  4. VT1 series variable speed drives (Modbus RTU / ASCII)

Variable frequency drive · Modbus register map

Lovato Electric VT1 series variable speed drives (Modbus RTU / ASCII) Modbus register map

Updated 19 November 2026

Short answer

The Lovato VT1 is an AC drive whose RS-485 port supports Modbus RTU/ASCII and BACnet MS/TP. Over Modbus a master writes a command word and frequency reference and reads a block of monitor registers. This map covers the command word, frequency command, status and fault code, terminal status, output frequency, voltage, current, power, PID values, analog inputs and drive temperature.

This page lists 17 Modbus registers for the Lovato Electric VT1 series variable speed drives (Modbus RTU / ASCII) — 2 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Lovato Electric’s own free documentation (linked below) and checked against it.

Manufacturer
Lovato Electric
Model
VT1 series variable speed drives (Modbus RTU / ASCII)
Equipment type
Variable frequency drive
Registers
17 (2 writable)
Transport
Modbus RTU, Modbus ASCII
Default unit ID
Not stated
Documented addressing
1-based (subtract 1 for the wire address)
Also known as
VT1, Lovato VT1, VT1 series
Source document
Variable speed drives VT1 series - Communication manual, Modbus and BACnet protocols · I646 GB I 02 21 · rev. 2021-02
Download CSV all columns JSON Manufacturer PDF ↗

Integration notes: Lovato Electric VT1 series variable speed drives (Modbus RTU / ASCII)

Integration in brief

Write the frequency reference (wire 0x2502) and set bit 0 of the command word (wire 0x2501) to run; a single function 16 write of two registers at 0x2501 does both. Read status, fault code and output values from the block starting at wire 0x2520.

Minimum registers to map

Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.

RegisterNameTypeWhyAccess
HR 9473Command wordBITMAP16Command word (run/stop, reset)Read/write
HR 9474Frequency commandUINT16Frequency referenceRead/write
HR 9504Drive statusBITMAP16Drive statusRead
HR 9505Fault codeUINT16Fault codeRead
HR 9508Output frequencyUINT16Output frequencyRead
HR 9511Output currentUINT16Output currentRead

Enable Modbus control & writes

Wire the drive's RS-485 port and select Modbus RTU or ASCII, the slave address and the run/frequency command source on the drive keypad; those parameter numbers are in the VT1 instruction manual, not in this protocol document.

Communication loss & watchdog

A lost connection shows Err6 on the drive; the reaction to an external abnormality written via command bit 2 follows parameter 07-09.

Byte order & addressing

Network setup

Watch out for

Lovato Electric VT1 series variable speed drives (Modbus RTU / ASCII) Modbus registers

Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.

17 of 17 shown
Lovato Electric VT1 series variable speed drives (Modbus RTU / ASCII) Modbus register map
TableAddressNameDescriptionTypeOrderScaleUnitsAccessValues / bits
HR9473doc 2502HCommand wordRun/stop, direction, reset, jog, S1-S5 and relay commands.BITMAP16Read/writebit 0 = Run (0 = stop); bit 1 = Reverse (0 = forward); bit 2 = External abnormality EFO; bit 3 = Fault reset; bit 4 = Jog forward; bit 5 = Jog reverse; bit 6 = Multi-function command S1; bit 7 = Multi-function command S2; bit 8 = Multi-function command S3; bit 9 = Multi-function command S4; bit 10 = Multi-function command S5; bit 12 = Relay RY1
HR9474doc 2503HFrequency command60.00 Hz is written as 6000.UINT16× 0.01HzRead/write
HR9504doc 2521HDrive statusBITMAP16Readbit 0 = Running (0 = stopped); bit 1 = Reverse (0 = forward); bit 2 = Ready; bit 3 = Abnormal; bit 4 = Data setting error
HR9505doc 2522HFault codeUINT16Read0 = Normal; 1 = Drive over heat (OH); 2 = Over current at stop (OC); 3 = Under voltage (LV); 4 = Over voltage (OV); 6 = External BB (bb); 7 = CPU error by external signal (CTE); 8 = PID feedback signal lost (PDER); 9 = EEPROM abnormal (EPR); 10 = Parameter auto-measure error (ATER); 11 = Over torque (OL3); 12 = Drive overload (OL2); 13 = Motor overload (OL1); 14 = External communication error (EFO); 15 = External stop (E.S); 16 = Parameters locked (LOC); 18 = Over current at constant speed (OC-C); 19 = Over current accelerating (OC-A); 20 = Over current decelerating (OC-D); 21 = Over current at start (OC-S); 23 = Under voltage running (LV-C); 24 = Over voltage decelerating (OV-C); 25 = Drive over heat running (OH-C); 26 = Stop at 0 speed (STP0); 27 = Direct start malfunction (STP1); 28 = Keypad emergency stop (STP2); 29 = Keypad operation error (Err1); 30 = Parameter setting error (Err2); 31 = Analog transfer error (Err4); 32 = Parameter changed during communication (Err5); 33 = Communication failure (Err6); 34 = Parameter setting error (Err7); 35 = Restore factory setting error (Err8); 38 = Copy unit parameter copy error (EPR1); 39 = Copy unit parameters incorrect (EPR2); 40 = Drive over speed (OVSP); 41 = Input phase lost (PF); 42 = Horsepower setting error (HPERR); 44 = Motor overheat error (OH4); 45 = Motor overheat alarm (OH3); 46 = Output current at current limit (CL); 47 = High pressure fault (HIPB); 48 = Low pressure fault (LOPB); 49 = PID feedback signal loss (FBLSS)
HR9506doc 2523HTerminal statusBITMAP16Readbit 0 = Terminal S1; bit 1 = Terminal S2; bit 2 = Terminal S3; bit 3 = Terminal S4; bit 4 = Terminal S5; bit 6 = Relay RY1
HR9507doc 2524HFrequency command (readback)UINT16× 0.01HzRead
HR9508doc 2525HOutput frequencyUINT16× 0.01HzRead
HR9509doc 2526HOutput voltage commandUINT16× 0.1VRead
HR9510doc 2527HDC voltage commandUINT16VRead
HR9511doc 2528HOutput currentUINT16× 0.1ARead
HR9513doc 252AHOutput powerUINT16× 0.1kWRead
HR9514doc 252BHPID feedbackPercent of maximum frequency.UINT16× 0.1%Read
HR9515doc 252CHPID inputUINT16× 0.1%Read
HR9516doc 252DHAVI input value1000 = 10 V.UINT16× 0.01VRead
HR9517doc 252EHACI input value1000 = 10 V (as printed).UINT16× 0.01VRead
HR9521doc 2532HDrive temperatureHeat sink or IGBT temperature.UINT16× 0.1°CRead
HR9522doc 2533HDrive/motor rated current ratioUINT16%Read

Notes on this map

Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.

Questions about the Lovato Electric VT1 series variable speed drives (Modbus RTU / ASCII)

What Modbus registers does the Lovato Electric VT1 series variable speed drives (Modbus RTU / ASCII) have?

This map lists 17 registers: 17 holding registers. 2 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.

Are the Lovato Electric VT1 series variable speed drives (Modbus RTU / ASCII) Modbus addresses 0-based or 1-based?

The manufacturer's document numbers registers 1-based (subtract 1 for the wire address). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. The register tables print hex numbers one above the wire address, as all three example frames show: reading the frequency command (table 2524H) sends 25 23; writing 60.0 Hz to the frequency command (table 2503H) sends 25 02; a two-register write of run command + frequency (table 2502H-2503H) starts at 25 01. Addresses here are the table value minus one.

What are the minimum Modbus registers to integrate the Lovato Electric VT1 series variable speed drives (Modbus RTU / ASCII)?

Start with HR 9473 Command word (Command word (run/stop, reset)); HR 9474 Frequency command (Frequency reference); HR 9504 Drive status (Drive status); HR 9505 Fault code (Fault code); HR 9508 Output frequency (Output frequency); HR 9511 Output current (Output current).

How do I enable Modbus control of the Lovato Electric VT1 series variable speed drives (Modbus RTU / ASCII)?

Wire the drive's RS-485 port and select Modbus RTU or ASCII, the slave address and the run/frequency command source on the drive keypad; those parameter numbers are in the VT1 instruction manual, not in this protocol document.

What happens when the Lovato Electric VT1 series variable speed drives (Modbus RTU / ASCII) loses Modbus communication?

A lost connection shows Err6 on the drive; the reaction to an external abnormality written via command bit 2 follows parameter 07-09.

Where is the official Lovato Electric VT1 series variable speed drives (Modbus RTU / ASCII) Modbus documentation?

The source is Variable speed drives VT1 series - Communication manual, Modbus and BACnet protocols (I646 GB I 02 21), revision 2021-02, published free by Lovato Electric at https://datasheet.lovatoelectric.com/DOWNLOAD/Technical/TechInstructions/06.%20AZIONAMENTI%20A%20VELOCITA%20VARIABILE/I646GBI02_21.pdf.

More Lovato Electric Modbus register maps

Other variable frequency drives register maps

All variable frequency drives Modbus register maps →

Source: Variable speed drives VT1 series - Communication manual, Modbus and BACnet protocols · I646 GB I 02 21 · rev. 2021-02. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.