- ME II evaporative humidifier / cooler (Integrated Controller, Modbus RTU/TCP)
Air handler humidifier (evaporative) · Modbus register map
Condair ME II evaporative humidifier / cooler (Integrated Controller, Modbus RTU/TCP) Modbus register map
Updated 17 November 2026
The Condair ME is an evaporative humidifier and adiabatic cooler for air handling units. Its Integrated Controller is a Modbus RTU slave on RS-485 or a Modbus TCP server. This map covers mode and status, pump faults and speeds, tank and valve states, humidity, air and water temperatures, stage capacities, service counters and the writable humidity and temperature control registers.
This page lists 60 Modbus registers for the Condair ME II evaporative humidifier / cooler (Integrated Controller, Modbus RTU/TCP) — 11 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Condair’s own free documentation (linked below) and checked against it.
- Manufacturer
- Condair
- Model
- ME II evaporative humidifier / cooler (Integrated Controller, Modbus RTU/TCP)
- Equipment type
- Air handler humidifier (evaporative)
- Registers
- 60 (11 writable)
- Transport
- Modbus RTU, Modbus TCP
- Default unit ID
- 10
- Default serial
- 19200 baud, 8E1
- TCP port
- 502
- Documented addressing
- Modicon 3xxxx/4xxxx (drop the prefix, subtract 1)
- 32-bit word order
- ABCD high word first (big-endian)
- Also known as
- Condair ME, Condair ME II, ME
Integration notes: Condair ME II evaporative humidifier / cooler (Integrated Controller, Modbus RTU/TCP)
Read input registers 2000-2031 (UInt16) and 2037-2070 (floats). Write the demand or humidity value to holding 3003 and, in cooling mode, the temperature to 3014 (float).
Minimum registers to map
Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.
| Register | Name | Type | Why | Access |
|---|---|---|---|---|
| IR 2000 | System Mode | UINT16 | System mode | Read |
| IR 2001 | Device Status | UINT16 | Device status | Read |
| IR 2002 | Maintenance and Error Status | UINT16 | Maintenance and error status | Read |
| IR 2005 | Number of Running Stages | UINT16 | Running stages | Read |
| IR 2037 | Actual Humidity or Demand | FLOAT32 ABCD | Actual humidity or demand | Read |
| HR 3003 | Actual Humidity or Demand via Modbus | UINT16 | Demand/humidity via Modbus | Read/write |
Enable Modbus control & writes
Controls > Signal Settings: set Source = Modbus and choose the control mode.
Communication loss & watchdog
When the demand or humidity signal comes from Modbus, it must be rewritten within 'Signal Timeout' (1-300 s, default 300 s); otherwise warning W35 is raised and the unit stops humidifying.
Byte order & addressing
- The address column is the wire address; 32001 is address 2000.
- Floats are two registers, MSR first by default.
Network setup
- Menu > password 8808 > Network > Modbus Settings: set protocol (Modbus/RTU or Modbus/TCP), address, parity, baud rate and register sequence; the controller restarts after a protocol change.
- For Modbus TCP set the IP parameters under Network > IP Settings (factory setting DHCP).
Watch out for
- Temperature setpoint registers (3010-3015) are floats; the humidity ones are UInt16.
Condair ME II evaporative humidifier / cooler (Integrated Controller, Modbus RTU/TCP) Modbus registers
Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.
| Table | Address | Name | Description | Type | Order | Scale | Units | Access | Values / bits |
|---|---|---|---|---|---|---|---|---|---|
| IR | 2000doc 32001 | System Mode | UINT16 | Read | 0 = Humidifying; 1 = Cooling | ||||
| IR | 2001doc 32002 | Device Status | UINT16 | Read | 0 = Initializing; 1 = Diagnostic; 2 = Stopped; 3 = Humidifying; 4 = Cooling; 5 = Holding; 6 = Draining; 7 = Refreshing; 8 = Filling; 9 = Standby; 10 = Diluting; 11 = Assisted Draining; 12 = Bleeding; 13 = Softstart; 14 = Switched Off; 15 = Remote Off; 16 = Purging; 17 = Drain Check | ||||
| IR | 2002doc 32003 | Maintenance and Error Status | UINT16 | Read | 0 = No Info; 1 = Warning; 2 = Maintenance; 3 = WET Tank empty; 4 = Replace PureFlo Cartridge; 5 = Replace UV Lamp; 6 = Matrix Wash Over; 7 = Out of Comissioning; 8 = Activation Code; 9 = Error; 10 = Disinfection Tank empty | ||||
| IR | 2003doc 32004 | Error or Warning Code | 0 = no error; other codes are listed in the device operation manual. | UINT16 | Read | ||||
| IR | 2004doc 32005 | Safety Loop | Range 0 = Open 1 = Closed (=ok). | UINT16 | Read | ||||
| IR | 2005doc 32006 | Number of Running Stages | Range 0 – 7 stages. | UINT16 | Read | ||||
| IR | 2006doc 32007 | Fault Pump 1 | UINT16 | Read | 0 = Fault; 1 = Ok | ||||
| IR | 2007doc 32008 | Fault Pump 2 | UINT16 | Read | 0 = Fault; 1 = Ok | ||||
| IR | 2008doc 32009 | Fault Pump 3 | UINT16 | Read | 0 = Fault; 1 = Ok | ||||
| IR | 2009doc 32010 | Fault Pump 4 | UINT16 | Read | 0 = Fault; 1 = Ok | ||||
| IR | 2010doc 32011 | Fault Pump 5 | UINT16 | Read | 0 = Fault; 1 = Ok | ||||
| IR | 2011doc 32012 | Fault Pump 6 | UINT16 | Read | 0 = Fault; 1 = Ok | ||||
| IR | 2012doc 32013 | Fault Pump 7 | UINT16 | Read | 0 = Fault; 1 = Ok | ||||
| IR | 2013doc 32014 | Fault Water Inlet | UINT16 | Read | 0 = Fault; 1 = Ok | ||||
| IR | 2014doc 32015 | Fault Water Temperature | UINT16 | Read | 0 = Fault; 1 = Ok | ||||
| IR | 2015doc 32016 | Fault Water Outlet | UINT16 | Read | 0 = Fault; 1 = Ok | ||||
| IR | 2016doc 32017 | Fault Level Sensor | UINT16 | Read | 0 = Fault; 1 = Ok | ||||
| IR | 2017doc 32018 | Fault Water Conductivity | UINT16 | Read | 0 = Fault; 1 = Ok | ||||
| IR | 2018doc 32019 | Speed Pump 1 | Range 0 - 100 %. | UINT16 | % | Read | |||
| IR | 2019doc 32020 | Speed Pump 2 | Range 0 - 100 %. | UINT16 | % | Read | |||
| IR | 2020doc 32021 | Speed Pump 3 | Range 0 - 100 %. | UINT16 | % | Read | |||
| IR | 2021doc 32022 | Speed Pump 4 | Range 0 - 100 %. | UINT16 | % | Read | |||
| IR | 2022doc 32023 | Speed Pump 5 | Range 0 - 100 %. | UINT16 | % | Read | |||
| IR | 2023doc 32024 | Speed Pump 6 | Range 0 - 100 %. | UINT16 | % | Read | |||
| IR | 2024doc 32025 | Speed Pump 7 | Range 0 - 100 %. | UINT16 | % | Read | |||
| IR | 2025doc 32026 | Water Level Tank | Range 0 - 7. | UINT16 | Read | ||||
| IR | 2026doc 32027 | WET Tank Level | UINT16 | Read | 0 = Empty; 1 = Ok | ||||
| IR | 2027doc 32028 | Disinfection Tank Level | UINT16 | Read | 0 = Empty; 1 = Ok | ||||
| IR | 2028doc 32029 | Leakage Sensor | UINT16 | Read | 0 = Leak; 1 = Ok | ||||
| IR | 2029doc 32030 | Inlet Valve | UINT16 | Read | 0 = Closed; 1 = Open | ||||
| IR | 2030doc 32031 | Drain Valve | UINT16 | Read | 0 = Open; 1 = Closed | ||||
| IR | 2031doc 32032 | Drain Pump | UINT16 | Read | 0 = Off; 1 = On | ||||
| IR | 2037doc 32038 | Actual Humidity or Demand | Range 0 - 100 %. | FLOAT32 | ABCD | % | Read | ||
| IR | 2039doc 32040 | Actual Air Temperature | Range °C or °F. Metric or imperial per controller setting. | FLOAT32 | ABCD | °C | Read | ||
| IR | 2041doc 32042 | Incoming Air Temperature | Range °C or °F. Metric or imperial per controller setting. | FLOAT32 | ABCD | °C | Read | ||
| IR | 2043doc 32044 | Actual Water Temperature | Range °C or °F. Metric or imperial per controller setting. | FLOAT32 | ABCD | °C | Read | ||
| IR | 2045doc 32046 | Water Conductivity | Range 0 - x uS/cm. | FLOAT32 | ABCD | uS/cm | Read | ||
| IR | 2047doc 32048 | UV Current | Range 0 - 4.0 A. | FLOAT32 | ABCD | A | Read | ||
| IR | 2049doc 32050 | Water Capacity Stage 1 | Range 1.0 - 360.0 kg/h 2.2 - 793.7 lb/hr. Metric or imperial per controller setting. | FLOAT32 | ABCD | kg/h | Read | ||
| IR | 2051doc 32052 | Water Capacity Stage 2 | Range 1.0 - 360.0 kg/h 2.2 - 793.7 lb/hr. Metric or imperial per controller setting. | FLOAT32 | ABCD | kg/h | Read | ||
| IR | 2053doc 32054 | Water Capacity Stage 3 | Range 1.0 - 360.0 kg/h 2.2 - 793.7 lb/hr. Metric or imperial per controller setting. | FLOAT32 | ABCD | kg/h | Read | ||
| IR | 2055doc 32056 | Water Capacity Stage 4 | Range 1.0 - 360.0 kg/h 2.2 - 793.7 lb/hr. Metric or imperial per controller setting. | FLOAT32 | ABCD | kg/h | Read | ||
| IR | 2057doc 32058 | Water Capacity Stage 5 | Range 1.0 - 360.0 kg/h 2.2 - 793.7 lb/hr. Metric or imperial per controller setting. | FLOAT32 | ABCD | kg/h | Read | ||
| IR | 2059doc 32060 | Water Capacity Stage 6 | Range 1.0 - 360.0 kg/h 2.2 - 793.7 lb/hr. Metric or imperial per controller setting. | FLOAT32 | ABCD | kg/h | Read | ||
| IR | 2061doc 32062 | Water Capacity Stage 7 | Range 1.0 - 360.0 kg/h 2.2 - 793.7 lb/hr. Metric or imperial per controller setting. | FLOAT32 | ABCD | kg/h | Read | ||
| IR | 2063doc 32064 | Operating Hours | Range 0 - 1200000 h. | FLOAT32 | ABCD | h | Read | ||
| IR | 2065doc 32066 | Next Maintenance | Range 0 - 10000 h. | FLOAT32 | ABCD | h | Read | ||
| IR | 2067doc 32068 | Next UV Lamp Exchange | Range 0 - 450 d. | FLOAT32 | ABCD | d | Read | ||
| IR | 2069doc 32070 | Next PureFlo Exchange | Range 0 - 365 d. | FLOAT32 | ABCD | d | Read | ||
| HR | 3000doc 43001 | Setpoint Humidity Control | Range 0 - 95 %. | UINT16 | % | Read/write | |||
| HR | 3001doc 43002 | P-Band Humidity Control | Range 6 - 65 %. | UINT16 | % | Read/write | |||
| HR | 3002doc 43003 | I-Time Humidity Control | Range 1 - 60 min. | UINT16 | min | Read/write | |||
| HR | 3003doc 43004 | Actual Humidity or Demand via Modbus | Range 0 - 100 %. | UINT16 | % | Read/write | |||
| HR | 3004doc 43005 | I-Time Temperature Control | Range 1 - 60 min. | UINT16 | min | Read/write | |||
| HR | 3010doc 43011 | Setpoint Temperature Control | Range 0 - 40 °C 32 - 104 °F. Metric or imperial per controller setting. | FLOAT32 | ABCD | °C | Read/write | ||
| HR | 3012doc 43013 | P-Band Temperature Control | Range 1 - 50 °C 1.8 - 89.9 °F. Metric or imperial per controller setting. | FLOAT32 | ABCD | °C | Read/write | ||
| HR | 3014doc 43015 | Actual Temperature via Modbus | Range -25 - 100 °C -12.9 - 211.9 °F. Metric or imperial per controller setting. | FLOAT32 | ABCD | °C | Read/write | ||
| HR | 5001doc 45002 | Remote Draining | Read 100 = off or 0-99 = progress %; write 1 = start, 0 = stop. | UINT16 | % | Read/write | |||
| HR | 5002doc 45003 | Remote Matrix Wash Over | Read 100 = off or 0-99 = progress %; write 1 = start, 0 = stop. | UINT16 | % | Read/write | |||
| HR | 5003doc 45004 | Remote Error/Warning Reset | UINT16 | Read/write | 0 = Off; 1 = On |
Notes on this map
- Input registers are read with function 04; holding registers with 03 and written with 06 or 16.
- Floats use 'Register Sequence': MSR first (high register first, ABCD) is the factory setting; LSR first (CDAB) is the option. The map assumes the factory setting.
- Factory serial settings: Modbus RTU, address 10, 19200 baud, even parity, 8 data bits, 1 stop bit. Modbus TCP uses port 502 and unit ID 255 (per the TCP technical data).
- Units marked metric/imperial follow the controller's Metric/Imperial setting; the listed unit is the metric one.
Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.
Questions about the Condair ME II evaporative humidifier / cooler (Integrated Controller, Modbus RTU/TCP)
What Modbus registers does the Condair ME II evaporative humidifier / cooler (Integrated Controller, Modbus RTU/TCP) have?
This map lists 60 registers: 49 input registers, 11 holding registers. 11 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.
Are the Condair ME II evaporative humidifier / cooler (Integrated Controller, Modbus RTU/TCP) Modbus addresses 0-based or 1-based?
The manufacturer's document numbers registers Modicon 3xxxx/4xxxx (drop the prefix, subtract 1). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. Tables print the 5-digit register (32001 = input register, 43001 = holding register) and the 0-based address beside it (2000 / 3000). The address column is what goes on the wire; the manual's own example: register 43004 = address 3003.
What byte order does the Condair ME II evaporative humidifier / cooler (Integrated Controller, Modbus RTU/TCP) use for 32-bit values?
Multi-register values in this map use ABCD (high word first (big-endian)). Set your client to this order for every 32/64-bit value in the table.
What are the minimum Modbus registers to integrate the Condair ME II evaporative humidifier / cooler (Integrated Controller, Modbus RTU/TCP)?
Start with IR 2000 System Mode (System mode); IR 2001 Device Status (Device status); IR 2002 Maintenance and Error Status (Maintenance and error status); IR 2005 Number of Running Stages (Running stages); IR 2037 Actual Humidity or Demand (Actual humidity or demand); HR 3003 Actual Humidity or Demand via Modbus (Demand/humidity via Modbus).
How do I enable Modbus control of the Condair ME II evaporative humidifier / cooler (Integrated Controller, Modbus RTU/TCP)?
Controls > Signal Settings: set Source = Modbus and choose the control mode.
What happens when the Condair ME II evaporative humidifier / cooler (Integrated Controller, Modbus RTU/TCP) loses Modbus communication?
When the demand or humidity signal comes from Modbus, it must be rewritten within 'Signal Timeout' (1-300 s, default 300 s); otherwise warning W35 is raised and the unit stops humidifying.
Where is the official Condair ME II evaporative humidifier / cooler (Integrated Controller, Modbus RTU/TCP) Modbus documentation?
The source is Modbus addendum manual for DL II, ME II, RS II, RO-E and Vita (Integrated Controller) (2603326-G EN 2607), published free by Condair at https://www.condair.com/m/0/2603326-e-modbus-for-dl-series-addendum.pdf.
More Condair Modbus register maps
- Air handler humidifier (hybrid / spray)
Condair DL II hybrid humidifier (Integrated Controller, Modbus RTU/TCP)
Condair DL with the Integrated Controller, per addendum 2603326-G.
Also known as: Condair DL, Condair DL II, DL - Pump (reverse osmosis water treatment unit)
Condair RO-E reverse osmosis water treatment (Integrated Controller, Modbus RTU/TCP)
Condair RO-E / RO-E+ with the Integrated Controller, per addendum 2603326-G.
Also known as: Condair RO-E, RO-E+, Condair RO-E+ - Air handler humidifier (resistive steam)
Condair RS II resistive steam humidifier (Integrated Controller, Modbus RTU/TCP)
Condair RS with the Integrated Controller (cylinders A and B), per addendum 2603326-G.
Also known as: Condair RS, Condair RS II, RS - Air handler humidifier (high-pressure room system)
Condair Vita high-pressure humidification system (Integrated Controller, Modbus RTU/TCP)
Condair Vita system with the Integrated Controller, per addendum 2603326-G.
Also known as: Condair Vita, Vita System Master
Other hvac equipment register maps
- Air handler (demand-controlled ventilation unit)
Duco DucoBox ventilation units / IQ unit (Modbus RTU, master node)
DucoBox Silent Connect, Focus, Energy (all variants) and ECO with the Communication Print option, and the Duco IQ unit (Modbus standard), per information sheet L8000009-B.
Also known as: DucoBox Silent Connect, DucoBox Focus, DucoBox Energy, DucoBox Energy Premium, DucoBox ECO, Duco IQ unit, L8000009 - Thermostat
Johnson Controls PENN TC3222 refrigeration temperature controller (Modbus RTU)
PENN TC3222 electronic refrigeration controller with built-in Modbus RTU, per the TC3 Modbus Protocol Reference Guide LIT-12013523 (2020-04-28).
Also known as: TC3222, TC3, PENN TC3, LIT-12013523 - Air handler (heat recovery ventilation unit)
Mitsubishi Electric MelcoBEMS MINI (A1M+ / A1M) gateway for Lossnay heat recovery ventilators (LGH and VL series)
Procon MelcoBEMS MINI A1M+ (manual v1.0.3, firmware 4.1.1) on Lossnay LGH-15..200RVX-E1, LGH-150..250RVXT-E1 and VL-250..500CZPVU-R/L-E; the older A1M (manual v1.1.11) prints the identical Lossnay table.
Also known as: A1M+ Lossnay, MelcoBEMS MINI Lossnay, Procon A1M+, Procon A1M, A1M, Lossnay LGH-RVX Modbus, LGH-15RVX-E1, LGH-200RVX-E1, LGH-150RVXT-E1, LGH-250RVXT-E1, VL-250CZPVU-R-E, VL-500CZPVU-L-E, Lossnay VL Vertical - Air handler humidifier (electric steam)
Neptronic SKE4 electric steam humidifier (Modbus communication module)
Neptronic SKE4 series electric steam humidifiers with the Modbus communication module, guide SKE4-Modbus Guide-240531 (V2.07).
Also known as: SKE4-E, SKE4-N, SKE4 Steam Humidifier, Neptronic SKE4 Modbus - Thermostat / temperature and process PID controller
Red Lion PAX2C temperature/process PID controller (Modbus RTU/ASCII)
PAX2C version 2.0 register table (LP0905F, 2017-02-27); the FlexCard (PX2FCA0/PX2FCA1) blocks of the same table are not included.
Also known as: PAX2CHZVR, PAX2C00000, PX2FCA0, PX2FCA1 - Air handler fan motor control
Swegon SILVER C fan motor control (RX/PX/CX/SD, generation E/F)
The EC/FC fan motor controllers inside Swegon SILVER C air handling units, generation E/F, document SILVERCModbus.210809.
Also known as: SILVER C RX, SILVER C PX, SILVER C CX, SILVER C SD, SILVER C generation E, SILVER C generation F
All hvac equipment Modbus register maps →
Source: Modbus addendum manual for DL II, ME II, RS II, RO-E and Vita (Integrated Controller) · 2603326-G EN 2607. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.