- RS II resistive steam humidifier (Integrated Controller, Modbus RTU/TCP)
Air handler humidifier (resistive steam) · Modbus register map
Condair RS II resistive steam humidifier (Integrated Controller, Modbus RTU/TCP) Modbus register map
Updated 17 November 2026
The Condair RS is a resistive-heating steam humidifier with one or two cylinders. Its Integrated Controller is a Modbus RTU slave on RS-485 or a Modbus TCP server. This map covers per-cylinder status, safety chain, heating, valves and levels, capacities, demand, operating hours and service counters, plus two-channel setpoint and control registers.
This page lists 59 Modbus registers for the Condair RS II resistive steam humidifier (Integrated Controller, Modbus RTU/TCP) — 12 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Condair’s own free documentation (linked below) and checked against it.
- Manufacturer
- Condair
- Model
- RS II resistive steam humidifier (Integrated Controller, Modbus RTU/TCP)
- Equipment type
- Air handler humidifier (resistive steam)
- Registers
- 59 (12 writable)
- Transport
- Modbus RTU, Modbus TCP
- Default unit ID
- 10
- Default serial
- 19200 baud, 8E1
- TCP port
- 502
- Documented addressing
- Modicon 3xxxx/4xxxx (drop the prefix, subtract 1)
- 32-bit word order
- ABCD high word first (big-endian)
- Also known as
- Condair RS, Condair RS II, RS
Integration notes: Condair RS II resistive steam humidifier (Integrated Controller, Modbus RTU/TCP)
Read input registers 2000-2030 (UInt16) and 2041-2072 (floats). Write channel 1 demand or humidity to holding 3007 (and channel 2 to 3008 for dual control).
Minimum registers to map
Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.
| Register | Name | Type | Why | Access |
|---|---|---|---|---|
| IR 2000 | Device Status Cyl. A | UINT16 | Status cylinder A | Read |
| IR 2002 | Maintenance and Error Status | UINT16 | Maintenance and error status | Read |
| IR 2003 | ErrorWarning Code | UINT16 | Error/warning code | Read |
| IR 2047 | Actual Hum. Capacity | FLOAT32 ABCD | Actual capacity | Read |
| IR 2057 | System Demand | FLOAT32 ABCD | System demand | Read |
| HR 3007 | Actual humidity or demand via Modbus CH1 | UINT16 | Demand/humidity via Modbus CH1 | Read/write |
Enable Modbus control & writes
Controls > Signal Settings: set Source = Modbus.
Communication loss & watchdog
When the demand or humidity signal comes from Modbus, it must be rewritten within 'Signal Timeout' (1-300 s, default 300 s); otherwise warning W35 is raised and the unit stops humidifying.
Byte order & addressing
- The address column is the wire address; 32001 is address 2000.
- Floats are two registers, MSR first by default.
Network setup
- Menu > password 8808 > Network > Modbus Settings: set protocol (Modbus/RTU or Modbus/TCP), address, parity, baud rate and register sequence; the controller restarts after a protocol change.
- For Modbus TCP set the IP parameters under Network > IP Settings (factory setting DHCP).
Watch out for
- Cylinder B registers read meaningfully only on two-cylinder units.
Condair RS II resistive steam humidifier (Integrated Controller, Modbus RTU/TCP) Modbus registers
Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.
| Table | Address | Name | Description | Type | Order | Scale | Units | Access | Values / bits |
|---|---|---|---|---|---|---|---|---|---|
| IR | 2000doc 32001 | Device Status Cyl. A | UINT16 | Read | 0 = Initializing; 1 = Diagnostic; 2 = Stopped; 3 = Break; 4 = Level Test; 5 = Standby; 6 = Humidifying; 7 = Filling; 8 = Idle; 9 = Draining; 10 = Remote Off; 11 = Keep Warm | ||||
| IR | 2001doc 32002 | Device Status Cyl. B | UINT16 | Read | 0 = Initializing; 1 = Diagnostic; 2 = Stopped; 3 = Break; 4 = Level Test; 5 = Standby; 6 = Humidifying; 7 = Filling; 8 = Idle; 9 = Draining; 10 = Remote Off; 11 = Keep Warm | ||||
| IR | 2002doc 32003 | Maintenance and Error Status | UINT16 | Read | 0 = Service Info; 1 = Warning; 2 = RO Service; 3 = Extended Maintenance; 4 = Small Maintenance; 5 = Activation Code; 6 = Error | ||||
| IR | 2003doc 32004 | ErrorWarning Code | 0 = no error; other codes are listed in the device operation manual. | UINT16 | Read | ||||
| IR | 2004doc 32005 | Overheat Switch Cyl. A | Range 0 = Open 1 = Closed (=ok). | UINT16 | Read | ||||
| IR | 2005doc 32006 | Overheat Switch Cyl. B | Range 0 = Open 1 = Closed (=ok). | UINT16 | Read | ||||
| IR | 2006doc 32007 | External Safety Loop Cyl. A | Range 0 = Open 1 = Closed (=ok). | UINT16 | Read | ||||
| IR | 2007doc 32008 | External Safety Loop Cyl. B | Range 0 = Open 1 = Closed (=ok). | UINT16 | Read | ||||
| IR | 2008doc 32009 | Security Floater Cyl. A | Range 0 = Open 1 = Closed (=ok). | UINT16 | Read | ||||
| IR | 2009doc 32010 | Security Floater Cyl. B | Range 0 = Open 1 = Closed (=ok). | UINT16 | Read | ||||
| IR | 2010doc 32011 | Heating Voltage Cyl. A | UINT16 | Read | 0 = Off; 1 = On | ||||
| IR | 2011doc 32012 | Heating Voltage Cyl. B | UINT16 | Read | 0 = Off; 1 = On | ||||
| IR | 2012doc 32013 | Blower Pack Cyl. A | UINT16 | Read | 0 = Off; 1 = On (ready) | ||||
| IR | 2013doc 32014 | Blower Pack Cyl. B | UINT16 | Read | 0 = Off; 1 = On (ready) | ||||
| IR | 2014doc 32015 | Main Contactor Cyl. A | UINT16 | Read | 0 = Off; 1 = On | ||||
| IR | 2015doc 32016 | Main Contactor Cyl. B | UINT16 | Read | 0 = Off; 1 = On | ||||
| IR | 2016doc 32017 | Relay Pump Cyl. A | UINT16 | Read | 0 = Off; 1 = On | ||||
| IR | 2017doc 32018 | Relay Pump Cyl. B | UINT16 | Read | 0 = Off; 1 = On | ||||
| IR | 2018doc 32019 | Inlet Valve 1 Cyl. A | UINT16 | Read | 0 = Closed; 1 = Open | ||||
| IR | 2019doc 32020 | Inlet Valve 1 Cyl. B | UINT16 | Read | 0 = Closed; 1 = Open | ||||
| IR | 2020doc 32021 | Inlet Valve 2 Cyl. A | UINT16 | Read | 0 = Closed; 1 = Open | ||||
| IR | 2021doc 32022 | Inlet Valve 2 Cyl. B | UINT16 | Read | 0 = Closed; 1 = Open | ||||
| IR | 2022doc 32023 | Drain Cooling Valve Cyl. A | UINT16 | Read | 0 = Closed; 1 = Open | ||||
| IR | 2023doc 32024 | Drain Cooling Valve Cyl. B | UINT16 | Read | 0 = Closed; 1 = Open | ||||
| IR | 2024doc 32025 | Complete Drain Valve Cyl. A | UINT16 | Read | 0 = Closed; 1 = Open | ||||
| IR | 2025doc 32026 | Complete Drain Valve Cyl. B | UINT16 | Read | 0 = Closed; 1 = Open | ||||
| IR | 2026doc 32027 | Leakage Sensor | UINT16 | Read | 0 = Off (leak); 1 = On | ||||
| IR | 2027doc 32028 | Furnace fan (UL) / external pipe flush (CE) | UL units: remote furnace/fan 0 off, 1 on. CE units: pipe flush 0 closed, 1 open. | UINT16 | Read | ||||
| IR | 2028doc 32029 | Level Cyl. A | UINT16 | Read | 0 = no level; 1 = low; 2 = low-mid; 3 = mid; 4 = mid-high; 5 = high | ||||
| IR | 2029doc 32030 | Level Cyl. B | UINT16 | Read | 0 = no level; 1 = low; 2 = low-mid; 3 = mid; 4 = mid-high; 5 = high | ||||
| IR | 2030doc 32031 | Nominal Voltage | UINT16 | Read | 0 = 200V; 1 = 208V; 2 = 230 V; 3 = 240 V; 4 = 380 V; 5 = 400 V; 6 = 415 V; 7 = 440 V; 8 = 460 V; 9 = 480 V; 10 = 500 V; 11 = 550V; 12 = 600 V | ||||
| IR | 2041doc 32042 | Max Hum. Capacity | Range 5 - 160 kg/h 10 - 360 lb/hr. Metric or imperial per controller setting. | FLOAT32 | ABCD | kg/h | Read | ||
| IR | 2043doc 32044 | Max Hum. Capacity Cyl. A | Range 5 - 40 kg/h 10 - 90 lb/hr. Metric or imperial per controller setting. | FLOAT32 | ABCD | kg/h | Read | ||
| IR | 2045doc 32046 | Max Hum. Capacity Cyl. B | Range 5 - 40 kg/h 10 - 90 lb/hr. Metric or imperial per controller setting. | FLOAT32 | ABCD | kg/h | Read | ||
| IR | 2047doc 32048 | Actual Hum. Capacity | Range 0 - 160 kg/h 0 - 360 lb/hr. Metric or imperial per controller setting. | FLOAT32 | ABCD | kg/h | Read | ||
| IR | 2049doc 32050 | Actual Hum. Capacity Cyl. A | Range 0 - 40 kg/h 0 - 90 lb/hr. Metric or imperial per controller setting. | FLOAT32 | ABCD | kg/h | Read | ||
| IR | 2051doc 32052 | Actual Hum. Capacity Cyl. B | Range 0 - 40 kg/h 0 - 90 lb/hr. Metric or imperial per controller setting. | FLOAT32 | ABCD | kg/h | Read | ||
| IR | 2053doc 32054 | Control CH1 | Range 0 - 100%. | FLOAT32 | ABCD | % | Read | ||
| IR | 2055doc 32056 | Control CH2 | Range 0 - 100%. | FLOAT32 | ABCD | % | Read | ||
| IR | 2057doc 32058 | System Demand | Range 0 - 100%. | FLOAT32 | ABCD | % | Read | ||
| IR | 2059doc 32060 | Operating Hours | Range 0 - 1'200'000 h. | FLOAT32 | ABCD | h | Read | ||
| IR | 2061doc 32062 | Operating Hours Cyl. A | Range 0 - 1'200'000 h. | FLOAT32 | ABCD | h | Read | ||
| IR | 2063doc 32064 | Operating Hours Cyl. B | Range 0 - 1'200'000 h. | FLOAT32 | ABCD | h | Read | ||
| IR | 2065doc 32066 | Next Small Maintenance Cyl. A | Range 0 - 6000 h. | FLOAT32 | ABCD | h | Read | ||
| IR | 2067doc 32068 | Next Small Maintenance Cyl. B | Range 0 - 6000 h. | FLOAT32 | ABCD | h | Read | ||
| IR | 2069doc 32070 | Next Extended Maintenance Cyl. A | Range 0 - 6000 h. | FLOAT32 | ABCD | h | Read | ||
| IR | 2071doc 32072 | Next Extended Maintenance Cyl. B | Range 0 - 6000 h. | FLOAT32 | ABCD | h | Read | ||
| HR | 3000doc 43001 | Setpoint CH1 | Range 5 - 95 %. | UINT16 | % | Read/write | |||
| HR | 3001doc 43002 | Setpoint CH2 | Range 5 - 95 %. | UINT16 | % | Read/write | |||
| HR | 3002doc 43003 | P-Band CH1 | Range 6 - 65 %. | UINT16 | % | Read/write | |||
| HR | 3003doc 43004 | P-Band CH2 | Range 6 - 65 %. | UINT16 | % | Read/write | |||
| HR | 3004doc 43005 | I-Time CH1 | Range 1 - 60 min. | UINT16 | min | Read/write | |||
| HR | 3005doc 43006 | I-Time CH2 | Range 1 - 60 min. | UINT16 | min | Read/write | |||
| HR | 3006doc 43007 | Capacity Limitation | Range 20 - 100 %. | UINT16 | % | Read/write | |||
| HR | 3007doc 43008 | Actual humidity or demand via Modbus CH1 | Range 0 - 100 %. | UINT16 | % | Read/write | |||
| HR | 3008doc 43009 | Actual humidity or demand via Modbus CH2 | Range 0 - 100 %. | UINT16 | % | Read/write | |||
| HR | 5001doc 45002 | Remote RS Drain | Read 100 = off or 0-99 = progress %; write 1 = start, 0 = stop. | UINT16 | % | Read/write | |||
| HR | 5002doc 45003 | Remote RS Drain Cyl. A | Read 100 = off or 0-99 = progress %; write 1 = start, 0 = stop. | UINT16 | % | Read/write | |||
| HR | 5003doc 45004 | Remote RS Drain Cyl. B | Read 100 = off or 0-99 = progress %; write 1 = start, 0 = stop. | UINT16 | % | Read/write |
Notes on this map
- Input registers are read with function 04; holding registers with 03 and written with 06 or 16.
- Floats use 'Register Sequence': MSR first (high register first, ABCD) is the factory setting; LSR first (CDAB) is the option. The map assumes the factory setting.
- Factory serial settings: Modbus RTU, address 10, 19200 baud, even parity, 8 data bits, 1 stop bit. Modbus TCP uses port 502 and unit ID 255 (per the TCP technical data).
- Units marked metric/imperial follow the controller's Metric/Imperial setting; the listed unit is the metric one.
Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.
Questions about the Condair RS II resistive steam humidifier (Integrated Controller, Modbus RTU/TCP)
What Modbus registers does the Condair RS II resistive steam humidifier (Integrated Controller, Modbus RTU/TCP) have?
This map lists 59 registers: 47 input registers, 12 holding registers. 12 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.
Are the Condair RS II resistive steam humidifier (Integrated Controller, Modbus RTU/TCP) Modbus addresses 0-based or 1-based?
The manufacturer's document numbers registers Modicon 3xxxx/4xxxx (drop the prefix, subtract 1). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. Tables print the 5-digit register (32001 = input register, 43001 = holding register) and the 0-based address beside it (2000 / 3000). The address column is what goes on the wire; the manual's own example: register 43004 = address 3003.
What byte order does the Condair RS II resistive steam humidifier (Integrated Controller, Modbus RTU/TCP) use for 32-bit values?
Multi-register values in this map use ABCD (high word first (big-endian)). Set your client to this order for every 32/64-bit value in the table.
What are the minimum Modbus registers to integrate the Condair RS II resistive steam humidifier (Integrated Controller, Modbus RTU/TCP)?
Start with IR 2000 Device Status Cyl. A (Status cylinder A); IR 2002 Maintenance and Error Status (Maintenance and error status); IR 2003 ErrorWarning Code (Error/warning code); IR 2047 Actual Hum. Capacity (Actual capacity); IR 2057 System Demand (System demand); HR 3007 Actual humidity or demand via Modbus CH1 (Demand/humidity via Modbus CH1).
How do I enable Modbus control of the Condair RS II resistive steam humidifier (Integrated Controller, Modbus RTU/TCP)?
Controls > Signal Settings: set Source = Modbus.
What happens when the Condair RS II resistive steam humidifier (Integrated Controller, Modbus RTU/TCP) loses Modbus communication?
When the demand or humidity signal comes from Modbus, it must be rewritten within 'Signal Timeout' (1-300 s, default 300 s); otherwise warning W35 is raised and the unit stops humidifying.
Where is the official Condair RS II resistive steam humidifier (Integrated Controller, Modbus RTU/TCP) Modbus documentation?
The source is Modbus addendum manual for DL II, ME II, RS II, RO-E and Vita (Integrated Controller) (2603326-G EN 2607), published free by Condair at https://www.condair.com/m/0/2603326-e-modbus-for-dl-series-addendum.pdf.
More Condair Modbus register maps
- Air handler humidifier (hybrid / spray)
Condair DL II hybrid humidifier (Integrated Controller, Modbus RTU/TCP)
Condair DL with the Integrated Controller, per addendum 2603326-G.
Also known as: Condair DL, Condair DL II, DL - Air handler humidifier (evaporative)
Condair ME II evaporative humidifier / cooler (Integrated Controller, Modbus RTU/TCP)
Condair ME with the Integrated Controller, per addendum 2603326-G.
Also known as: Condair ME, Condair ME II, ME - Pump (reverse osmosis water treatment unit)
Condair RO-E reverse osmosis water treatment (Integrated Controller, Modbus RTU/TCP)
Condair RO-E / RO-E+ with the Integrated Controller, per addendum 2603326-G.
Also known as: Condair RO-E, RO-E+, Condair RO-E+ - Air handler humidifier (high-pressure room system)
Condair Vita high-pressure humidification system (Integrated Controller, Modbus RTU/TCP)
Condair Vita system with the Integrated Controller, per addendum 2603326-G.
Also known as: Condair Vita, Vita System Master
Other hvac equipment register maps
- Air handler (EC fan)
ebm-papst EC fans with MODBUS Lite (series 84/112/150/200 Lite)
ebm-papst EC fans and motors whose electronics report the MODBUS Lite parameter set (series 84 / 112 / 150 / 200 Lite), specification V5.01.
Also known as: MODBUS Lite V5.01, ebm-papst RadiCal Modbus, ebm-papst RadiPac Modbus, ebm-papst series 84 Lite, ebm-papst series 112 Lite, ebm-papst series 150 Lite, ebm-papst series 200 Lite - Thermostat
Johnson Controls PENN TC3223 refrigeration temperature controller (Modbus RTU)
PENN TC3223 electronic refrigeration controller with built-in Modbus RTU, per the TC3 Modbus Protocol Reference Guide LIT-12013523 (2020-04-28).
Also known as: TC3223, TC3, PENN TC3, LIT-12013523 - Air handler (computer room air conditioner)
Mitsubishi Electric s-MEXT-G00 computer room air conditioner (ME28 relC)
Mitsubishi Electric (Hydronics & IT Cooling) s-MEXT-G00 006-044 close-control units with ME28-relC software and the Modbus serial board.
Also known as: s-MEXT, s-MEXT-G00 006-044, s-MEXT G00, ME28 relC - Air handler humidifier (gas-fired steam)
Neptronic SKG4 gas-fired steam humidifier (Modbus communication module)
Neptronic SKG4 series gas-fired steam humidifiers (one to four burner modules) with the Modbus communication module, guide SKG4-Modbus Guide-221114 (V2.04).
Also known as: SKG4-E, SKG4-N, SKG4 Gas Fired Humidifier, Neptronic SKG4 Modbus - Air handler controller
Regin Corrigo ventilation controller (ventilation application 3.6)
Regin Corrigo controllers running the pre-programmed ventilation (air handling unit) application, version 3.6 or later; not the heating or Exigo applications.
Also known as: Corrigo E, Corrigo ventilation, Corrigo E ventilation, Corrigo AHU controller - Air handler (heat recovery unit controller)
Swegon TAC5 DG/DM/DT controller (Global HRglobal, HRup, HRflat, HRtotal, HRmural)
Swegon (Global) TAC5 DG, DM and DT regulation boards with the SAT MODBUS (RTU) or SAT WIFI/ETHERNET (TCP) satellite; TAC5 + MODBUS TABLE Cid 050338 (2021-09-20). The TAC5 SC/F single-flow boards use other registers and are not covered.
Also known as: TAC5 DG, TAC5 DM, TAC5 DT, Global HRglobal, Global HRup, Global HRflat, Global HRtotal, Global HRmural, SAT MODBUS
All hvac equipment Modbus register maps →
Source: Modbus addendum manual for DL II, ME II, RS II, RO-E and Vita (Integrated Controller) · 2603326-G EN 2607. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.