Johnson Controls T7000 series fan coil thermostat (Modbus RTU) Modbus register map

Updated 19 November 2026

Short answer

The T7000 is a Johnson Controls room thermostat family for 2- and 4-pipe fan coil units (plus floor-heating, TiO2/ESP and single-stage heating variants) with a Modbus RTU port. Relays read as coils, live values as input registers, and power, mode, setpoint, fan speed and all settings as holding registers. Temperatures are stored as tenths of a degree.

This page lists 45 Modbus registers for the Johnson Controls T7000 series fan coil thermostat (Modbus RTU) — 31 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Johnson Controls’s own free documentation (linked below) and checked against it.

Manufacturer
Johnson Controls
Model
T7000 series fan coil thermostat (Modbus RTU)
Equipment type
Thermostat (fan coil)
Registers
45 (31 writable)
Transport
Modbus RTU
Default unit ID
Not stated
Default serial
8N1
Documented addressing
1-based (subtract 1 for the wire address)
Also known as
T7600-TF21-9JS0, T7601-TF20-9JS0, T7600-TF20-9JS0, T7603-T000-9JF0, T7600-TF21-1JS0, T7601-TF20-1JS0, T7600-TF20-1JS0, T7603-T000-1JF0, T7600-TB21-9JA0, T7600, T7601, T7603
Source document
T7000 Thermostat Modbus Data Table · Revision 2.4 · rev. 2019-12-23
Download CSV all columns JSON Manufacturer PDF ↗

Integration notes: Johnson Controls T7000 series fan coil thermostat (Modbus RTU)

Integration in brief

Poll input register 2 (room temperature x10) and holding registers 5-8 for power, mode, setpoint and fan speed; write those holding registers with function 06 to control the fan coil.

Minimum registers to map

Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.

RegisterNameTypeWhyAccess
IR 1Room temperatureUINT16Room temperature x10Read
HR 4PowerUINT16Power on/offRead/write
HR 5ModeUINT16ModeRead/write
HR 6SetpointUINT16Setpoint x10Read/write
HR 7Fan speedUINT16Fan speedRead/write
IR 3ErrorUINT16Error codeRead
CO 2Relay 1BITRelay 1 (fan low on most applications)Read

Enable Modbus control & writes

Set the Modbus address (1-64) and baud rate on the thermostat; no separate enable is described.

Byte order & addressing

Network setup

Watch out for

Johnson Controls T7000 series fan coil thermostat (Modbus RTU) Modbus registers

Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.

45 of 45 shown
Johnson Controls T7000 series fan coil thermostat (Modbus RTU) Modbus register map
TableAddressNameDescriptionTypeOrderScaleUnitsAccessValues / bits
CO0doc 1Relay 4BITRead0 = Off; 1 = On
CO1doc 2Relay 5BITRead0 = Off; 1 = On
CO2doc 3Relay 1BITRead0 = Off; 1 = On
CO3doc 4Relay 2BITRead0 = Off; 1 = On
CO4doc 5Relay 3BITRead0 = Off; 1 = On
IR0doc 1Model + applicationHigh byte = model number, low byte = application.UINT16Read
IR1doc 2Room temperatureTemperature x10 (26.5 °C = 265).UINT16× 0.1°CRead
IR2doc 3Occupancy statusUINT16Read0 = Unoccupied; 1 = Occupied
IR3doc 4ErrorUINT16Read1 = Internal sensor shorted; 2 = Internal sensor open; 3 = High temperature (room above 55 °C); 4 = Low temperature (room below 0 °C); 5 = Remote sensor shorted; 6 = Remote sensor open; 7 = Dew risk
HR0doc 1Model + applicationHigh byte = model number, low byte = application.UINT16Read
HR1doc 2Room temperatureTemperature x10 (26.5 °C = 265).UINT16× 0.1°CRead
HR2doc 3Occupancy statusUINT16Read0 = Unoccupied; 1 = Occupied
HR3doc 4ErrorUINT16Read1 = Internal sensor shorted; 2 = Internal sensor open; 3 = High temperature (room above 55 °C); 4 = Low temperature (room below 0 °C); 5 = Remote sensor shorted; 6 = Remote sensor open; 7 = Dew risk
HR4doc 5PowerUINT16Read/write0 = Off; 1 = On
HR5doc 6ModeUINT16Read/write0 = Cooling; 1 = Heating; 2 = Ventilation
HR6doc 7SetpointRange 0-40 °C, x10.UINT16× 0.1°CRead/write
HR7doc 8Fan speedNot on T7600-TB21-..JA0.UINT16Read/write0 = Low; 1 = Medium; 2 = High; 3 = Auto
HR8doc 9Upper setpoint limitRange 2-40 °C, x10.UINT16× 0.1°CRead/write
HR9doc 10Lower setpoint limitRange 0-38 °C, x10.UINT16× 0.1°CRead/write
HR10doc 11Unoccupied cooling setpointRange 22-32 °C, x10. Not on T7603.UINT16× 0.1°CRead/write
HR11doc 12Unoccupied heating setpointRange 10-21 °C, x10.UINT16× 0.1°CRead/write
HR12doc 13Frost protectionNote the inverted coding: 0 = on.UINT16Read/write0 = On; 1 = Off
HR13doc 14Frost protection setpointRange 0-20 °C, x10.UINT16× 0.1°CRead/write
HR14doc 15Fan in deadbandNot on T7603.UINT16Read/write0 = Off; 1 = Low
HR15doc 16Unoccupied fan speedNot on T7603.UINT16Read/write0 = Low; 1 = Set speed
HR16doc 17Power recovery after restartUINT16Read/write0 = Keep last status; 1 = On; 2 = Off
HR17doc 18Key lockUINT16Read/write0 = No lock; 1 = Lock all keys; 2 = Lock all but fan speed and temperature keys; 3 = Lock the ON/OFF and clock keys; 4 = Lock all but the ON/OFF key
HR18doc 19Screen displayUINT16Read/write0 = Room temperature; 1 = Setpoint
HR19doc 20BI functionMeaning of the binary input contact.UINT16Read/write0 = Key card, open = occupied; 1 = Key card, closed = occupied; 2 = Dew point risk when closed; 3 = Dew point risk when open; 4 = Open = occupied; closed = unoccupied, fan and valve off; 5 = Filter alarm when closed; 6 = Filter alarm when open
HR20doc 21Temperature unitUINT16Read/write0 = Celsius; 1 = Fahrenheit
HR22doc 23Fan speed limitNot on T7603.UINT16Read/write0 = 3 speed; 1 = 2 speed; 2 = 1 speed; 3 = No fan
HR23doc 24LanguageUINT16Read/write0 = Chinese; 1 = English
HR24doc 25Mode selectionNot on T7603.UINT16Read/write0 = Cooling/heating/ventilation; 1 = Cooling only; 2 = Heating only
HR25doc 26LCD backlight timeBacklight turns off after this many idle seconds (5-60).UINT16sRead/write
HR27doc 28Remote sensor typeUINT16Read/write0 = China market 10K NTC; 1 = JCI type II 10K NTC
HR28doc 29DeadbandRange 0-10 °C, x10.UINT16× 0.1°CRead/write
HR29doc 30Auto changeoverNot on T7603.UINT16Read/write0 = Disable; 1 = Enable
HR30doc 31ECM fan minimum voltageT7601-TF20 only. 0-10 V in 0.5 V steps, x10.UINT16× 0.1VRead/write
HR31doc 32ECM fan maximum voltageT7601-TF20 only. 0-10 V, x10.UINT16× 0.1VRead/write
HR32doc 33ECM relayT7601-TF20 only.UINT16Read/write0 = Disable; 1 = Enable
HR36doc 37Floor heater inter-stage differenceT7600-TF20 / T7601-TF20 only. 0-10 °C, x10.UINT16× 0.1°CRead/write
HR37doc 38Floor heater heating stagesT7600-TF20 / T7601-TF20 only.UINT16Read/write0 = Two stage; 1 = One stage
HR38doc 39TiO2/ESP controlT7600-TF20 / T7601-TF20 only.UINT16Read/write0 = Controlled separately; 1 = Runs with the FCU
HR42doc 43TiO2/ESP relayUINT16Read/write0 = Off; 1 = On
HR43doc 44AO1 outputPWM duty 0-100 %. T7600-TF21, T7601-TF20, T7600-TB21 only.UINT16%Read

Notes on this map

Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.

Questions about the Johnson Controls T7000 series fan coil thermostat (Modbus RTU)

What Modbus registers does the Johnson Controls T7000 series fan coil thermostat (Modbus RTU) have?

This map lists 45 registers: 5 coils, 4 input registers, 36 holding registers. 31 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.

Are the Johnson Controls T7000 series fan coil thermostat (Modbus RTU) Modbus addresses 0-based or 1-based?

The manufacturer's document numbers registers 1-based (subtract 1 for the wire address). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. The table numbers points from 1. The demo frames settle it: reading room temperature (address 2) sends start address 00 01, and powering on (address 5) writes to 00 04, so wire address = listed address - 1.

What are the minimum Modbus registers to integrate the Johnson Controls T7000 series fan coil thermostat (Modbus RTU)?

Start with IR 1 Room temperature (Room temperature x10); HR 4 Power (Power on/off); HR 5 Mode (Mode); HR 6 Setpoint (Setpoint x10); HR 7 Fan speed (Fan speed); IR 3 Error (Error code); CO 2 Relay 1 (Relay 1 (fan low on most applications)).

How do I enable Modbus control of the Johnson Controls T7000 series fan coil thermostat (Modbus RTU)?

Set the Modbus address (1-64) and baud rate on the thermostat; no separate enable is described.

Where is the official Johnson Controls T7000 series fan coil thermostat (Modbus RTU) Modbus documentation?

The source is T7000 Thermostat Modbus Data Table (Revision 2.4), revision 2019-12-23, published free by Johnson Controls at https://docs.johnsoncontrols.com/bas/api/khub/documents/hw6JWFAKzTKFpujvU7eW7g/content.

More Johnson Controls Modbus register maps

Other hvac equipment register maps

All hvac equipment Modbus register maps →

Source: T7000 Thermostat Modbus Data Table · Revision 2.4 · rev. 2019-12-23. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.