Pump (reverse osmosis water treatment unit) · Modbus register map

Condair RO-E reverse osmosis water treatment (Integrated Controller, Modbus RTU/TCP) Modbus register map

Updated 17 November 2026

Short answer

The Condair RO-E is a reverse osmosis unit that makes demineralised water for humidifiers. Its Integrated Controller is a Modbus RTU slave or Modbus TCP server. This map covers fault and RO status, valve states, unit type and capacity, pressures, permeate conductivity, temperature and flow, and service counters.

This page lists 20 Modbus registers for the Condair RO-E reverse osmosis water treatment (Integrated Controller, Modbus RTU/TCP) — 0 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Condair’s own free documentation (linked below) and checked against it.

Manufacturer
Condair
Model
RO-E reverse osmosis water treatment (Integrated Controller, Modbus RTU/TCP)
Equipment type
Pump (reverse osmosis water treatment unit)
Registers
20 (0 writable)
Transport
Modbus RTU, Modbus TCP
Default unit ID
10
Default serial
19200 baud, 8E1
TCP port
502
Documented addressing
Modicon 3xxxx/4xxxx (drop the prefix, subtract 1)
32-bit word order
ABCD high word first (big-endian)
Also known as
Condair RO-E, RO-E+, Condair RO-E+
Source document
Modbus addendum manual for DL II, ME II, RS II, RO-E and Vita (Integrated Controller) · 2603326-G EN 2607
Download CSV all columns JSON Manufacturer PDF ↗

Integration notes: Condair RO-E reverse osmosis water treatment (Integrated Controller, Modbus RTU/TCP)

Integration in brief

Read input registers 2500-2510 (UInt16 states) and 2513-2529 (floats and the disinfection counter).

Minimum registers to map

Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.

RegisterNameTypeWhyAccess
IR 2500Fault StatusUINT16Fault statusRead
IR 2507RO StatusUINT16RO statusRead
IR 2513Inlet pressureFLOAT32 ABCDInlet pressureRead
IR 2517Membrane pressureFLOAT32 ABCDMembrane pressureRead
IR 2519Permeate conductivityFLOAT32 ABCDPermeate conductivityRead

Enable Modbus control & writes

Network > Modbus Settings on the controller.

Byte order & addressing

Network setup

Watch out for

Condair RO-E reverse osmosis water treatment (Integrated Controller, Modbus RTU/TCP) Modbus registers

Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.

20 of 20 shown
Condair RO-E reverse osmosis water treatment (Integrated Controller, Modbus RTU/TCP) Modbus register map
TableAddressNameDescriptionTypeOrderScaleUnitsAccessValues / bits
IR2003doc 32004Error or Warning Code0 = no error; other codes are listed in the device operation manual.UINT16Read
IR2500doc 32501Fault StatusUINT16Read0 = No Error; 1 = Warning; 2 = Error
IR2501doc 32502Y11 Inlet valveUINT16Read0 = Closed; 1 = Open
IR2502doc 32503Y12 Drain valveUINT16Read0 = Open; 1 = Closed
IR2503doc 32504Y13 Outlet valveUINT16Read0 = Open; 1 = Closed
IR2504doc 32505Y15 Permeate valveUINT16Read0 = Drain; 1 = Tank
IR2505doc 32506Y16 Concentrate valveUINT16Read0 = Closed; 1 = Open
IR2506doc 32507UO TypeUINT16Read0 = RO-E; 1 = RO-E+
IR2507doc 32508RO StatusUINT16Read0 = Initializing; 1 = Diagnostic; 2 = Stopped; 3 = Hold; 4 = Filling; 5 = Standby; 6 = Flushing; 7 = Draining
IR2508doc 32509UO CapacityUINT16Read0 = 20 l/h / 5.3 gal/hr; 1 = 40 l/h / 10.6 gal/hr; 2 = 100 l/h / 26.4 gal/hr; 3 = 200 l/h / 52.8 gal/hr; 4 = 300 l/h / 79.3 gal/hr
IR2510doc 32511UO Maintenance statusUINT16Read0 = No Info; 1 = Warning; 2 = Warning Sys; 3 = Warning Commissioning; 4 = Warning Activation; 5 = Error; 6 = Warning Disinfection
IR2513doc 32514Inlet pressureRange 0 - 6 bar 0 - 87.0 psi. Metric or imperial per controller setting.FLOAT32ABCDbarRead
IR2515doc 32516Tank pressureRange 0 - 6 bar 0 - 87.0 psi. Metric or imperial per controller setting.FLOAT32ABCDbarRead
IR2517doc 32518Membrane pressureRange 0 - 20 bar 0 - 290.0 psi. Metric or imperial per controller setting.FLOAT32ABCDbarRead
IR2519doc 32520Permeate conductivityRange 0 - 100 µS/cm.FLOAT32ABCDuS/cmRead
IR2521doc 32522Permeate temperatureRange 0 - 60 °C 32 - 140 °F. Metric or imperial per controller setting.FLOAT32ABCD°CRead
IR2523doc 32524Permeat flowRange 0 - 400 l/h 0 - 106 gal/hr.FLOAT32ABCDl/hRead
IR2525doc 32526Next maintenanceRange 0 - 4000 h.FLOAT32ABCDhRead
IR2527doc 32528Next DisinfectionRange 0 - 365 [Days].UINT16dRead
IR2528doc 32529Operating hoursRange 0 - 1200000 h.FLOAT32ABCDhRead

Notes on this map

Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.

Questions about the Condair RO-E reverse osmosis water treatment (Integrated Controller, Modbus RTU/TCP)

What Modbus registers does the Condair RO-E reverse osmosis water treatment (Integrated Controller, Modbus RTU/TCP) have?

This map lists 20 registers: 20 input registers. 0 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.

Are the Condair RO-E reverse osmosis water treatment (Integrated Controller, Modbus RTU/TCP) Modbus addresses 0-based or 1-based?

The manufacturer's document numbers registers Modicon 3xxxx/4xxxx (drop the prefix, subtract 1). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. Tables print the 5-digit register (32001 = input register, 43001 = holding register) and the 0-based address beside it (2000 / 3000). The address column is what goes on the wire; the manual's own example: register 43004 = address 3003.

What byte order does the Condair RO-E reverse osmosis water treatment (Integrated Controller, Modbus RTU/TCP) use for 32-bit values?

Multi-register values in this map use ABCD (high word first (big-endian)). Set your client to this order for every 32/64-bit value in the table.

What are the minimum Modbus registers to integrate the Condair RO-E reverse osmosis water treatment (Integrated Controller, Modbus RTU/TCP)?

Start with IR 2500 Fault Status (Fault status); IR 2507 RO Status (RO status); IR 2513 Inlet pressure (Inlet pressure); IR 2517 Membrane pressure (Membrane pressure); IR 2519 Permeate conductivity (Permeate conductivity).

How do I enable Modbus control of the Condair RO-E reverse osmosis water treatment (Integrated Controller, Modbus RTU/TCP)?

Network > Modbus Settings on the controller.

Where is the official Condair RO-E reverse osmosis water treatment (Integrated Controller, Modbus RTU/TCP) Modbus documentation?

The source is Modbus addendum manual for DL II, ME II, RS II, RO-E and Vita (Integrated Controller) (2603326-G EN 2607), published free by Condair at https://www.condair.com/m/0/2603326-e-modbus-for-dl-series-addendum.pdf.

More Condair Modbus register maps

Other pumps register maps

All pumps Modbus register maps →

Source: Modbus addendum manual for DL II, ME II, RS II, RO-E and Vita (Integrated Controller) · 2603326-G EN 2607. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.