- Home
- Modbus register maps
- Johnson Controls
- PENN TC3223 refrigeration temperature controller (Modbus RTU)
Thermostat · Modbus register map
Johnson Controls PENN TC3223 refrigeration temperature controller (Modbus RTU) Modbus register map
Updated 17 November 2026
Electronic refrigeration temperature controller with 2 probe inputs and 3 relay outputs. Everything is a holding register: probe readings in tenths, relay and digital-input bits, alarm flags, on/standby and defrost commands, and the full parameter list (setpoint, differential, compressor protection, defrost, alarm, door input, energy saving, real-time-clock defrosts and Modbus address/baud).
This page lists 107 Modbus registers for the Johnson Controls PENN TC3223 refrigeration temperature controller (Modbus RTU) — 99 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Johnson Controls’s own free documentation (linked below) and checked against it.
- Manufacturer
- Johnson Controls
- Model
- PENN TC3223 refrigeration temperature controller (Modbus RTU)
- Equipment type
- Thermostat
- Registers
- 107 (99 writable)
- Transport
- Modbus RTU
- Default unit ID
- Not stated
- Documented addressing
- hexadecimal, 0-based
- Also known as
- TC3223, TC3, PENN TC3, LIT-12013523
Integration notes: Johnson Controls PENN TC3223 refrigeration temperature controller (Modbus RTU)
Set the LA (address) and Lb (baud) parameters, then poll holding registers with function 03: Probe 1 at 0x0201 (tenths), relay bits at 0x0181 and alarm bits at 0x0301. Write On/Standby (0x0501), the setpoint SP (0x0601, tenths) and trigger defrosts through 0x28B0.
Minimum registers to map
Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.
| Register | Name | Type | Why | Access |
|---|---|---|---|---|
| HR 513 | Probe 1 | INT16 | Cabinet probe temperature | Read |
| HR 1537 | Setpoint (SP) | INT16 | Control setpoint | Read/write |
| HR 1281 | On or standby | UINT16 | Run / standby command | Read/write |
| HR 385 | Digital outputs | BITMAP16 | Relay output states | Read |
| HR 769 | Alarm flags | BITMAP16 | Alarm and probe-failure flags | Read |
| HR 10416 | Defrost command | UINT16 | Start/stop a defrost (0Dh/0Ch) | Write |
| HR 1544 | Celsius or Fahrenheit (P2) | UINT16 | Temperature unit | Read/write |
Enable Modbus control & writes
Modbus RTU is built in; set the Modbus address (LA) and baud rate (Lb) parameters at the controller.
Byte order & addressing
- Use the hex Base 0 column as the wire address; the HR: column is 1-based.
- Temperatures are in tenths; their printed ranges go below zero, so read them as signed (the guide does not state signedness).
- Defrost command register takes 0Dh to start and 0Ch to stop a defrost.
Network setup
- Address LA 1-247; baud Lb 0 = 2400, 1 = 4800, 2 = 9600, 3 = 19200.
Watch out for
- Parameter register numbers differ between the TC3221, TC3222, TC3223 and TC3224 versions; use the map for the exact model.
Johnson Controls PENN TC3223 refrigeration temperature controller (Modbus RTU) Modbus registers
Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.
| Table | Address | Name | Description | Type | Order | Scale | Units | Access | Values / bits |
|---|---|---|---|---|---|---|---|---|---|
| HR | 257doc 0101h (HR:258) | Digital inputs | BITMAP16 | Read | bit 2 = Digital input | ||||
| HR | 385doc 0181h (HR:386) | Digital outputs | BITMAP16 | Read | bit 0 = K1 output; bit 1 = K2 output; bit 2 = K3 output | ||||
| HR | 513doc 0201h (HR:514) | Probe 1 | Probe reading in tenths; °C or °F per parameter P2. | INT16 | × 0.1 | Read | |||
| HR | 514doc 0202h (HR:515) | Probe 2 | Probe reading in tenths; °C or °F per parameter P2. | INT16 | × 0.1 | Read | |||
| HR | 769doc 0301h (HR:770) | Alarm flags | 1 = active. | BITMAP16 | Read | bit 0 = Cabinet probe failure (Pr1); bit 1 = Evaporator probe failure (Pr2); bit 2 = Condenser probe failure (Pr3); bit 3 = Maximum temperature alarm (AH); bit 4 = Minimum temperature alarm (AL); bit 5 = Global thermical switch (th); bit 6 = Multifunction input alarm (iA); bit 7 = Door alarm (id); bit 9 = Condenser overheating alarm (COH); bit 10 = Compressor blocked alarm (CSd); bit 11 = Defrost ended by timeout (dFd); bit 12 = Compressor thermal switch alarm (Cth); bit 13 = Real-time clock error (rtc) | |||
| HR | 1281doc 0501h (HR:1282) | On or standby | UINT16 | Read/write | 0 = Standby mode; 1 = On | ||||
| HR | 1282doc 0502h (HR:1283) | Light status | UINT16 | Read/write | 0 = Off; 1 = On | ||||
| HR | 1283doc 0503h (HR:1284) | Auxiliary status | UINT16 | Read/write | 0 = Off; 1 = On | ||||
| HR | 1284doc 0504h (HR:1285) | Heater status | UINT16 | Read/write | 0 = Off; 1 = On | ||||
| HR | 1368doc 0558h (HR:1369) | Setpoint | INT16 | × 0.1 | °C | Read | |||
| HR | 1537doc 0601h (HR:1538) | Setpoint (SP) | Range -99 to 199 °C. | INT16 | × 0.1 | °C | Read/write | ||
| HR | 1539doc 0603h (HR:1540) | Calibration Probe 1 (CA1) | Range -25 to 25 °C. | INT16 | × 0.1 | °C | Read/write | ||
| HR | 1540doc 0604h (HR:1541) | Calibration Probe 2 (CA2) | Range -25 to 25 °C. | INT16 | × 0.1 | °C | Read/write | ||
| HR | 1542doc 0606h (HR:1543) | Type of probe (P0) | UINT16 | Read/write | 0 = PTC; 1 = NTC | ||||
| HR | 1543doc 0607h (HR:1544) | Decimal point (P1) | UINT16 | Read/write | 0 = No; 1 = Yes | ||||
| HR | 1544doc 0608h (HR:1545) | Celsius or Fahrenheit (P2) | UINT16 | Read/write | 0 = °C; 1 = °F | ||||
| HR | 1545doc 0609h (HR:1546) | Second probe configuration (P4) | UINT16 | Read/write | 0 = Disabled; 1 = Defrost_Fan; 2 = Fan; 3 = Condenser | ||||
| HR | 1546doc 060Ah (HR:1547) | Value displayed in the main display (P5) | UINT16 | Read/write | 0 = Probe; 1 = Setpoint; 2 = Evaporator probe | ||||
| HR | 1548doc 060Ch (HR:1549) | Display refresh time (P8) | Printed range 0 to 250 in units of 1/10 sec. | UINT16 | × 0.1 | s | Read/write | ||
| HR | 1549doc 060Dh (HR:1550) | Setpoint differential (r0) | Range 0.1 to 15 °C. | INT16 | × 0.1 | °C | Read/write | ||
| HR | 1550doc 060Eh (HR:1551) | Minimum setpoint (r1) | Range -99 to 199 °C. | INT16 | × 0.1 | °C | Read/write | ||
| HR | 1551doc 060Fh (HR:1552) | Maximum setpoint (r2) | Range -99 to 199 °C. | INT16 | × 0.1 | °C | Read/write | ||
| HR | 1552doc 0610h (HR:1553) | Energy saving set point, relative (r4) | Range 0 to 99 °C. | INT16 | × 0.1 | °C | Read/write | ||
| HR | 1553doc 0611h (HR:1554) | Cooling or heating operaton (r5) | UINT16 | Read/write | 0 = Cooling; 1 = Heating | ||||
| HR | 1554doc 0612h (HR:1555) | Setpoint offset in overcooling or overheating (r6) | Range 0 to 99 °C. | INT16 | × 0.1 | °C | Read/write | ||
| HR | 1555doc 0613h (HR:1556) | Overcooling or overheating duration (r7) | Range 0 to 240 min. | UINT16 | min | Read/write | |||
| HR | 1556doc 0614h (HR:1557) | Down key configuration (r8) | UINT16 | Read/write | 0 = None; 1 = Overcooling or overheating; 2 = Energy saving | ||||
| HR | 1557doc 0615h (HR:1558) | r0 type (r12) | UINT16 | Read/write | 0 = asymmetric; 1 = symmetric | ||||
| HR | 1559doc 0617h (HR:1560) | Power-on delay (C0) | Range 0 to 240 min. | UINT16 | min | Read/write | |||
| HR | 1560doc 0618h (HR:1561) | Delay since last deactivation (C2) | Range 0 to 240 min. | UINT16 | min | Read/write | |||
| HR | 1561doc 0619h (HR:1562) | Minimum time compressor on (C3) | Range 0 to 240 s. | UINT16 | s | Read/write | |||
| HR | 1562doc 061Ah (HR:1563) | Time compressor turned off during probe failure (C4) | Range 0 to 240 min. | UINT16 | min | Read/write | |||
| HR | 1563doc 061Bh (HR:1564) | Time compressor turned on during probe failure (C5) | Range 0 to 240 min. | UINT16 | min | Read/write | |||
| HR | 1564doc 061Ch (HR:1565) | Set point for COH alarm (C6) | Range 0 to 199 °C. | INT16 | × 0.1 | °C | Read/write | ||
| HR | 1565doc 061Dh (HR:1566) | Set point for CSd alarm (C7) | Range 0 to 199 °C. | INT16 | × 0.1 | °C | Read/write | ||
| HR | 1566doc 061Eh (HR:1567) | CSd alarm delay (C8) | Range 0 to 15 min. | UINT16 | min | Read/write | |||
| HR | 1567doc 061Fh (HR:1568) | Compressor hours for service request (C10) | Printed range 0 to 999 in units of 100h. | UINT16 | × 100 | h | Read/write | ||
| HR | 1570doc 0622h (HR:1571) | Defrost lag (d0) | Range 0 to 99 h. | UINT16 | h | Read/write | |||
| HR | 1571doc 0623h (HR:1572) | Defrost type (d1) | UINT16 | Read/write | 0 = Heaters; 1 = Gas; 2 = Stop compressor | ||||
| HR | 1572doc 0624h (HR:1573) | Defrost cutoff temperature (d2) | Range -99 to 99 °C. | INT16 | × 0.1 | °C | Read/write | ||
| HR | 1573doc 0625h (HR:1574) | Defrost maximum time (d3) | Range 0 to 99 min. | UINT16 | min | Read/write | |||
| HR | 1574doc 0626h (HR:1575) | Defrost from power-on (d4) | UINT16 | Read/write | 0 = No; 1 = Yes | ||||
| HR | 1575doc 0627h (HR:1576) | Defrost delay from power-on (d5) | Range 0 to 99 min. | UINT16 | min | Read/write | |||
| HR | 1576doc 0628h (HR:1577) | Data displayed during defrost (d6) | UINT16 | Read/write | 0 = Probe; 1 = Limited in defrost; 2 = Label from the dEF parameter | ||||
| HR | 1577doc 0629h (HR:1578) | Dripping time (d7) | Range 0 to 15 min. | UINT16 | min | Read/write | |||
| HR | 1578doc 062Ah (HR:1579) | Type of defrost interval (d8) | UINT16 | Read/write | 0 = Time; 1 = Compressor hours; 2 = Threshold d9; 3 = Adaptive; 4 = Real time | ||||
| HR | 1579doc 062Bh (HR:1580) | Stop counter threshold (d9) | Range -99 to 99 °C. | INT16 | × 0.1 | °C | Read/write | ||
| HR | 1580doc 062Ch (HR:1581) | Enable defrost timeout alarm (d11) | UINT16 | Read/write | 0 = Disabled; 1 = Enabled | ||||
| HR | 1581doc 062Dh (HR:1582) | Minimum time compressor on for gas defrost (d15) | Range 0 to 99 min. | UINT16 | min | Read/write | |||
| HR | 1582doc 062Eh (HR:1583) | Pre-dripping time, defrost relay on (d16) | Range 0 to 99 min. | UINT16 | min | Read/write | |||
| HR | 1583doc 062Fh (HR:1584) | Time for adaptive defrost, d8=3 (d18) | Range 0 to 999 min. | UINT16 | min | Read/write | |||
| HR | 1584doc 0630h (HR:1585) | Temperature threshold for adaptive defrost, d8=3 (d19) | Range 0 to 40 °C. | INT16 | × 0.1 | °C | Read/write | ||
| HR | 1585doc 0631h (HR:1586) | Maximum time for safety defrost in normal operation (d20) | Range 0 to 999 min. | UINT16 | min | Read/write | |||
| HR | 1586doc 0632h (HR:1587) | Maximum time for safety defrost in pull down (d21) | Range 0 to 500 min. | UINT16 | min | Read/write | |||
| HR | 1587doc 0633h (HR:1588) | Evaporation threshold for adaptive defrost interval counting, relative to optimal evaporation temperature (d22) | Range -10 to 10 °C. | INT16 | × 0.1 | °C | Read/write | ||
| HR | 1588doc 0634h (HR:1589) | Alarm probe (AA) | UINT16 | Read/write | 0 = Cabinet probe; 1 = Second probe | ||||
| HR | 1589doc 0635h (HR:1590) | Minimum alarm threshold (A1) | Range -99 to 99 °C. | INT16 | × 0.1 | °C | Read/write | ||
| HR | 1590doc 0636h (HR:1591) | Minimum alarm type (A2) | UINT16 | Read/write | 0 = Disabled; 1 = Relative; 2 = Absolute | ||||
| HR | 1591doc 0637h (HR:1592) | Maximum alarm threshold (A4) | Range -99 to 99 °C. | INT16 | × 0.1 | °C | Read/write | ||
| HR | 1592doc 0638h (HR:1593) | Maximum alarm type (A5) | UINT16 | Read/write | 0 = Disabled; 1 = Relative; 2 = Absolute | ||||
| HR | 1593doc 0639h (HR:1594) | Alarm delay from power-on (A6) | Printed range 0 to 99 in units of 10 Minutes. | UINT16 | × 10 | min | Read/write | ||
| HR | 1594doc 063Ah (HR:1595) | Alarm delay (A7) | Range 0 to 240 min. | UINT16 | min | Read/write | |||
| HR | 1595doc 063Bh (HR:1596) | High temperature alarm delay after defrost (A8) | Range 0 to 240 min. | UINT16 | min | Read/write | |||
| HR | 1596doc 063Ch (HR:1597) | High temperature alarm delay after door closing (A9) | Range 0 to 240 min. | UINT16 | min | Read/write | |||
| HR | 1597doc 063Dh (HR:1598) | Minimum time for power failure alarm (A10) | Range 0 to 240 min. | UINT16 | min | Read/write | |||
| HR | 1598doc 063Eh (HR:1599) | Histeresys alarms regulator (A11) | Range 0.1 to 15 °C. | INT16 | × 0.1 | °C | Read/write | ||
| HR | 1599doc 063Fh (HR:1600) | High or low temperature alarms reset differential (A12) | UINT16 | Read/write | 0 = LED; 1 = LED, power failure label, and buzzer; 2 = LED and power failure label; buzzer if the duration is more than A10 | ||||
| HR | 1600doc 0640h (HR:1601) | Buzzer configuration (A13) | UINT16 | Read/write | 0 = Disabled; 1 = Enabled | ||||
| HR | 1601doc 0641h (HR:1602) | Fan activity during normal operation (F0) | UINT16 | Read/write | 0 = Off; 1 = On; 2 = Behaves according to F15 and F16 if compressor off; On if compressor on; 3 = Thermoregulated with F1; 4 = Thermoregulated with F1 if compressor on | ||||
| HR | 1602doc 0642h (HR:1603) | Fan setpoint (F1) | Range -99 to 99 °C. | INT16 | × 0.1 | °C | Read/write | ||
| HR | 1603doc 0643h (HR:1604) | Fan activity during defrost (F2) | UINT16 | Read/write | 0 = Off; 1 = On; 2 = F0 | ||||
| HR | 1604doc 0644h (HR:1605) | Fan-stop time (F3) | Range 0 to 15 min. | UINT16 | min | Read/write | |||
| HR | 1605doc 0645h (HR:1606) | Time evaporator fans off during energy saving (F4) | Printed range 0 to 240 in units of 10 s. | UINT16 | × 10 | s | Read/write | ||
| HR | 1606doc 0646h (HR:1607) | Time evaporator fans on during energy saving (F5) | Printed range 0 to 240 in units of 10 s. | UINT16 | × 10 | s | Read/write | ||
| HR | 1607doc 0647h (HR:1608) | Fan-stop temperature cutoff, relative (F7) | Range -99 to 99 °C. | INT16 | × 0.1 | °C | Read/write | ||
| HR | 1608doc 0648h (HR:1609) | Fan delay switching off (F9) | Range 0 to 240 s. | UINT16 | s | Read/write | |||
| HR | 1611doc 064Bh (HR:1612) | Time evaporator fans off with compressor off (F15) | Range 0 to 240 s. | UINT16 | s | Read/write | |||
| HR | 1612doc 064Ch (HR:1613) | Time evaporator fans on with compressor off (F16) | Range 0 to 240 s. | UINT16 | s | Read/write | |||
| HR | 1613doc 064Dh (HR:1614) | Digital input 1 action (i0) | UINT16 | Read/write | 0 = None; 1 = Compressor and evaporator fan off; 2 = Evaporator fan off; 3 = Cabinet light on; 4 = Compressor and evaporator fan off, cabinet light on; 5 = Evaporator fan off, cabinet light on; 6 = Reserved; 7 = Energy saving; 8 = Warning; 9 = Standby mode; 10 = Cth alarm; 11 = th alarm | ||||
| HR | 1614doc 064Eh (HR:1615) | Digital input 1 polarity (i1) | UINT16 | Read/write | 0 = Active contact closed; 1 = Active contact opened | ||||
| HR | 1615doc 064Fh (HR:1616) | Open door alarm delay (i2) | Range -1 to 120 min. | INT16 | min | Read/write | |||
| HR | 1616doc 0650h (HR:1617) | Maximum duration of door switch (i3) | Range -1 to 120 min. | INT16 | min | Read/write | |||
| HR | 1617doc 0651h (HR:1618) | Multifunction alarm delay (i7) | Range -1 to 120 min. | INT16 | min | Read/write | |||
| HR | 1618doc 0652h (HR:1619) | Duration with door closed before energy saving starts (i10) | Range 0 to 999 min. | UINT16 | min | Read/write | |||
| HR | 1619doc 0653h (HR:1620) | Number of door openings before safety defrost starts (i13) | Range 0 to 240. | UINT16 | Read/write | ||||
| HR | 1620doc 0654h (HR:1621) | Duration with door open before safety defrost starts (i14) | Range 0 to 240 min. | UINT16 | min | Read/write | |||
| HR | 1627doc 065Bh (HR:1628) | Energy saving maximum duration (HE2) | Range 0 to 999 min. | UINT16 | min | Read/write | |||
| HR | 1628doc 065Ch (HR:1629) | Energy saving time (H01) | Range 0 to 23 h. | UINT16 | h | Read/write | |||
| HR | 1629doc 065Dh (HR:1630) | Energy saving duration (H02) | Range 0 to 24 h. | UINT16 | h | Read/write | |||
| HR | 1630doc 065Eh (HR:1631) | Holiday (HEd) | UINT16 | Read/write | 0 = Monday; 1 = Tuesday; 2 = Wednesday; 3 = Thursday; 4 = Friday; 5 = Saturday; 6 = Sunday; 7 = None | ||||
| HR | 1631doc 065Fh (HR:1632) | Defrost 1 starting time (Hd1) | Range 0 to 24 h. | UINT16 | h | Read/write | |||
| HR | 1632doc 0660h (HR:1633) | Defrost 2 starting time (Hd2) | Range 0 to 24 h. | UINT16 | h | Read/write | |||
| HR | 1633doc 0661h (HR:1634) | Defrost 3 starting time (Hd3) | Range 0 to 24 h. | UINT16 | h | Read/write | |||
| HR | 1634doc 0662h (HR:1635) | Defrost 4 starting time (Hd4) | Range 0 to 24 h. | UINT16 | h | Read/write | |||
| HR | 1635doc 0663h (HR:1636) | Defrost 5 starting time (Hd5) | Range 0 to 24 h. | UINT16 | h | Read/write | |||
| HR | 1636doc 0664h (HR:1637) | Defrost 6 starting time (Hd6) | Range 0 to 24 h. | UINT16 | h | Read/write | |||
| HR | 1637doc 0665h (HR:1638) | Enable On/ standby key (POF) | UINT16 | Read/write | 0 = Disabled; 1 = Enabled | ||||
| HR | 1639doc 0667h (HR:1640) | RTC configuration (Hr0) | UINT16 | Read/write | 0 = Disabled; 1 = Enabled | ||||
| HR | 1640doc 0668h (HR:1641) | Address (LA) | Range 1 to 247. | UINT16 | Read/write | ||||
| HR | 1641doc 0669h (HR:1642) | Baud rate (Lb) | UINT16 | Read/write | 0 = 2400; 1 = 4800; 2 = 9600; 3 = 19200 | ||||
| HR | 10374doc 2886h (HR:10375) | Next defrost counter | Range 0 to 65535. | UINT16 | Read/write | ||||
| HR | 10416doc 28B0h (HR:10417) | Defrost command | UINT16 | Write | 12 = Stop defrost; 13 = Start defrost | ||||
| HR | 10436doc 28C4h (HR:10437) | Status flags HR:10437 | BITMAP16 | Read/write | bit 9 = Energy saving for door inactivity; bit 10 = Pull down done; bit 11 = Setpoint reached; bit 14 = Adaptive defrost calibration done | ||||
| HR | 10438doc 28C6h (HR:10439) | Status flags HR:10439 | BITMAP16 | Read/write | bit 1 = Energy saving; bit 10 = Service request; bit 12 = Overcooling | ||||
| HR | 10503doc 2907h (HR:10504) | Remote energy saving | UINT16 | Read/write | 0 = Inactive; 1 = Active | ||||
| HR | 65288doc FF08h (HR:65289) | Firmware identifier | UINT16 | Read | |||||
| HR | 65290doc FF0Ah (HR:65291) | Firmware program | UINT16 | Read |
Notes on this map
- Source is Johnson Controls' own documentation portal (PENN Controls); a PDF of the guide is attached there.
- '(0.1 resolution)' is taken as raw = value x 10 (scale 0.1); '1/10 sec', '10sec', '10 Minutes' and '100h' units are applied as multipliers 0.1 s, 10 s, 10 min and 100 h.
- Signedness is not stated. Temperatures and probe readings, and parameters whose range goes negative, are typed INT16; others UINT16.
- Temperatures follow parameter P2 (0 = °C, 1 = °F); units are shown as printed (°C).
- The guide's Maximum and Minimum columns are swapped in places; ranges here are written low to high.
- Bit points are grouped into one BITMAP16 per register (digital inputs, relay outputs, alarm flags, status flags). The status-flag registers mix read-only and read/write bits.
- Left out: Defrost phase (HR:1368 bits 8-11, a multi-bit field), Time to next defrost (HR:1370, 0.25 resolution but no unit) and Time to defrost end (HR:1371, no unit), the four-register real-time clock, the UI password, and the firmware revision/variation byte fields.
- Serial parity, stop bits and the factory address/baud are not stated; address (LA, 1-247) and baud (Lb, 2400-19200) are parameters in the list.
Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.
Questions about the Johnson Controls PENN TC3223 refrigeration temperature controller (Modbus RTU)
What Modbus registers does the Johnson Controls PENN TC3223 refrigeration temperature controller (Modbus RTU) have?
This map lists 107 registers: 107 holding registers. 99 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.
Are the Johnson Controls PENN TC3223 refrigeration temperature controller (Modbus RTU) Modbus addresses 0-based or 1-based?
The manufacturer's document numbers registers hexadecimal, 0-based. Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. The guide prints every point twice: a hex 'Base 0' address (0201h) and a decimal 'Base 1' holding-register number (HR:514). The wire address is the Base 0 value (0x0201 = 513 = HR:514 - 1). Bit points are given as register.BitN.
What are the minimum Modbus registers to integrate the Johnson Controls PENN TC3223 refrigeration temperature controller (Modbus RTU)?
Start with HR 513 Probe 1 (Cabinet probe temperature); HR 1537 Setpoint (SP) (Control setpoint); HR 1281 On or standby (Run / standby command); HR 385 Digital outputs (Relay output states); HR 769 Alarm flags (Alarm and probe-failure flags); HR 10416 Defrost command (Start/stop a defrost (0Dh/0Ch)); HR 1544 Celsius or Fahrenheit (P2) (Temperature unit).
How do I enable Modbus control of the Johnson Controls PENN TC3223 refrigeration temperature controller (Modbus RTU)?
Modbus RTU is built in; set the Modbus address (LA) and baud rate (Lb) parameters at the controller.
Where is the official Johnson Controls PENN TC3223 refrigeration temperature controller (Modbus RTU) Modbus documentation?
The source is TC3 Modbus Protocol Reference Guide (TC3221, TC3222, TC3223, TC3224N9R) (LIT-12013523), revision 2020-04-28, published free by Johnson Controls at https://docs.johnsoncontrols.com/bas/r/PENN-Controls/en-US/TC3-Modbus-Protocol-Reference-Guide.
More Johnson Controls Modbus register maps
- Sensor
Johnson Controls GS3000 indoor Modbus carbon monoxide transmitter
Johnson Controls GS3000 / GS3001 electrochemical CO transmitters with RS-485 Modbus RTU, per installation guide 24-11484-00021 (2020-10-01).
Also known as: GS3000, GS3001, 24-11484-00021 - Thermostat
Johnson Controls PENN System 450 with C450CRN-1 Modbus communications control module
PENN System 450 modular temperature, pressure and humidity control systems built around a C450CRN-1 Modbus RTU control module (up to 3 sensors and 10 relay/analog outputs), per LIT-12011826 (2021-01-14).
Also known as: C450CRN-1, C450CRN, System 450, PENN System 450, LIT-12011826 - Thermostat
Johnson Controls PENN TC3221 refrigeration temperature controller (Modbus RTU)
PENN TC3221 electronic refrigeration controller with built-in Modbus RTU, per the TC3 Modbus Protocol Reference Guide LIT-12013523 (2020-04-28).
Also known as: TC3221, TC3, PENN TC3, LIT-12013523 - Thermostat
Johnson Controls PENN TC3222 refrigeration temperature controller (Modbus RTU)
PENN TC3222 electronic refrigeration controller with built-in Modbus RTU, per the TC3 Modbus Protocol Reference Guide LIT-12013523 (2020-04-28).
Also known as: TC3222, TC3, PENN TC3, LIT-12013523 - Thermostat
Johnson Controls PENN TC3224N9V refrigeration temperature controller (Modbus RTU)
PENN TC3224N9V electronic refrigeration controller with built-in Modbus RTU, per the TC3 Modbus Protocol Reference Guide LIT-12013523 (2020-04-28).
Also known as: TC3224N9V, TC3, PENN TC3, LIT-12013523, TC3224N9R, TC3224 - Thermostat (fan coil)
Johnson Controls T7000 series fan coil thermostat (Modbus RTU)
Johnson Controls T7000 series Modbus thermostats listed in the data table: T7600-TF21, T7601-TF20 (ECM fan), T7600-TF20 (relay), T7603-T000 (single-stage heating) and T7600-TB21 (with AI); data table revision 2.4 (2019-12-23).
Also known as: T7600-TF21-9JS0, T7601-TF20-9JS0, T7600-TF20-9JS0, T7603-T000-9JF0, T7600-TF21-1JS0, T7601-TF20-1JS0, T7600-TF20-1JS0, T7603-T000-1JF0, T7600-TB21-9JA0, T7600, T7601, T7603 - Variable frequency drive
Johnson Controls VFD68 variable frequency drive (VFD68Bxx / VFD68Cxx, Modbus RTU)
Johnson Controls / PENN VFD68Bxx (200-240 V) and VFD68Cxx (380-480 V) drives on their RJ45 PU port with Modbus RTU selected (P.549 = 1), per the VFD68 Variable Frequency Drives Technical Bulletin, Appendix 4.
Also known as: VFD68Bxx, VFD68Cxx, VFD68BDC-2C, VFD68CDF-2C, PENN VFD68
Other hvac equipment register maps
- Air handler (computer room air conditioner)
Mitsubishi Electric s-MEXT-G00 computer room air conditioner (ME28 relC)
Mitsubishi Electric (Hydronics & IT Cooling) s-MEXT-G00 006-044 close-control units with ME28-relC software and the Modbus serial board.
Also known as: s-MEXT, s-MEXT-G00 006-044, s-MEXT G00, ME28 relC - Air handler humidifier (gas-fired steam)
Neptronic SKG4 gas-fired steam humidifier (Modbus communication module)
Neptronic SKG4 series gas-fired steam humidifiers (one to four burner modules) with the Modbus communication module, guide SKG4-Modbus Guide-221114 (V2.04).
Also known as: SKG4-E, SKG4-N, SKG4 Gas Fired Humidifier, Neptronic SKG4 Modbus - Air handler controller
Regin Corrigo ventilation controller (ventilation application 3.6)
Regin Corrigo controllers running the pre-programmed ventilation (air handling unit) application, version 3.6 or later; not the heating or Exigo applications.
Also known as: Corrigo E, Corrigo ventilation, Corrigo E ventilation, Corrigo AHU controller - Air handler (heat recovery unit controller)
Swegon TAC5 DG/DM/DT controller (Global HRglobal, HRup, HRflat, HRtotal, HRmural)
Swegon (Global) TAC5 DG, DM and DT regulation boards with the SAT MODBUS (RTU) or SAT WIFI/ETHERNET (TCP) satellite; TAC5 + MODBUS TABLE Cid 050338 (2021-09-20). The TAC5 SC/F single-flow boards use other registers and are not covered.
Also known as: TAC5 DG, TAC5 DM, TAC5 DT, Global HRglobal, Global HRup, Global HRflat, Global HRtotal, Global HRmural, SAT MODBUS - Thermostat / temperature controller
Watlow EZ-ZONE PM PID / limit / integrated controller (Modbus RTU)
Watlow EZ-ZONE PM panel-mount controllers (PID, limit and integrated models) with Modbus RTU, per communications manual 0600-0056-0000 Rev. B (Nov 2007).
Also known as: EZ-ZONE PM, EZ-ZONE PM Limit, EZ-ZONE PM Integrated - Air handler humidifier (hybrid / spray)
Condair DL II hybrid humidifier (Integrated Controller, Modbus RTU/TCP)
Condair DL with the Integrated Controller, per addendum 2603326-G.
Also known as: Condair DL, Condair DL II, DL
All hvac equipment Modbus register maps →
Source: TC3 Modbus Protocol Reference Guide (TC3221, TC3222, TC3223, TC3224N9R) · LIT-12013523 · rev. 2020-04-28. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.