Variable frequency drive · Modbus register map
INVT Goodrive10 (GD10) mini VFD Modbus register map
Updated 19 November 2026
INVT's small V/F drive for fans, pumps and light machinery. The built-in RS-485 port speaks Modbus RTU. A reduced command block (2000H-2003H, 200AH, 200BH, 200DH) takes run commands and setpoints, status and fault words sit at 2100H-2103H, monitors at 3000H onwards, and each function parameter has its own hex address. This map covers those plus the run-source, P14 serial and fault parameters.
This page lists 38 Modbus registers for the INVT Goodrive10 (GD10) mini VFD — 16 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from INVT’s own free documentation (linked below) and checked against it.
- Manufacturer
- INVT
- Model
- Goodrive10 (GD10) mini VFD
- Equipment type
- Variable frequency drive
- Registers
- 38 (16 writable)
- Transport
- Modbus RTU
- Default unit ID
- 1
- Default serial
- 19200 baud, 8E1
- Documented addressing
- hexadecimal, 0-based
- Also known as
- GD10, Goodrive10, GD10 mini VFD
Integration notes: INVT Goodrive10 (GD10) mini VFD
Set P00.01 = 2 so run commands come from Modbus, and P00.06 = 8 so the speed reference does too. Write the frequency to 2001H in 0.01 Hz and a run/stop code to 2000H, then poll 2100H, 2102H and 3000H-3004H.
Minimum registers to map
Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.
| Register | Name | Type | Why | Access |
|---|---|---|---|---|
| HR 8192 | Communication control command | UINT16 | Run / stop / fault reset command | Read/write |
| HR 8193 | Communication frequency setting | UINT16 | Speed reference in 0.01 Hz | Read/write |
| HR 8448 | VFD status word 1 | UINT16 | Running / stopped / fault state | Read |
| HR 8450 | VFD fault code | UINT16 | Active fault code | Read |
| HR 12288 | Running frequency | UINT16 | Output frequency | Read |
| HR 12292 | Output current | UINT16 | Output current | Read |
| HR 12290 | Bus voltage | UINT16 | DC bus voltage | Read |
Enable Modbus control & writes
P00.01 = 2 gives the run command to communication. P00.06 (A frequency source) = 8 makes 2001H the speed reference. P09.00 must select Modbus before 2002H/2003H act as PID reference/feedback. P14.00-P14.02 set address, baud and format.
Communication loss & watchdog
P14.04 sets a bus-silence timeout (0.0 s = off). When it runs out the drive raises CE (fault 18) and P14.05 decides whether it coasts, keeps running or stops with its stop mode.
Byte order & addressing
- Parameter Pxx.yy sits at hex register (xx << 8) | yy: P14.01 = 0E01H, P07.27 = 071BH.
- Setting the top bit of a parameter address (for example 8007H for P00.07) writes RAM only and spares the EEPROM; those aliases cannot be read.
- Scaled values follow the decimals printed in the parameter list or address table (one decimal = x10, two decimals = x100), per the manual's fieldbus-scale section. Registers with a negative printed range are typed INT16 here.
Network setup
- P14.00 slave address (default 1), P14.01 baud (default 4 = 19200 bps), P14.02 format (default 1 = E,8,1 RTU).
- Read with function 03H; write with 06H (this manual documents no 10H multi-write).
Watch out for
- Frequent parameter writes wear the EEPROM; use the RAM alias (address + 8000H) for values that change often.
- Some parameters cannot be changed while the drive runs; the drive answers with exception 08H.
INVT Goodrive10 (GD10) mini VFD Modbus registers
Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.
| Table | Address | Name | Description | Type | Order | Scale | Units | Access | Values / bits |
|---|---|---|---|---|---|---|---|---|---|
| HR | 1doc P00.01 (0001H) | P00.01 Run command channel | Set 2 so run/stop comes from 2000H. | UINT16 | Read/write | 0 = Keypad; 1 = Terminal; 2 = Communication | |||
| HR | 3doc P00.03 (0003H) | P00.03 Max. output frequency | Fmax; ceiling for 2001H. | UINT16 | × 0.01 | Hz | Read/write | ||
| HR | 6doc P00.06 (0006H) | P00.06 A frequency command channel | Set to the Modbus option so 2001H sets the speed; other values pick local sources. | UINT16 | Read/write | 8 = Modbus communication setting | |||
| HR | 1819doc P07.27 (071BH) | P07.27 Present fault type | Same codes as 2102H. | UINT16 | Read | 0 = No fault; 4 = Overcurrent during acceleration (OC1); 5 = Overcurrent during deceleration (OC2); 6 = Overcurrent during constant speed running (OC3); 7 = Overvoltage during acceleration (OV1); 8 = Overvoltage during deceleration (OV2); 9 = Overvoltage during constant speed running (OV3); 10 = Bus undervoltage (UV); 11 = Motor overload (OL1); 12 = VFD overload (OL2); 15 = Rectifier module overheat (OH1); 16 = Inverter module overheat (OH2); 17 = External fault (EF); 18 = RS485 communication fault (CE); 21 = EEPROM operation fault (EEP); 22 = PID feedback offline fault (PIDE); 24 = Running time reached (END); 25 = Electronic overload fault (OL3); 36 = Electronic underload fault (LL) | |||
| HR | 3584doc P14.00 (0E00H) | P14.00 Local communication address | 1-247; 0 is broadcast. | UINT16 | Read/write | ||||
| HR | 3585doc P14.01 (0E01H) | P14.01 Baud rate | UINT16 | Read/write | 0 = 1200 bps; 1 = 2400 bps; 2 = 4800 bps; 3 = 9600 bps; 4 = 19200 bps; 5 = 38400 bps | ||||
| HR | 3586doc P14.02 (0E02H) | P14.02 Data bit check | UINT16 | Read/write | 0 = N,8,1 RTU; 1 = E,8,1 RTU; 2 = O,8,1 RTU; 3 = N,8,2 RTU; 4 = E,8,2 RTU; 5 = O,8,2 RTU | ||||
| HR | 3587doc P14.03 (0E03H) | P14.03 Communication response delay | 0-200 ms extra delay before replying. | UINT16 | ms | Read/write | |||
| HR | 3588doc P14.04 (0E04H) | P14.04 Communication timeout | 0.0 = off; otherwise CE fault after this much bus silence. | UINT16 | × 0.1 | s | Read/write | ||
| HR | 3589doc P14.05 (0E05H) | P14.05 Transmission fault processing | UINT16 | Read/write | 0 = Alarm and coast to stop; 1 = Keep running, no alarm; 2 = Stop by stop mode, no alarm (communication mode only); 3 = Stop by stop mode, no alarm (any mode) | ||||
| HR | 8192doc 2000H | Communication control command | Needs P00.01 = 2. | UINT16 | Read/write | 1 = Forward running; 2 = Reverse running; 3 = Forward jogging; 4 = Reverse jogging; 5 = Stop; 6 = Coast to stop; 7 = Fault reset; 8 = Jogging stop | |||
| HR | 8193doc 2001H | Communication frequency setting | 0 to Fmax. | UINT16 | × 0.01 | Hz | Read/write | ||
| HR | 8194doc 2002H | PID reference | 0-1000 = 0-100.0 %. | UINT16 | × 0.1 | % | Read/write | ||
| HR | 8195doc 2003H | PID feedback | 0-1000 = 0-100.0 %. | UINT16 | × 0.1 | % | Read/write | ||
| HR | 8202doc 200AH | Virtual input terminal command | Range 0x000-0x1FF. | BITMAP16 | Read/write | ||||
| HR | 8203doc 200BH | Virtual output terminal command | Range 0x00-0x0F. | BITMAP16 | Read/write | ||||
| HR | 8205doc 200DH | AO output setting 1 | -1000 to 1000 = -100.0 to 100.0 %. | INT16 | × 0.1 | % | Read/write | ||
| HR | 8448doc 2100H | VFD status word 1 | UINT16 | Read | 1 = Forward running; 2 = Running (printed as forward running twice); 3 = Stop; 4 = Fault; 5 = POFF state | ||||
| HR | 8449doc 2101H | VFD status word 2 | BITMAP16 | Read | bit 0 = 1 = bus voltage established; bit 1 = Motor select bit 0 (00 = motor 1); bit 2 = Motor select bit 1; bit 3 = 1 = synchronous motor, 0 = asynchronous; bit 4 = 1 = overload pre-alarm; bit 5 = Control source bit 0 (bits 5-6: 00 keypad, 01 terminal, 10 communication); bit 6 = Control source bit 1 | ||||
| HR | 8450doc 2102H | VFD fault code | Codes match P07.27. | UINT16 | Read | 0 = No fault; 4 = Overcurrent during acceleration (OC1); 5 = Overcurrent during deceleration (OC2); 6 = Overcurrent during constant speed running (OC3); 7 = Overvoltage during acceleration (OV1); 8 = Overvoltage during deceleration (OV2); 9 = Overvoltage during constant speed running (OV3); 10 = Bus undervoltage (UV); 11 = Motor overload (OL1); 12 = VFD overload (OL2); 15 = Rectifier module overheat (OH1); 16 = Inverter module overheat (OH2); 17 = External fault (EF); 18 = RS485 communication fault (CE); 21 = EEPROM operation fault (EEP); 22 = PID feedback offline fault (PIDE); 24 = Running time reached (END); 25 = Electronic overload fault (OL3); 36 = Electronic underload fault (LL) | |||
| HR | 8451doc 2103H | VFD identification code | 0x010D = Goodrive10 (high byte 0x01 Goodrive series). | UINT16 | Read | ||||
| HR | 12288doc 3000H | Running frequency | UINT16 | × 0.01 | Hz | Read | |||
| HR | 12289doc 3001H | Set frequency | UINT16 | × 0.01 | Hz | Read | |||
| HR | 12290doc 3002H | Bus voltage | UINT16 | × 0.1 | V | Read | |||
| HR | 12291doc 3003H | Output voltage | UINT16 | V | Read | ||||
| HR | 12292doc 3004H | Output current | UINT16 | × 0.1 | A | Read | |||
| HR | 12293doc 3005H | Rotating speed | UINT16 | rpm | Read | ||||
| HR | 12294doc 3006H | Output power | -300.0 to 300.0 %. | INT16 | × 0.1 | % | Read | ||
| HR | 12295doc 3007H | Output torque | -250.0 to 250.0 %. | INT16 | × 0.1 | % | Read | ||
| HR | 12296doc 3008H | PID setting | -100.0 to 100.0 %. | INT16 | × 0.1 | % | Read | ||
| HR | 12297doc 3009H | PID feedback | -100.0 to 100.0 %. | INT16 | × 0.1 | % | Read | ||
| HR | 12298doc 300AH | Input terminal state | Range 000-1FF. | BITMAP16 | Read | ||||
| HR | 12299doc 300BH | Output terminal state | Range 000-1FF. | BITMAP16 | Read | ||||
| HR | 12300doc 300CH | Analog input 1 | 0.00-10.00 V. | UINT16 | × 0.01 | V | Read | ||
| HR | 12301doc 300DH | Analog input 2 | 0.00-10.00 V. | UINT16 | × 0.01 | V | Read | ||
| HR | 12306doc 3012H | Current step of multi-step speed | 0-15. | UINT16 | Read | ||||
| HR | 12308doc 3014H | External count value | UINT16 | Read | |||||
| HR | 12309doc 3015H | Torque setting | -300.0 to 300.0 %. | INT16 | × 0.1 | % | Read |
Notes on this map
- Every register is a single 16-bit word; there are no 32-bit values in this map.
- Any function parameter can be read or written at (group << 8) | index; only the parameters an integrator needs most are listed here.
- 3016H (identification code) and 5000H (fault code) are printed without range or unit, so they are left out; 2102H and 2103H carry the same information.
- GD10 has a smaller command block than other Goodrive drives: only 2000H-2003H, 200AH, 200BH and 200DH are listed. 300EH, 300FH, 3011H and 3013H are reserved.
- 200BH is printed as 'Virtual input terminal command, range 0x00-0x0F' (the same name as 200AH); the range matches the virtual output command of other Goodrive drives.
- 2100H code 0002H is printed as 'Forward running' a second time; sister INVT manuals use it for reverse running.
- This manual has no P00.02 entry; P00.01 = 2 is enough to take run commands from Modbus.
- Fault codes are the ones listed for GD10 (no 1-3, 13-14, 19-20, 23, 26-35).
Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.
Questions about the INVT Goodrive10 (GD10) mini VFD
What Modbus registers does the INVT Goodrive10 (GD10) mini VFD have?
This map lists 38 registers: 38 holding registers. 16 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.
Are the INVT Goodrive10 (GD10) mini VFD Modbus addresses 0-based or 1-based?
The manufacturer's document numbers registers hexadecimal, 0-based. Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. Addresses are printed in hex and go on the wire unchanged. Parameter P00.00 sits at 0000H and the manual's example frames carry the address bytes directly (writing P00.01 is sent as 01 06 00 01 00 03, and the read example asks for state word 2100H).
What are the minimum Modbus registers to integrate the INVT Goodrive10 (GD10) mini VFD?
Start with HR 8192 Communication control command (Run / stop / fault reset command); HR 8193 Communication frequency setting (Speed reference in 0.01 Hz); HR 8448 VFD status word 1 (Running / stopped / fault state); HR 8450 VFD fault code (Active fault code); HR 12288 Running frequency (Output frequency); HR 12292 Output current (Output current); HR 12290 Bus voltage (DC bus voltage).
How do I enable Modbus control of the INVT Goodrive10 (GD10) mini VFD?
P00.01 = 2 gives the run command to communication. P00.06 (A frequency source) = 8 makes 2001H the speed reference. P09.00 must select Modbus before 2002H/2003H act as PID reference/feedback. P14.00-P14.02 set address, baud and format.
What happens when the INVT Goodrive10 (GD10) mini VFD loses Modbus communication?
P14.04 sets a bus-silence timeout (0.0 s = off). When it runs out the drive raises CE (fault 18) and P14.05 decides whether it coasts, keeps running or stops with its stop mode.
Where is the official INVT Goodrive10 (GD10) mini VFD Modbus documentation?
The source is Goodrive10 Series Mini VFD Operation Manual (V2.9), revision 2025-04, published free by INVT at https://www.invt.com/uploads/file1/20250902/GD10%20VFD%20Manual_V2.9.pdf.
More INVT Modbus register maps
- Variable frequency drive
INVT Goodrive20 (GD20) general-purpose VFD
INVT Goodrive20 drives using the built-in RS-485 Modbus port, per the GD20 VFD manual V2.1 (chapter 7, communication protocol).
Also known as: GD20, Goodrive20, GD20-EU, GD20-UL, GD20 vector VFD - Variable frequency drive
INVT Goodrive200A (GD200A) general-purpose VFD
INVT Goodrive200A drives using the built-in RS-485 Modbus port, per the GD200A manual V3.1 (chapter 9).
Also known as: GD200A, Goodrive200A, GD200A general VFD - Variable frequency drive
INVT Goodrive270 (GD270) fan and pump VFD
INVT Goodrive270 fan and pump drives using the built-in RS-485 Modbus RTU port, per the GD270 manual V1.4 (chapter 9).
Also known as: GD270, Goodrive270, GD270 fan and pump drive, GD270 HVAC drive - Variable frequency drive
INVT Goodrive300 (GD300) vector VFD
INVT Goodrive300 open-loop vector drives using the built-in RS-485 Modbus RTU port, per the GD300 VFD manual V3.6 (chapter 10).
Also known as: GD300, Goodrive300, GD300 vector VFD - Variable frequency drive
INVT Goodrive35 (GD35) closed-loop vector VFD
INVT Goodrive35 closed-loop vector drives using the built-in RS-485 Modbus RTU port, per the GD35 VFD manual V4.0 (communication protocol chapter).
Also known as: GD35, Goodrive35, GD35 vector VFD - Variable frequency drive
INVT Goodrive350 (GD350) high-performance multifunction VFD
INVT Goodrive350 drives (not GD350A) using the built-in RS-485 Modbus RTU port, per the GD350 manual V1.1 (communication chapter).
Also known as: GD350, Goodrive350, GD350 series - Variable frequency drive
INVT Goodrive350A (GD350A) high-performance multifunction VFD
INVT Goodrive350A drives using the built-in RS-485 Modbus RTU port, per the GD350A manual V1.3 (chapter 9).
Also known as: GD350A, Goodrive350A, GD350A series
Other variable frequency drives register maps
- Variable frequency drive
Lovato Electric VT1 series variable speed drives (Modbus RTU / ASCII)
Lovato VT1 series drives on the built-in RS-485 port, per communication manual I646 GB I 02 21 (Modbus part).
Also known as: VT1, Lovato VT1, VT1 series - Variable frequency drive
NORD Drivesystems SK 540E / SK 545E frequency inverter (built-in Modbus RTU)
NORD SK 500E-series inverters from SK 540E up (SK 540E, SK 545E) on the RS485 interface, per supplementary manual BU 0050 (GB-3111).
Also known as: SK 540E, SK 545E, SK 54xE, NORDAC SK 500E series (SK 540E and above) - Actuator / valve driver (I/O module, 3 analog outputs)
Seneca Z-3AO 3-channel analog output module
Seneca Z-3AO DIN-rail module with three voltage/current outputs and RS-485 Modbus RTU, per user manual MI00260-2-EN.
Also known as: Z-3AO - Variable frequency drive
TECO-Westinghouse E510 Compact (E510N1) inverter (Modbus RTU/ASCII)
TECO-Westinghouse E510 Compact (E510N1) inverters with the built-in RS-485 port (CON2), per communication addendum DOCUMENT-TECO-E510N1-AC002 Ver01 (2017-08).
Also known as: E510N1, E510s, TECO E510 Compact - Variable frequency drive
Vacon VACON 10 AC drive (built-in Modbus RTU)
VACON 10 micro drives on the built-in RS-485 Modbus RTU port, per complete user manual DPD00717F1 (software FW0135V010).
Also known as: VACON 10, Vacon 10, VACON0010 - Variable frequency drive
Yaskawa FP605 industrial fan and pump drive (MEMOBUS/Modbus RTU)
Yaskawa FP605 drives using the built-in RS-485 port (MEMOBUS/Modbus RTU), per technical reference SIEPC7106171F.
Also known as: CIPR-FP6, FP605 drive, FP605 AC Drive for Industrial Fan and Pump Applications
All variable frequency drives Modbus register maps →
Source: Goodrive10 Series Mini VFD Operation Manual · V2.9 · rev. 2025-04. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.