- Vita high-pressure humidification system (Integrated Controller, Modbus RTU/TCP)
Air handler humidifier (high-pressure room system) · Modbus register map
Condair Vita high-pressure humidification system (Integrated Controller, Modbus RTU/TCP) Modbus register map
Updated 17 November 2026
The Condair Vita is a high-pressure nebulising humidification system serving up to 50 areas. Its Integrated Controller is a Modbus RTU slave or Modbus TCP server. This map covers system, RO, deionisation and HP-line states, error flag, code and category, per-area state and humidity, and the per-area humidity setpoints.
This page lists 159 Modbus registers for the Condair Vita high-pressure humidification system (Integrated Controller, Modbus RTU/TCP) — 50 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Condair’s own free documentation (linked below) and checked against it.
- Manufacturer
- Condair
- Model
- Vita high-pressure humidification system (Integrated Controller, Modbus RTU/TCP)
- Equipment type
- Air handler humidifier (high-pressure room system)
- Registers
- 159 (50 writable)
- Transport
- Modbus RTU, Modbus TCP
- Default unit ID
- 10
- Default serial
- 19200 baud, 8E1
- TCP port
- 502
- Documented addressing
- Modicon 3xxxx/4xxxx (drop the prefix, subtract 1)
- 32-bit word order
- ABCD high word first (big-endian)
- Also known as
- Condair Vita, Vita System Master
Integration notes: Condair Vita high-pressure humidification system (Integrated Controller, Modbus RTU/TCP)
Read input registers 2000-2009 for system and error state and 2500-2549 for area states; write area setpoints to holding 3500-3549.
Minimum registers to map
Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.
| Register | Name | Type | Why | Access |
|---|---|---|---|---|
| IR 2000 | Number of Areas | UINT16 | Number of areas | Read |
| IR 2007 | Error Flag | UINT16 | Error flag | Read |
| IR 2006 | Error Category | UINT16 | Error category | Read |
| IR 2900 | Reverse Osmosis State | UINT16 | RO state | Read |
| IR 2500 | Area 1 state | UINT16 | Area 1 state | Read |
| HR 3500 | Area 1 setpoint | UINT16 | Area 1 setpoint | Read/write |
Enable Modbus control & writes
Network > Modbus Settings on the controller.
Byte order & addressing
- The address column is the wire address; 32001 is address 2000.
- Floats are two registers, MSR first by default.
Network setup
- Menu > password 8808 > Network > Modbus Settings: set protocol (Modbus/RTU or Modbus/TCP), address, parity, baud rate and register sequence; the controller restarts after a protocol change.
- For Modbus TCP set the IP parameters under Network > IP Settings (factory setting DHCP).
Watch out for
- Read the error category (2006) together with the error flag; the manual warns that ignoring the category causes needless warning messages.
- Wrong setpoints or sensor values can cause water damage; the operator must monitor them.
Condair Vita high-pressure humidification system (Integrated Controller, Modbus RTU/TCP) Modbus registers
Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.
| Table | Address | Name | Description | Type | Order | Scale | Units | Access | Values / bits |
|---|---|---|---|---|---|---|---|---|---|
| IR | 2000doc 32001 | Number of Areas | Range 1-50. | UINT16 | Read | ||||
| IR | 2005doc 32006 | Error Code | Range 0x0000 to 0x7FFF. | UINT16 | Read | ||||
| IR | 2006doc 32007 | Error Category | UINT16 | Read | 0 = Fatal error system; 1 = Fatal error hp-ring; 2 = Error hp-ring (FWA -possible); 3 = Error w. impact on water quality; 4 = Error (system partially down); 5 = Error (limited operation); 6 = Warning (action urgently needed); 7 = Warning (action may needed); 8 = Service due; 9 = Service soon due; 10 = No error (software 3.2.0 or later) | ||||
| IR | 2007doc 32008 | Error Flag | UINT16 | Read | 0 = No errors and no warnings pending; 1 = Errors pending; 2 = Warnings pending; 3 = Info pending | ||||
| IR | 2008doc 32009 | System Viewer Error State | UINT16 | Read | 0 = no error; 1 = warning; 2 = error | ||||
| IR | 2009doc 32010 | System Viewer Err Warn Code | 0 = no error; other codes are listed in the device operation manual. | UINT16 | Read | ||||
| IR | 2500doc 32501 | Area 1 state | UINT16 | Read | 0 = Warning; 1 = Error; 2 = Absent; 3 = Inactive; 4 = FWA (fresh-water automatic active); 5 = Active | ||||
| IR | 2501doc 32502 | Area 2 state | UINT16 | Read | 0 = Warning; 1 = Error; 2 = Absent; 3 = Inactive; 4 = FWA (fresh-water automatic active); 5 = Active | ||||
| IR | 2502doc 32503 | Area 3 state | UINT16 | Read | 0 = Warning; 1 = Error; 2 = Absent; 3 = Inactive; 4 = FWA (fresh-water automatic active); 5 = Active | ||||
| IR | 2503doc 32504 | Area 4 state | UINT16 | Read | 0 = Warning; 1 = Error; 2 = Absent; 3 = Inactive; 4 = FWA (fresh-water automatic active); 5 = Active | ||||
| IR | 2504doc 32505 | Area 5 state | UINT16 | Read | 0 = Warning; 1 = Error; 2 = Absent; 3 = Inactive; 4 = FWA (fresh-water automatic active); 5 = Active | ||||
| IR | 2505doc 32506 | Area 6 state | UINT16 | Read | 0 = Warning; 1 = Error; 2 = Absent; 3 = Inactive; 4 = FWA (fresh-water automatic active); 5 = Active | ||||
| IR | 2506doc 32507 | Area 7 state | UINT16 | Read | 0 = Warning; 1 = Error; 2 = Absent; 3 = Inactive; 4 = FWA (fresh-water automatic active); 5 = Active | ||||
| IR | 2507doc 32508 | Area 8 state | UINT16 | Read | 0 = Warning; 1 = Error; 2 = Absent; 3 = Inactive; 4 = FWA (fresh-water automatic active); 5 = Active | ||||
| IR | 2508doc 32509 | Area 9 state | UINT16 | Read | 0 = Warning; 1 = Error; 2 = Absent; 3 = Inactive; 4 = FWA (fresh-water automatic active); 5 = Active | ||||
| IR | 2509doc 32510 | Area 10 state | UINT16 | Read | 0 = Warning; 1 = Error; 2 = Absent; 3 = Inactive; 4 = FWA (fresh-water automatic active); 5 = Active | ||||
| IR | 2510doc 32511 | Area 11 state | UINT16 | Read | 0 = Warning; 1 = Error; 2 = Absent; 3 = Inactive; 4 = FWA (fresh-water automatic active); 5 = Active | ||||
| IR | 2511doc 32512 | Area 12 state | UINT16 | Read | 0 = Warning; 1 = Error; 2 = Absent; 3 = Inactive; 4 = FWA (fresh-water automatic active); 5 = Active | ||||
| IR | 2512doc 32513 | Area 13 state | UINT16 | Read | 0 = Warning; 1 = Error; 2 = Absent; 3 = Inactive; 4 = FWA (fresh-water automatic active); 5 = Active | ||||
| IR | 2513doc 32514 | Area 14 state | UINT16 | Read | 0 = Warning; 1 = Error; 2 = Absent; 3 = Inactive; 4 = FWA (fresh-water automatic active); 5 = Active | ||||
| IR | 2514doc 32515 | Area 15 state | UINT16 | Read | 0 = Warning; 1 = Error; 2 = Absent; 3 = Inactive; 4 = FWA (fresh-water automatic active); 5 = Active | ||||
| IR | 2515doc 32516 | Area 16 state | UINT16 | Read | 0 = Warning; 1 = Error; 2 = Absent; 3 = Inactive; 4 = FWA (fresh-water automatic active); 5 = Active | ||||
| IR | 2516doc 32517 | Area 17 state | UINT16 | Read | 0 = Warning; 1 = Error; 2 = Absent; 3 = Inactive; 4 = FWA (fresh-water automatic active); 5 = Active | ||||
| IR | 2517doc 32518 | Area 18 state | UINT16 | Read | 0 = Warning; 1 = Error; 2 = Absent; 3 = Inactive; 4 = FWA (fresh-water automatic active); 5 = Active | ||||
| IR | 2518doc 32519 | Area 19 state | UINT16 | Read | 0 = Warning; 1 = Error; 2 = Absent; 3 = Inactive; 4 = FWA (fresh-water automatic active); 5 = Active | ||||
| IR | 2519doc 32520 | Area 20 state | UINT16 | Read | 0 = Warning; 1 = Error; 2 = Absent; 3 = Inactive; 4 = FWA (fresh-water automatic active); 5 = Active | ||||
| IR | 2520doc 32521 | Area 21 state | UINT16 | Read | 0 = Warning; 1 = Error; 2 = Absent; 3 = Inactive; 4 = FWA (fresh-water automatic active); 5 = Active | ||||
| IR | 2521doc 32522 | Area 22 state | UINT16 | Read | 0 = Warning; 1 = Error; 2 = Absent; 3 = Inactive; 4 = FWA (fresh-water automatic active); 5 = Active | ||||
| IR | 2522doc 32523 | Area 23 state | UINT16 | Read | 0 = Warning; 1 = Error; 2 = Absent; 3 = Inactive; 4 = FWA (fresh-water automatic active); 5 = Active | ||||
| IR | 2523doc 32524 | Area 24 state | UINT16 | Read | 0 = Warning; 1 = Error; 2 = Absent; 3 = Inactive; 4 = FWA (fresh-water automatic active); 5 = Active | ||||
| IR | 2524doc 32525 | Area 25 state | UINT16 | Read | 0 = Warning; 1 = Error; 2 = Absent; 3 = Inactive; 4 = FWA (fresh-water automatic active); 5 = Active | ||||
| IR | 2525doc 32526 | Area 26 state | UINT16 | Read | 0 = Warning; 1 = Error; 2 = Absent; 3 = Inactive; 4 = FWA (fresh-water automatic active); 5 = Active | ||||
| IR | 2526doc 32527 | Area 27 state | UINT16 | Read | 0 = Warning; 1 = Error; 2 = Absent; 3 = Inactive; 4 = FWA (fresh-water automatic active); 5 = Active | ||||
| IR | 2527doc 32528 | Area 28 state | UINT16 | Read | 0 = Warning; 1 = Error; 2 = Absent; 3 = Inactive; 4 = FWA (fresh-water automatic active); 5 = Active | ||||
| IR | 2528doc 32529 | Area 29 state | UINT16 | Read | 0 = Warning; 1 = Error; 2 = Absent; 3 = Inactive; 4 = FWA (fresh-water automatic active); 5 = Active | ||||
| IR | 2529doc 32530 | Area 30 state | UINT16 | Read | 0 = Warning; 1 = Error; 2 = Absent; 3 = Inactive; 4 = FWA (fresh-water automatic active); 5 = Active | ||||
| IR | 2530doc 32531 | Area 31 state | UINT16 | Read | 0 = Warning; 1 = Error; 2 = Absent; 3 = Inactive; 4 = FWA (fresh-water automatic active); 5 = Active | ||||
| IR | 2531doc 32532 | Area 32 state | UINT16 | Read | 0 = Warning; 1 = Error; 2 = Absent; 3 = Inactive; 4 = FWA (fresh-water automatic active); 5 = Active | ||||
| IR | 2532doc 32533 | Area 33 state | UINT16 | Read | 0 = Warning; 1 = Error; 2 = Absent; 3 = Inactive; 4 = FWA (fresh-water automatic active); 5 = Active | ||||
| IR | 2533doc 32534 | Area 34 state | UINT16 | Read | 0 = Warning; 1 = Error; 2 = Absent; 3 = Inactive; 4 = FWA (fresh-water automatic active); 5 = Active | ||||
| IR | 2534doc 32535 | Area 35 state | UINT16 | Read | 0 = Warning; 1 = Error; 2 = Absent; 3 = Inactive; 4 = FWA (fresh-water automatic active); 5 = Active | ||||
| IR | 2535doc 32536 | Area 36 state | UINT16 | Read | 0 = Warning; 1 = Error; 2 = Absent; 3 = Inactive; 4 = FWA (fresh-water automatic active); 5 = Active | ||||
| IR | 2536doc 32537 | Area 37 state | UINT16 | Read | 0 = Warning; 1 = Error; 2 = Absent; 3 = Inactive; 4 = FWA (fresh-water automatic active); 5 = Active | ||||
| IR | 2537doc 32538 | Area 38 state | UINT16 | Read | 0 = Warning; 1 = Error; 2 = Absent; 3 = Inactive; 4 = FWA (fresh-water automatic active); 5 = Active | ||||
| IR | 2538doc 32539 | Area 39 state | UINT16 | Read | 0 = Warning; 1 = Error; 2 = Absent; 3 = Inactive; 4 = FWA (fresh-water automatic active); 5 = Active | ||||
| IR | 2539doc 32540 | Area 40 state | UINT16 | Read | 0 = Warning; 1 = Error; 2 = Absent; 3 = Inactive; 4 = FWA (fresh-water automatic active); 5 = Active | ||||
| IR | 2540doc 32541 | Area 41 state | UINT16 | Read | 0 = Warning; 1 = Error; 2 = Absent; 3 = Inactive; 4 = FWA (fresh-water automatic active); 5 = Active | ||||
| IR | 2541doc 32542 | Area 42 state | UINT16 | Read | 0 = Warning; 1 = Error; 2 = Absent; 3 = Inactive; 4 = FWA (fresh-water automatic active); 5 = Active | ||||
| IR | 2542doc 32543 | Area 43 state | UINT16 | Read | 0 = Warning; 1 = Error; 2 = Absent; 3 = Inactive; 4 = FWA (fresh-water automatic active); 5 = Active | ||||
| IR | 2543doc 32544 | Area 44 state | UINT16 | Read | 0 = Warning; 1 = Error; 2 = Absent; 3 = Inactive; 4 = FWA (fresh-water automatic active); 5 = Active | ||||
| IR | 2544doc 32545 | Area 45 state | UINT16 | Read | 0 = Warning; 1 = Error; 2 = Absent; 3 = Inactive; 4 = FWA (fresh-water automatic active); 5 = Active | ||||
| IR | 2545doc 32546 | Area 46 state | UINT16 | Read | 0 = Warning; 1 = Error; 2 = Absent; 3 = Inactive; 4 = FWA (fresh-water automatic active); 5 = Active | ||||
| IR | 2546doc 32547 | Area 47 state | UINT16 | Read | 0 = Warning; 1 = Error; 2 = Absent; 3 = Inactive; 4 = FWA (fresh-water automatic active); 5 = Active | ||||
| IR | 2547doc 32548 | Area 48 state | UINT16 | Read | 0 = Warning; 1 = Error; 2 = Absent; 3 = Inactive; 4 = FWA (fresh-water automatic active); 5 = Active | ||||
| IR | 2548doc 32549 | Area 49 state | UINT16 | Read | 0 = Warning; 1 = Error; 2 = Absent; 3 = Inactive; 4 = FWA (fresh-water automatic active); 5 = Active | ||||
| IR | 2549doc 32550 | Area 50 state | UINT16 | Read | 0 = Warning; 1 = Error; 2 = Absent; 3 = Inactive; 4 = FWA (fresh-water automatic active); 5 = Active | ||||
| IR | 2550doc 32551 | Area 1 actual humidity | FLOAT32 | ABCD | % | Read | |||
| IR | 2552doc 32553 | Area 2 actual humidity | FLOAT32 | ABCD | % | Read | |||
| IR | 2554doc 32555 | Area 3 actual humidity | FLOAT32 | ABCD | % | Read | |||
| IR | 2556doc 32557 | Area 4 actual humidity | FLOAT32 | ABCD | % | Read | |||
| IR | 2558doc 32559 | Area 5 actual humidity | FLOAT32 | ABCD | % | Read | |||
| IR | 2560doc 32561 | Area 6 actual humidity | FLOAT32 | ABCD | % | Read | |||
| IR | 2562doc 32563 | Area 7 actual humidity | FLOAT32 | ABCD | % | Read | |||
| IR | 2564doc 32565 | Area 8 actual humidity | FLOAT32 | ABCD | % | Read | |||
| IR | 2566doc 32567 | Area 9 actual humidity | FLOAT32 | ABCD | % | Read | |||
| IR | 2568doc 32569 | Area 10 actual humidity | FLOAT32 | ABCD | % | Read | |||
| IR | 2570doc 32571 | Area 11 actual humidity | FLOAT32 | ABCD | % | Read | |||
| IR | 2572doc 32573 | Area 12 actual humidity | FLOAT32 | ABCD | % | Read | |||
| IR | 2574doc 32575 | Area 13 actual humidity | FLOAT32 | ABCD | % | Read | |||
| IR | 2576doc 32577 | Area 14 actual humidity | FLOAT32 | ABCD | % | Read | |||
| IR | 2578doc 32579 | Area 15 actual humidity | FLOAT32 | ABCD | % | Read | |||
| IR | 2580doc 32581 | Area 16 actual humidity | FLOAT32 | ABCD | % | Read | |||
| IR | 2582doc 32583 | Area 17 actual humidity | FLOAT32 | ABCD | % | Read | |||
| IR | 2584doc 32585 | Area 18 actual humidity | FLOAT32 | ABCD | % | Read | |||
| IR | 2586doc 32587 | Area 19 actual humidity | FLOAT32 | ABCD | % | Read | |||
| IR | 2588doc 32589 | Area 20 actual humidity | FLOAT32 | ABCD | % | Read | |||
| IR | 2590doc 32591 | Area 21 actual humidity | FLOAT32 | ABCD | % | Read | |||
| IR | 2592doc 32593 | Area 22 actual humidity | FLOAT32 | ABCD | % | Read | |||
| IR | 2594doc 32595 | Area 23 actual humidity | FLOAT32 | ABCD | % | Read | |||
| IR | 2596doc 32597 | Area 24 actual humidity | FLOAT32 | ABCD | % | Read | |||
| IR | 2598doc 32599 | Area 25 actual humidity | FLOAT32 | ABCD | % | Read | |||
| IR | 2600doc 32601 | Area 26 actual humidity | FLOAT32 | ABCD | % | Read | |||
| IR | 2602doc 32603 | Area 27 actual humidity | FLOAT32 | ABCD | % | Read | |||
| IR | 2604doc 32605 | Area 28 actual humidity | FLOAT32 | ABCD | % | Read | |||
| IR | 2606doc 32607 | Area 29 actual humidity | FLOAT32 | ABCD | % | Read | |||
| IR | 2608doc 32609 | Area 30 actual humidity | FLOAT32 | ABCD | % | Read | |||
| IR | 2610doc 32611 | Area 31 actual humidity | FLOAT32 | ABCD | % | Read | |||
| IR | 2612doc 32613 | Area 32 actual humidity | FLOAT32 | ABCD | % | Read | |||
| IR | 2614doc 32615 | Area 33 actual humidity | FLOAT32 | ABCD | % | Read | |||
| IR | 2616doc 32617 | Area 34 actual humidity | FLOAT32 | ABCD | % | Read | |||
| IR | 2618doc 32619 | Area 35 actual humidity | FLOAT32 | ABCD | % | Read | |||
| IR | 2620doc 32621 | Area 36 actual humidity | FLOAT32 | ABCD | % | Read | |||
| IR | 2622doc 32623 | Area 37 actual humidity | FLOAT32 | ABCD | % | Read | |||
| IR | 2624doc 32625 | Area 38 actual humidity | FLOAT32 | ABCD | % | Read | |||
| IR | 2626doc 32627 | Area 39 actual humidity | FLOAT32 | ABCD | % | Read | |||
| IR | 2628doc 32629 | Area 40 actual humidity | FLOAT32 | ABCD | % | Read | |||
| IR | 2630doc 32631 | Area 41 actual humidity | FLOAT32 | ABCD | % | Read | |||
| IR | 2632doc 32633 | Area 42 actual humidity | FLOAT32 | ABCD | % | Read | |||
| IR | 2634doc 32635 | Area 43 actual humidity | FLOAT32 | ABCD | % | Read | |||
| IR | 2636doc 32637 | Area 44 actual humidity | FLOAT32 | ABCD | % | Read | |||
| IR | 2638doc 32639 | Area 45 actual humidity | FLOAT32 | ABCD | % | Read | |||
| IR | 2640doc 32641 | Area 46 actual humidity | FLOAT32 | ABCD | % | Read | |||
| IR | 2642doc 32643 | Area 47 actual humidity | FLOAT32 | ABCD | % | Read | |||
| IR | 2644doc 32645 | Area 48 actual humidity | FLOAT32 | ABCD | % | Read | |||
| IR | 2646doc 32647 | Area 49 actual humidity | FLOAT32 | ABCD | % | Read | |||
| IR | 2648doc 32649 | Area 50 actual humidity | FLOAT32 | ABCD | % | Read | |||
| IR | 2900doc 32901 | Reverse Osmosis State | UINT16 | Read | 0 = Stopped; 1 = Depressuring; 2 = Empty; 3 = Flushing; 4 = Flushing no water; 5 = Producing; 6 = Holding; 7 = Wait for pressure | ||||
| IR | 2901doc 32902 | Deionization State | UINT16 | Read | 0 = Syn_Idle; 1 = Syn_Active | ||||
| IR | 2902doc 32903 | Pressure Status HP Line | UINT16 | Read | 0 = HP_Stopped; 1 = HP_Flushing; 2 = HP_Flushing no water; 3 = HP_Producing; 4 = HP_Producing no water; 5 = HP_Holding; 6 = HP_Depressuring; 7 = HP_Empty; 8 = HP_Ventilating | ||||
| HR | 3500doc 43501 | Area 1 setpoint | Range 20-100 %. | UINT16 | % | Read/write | |||
| HR | 3501doc 43502 | Area 2 setpoint | Range 20-100 %. | UINT16 | % | Read/write | |||
| HR | 3502doc 43503 | Area 3 setpoint | Range 20-100 %. | UINT16 | % | Read/write | |||
| HR | 3503doc 43504 | Area 4 setpoint | Range 20-100 %. | UINT16 | % | Read/write | |||
| HR | 3504doc 43505 | Area 5 setpoint | Range 20-100 %. | UINT16 | % | Read/write | |||
| HR | 3505doc 43506 | Area 6 setpoint | Range 20-100 %. | UINT16 | % | Read/write | |||
| HR | 3506doc 43507 | Area 7 setpoint | Range 20-100 %. | UINT16 | % | Read/write | |||
| HR | 3507doc 43508 | Area 8 setpoint | Range 20-100 %. | UINT16 | % | Read/write | |||
| HR | 3508doc 43509 | Area 9 setpoint | Range 20-100 %. | UINT16 | % | Read/write | |||
| HR | 3509doc 43510 | Area 10 setpoint | Range 20-100 %. | UINT16 | % | Read/write | |||
| HR | 3510doc 43511 | Area 11 setpoint | Range 20-100 %. | UINT16 | % | Read/write | |||
| HR | 3511doc 43512 | Area 12 setpoint | Range 20-100 %. | UINT16 | % | Read/write | |||
| HR | 3512doc 43513 | Area 13 setpoint | Range 20-100 %. | UINT16 | % | Read/write | |||
| HR | 3513doc 43514 | Area 14 setpoint | Range 20-100 %. | UINT16 | % | Read/write | |||
| HR | 3514doc 43515 | Area 15 setpoint | Range 20-100 %. | UINT16 | % | Read/write | |||
| HR | 3515doc 43516 | Area 16 setpoint | Range 20-100 %. | UINT16 | % | Read/write | |||
| HR | 3516doc 43517 | Area 17 setpoint | Range 20-100 %. | UINT16 | % | Read/write | |||
| HR | 3517doc 43518 | Area 18 setpoint | Range 20-100 %. | UINT16 | % | Read/write | |||
| HR | 3518doc 43519 | Area 19 setpoint | Range 20-100 %. | UINT16 | % | Read/write | |||
| HR | 3519doc 43520 | Area 20 setpoint | Range 20-100 %. | UINT16 | % | Read/write | |||
| HR | 3520doc 43521 | Area 21 setpoint | Range 20-100 %. | UINT16 | % | Read/write | |||
| HR | 3521doc 43522 | Area 22 setpoint | Range 20-100 %. | UINT16 | % | Read/write | |||
| HR | 3522doc 43523 | Area 23 setpoint | Range 20-100 %. | UINT16 | % | Read/write | |||
| HR | 3523doc 43524 | Area 24 setpoint | Range 20-100 %. | UINT16 | % | Read/write | |||
| HR | 3524doc 43525 | Area 25 setpoint | Range 20-100 %. | UINT16 | % | Read/write | |||
| HR | 3525doc 43526 | Area 26 setpoint | Range 20-100 %. | UINT16 | % | Read/write | |||
| HR | 3526doc 43527 | Area 27 setpoint | Range 20-100 %. | UINT16 | % | Read/write | |||
| HR | 3527doc 43528 | Area 28 setpoint | Range 20-100 %. | UINT16 | % | Read/write | |||
| HR | 3528doc 43529 | Area 29 setpoint | Range 20-100 %. | UINT16 | % | Read/write | |||
| HR | 3529doc 43530 | Area 30 setpoint | Range 20-100 %. | UINT16 | % | Read/write | |||
| HR | 3530doc 43531 | Area 31 setpoint | Range 20-100 %. | UINT16 | % | Read/write | |||
| HR | 3531doc 43532 | Area 32 setpoint | Range 20-100 %. | UINT16 | % | Read/write | |||
| HR | 3532doc 43533 | Area 33 setpoint | Range 20-100 %. | UINT16 | % | Read/write | |||
| HR | 3533doc 43534 | Area 34 setpoint | Range 20-100 %. | UINT16 | % | Read/write | |||
| HR | 3534doc 43535 | Area 35 setpoint | Range 20-100 %. | UINT16 | % | Read/write | |||
| HR | 3535doc 43536 | Area 36 setpoint | Range 20-100 %. | UINT16 | % | Read/write | |||
| HR | 3536doc 43537 | Area 37 setpoint | Range 20-100 %. | UINT16 | % | Read/write | |||
| HR | 3537doc 43538 | Area 38 setpoint | Range 20-100 %. | UINT16 | % | Read/write | |||
| HR | 3538doc 43539 | Area 39 setpoint | Range 20-100 %. | UINT16 | % | Read/write | |||
| HR | 3539doc 43540 | Area 40 setpoint | Range 20-100 %. | UINT16 | % | Read/write | |||
| HR | 3540doc 43541 | Area 41 setpoint | Range 20-100 %. | UINT16 | % | Read/write | |||
| HR | 3541doc 43542 | Area 42 setpoint | Range 20-100 %. | UINT16 | % | Read/write | |||
| HR | 3542doc 43543 | Area 43 setpoint | Range 20-100 %. | UINT16 | % | Read/write | |||
| HR | 3543doc 43544 | Area 44 setpoint | Range 20-100 %. | UINT16 | % | Read/write | |||
| HR | 3544doc 43545 | Area 45 setpoint | Range 20-100 %. | UINT16 | % | Read/write | |||
| HR | 3545doc 43546 | Area 46 setpoint | Range 20-100 %. | UINT16 | % | Read/write | |||
| HR | 3546doc 43547 | Area 47 setpoint | Range 20-100 %. | UINT16 | % | Read/write | |||
| HR | 3547doc 43548 | Area 48 setpoint | Range 20-100 %. | UINT16 | % | Read/write | |||
| HR | 3548doc 43549 | Area 49 setpoint | Range 20-100 %. | UINT16 | % | Read/write | |||
| HR | 3549doc 43550 | Area 50 setpoint | Range 20-100 %. | UINT16 | % | Read/write |
Notes on this map
- Input registers are read with function 04; holding registers with 03 and written with 06 or 16.
- Floats use 'Register Sequence': MSR first (high register first, ABCD) is the factory setting; LSR first (CDAB) is the option. The map assumes the factory setting.
- Factory serial settings: Modbus RTU, address 10, 19200 baud, even parity, 8 data bits, 1 stop bit. Modbus TCP uses port 502 and unit ID 255 (per the TCP technical data).
- Units marked metric/imperial follow the controller's Metric/Imperial setting; the listed unit is the metric one.
- Left out: UInt32 values (serial number, replacement and error timestamps) because the manual gives the register sequence for floats only.
- Left out: area actual temperatures; the range is printed 32651-32751 / 2650-2750 (101 registers) for 50 floats, so the end of the block is unclear.
- Area humidity floats are listed two registers per area from 2550, matching the printed 2550-2649 range.
Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.
Questions about the Condair Vita high-pressure humidification system (Integrated Controller, Modbus RTU/TCP)
What Modbus registers does the Condair Vita high-pressure humidification system (Integrated Controller, Modbus RTU/TCP) have?
This map lists 159 registers: 109 input registers, 50 holding registers. 50 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.
Are the Condair Vita high-pressure humidification system (Integrated Controller, Modbus RTU/TCP) Modbus addresses 0-based or 1-based?
The manufacturer's document numbers registers Modicon 3xxxx/4xxxx (drop the prefix, subtract 1). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. Tables print the 5-digit register (32001 = input register, 43001 = holding register) and the 0-based address beside it (2000 / 3000). The address column is what goes on the wire; the manual's own example: register 43004 = address 3003.
What byte order does the Condair Vita high-pressure humidification system (Integrated Controller, Modbus RTU/TCP) use for 32-bit values?
Multi-register values in this map use ABCD (high word first (big-endian)). Set your client to this order for every 32/64-bit value in the table.
What are the minimum Modbus registers to integrate the Condair Vita high-pressure humidification system (Integrated Controller, Modbus RTU/TCP)?
Start with IR 2000 Number of Areas (Number of areas); IR 2007 Error Flag (Error flag); IR 2006 Error Category (Error category); IR 2900 Reverse Osmosis State (RO state); IR 2500 Area 1 state (Area 1 state); HR 3500 Area 1 setpoint (Area 1 setpoint).
How do I enable Modbus control of the Condair Vita high-pressure humidification system (Integrated Controller, Modbus RTU/TCP)?
Network > Modbus Settings on the controller.
Where is the official Condair Vita high-pressure humidification system (Integrated Controller, Modbus RTU/TCP) Modbus documentation?
The source is Modbus addendum manual for DL II, ME II, RS II, RO-E and Vita (Integrated Controller) (2603326-G EN 2607), published free by Condair at https://www.condair.com/m/0/2603326-e-modbus-for-dl-series-addendum.pdf.
More Condair Modbus register maps
- Air handler humidifier (hybrid / spray)
Condair DL II hybrid humidifier (Integrated Controller, Modbus RTU/TCP)
Condair DL with the Integrated Controller, per addendum 2603326-G.
Also known as: Condair DL, Condair DL II, DL - Air handler humidifier (evaporative)
Condair ME II evaporative humidifier / cooler (Integrated Controller, Modbus RTU/TCP)
Condair ME with the Integrated Controller, per addendum 2603326-G.
Also known as: Condair ME, Condair ME II, ME - Pump (reverse osmosis water treatment unit)
Condair RO-E reverse osmosis water treatment (Integrated Controller, Modbus RTU/TCP)
Condair RO-E / RO-E+ with the Integrated Controller, per addendum 2603326-G.
Also known as: Condair RO-E, RO-E+, Condair RO-E+ - Air handler humidifier (resistive steam)
Condair RS II resistive steam humidifier (Integrated Controller, Modbus RTU/TCP)
Condair RS with the Integrated Controller (cylinders A and B), per addendum 2603326-G.
Also known as: Condair RS, Condair RS II, RS
Other hvac equipment register maps
- Rooftop unit / packaged wall-mount air conditioner
Eubank EAH / EGH wall-mount air conditioner control board (Modbus RTU)
Eubank EAH1020A-1060A, EGH1072A, EAH2024A-2060A and EGH2072A wall-mount air conditioners with the electronic control board (I&O manual rev. 7).
Also known as: EAH1020A, EAH1024A, EAH1030A, EAH1036A, EAH1042A, EAH1048A, EAH1060A, EGH1072A, EAH2024A, EAH2030A, EAH2036A, EAH2042A, EAH2048A, EAH2060A, EGH2072A, Eubank EAH, Eubank EGH - Thermostat
Johnson Controls PENN TC3224N9V refrigeration temperature controller (Modbus RTU)
PENN TC3224N9V electronic refrigeration controller with built-in Modbus RTU, per the TC3 Modbus Protocol Reference Guide LIT-12013523 (2020-04-28).
Also known as: TC3224N9V, TC3, PENN TC3, LIT-12013523, TC3224N9R, TC3224 - Thermostat / room controller (temperature, humidity, CO2, VOC)
Neptronic AROB series universal room controller (Modbus communication module)
Neptronic AROB24T / AROB24TH / AROB24TGH / AROB24TGVH universal room controllers with the Modbus module, ARO Modbus Guide_170824.
Also known as: AROB, AROB24T, AROB24TH, AROB24TGH, AROB24TGVH, ARO - Air handler humidifier (high-pressure atomizer)
Neptronic SKH4 high-pressure atomizer humidifier (Modbus communication module)
Neptronic SKH4 high-pressure atomizers with the Modbus communication module, guide SKH4-Modbus Guide-240126 (V.1.00).
Also known as: SKH4, SKH4 High-Pressure Atomizer, Neptronic SKH4 Modbus - Air handler (enclosure air conditioner)
Seifert Systems Enclosure air conditioners (standard Modbus table)
Seifert Systems enclosure cooling units with Carel, Variable Speed or Seifert Standard controllers, per technical guide RDTG2001 rev 0.2 (09.02.2021).
Also known as: RDTG2001, Seifert enclosure cooling unit Modbus - Air handler (heat recovery unit controller)
Swegon TAC6 controller (Global units)
Swegon (Global) units with the TAC6 regulation board and a Modbus satellite; TAC6 + MODBUS TABLE Cid 050360 (2021-05-20).
Also known as: Global TAC6, SAT WIFI-ETHERNET (TAC6)
All hvac equipment Modbus register maps →
Source: Modbus addendum manual for DL II, ME II, RS II, RO-E and Vita (Integrated Controller) · 2603326-G EN 2607. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.