- H-Max HVAC drive (embedded Modbus RTU / TCP)
Variable frequency drive (HVAC) · Modbus register map
Eaton H-Max HVAC drive (embedded Modbus RTU / TCP) Modbus register map
Updated 17 November 2026
The Eaton H-Max is an HVAC variable frequency drive with built-in RS-485 (Modbus RTU, N2, BACnet MS/TP) and Ethernet (Modbus TCP, BACnet IP). Its Modbus map uses fixed process-data blocks for control and status plus direct access to application IDs. This map covers the control/status words, speed reference, the default process-data outputs, coils/discrete inputs and the RTU settings.
This page lists 36 Modbus registers for the Eaton H-Max HVAC drive (embedded Modbus RTU / TCP) — 16 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Eaton’s own free documentation (linked below) and checked against it.
- Manufacturer
- Eaton
- Model
- H-Max HVAC drive (embedded Modbus RTU / TCP)
- Equipment type
- Variable frequency drive (HVAC)
- Registers
- 36 (16 writable)
- Transport
- Modbus RTU, Modbus TCP
- Default unit ID
- 1
- Default serial
- 9600 baud, 8N2
- TCP port
- 502
- Documented addressing
- 1-based (subtract 1 for the wire address)
- 32-bit word order
- ABCD high word first (big-endian)
- Also known as
- HMX, H-Max HVAC, HMX32, HMX34
Integration notes: Eaton H-Max HVAC drive (embedded Modbus RTU / TCP)
Select Fieldbus as the remote control place, then write the control word to 2000 and the speed reference (0-10000 = 0-100 %) to 2002 in one write. Read status 2100 and process data out 2103-2110 for frequency, current and fault code.
Minimum registers to map
Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.
| Register | Name | Type | Why | Access |
|---|---|---|---|---|
| HR 2000 | FB control word | BITMAP16 | Control word (run, direction, reset) | Read/write |
| HR 2002 | FB speed reference | UINT16 | Speed reference 0.01 % | Read/write |
| HR 2100 | FB status word | BITMAP16 | Status word | Read |
| HR 2103 | Process data out 1 (output frequency) | UINT16 | Output frequency 0.01 Hz | Read |
| HR 2105 | Process data out 3 (motor current) | UINT16 | Motor current 0.1 A | Read |
| HR 2110 | Process data out 8 (active fault code) | UINT16 | Active fault code | Read |
Enable Modbus control & writes
Select Modbus RTU as the RS-485 protocol (P4.7.1.1, ID 2208), set slave address, baud and parity under I/O and Hardware > RS-485, then set the remote control place to Fieldbus control (Basic Parameters > Start Src Auto) and the auto speed reference to fieldbus.
Communication loss & watchdog
P4.7.3.1.4 RTU communication time-out (default 10 s, 0 = not used) and P4.8.2.1.3 for Modbus TCP raise a fieldbus fault when polling stops.
Byte order & addressing
- Printed addresses are 1-based: subtract 1.
- The 32-bit control/status words are high word first; the 16-bit copies hold only bits 0-15.
Network setup
- RTU defaults: address 1, 9600 baud, no parity with 2 stop bits.
- Terminate both ends of the RS-485 line; the manual recommends active biasing for idle-bus stability.
Watch out for
- The drive ignores fieldbus run commands unless Fieldbus is the active control place (status word bits 29-31).
Eaton H-Max HVAC drive (embedded Modbus RTU / TCP) Modbus registers
Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.
| Table | Address | Name | Description | Type | Order | Scale | Units | Access | Values / bits |
|---|---|---|---|---|---|---|---|---|---|
| CO | 0doc 0001 | Run/stop (control word bit 0) | BIT | Read/write | 0 = Stop; 1 = Run | ||||
| CO | 1doc 0002 | Direction (control word bit 1) | BIT | Read/write | 0 = Forward; 1 = Reverse | ||||
| CO | 2doc 0003 | Fault reset (control word bit 2) | BIT | Read/write | 0 = No action; 1 = Reset faults | ||||
| DI | 0doc 10001 | Ready (status word bit 0) | BIT | Read | 0 = Not ready; 1 = Ready | ||||
| DI | 1doc 10002 | Run (status word bit 1) | BIT | Read | 0 = Stopped; 1 = Running | ||||
| DI | 2doc 10003 | Direction (status word bit 2) | BIT | Read | 0 = Clockwise; 1 = Counterclockwise | ||||
| DI | 3doc 10004 | Fault (status word bit 3) | BIT | Read | 0 = No fault; 1 = Faulted | ||||
| DI | 4doc 10005 | Alarm (status word bit 4) | BIT | Read | 0 = No alarm; 1 = Alarm | ||||
| DI | 5doc 10006 | At reference (status word bit 5) | BIT | Read | |||||
| DI | 6doc 10007 | Zero speed (status word bit 6) | BIT | Read | |||||
| DI | 7doc 10008 | Flux ready (status word bit 7) | BIT | Read | |||||
| HR | 36doc ID 37 (register 37) | Last active fault | Code of the newest fault that has not been reset. | UINT16 | Read | ||||
| HR | 2000doc 2001 | FB control word | Lower 16 bits of the 32-bit control word. | BITMAP16 | Read/write | bit 0 = Start (1) / stop (0); bit 1 = Reverse (1) / forward (0); bit 2 = Fault reset | |||
| HR | 2002doc 2003 | FB speed reference | 0-10000 = 0.00-100.00 % of the speed range. | UINT16 | × 0.01 | % | Read/write | ||
| HR | 2003doc 2004 | FB process data in 1 | Application-defined input value. | UINT16 | Read/write | ||||
| HR | 2004doc 2005 | FB process data in 2 | Application-defined input value. | UINT16 | Read/write | ||||
| HR | 2005doc 2006 | FB process data in 3 | Application-defined input value. | UINT16 | Read/write | ||||
| HR | 2006doc 2007 | FB process data in 4 | Application-defined input value. | UINT16 | Read/write | ||||
| HR | 2007doc 2008 | FB process data in 5 | Application-defined input value. | UINT16 | Read/write | ||||
| HR | 2008doc 2009 | FB process data in 6 | Application-defined input value. | UINT16 | Read/write | ||||
| HR | 2009doc 2010 | FB process data in 7 | Application-defined input value. | UINT16 | Read/write | ||||
| HR | 2010doc 2011 | FB process data in 8 | Application-defined input value. | UINT16 | Read/write | ||||
| HR | 2100doc 2101 | FB status word | Lower 16 bits of the 32-bit status word. | BITMAP16 | Read | bit 0 = Ready; bit 1 = Running; bit 2 = Counterclockwise; bit 3 = Faulted; bit 4 = Alarm; bit 5 = At reference; bit 6 = Zero speed; bit 7 = Flux ready | |||
| HR | 2102doc 2103 | FB actual speed | 0-10000 = 0.00-100.00 %. | UINT16 | × 0.01 | % | Read | ||
| HR | 2103doc 2104 | Process data out 1 (output frequency) | Output frequency in the default process-data mapping. | UINT16 | × 0.01 | Hz | Read | ||
| HR | 2104doc 2105 | Process data out 2 (motor speed) | Motor speed in the default process-data mapping. | UINT16 | rpm | Read | |||
| HR | 2105doc 2106 | Process data out 3 (motor current) | Motor current in the default process-data mapping. | UINT16 | × 0.1 | A | Read | ||
| HR | 2106doc 2107 | Process data out 4 (motor torque) | Motor torque in the default process-data mapping. | UINT16 | × 0.1 | % | Read | ||
| HR | 2107doc 2108 | Process data out 5 (motor power) | Motor power in the default process-data mapping. | UINT16 | × 0.1 | % | Read | ||
| HR | 2108doc 2109 | Process data out 6 (motor voltage) | Motor voltage in the default process-data mapping. | UINT16 | × 0.1 | V | Read | ||
| HR | 2109doc 2110 | Process data out 7 (dc link voltage) | DC link voltage in the default process-data mapping. | UINT16 | V | Read | |||
| HR | 2110doc 2111 | Process data out 8 (active fault code) | Active fault code in the default process-data mapping. | UINT16 | Read | ||||
| HR | 2150doc 2151-2152 | FB status word (32-bit) | Full status word; bits 29-31 give the control place. | UINT32 | ABCD | Read | bit 0 = Ready; bit 1 = Running; bit 2 = Counterclockwise; bit 3 = Faulted; bit 4 = Alarm; bit 5 = At reference; bit 6 = Zero speed; bit 7 = Flux ready | ||
| HR | 2207doc ID 2208 (register 2208) | RS-485 protocol | UINT16 | Read/write | 0 = No protocol; 1 = Modbus RTU; 2 = N2; 3 = BACnet MS/TP | ||||
| HR | 2235doc ID 2236 (register 2236) | RTU baud rate | UINT16 | Read/write | 1 = 300; 2 = 600; 3 = 1200; 4 = 2400; 5 = 4800; 6 = 9600 (default); 7 = 19200; 8 = 38400; 9 = 57600 | ||||
| HR | 2238doc ID 2239 (register 2239) | RTU parity type | UINT16 | Read/write | 0 = None (2 stop bits, default); 1 = Odd (1 stop bit); 2 = Even (1 stop bit) |
Notes on this map
- This copy is hosted by the US distributor Precision Electric; it is Eaton manual MN04008006E (January 2012).
- The 32-bit status word is printed as 2151 = high data, 2152 = low data, so it is high word first (ABCD). The 16-bit control/status words at 2001/2101 carry only the lower 16 bits.
- Process data out 1-8 scales come from the annex table (output frequency 0.01 Hz, speed 1 rpm, current 0.1 A, torque/power 0.1 %, voltage 0.1 V, DC link 1 V); the manual's read example decodes 09C4h at 2104 as 25.00 Hz. They are typed UINT16 here; signedness is not stated.
- Registers 2002 and 2102 are reserved. Process data in 1-8 are application-defined and carry no fixed meaning.
- All holding registers can also be read with function 04 at the same address.
- Left out: monitoring IDs other than 37, because the H-Max monitoring table lists IDs and units but no scale; the operation-day, energy and fault-history counters at 40001-40430, which the manual prints as both 40001 and 440001, so their wire address is ambiguous; the ID map ranges (usable, but empty until configured).
Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.
Questions about the Eaton H-Max HVAC drive (embedded Modbus RTU / TCP)
What Modbus registers does the Eaton H-Max HVAC drive (embedded Modbus RTU / TCP) have?
This map lists 36 registers: 3 coils, 8 discrete inputs, 25 holding registers. 16 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.
Are the Eaton H-Max HVAC drive (embedded Modbus RTU / TCP) Modbus addresses 0-based or 1-based?
The manufacturer's document numbers registers 1-based (subtract 1 for the wire address). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. The manual says data addresses start at zero (holding register 40001 = address 0) and prints the map 1-based; its write example sends start address 07D0h (2000) for control word 2001 and its read example sends 0836h (2102) for register 2103. Subtract 1 from every printed number; application ID n is register n, wire n-1. Coils 0001-0003 are 1-based too (coil 1 = wire 0); discrete inputs printed 10001-10008 are Modicon-style references for wire 0-7.
What byte order does the Eaton H-Max HVAC drive (embedded Modbus RTU / TCP) use for 32-bit values?
Multi-register values in this map use ABCD (high word first (big-endian)). Set your client to this order for every 32/64-bit value in the table.
What are the minimum Modbus registers to integrate the Eaton H-Max HVAC drive (embedded Modbus RTU / TCP)?
Start with HR 2000 FB control word (Control word (run, direction, reset)); HR 2002 FB speed reference (Speed reference 0.01 %); HR 2100 FB status word (Status word); HR 2103 Process data out 1 (output frequency) (Output frequency 0.01 Hz); HR 2105 Process data out 3 (motor current) (Motor current 0.1 A); HR 2110 Process data out 8 (active fault code) (Active fault code).
How do I enable Modbus control of the Eaton H-Max HVAC drive (embedded Modbus RTU / TCP)?
Select Modbus RTU as the RS-485 protocol (P4.7.1.1, ID 2208), set slave address, baud and parity under I/O and Hardware > RS-485, then set the remote control place to Fieldbus control (Basic Parameters > Start Src Auto) and the auto speed reference to fieldbus.
What happens when the Eaton H-Max HVAC drive (embedded Modbus RTU / TCP) loses Modbus communication?
P4.7.3.1.4 RTU communication time-out (default 10 s, 0 = not used) and P4.8.2.1.3 for Modbus TCP raise a fieldbus fault when polling stops.
Where is the official Eaton H-Max HVAC drive (embedded Modbus RTU / TCP) Modbus documentation?
The source is H-Max HVAC Drives Application Manual (MN04008006E), revision 2012-01. Eaton doesn't publish it on its own website, so this map was re-typed from a free copy at https://www.precision-elec.com/wp-content/uploads/2020/12/H-Max-Application-Manual.pdf. It may be an older revision, so check it against the live unit.
More Eaton Modbus register maps
- Motor protection relay (overload relay)
Eaton C440 electronic overload relay (via C441 Ethernet module)
Eaton C440 electronic overload relays read through a C441 Ethernet module, per Table 97 of MN04200002E.
Also known as: C440, C440 overload relay, C441U, C441V - Motor protection relay
Eaton C441 Motor Insight motor protection relay (via C441 Ethernet module)
Eaton C441 Motor Insight relays read through a C441R or C441T plug-in Ethernet module, per Table 96 of MN04200002E.
Also known as: Motor Insight, C441BA, C441BB, C441CA, C441CB, C441DA, C441DB, C441R, C441T - Power meter
Eaton IQ 250 / IQ 260 Electronic Power Meter
Eaton IQ 250 and IQ 260 meters (including the L logging versions), Modbus map Appendix B of IB02601006E.
Also known as: IQ 250, IQ 260, IQ 250L, IQ 260L, IQ250, IQ260 - Power meter
Eaton Power Xpert Meter 1000 Series (PXM 1000/1100/1200/1300)
Eaton PXM 1000 series meters on the built-in RS-485 Modbus RTU port, per user manual MN150009EN (October 2018).
Also known as: PXM 1000, PXM 1100, PXM 1200, PXM 1300, PXM1000, PXM1100, PXM1200, PXM1300, Power Xpert Meter 1000 - Variable frequency drive
Eaton PowerXL DA1 variable frequency drive (Modbus RTU)
Eaton PowerXL DA1 per the Modbus RTU communication manual MN040018EN, edition 12/22.
Also known as: DA1, PowerXL DA1, DA1-12, DA1-32, DA1-34, DA1-35 - Variable frequency drive
Eaton PowerXL DB1 compact drive (Modbus RTU)
Eaton PowerXL DB1 per the Modbus RTU communication manual MN040018EN, edition 12/22.
Also known as: DB1, PowerXL DB1, DB1-12, DB1-32, DB1-34 - Variable frequency drive
Eaton PowerXL DC1 compact drive (Modbus RTU)
Eaton PowerXL DC1 per the Modbus RTU communication manual MN040018EN, edition 12/22.
Also known as: DC1, PowerXL DC1, DC1-1D, DC1-12, DC1-32, DC1-34, DC1-S2 - Variable frequency drive (variable speed starter)
Eaton PowerXL DE1 variable speed starter (Modbus RTU)
Eaton PowerXL DE1 per the Modbus RTU communication manual MN040018EN, edition 12/22.
Also known as: DE1, DE11, PowerXL DE1, PowerXL DE11, DE1-12, DE1-34, DE11-12, DE11-34 - Variable frequency drive
Eaton PowerXL DG1 / DH1 drives (on-board Modbus RTU / TCP)
PowerXL DG1 general-purpose and DH1 HVAC drives per PowerXL Series VFD Communication Manual MN040010EN (June 2018).
Also known as: DG1, DH1, PowerXL DG1, PowerXL DH1, DG1 general purpose drive, DH1 HVAC drive - Soft starter
Eaton S611 soft starter (via C441 Ethernet module)
Eaton S611 soft starters read through a C441R or C441T plug-in Ethernet module, per Table 98 of MN04200002E.
Also known as: S611, S611 soft starter, C441R, C441T - Soft starter
Eaton S811+ soft starter (via C441 Ethernet module)
Eaton S811+ soft starters read through a C441 Ethernet module, per Table 99 of MN04200002E.
Also known as: S811+, S811 Plus, S811+ soft starter, C441U, C441V
Other variable frequency drives register maps
- Pump (circulator / E-pump / pump drive)
Grundfos E-pumps (MAGNA3, TPE, CRE, CUE) via CIM 200 / CIM 500
Grundfos E-pumps (CRE/CRNE/CRIE, MTRE, CHIE, CME, TPE, TPE Series 2000, NBE/NKE), CUE drives and MAGNA3 with a CIM/CIU 200, CIM/CIU 500 or built-in SoftCIM.
Also known as: MAGNA3, TPE, TPE Series 2000, CRE, CRNE, CRIE, MTRE, CHIE, CME, NBE, NKE, CUE, MGE, CIM 200, CIU 200, CIM 500, CIU 500, SoftCIM Modbus RTU - Variable frequency drive
Invertek Drives Optidrive E3 IP20 (built-in Modbus RTU)
Invertek Optidrive E3 (ODE-3) IP20 drives on the RJ45 Modbus RTU port, per user guide 82-E3I20-IN V1.05.
Also known as: ODE-3, Optidrive E3, ODE-3 IP20, Optidrive ODE-3 - Variable frequency drive
INVT Goodrive270 (GD270) fan and pump VFD
INVT Goodrive270 fan and pump drives using the built-in RS-485 Modbus RTU port, per the GD270 manual V1.4 (chapter 9).
Also known as: GD270, Goodrive270, GD270 fan and pump drive, GD270 HVAC drive - Variable frequency drive
Lenze MC Series drives MC1000 / MC3000 (Modbus RTU)
Lenze AC Tech MC1000 and MC3000 Series drives, software 213-083 rev 13 (parameter configurations 188-190); reference guide RG-MCMOD.
Also known as: MC1000, MC3000, MC Series, Lenze AC Tech MC, RG-MCMOD - Variable frequency drive
Mitsubishi Electric FR-A800 inverter (RS-485 terminals, Modbus RTU)
FR-A800 series inverters (FR-A820/A840/A842/A846, incl. -GF) using the built-in RS-485 terminals with Pr.549 = 1 (MODBUS RTU); Instruction Manual (Detailed) revision P.
Also known as: FR-A820, FR-A840, FR-A842, FR-A846, FR-A800-GF, FR-A800 series - Variable frequency drive
Schneider Electric Altivar Machine ATV340 (embedded Modbus serial / Modbus TCP)
ATV340 drives on the built-in Modbus serial port; Ethernet versions (ATV340...N4E) expose the same addresses on embedded Modbus TCP. Per Communication Parameters file NVE61728 V4.6.
Also known as: ATV340, Altivar 340, Altivar Machine ATV340, ATV340U, ATV340D, ATV340...N4E
All variable frequency drives Modbus register maps →
Source: H-Max HVAC Drives Application Manual · MN04008006E · rev. 2012-01 · unofficial copy. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.