Pump (high-efficiency circulator) · Modbus register map
Wilo Atmos MAXO with CIF module Modbus RTU Modbus register map
Updated 17 November 2026
The Wilo Atmos MAXO gets Modbus RTU through Wilo's plug-in CIF module. A master switches the pump on/off with the pump command word, selects the control mode and writes a relative duty point in 0.5 % steps; a bus command timer can fall back to preset values when communication stops. Read-only data covers head, flow, power, energy, speed, temperatures and status/error words. This map keeps only the points Wilo marks as supported on the Atmos MAXO.
This page lists 36 Modbus registers for the Wilo Atmos MAXO with CIF module Modbus RTU — 10 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Wilo’s own free documentation (linked below) and checked against it.
- Manufacturer
- Wilo
- Model
- Atmos MAXO with CIF module Modbus RTU
- Equipment type
- Pump (high-efficiency circulator)
- Registers
- 36 (10 writable)
- Transport
- Modbus RTU
- Default unit ID
- Not stated
- Documented addressing
- 0-based (the number printed is the address on the wire)
- 32-bit word order
- ABCD high word first (big-endian)
- Firmware
- CIF module Modbus RTU 1.00-99.99 (module versions per register as noted)
- Also known as
- Wilo-Atmos MAXO
- Source document
- WILO Modbus RTU · wilo194406
Integration notes: Wilo Atmos MAXO with CIF module Modbus RTU
Set bus address, baud (parameter A) and frame (parameter C) in the pump menu, then write the control mode (H 42), the duty point (H 1) and the pump command (H 40). Poll status (I 404 if present), error code (I 940) and the measured values in the I 1-I 10 block.
Minimum registers to map
Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.
| Register | Name | Type | Why | Access |
|---|---|---|---|---|
| HR 40 | Pump Command in | BITMAP16 | On/off command (bit 3 = 1 when writing, if listed) | Read/write |
| HR 42 | controlFunction | UINT16 | Control mode | Read/write |
| HR 1 | dutyPointRel | INT16 | Setpoint (duty point, 0.5 % steps) | Read/write |
| IR 404 | Operation Status | BITMAP16 | Operation status flags | Read |
| IR 940 | warning/errorMessage | UINT16 | Active warning/error code | Read |
| IR 1 | pressure | UINT16 | Actual pressure | Read |
| IR 2 | flow | UINT16 | Flow | Read |
| IR 4 | powerInput | UINT16 | Power input | Read |
Enable Modbus control & writes
Plug in the CIF module Modbus RTU and set the bus address (menu <5.2.3.0>), baud rate (parameter A, <5.2.4.0>: 5 = 9600, 6 = 19200, 7 = 38400 ...) and frame (parameter C, <5.2.5.0>: 2 = 8N1, 3 = 8N2, 6 = 8E1, 10 = 8O1). OFF as bus address disables the interface.
Communication loss & watchdog
The bus command timer (H 300, timeout in H 400 where supported) can switch the pump to the preset command, mode and duty point (H 402-405) when the master stops refreshing it.
Byte order & addressing
- Register numbers are raw wire addresses; do not subtract 1.
- Duty points are in 0.5 % steps (200 = 100 %).
- Unsupported control-mode values are ignored by the pump.
Network setup
- Where a setpointSignalSource register is listed, select IF-Module (value 1) as the setpoint source if the duty point should come from the bus.
- Terminate the RS-485 line at both ends.
Watch out for
- Temperatures are in kelvin.
- Last write wins between the bus, the pump display and other remote controls.
Wilo Atmos MAXO with CIF module Modbus RTU Modbus registers
Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.
| Table | Address | Name | Description | Type | Order | Scale | Units | Access | Values / bits |
|---|---|---|---|---|---|---|---|---|---|
| IR | 1 | pressure | Actual pressure (head) at the pump. | UINT16 | × 10 | cm H₂O | Read | ||
| IR | 2 | flow | Actual or calculated flow. Error value 9999 up to module 6.00, 65535 from 6.01. | UINT16 | × 0.1 | m³/h | Read | ||
| IR | 3 | energyConsumption | Energy consumption counter. | UINT16 | kWh | Read | |||
| IR | 4 | powerInput | Electrical power input. | UINT16 | W | Read | |||
| IR | 7 | speed | Motor speed. | INT16 | 1/min | Read | |||
| IR | 10 | controlFunction | Active control mode. | UINT16 | Read | 1 = Gen_Spd; 3 = Gen_PHdConst; 4 = Gen_PHdVar; 15 = INVALID | |||
| IR | 18 | speed max-pres-value | Maximum speed. | UINT16 | 1/min | Read | |||
| IR | 19 | speed min-pres-value | Minimum speed. | UINT16 | 1/min | Read | |||
| IR | 24 | flow max-pres-value | Maximum (calculated) flow. | UINT16 | × 0.1 | m³/h | Read | ||
| IR | 36 | Error Type | Legacy register; prefer I 940 for new work. | BITMAP16 | Read | bit 3 = errorPresent | |||
| IR | 38 | Pump Status | Legacy controller status flags. | BITMAP16 | Read | bit 0 = device/functionOn; bit 5 = localOperation | |||
| IR | 39 | State Diagnostics | Legacy diagnostic flags. | BITMAP16 | Read | bit 0 = errorPresent; bit 8 = localOperation; bit 10 = device/functionOn | |||
| IR | 102 | Pump Status | Status flags of the partner pump (twin-head). | BITMAP16 | Read | bit 5 = localOperation | |||
| IR | 200 | dutyPointRel | Setpoint the pump is actually using (200 = 100 %). Module 3.00+. | INT16 | × 0.5 | % | Read | ||
| IR | 202 | dutyPointRel maximum-output | Upper limit of the active setpoint. Module 3.00+. | INT16 | × 0.5 | % | Read | ||
| IR | 204 | dutyPointRel minimum-output | Lower limit; lower writes are limited to it. Module 3.00+. | INT16 | × 0.5 | % | Read | ||
| IR | 206 | dutyPoint100%Val | Engineering value at 100 % in the current mode; unit in I 208. Module 3.00+. | FLOAT32 | ABCD | Read | |||
| IR | 208 | dutyPointRel units | Unit code for I 206. Module 3.00+. | UINT16 | Read | ||||
| IR | 210 | setpointSignalSource | Module 3.00+. | UINT16 | Read | 1 = IF-Module; 6 = Internal; 9 = INVALID | |||
| IR | 320 | voltageInput | Mains input voltage. Module 3.00+. | UINT16 | × 0.1 | V | Read | ||
| IR | 400 | dutyPointRel | Duty point currently in use. | INT16 | × 0.5 | % | Read | ||
| IR | 402 | Pump Command active | Command currently in effect. | BITMAP16 | Read | bit 0 = device/functionOn | |||
| IR | 404 | Operation Status | Main run / warning / error flags. | BITMAP16 | Read | bit 0 = ready4Operation; bit 1 = device/functionOn; bit 3 = warningPresent; bit 4 = errorPresent; bit 5 = finalErrorPresent | |||
| IR | 500 | heartbeatCount | Counts pump-to-module heartbeats; resets on restart. | UINT32 | ABCD | Read | |||
| IR | 504 | busCmd.TimerTimeRemain. | Seconds left before the bus command timer elapses (module 3.02+). | UINT16 | s | Read | |||
| IR | 940 | warning/errorMessage | Active Wilo warning/error code. | UINT16 | Read | ||||
| HR | 1 | dutyPointRel | Setpoint in % of the active mode's 100 % value (200 = 100 %). | INT16 | × 0.5 | % | Read/write | ||
| HR | 40 | Pump Command in | On/off and override command word. | BITMAP16 | Read/write | bit 0 = device/functionOn; bit 4 = overrideOff (module 3.00+) | |||
| HR | 42 | controlFunction | Control mode; unsupported values are ignored. | UINT16 | Read/write | 1 = Gen_Spd; 3 = Gen_PHdConst; 4 = Gen_PHdVar; 15 = INVALID | |||
| HR | 300 | busCmd.Timer | Bus command timer / fallback state machine. | UINT16 | Read/write | 1 = OFF; 5 = MANUAL; 6 = SET_PRESET; 7 = ACTIVE_PRESET; 8 = RESET_PRESET; 9 = MANUAL_PRESET; 10 = INVALID | |||
| HR | 400 | busCmd.TimerTimeout | Bus command timer timeout. Module 3.00+. | UINT16 | s | Read/write | |||
| HR | 401 | setpointSignalSource | Where the setpoint comes from; write 1 for bus control. | UINT16 | Read/write | 1 = IF-Module; 6 = Internal; 9 = INVALID | |||
| HR | 402 | dutyPointRel preset | Fallback setpoint used by the bus command timer. | INT16 | × 0.5 | % | Read/write | ||
| HR | 403 | controlFunction preset | Fallback control mode. | UINT16 | Read/write | 1 = Gen_Spd; 3 = Gen_PHdConst; 4 = Gen_PHdVar; 15 = INVALID | |||
| HR | 404 | Pump Command preset | Fallback on/off command. | BITMAP16 | Read/write | bit 0 = device/functionOn preset | |||
| HR | 405 | setpointSignalSource preset | Fallback setpoint source. | UINT16 | Read/write | 1 = IF-Module; 6 = Internal; 9 = INVALID |
Notes on this map
- Source is Wilo's public HTML functional description for the CIF module Modbus RTU, which marks every register and every enumeration/bit value with the pump families that support it. Only registers, values and bits marked for Atmos MAXO are kept here; values and bits not listed are not supported on this pump. Facts are re-keyed and the document is linked, not re-hosted.
- 32-bit values (REAL = FLOAT32, UDINT = UINT32) are stored with the most significant 16 bits at the base address (ABCD), as stated in section 6.1.4.
- Scale: engineering value = raw x scale from Wilo's list (e.g. pressure x 10 = cm H2O, operation time x 10 = h, flow x 0.1 = m3/h, duty point x 0.5 = %, temperatures x 0.1 = K).
- Temperatures are in kelvin with scale 0.1 (raw 2932 = 293.2 K, about 20 °C).
- Error values: an unavailable reading returns the largest positive value of its data type (65535 for UINT, 32767 for INT).
- Flow (input register 2): Wilo lists it twice with the same address, type and scale; up to module 6.00 its error value is 9999, from 6.01 it is 65535.
- Module-version requirements from the list are noted in descriptions ('Module 3.01+' etc.); registers without a note exist from module version 1.00.
- Left out: identification registers (700-750: BCD software revisions, vendor ID, UUID, article number), system time (502), energy-meter start timestamps (306/310), the double-pump total runtime (9) and 'pressure max-pres-value' (212, ambiguous between live and maximum pressure).
Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.
Questions about the Wilo Atmos MAXO with CIF module Modbus RTU
What Modbus registers does the Wilo Atmos MAXO with CIF module Modbus RTU have?
This map lists 36 registers: 26 input registers, 10 holding registers. 10 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.
Are the Wilo Atmos MAXO with CIF module Modbus RTU Modbus addresses 0-based or 1-based?
The manufacturer's document numbers registers 0-based (the number printed is the address on the wire). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. Wilo states that all register addresses are raw addresses as sent on the bus; its example frame 01 04 02 BC 00 01 reads input register 700 (0x02BC). Masters that count registers from 1 must add 1.
What byte order does the Wilo Atmos MAXO with CIF module Modbus RTU use for 32-bit values?
Multi-register values in this map use ABCD (high word first (big-endian)). Set your client to this order for every 32/64-bit value in the table.
What are the minimum Modbus registers to integrate the Wilo Atmos MAXO with CIF module Modbus RTU?
Start with HR 40 Pump Command in (On/off command (bit 3 = 1 when writing, if listed)); HR 42 controlFunction (Control mode); HR 1 dutyPointRel (Setpoint (duty point, 0.5 % steps)); IR 404 Operation Status (Operation status flags); IR 940 warning/errorMessage (Active warning/error code); IR 1 pressure (Actual pressure); IR 2 flow (Flow); IR 4 powerInput (Power input).
How do I enable Modbus control of the Wilo Atmos MAXO with CIF module Modbus RTU?
Plug in the CIF module Modbus RTU and set the bus address (menu <5.2.3.0>), baud rate (parameter A, <5.2.4.0>: 5 = 9600, 6 = 19200, 7 = 38400 ...) and frame (parameter C, <5.2.5.0>: 2 = 8N1, 3 = 8N2, 6 = 8E1, 10 = 8O1). OFF as bus address disables the interface.
What happens when the Wilo Atmos MAXO with CIF module Modbus RTU loses Modbus communication?
The bus command timer (H 300, timeout in H 400 where supported) can switch the pump to the preset command, mode and duty point (H 402-405) when the master stops refreshing it.
Where is the official Wilo Atmos MAXO with CIF module Modbus RTU Modbus documentation?
The source is WILO Modbus RTU (wilo194406), published free by Wilo at https://cms.media.wilo.com/cdndoc/wilo194406/11516106/wilo194406.html.
More Wilo Modbus register maps
- Pump (multistage pressure-boosting pump)
Wilo Helix2.0-VE / Medana CH3-LE with CIF module Modbus RTU
Wilo Helix2.0-VE pumps fitted with the plug-in CIF module Modbus RTU (module firmware 1.00-99.99); registers needing a newer module are marked.
Also known as: Wilo-Helix2.0-VE, Medana CH3-LE, Wilo-Medana CH3-LE - Pump (pressure-boosting pump)
Wilo Isar MODH1-E with CIF module Modbus RTU
Wilo Isar MODH1-E pumps fitted with the plug-in CIF module Modbus RTU (module firmware 1.00-99.99); registers needing a newer module are marked.
Also known as: Wilo-Isar MODH1-E - Pump (high-efficiency circulator)
Wilo Para MAXO (built-in Modbus RTU)
Wilo-Para MAXO OEM circulators with the built-in Modbus RTU interface (module versions 1.00-99.99).
Also known as: Para MAXO, Wilo-Para MAXO, Para MAXO Modbus - Pump system
Wilo SiFresh with CIF module Modbus RTU
Wilo SiFresh pumps fitted with the plug-in CIF module Modbus RTU (module firmware 1.00-99.99); registers needing a newer module are marked.
Also known as: Wilo-SiFresh - Pump (high-efficiency inline circulator)
Wilo Stratos GIGA2.0 with CIF module Modbus RTU
Wilo Stratos GIGA2.0 pumps fitted with the plug-in CIF module Modbus RTU (module firmware 1.00-99.99); registers needing a newer module are marked.
Also known as: Stratos GIGA2.0-I, Stratos GIGA2.0-D, Wilo-Stratos GIGA2.0 - Pump (smart circulator)
Wilo Stratos MAXO with CIF module Modbus RTU
Wilo-Stratos MAXO single and twin-head circulators fitted with the plug-in CIF module Modbus RTU (article 2190368, UL 2237080), module firmware 1.00-99.99; some registers need a newer module version as noted.
Also known as: Wilo-Stratos MAXO, Stratos MAXO-D, Stratos MAXO-Z, CIF-Module Modbus RTU, CIF Modbus RTU 2190368, CIF Modbus RTU UL 2237080 - Pump (high-efficiency circulator)
Wilo Stratos PICO plus with CIF module Modbus RTU
Wilo Stratos PICO plus pumps fitted with the plug-in CIF module Modbus RTU (module firmware 1.00-99.99); registers needing a newer module are marked.
Also known as: Wilo-Stratos PICO plus - Pump controller (switchgear)
Wilo Wilo-Control EC-WP switchgear (ModBus RTU)
Wilo-Control EC-WP for one or two fixed-speed pumps, hardware HW2, software SW102x (instructions Ed.01/2024-08, 2552567).
Also known as: Control EC-WP, Wilo Control EC WP, EC-WP - Pump (high-efficiency inline circulator)
Wilo Yonos GIGA2.0 with CIF module Modbus RTU
Wilo Yonos GIGA2.0 pumps fitted with the plug-in CIF module Modbus RTU (module firmware 1.00-99.99); registers needing a newer module are marked.
Also known as: Yonos GIGA2.0-I, Yonos GIGA2.0-D, Wilo-Yonos GIGA2.0
Other pumps register maps
- Heat pump
CTC CTC heat pumps and controllers via BMS (Modbus TCP)
CTC EcoHeat 400, EcoZenith i250/i350/i550, EcoVent i350F, GSi/GS, EcoPart 6xx M/Pro and EcoLogic controllers whose display has three ports (Ethernet), BMS document 16260016-3 (CR01143, 2026-02-02).
Also known as: CTC EcoHeat 400, CTC EcoZenith i250, CTC GSi, CTC GS, CTC EcoZenith i350, CTC EcoVent i350F, CTC EcoZenith i550, CTC EcoPart 600M, CTC EcoPart Pro, CTC EcoLogic, CTC EcoLogic S, 16260016-3 - Remote I/O module (engine / pump controller expansion)
FW Murphy Interchange Comm Control Module MX5-R2 (Standard IO mode)
FW Murphy MX5-R2 modules with date code S8 or later running the Standard IO application (default); pulse registers need firmware 4.4.10111 / date code U10 or later.
Also known as: MX5-R2, Interchange MX5-R2, Enovation Controls MX5-R2 - Pump (chemical dosing pump)
Grundfos SMART Digital DDA dosing pump (SoftCIM, CIM 200 / CIM 500)
Grundfos SMART Digital DDA dosing pumps: DDA model C with built-in SoftCIM Modbus RTU/TCP, and DDA XL (or others) through a CIM 200 Modbus RTU or CIM 500 Modbus TCP module in a CIU 900, per functional profile 98473491 (09.2026).
Also known as: DDA, DDA S, DDA XL, DDA-C, DDA model C, SMART Digital S, SMART Digital XL, CIM 200, CIM 500, 98473491 - Thermostat / heat pump and unitary controller
Neptronic TUUB Series universal wall-mount controller (Modbus RTU)
Neptronic TUUB Series universal wall-mount controllers with Modbus, guide TUUB-Modbus Guide-250829 (V1.13).
Also known as: TUUB Series, TUUB universal wall-mount controller - Pump (data-centre coolant distribution unit)
Trane TCDU coolant distribution unit (data-centre liquid cooling)
Trane Coolant Distribution Unit (TCDU) for direct-to-chip liquid cooling, as documented in IOM DC-SVX001A-EN (April 2025).
Also known as: TCDU, Trane CDU, Trane Coolant Distribution Unit, DC-SVX001A - Heat pump (water-to-air heat pump controller)
Bosch Control Air 5600 water-to-air heat pump controller (Modbus RTU, standard software)
Bosch commercial water-to-air heat pumps fitted with the Control Air 5600 DDC controller running the water-to-air standard software (integration points list version 1.03).
Also known as: Control Air 5600, IPL WAZ, IPL_WAZ_1_03, Bosch water-to-air DDC controller, BTC 761601101
All pumps Modbus register maps →
Source: WILO Modbus RTU · wilo194406. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.