Pump (diesel fire pump controller) · Modbus register map

Lovato Electric FFL700DP / FFL800DP diesel engine fire pump controllers Modbus register map

Updated 19 November 2026

Short answer

The Lovato FFL700DP and FFL800DP are diesel engine fire pump controllers (EN 12845). They speak Modbus RTU, ASCII or TCP on the built-in RS-485, the optical port and, on FFL800DP, expansion modules. This map covers mains voltage, engine speed, hours, engine temperatures, oil pressure, fuel level, battery voltages, the alarm words, I/O states, the global status word and the reset/save commands.

This page lists 32 Modbus registers for the Lovato Electric FFL700DP / FFL800DP diesel engine fire pump controllers — 4 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Lovato Electric’s own free documentation (linked below) and checked against it.

Manufacturer
Lovato Electric
Model
FFL700DP / FFL800DP diesel engine fire pump controllers
Equipment type
Pump (diesel fire pump controller)
Registers
32 (4 writable)
Transport
Modbus RTU, Modbus ASCII, Modbus TCP
Default unit ID
1
Default serial
9600 baud, 8N1
TCP port
1001
Documented addressing
1-based (subtract 1 for the wire address)
32-bit word order
ABCD high word first (big-endian)
Also known as
FFL700DP, FFL800DP, FFL 700 DP, FFL 800 DP
Source document
FFL700DP - FFL800DP diesel engine fire pump controllers - Communication protocol Modbus · I557 GB I 11 17 · rev. 2017-11-08
Download CSV all columns JSON Manufacturer PDF ↗

Integration notes: Lovato Electric FFL700DP / FFL800DP diesel engine fire pump controllers

Integration in brief

Read the alarm words 2200h-2205h and the global status 2210h for supervision, plus engine speed, battery voltages and fuel level. Subtract one from every table address.

Minimum registers to map

Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.

RegisterNameTypeWhyAccess
IR 8719Device global statusBITMAP16Global status (MAN/AUT, alarm, engine started)Read
IR 8703Alarms A01-A16BITMAP16Alarms A01-A16Read
IR 8704Alarms A17-A32BITMAP16Alarms A17-A32 (failure to start)Read
IR 5Engine speedUINT32 ABCDEngine speedRead
IR 3853Battery A voltageUINT32 ABCDBattery A voltageRead
IR 4003Fuel levelUINT32 ABCDFuel levelRead

Enable Modbus control & writes

In SETUP, menu M17 (communication), set node address, port speed, data format, stop bits and protocol for the port in use; port 1 is the built-in RS-485.

Byte order & addressing

Network setup

Watch out for

Lovato Electric FFL700DP / FFL800DP diesel engine fire pump controllers Modbus registers

Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.

32 of 32 shown
Lovato Electric FFL700DP / FFL800DP diesel engine fire pump controllers Modbus register map
TableAddressNameDescriptionTypeOrderScaleUnitsAccessValues / bits
IR1doc 0002hMains (VAC) voltageUINT32ABCD× 0.01VRead
IR5doc 0006hEngine speedUINT32ABCDrpmRead
IR3849doc 0F0AhExternal temperature probe°C or °F (the table prints both).INT32ABCDRead
IR3853doc 0F0EhBattery A voltageUINT32ABCD× 0.01VRead
IR3855doc 0F10hD+ voltageUINT32ABCDVRead
IR3857doc 0F12hInternal temperature probe°C or °F (the table prints both).INT32ABCDRead
IR3863doc 0F18hPinion feedbackUINT32ABCDVRead
IR3865doc 0F1AhBattery B voltageUINT32ABCD× 0.01VRead
IR3869doc 0F1EhTemperature on the display°C or °F (the table prints both), /100.INT32ABCD× 0.01Read
IR3879doc 0F28hWater reserve% or litres (the table prints both).UINT32ABCDRead
IR3967doc 0F80hPartial working hoursUINT32ABCDhRead
IR3971doc 0F84hTotal working hoursUINT32ABCDhRead
IR3999doc 0FA0hEngine temperature sensor 1°C or °F (the table prints both).INT32ABCDRead
IR4001doc 0FA2hOil pressurebar or psi (the table prints both), /10.UINT32ABCD× 0.1Read
IR4003doc 0FA4hFuel level%, litres or gallons (the table prints all three).UINT32ABCDRead
IR4005doc 0FA6hEngine temperature sensor 2°C or °F (the table prints both).INT32ABCDRead
IR8303doc 2070hFront panel keyboard statusBITMAP16Readbit 0 = RIGHT; bit 1 = LEFT; bit 2 = DOWN; bit 3 = UP; bit 4 = MAN/TEST; bit 5 = RESET; bit 6 = STOP; bit 7 = ENTER; bit 8 = BAT A; bit 9 = BAT B
IR8447doc 2100hDigital inputs 1-16BITMAP16Readbit 0 = Input 1; bit 1 = Input 2; bit 2 = Input 3; bit 3 = Input 4; bit 4 = Input 5; bit 5 = Input 6; bit 6 = Input 7; bit 7 = Input 8; bit 8 = Input 9; bit 9 = Input 10; bit 10 = Input 11; bit 11 = Input 12; bit 12 = Input 13; bit 13 = Input 14; bit 14 = Input 15; bit 15 = Input 16
IR8510doc 213FhDigital inputs 17-25BITMAP16Readbit 0 = Input 17; bit 1 = Input 18; bit 2 = Input 19; bit 3 = Input 20; bit 4 = Input 21; bit 5 = Input 22; bit 6 = Input 23; bit 7 = Input 24; bit 8 = Input 25
IR8511doc 2140hDigital outputs 1-16BITMAP16Readbit 0 = Output 1; bit 1 = Output 2; bit 2 = Output 3; bit 3 = Output 4; bit 4 = Output 5; bit 5 = Output 6; bit 6 = Output 7; bit 7 = Output 8; bit 8 = Output 9; bit 9 = Output 10; bit 10 = Output 11; bit 11 = Output 12; bit 12 = Output 13; bit 13 = Output 14; bit 14 = Output 15; bit 15 = Output 16
IR8574doc 217FhDigital outputs 17-20BITMAP16Readbit 0 = Output 17; bit 1 = Output 18; bit 2 = Output 19; bit 3 = Output 20
IR8703doc 2200hAlarms A01-A16BITMAP16Readbit 0 = A01 Engine temperature 1 warning (analog); bit 1 = A02 Engine temperature 1 high (analog); bit 2 = A03 Engine temperature 1 sensor failure; bit 3 = A04 Engine temperature 1 low (analog); bit 4 = A05 Engine temperature 2 warning (analog); bit 5 = A06 Engine temperature 2 high (analog); bit 6 = A07 Engine temperature 2 sensor failure; bit 7 = A08 Engine temperature 2 low (analog); bit 8 = A09 Engine temperature high (digital); bit 9 = A10 Engine temperature too low (digital), heater failure; bit 10 = A11 Oil pressure warning (analog); bit 11 = A12 Low oil pressure (analog); bit 12 = A13 Analog pressure sensor failure; bit 13 = A14 Low oil pressure (digital); bit 14 = A15 Digital pressure sensor failure; bit 15 = A16 Warning low fuel level (analog)
IR8704doc 2201hAlarms A17-A32BITMAP16Readbit 0 = A17 Low fuel level (analog); bit 1 = A18 Warning high fuel level (analog); bit 2 = A19 High fuel level (analog); bit 3 = A20 Analog fuel level sensor failure; bit 4 = A21 Low fuel level (digital); bit 5 = A22 Low radiator fluid level; bit 6 = A23 W/pick-up signal failure; bit 7 = A24 W/pick-up disconnected; bit 8 = A25 Low engine speed (W/pick-up); bit 9 = A26 High engine speed (W/pick-up); bit 10 = A27 Pinion inserted (feedback on during pause); bit 11 = A28 Pinion not inserted (feedback off during cranking); bit 12 = A29 Pinion sensor disconnected; bit 13 = A30 Water in the fuel; bit 14 = A31 Failure to start; bit 15 = A32 Unexpected stop
IR8705doc 2202hAlarms A33-A48BITMAP16Readbit 0 = A33 Failure to stop; bit 1 = A34 High battery A voltage; bit 2 = A35 Low battery A voltage; bit 3 = A36 Battery A inefficient; bit 4 = A37 Alarm from battery charger A; bit 5 = A38 High battery B voltage; bit 6 = A39 Low battery B voltage; bit 7 = A40 Battery B inefficient; bit 8 = A41 Alarm from battery charger B; bit 9 = A42 Battery charger alternator failure; bit 10 = A43 Auxiliary voltage too low; bit 11 = A44 Auxiliary voltage too high; bit 12 = A45 System error; bit 13 = A46 Room temperature too low (analog); bit 14 = A47 Room temperature too high (analog); bit 15 = A48 Water reserve (digital)
IR8706doc 2203hAlarms A49-A60Bit 1 (A50): English says water reserve high; Italian says empty (used here).BITMAP16Readbit 0 = A49 Water reserve low (analog); bit 1 = A50 Water reserve empty (analog); bit 2 = A51 Low priming tank level; bit 3 = A52 Supply of outputs disconnected; bit 4 = A54 System not in automatic mode for 24 h; bit 5 = A55 Engine pump running; bit 6 = A56 Pump failure; bit 7 = A57 Pump in pressure with engine off; bit 8 = A58 Maintenance request 1; bit 9 = A59 Maintenance request 2; bit 10 = A60 Maintenance request 3
IR8707doc 2204hAlarms A69-UA6BITMAP16Readbit 3 = A69 Suction valve partially open; bit 4 = A70 Delivery valve partially open; bit 5 = A71 Pump room sprinkler alarm; bit 6 = A72 Jockey pump starts alarm; bit 7 = A73 Jockey pump thermal alarm; bit 8 = A74 Drain pump alarm; bit 9 = A75 Fuel leak; bit 10 = UA1 User alarm 1; bit 11 = UA2 User alarm 2; bit 12 = UA3 User alarm 3; bit 13 = UA4 User alarm 4; bit 14 = UA5 User alarm 5; bit 15 = UA6 User alarm 6
IR8708doc 2205hUser alarms UA7-UA8BITMAP16Readbit 0 = UA7 User alarm 7; bit 1 = UA8 User alarm 8
IR8719doc 2210hDevice global statusBITMAP16Readbit 1 = Device in MAN mode; bit 2 = Device in AUT mode; bit 3 = Global alarm; bit 4 = Type A alarm; bit 5 = Type B alarm; bit 6 = Siren alarms; bit 7 = Failure to start; bit 8 = Engine started; bit 9 = Low fuel level; bit 10 = Automatic test in progress
HR12034doc 2F03hSave / rebootUINT16Write1 = Save to EEPROM; 4 = Reboot; 5 = Save and reboot
HR12038doc 2F07hDevice resetUINT16Write0 = Reset device; 1 = Reset device and save FRAM
HR12271doc 2FF0hCommand menu executionUINT16Write0 = Reset maintenance 1; 1 = Reset maintenance 2; 2 = Reset maintenance 3; 3 = Reset partial engine hours; 4 = Reset generic counters CNTx; 5 = Reset LIMx limits; 6 = Reset total engine hours; 8 = Reset start counter; 9 = Reset events list; 10 = Reset default parameters; 11 = Save parameters to backup; 12 = Reload parameters from backup; 15 = Reset PLC program
HR20223doc 4F00hRemote variable REM1REM2-REM16 follow at 4F01h-4F0Fh.UINT16Write170 = Set to 1 (AAh); 187 = Set to 0 (BBh)

Notes on this map

Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.

Questions about the Lovato Electric FFL700DP / FFL800DP diesel engine fire pump controllers

What Modbus registers does the Lovato Electric FFL700DP / FFL800DP diesel engine fire pump controllers have?

This map lists 32 registers: 28 input registers, 4 holding registers. 4 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.

Are the Lovato Electric FFL700DP / FFL800DP diesel engine fire pump controllers Modbus addresses 0-based or 1-based?

The manufacturer's document numbers registers 1-based (subtract 1 for the wire address). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. The tables print hex addresses one above the request address; the document says to subtract one, and its example reads battery A voltage (table 0F0Eh) by sending 0F 0D. Addresses here are already reduced by one.

What byte order does the Lovato Electric FFL700DP / FFL800DP diesel engine fire pump controllers use for 32-bit values?

Multi-register values in this map use ABCD (high word first (big-endian)). Set your client to this order for every 32/64-bit value in the table.

What are the minimum Modbus registers to integrate the Lovato Electric FFL700DP / FFL800DP diesel engine fire pump controllers?

Start with IR 8719 Device global status (Global status (MAN/AUT, alarm, engine started)); IR 8703 Alarms A01-A16 (Alarms A01-A16); IR 8704 Alarms A17-A32 (Alarms A17-A32 (failure to start)); IR 5 Engine speed (Engine speed); IR 3853 Battery A voltage (Battery A voltage); IR 4003 Fuel level (Fuel level).

How do I enable Modbus control of the Lovato Electric FFL700DP / FFL800DP diesel engine fire pump controllers?

In SETUP, menu M17 (communication), set node address, port speed, data format, stop bits and protocol for the port in use; port 1 is the built-in RS-485.

Where is the official Lovato Electric FFL700DP / FFL800DP diesel engine fire pump controllers Modbus documentation?

The source is FFL700DP - FFL800DP diesel engine fire pump controllers - Communication protocol Modbus (I557 GB I 11 17), revision 2017-11-08, published free by Lovato Electric at https://datasheet.lovatoelectric.com/DOWNLOAD/Technical/TechInstructions/33.%20CONTROLLORI%20ANTINCENDIO/I557IGB11_17.pdf.