- RO-E reverse osmosis water treatment (Integrated Controller, Modbus RTU/TCP)
Pump (reverse osmosis water treatment unit) · Modbus register map
Condair RO-E reverse osmosis water treatment (Integrated Controller, Modbus RTU/TCP) Modbus register map
Updated 17 November 2026
The Condair RO-E is a reverse osmosis unit that makes demineralised water for humidifiers. Its Integrated Controller is a Modbus RTU slave or Modbus TCP server. This map covers fault and RO status, valve states, unit type and capacity, pressures, permeate conductivity, temperature and flow, and service counters.
This page lists 20 Modbus registers for the Condair RO-E reverse osmosis water treatment (Integrated Controller, Modbus RTU/TCP) — 0 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Condair’s own free documentation (linked below) and checked against it.
- Manufacturer
- Condair
- Model
- RO-E reverse osmosis water treatment (Integrated Controller, Modbus RTU/TCP)
- Equipment type
- Pump (reverse osmosis water treatment unit)
- Registers
- 20 (0 writable)
- Transport
- Modbus RTU, Modbus TCP
- Default unit ID
- 10
- Default serial
- 19200 baud, 8E1
- TCP port
- 502
- Documented addressing
- Modicon 3xxxx/4xxxx (drop the prefix, subtract 1)
- 32-bit word order
- ABCD high word first (big-endian)
- Also known as
- Condair RO-E, RO-E+, Condair RO-E+
Integration notes: Condair RO-E reverse osmosis water treatment (Integrated Controller, Modbus RTU/TCP)
Read input registers 2500-2510 (UInt16 states) and 2513-2529 (floats and the disinfection counter).
Minimum registers to map
Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.
| Register | Name | Type | Why | Access |
|---|---|---|---|---|
| IR 2500 | Fault Status | UINT16 | Fault status | Read |
| IR 2507 | RO Status | UINT16 | RO status | Read |
| IR 2513 | Inlet pressure | FLOAT32 ABCD | Inlet pressure | Read |
| IR 2517 | Membrane pressure | FLOAT32 ABCD | Membrane pressure | Read |
| IR 2519 | Permeate conductivity | FLOAT32 ABCD | Permeate conductivity | Read |
Enable Modbus control & writes
Network > Modbus Settings on the controller.
Byte order & addressing
- The address column is the wire address; 32001 is address 2000.
- Floats are two registers, MSR first by default.
Network setup
- Menu > password 8808 > Network > Modbus Settings: set protocol (Modbus/RTU or Modbus/TCP), address, parity, baud rate and register sequence; the controller restarts after a protocol change.
- For Modbus TCP set the IP parameters under Network > IP Settings (factory setting DHCP).
Watch out for
- 2527 (next disinfection) is UInt16 between two floats; read it on its own or mind the block layout.
Condair RO-E reverse osmosis water treatment (Integrated Controller, Modbus RTU/TCP) Modbus registers
Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.
| Table | Address | Name | Description | Type | Order | Scale | Units | Access | Values / bits |
|---|---|---|---|---|---|---|---|---|---|
| IR | 2003doc 32004 | Error or Warning Code | 0 = no error; other codes are listed in the device operation manual. | UINT16 | Read | ||||
| IR | 2500doc 32501 | Fault Status | UINT16 | Read | 0 = No Error; 1 = Warning; 2 = Error | ||||
| IR | 2501doc 32502 | Y11 Inlet valve | UINT16 | Read | 0 = Closed; 1 = Open | ||||
| IR | 2502doc 32503 | Y12 Drain valve | UINT16 | Read | 0 = Open; 1 = Closed | ||||
| IR | 2503doc 32504 | Y13 Outlet valve | UINT16 | Read | 0 = Open; 1 = Closed | ||||
| IR | 2504doc 32505 | Y15 Permeate valve | UINT16 | Read | 0 = Drain; 1 = Tank | ||||
| IR | 2505doc 32506 | Y16 Concentrate valve | UINT16 | Read | 0 = Closed; 1 = Open | ||||
| IR | 2506doc 32507 | UO Type | UINT16 | Read | 0 = RO-E; 1 = RO-E+ | ||||
| IR | 2507doc 32508 | RO Status | UINT16 | Read | 0 = Initializing; 1 = Diagnostic; 2 = Stopped; 3 = Hold; 4 = Filling; 5 = Standby; 6 = Flushing; 7 = Draining | ||||
| IR | 2508doc 32509 | UO Capacity | UINT16 | Read | 0 = 20 l/h / 5.3 gal/hr; 1 = 40 l/h / 10.6 gal/hr; 2 = 100 l/h / 26.4 gal/hr; 3 = 200 l/h / 52.8 gal/hr; 4 = 300 l/h / 79.3 gal/hr | ||||
| IR | 2510doc 32511 | UO Maintenance status | UINT16 | Read | 0 = No Info; 1 = Warning; 2 = Warning Sys; 3 = Warning Commissioning; 4 = Warning Activation; 5 = Error; 6 = Warning Disinfection | ||||
| IR | 2513doc 32514 | Inlet pressure | Range 0 - 6 bar 0 - 87.0 psi. Metric or imperial per controller setting. | FLOAT32 | ABCD | bar | Read | ||
| IR | 2515doc 32516 | Tank pressure | Range 0 - 6 bar 0 - 87.0 psi. Metric or imperial per controller setting. | FLOAT32 | ABCD | bar | Read | ||
| IR | 2517doc 32518 | Membrane pressure | Range 0 - 20 bar 0 - 290.0 psi. Metric or imperial per controller setting. | FLOAT32 | ABCD | bar | Read | ||
| IR | 2519doc 32520 | Permeate conductivity | Range 0 - 100 µS/cm. | FLOAT32 | ABCD | uS/cm | Read | ||
| IR | 2521doc 32522 | Permeate temperature | Range 0 - 60 °C 32 - 140 °F. Metric or imperial per controller setting. | FLOAT32 | ABCD | °C | Read | ||
| IR | 2523doc 32524 | Permeat flow | Range 0 - 400 l/h 0 - 106 gal/hr. | FLOAT32 | ABCD | l/h | Read | ||
| IR | 2525doc 32526 | Next maintenance | Range 0 - 4000 h. | FLOAT32 | ABCD | h | Read | ||
| IR | 2527doc 32528 | Next Disinfection | Range 0 - 365 [Days]. | UINT16 | d | Read | |||
| IR | 2528doc 32529 | Operating hours | Range 0 - 1200000 h. | FLOAT32 | ABCD | h | Read |
Notes on this map
- Input registers are read with function 04; holding registers with 03 and written with 06 or 16.
- Floats use 'Register Sequence': MSR first (high register first, ABCD) is the factory setting; LSR first (CDAB) is the option. The map assumes the factory setting.
- Factory serial settings: Modbus RTU, address 10, 19200 baud, even parity, 8 data bits, 1 stop bit. Modbus TCP uses port 502 and unit ID 255 (per the TCP technical data).
- Units marked metric/imperial follow the controller's Metric/Imperial setting; the listed unit is the metric one.
- Left out: holding registers 'Minimum / Maximum tank pressure', printed as 43501 / 43503 but with addresses 13500 / 13502, which do not match each other.
Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.
Questions about the Condair RO-E reverse osmosis water treatment (Integrated Controller, Modbus RTU/TCP)
What Modbus registers does the Condair RO-E reverse osmosis water treatment (Integrated Controller, Modbus RTU/TCP) have?
This map lists 20 registers: 20 input registers. 0 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.
Are the Condair RO-E reverse osmosis water treatment (Integrated Controller, Modbus RTU/TCP) Modbus addresses 0-based or 1-based?
The manufacturer's document numbers registers Modicon 3xxxx/4xxxx (drop the prefix, subtract 1). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. Tables print the 5-digit register (32001 = input register, 43001 = holding register) and the 0-based address beside it (2000 / 3000). The address column is what goes on the wire; the manual's own example: register 43004 = address 3003.
What byte order does the Condair RO-E reverse osmosis water treatment (Integrated Controller, Modbus RTU/TCP) use for 32-bit values?
Multi-register values in this map use ABCD (high word first (big-endian)). Set your client to this order for every 32/64-bit value in the table.
What are the minimum Modbus registers to integrate the Condair RO-E reverse osmosis water treatment (Integrated Controller, Modbus RTU/TCP)?
Start with IR 2500 Fault Status (Fault status); IR 2507 RO Status (RO status); IR 2513 Inlet pressure (Inlet pressure); IR 2517 Membrane pressure (Membrane pressure); IR 2519 Permeate conductivity (Permeate conductivity).
How do I enable Modbus control of the Condair RO-E reverse osmosis water treatment (Integrated Controller, Modbus RTU/TCP)?
Network > Modbus Settings on the controller.
Where is the official Condair RO-E reverse osmosis water treatment (Integrated Controller, Modbus RTU/TCP) Modbus documentation?
The source is Modbus addendum manual for DL II, ME II, RS II, RO-E and Vita (Integrated Controller) (2603326-G EN 2607), published free by Condair at https://www.condair.com/m/0/2603326-e-modbus-for-dl-series-addendum.pdf.
More Condair Modbus register maps
- Air handler humidifier (hybrid / spray)
Condair DL II hybrid humidifier (Integrated Controller, Modbus RTU/TCP)
Condair DL with the Integrated Controller, per addendum 2603326-G.
Also known as: Condair DL, Condair DL II, DL - Air handler humidifier (evaporative)
Condair ME II evaporative humidifier / cooler (Integrated Controller, Modbus RTU/TCP)
Condair ME with the Integrated Controller, per addendum 2603326-G.
Also known as: Condair ME, Condair ME II, ME - Air handler humidifier (resistive steam)
Condair RS II resistive steam humidifier (Integrated Controller, Modbus RTU/TCP)
Condair RS with the Integrated Controller (cylinders A and B), per addendum 2603326-G.
Also known as: Condair RS, Condair RS II, RS - Air handler humidifier (high-pressure room system)
Condair Vita high-pressure humidification system (Integrated Controller, Modbus RTU/TCP)
Condair Vita system with the Integrated Controller, per addendum 2603326-G.
Also known as: Condair Vita, Vita System Master
Other pumps register maps
- Heat pump (water-source heat pump controller)
First Co. WSHP series DDC controller CB900 (water-source heat pump, Modbus RTU/TCP)
First Co. / AE-Air water-source heat pumps (WSV and related series) with the factory DDC controller CB900, without hot-gas reheat (IOM8083D02 rev. A).
Also known as: CB900, CB900-1, CB900-2, IOM8083D02, WSV series DDC, First Co. WSHP DDC controller, AE-Air WSHP DDC - Pump (submersible grinder pump pit)
Grundfos SEG AUTOADAPT grinder pumps with CIU 202 / CIU 262 / CIU 502 (Modbus)
Up to four Grundfos SEG AUTOADAPT grinder pumps in one or more pits, connected to a CIU 202 (Modbus RTU), CIU 262 (cellular) or CIU 502 (Modbus TCP); functional profile 96846341 (2019-01).
Also known as: SEG AUTOADAPT, CIU 202, CIU 262, CIU 502, 96846341 - Thermostat / heat pump and unitary controller
Neptronic TUCB / TUHB Series universal wall-mount controller (Modbus RTU)
Neptronic TUCB24C6X2 (temperature) and TUHB24C6X2 (temperature and humidity) universal wall-mount controllers with 6 binary and 2 analog outputs, guide TUXB-Modbus Guide-190515.
Also known as: TUCB24C6X2, TUHB24C6X2, TUCB, TUHB, TUXB - Heat pump (air-to-water) Modbus interface
Toshiba BMS-IFMB0UEW-E Modbus RTU interface for ESTIA air-to-water heat pumps
Toshiba BMS-IFMB0UEW-E MB interface on ESTIA R410A 4 Series and 5 Series (WM type) and R32 1 Series (WM and AIO type) hydro units, user manual EEU-006 issued 31/05/2021.
Also known as: BMS-IFMB0UEW-E, ESTIA Modbus interface, Toshiba MB interface, EEU-006 - Pump system
Wilo SiFresh with CIF module Modbus RTU
Wilo SiFresh pumps fitted with the plug-in CIF module Modbus RTU (module firmware 1.00-99.99); registers needing a newer module are marked.
Also known as: Wilo-SiFresh - Heat pump Modbus interface
Airzone Aidoo Pro Modbus control for air-to-water heat pumps
Airzone Aidoo Pro units configured for Modbus output and connected to an air-to-water heat pump; register table 'Registers for Air-to-Water HP units' of the Aidoo - Modbus integration manual (v. 201).
Also known as: Aidoo Pro, Aidoo Pro Modbus air-to-water, Airzone Aidoo Modbus aerothermal
All pumps Modbus register maps →
Source: Modbus addendum manual for DL II, ME II, RS II, RO-E and Vita (Integrated Controller) · 2603326-G EN 2607. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.