Variable frequency drive (variable speed starter) · Modbus register map
Eaton PowerXL DE1 variable speed starter (Modbus RTU) Modbus register map
Updated 19 November 2026
The PowerXL DE1 talks Modbus RTU on its RJ45 RS-485 socket. Eaton numbers every value by an ID: a small process-data block (command, speed reference, status/fault word, speed, current) plus parameter IDs. Every value is a single 16-bit register with an implied decimal point. This map covers the process data and the communication settings.
This page lists 16 Modbus registers for the Eaton PowerXL DE1 variable speed starter (Modbus RTU) — 7 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Eaton’s own free documentation (linked below) and checked against it.
- Manufacturer
- Eaton
- Model
- PowerXL DE1 variable speed starter (Modbus RTU)
- Equipment type
- Variable frequency drive (variable speed starter)
- Registers
- 16 (7 writable)
- Transport
- Modbus RTU
- Default unit ID
- 1
- Default serial
- 115200 baud, 8N1
- Documented addressing
- 1-based (subtract 1 for the wire address)
- Also known as
- DE1, DE11, PowerXL DE1, PowerXL DE11, DE1-12, DE1-34, DE11-12, DE11-34
Integration notes: Eaton PowerXL DE1 variable speed starter (Modbus RTU)
Write the speed reference to ID 2 and the command word to ID 1 (bit 0 = run), then read IDs 6-8 for status, speed and current. The control-source parameter must select Modbus first.
Minimum registers to map
Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.
| Register | Name | Type | Why | Access |
|---|---|---|---|---|
| HR 0 | Fieldbus command | BITMAP16 | Run/stop/reset command word | Read/write |
| HR 1 | Fieldbus speed reference | UINT16 | Speed reference (0.1 Hz) | Read/write |
| HR 5 | Status and fault word | BITMAP16 | Status bits and fault number | Read |
| HR 6 | Actual speed | UINT16 | Actual frequency | Read |
| HR 7 | Motor current | UINT16 | Motor current | Read |
| HR 139 | Local process data source | UINT16 | Control source must select Modbus | Read/write |
Enable Modbus control & writes
Set P-12 = 3 (Modbus control). DI1 must be held high (enable) when running from Modbus. Address is P-47, baud P-35, data format P-48, timeout P-36.
Communication loss & watchdog
P-36: 0 = no action (default), 1-4 = trip after 30 ms / 100 ms / 1 s / 3 s, 5-8 = ramp to stop after 30 ms / 100 ms / 1 s / 3 s.
Byte order & addressing
- Register = ID - 1 on the wire; tools with a +1 offset take the ID directly.
- Function codes 03, 06, 16 and 23 only; at most 11 registers per read.
- The high byte of ID 6 is a fault number, not flags.
Network setup
- P-47 = Modbus address (1-255, default 1); P-35 = baud (default 4 = 115.2 kbit/s); P-48 = data format.
- The RS-485 link is on the RJ45 socket.
Watch out for
- Without the DI1/STO enable the drive reports 'Stop' and will not run from Modbus.
- Set bit 2 of the command word to reset a fault.
Eaton PowerXL DE1 variable speed starter (Modbus RTU) Modbus registers
Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.
| Table | Address | Name | Description | Type | Order | Scale | Units | Access | Values / bits |
|---|---|---|---|---|---|---|---|---|---|
| HR | 0doc ID 1 | Fieldbus command | Control word: run, direction, reset, coast, quick stop. | BITMAP16 | Read/write | bit 0 = 0 = stop, 1 = run (operational); bit 1 = 0 = forward (clockwise), 1 = reverse; bit 2 = 1 = reset fault; bit 3 = 1 = coast to stop; bit 5 = 1 = quick stop (ramp 2); bit 6 = 1 = run at fixed frequency FF1; bit 7 = 1 = force the setpoint to 0 | |||
| HR | 1doc ID 2 | Fieldbus speed reference | Setpoint frequency, limited to the min/max frequency parameters. | UINT16 | × 0.1 | Hz | Read/write | ||
| HR | 5doc ID 6 | Status and fault word | Low byte = status bits, high byte = fault number. | BITMAP16 | Read | bit 0 = 1 = ready (READY); bit 1 = 1 = running (RUN); bit 2 = 0 = forward, 1 = reverse; bit 3 = 1 = fault (FAULT); bit 4 = 1 = actual frequency equals setpoint (0 = ramping); bit 5 = 1 = zero speed; bit 6 = 1 = speed control active; bit 7 = Hardware enable: 0 = no, 1 = yes; bit 8-15 = Fault word: the fault number (see notes), 0 = no fault | |||
| HR | 6doc ID 7 | Actual speed | Output frequency. | UINT16 | × 0.1 | Hz | Read | ||
| HR | 7doc ID 8 | Motor current | UINT16 | × 0.1 | A | Read | |||
| HR | 10doc ID 11 | Digital inputs | Input states; the lowest bit is DI1. | BITMAP16 | Read | bit 0 = DI1; bit 1 = DI2 | |||
| HR | 11doc ID 12 | Drive type code | Part-number code: frame size, voltage class, phases and power index as hex digits. | UINT16 | Read | ||||
| HR | 14doc ID 15 | Control section software version | Two implied decimals. | UINT16 | × 0.01 | Read | |||
| HR | 15doc ID 16 | Power section software version | Two implied decimals. | UINT16 | × 0.01 | Read | |||
| HR | 16doc ID 17 | Drive recognition | Fixed family code; DE1 reads 8 (DE11: 9). | UINT16 | Read | ||||
| HR | 22doc 23 (P0-08) | DC-link voltage | UINT16 | V | Read | ||||
| HR | 139doc 140 (P-12) | Local process data source | Selects where run commands and the speed reference come from. | UINT16 | Read/write | 0 = Terminal control; 1 = Keypad, forward only; 2 = Keypad, forward and reverse; 3 = Modbus RTU control; 4 = CANopen; 9 = SmartWire-DT control and speed reference; 10 = SmartWire-DT control, terminal speed reference; 11 = Terminal control, SmartWire-DT speed reference; 13 = SmartWire-DT control and reference, digital input enables | |||
| HR | 162doc 163 (P-35) | RS-485 baud rate | UINT16 | Read/write | 0 = 9.6 kbit/s; 1 = 19.2 kbit/s; 2 = 38.4 kbit/s; 3 = 57.6 kbit/s; 4 = 115.2 kbit/s | ||||
| HR | 163doc 164 (P-36) | Modbus comms timeout | Action and delay after loss of Modbus telegrams. | UINT16 | Read/write | 0 = No action; 1 = Trip after 30 ms; 2 = Trip after 100 ms; 3 = Trip after 1000 ms; 4 = Trip after 3000 ms; 5 = Ramp to stop after 30 ms; 6 = Ramp to stop after 100 ms; 7 = Ramp to stop after 1000 ms; 8 = Ramp to stop after 3000 ms | |||
| HR | 174doc 175 (P-47) | Modbus address | 1-255; set to 1 when a SmartWire-DT module is used. | UINT16 | Read/write | ||||
| HR | 175doc 176 (P-48) | Modbus data format | 8 data bits; parity and stop bits. | UINT16 | Read/write | 0 = No parity, 1 stop bit; 1 = No parity, 2 stop bits; 2 = Odd parity, 1 stop bit; 3 = Even parity, 1 stop bit |
Notes on this map
- Every value is one 16-bit register; the decimal point is implied (a displayed 0.3 A is sent as 3).
- The manual does not state signedness for the process data; they are typed UINT16 because their ranges are non-negative (direction is a status bit).
- The power (ID 13) and voltage range (ID 14) words are left out because their meaning depends on the drive's kW/HP setting.
- Fault numbers in the high byte of ID 6 for the DE1 (decimal, as printed in table 11): 0 no-Flt (no fault), 1 OI-b brake overcurrent, 2 OL-br brake resistor overload, 3 O-I output overcurrent, 4 I.t-trP motor overload, 5 PS-trp hardware overcurrent, 6 O.Volt DC overvoltage, 7 U.Volt DC undervoltage, 8 O-t heatsink overtemperature, 9 U-t undertemperature, 10 P-dEf defaults loaded, 11 E-trip external fault, 12 SC-ObS keypad/PC comms error, 13 FlT-dc DC ripple too high, 14 P-LOss input phase loss, 15 h O-I output overcurrent, 16 Th-flt heatsink thermistor fault, 17 dAtA-F memory error, 18 4-20 F analog input out of range. The 'Stop' display (enable signal missing) is listed without a number and is not a fault.
- Stop bits: section 2.3.2 says the default is 1 stop bit, but the DE1 table prints default 1 for P-48 (= no parity, 2 stop bits), so stop_bits is left null.
- DE1 has no torque (ID 9), output power (ID 10) or ramp-time (ID 4) process data, and no serial number over Modbus.
- Left out: heatsink temperature (24), whose range starts at -10 °C but whose data-format cell is blank, so signedness is not stated; and the run-hour words 25/26 (hours plus a separate min/sec word with no data format).
- The DE1 baud table prints option 0 as '960 Bit/s'; it is read here as 9.6 kbit/s, matching the other drives.
Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.
Questions about the Eaton PowerXL DE1 variable speed starter (Modbus RTU)
What Modbus registers does the Eaton PowerXL DE1 variable speed starter (Modbus RTU) have?
This map lists 16 registers: 16 holding registers. 7 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.
Are the Eaton PowerXL DE1 variable speed starter (Modbus RTU) Modbus addresses 0-based or 1-based?
The manufacturer's document numbers registers 1-based (subtract 1 for the wire address). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. The manual numbers registers from ID 1. Its frame examples read status ID 6 with start address 0005h and write command ID 1 to address 0000h, so ID n is wire address n-1.
What are the minimum Modbus registers to integrate the Eaton PowerXL DE1 variable speed starter (Modbus RTU)?
Start with HR 0 Fieldbus command (Run/stop/reset command word); HR 1 Fieldbus speed reference (Speed reference (0.1 Hz)); HR 5 Status and fault word (Status bits and fault number); HR 6 Actual speed (Actual frequency); HR 7 Motor current (Motor current); HR 139 Local process data source (Control source must select Modbus).
How do I enable Modbus control of the Eaton PowerXL DE1 variable speed starter (Modbus RTU)?
Set P-12 = 3 (Modbus control). DI1 must be held high (enable) when running from Modbus. Address is P-47, baud P-35, data format P-48, timeout P-36.
What happens when the Eaton PowerXL DE1 variable speed starter (Modbus RTU) loses Modbus communication?
P-36: 0 = no action (default), 1-4 = trip after 30 ms / 100 ms / 1 s / 3 s, 5-8 = ramp to stop after 30 ms / 100 ms / 1 s / 3 s.
Where is the official Eaton PowerXL DE1 variable speed starter (Modbus RTU) Modbus documentation?
The source is PowerXL Modbus RTU Communication manual for Variable Frequency Drives / Variable Speed Starters DA1, DB1, DC1, DE1 (MN040018EN), revision 2022-12, published free by Eaton at https://es-assets.eaton.com/DOCUMENTATION/AWB_MANUALS/MN040018_EN.pdf.
More Eaton Modbus register maps
- Motor protection relay (overload relay)
Eaton C440 electronic overload relay (via C441 Ethernet module)
Eaton C440 electronic overload relays read through a C441 Ethernet module, per Table 97 of MN04200002E.
Also known as: C440, C440 overload relay, C441U, C441V - Motor protection relay
Eaton C441 Motor Insight motor protection relay (via C441 Ethernet module)
Eaton C441 Motor Insight relays read through a C441R or C441T plug-in Ethernet module, per Table 96 of MN04200002E.
Also known as: Motor Insight, C441BA, C441BB, C441CA, C441CB, C441DA, C441DB, C441R, C441T - Variable frequency drive (HVAC)
Eaton H-Max HVAC drive (embedded Modbus RTU / TCP)
H-Max HVAC drives with the application described in application manual MN04008006E (January 2012).
Also known as: HMX, H-Max HVAC, HMX32, HMX34 - Power meter
Eaton IQ 250 / IQ 260 Electronic Power Meter
Eaton IQ 250 and IQ 260 meters (including the L logging versions), Modbus map Appendix B of IB02601006E.
Also known as: IQ 250, IQ 260, IQ 250L, IQ 260L, IQ250, IQ260 - Power meter
Eaton Power Xpert Meter 1000 Series (PXM 1000/1100/1200/1300)
Eaton PXM 1000 series meters on the built-in RS-485 Modbus RTU port, per user manual MN150009EN (October 2018).
Also known as: PXM 1000, PXM 1100, PXM 1200, PXM 1300, PXM1000, PXM1100, PXM1200, PXM1300, Power Xpert Meter 1000 - Variable frequency drive
Eaton PowerXL DA1 variable frequency drive (Modbus RTU)
Eaton PowerXL DA1 per the Modbus RTU communication manual MN040018EN, edition 12/22.
Also known as: DA1, PowerXL DA1, DA1-12, DA1-32, DA1-34, DA1-35 - Variable frequency drive
Eaton PowerXL DB1 compact drive (Modbus RTU)
Eaton PowerXL DB1 per the Modbus RTU communication manual MN040018EN, edition 12/22.
Also known as: DB1, PowerXL DB1, DB1-12, DB1-32, DB1-34 - Variable frequency drive
Eaton PowerXL DC1 compact drive (Modbus RTU)
Eaton PowerXL DC1 per the Modbus RTU communication manual MN040018EN, edition 12/22.
Also known as: DC1, PowerXL DC1, DC1-1D, DC1-12, DC1-32, DC1-34, DC1-S2 - Variable frequency drive
Eaton PowerXL DG1 / DH1 drives (on-board Modbus RTU / TCP)
PowerXL DG1 general-purpose and DH1 HVAC drives per PowerXL Series VFD Communication Manual MN040010EN (June 2018).
Also known as: DG1, DH1, PowerXL DG1, PowerXL DH1, DG1 general purpose drive, DH1 HVAC drive - Soft starter
Eaton S611 soft starter (via C441 Ethernet module)
Eaton S611 soft starters read through a C441R or C441T plug-in Ethernet module, per Table 98 of MN04200002E.
Also known as: S611, S611 soft starter, C441R, C441T - Soft starter
Eaton S811+ soft starter (via C441 Ethernet module)
Eaton S811+ soft starters read through a C441 Ethernet module, per Table 99 of MN04200002E.
Also known as: S811+, S811 Plus, S811+ soft starter, C441U, C441V
Other variable frequency drives register maps
- Variable frequency drive
Inovance MD200 series compact AC drive
Inovance MD200 single- and three-phase compact drives using the RS-485 Modbus RTU port, per user guide 19012113 rev. C02.
Also known as: MD200, MD200T, MD200S, MD200-NC, Inovance MD200 - Variable frequency drive
INVT Goodrive10 (GD10) mini VFD
INVT Goodrive10 mini drives using the built-in RS-485 Modbus RTU port, per the GD10 VFD manual V2.9 (chapter 7).
Also known as: GD10, Goodrive10, GD10 mini VFD - Variable frequency drive
INVT Goodrive350A (GD350A) high-performance multifunction VFD
INVT Goodrive350A drives using the built-in RS-485 Modbus RTU port, per the GD350A manual V1.3 (chapter 9).
Also known as: GD350A, Goodrive350A, GD350A series - Variable frequency drive
Lovato Electric VT1 series variable speed drives (Modbus RTU / ASCII)
Lovato VT1 series drives on the built-in RS-485 port, per communication manual I646 GB I 02 21 (Modbus part).
Also known as: VT1, Lovato VT1, VT1 series - Variable frequency drive
NORD Drivesystems SK 540E / SK 545E frequency inverter (built-in Modbus RTU)
NORD SK 500E-series inverters from SK 540E up (SK 540E, SK 545E) on the RS485 interface, per supplementary manual BU 0050 (GB-3111).
Also known as: SK 540E, SK 545E, SK 54xE, NORDAC SK 500E series (SK 540E and above) - Actuator / valve driver (I/O module, 3 analog outputs)
Seneca Z-3AO 3-channel analog output module
Seneca Z-3AO DIN-rail module with three voltage/current outputs and RS-485 Modbus RTU, per user manual MI00260-2-EN.
Also known as: Z-3AO
All variable frequency drives Modbus register maps →
Source: PowerXL Modbus RTU Communication manual for Variable Frequency Drives / Variable Speed Starters DA1, DB1, DC1, DE1 · MN040018EN · rev. 2022-12. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.