Pump (multistage pressure-boosting pump) · Modbus register map
Wilo Helix2.0-VE / Medana CH3-LE with CIF module Modbus RTU Modbus register map
Updated 17 November 2026
The Wilo Helix2.0-VE gets Modbus RTU through Wilo's plug-in CIF module. A master switches the pump on/off with the pump command word, selects the control mode and writes a relative duty point in 0.5 % steps; a bus command timer can fall back to preset values when communication stops. Read-only data covers head, flow, power, energy, speed, temperatures and status/error words. This map keeps only the points Wilo marks as supported on the Helix2.0-VE.
This page lists 90 Modbus registers for the Wilo Helix2.0-VE / Medana CH3-LE with CIF module Modbus RTU — 21 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Wilo’s own free documentation (linked below) and checked against it.
- Manufacturer
- Wilo
- Model
- Helix2.0-VE / Medana CH3-LE with CIF module Modbus RTU
- Equipment type
- Pump (multistage pressure-boosting pump)
- Registers
- 90 (21 writable)
- Transport
- Modbus RTU
- Default unit ID
- Not stated
- Documented addressing
- 0-based (the number printed is the address on the wire)
- 32-bit word order
- ABCD high word first (big-endian)
- Firmware
- CIF module Modbus RTU 1.00-99.99 (module versions per register as noted)
- Also known as
- Wilo-Helix2.0-VE, Medana CH3-LE, Wilo-Medana CH3-LE
- Source document
- WILO Modbus RTU · wilo194406
Integration notes: Wilo Helix2.0-VE / Medana CH3-LE with CIF module Modbus RTU
Set bus address, baud (parameter A) and frame (parameter C) in the pump menu, then write the control mode (H 42), the duty point (H 1) and the pump command (H 40). Poll status (I 404 if present), error code (I 940) and the measured values in the I 1-I 10 block.
Minimum registers to map
Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.
| Register | Name | Type | Why | Access |
|---|---|---|---|---|
| HR 40 | Pump Command in | BITMAP16 | On/off command (bit 3 = 1 when writing, if listed) | Read/write |
| HR 42 | controlFunction | UINT16 | Control mode | Read/write |
| HR 1 | dutyPointRel | INT16 | Setpoint (duty point, 0.5 % steps) | Read/write |
| IR 404 | Operation Status | BITMAP16 | Operation status flags | Read |
| IR 940 | warning/errorMessage | UINT16 | Active warning/error code | Read |
| IR 1 | pressure | UINT16 | Actual pressure | Read |
| IR 2 | flow | UINT16 | Flow | Read |
| IR 4 | powerInput | UINT16 | Power input | Read |
Enable Modbus control & writes
Plug in the CIF module Modbus RTU and set the bus address (menu <5.2.3.0>), baud rate (parameter A, <5.2.4.0>: 5 = 9600, 6 = 19200, 7 = 38400 ...) and frame (parameter C, <5.2.5.0>: 2 = 8N1, 3 = 8N2, 6 = 8E1, 10 = 8O1). OFF as bus address disables the interface.
Communication loss & watchdog
The bus command timer (H 300, timeout in H 400 where supported) can switch the pump to the preset command, mode and duty point (H 402-405) when the master stops refreshing it.
Byte order & addressing
- Register numbers are raw wire addresses; do not subtract 1.
- Duty points are in 0.5 % steps (200 = 100 %).
- Unsupported control-mode values are ignored by the pump.
Network setup
- Where a setpointSignalSource register is listed, select IF-Module (value 1) as the setpoint source if the duty point should come from the bus.
- Terminate the RS-485 line at both ends.
Watch out for
- Temperatures are in kelvin.
- Last write wins between the bus, the pump display and other remote controls.
Wilo Helix2.0-VE / Medana CH3-LE with CIF module Modbus RTU Modbus registers
Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.
| Table | Address | Name | Description | Type | Order | Scale | Units | Access | Values / bits |
|---|---|---|---|---|---|---|---|---|---|
| IR | 1 | pressure | Actual pressure (head) at the pump. | UINT16 | × 10 | cm H₂O | Read | ||
| IR | 2 | flow | Actual or calculated flow. Error value 9999 up to module 6.00, 65535 from 6.01. | UINT16 | × 0.1 | m³/h | Read | ||
| IR | 3 | energyConsumption | Energy consumption counter. | UINT16 | kWh | Read | |||
| IR | 4 | powerInput | Electrical power input. | UINT16 | W | Read | |||
| IR | 5 | operationTime | Operating hours counter. | UINT16 | × 10 | h | Read | ||
| IR | 7 | speed | Motor speed. | INT16 | 1/min | Read | |||
| IR | 10 | controlFunction | Active control mode. | UINT16 | Read | 1 = Gen_Spd; 3 = Gen_PHdConst; 4 = Gen_PHdVar; 5 = Gen_PConst; 15 = INVALID; 86 = ScndSpd; 139 = Gen_PVar; 140 = Gen_UsrDfd | |||
| IR | 16 | Pump Module | Pump module flags. | BITMAP16 | Read | bit 0 = TRUE | |||
| IR | 17 | pumpTypePLR | Pump type code. | UINT16 | Read | 254 = EXTENDED | |||
| IR | 18 | speed max-pres-value | Maximum speed. | UINT16 | 1/min | Read | |||
| IR | 19 | speed min-pres-value | Minimum speed. | UINT16 | 1/min | Read | |||
| IR | 20 | pressureMaxPHdConst | Max pressure setpoint in dp-c; scales % back to head. | UINT16 | × 10 | cm H₂O | Read | ||
| IR | 21 | pressureMinPHdConst | Min pressure setpoint in dp-c. | UINT16 | × 10 | cm H₂O | Read | ||
| IR | 22 | pressureMaxPHdVar | Max pressure setpoint in dp-v. | UINT16 | × 10 | cm H₂O | Read | ||
| IR | 23 | pressureMinPHdVar | Min pressure setpoint in dp-v. | UINT16 | × 10 | cm H₂O | Read | ||
| IR | 24 | flow max-pres-value | Maximum (calculated) flow. | UINT16 | × 0.1 | m³/h | Read | ||
| IR | 25 | flow min-pres-value | Minimum (calculated) flow. | UINT16 | × 0.1 | m³/h | Read | ||
| IR | 28 | powerInput max-pres-value | Maximum electrical input power. | UINT16 | W | Read | |||
| IR | 35 | Service Message | Legacy register. | BITMAP16 | Read | bit 0 = serviceRequired; bit 1 = FALSE; bit 2 = FALSE; bit 3 = FALSE | |||
| IR | 36 | Error Type | Legacy register; prefer I 940 for new work. | BITMAP16 | Read | bit 0 = moduleError; bit 1 = motorError; bit 3 = errorPresent; bit 4 = supplyVoltageError | |||
| IR | 37 | Error Message | Legacy detailed error flags. | BITMAP16 | Read | bit 0 = statusUndervoltage; bit 1 = overVoltage; bit 2 = phaseFault; bit 3 = idleRunning; bit 8 = motorOverheated; bit 9 = motorError; bit 10 = pumpBlocked; bit 11 = moduleOverheated; bit 12 = moduleWarning; bit 13 = moduleError; bit 14 = sensorMalfunction | |||
| IR | 38 | Pump Status | Legacy controller status flags. | BITMAP16 | Read | bit 0 = device/functionOn; bit 1 = FALSE; bit 2 = setpointDifference; bit 3 = overrideOff; bit 5 = localOperation; bit 7 = overrideMin; bit 8 = FALSE (module 5.00+); bit 9 = FALSE (module 5.00+); bit 10 = FALSE (module 5.00+); bit 11 = FALSE (module 5.00+); bit 12 = externalSetpoint (module 5.00+); bit 14 = FALSE (module 5.00+) | |||
| IR | 39 | State Diagnostics | Legacy diagnostic flags. | BITMAP16 | Read | bit 0 = errorPresent; bit 1 = supplyVoltageError; bit 3 = lowRegulationLimit; bit 4 = highRegulationLimit; bit 6 = setpointOutOfRange; bit 8 = localOperation; bit 10 = device/functionOn | |||
| IR | 80 | Pump Module | Module flags of the partner pump (twin-head). | BITMAP16 | Read | bit 0 = TRUE | |||
| IR | 81 | pumpTypePLR | Pump type code of the partner pump. | UINT16 | Read | 254 = EXTENDED | |||
| IR | 102 | Pump Status | Status flags of the partner pump (twin-head). | BITMAP16 | Read | bit 1 = FALSE; bit 2 = setpointDifference; bit 3 = overrideOff; bit 5 = localOperation; bit 7 = overrideMin | |||
| IR | 200 | dutyPointRel | Setpoint the pump is actually using (200 = 100 %). Module 3.00+. | INT16 | × 0.5 | % | Read | ||
| IR | 202 | dutyPointRel maximum-output | Upper limit of the active setpoint. Module 3.00+. | INT16 | × 0.5 | % | Read | ||
| IR | 204 | dutyPointRel minimum-output | Lower limit; lower writes are limited to it. Module 3.00+. | INT16 | × 0.5 | % | Read | ||
| IR | 206 | dutyPoint100%Val | Engineering value at 100 % in the current mode; unit in I 208. Module 3.00+. | FLOAT32 | ABCD | Read | |||
| IR | 208 | dutyPointRel units | Unit code for I 206. Module 3.00+. | UINT16 | Read | 5 = V; 19 = kWh; 47 = W; 55 = bar; 62 = Cel; 63 = K; 73 = s; 80 = m3; 95 = {noUnit}; 104 = min-1; 135 = m3/h | |||
| IR | 210 | setpointSignalSource | Module 3.00+. | UINT16 | Read | 1 = IF-Module; 6 = Internal; 7 = EXT 1; 8 = EXT 2; 9 = INVALID | |||
| IR | 211 | parameterSetSelector | Parameter set in use (module 3.01+). | UINT16 | Read | 1 = norm; 2 = aux; 3 = preset | |||
| IR | 222 | dutyPointRel maximum-output | Module 3.01+. | INT16 | × 0.5 | % | Read | ||
| IR | 224 | dutyPointRel minimum-output | Module 3.01+. | INT16 | × 0.5 | % | Read | ||
| IR | 226 | dutyPoint100%Val | Module 3.01+. | FLOAT32 | ABCD | Read | |||
| IR | 228 | dutyPointRel units | Module 3.01+. | UINT16 | Read | 5 = V; 19 = kWh; 47 = W; 55 = bar; 62 = Cel; 63 = K; 73 = s; 80 = m3; 95 = {noUnit}; 104 = min-1; 135 = m3/h | |||
| IR | 232 | dutyPointRel aux. maximum-output | Module 3.01+. | INT16 | × 0.5 | % | Read | ||
| IR | 234 | dutyPointRel aux. minimum-output | Module 3.01+. | INT16 | × 0.5 | % | Read | ||
| IR | 236 | dutyPoint100%Val aux. | Module 3.01+. | FLOAT32 | ABCD | Read | |||
| IR | 238 | dutyPointRel aux. units | Module 3.01+. | UINT16 | Read | 5 = V; 19 = kWh; 47 = W; 55 = bar; 62 = Cel; 63 = K; 73 = s; 80 = m3; 95 = {noUnit}; 104 = min-1; 135 = m3/h | |||
| IR | 242 | dutyPointRel preset maximum-output | Module 3.01+. | INT16 | × 0.5 | % | Read | ||
| IR | 244 | dutyPointRel preset minimum-output | Module 3.01+. | INT16 | × 0.5 | % | Read | ||
| IR | 246 | dutyPoint100%Val preset | Module 3.01+. | FLOAT32 | ABCD | Read | |||
| IR | 248 | dutyPointRel preset units | Module 3.01+. | UINT16 | Read | 5 = V; 19 = kWh; 47 = W; 55 = bar; 62 = Cel; 63 = K; 73 = s; 80 = m3; 95 = {noUnit}; 104 = min-1; 135 = m3/h | |||
| IR | 250 | dutyPointRel | Module 3.01+. | INT16 | × 0.5 | % | Read | ||
| IR | 252 | dutyPointRel maximum-output | Module 3.01+. | INT16 | × 0.5 | % | Read | ||
| IR | 254 | dutyPointRel minimum-output | Module 3.01+. | INT16 | × 0.5 | % | Read | ||
| IR | 256 | dutyPoint100%Val | Module 3.01+. | FLOAT32 | ABCD | Read | |||
| IR | 258 | dutyPointRel units | Module 3.01+. | UINT16 | Read | 5 = V; 19 = kWh; 47 = W; 55 = bar; 62 = Cel; 63 = K; 73 = s; 80 = m3; 95 = {noUnit}; 104 = min-1; 135 = m3/h | |||
| IR | 260 | controlFunction | Module 3.01+. | UINT16 | Read | 1 = Gen_Spd; 3 = Gen_PHdConst; 4 = Gen_PHdVar; 5 = Gen_PConst; 15 = INVALID; 86 = ScndSpd; 139 = Gen_PVar; 140 = Gen_UsrDfd | |||
| IR | 261 | Pump Command | Module 3.01+. | BITMAP16 | Read | bit 0 = device/functionOn (module 3.01+) | |||
| IR | 262 | setpointSignalSource | Module 3.01+. | UINT16 | Read | 1 = IF-Module; 6 = Internal; 7 = EXT 1; 8 = EXT 2; 9 = INVALID | |||
| IR | 282 | motorSpaceHeating | Module 6.10+. | UINT16 | Read | 1 = FUN_INVALID; 2 = FUN_RESERVED; 3 = FUN_NOT_SUPP; 4 = FUN_NOT_AVAIL; 5 = FUN_DISABLE; 6 = FUN_ENABLE; 7 = FUN_ACTIVE | |||
| IR | 320 | voltageInput | Mains input voltage. Module 3.00+. | UINT16 | × 0.1 | V | Read | ||
| IR | 324 | analogIn1MeasuredVal | Module 3.00+. | FLOAT32 | ABCD | Read | |||
| IR | 326 | analogIn2MeasuredVal | Module 3.00+. | FLOAT32 | ABCD | Read | |||
| IR | 328 | analogIn1MeasuredVal units | Module 3.02+. | UINT16 | Read | 5 = V; 19 = kWh; 47 = W; 55 = bar; 62 = Cel; 63 = K; 73 = s; 80 = m3; 95 = {noUnit}; 104 = min-1; 135 = m3/h | |||
| IR | 329 | analogIn2MeasuredVal units | Module 3.02+. | UINT16 | Read | 5 = V; 19 = kWh; 47 = W; 55 = bar; 62 = Cel; 63 = K; 73 = s; 80 = m3; 95 = {noUnit}; 104 = min-1; 135 = m3/h | |||
| IR | 340 | sensorSignal | Module 5.02+. | FLOAT32 | ABCD | Read | |||
| IR | 342 | pressureSuction | Module 6.01+. | FLOAT32 | ABCD | bar | Read | ||
| IR | 344 | pressureDischarge | Module 6.01+. | FLOAT32 | ABCD | bar | Read | ||
| IR | 400 | dutyPointRel | Duty point currently in use. | INT16 | × 0.5 | % | Read | ||
| IR | 402 | Pump Command active | Command currently in effect. | BITMAP16 | Read | bit 0 = device/functionOn; bit 1 = overrideMin; bit 2 = overrideMax; bit 3 = TRUE (module 3.00+); bit 4 = overrideOff (module 3.00+); bit 5 = overrideOn (module 3.00+) | |||
| IR | 404 | Operation Status | Main run / warning / error flags. | BITMAP16 | Read | bit 0 = ready4Operation; bit 1 = device/functionOn; bit 2 = serviceRequired; bit 3 = warningPresent; bit 4 = errorPresent; bit 5 = finalErrorPresent | |||
| IR | 500 | heartbeatCount | Counts pump-to-module heartbeats; resets on restart. | UINT32 | ABCD | Read | |||
| IR | 504 | busCmd.TimerTimeRemain. | Seconds left before the bus command timer elapses (module 3.02+). | UINT16 | s | Read | |||
| IR | 901 | userTroubleCode | Module 3.00+. | UINT16 | Read | 0 = CODE_0; 401 = CODE_401; 402 = CODE_402; 403 = CODE_403; 404 = CODE_404; 405 = CODE_405; 406 = CODE_406; 407 = CODE_407; 408 = CODE_408; 409 = CODE_409; 410 = CODE_410; 412 = CODE_412; 413 = CODE_413; 414 = CODE_414; 415 = CODE_415; 416 = CODE_416; 420 = CODE_420; 421 = CODE_421; 449 = CODE_449; 550 = CODE_550; 551 = CODE_551; 552 = CODE_552; 553 = CODE_553; 556 = CODE_556; 558 = CODE_558; 560 = CODE_560; 561 = CODE_561; 562 = CODE_562; 564 = CODE_564; 565 = CODE_565; 566 = CODE_566; 570 = CODE_570; 571 = CODE_571; 573 = CODE_573; 574 = CODE_574; 578 = CODE_578; 582 = CODE_582; 588 = CODE_588; 597 = CODE_597; 660 = CODE_660; 661 = CODE_661; 662 = CODE_662; 888 = INVALID | |||
| IR | 940 | warning/errorMessage | Active Wilo warning/error code. | UINT16 | Read | 0 = NO_ERROR; 3 = FLUID_TEMP_HI; 4 = MAINS_VOLT_LO; 5 = MAINS_VOLT_HI; 6 = MAINS_PHASE; 7 = PUMP_GENERATOR; 9 = PUMP_TURBINE; 10 = PUMP_BLOCKED; 11 = PUMP_DRY_RUN; 25 = MOT_OPEN_CIRC; 26 = MOT_TEMP_SENS; 30 = MOD_TEMP_HI; 33 = MOD_VOLT_DC_HI; 42 = SENS_IN1; 43 = SENS_IN2; 50 = COM_LOC_BIND; 51 = COM_MP; 52 = COM_MP_TIMEOUT; 54 = COM_REM_BIND; 72 = ELECT_POW; 77 = ELECT_SUPP_24_I; 89 = MOT_MOD_FAULT; 97 = SET_DATA_MISS; 100 = CTRL_BATT; 104 = CTRL_FAN_EXT; 119 = MCTL_TURBINE; 251 = EXTENDED_WARN; 252 = EXTENDED_ERR; 255 = INVALID | |||
| HR | 1 | dutyPointRel | Setpoint in % of the active mode's 100 % value (200 = 100 %). | INT16 | × 0.5 | % | Read/write | ||
| HR | 40 | Pump Command in | On/off and override command word. | BITMAP16 | Read/write | bit 0 = device/functionOn; bit 1 = overrideMin; bit 2 = overrideMax; bit 3 = TRUE; bit 4 = overrideOff (module 3.00+); bit 5 = overrideOn (module 3.00+) | |||
| HR | 42 | controlFunction | Control mode; unsupported values are ignored. | UINT16 | Read/write | 1 = Gen_Spd; 3 = Gen_PHdConst; 4 = Gen_PHdVar; 5 = Gen_PConst; 15 = INVALID; 86 = ScndSpd; 139 = Gen_PVar; 140 = Gen_UsrDfd | |||
| HR | 300 | busCmd.Timer | Bus command timer / fallback state machine. | UINT16 | Read/write | 1 = OFF; 2 = SET; 3 = ACTIVE; 4 = RESET; 5 = MANUAL; 6 = SET_PRESET; 7 = ACTIVE_PRESET; 8 = RESET_PRESET; 9 = MANUAL_PRESET; 10 = INVALID | |||
| HR | 306 | sensorSignal | Module 3.02+. | FLOAT32 | ABCD | Read/write | |||
| HR | 400 | busCmd.TimerTimeout | Bus command timer timeout. Module 3.00+. | UINT16 | s | Read/write | |||
| HR | 401 | setpointSignalSource | Where the setpoint comes from; write 1 for bus control. | UINT16 | Read/write | 1 = IF-Module; 6 = Internal; 7 = EXT 1; 8 = EXT 2; 9 = INVALID | |||
| HR | 402 | dutyPointRel preset | Fallback setpoint used by the bus command timer. | INT16 | × 0.5 | % | Read/write | ||
| HR | 403 | controlFunction preset | Fallback control mode. | UINT16 | Read/write | 1 = Gen_Spd; 3 = Gen_PHdConst; 4 = Gen_PHdVar; 5 = Gen_PConst; 15 = INVALID; 86 = ScndSpd; 139 = Gen_PVar; 140 = Gen_UsrDfd | |||
| HR | 404 | Pump Command preset | Fallback on/off command. | BITMAP16 | Read/write | bit 0 = device/functionOn preset | |||
| HR | 405 | setpointSignalSource preset | Fallback setpoint source. | UINT16 | Read/write | 1 = IF-Module; 6 = Internal; 7 = EXT 1; 8 = EXT 2; 9 = INVALID | |||
| HR | 408 | pidKp | INT16 | × 0.01 | Read/write | ||||
| HR | 409 | pidTi | INT16 | × 0.01 | s | Read/write | |||
| HR | 410 | pidTd | INT16 | × 0.01 | s | Read/write | |||
| HR | 412 | dutyPointRel aux. | Module 3.01+. | INT16 | × 0.5 | % | Read/write | ||
| HR | 413 | controlFunction aux. | Module 3.01+. | UINT16 | Read/write | 1 = Gen_Spd; 3 = Gen_PHdConst; 4 = Gen_PHdVar; 5 = Gen_PConst; 15 = INVALID; 86 = ScndSpd; 139 = Gen_PVar; 140 = Gen_UsrDfd | |||
| HR | 414 | Pump Command aux. | Module 3.01+. | BITMAP16 | Read/write | bit 0 = device/functionOn aux. (module 3.01+) | |||
| HR | 415 | setpointSignalSource aux. | Module 3.01+. | UINT16 | Read/write | 1 = IF-Module; 6 = Internal; 7 = EXT 1; 8 = EXT 2; 9 = INVALID | |||
| HR | 416 | parameterSetSelector | Which parameter set drives the pump (module 3.01+). | UINT16 | Read/write | 1 = norm; 2 = aux; 3 = preset | |||
| HR | 426 | flowZeroSetpointRed.Factor | Module 3.02+. | INT16 | × 0.5 | % | Read/write | ||
| HR | 427 | flowNominal4Ctrl.Fun. | Module 3.02+. | UINT16 | × 0.1 | m³/h | Read/write |
Notes on this map
- Source is Wilo's public HTML functional description for the CIF module Modbus RTU, which marks every register and every enumeration/bit value with the pump families that support it. Only registers, values and bits marked for Helix2.0-VE are kept here; values and bits not listed are not supported on this pump. Facts are re-keyed and the document is linked, not re-hosted.
- 32-bit values (REAL = FLOAT32, UDINT = UINT32) are stored with the most significant 16 bits at the base address (ABCD), as stated in section 6.1.4.
- Scale: engineering value = raw x scale from Wilo's list (e.g. pressure x 10 = cm H2O, operation time x 10 = h, flow x 0.1 = m3/h, duty point x 0.5 = %, temperatures x 0.1 = K).
- Temperatures are in kelvin with scale 0.1 (raw 2932 = 293.2 K, about 20 °C).
- Error values: an unavailable reading returns the largest positive value of its data type (65535 for UINT, 32767 for INT).
- Flow (input register 2): Wilo lists it twice with the same address, type and scale; up to module 6.00 its error value is 9999, from 6.01 it is 65535.
- Module-version requirements from the list are noted in descriptions ('Module 3.01+' etc.); registers without a note exist from module version 1.00.
- Left out: identification registers (700-750: BCD software revisions, vendor ID, UUID, article number), system time (502), energy-meter start timestamps (306/310), the double-pump total runtime (9) and 'pressure max-pres-value' (212, ambiguous between live and maximum pressure).
Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.
Questions about the Wilo Helix2.0-VE / Medana CH3-LE with CIF module Modbus RTU
What Modbus registers does the Wilo Helix2.0-VE / Medana CH3-LE with CIF module Modbus RTU have?
This map lists 90 registers: 69 input registers, 21 holding registers. 21 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.
Are the Wilo Helix2.0-VE / Medana CH3-LE with CIF module Modbus RTU Modbus addresses 0-based or 1-based?
The manufacturer's document numbers registers 0-based (the number printed is the address on the wire). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. Wilo states that all register addresses are raw addresses as sent on the bus; its example frame 01 04 02 BC 00 01 reads input register 700 (0x02BC). Masters that count registers from 1 must add 1.
What byte order does the Wilo Helix2.0-VE / Medana CH3-LE with CIF module Modbus RTU use for 32-bit values?
Multi-register values in this map use ABCD (high word first (big-endian)). Set your client to this order for every 32/64-bit value in the table.
What are the minimum Modbus registers to integrate the Wilo Helix2.0-VE / Medana CH3-LE with CIF module Modbus RTU?
Start with HR 40 Pump Command in (On/off command (bit 3 = 1 when writing, if listed)); HR 42 controlFunction (Control mode); HR 1 dutyPointRel (Setpoint (duty point, 0.5 % steps)); IR 404 Operation Status (Operation status flags); IR 940 warning/errorMessage (Active warning/error code); IR 1 pressure (Actual pressure); IR 2 flow (Flow); IR 4 powerInput (Power input).
How do I enable Modbus control of the Wilo Helix2.0-VE / Medana CH3-LE with CIF module Modbus RTU?
Plug in the CIF module Modbus RTU and set the bus address (menu <5.2.3.0>), baud rate (parameter A, <5.2.4.0>: 5 = 9600, 6 = 19200, 7 = 38400 ...) and frame (parameter C, <5.2.5.0>: 2 = 8N1, 3 = 8N2, 6 = 8E1, 10 = 8O1). OFF as bus address disables the interface.
What happens when the Wilo Helix2.0-VE / Medana CH3-LE with CIF module Modbus RTU loses Modbus communication?
The bus command timer (H 300, timeout in H 400 where supported) can switch the pump to the preset command, mode and duty point (H 402-405) when the master stops refreshing it.
Where is the official Wilo Helix2.0-VE / Medana CH3-LE with CIF module Modbus RTU Modbus documentation?
The source is WILO Modbus RTU (wilo194406), published free by Wilo at https://cms.media.wilo.com/cdndoc/wilo194406/11516106/wilo194406.html.
More Wilo Modbus register maps
- Pump (high-efficiency circulator)
Wilo Atmos MAXO with CIF module Modbus RTU
Wilo Atmos MAXO pumps fitted with the plug-in CIF module Modbus RTU (module firmware 1.00-99.99); registers needing a newer module are marked.
Also known as: Wilo-Atmos MAXO - Pump (pressure-boosting pump)
Wilo Isar MODH1-E with CIF module Modbus RTU
Wilo Isar MODH1-E pumps fitted with the plug-in CIF module Modbus RTU (module firmware 1.00-99.99); registers needing a newer module are marked.
Also known as: Wilo-Isar MODH1-E - Pump (high-efficiency circulator)
Wilo Para MAXO (built-in Modbus RTU)
Wilo-Para MAXO OEM circulators with the built-in Modbus RTU interface (module versions 1.00-99.99).
Also known as: Para MAXO, Wilo-Para MAXO, Para MAXO Modbus - Pump system
Wilo SiFresh with CIF module Modbus RTU
Wilo SiFresh pumps fitted with the plug-in CIF module Modbus RTU (module firmware 1.00-99.99); registers needing a newer module are marked.
Also known as: Wilo-SiFresh - Pump (high-efficiency inline circulator)
Wilo Stratos GIGA2.0 with CIF module Modbus RTU
Wilo Stratos GIGA2.0 pumps fitted with the plug-in CIF module Modbus RTU (module firmware 1.00-99.99); registers needing a newer module are marked.
Also known as: Stratos GIGA2.0-I, Stratos GIGA2.0-D, Wilo-Stratos GIGA2.0 - Pump (smart circulator)
Wilo Stratos MAXO with CIF module Modbus RTU
Wilo-Stratos MAXO single and twin-head circulators fitted with the plug-in CIF module Modbus RTU (article 2190368, UL 2237080), module firmware 1.00-99.99; some registers need a newer module version as noted.
Also known as: Wilo-Stratos MAXO, Stratos MAXO-D, Stratos MAXO-Z, CIF-Module Modbus RTU, CIF Modbus RTU 2190368, CIF Modbus RTU UL 2237080 - Pump (high-efficiency circulator)
Wilo Stratos PICO plus with CIF module Modbus RTU
Wilo Stratos PICO plus pumps fitted with the plug-in CIF module Modbus RTU (module firmware 1.00-99.99); registers needing a newer module are marked.
Also known as: Wilo-Stratos PICO plus - Pump controller (switchgear)
Wilo Wilo-Control EC-WP switchgear (ModBus RTU)
Wilo-Control EC-WP for one or two fixed-speed pumps, hardware HW2, software SW102x (instructions Ed.01/2024-08, 2552567).
Also known as: Control EC-WP, Wilo Control EC WP, EC-WP - Pump (high-efficiency inline circulator)
Wilo Yonos GIGA2.0 with CIF module Modbus RTU
Wilo Yonos GIGA2.0 pumps fitted with the plug-in CIF module Modbus RTU (module firmware 1.00-99.99); registers needing a newer module are marked.
Also known as: Yonos GIGA2.0-I, Yonos GIGA2.0-D, Wilo-Yonos GIGA2.0
Other pumps register maps
- Heat pump
Daikin DCOM-LT/MB Modbus interface for Daikin Altherma LT heat pumps
Daikin Altherma low-temperature (LT) air-to-water heat pumps fitted with the DCOM-LT/MB (model number 534-001) P1P2-to-Modbus RTU interface, standard operating mode, per reference manual 534-252-A3.
Also known as: DCOM-LT-MB, 534-001, Altherma LT Modbus interface - Heat pump (air-to-water)
Gree Versati heat pump water heater (wired-controller Modbus RTU, protocol V1.5)
Gree Versati air-to-water heat pumps through the BMS port of the wired controller, per 'Modbus Protocol (V1.5) for the Versati Heat Pump Water Heater'. The document itself does not name a generation or refrigerant; the distributor files it as the R32 Versati III protocol.
Also known as: Versati III, R32 Versati, Versati heat pump water heater, Gree Versati Modbus V1.5 - Heat pump (air-to-water)
LG THERMA V R32 Monobloc air-to-water heat pump (built-in Modbus RTU)
LG THERMA V R32 Monobloc air-to-water heat pumps covered by installation manual MFL68026615 Rev.02 (North American models ZHBW041GA0 / ZHBW048GA0 / ZHBW055GA0), using the indoor PCB's own Modbus RTU slave port.
Also known as: ZHBW041GA0, ZHBW048GA0, ZHBW055GA0, KPHTC411M, KPHTC481M, KPHTC551M, THERMA V, MFL68026615 - Heat pump / ventilation unit controller (air handler)
Nilan CTS602 controller with HMI350T panel (Modbus version 23)
Nilan ventilation, heat-recovery and compact heat pump units with the CTS602 board and HMI350T user panel, Modbus protocol version 23 (software 3.6.58/3.6.59).
Also known as: CTS 602, CTS602 HMI350T, CTS602 w. HMI350T - Pump (refrigerant pumping unit for Liebert XD rack cooling)
Vertiv Liebert XDP pumping unit for XD systems with iCOM v4 (IntelliSlot Modbus)
Liebert XDP pumping units on the iCOM v4 controller with a Liebert IntelliSlot Modbus card.
Also known as: Liebert XDP, XDP, Liebert XD pumping unit - Pump (reverse osmosis water treatment unit)
Condair RO-E reverse osmosis water treatment (Integrated Controller, Modbus RTU/TCP)
Condair RO-E / RO-E+ with the Integrated Controller, per addendum 2603326-G.
Also known as: Condair RO-E, RO-E+, Condair RO-E+
All pumps Modbus register maps →
Source: WILO Modbus RTU · wilo194406. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.