Easy Modbus
  1. Home
  2. Modbus register maps
  3. Condair
  4. ME II evaporative humidifier / cooler (Integrated Controller, Modbus RTU/TCP)

Air handler humidifier (evaporative) · Modbus register map

Condair ME II evaporative humidifier / cooler (Integrated Controller, Modbus RTU/TCP) Modbus register map

Updated 17 November 2026

Short answer

The Condair ME is an evaporative humidifier and adiabatic cooler for air handling units. Its Integrated Controller is a Modbus RTU slave on RS-485 or a Modbus TCP server. This map covers mode and status, pump faults and speeds, tank and valve states, humidity, air and water temperatures, stage capacities, service counters and the writable humidity and temperature control registers.

This page lists 60 Modbus registers for the Condair ME II evaporative humidifier / cooler (Integrated Controller, Modbus RTU/TCP) — 11 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Condair’s own free documentation (linked below) and checked against it.

Manufacturer
Condair
Model
ME II evaporative humidifier / cooler (Integrated Controller, Modbus RTU/TCP)
Equipment type
Air handler humidifier (evaporative)
Registers
60 (11 writable)
Transport
Modbus RTU, Modbus TCP
Default unit ID
10
Default serial
19200 baud, 8E1
TCP port
502
Documented addressing
Modicon 3xxxx/4xxxx (drop the prefix, subtract 1)
32-bit word order
ABCD high word first (big-endian)
Also known as
Condair ME, Condair ME II, ME
Source document
Modbus addendum manual for DL II, ME II, RS II, RO-E and Vita (Integrated Controller) · 2603326-G EN 2607
Download CSV all columns JSON Manufacturer PDF ↗

Integration notes: Condair ME II evaporative humidifier / cooler (Integrated Controller, Modbus RTU/TCP)

Integration in brief

Read input registers 2000-2031 (UInt16) and 2037-2070 (floats). Write the demand or humidity value to holding 3003 and, in cooling mode, the temperature to 3014 (float).

Minimum registers to map

Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.

RegisterNameTypeWhyAccess
IR 2000System ModeUINT16System modeRead
IR 2001Device StatusUINT16Device statusRead
IR 2002Maintenance and Error StatusUINT16Maintenance and error statusRead
IR 2005Number of Running StagesUINT16Running stagesRead
IR 2037Actual Humidity or DemandFLOAT32 ABCDActual humidity or demandRead
HR 3003Actual Humidity or Demand via ModbusUINT16Demand/humidity via ModbusRead/write

Enable Modbus control & writes

Controls > Signal Settings: set Source = Modbus and choose the control mode.

Communication loss & watchdog

When the demand or humidity signal comes from Modbus, it must be rewritten within 'Signal Timeout' (1-300 s, default 300 s); otherwise warning W35 is raised and the unit stops humidifying.

Byte order & addressing

Network setup

Watch out for

Condair ME II evaporative humidifier / cooler (Integrated Controller, Modbus RTU/TCP) Modbus registers

Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.

60 of 60 shown
Condair ME II evaporative humidifier / cooler (Integrated Controller, Modbus RTU/TCP) Modbus register map
TableAddressNameDescriptionTypeOrderScaleUnitsAccessValues / bits
IR2000doc 32001System ModeUINT16Read0 = Humidifying; 1 = Cooling
IR2001doc 32002Device StatusUINT16Read0 = Initializing; 1 = Diagnostic; 2 = Stopped; 3 = Humidifying; 4 = Cooling; 5 = Holding; 6 = Draining; 7 = Refreshing; 8 = Filling; 9 = Standby; 10 = Diluting; 11 = Assisted Draining; 12 = Bleeding; 13 = Softstart; 14 = Switched Off; 15 = Remote Off; 16 = Purging; 17 = Drain Check
IR2002doc 32003Maintenance and Error StatusUINT16Read0 = No Info; 1 = Warning; 2 = Maintenance; 3 = WET Tank empty; 4 = Replace PureFlo Cartridge; 5 = Replace UV Lamp; 6 = Matrix Wash Over; 7 = Out of Comissioning; 8 = Activation Code; 9 = Error; 10 = Disinfection Tank empty
IR2003doc 32004Error or Warning Code0 = no error; other codes are listed in the device operation manual.UINT16Read
IR2004doc 32005Safety LoopRange 0 = Open 1 = Closed (=ok).UINT16Read
IR2005doc 32006Number of Running StagesRange 0 – 7 stages.UINT16Read
IR2006doc 32007Fault Pump 1UINT16Read0 = Fault; 1 = Ok
IR2007doc 32008Fault Pump 2UINT16Read0 = Fault; 1 = Ok
IR2008doc 32009Fault Pump 3UINT16Read0 = Fault; 1 = Ok
IR2009doc 32010Fault Pump 4UINT16Read0 = Fault; 1 = Ok
IR2010doc 32011Fault Pump 5UINT16Read0 = Fault; 1 = Ok
IR2011doc 32012Fault Pump 6UINT16Read0 = Fault; 1 = Ok
IR2012doc 32013Fault Pump 7UINT16Read0 = Fault; 1 = Ok
IR2013doc 32014Fault Water InletUINT16Read0 = Fault; 1 = Ok
IR2014doc 32015Fault Water TemperatureUINT16Read0 = Fault; 1 = Ok
IR2015doc 32016Fault Water OutletUINT16Read0 = Fault; 1 = Ok
IR2016doc 32017Fault Level SensorUINT16Read0 = Fault; 1 = Ok
IR2017doc 32018Fault Water ConductivityUINT16Read0 = Fault; 1 = Ok
IR2018doc 32019Speed Pump 1Range 0 - 100 %.UINT16%Read
IR2019doc 32020Speed Pump 2Range 0 - 100 %.UINT16%Read
IR2020doc 32021Speed Pump 3Range 0 - 100 %.UINT16%Read
IR2021doc 32022Speed Pump 4Range 0 - 100 %.UINT16%Read
IR2022doc 32023Speed Pump 5Range 0 - 100 %.UINT16%Read
IR2023doc 32024Speed Pump 6Range 0 - 100 %.UINT16%Read
IR2024doc 32025Speed Pump 7Range 0 - 100 %.UINT16%Read
IR2025doc 32026Water Level TankRange 0 - 7.UINT16Read
IR2026doc 32027WET Tank LevelUINT16Read0 = Empty; 1 = Ok
IR2027doc 32028Disinfection Tank LevelUINT16Read0 = Empty; 1 = Ok
IR2028doc 32029Leakage SensorUINT16Read0 = Leak; 1 = Ok
IR2029doc 32030Inlet ValveUINT16Read0 = Closed; 1 = Open
IR2030doc 32031Drain ValveUINT16Read0 = Open; 1 = Closed
IR2031doc 32032Drain PumpUINT16Read0 = Off; 1 = On
IR2037doc 32038Actual Humidity or DemandRange 0 - 100 %.FLOAT32ABCD%Read
IR2039doc 32040Actual Air TemperatureRange °C or °F. Metric or imperial per controller setting.FLOAT32ABCD°CRead
IR2041doc 32042Incoming Air TemperatureRange °C or °F. Metric or imperial per controller setting.FLOAT32ABCD°CRead
IR2043doc 32044Actual Water TemperatureRange °C or °F. Metric or imperial per controller setting.FLOAT32ABCD°CRead
IR2045doc 32046Water ConductivityRange 0 - x uS/cm.FLOAT32ABCDuS/cmRead
IR2047doc 32048UV CurrentRange 0 - 4.0 A.FLOAT32ABCDARead
IR2049doc 32050Water Capacity Stage 1Range 1.0 - 360.0 kg/h 2.2 - 793.7 lb/hr. Metric or imperial per controller setting.FLOAT32ABCDkg/hRead
IR2051doc 32052Water Capacity Stage 2Range 1.0 - 360.0 kg/h 2.2 - 793.7 lb/hr. Metric or imperial per controller setting.FLOAT32ABCDkg/hRead
IR2053doc 32054Water Capacity Stage 3Range 1.0 - 360.0 kg/h 2.2 - 793.7 lb/hr. Metric or imperial per controller setting.FLOAT32ABCDkg/hRead
IR2055doc 32056Water Capacity Stage 4Range 1.0 - 360.0 kg/h 2.2 - 793.7 lb/hr. Metric or imperial per controller setting.FLOAT32ABCDkg/hRead
IR2057doc 32058Water Capacity Stage 5Range 1.0 - 360.0 kg/h 2.2 - 793.7 lb/hr. Metric or imperial per controller setting.FLOAT32ABCDkg/hRead
IR2059doc 32060Water Capacity Stage 6Range 1.0 - 360.0 kg/h 2.2 - 793.7 lb/hr. Metric or imperial per controller setting.FLOAT32ABCDkg/hRead
IR2061doc 32062Water Capacity Stage 7Range 1.0 - 360.0 kg/h 2.2 - 793.7 lb/hr. Metric or imperial per controller setting.FLOAT32ABCDkg/hRead
IR2063doc 32064Operating HoursRange 0 - 1200000 h.FLOAT32ABCDhRead
IR2065doc 32066Next MaintenanceRange 0 - 10000 h.FLOAT32ABCDhRead
IR2067doc 32068Next UV Lamp ExchangeRange 0 - 450 d.FLOAT32ABCDdRead
IR2069doc 32070Next PureFlo ExchangeRange 0 - 365 d.FLOAT32ABCDdRead
HR3000doc 43001Setpoint Humidity ControlRange 0 - 95 %.UINT16%Read/write
HR3001doc 43002P-Band Humidity ControlRange 6 - 65 %.UINT16%Read/write
HR3002doc 43003I-Time Humidity ControlRange 1 - 60 min.UINT16minRead/write
HR3003doc 43004Actual Humidity or Demand via ModbusRange 0 - 100 %.UINT16%Read/write
HR3004doc 43005I-Time Temperature ControlRange 1 - 60 min.UINT16minRead/write
HR3010doc 43011Setpoint Temperature ControlRange 0 - 40 °C 32 - 104 °F. Metric or imperial per controller setting.FLOAT32ABCD°CRead/write
HR3012doc 43013P-Band Temperature ControlRange 1 - 50 °C 1.8 - 89.9 °F. Metric or imperial per controller setting.FLOAT32ABCD°CRead/write
HR3014doc 43015Actual Temperature via ModbusRange -25 - 100 °C -12.9 - 211.9 °F. Metric or imperial per controller setting.FLOAT32ABCD°CRead/write
HR5001doc 45002Remote DrainingRead 100 = off or 0-99 = progress %; write 1 = start, 0 = stop.UINT16%Read/write
HR5002doc 45003Remote Matrix Wash OverRead 100 = off or 0-99 = progress %; write 1 = start, 0 = stop.UINT16%Read/write
HR5003doc 45004Remote Error/Warning ResetUINT16Read/write0 = Off; 1 = On

Notes on this map

Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.

Questions about the Condair ME II evaporative humidifier / cooler (Integrated Controller, Modbus RTU/TCP)

What Modbus registers does the Condair ME II evaporative humidifier / cooler (Integrated Controller, Modbus RTU/TCP) have?

This map lists 60 registers: 49 input registers, 11 holding registers. 11 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.

Are the Condair ME II evaporative humidifier / cooler (Integrated Controller, Modbus RTU/TCP) Modbus addresses 0-based or 1-based?

The manufacturer's document numbers registers Modicon 3xxxx/4xxxx (drop the prefix, subtract 1). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. Tables print the 5-digit register (32001 = input register, 43001 = holding register) and the 0-based address beside it (2000 / 3000). The address column is what goes on the wire; the manual's own example: register 43004 = address 3003.

What byte order does the Condair ME II evaporative humidifier / cooler (Integrated Controller, Modbus RTU/TCP) use for 32-bit values?

Multi-register values in this map use ABCD (high word first (big-endian)). Set your client to this order for every 32/64-bit value in the table.

What are the minimum Modbus registers to integrate the Condair ME II evaporative humidifier / cooler (Integrated Controller, Modbus RTU/TCP)?

Start with IR 2000 System Mode (System mode); IR 2001 Device Status (Device status); IR 2002 Maintenance and Error Status (Maintenance and error status); IR 2005 Number of Running Stages (Running stages); IR 2037 Actual Humidity or Demand (Actual humidity or demand); HR 3003 Actual Humidity or Demand via Modbus (Demand/humidity via Modbus).

How do I enable Modbus control of the Condair ME II evaporative humidifier / cooler (Integrated Controller, Modbus RTU/TCP)?

Controls > Signal Settings: set Source = Modbus and choose the control mode.

What happens when the Condair ME II evaporative humidifier / cooler (Integrated Controller, Modbus RTU/TCP) loses Modbus communication?

When the demand or humidity signal comes from Modbus, it must be rewritten within 'Signal Timeout' (1-300 s, default 300 s); otherwise warning W35 is raised and the unit stops humidifying.

Where is the official Condair ME II evaporative humidifier / cooler (Integrated Controller, Modbus RTU/TCP) Modbus documentation?

The source is Modbus addendum manual for DL II, ME II, RS II, RO-E and Vita (Integrated Controller) (2603326-G EN 2607), published free by Condair at https://www.condair.com/m/0/2603326-e-modbus-for-dl-series-addendum.pdf.

More Condair Modbus register maps

Other hvac equipment register maps

All hvac equipment Modbus register maps →

Source: Modbus addendum manual for DL II, ME II, RS II, RO-E and Vita (Integrated Controller) · 2603326-G EN 2607. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.