Pump system · Modbus register map
Wilo SiFresh with CIF module Modbus RTU Modbus register map
Updated 17 November 2026
The Wilo SiFresh gets Modbus RTU through Wilo's plug-in CIF module. A master switches the pump on/off with the pump command word, selects the control mode and writes a relative duty point in 0.5 % steps; a bus command timer can fall back to preset values when communication stops. Read-only data covers head, flow, power, energy, speed, temperatures and status/error words. This map keeps only the points Wilo marks as supported on the SiFresh.
This page lists 92 Modbus registers for the Wilo SiFresh with CIF module Modbus RTU — 20 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Wilo’s own free documentation (linked below) and checked against it.
- Manufacturer
- Wilo
- Model
- SiFresh with CIF module Modbus RTU
- Equipment type
- Pump system
- Registers
- 92 (20 writable)
- Transport
- Modbus RTU
- Default unit ID
- Not stated
- Documented addressing
- 0-based (the number printed is the address on the wire)
- 32-bit word order
- ABCD high word first (big-endian)
- Firmware
- CIF module Modbus RTU 1.00-99.99 (module versions per register as noted)
- Also known as
- Wilo-SiFresh
- Source document
- WILO Modbus RTU · wilo194406
Integration notes: Wilo SiFresh with CIF module Modbus RTU
Set bus address, baud (parameter A) and frame (parameter C) in the pump menu, then write the control mode (H 42), the duty point (H 1) and the pump command (H 40). Poll status (I 404 if present), error code (I 940) and the measured values in the I 1-I 10 block.
Minimum registers to map
Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.
| Register | Name | Type | Why | Access |
|---|---|---|---|---|
| HR 40 | Pump Command in | BITMAP16 | On/off command (bit 3 = 1 when writing, if listed) | Read/write |
| HR 42 | controlFunction | UINT16 | Control mode | Read/write |
| HR 1 | dutyPointRel | INT16 | Setpoint (duty point, 0.5 % steps) | Read/write |
| IR 404 | Operation Status | BITMAP16 | Operation status flags | Read |
| IR 940 | warning/errorMessage | UINT16 | Active warning/error code | Read |
| IR 1 | pressure | UINT16 | Actual pressure | Read |
| IR 2 | flow | UINT16 | Flow | Read |
| IR 4 | powerInput | UINT16 | Power input | Read |
Enable Modbus control & writes
Plug in the CIF module Modbus RTU and set the bus address (menu <5.2.3.0>), baud rate (parameter A, <5.2.4.0>: 5 = 9600, 6 = 19200, 7 = 38400 ...) and frame (parameter C, <5.2.5.0>: 2 = 8N1, 3 = 8N2, 6 = 8E1, 10 = 8O1). OFF as bus address disables the interface.
Communication loss & watchdog
The bus command timer (H 300, timeout in H 400 where supported) can switch the pump to the preset command, mode and duty point (H 402-405) when the master stops refreshing it.
Byte order & addressing
- Register numbers are raw wire addresses; do not subtract 1.
- Duty points are in 0.5 % steps (200 = 100 %).
- Unsupported control-mode values are ignored by the pump.
Network setup
- Where a setpointSignalSource register is listed, select IF-Module (value 1) as the setpoint source if the duty point should come from the bus.
- Terminate the RS-485 line at both ends.
Watch out for
- Temperatures are in kelvin.
- Last write wins between the bus, the pump display and other remote controls.
Wilo SiFresh with CIF module Modbus RTU Modbus registers
Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.
| Table | Address | Name | Description | Type | Order | Scale | Units | Access | Values / bits |
|---|---|---|---|---|---|---|---|---|---|
| IR | 1 | pressure | Actual pressure (head) at the pump. | UINT16 | × 10 | cm H₂O | Read | ||
| IR | 2 | flow | Actual or calculated flow. Error value 9999 up to module 6.00, 65535 from 6.01. | UINT16 | × 0.1 | m³/h | Read | ||
| IR | 3 | energyConsumption | Energy consumption counter. | UINT16 | kWh | Read | |||
| IR | 4 | powerInput | Electrical power input. | UINT16 | W | Read | |||
| IR | 5 | operationTime | Operating hours counter. | UINT16 | × 10 | h | Read | ||
| IR | 7 | speed | Motor speed. | INT16 | 1/min | Read | |||
| IR | 8 | temperatureFluid@Device | Fluid temperature measured at the pump, in kelvin. | UINT16 | × 0.1 | K | Read | ||
| IR | 10 | controlFunction | Active control mode. | UINT16 | Read | 1 = Gen_Spd; 3 = Gen_PHdConst; 15 = INVALID | |||
| IR | 18 | speed max-pres-value | Maximum speed. | UINT16 | 1/min | Read | |||
| IR | 19 | speed min-pres-value | Minimum speed. | UINT16 | 1/min | Read | |||
| IR | 24 | flow max-pres-value | Maximum (calculated) flow. | UINT16 | × 0.1 | m³/h | Read | ||
| IR | 25 | flow min-pres-value | Minimum (calculated) flow. | UINT16 | × 0.1 | m³/h | Read | ||
| IR | 28 | powerInput max-pres-value | Maximum electrical input power. | UINT16 | W | Read | |||
| IR | 36 | Error Type | Legacy register; prefer I 940 for new work. | BITMAP16 | Read | bit 3 = errorPresent | |||
| IR | 38 | Pump Status | Legacy controller status flags. | BITMAP16 | Read | bit 0 = device/functionOn; bit 3 = overrideOff; bit 7 = overrideMin | |||
| IR | 39 | State Diagnostics | Legacy diagnostic flags. | BITMAP16 | Read | bit 0 = errorPresent; bit 10 = device/functionOn | |||
| IR | 102 | Pump Status | Status flags of the partner pump (twin-head). | BITMAP16 | Read | bit 3 = overrideOff; bit 7 = overrideMin | |||
| IR | 200 | dutyPointRel | Setpoint the pump is actually using (200 = 100 %). Module 3.00+. | INT16 | × 0.5 | % | Read | ||
| IR | 202 | dutyPointRel maximum-output | Upper limit of the active setpoint. Module 3.00+. | INT16 | × 0.5 | % | Read | ||
| IR | 204 | dutyPointRel minimum-output | Lower limit; lower writes are limited to it. Module 3.00+. | INT16 | × 0.5 | % | Read | ||
| IR | 206 | dutyPoint100%Val | Engineering value at 100 % in the current mode; unit in I 208. Module 3.00+. | FLOAT32 | ABCD | Read | |||
| IR | 208 | dutyPointRel units | Unit code for I 206. Module 3.00+. | UINT16 | Read | 5 = V; 19 = kWh; 47 = W; 55 = bar; 62 = Cel; 63 = K; 73 = s; 80 = m3; 95 = {noUnit}; 104 = min-1; 135 = m3/h | |||
| IR | 210 | setpointSignalSource | Module 3.00+. | UINT16 | Read | 1 = IF-Module; 6 = Internal; 9 = INVALID | |||
| IR | 211 | parameterSetSelector | Parameter set in use (module 3.01+). | UINT16 | Read | 1 = norm; 2 = aux; 3 = preset | |||
| IR | 222 | dutyPointRel maximum-output | Module 3.01+. | INT16 | × 0.5 | % | Read | ||
| IR | 224 | dutyPointRel minimum-output | Module 3.01+. | INT16 | × 0.5 | % | Read | ||
| IR | 226 | dutyPoint100%Val | Module 3.01+. | FLOAT32 | ABCD | Read | |||
| IR | 228 | dutyPointRel units | Module 3.01+. | UINT16 | Read | 5 = V; 19 = kWh; 47 = W; 55 = bar; 62 = Cel; 63 = K; 73 = s; 80 = m3; 95 = {noUnit}; 104 = min-1; 135 = m3/h | |||
| IR | 232 | dutyPointRel aux. maximum-output | Module 3.01+. | INT16 | × 0.5 | % | Read | ||
| IR | 234 | dutyPointRel aux. minimum-output | Module 3.01+. | INT16 | × 0.5 | % | Read | ||
| IR | 236 | dutyPoint100%Val aux. | Module 3.01+. | FLOAT32 | ABCD | Read | |||
| IR | 238 | dutyPointRel aux. units | Module 3.01+. | UINT16 | Read | 5 = V; 19 = kWh; 47 = W; 55 = bar; 62 = Cel; 63 = K; 73 = s; 80 = m3; 95 = {noUnit}; 104 = min-1; 135 = m3/h | |||
| IR | 242 | dutyPointRel preset maximum-output | Module 3.01+. | INT16 | × 0.5 | % | Read | ||
| IR | 244 | dutyPointRel preset minimum-output | Module 3.01+. | INT16 | × 0.5 | % | Read | ||
| IR | 246 | dutyPoint100%Val preset | Module 3.01+. | FLOAT32 | ABCD | Read | |||
| IR | 248 | dutyPointRel preset units | Module 3.01+. | UINT16 | Read | 5 = V; 19 = kWh; 47 = W; 55 = bar; 62 = Cel; 63 = K; 73 = s; 80 = m3; 95 = {noUnit}; 104 = min-1; 135 = m3/h | |||
| IR | 250 | dutyPointRel | Module 3.01+. | INT16 | × 0.5 | % | Read | ||
| IR | 252 | dutyPointRel maximum-output | Module 3.01+. | INT16 | × 0.5 | % | Read | ||
| IR | 254 | dutyPointRel minimum-output | Module 3.01+. | INT16 | × 0.5 | % | Read | ||
| IR | 256 | dutyPoint100%Val | Module 3.01+. | FLOAT32 | ABCD | Read | |||
| IR | 258 | dutyPointRel units | Module 3.01+. | UINT16 | Read | 5 = V; 19 = kWh; 47 = W; 55 = bar; 62 = Cel; 63 = K; 73 = s; 80 = m3; 95 = {noUnit}; 104 = min-1; 135 = m3/h | |||
| IR | 260 | controlFunction | Module 3.01+. | UINT16 | Read | 1 = Gen_Spd; 3 = Gen_PHdConst; 15 = INVALID | |||
| IR | 261 | Pump Command | Module 3.01+. | BITMAP16 | Read | bit 0 = device/functionOn (module 3.01+) | |||
| IR | 262 | setpointSignalSource | Module 3.01+. | UINT16 | Read | 1 = IF-Module; 6 = Internal; 9 = INVALID | |||
| IR | 270 | flow limit. max | Module 3.02+. | FLOAT32 | ABCD | m³/h | Read | ||
| IR | 272 | flow limit. min | Module 3.02+. | FLOAT32 | ABCD | m³/h | Read | ||
| IR | 274 | flow limit. off | Module 3.02+. | FLOAT32 | ABCD | m³/h | Read | ||
| IR | 316 | temperat.FluidFwd | Forward (supply) temperature in kelvin. Module 3.00+. | UINT16 | × 0.1 | K | Read | ||
| IR | 318 | temperat.FluidRet | Return temperature in kelvin. Module 3.00+. | UINT16 | × 0.1 | K | Read | ||
| IR | 320 | voltageInput | Mains input voltage. Module 3.00+. | UINT16 | × 0.1 | V | Read | ||
| IR | 400 | dutyPointRel | Duty point currently in use. | INT16 | × 0.5 | % | Read | ||
| IR | 402 | Pump Command active | Command currently in effect. | BITMAP16 | Read | bit 0 = device/functionOn; bit 1 = overrideMin; bit 2 = overrideMax; bit 3 = TRUE (module 3.00+); bit 4 = overrideOff (module 3.00+); bit 5 = overrideOn (module 3.00+) | |||
| IR | 404 | Operation Status | Main run / warning / error flags. | BITMAP16 | Read | bit 0 = ready4Operation; bit 1 = device/functionOn; bit 2 = serviceRequired; bit 3 = warningPresent; bit 4 = errorPresent; bit 5 = finalErrorPresent | |||
| IR | 500 | heartbeatCount | Counts pump-to-module heartbeats; resets on restart. | UINT32 | ABCD | Read | |||
| IR | 504 | busCmd.TimerTimeRemain. | Seconds left before the bus command timer elapses (module 3.02+). | UINT16 | s | Read | |||
| IR | 901 | userTroubleCode | Module 3.00+. | UINT16 | Read | 0 = CODE_0; 401 = CODE_401; 402 = CODE_402; 403 = CODE_403; 404 = CODE_404; 405 = CODE_405; 406 = CODE_406; 407 = CODE_407; 408 = CODE_408; 409 = CODE_409; 410 = CODE_410; 420 = CODE_420; 421 = CODE_421; 449 = CODE_449; 550 = CODE_550; 551 = CODE_551; 552 = CODE_552; 553 = CODE_553; 554 = CODE_554; 555 = CODE_555; 556 = CODE_556; 557 = CODE_557; 558 = CODE_558; 560 = CODE_560; 561 = CODE_561; 562 = CODE_562; 563 = CODE_563; 564 = CODE_564; 565 = CODE_565; 566 = CODE_566; 567 = CODE_567; 568 = CODE_568; 569 = CODE_569; 570 = CODE_570; 571 = CODE_571; 572 = CODE_572; 573 = CODE_573; 574 = CODE_574; 575 = CODE_575; 576 = CODE_576; 577 = CODE_577; 578 = CODE_578; 579 = CODE_579; 580 = CODE_580; 581 = CODE_581; 582 = CODE_582; 583 = CODE_583; 584 = CODE_584; 586 = CODE_586; 590 = CODE_590; 598 = CODE_598; 601 = CODE_601; 602 = CODE_602; 603 = CODE_603; 604 = CODE_604; 606 = CODE_606; 607 = CODE_607; 609 = CODE_609; 610 = CODE_610; 611 = CODE_611; 614 = CODE_614; 615 = CODE_615; 618 = CODE_618; 619 = CODE_619; 621 = CODE_621; 641 = CODE_641; 642 = CODE_642; 643 = CODE_643; 644 = CODE_644; 646 = CODE_646; 647 = CODE_647; 649 = CODE_649; 650 = CODE_650; 658 = CODE_658; 659 = CODE_659; 888 = INVALID | |||
| IR | 940 | warning/errorMessage | Active Wilo warning/error code. | UINT16 | Read | 0 = NO_ERROR; 3 = FLUID_TEMP_HI; 4 = MAINS_VOLT_LO; 5 = MAINS_VOLT_HI; 6 = MAINS_PHASE; 7 = PUMP_GENERATOR; 9 = PUMP_TURBINE; 10 = PUMP_BLOCKED; 11 = PUMP_DRY_RUN; 25 = MOT_OPEN_CIRC; 26 = MOT_TEMP_SENS; 30 = MOD_TEMP_HI; 33 = MOD_VOLT_DC_HI; 42 = SENS_IN1; 43 = SENS_IN2; 50 = COM_LOC_BIND; 51 = COM_MP; 52 = COM_MP_TIMEOUT; 54 = COM_REM_BIND; 72 = ELECT_POW; 77 = ELECT_SUPP_24_I; 89 = MOT_MOD_FAULT; 97 = SET_DATA_MISS; 100 = CTRL_BATT; 104 = CTRL_FAN_EXT; 119 = MCTL_TURBINE; 251 = EXTENDED_WARN; 252 = EXTENDED_ERR; 255 = INVALID | |||
| IR | 5000 | temperat.FluidRet flush system high-limit | Module 6.00+. | UINT16 | × 0.1 | K | Read | ||
| IR | 5002 | temperat.FluidRet flush system low-limit | Module 6.00+. | UINT16 | × 0.1 | K | Read | ||
| IR | 5008 | operationTimeRemain. flush system | Module 6.00+. | UINT16 | s | Read | |||
| IR | 5009 | operationTimeRst.able flush system max-pres-value | Module 6.00+. | UINT16 | s | Read | |||
| IR | 5012 | device/functionOn flush system average-value-168h | Module 6.00+. | UINT16 | Read | ||||
| IR | 5013 | volume flush system | Module 6.00+. | UINT16 | × 0.01 | m³ | Read | ||
| IR | 5014 | temperat.FluidRet flush system start-value | Module 6.00+. | UINT16 | × 0.1 | K | Read | ||
| IR | 5015 | flow flush system | Module 6.00+. | UINT16 | × 0.01 | m³/h | Read | ||
| IR | 5016 | volume flush system average-value-168h | Module 6.00+. | UINT16 | × 0.01 | m³ | Read | ||
| IR | 5017 | temperat.FluidRet minimum-value-24h | Module 6.00+. | UINT16 | × 0.1 | K | Read | ||
| IR | 5018 | temperat.FluidRet average-value-24h | Module 6.00+. | UINT16 | × 0.1 | K | Read | ||
| IR | 5019 | temperat.FluidRet maximum-value-24h | Module 6.00+. | UINT16 | × 0.1 | K | Read | ||
| IR | 5020 | temperat.FluidFwd minimum-value-24h | Module 6.00+. | UINT16 | × 0.1 | K | Read | ||
| IR | 5021 | temperat.FluidFwd average-value-24h | Module 6.00+. | UINT16 | × 0.1 | K | Read | ||
| IR | 5022 | temperat.FluidFwd maximum-value-24h | Module 6.00+. | UINT16 | × 0.1 | K | Read | ||
| HR | 1 | dutyPointRel | Setpoint in % of the active mode's 100 % value (200 = 100 %). | INT16 | × 0.5 | % | Read/write | ||
| HR | 40 | Pump Command in | On/off and override command word. | BITMAP16 | Read/write | bit 0 = device/functionOn; bit 1 = overrideMin; bit 2 = overrideMax; bit 3 = TRUE; bit 4 = overrideOff (module 3.00+); bit 5 = overrideOn (module 3.00+) | |||
| HR | 42 | controlFunction | Control mode; unsupported values are ignored. | UINT16 | Read/write | 1 = Gen_Spd; 3 = Gen_PHdConst; 15 = INVALID | |||
| HR | 300 | busCmd.Timer | Bus command timer / fallback state machine. | UINT16 | Read/write | 1 = OFF; 2 = SET; 3 = ACTIVE; 4 = RESET; 5 = MANUAL; 6 = SET_PRESET; 7 = ACTIVE_PRESET; 8 = RESET_PRESET; 9 = MANUAL_PRESET | |||
| HR | 400 | busCmd.TimerTimeout | Bus command timer timeout. Module 3.00+. | UINT16 | s | Read/write | |||
| HR | 401 | setpointSignalSource | Where the setpoint comes from; write 1 for bus control. | UINT16 | Read/write | 1 = IF-Module; 6 = Internal; 9 = INVALID | |||
| HR | 402 | dutyPointRel preset | Fallback setpoint used by the bus command timer. | INT16 | × 0.5 | % | Read/write | ||
| HR | 403 | controlFunction preset | Fallback control mode. | UINT16 | Read/write | 1 = Gen_Spd; 3 = Gen_PHdConst; 15 = INVALID | |||
| HR | 404 | Pump Command preset | Fallback on/off command. | BITMAP16 | Read/write | bit 0 = device/functionOn preset | |||
| HR | 405 | setpointSignalSource preset | Fallback setpoint source. | UINT16 | Read/write | 1 = IF-Module; 6 = Internal; 9 = INVALID | |||
| HR | 412 | dutyPointRel aux. | Module 3.01+. | INT16 | × 0.5 | % | Read/write | ||
| HR | 413 | controlFunction aux. | Module 3.01+. | UINT16 | Read/write | 1 = Gen_Spd; 3 = Gen_PHdConst; 15 = INVALID | |||
| HR | 414 | Pump Command aux. | Module 3.01+. | BITMAP16 | Read/write | bit 0 = device/functionOn aux. (module 3.01+) | |||
| HR | 415 | setpointSignalSource aux. | Module 3.01+. | UINT16 | Read/write | 1 = IF-Module; 6 = Internal; 9 = INVALID | |||
| HR | 416 | parameterSetSelector | Which parameter set drives the pump (module 3.01+). | UINT16 | Read/write | 1 = norm; 2 = aux; 3 = preset | |||
| HR | 420 | flow limit. max | Module 3.02+. | FLOAT32 | ABCD | m³/h | Read/write | ||
| HR | 422 | flow limit. min | Module 3.02+. | FLOAT32 | ABCD | m³/h | Read/write | ||
| HR | 424 | flow limit. off | Module 3.02+. | FLOAT32 | ABCD | m³/h | Read/write | ||
| HR | 5000 | temperat.FluidRet flush system high-limit | Module 6.00+. | UINT16 | × 0.1 | K | Read/write | ||
| HR | 5002 | temperat.FluidRet flush system low-limit | Module 6.00+. | UINT16 | × 0.1 | K | Read/write |
Notes on this map
- Source is Wilo's public HTML functional description for the CIF module Modbus RTU, which marks every register and every enumeration/bit value with the pump families that support it. Only registers, values and bits marked for SiFresh are kept here; values and bits not listed are not supported on this pump. Facts are re-keyed and the document is linked, not re-hosted.
- 32-bit values (REAL = FLOAT32, UDINT = UINT32) are stored with the most significant 16 bits at the base address (ABCD), as stated in section 6.1.4.
- Scale: engineering value = raw x scale from Wilo's list (e.g. pressure x 10 = cm H2O, operation time x 10 = h, flow x 0.1 = m3/h, duty point x 0.5 = %, temperatures x 0.1 = K).
- Temperatures are in kelvin with scale 0.1 (raw 2932 = 293.2 K, about 20 °C).
- Error values: an unavailable reading returns the largest positive value of its data type (65535 for UINT, 32767 for INT).
- Flow (input register 2): Wilo lists it twice with the same address, type and scale; up to module 6.00 its error value is 9999, from 6.01 it is 65535.
- Module-version requirements from the list are noted in descriptions ('Module 3.01+' etc.); registers without a note exist from module version 1.00.
- Left out: identification registers (700-750: BCD software revisions, vendor ID, UUID, article number), system time (502), energy-meter start timestamps (306/310), the double-pump total runtime (9) and 'pressure max-pres-value' (212, ambiguous between live and maximum pressure).
- Also left out: the SiFresh flushing-program registers (holding 5003 and input 5003-5010: flushing type, phase and active/idle time, module 6.00+).
Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.
Questions about the Wilo SiFresh with CIF module Modbus RTU
What Modbus registers does the Wilo SiFresh with CIF module Modbus RTU have?
This map lists 92 registers: 72 input registers, 20 holding registers. 20 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.
Are the Wilo SiFresh with CIF module Modbus RTU Modbus addresses 0-based or 1-based?
The manufacturer's document numbers registers 0-based (the number printed is the address on the wire). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. Wilo states that all register addresses are raw addresses as sent on the bus; its example frame 01 04 02 BC 00 01 reads input register 700 (0x02BC). Masters that count registers from 1 must add 1.
What byte order does the Wilo SiFresh with CIF module Modbus RTU use for 32-bit values?
Multi-register values in this map use ABCD (high word first (big-endian)). Set your client to this order for every 32/64-bit value in the table.
What are the minimum Modbus registers to integrate the Wilo SiFresh with CIF module Modbus RTU?
Start with HR 40 Pump Command in (On/off command (bit 3 = 1 when writing, if listed)); HR 42 controlFunction (Control mode); HR 1 dutyPointRel (Setpoint (duty point, 0.5 % steps)); IR 404 Operation Status (Operation status flags); IR 940 warning/errorMessage (Active warning/error code); IR 1 pressure (Actual pressure); IR 2 flow (Flow); IR 4 powerInput (Power input).
How do I enable Modbus control of the Wilo SiFresh with CIF module Modbus RTU?
Plug in the CIF module Modbus RTU and set the bus address (menu <5.2.3.0>), baud rate (parameter A, <5.2.4.0>: 5 = 9600, 6 = 19200, 7 = 38400 ...) and frame (parameter C, <5.2.5.0>: 2 = 8N1, 3 = 8N2, 6 = 8E1, 10 = 8O1). OFF as bus address disables the interface.
What happens when the Wilo SiFresh with CIF module Modbus RTU loses Modbus communication?
The bus command timer (H 300, timeout in H 400 where supported) can switch the pump to the preset command, mode and duty point (H 402-405) when the master stops refreshing it.
Where is the official Wilo SiFresh with CIF module Modbus RTU Modbus documentation?
The source is WILO Modbus RTU (wilo194406), published free by Wilo at https://cms.media.wilo.com/cdndoc/wilo194406/11516106/wilo194406.html.
More Wilo Modbus register maps
- Pump (high-efficiency circulator)
Wilo Atmos MAXO with CIF module Modbus RTU
Wilo Atmos MAXO pumps fitted with the plug-in CIF module Modbus RTU (module firmware 1.00-99.99); registers needing a newer module are marked.
Also known as: Wilo-Atmos MAXO - Pump (multistage pressure-boosting pump)
Wilo Helix2.0-VE / Medana CH3-LE with CIF module Modbus RTU
Wilo Helix2.0-VE pumps fitted with the plug-in CIF module Modbus RTU (module firmware 1.00-99.99); registers needing a newer module are marked.
Also known as: Wilo-Helix2.0-VE, Medana CH3-LE, Wilo-Medana CH3-LE - Pump (pressure-boosting pump)
Wilo Isar MODH1-E with CIF module Modbus RTU
Wilo Isar MODH1-E pumps fitted with the plug-in CIF module Modbus RTU (module firmware 1.00-99.99); registers needing a newer module are marked.
Also known as: Wilo-Isar MODH1-E - Pump (high-efficiency circulator)
Wilo Para MAXO (built-in Modbus RTU)
Wilo-Para MAXO OEM circulators with the built-in Modbus RTU interface (module versions 1.00-99.99).
Also known as: Para MAXO, Wilo-Para MAXO, Para MAXO Modbus - Pump (high-efficiency inline circulator)
Wilo Stratos GIGA2.0 with CIF module Modbus RTU
Wilo Stratos GIGA2.0 pumps fitted with the plug-in CIF module Modbus RTU (module firmware 1.00-99.99); registers needing a newer module are marked.
Also known as: Stratos GIGA2.0-I, Stratos GIGA2.0-D, Wilo-Stratos GIGA2.0 - Pump (smart circulator)
Wilo Stratos MAXO with CIF module Modbus RTU
Wilo-Stratos MAXO single and twin-head circulators fitted with the plug-in CIF module Modbus RTU (article 2190368, UL 2237080), module firmware 1.00-99.99; some registers need a newer module version as noted.
Also known as: Wilo-Stratos MAXO, Stratos MAXO-D, Stratos MAXO-Z, CIF-Module Modbus RTU, CIF Modbus RTU 2190368, CIF Modbus RTU UL 2237080 - Pump (high-efficiency circulator)
Wilo Stratos PICO plus with CIF module Modbus RTU
Wilo Stratos PICO plus pumps fitted with the plug-in CIF module Modbus RTU (module firmware 1.00-99.99); registers needing a newer module are marked.
Also known as: Wilo-Stratos PICO plus - Pump controller (switchgear)
Wilo Wilo-Control EC-WP switchgear (ModBus RTU)
Wilo-Control EC-WP for one or two fixed-speed pumps, hardware HW2, software SW102x (instructions Ed.01/2024-08, 2552567).
Also known as: Control EC-WP, Wilo Control EC WP, EC-WP - Pump (high-efficiency inline circulator)
Wilo Yonos GIGA2.0 with CIF module Modbus RTU
Wilo Yonos GIGA2.0 pumps fitted with the plug-in CIF module Modbus RTU (module firmware 1.00-99.99); registers needing a newer module are marked.
Also known as: Yonos GIGA2.0-I, Yonos GIGA2.0-D, Wilo-Yonos GIGA2.0
Other pumps register maps
- Heat pump Modbus interface
Airzone Aidoo Pro Modbus control for air-to-water heat pumps
Airzone Aidoo Pro units configured for Modbus output and connected to an air-to-water heat pump; register table 'Registers for Air-to-Water HP units' of the Aidoo - Modbus integration manual (v. 201).
Also known as: Aidoo Pro, Aidoo Pro Modbus air-to-water, Airzone Aidoo Modbus aerothermal - Heat pump
Ecoforest ecoGEO / ecoAIR heat pump (API HP24 Client, Modbus RTU)
Ecoforest ecoGEO, ecoGEO HP and ecoAIR heat pumps on software AWD24, WWD24, WWC24 or later, register list API HP24_V01.02 (heat pump list only; supervisor and source-manager lists not included).
Also known as: ecoGEO, ecoGEO B&C, ecoGEO HP, ecoAIR, AWD24, WWD24, WWC24, API HP24_V01.02 - Pump protection / monitoring module (Sensor)
Grundfos IO 113 pump protection module (Modbus RTU)
Grundfos IO 113 interface module for wastewater and sewage pumps (with or without the SM 113 sensor board) set to Modbus with DIP switch 9; document edition 1.7, January 2015.
Also known as: IO113, IO 113 with SM 113, 98288208 - Heat pump (packaged wall-mount / classroom unit)
Marvair MAH heat pump and VAH/VDH Vanguard control board (Modbus RTU)
Marvair MAH1020H-1060H and MAH2024H-2060H wall-mount heat pumps (I&O manual rev. 6); the GAH1024-1060 gas-heat AC manual (rev. 5) and the VAH/VDH Vanguard classroom unit appendices (08/2026) print the same table.
Also known as: MAH1020H, MAH1024H, MAH1030H, MAH1036H, MAH1042H, MAH1048H, MAH1060H, MAH2024H, MAH2030H, MAH2036H, MAH2042H, MAH2048H, MAH2060H, Vanguard VAH, Vanguard VDH, VAH2030, VDH2060, GAH1024, GAH1030, GAH1036, GAH1042, GAH1048, GAH1060, Marvair GAH, Scholar 2 VAH/VDH, Scholar QR VAH/VDH - Heat pump Modbus interface
Realtime Control Systems RTD-LT/CA Modbus interface for Daikin Altherma LT (split, CA) air-to-water heat pumps
RTD-LT/CA on the P1/P2 bus of Daikin Altherma Split LT CA hydroboxes (heating only and heating/cooling), with an EKRUCAL1 as main controller; all modes except Sequencer. Instructions 22570-2.09.12.
Also known as: RTD-LT/CA, RTD-LT-CA, Daikin RTD-LT/CA - Heat pump (air-to-water) Modbus interface
Daikin EKRHH Daikin HomeHub (Modbus TCP/RTU for Daikin Altherma and air-to-air heat pumps)
Daikin HomeHub EKRHH in use case 3 (Modbus for Daikin Altherma air-to-water heat pumps) and use case 4 (Modbus smart-grid control of air-to-air heat pumps), installer reference guide 4P744838-1E (2026.01).
Also known as: EKRHH, Daikin HomeHub, 4P744838-1E, Daikin Altherma 3 Modbus, Altherma Smart Grid Modbus
All pumps Modbus register maps →
Source: WILO Modbus RTU · wilo194406. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.