Easy Modbus
  1. Home
  2. Modbus register maps
  3. Condair
  4. RS II resistive steam humidifier (Integrated Controller, Modbus RTU/TCP)

Air handler humidifier (resistive steam) · Modbus register map

Condair RS II resistive steam humidifier (Integrated Controller, Modbus RTU/TCP) Modbus register map

Updated 17 November 2026

Short answer

The Condair RS is a resistive-heating steam humidifier with one or two cylinders. Its Integrated Controller is a Modbus RTU slave on RS-485 or a Modbus TCP server. This map covers per-cylinder status, safety chain, heating, valves and levels, capacities, demand, operating hours and service counters, plus two-channel setpoint and control registers.

This page lists 59 Modbus registers for the Condair RS II resistive steam humidifier (Integrated Controller, Modbus RTU/TCP) — 12 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Condair’s own free documentation (linked below) and checked against it.

Manufacturer
Condair
Model
RS II resistive steam humidifier (Integrated Controller, Modbus RTU/TCP)
Equipment type
Air handler humidifier (resistive steam)
Registers
59 (12 writable)
Transport
Modbus RTU, Modbus TCP
Default unit ID
10
Default serial
19200 baud, 8E1
TCP port
502
Documented addressing
Modicon 3xxxx/4xxxx (drop the prefix, subtract 1)
32-bit word order
ABCD high word first (big-endian)
Also known as
Condair RS, Condair RS II, RS
Source document
Modbus addendum manual for DL II, ME II, RS II, RO-E and Vita (Integrated Controller) · 2603326-G EN 2607
Download CSV all columns JSON Manufacturer PDF ↗

Integration notes: Condair RS II resistive steam humidifier (Integrated Controller, Modbus RTU/TCP)

Integration in brief

Read input registers 2000-2030 (UInt16) and 2041-2072 (floats). Write channel 1 demand or humidity to holding 3007 (and channel 2 to 3008 for dual control).

Minimum registers to map

Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.

RegisterNameTypeWhyAccess
IR 2000Device Status Cyl. AUINT16Status cylinder ARead
IR 2002Maintenance and Error StatusUINT16Maintenance and error statusRead
IR 2003ErrorWarning CodeUINT16Error/warning codeRead
IR 2047Actual Hum. CapacityFLOAT32 ABCDActual capacityRead
IR 2057System DemandFLOAT32 ABCDSystem demandRead
HR 3007Actual humidity or demand via Modbus CH1UINT16Demand/humidity via Modbus CH1Read/write

Enable Modbus control & writes

Controls > Signal Settings: set Source = Modbus.

Communication loss & watchdog

When the demand or humidity signal comes from Modbus, it must be rewritten within 'Signal Timeout' (1-300 s, default 300 s); otherwise warning W35 is raised and the unit stops humidifying.

Byte order & addressing

Network setup

Watch out for

Condair RS II resistive steam humidifier (Integrated Controller, Modbus RTU/TCP) Modbus registers

Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.

59 of 59 shown
Condair RS II resistive steam humidifier (Integrated Controller, Modbus RTU/TCP) Modbus register map
TableAddressNameDescriptionTypeOrderScaleUnitsAccessValues / bits
IR2000doc 32001Device Status Cyl. AUINT16Read0 = Initializing; 1 = Diagnostic; 2 = Stopped; 3 = Break; 4 = Level Test; 5 = Standby; 6 = Humidifying; 7 = Filling; 8 = Idle; 9 = Draining; 10 = Remote Off; 11 = Keep Warm
IR2001doc 32002Device Status Cyl. BUINT16Read0 = Initializing; 1 = Diagnostic; 2 = Stopped; 3 = Break; 4 = Level Test; 5 = Standby; 6 = Humidifying; 7 = Filling; 8 = Idle; 9 = Draining; 10 = Remote Off; 11 = Keep Warm
IR2002doc 32003Maintenance and Error StatusUINT16Read0 = Service Info; 1 = Warning; 2 = RO Service; 3 = Extended Maintenance; 4 = Small Maintenance; 5 = Activation Code; 6 = Error
IR2003doc 32004ErrorWarning Code0 = no error; other codes are listed in the device operation manual.UINT16Read
IR2004doc 32005Overheat Switch Cyl. ARange 0 = Open 1 = Closed (=ok).UINT16Read
IR2005doc 32006Overheat Switch Cyl. BRange 0 = Open 1 = Closed (=ok).UINT16Read
IR2006doc 32007External Safety Loop Cyl. ARange 0 = Open 1 = Closed (=ok).UINT16Read
IR2007doc 32008External Safety Loop Cyl. BRange 0 = Open 1 = Closed (=ok).UINT16Read
IR2008doc 32009Security Floater Cyl. ARange 0 = Open 1 = Closed (=ok).UINT16Read
IR2009doc 32010Security Floater Cyl. BRange 0 = Open 1 = Closed (=ok).UINT16Read
IR2010doc 32011Heating Voltage Cyl. AUINT16Read0 = Off; 1 = On
IR2011doc 32012Heating Voltage Cyl. BUINT16Read0 = Off; 1 = On
IR2012doc 32013Blower Pack Cyl. AUINT16Read0 = Off; 1 = On (ready)
IR2013doc 32014Blower Pack Cyl. BUINT16Read0 = Off; 1 = On (ready)
IR2014doc 32015Main Contactor Cyl. AUINT16Read0 = Off; 1 = On
IR2015doc 32016Main Contactor Cyl. BUINT16Read0 = Off; 1 = On
IR2016doc 32017Relay Pump Cyl. AUINT16Read0 = Off; 1 = On
IR2017doc 32018Relay Pump Cyl. BUINT16Read0 = Off; 1 = On
IR2018doc 32019Inlet Valve 1 Cyl. AUINT16Read0 = Closed; 1 = Open
IR2019doc 32020Inlet Valve 1 Cyl. BUINT16Read0 = Closed; 1 = Open
IR2020doc 32021Inlet Valve 2 Cyl. AUINT16Read0 = Closed; 1 = Open
IR2021doc 32022Inlet Valve 2 Cyl. BUINT16Read0 = Closed; 1 = Open
IR2022doc 32023Drain Cooling Valve Cyl. AUINT16Read0 = Closed; 1 = Open
IR2023doc 32024Drain Cooling Valve Cyl. BUINT16Read0 = Closed; 1 = Open
IR2024doc 32025Complete Drain Valve Cyl. AUINT16Read0 = Closed; 1 = Open
IR2025doc 32026Complete Drain Valve Cyl. BUINT16Read0 = Closed; 1 = Open
IR2026doc 32027Leakage SensorUINT16Read0 = Off (leak); 1 = On
IR2027doc 32028Furnace fan (UL) / external pipe flush (CE)UL units: remote furnace/fan 0 off, 1 on. CE units: pipe flush 0 closed, 1 open.UINT16Read
IR2028doc 32029Level Cyl. AUINT16Read0 = no level; 1 = low; 2 = low-mid; 3 = mid; 4 = mid-high; 5 = high
IR2029doc 32030Level Cyl. BUINT16Read0 = no level; 1 = low; 2 = low-mid; 3 = mid; 4 = mid-high; 5 = high
IR2030doc 32031Nominal VoltageUINT16Read0 = 200V; 1 = 208V; 2 = 230 V; 3 = 240 V; 4 = 380 V; 5 = 400 V; 6 = 415 V; 7 = 440 V; 8 = 460 V; 9 = 480 V; 10 = 500 V; 11 = 550V; 12 = 600 V
IR2041doc 32042Max Hum. CapacityRange 5 - 160 kg/h 10 - 360 lb/hr. Metric or imperial per controller setting.FLOAT32ABCDkg/hRead
IR2043doc 32044Max Hum. Capacity Cyl. ARange 5 - 40 kg/h 10 - 90 lb/hr. Metric or imperial per controller setting.FLOAT32ABCDkg/hRead
IR2045doc 32046Max Hum. Capacity Cyl. BRange 5 - 40 kg/h 10 - 90 lb/hr. Metric or imperial per controller setting.FLOAT32ABCDkg/hRead
IR2047doc 32048Actual Hum. CapacityRange 0 - 160 kg/h 0 - 360 lb/hr. Metric or imperial per controller setting.FLOAT32ABCDkg/hRead
IR2049doc 32050Actual Hum. Capacity Cyl. ARange 0 - 40 kg/h 0 - 90 lb/hr. Metric or imperial per controller setting.FLOAT32ABCDkg/hRead
IR2051doc 32052Actual Hum. Capacity Cyl. BRange 0 - 40 kg/h 0 - 90 lb/hr. Metric or imperial per controller setting.FLOAT32ABCDkg/hRead
IR2053doc 32054Control CH1Range 0 - 100%.FLOAT32ABCD%Read
IR2055doc 32056Control CH2Range 0 - 100%.FLOAT32ABCD%Read
IR2057doc 32058System DemandRange 0 - 100%.FLOAT32ABCD%Read
IR2059doc 32060Operating HoursRange 0 - 1'200'000 h.FLOAT32ABCDhRead
IR2061doc 32062Operating Hours Cyl. ARange 0 - 1'200'000 h.FLOAT32ABCDhRead
IR2063doc 32064Operating Hours Cyl. BRange 0 - 1'200'000 h.FLOAT32ABCDhRead
IR2065doc 32066Next Small Maintenance Cyl. ARange 0 - 6000 h.FLOAT32ABCDhRead
IR2067doc 32068Next Small Maintenance Cyl. BRange 0 - 6000 h.FLOAT32ABCDhRead
IR2069doc 32070Next Extended Maintenance Cyl. ARange 0 - 6000 h.FLOAT32ABCDhRead
IR2071doc 32072Next Extended Maintenance Cyl. BRange 0 - 6000 h.FLOAT32ABCDhRead
HR3000doc 43001Setpoint CH1Range 5 - 95 %.UINT16%Read/write
HR3001doc 43002Setpoint CH2Range 5 - 95 %.UINT16%Read/write
HR3002doc 43003P-Band CH1Range 6 - 65 %.UINT16%Read/write
HR3003doc 43004P-Band CH2Range 6 - 65 %.UINT16%Read/write
HR3004doc 43005I-Time CH1Range 1 - 60 min.UINT16minRead/write
HR3005doc 43006I-Time CH2Range 1 - 60 min.UINT16minRead/write
HR3006doc 43007Capacity LimitationRange 20 - 100 %.UINT16%Read/write
HR3007doc 43008Actual humidity or demand via Modbus CH1Range 0 - 100 %.UINT16%Read/write
HR3008doc 43009Actual humidity or demand via Modbus CH2Range 0 - 100 %.UINT16%Read/write
HR5001doc 45002Remote RS DrainRead 100 = off or 0-99 = progress %; write 1 = start, 0 = stop.UINT16%Read/write
HR5002doc 45003Remote RS Drain Cyl. ARead 100 = off or 0-99 = progress %; write 1 = start, 0 = stop.UINT16%Read/write
HR5003doc 45004Remote RS Drain Cyl. BRead 100 = off or 0-99 = progress %; write 1 = start, 0 = stop.UINT16%Read/write

Notes on this map

Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.

Questions about the Condair RS II resistive steam humidifier (Integrated Controller, Modbus RTU/TCP)

What Modbus registers does the Condair RS II resistive steam humidifier (Integrated Controller, Modbus RTU/TCP) have?

This map lists 59 registers: 47 input registers, 12 holding registers. 12 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.

Are the Condair RS II resistive steam humidifier (Integrated Controller, Modbus RTU/TCP) Modbus addresses 0-based or 1-based?

The manufacturer's document numbers registers Modicon 3xxxx/4xxxx (drop the prefix, subtract 1). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. Tables print the 5-digit register (32001 = input register, 43001 = holding register) and the 0-based address beside it (2000 / 3000). The address column is what goes on the wire; the manual's own example: register 43004 = address 3003.

What byte order does the Condair RS II resistive steam humidifier (Integrated Controller, Modbus RTU/TCP) use for 32-bit values?

Multi-register values in this map use ABCD (high word first (big-endian)). Set your client to this order for every 32/64-bit value in the table.

What are the minimum Modbus registers to integrate the Condair RS II resistive steam humidifier (Integrated Controller, Modbus RTU/TCP)?

Start with IR 2000 Device Status Cyl. A (Status cylinder A); IR 2002 Maintenance and Error Status (Maintenance and error status); IR 2003 ErrorWarning Code (Error/warning code); IR 2047 Actual Hum. Capacity (Actual capacity); IR 2057 System Demand (System demand); HR 3007 Actual humidity or demand via Modbus CH1 (Demand/humidity via Modbus CH1).

How do I enable Modbus control of the Condair RS II resistive steam humidifier (Integrated Controller, Modbus RTU/TCP)?

Controls > Signal Settings: set Source = Modbus.

What happens when the Condair RS II resistive steam humidifier (Integrated Controller, Modbus RTU/TCP) loses Modbus communication?

When the demand or humidity signal comes from Modbus, it must be rewritten within 'Signal Timeout' (1-300 s, default 300 s); otherwise warning W35 is raised and the unit stops humidifying.

Where is the official Condair RS II resistive steam humidifier (Integrated Controller, Modbus RTU/TCP) Modbus documentation?

The source is Modbus addendum manual for DL II, ME II, RS II, RO-E and Vita (Integrated Controller) (2603326-G EN 2607), published free by Condair at https://www.condair.com/m/0/2603326-e-modbus-for-dl-series-addendum.pdf.

More Condair Modbus register maps

Other hvac equipment register maps

All hvac equipment Modbus register maps →

Source: Modbus addendum manual for DL II, ME II, RS II, RO-E and Vita (Integrated Controller) · 2603326-G EN 2607. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.