Variable frequency drive · Modbus register map
INVT Goodrive20 (GD20) general-purpose VFD Modbus register map
Updated 19 November 2026
INVT's compact open-loop vector drive for general machinery, pumps and fans. The built-in RS-485 port speaks Modbus RTU or ASCII. Commands and setpoints go to the 2000H block, status and fault words sit at 2100H-2103H, live monitors at 3000H onwards, and every function parameter has its own hex address. This map covers that whole command/status/monitor block plus the run-source, P14 serial and fault-history parameters.
This page lists 48 Modbus registers for the INVT Goodrive20 (GD20) general-purpose VFD — 24 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from INVT’s own free documentation (linked below) and checked against it.
- Manufacturer
- INVT
- Model
- Goodrive20 (GD20) general-purpose VFD
- Equipment type
- Variable frequency drive
- Registers
- 48 (24 writable)
- Transport
- Modbus RTU, Modbus ASCII
- Default unit ID
- 1
- Default serial
- 19200 baud, 8E1
- Documented addressing
- hexadecimal, 0-based
- Also known as
- GD20, Goodrive20, GD20-EU, GD20-UL, GD20 vector VFD
- Source document
- Goodrive20 Series VFD Operation Manual · V2.1
Integration notes: INVT Goodrive20 (GD20) general-purpose VFD
Set P00.01 = 2 so run commands come from Modbus, and P00.06 = 8 so the speed reference does too. Write the frequency to 2001H in 0.01 Hz and a run/stop code to 2000H, then poll 2100H, 2102H and 3000H-3004H.
Minimum registers to map
Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.
| Register | Name | Type | Why | Access |
|---|---|---|---|---|
| HR 8192 | Communication control command | UINT16 | Run / stop / fault reset command | Read/write |
| HR 8193 | Communication frequency setting | UINT16 | Speed reference in 0.01 Hz | Read/write |
| HR 8448 | VFD status word 1 | UINT16 | Running / stopped / fault state | Read |
| HR 8450 | VFD fault code | UINT16 | Active fault code | Read |
| HR 12288 | Running frequency | UINT16 | Output frequency | Read |
| HR 12292 | Output current | UINT16 | Output current | Read |
| HR 12290 | Bus voltage | UINT16 | DC bus voltage | Read |
Enable Modbus control & writes
P00.01 = 2 gives the run command to communication. P00.06 (A frequency source) = 8 makes 2001H the speed reference. P09.00 must select Modbus before 2002H/2003H act as PID reference/feedback. P14.00-P14.02 set address, baud and format.
Communication loss & watchdog
P14.04 sets a bus-silence timeout (0.0 s = off). When it runs out the drive raises CE (fault 18) and P14.05 decides whether it coasts, keeps running or stops with its stop mode.
Byte order & addressing
- Parameter Pxx.yy sits at hex register (xx << 8) | yy: P14.01 = 0E01H, P07.27 = 071BH.
- Setting the top bit of a parameter address (for example 8007H for P00.07) writes RAM only and spares the EEPROM; those aliases cannot be read.
- Scaled values follow the decimals printed in the parameter list or address table (one decimal = x10, two decimals = x100), per the manual's fieldbus-scale section. Registers with a negative printed range are typed INT16 here.
Network setup
- P14.00 slave address (default 1), P14.01 baud (default 4 = 19200 bps), P14.02 format (default 1 = E,8,1 RTU).
- Read with function 03H; write with 06H or 10H.
Watch out for
- Frequent parameter writes wear the EEPROM; use the RAM alias (address + 8000H) for values that change often.
- Some parameters cannot be changed while the drive runs; the drive answers with exception 08H.
INVT Goodrive20 (GD20) general-purpose VFD Modbus registers
Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.
| Table | Address | Name | Description | Type | Order | Scale | Units | Access | Values / bits |
|---|---|---|---|---|---|---|---|---|---|
| HR | 1doc P00.01 (0001H) | P00.01 Run command channel | Set 2 so run/stop comes from 2000H. | UINT16 | Read/write | 0 = Keypad; 1 = Terminal; 2 = Communication | |||
| HR | 3doc P00.03 (0003H) | P00.03 Max. output frequency | Fmax; ceiling for 2001H. | UINT16 | × 0.01 | Hz | Read/write | ||
| HR | 6doc P00.06 (0006H) | P00.06 A frequency command channel | Set to the Modbus option so 2001H sets the speed; other values pick local sources. | UINT16 | Read/write | 8 = Modbus communication setting | |||
| HR | 1819doc P07.27 (071BH) | P07.27 Present fault type | Same codes as 2102H. | UINT16 | Read | 0 = No fault; 1 = Inverter unit U phase protection (OUt1); 2 = Inverter unit V phase protection (OUt2); 3 = Inverter unit W phase protection (OUt3); 4 = Overcurrent during acceleration (OC1); 5 = Overcurrent during deceleration (OC2); 6 = Overcurrent during constant speed running (OC3); 7 = Overvoltage during acceleration (OV1); 8 = Overvoltage during deceleration (OV2); 9 = Overvoltage during constant speed running (OV3); 10 = Bus undervoltage (UV); 11 = Motor overload (OL1); 12 = VFD overload (OL2); 13 = Phase loss on input side (SPI); 14 = Phase loss on output side (SPO); 15 = Rectifier module overheat (OH1); 16 = Inverter module overheat (OH2); 17 = External fault (EF); 18 = RS485 communication fault (CE); 19 = Current detection fault (ItE); 20 = Motor autotuning fault (tE); 21 = EEPROM operation fault (EEP); 22 = PID feedback offline fault (PIDE); 23 = Braking unit fault (bCE); 24 = Running time reached (END); 25 = Electronic overload (OL3); 26 = Keypad communication error (PCE); 27 = Parameter upload error (UPE); 28 = Parameter download error (DNE); 32 = To-ground short-circuit fault 1 (ETH1); 33 = To-ground short-circuit fault 2 (ETH2); 34 = Speed deviation fault (dEu); 35 = Mal-adjustment fault (STo); 36 = Underload fault (LL) | |||
| HR | 3584doc P14.00 (0E00H) | P14.00 Local communication address | 1-247; 0 is broadcast. | UINT16 | Read/write | ||||
| HR | 3585doc P14.01 (0E01H) | P14.01 Baud rate | UINT16 | Read/write | 0 = 1200 bps; 1 = 2400 bps; 2 = 4800 bps; 3 = 9600 bps; 4 = 19200 bps; 5 = 38400 bps; 6 = 57600 bps | ||||
| HR | 3586doc P14.02 (0E02H) | P14.02 Data bit check | UINT16 | Read/write | 0 = N,8,1 RTU; 1 = E,8,1 RTU; 2 = O,8,1 RTU; 3 = N,8,2 RTU; 4 = E,8,2 RTU; 5 = O,8,2 RTU; 6 = N,7,1 ASCII; 7 = E,7,1 ASCII; 8 = O,7,1 ASCII; 9 = N,7,2 ASCII; 10 = E,7,2 ASCII; 11 = O,7,2 ASCII; 12 = N,8,1 ASCII; 13 = E,8,1 ASCII; 14 = O,8,1 ASCII; 15 = N,8,2 ASCII; 16 = E,8,2 ASCII; 17 = O,8,2 ASCII | ||||
| HR | 3587doc P14.03 (0E03H) | P14.03 Communication response delay | 0-200 ms extra delay before replying. | UINT16 | ms | Read/write | |||
| HR | 3588doc P14.04 (0E04H) | P14.04 Communication timeout | 0.0 = off; otherwise CE fault after this much bus silence. | UINT16 | × 0.1 | s | Read/write | ||
| HR | 3589doc P14.05 (0E05H) | P14.05 Transmission fault processing | UINT16 | Read/write | 0 = Alarm and coast to stop; 1 = Keep running, no alarm; 2 = Stop by stop mode, no alarm (communication mode only); 3 = Stop by stop mode, no alarm (any mode) | ||||
| HR | 8192doc 2000H | Communication control command | Needs P00.01 = 2. | UINT16 | Read/write | 1 = Forward running; 2 = Reverse running; 3 = Forward jogging; 4 = Reverse jogging; 5 = Stop; 6 = Coast to stop; 7 = Fault reset; 8 = Jogging stop | |||
| HR | 8193doc 2001H | Communication frequency setting | 0 to Fmax. | UINT16 | × 0.01 | Hz | Read/write | ||
| HR | 8194doc 2002H | PID reference | 0-1000 = 0-100.0 %. | UINT16 | × 0.1 | % | Read/write | ||
| HR | 8195doc 2003H | PID feedback | 0-1000 = 0-100.0 %. | UINT16 | × 0.1 | % | Read/write | ||
| HR | 8196doc 2004H | Torque setting | -3000 to 3000; 1000 = 100.0 % of motor rated current. | INT16 | × 0.1 | % | Read/write | ||
| HR | 8197doc 2005H | Forward upper frequency limit | 0 to Fmax. | UINT16 | × 0.01 | Hz | Read/write | ||
| HR | 8198doc 2006H | Reverse upper frequency limit | 0 to Fmax. | UINT16 | × 0.01 | Hz | Read/write | ||
| HR | 8199doc 2007H | Motoring torque upper limit | 0-3000; 1000 = 100.0 % of motor rated current. | UINT16 | × 0.1 | % | Read/write | ||
| HR | 8200doc 2008H | Braking torque upper limit | 0-3000; 1000 = 100.0 % of motor rated current. | UINT16 | × 0.1 | % | Read/write | ||
| HR | 8201doc 2009H | Special control command word | Bits 0-1 select the motor (00 = motor 1, 01 = motor 2, 10 = motor 3, 11 = motor 4). | BITMAP16 | Read/write | bit 2 = 1 = torque control prohibited; bit 3 = 1 = clear power consumption; bit 4 = 1 = pre-exciting; bit 5 = 1 = DC braking | |||
| HR | 8202doc 200AH | Virtual input terminal command | Virtual input terminals, range 0x000-0x1FF. | BITMAP16 | Read/write | ||||
| HR | 8203doc 200BH | Virtual output terminal command | Virtual output terminals, range 0x00-0x0F. | BITMAP16 | Read/write | ||||
| HR | 8204doc 200CH | Voltage setting (V/F separation) | 0-1000 = 0-100.0 % of motor rated voltage. | UINT16 | × 0.1 | % | Read/write | ||
| HR | 8205doc 200DH | AO output setting 1 | -1000 to 1000 = -100.0 to 100.0 %. | INT16 | × 0.1 | % | Read/write | ||
| HR | 8206doc 200EH | AO output setting 2 | -1000 to 1000 = -100.0 to 100.0 %. | INT16 | × 0.1 | % | Read/write | ||
| HR | 8448doc 2100H | VFD status word 1 | UINT16 | Read | 1 = Forward running; 2 = Running (printed as forward running twice); 3 = Stop; 4 = Fault; 5 = POFF state; 6 = Pre-exciting | ||||
| HR | 8449doc 2101H | VFD status word 2 | BITMAP16 | Read | bit 0 = 1 = bus voltage established; bit 1 = Motor select bit 0 (bits 1-2: 00 motor 1 .. 11 motor 4); bit 2 = Motor select bit 1; bit 3 = 1 = synchronous motor, 0 = asynchronous; bit 4 = 1 = overload pre-alarm; bit 5 = Control source bit 0 (bits 5-6: 00 keypad, 01 terminal, 10 communication); bit 6 = Control source bit 1 | ||||
| HR | 8450doc 2102H | VFD fault code | Codes match P07.27. | UINT16 | Read | 0 = No fault; 1 = Inverter unit U phase protection (OUt1); 2 = Inverter unit V phase protection (OUt2); 3 = Inverter unit W phase protection (OUt3); 4 = Overcurrent during acceleration (OC1); 5 = Overcurrent during deceleration (OC2); 6 = Overcurrent during constant speed running (OC3); 7 = Overvoltage during acceleration (OV1); 8 = Overvoltage during deceleration (OV2); 9 = Overvoltage during constant speed running (OV3); 10 = Bus undervoltage (UV); 11 = Motor overload (OL1); 12 = VFD overload (OL2); 13 = Phase loss on input side (SPI); 14 = Phase loss on output side (SPO); 15 = Rectifier module overheat (OH1); 16 = Inverter module overheat (OH2); 17 = External fault (EF); 18 = RS485 communication fault (CE); 19 = Current detection fault (ItE); 20 = Motor autotuning fault (tE); 21 = EEPROM operation fault (EEP); 22 = PID feedback offline fault (PIDE); 23 = Braking unit fault (bCE); 24 = Running time reached (END); 25 = Electronic overload (OL3); 26 = Keypad communication error (PCE); 27 = Parameter upload error (UPE); 28 = Parameter download error (DNE); 32 = To-ground short-circuit fault 1 (ETH1); 33 = To-ground short-circuit fault 2 (ETH2); 34 = Speed deviation fault (dEu); 35 = Mal-adjustment fault (STo); 36 = Underload fault (LL) | |||
| HR | 8451doc 2103H | VFD identification code | 0x0106 = Goodrive20 (high byte 0x01 Goodrive series). | UINT16 | Read | ||||
| HR | 12288doc 3000H | Running frequency | UINT16 | × 0.01 | Hz | Read | |||
| HR | 12289doc 3001H | Set frequency | UINT16 | × 0.01 | Hz | Read | |||
| HR | 12290doc 3002H | Bus voltage | UINT16 | × 0.1 | V | Read | |||
| HR | 12291doc 3003H | Output voltage | UINT16 | V | Read | ||||
| HR | 12292doc 3004H | Output current | UINT16 | × 0.1 | A | Read | |||
| HR | 12293doc 3005H | Rotating speed | UINT16 | rpm | Read | ||||
| HR | 12294doc 3006H | Output power | -300.0 to 300.0 %. | INT16 | × 0.1 | % | Read | ||
| HR | 12295doc 3007H | Output torque | -250.0 to 250.0 %. | INT16 | × 0.1 | % | Read | ||
| HR | 12296doc 3008H | PID setting | -100.0 to 100.0 %. | INT16 | × 0.1 | % | Read | ||
| HR | 12297doc 3009H | PID feedback | -100.0 to 100.0 %. | INT16 | × 0.1 | % | Read | ||
| HR | 12298doc 300AH | Input terminal state | Range 000-1FF. | BITMAP16 | Read | ||||
| HR | 12299doc 300BH | Output terminal state | Range 000-1FF. | BITMAP16 | Read | ||||
| HR | 12300doc 300CH | Analog input 1 | 0.00-10.00 V. | UINT16 | × 0.01 | V | Read | ||
| HR | 12301doc 300DH | Analog input 2 | 0.00-10.00 V. | UINT16 | × 0.01 | V | Read | ||
| HR | 12302doc 300EH | Analog input 3 | -10.00 to 10.00 V. | INT16 | × 0.01 | V | Read | ||
| HR | 12306doc 3012H | Current step of multi-step speed | 0-15. | UINT16 | Read | ||||
| HR | 12307doc 3013H | External length value | UINT16 | Read | |||||
| HR | 12308doc 3014H | External count value | UINT16 | Read | |||||
| HR | 12309doc 3015H | Torque setting | -300.0 to 300.0 %. | INT16 | × 0.1 | % | Read |
Notes on this map
- Every register is a single 16-bit word; there are no 32-bit values in this map.
- Any function parameter can be read or written at (group << 8) | index; only the parameters an integrator needs most are listed here.
- 3016H (identification code) and 5000H (fault code) are printed without range or unit, so they are left out; 2102H and 2103H carry the same information.
- 2100H code 0002H is printed as 'Forward running' a second time in this manual (sister INVT manuals use it for reverse running); treat it as running.
- 3010H (high-speed pulse input) is printed as 0.00-50.00 kHz with a unit of 0.01 Hz, so its scale is unclear and it is left out.
- Fault codes 29-31 are not listed for GD20 and 32-36 follow the manual's P07.27 list.
Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.
Questions about the INVT Goodrive20 (GD20) general-purpose VFD
What Modbus registers does the INVT Goodrive20 (GD20) general-purpose VFD have?
This map lists 48 registers: 48 holding registers. 24 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.
Are the INVT Goodrive20 (GD20) general-purpose VFD Modbus addresses 0-based or 1-based?
The manufacturer's document numbers registers hexadecimal, 0-based. Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. Addresses are printed in hex and go on the wire unchanged. Parameter P00.00 sits at 0000H and the manual's example frames carry the address bytes directly (reading state word 2100H is sent as 01 03 21 00 00 01, and writing P00.01 as 01 06 00 01 00 03).
What are the minimum Modbus registers to integrate the INVT Goodrive20 (GD20) general-purpose VFD?
Start with HR 8192 Communication control command (Run / stop / fault reset command); HR 8193 Communication frequency setting (Speed reference in 0.01 Hz); HR 8448 VFD status word 1 (Running / stopped / fault state); HR 8450 VFD fault code (Active fault code); HR 12288 Running frequency (Output frequency); HR 12292 Output current (Output current); HR 12290 Bus voltage (DC bus voltage).
How do I enable Modbus control of the INVT Goodrive20 (GD20) general-purpose VFD?
P00.01 = 2 gives the run command to communication. P00.06 (A frequency source) = 8 makes 2001H the speed reference. P09.00 must select Modbus before 2002H/2003H act as PID reference/feedback. P14.00-P14.02 set address, baud and format.
What happens when the INVT Goodrive20 (GD20) general-purpose VFD loses Modbus communication?
P14.04 sets a bus-silence timeout (0.0 s = off). When it runs out the drive raises CE (fault 18) and P14.05 decides whether it coasts, keeps running or stops with its stop mode.
Where is the official INVT Goodrive20 (GD20) general-purpose VFD Modbus documentation?
The source is Goodrive20 Series VFD Operation Manual (V2.1), published free by INVT at https://www.invt.com/uploads/file1/20250902/GD20%20VFD%20Manual_V2.1.pdf.
More INVT Modbus register maps
- Variable frequency drive
INVT Goodrive10 (GD10) mini VFD
INVT Goodrive10 mini drives using the built-in RS-485 Modbus RTU port, per the GD10 VFD manual V2.9 (chapter 7).
Also known as: GD10, Goodrive10, GD10 mini VFD - Variable frequency drive
INVT Goodrive200A (GD200A) general-purpose VFD
INVT Goodrive200A drives using the built-in RS-485 Modbus port, per the GD200A manual V3.1 (chapter 9).
Also known as: GD200A, Goodrive200A, GD200A general VFD - Variable frequency drive
INVT Goodrive270 (GD270) fan and pump VFD
INVT Goodrive270 fan and pump drives using the built-in RS-485 Modbus RTU port, per the GD270 manual V1.4 (chapter 9).
Also known as: GD270, Goodrive270, GD270 fan and pump drive, GD270 HVAC drive - Variable frequency drive
INVT Goodrive300 (GD300) vector VFD
INVT Goodrive300 open-loop vector drives using the built-in RS-485 Modbus RTU port, per the GD300 VFD manual V3.6 (chapter 10).
Also known as: GD300, Goodrive300, GD300 vector VFD - Variable frequency drive
INVT Goodrive35 (GD35) closed-loop vector VFD
INVT Goodrive35 closed-loop vector drives using the built-in RS-485 Modbus RTU port, per the GD35 VFD manual V4.0 (communication protocol chapter).
Also known as: GD35, Goodrive35, GD35 vector VFD - Variable frequency drive
INVT Goodrive350 (GD350) high-performance multifunction VFD
INVT Goodrive350 drives (not GD350A) using the built-in RS-485 Modbus RTU port, per the GD350 manual V1.1 (communication chapter).
Also known as: GD350, Goodrive350, GD350 series - Variable frequency drive
INVT Goodrive350A (GD350A) high-performance multifunction VFD
INVT Goodrive350A drives using the built-in RS-485 Modbus RTU port, per the GD350A manual V1.3 (chapter 9).
Also known as: GD350A, Goodrive350A, GD350A series
Other variable frequency drives register maps
- Variable frequency drive
Johnson Controls VFD68 variable frequency drive (VFD68Bxx / VFD68Cxx, Modbus RTU)
Johnson Controls / PENN VFD68Bxx (200-240 V) and VFD68Cxx (380-480 V) drives on their RJ45 PU port with Modbus RTU selected (P.549 = 1), per the VFD68 Variable Frequency Drives Technical Bulletin, Appendix 4.
Also known as: VFD68Bxx, VFD68Cxx, VFD68BDC-2C, VFD68CDF-2C, PENN VFD68 - Variable frequency drive
LS Electric LSLV-S100 AC drive (built-in RS-485 Modbus RTU)
LS Electric S100 drives (0.4-75 kW, including IP66) using the built-in RS-485 terminals S+/S-/SG with CM.02 = Modbus-RTU, per S100 User Manual V4.3.
Also known as: LSLV-S100, LSIS S100, LS S100, LSLV0075S100-4EOFNS - Variable frequency drive (HVAC fans and pumps)
Schneider Electric Altivar 212 (embedded Modbus RTU)
ATV212H (IP21) and ATV212W (IP55) drives on the built-in Modbus RTU ports (RJ45 and open-style terminal), per Modbus manual S1A53844.
Also known as: ATV212, Altivar 212, ATV212H, ATV212W, ATV212HU15N4, ATV212WD11N4 - Variable frequency drive
SEW-EURODRIVE MOVITRAC LTE-B+ frequency inverter (built-in Modbus RTU)
SEW-EURODRIVE MOVITRAC LTE-B+ inverters on the RJ45 Modbus RTU port, per product manual 31965822/EN edition 03/2024.
Also known as: MOVITRAC LTE-B+, LTE-B+, MC LTE B+, MOVITRAC LTE B plus - Variable frequency drive
TECO-Westinghouse E510 inverter (Modbus RTU/ASCII)
TECO-Westinghouse E510 inverters using the built-in RS-485 port (CON2), per communication addendum DOCUMENT-TECO-E510-AC001 Ver01 (2015-03).
Also known as: TECO E510, E510 Communication Addendum - Variable frequency drive
Vacon VACON 20 AC drive (built-in Modbus RTU)
VACON 20 compact drives with the standard Vacon 20 application on the built-in RS-485 Modbus RTU port, per complete user manual DPD00716H1 (software FW0107V012).
Also known as: VACON 20, Vacon 20, VACON0020
All variable frequency drives Modbus register maps →
Source: Goodrive20 Series VFD Operation Manual · V2.1. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.