Condair Modbus register maps

Updated 17 November 2026

5 Condair models, 338 registers in all, each re-typed from Condair’s own free documentation and checked against it.

5 of 5 shown

Condair: default communication settings

Factory defaults as the manufacturer documents them. Change one setting at a time on site and write down what you changed. Word order applies to 32-bit values; the addressing column says how the manufacturer prints register numbers (every map on this site also gives the 0-based wire address).

ModelTransportUnit IDSerialWord orderDocumented addressingRegisters
DL II hybrid humidifier (Integrated Controller, Modbus RTU/TCP)RTU/TCP1019200 baud, 8E1ABCDModicon40
ME II evaporative humidifier / cooler (Integrated Controller, Modbus RTU/TCP)RTU/TCP1019200 baud, 8E1ABCDModicon60
RO-E reverse osmosis water treatment (Integrated Controller, Modbus RTU/TCP)RTU/TCP1019200 baud, 8E1ABCDModicon20
RS II resistive steam humidifier (Integrated Controller, Modbus RTU/TCP)RTU/TCP1019200 baud, 8E1ABCDModicon59
Vita high-pressure humidification system (Integrated Controller, Modbus RTU/TCP)RTU/TCP1019200 baud, 8E1ABCDModicon159