleUnitsAccessValues / bits
CO0doc 0001Run/stop (control word bit 0)BITRead/write0 = Stop; 1 = Run
CO1doc 0002Direction (control word bit 1)BITRead/write0 = Forward; 1 = Reverse
CO2doc 0003Fault reset (control word bit 2)BITRead/write0 = No action; 1 = Reset faults
DI0doc 10001Ready (status word bit 0)BITRead0 = Not ready; 1 = Ready
DI1doc 10002Run (status word bit 1)BITRead0 = Stopped; 1 = Running
DI2doc 10003Direction (status word bit 2)BITRead0 = Clockwise; 1 = Counterclockwise
DI3doc 10004Fault (status word bit 3)BITRead0 = No fault; 1 = Faulted
DI4doc 10005Alarm (status word bit 4)BITRead0 = No alarm; 1 = Alarm
DI5doc 10006At reference (status word bit 5)BITRead
DI6doc 10007Zero speed (status word bit 6)BITRead
DI7doc 10008Flux ready (status word bit 7)BITRead
HR36doc ID 37 (register 37)Last active faultCode of the newest fault that has not been reset.UINT16Read
HR2000doc 2001FB control wordLower 16 bits of the 32-bit control word.BITMAP16Read/writebit 0 = Start (1) / stop (0); bit 1 = Reverse (1) / forward (0); bit 2 = Fault reset
HR2002doc 2003FB speed reference0-10000 = 0.00-100.00 % of the speed range.UINT16× 0.01%Read/write
HR2003doc 2004FB process data in 1Application-defined input value.UINT16Read/write
HR2004doc 2005FB process data in 2Application-defined input value.UINT16Read/write
HR2005doc 2006FB process data in 3Application-defined input value.UINT16Read/write
HR2006doc 2007FB process data in 4Application-defined input value.UINT16Read/write
HR2007doc 2008FB process data in 5Application-defined input value.UINT16Read/write
HR2008doc 2009FB process data in 6Application-defined input value.UINT16Read/write
HR2009doc 2010FB process data in 7Application-defined input value.UINT16Read/write
HR2010doc 2011FB process data in 8Application-defined input value.UINT16Read/write
HR2100doc 2101FB status wordLower 16 bits of the 32-bit status word.BITMAP16Readbit 0 = Ready; bit 1 = Running; bit 2 = Counterclockwise; bit 3 = Faulted; bit 4 = Alarm; bit 5 = At reference; bit 6 = Zero speed; bit 7 = Flux ready
HR2102doc 2103FB actual speed0-10000 = 0.00-100.00 %.UINT16× 0.01%Read
HR2103doc 2104Process data out 1 (output frequency)Output frequency in the default process-data mapping.UINT16× 0.01HzRead
HR2104doc 2105Process data out 2 (motor speed)Motor speed in the default process-data mapping.UINT16rpmRead
HR2105doc 2106Process data out 3 (motor current)Motor current in the default process-data mapping.UINT16× 0.1ARead
HR2106doc 2107Process data out 4 (motor torque)Motor torque in the default process-data mapping.UINT16× 0.1%Read
HR2107doc 2108Process data out 5 (motor power)Motor power in the default process-data mapping.UINT16× 0.1%Read
HR2108doc 2109Process data out 6 (motor voltage)Motor voltage in the default process-data mapping.UINT16× 0.1VRead
HR2109doc 2110Process data out 7 (dc link voltage)DC link voltage in the default process-data mapping.UINT16VRead
HR2110doc 2111Process data out 8 (active fault code)Active fault code in the default process-data mapping.UINT16Read
HR2150doc 2151-2152FB status word (32-bit)Full status word; bits 29-31 give the control place.UINT32ABCDReadbit 0 = Ready; bit 1 = Running; bit 2 = Counterclockwise; bit 3 = Faulted; bit 4 = Alarm; bit 5 = At reference; bit 6 = Zero speed; bit 7 = Flux ready
HR2207doc ID 2208 (register 2208)RS-485 protocolUINT16Read/write0 = No protocol; 1 = Modbus RTU; 2 = N2; 3 = BACnet MS/TP
HR2235doc ID 2236 (register 2236)RTU baud rateUINT16Read/write1 = 300; 2 = 600; 3 = 1200; 4 = 2400; 5 = 4800; 6 = 9600 (default); 7 = 19200; 8 = 38400; 9 = 57600
HR2238doc ID 2239 (register 2239)RTU parity typeUINT16Read/write0 = None (2 stop bits, default); 1 = Odd (1 stop bit); 2 = Even (1 stop bit)

Notes on this map

Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.

Questions about the Eaton H-Max HVAC drive (embedded Modbus RTU / TCP)

What Modbus registers does the Eaton H-Max HVAC drive (embedded Modbus RTU / TCP) have?

This map lists 36 registers: 3 coils, 8 discrete inputs, 25 holding registers. 16 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.

Are the Eaton H-Max HVAC drive (embedded Modbus RTU / TCP) Modbus addresses 0-based or 1-based?

The manufacturer's document numbers registers 1-based (subtract 1 for the wire address). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. The manual says data addresses start at zero (holding register 40001 = address 0) and prints the map 1-based; its write example sends start address 07D0h (2000) for control word 2001 and its read example sends 0836h (2102) for register 2103. Subtract 1 from every printed number; application ID n is register n, wire n-1. Coils 0001-0003 are 1-based too (coil 1 = wire 0); discrete inputs printed 10001-10008 are Modicon-style references for wire 0-7.

What byte order does the Eaton H-Max HVAC drive (embedded Modbus RTU / TCP) use for 32-bit values?

Multi-register values in this map use ABCD (high word first (big-endian)). Set your client to this order for every 32/64-bit value in the table.

What are the minimum Modbus registers to integrate the Eaton H-Max HVAC drive (embedded Modbus RTU / TCP)?

Start with HR 2000 FB control word (Control word (run, direction, reset)); HR 2002 FB speed reference (Speed reference 0.01 %); HR 2100 FB status word (Status word); HR 2103 Process data out 1 (output frequency) (Output frequency 0.01 Hz); HR 2105 Process data out 3 (motor current) (Motor current 0.1 A); HR 2110 Process data out 8 (active fault code) (Active fault code).

How do I enable Modbus control of the Eaton H-Max HVAC drive (embedded Modbus RTU / TCP)?

Select Modbus RTU as the RS-485 protocol (P4.7.1.1, ID 2208), set slave address, baud and parity under I/O and Hardware > RS-485, then set the remote control place to Fieldbus control (Basic Parameters > Start Src Auto) and the auto speed reference to fieldbus.

What happens when the Eaton H-Max HVAC drive (embedded Modbus RTU / TCP) loses Modbus communication?

P4.7.3.1.4 RTU communication time-out (default 10 s, 0 = not used) and P4.8.2.1.3 for Modbus TCP raise a fieldbus fault when polling stops.

Where is the official Eaton H-Max HVAC drive (embedded Modbus RTU / TCP) Modbus documentation?

The source is H-Max HVAC Drives Application Manual (MN04008006E), revision 2012-01. Eaton doesn't publish it on its own website, so this map was re-typed from a free copy at https://www.precision-elec.com/wp-content/uploads/2020/12/H-Max-Application-Manual.pdf. It may be an older revision, so check it against the live unit.