Johnson Controls T7000 series fan coil thermostat (Modbus RTU) Modbus register map
Updated 19 November 2026
The T7000 is a Johnson Controls room thermostat family for 2- and 4-pipe fan coil units (plus floor-heating, TiO2/ESP and single-stage heating variants) with a Modbus RTU port. Relays read as coils, live values as input registers, and power, mode, setpoint, fan speed and all settings as holding registers. Temperatures are stored as tenths of a degree.
This page lists 45 Modbus registers for the Johnson Controls T7000 series fan coil thermostat (Modbus RTU) — 31 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Johnson Controls’s own free documentation (linked below) and checked against it.
- Manufacturer
- Johnson Controls
- Model
- T7000 series fan coil thermostat (Modbus RTU)
- Equipment type
- Thermostat (fan coil)
- Registers
- 45 (31 writable)
- Transport
- Modbus RTU
- Default unit ID
- Not stated
- Default serial
- 8N1
- Documented addressing
- 1-based (subtract 1 for the wire address)
- Also known as
- T7600-TF21-9JS0, T7601-TF20-9JS0, T7600-TF20-9JS0, T7603-T000-9JF0, T7600-TF21-1JS0, T7601-TF20-1JS0, T7600-TF20-1JS0, T7603-T000-1JF0, T7600-TB21-9JA0, T7600, T7601, T7603
Integration notes: Johnson Controls T7000 series fan coil thermostat (Modbus RTU)
Poll input register 2 (room temperature x10) and holding registers 5-8 for power, mode, setpoint and fan speed; write those holding registers with function 06 to control the fan coil.
Minimum registers to map
Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.
| Register | Name | Type | Why | Access |
|---|---|---|---|---|
| IR 1 | Room temperature | UINT16 | Room temperature x10 | Read |
| HR 4 | Power | UINT16 | Power on/off | Read/write |
| HR 5 | Mode | UINT16 | Mode | Read/write |
| HR 6 | Setpoint | UINT16 | Setpoint x10 | Read/write |
| HR 7 | Fan speed | UINT16 | Fan speed | Read/write |
| IR 3 | Error | UINT16 | Error code | Read |
| CO 2 | Relay 1 | BIT | Relay 1 (fan low on most applications) | Read |
Enable Modbus control & writes
Set the Modbus address (1-64) and baud rate on the thermostat; no separate enable is described.
Byte order & addressing
- Listed address minus 1 = wire address, confirmed by the demo frames.
- Frost protection uses 0 = on, 1 = off.
- Coils 1-2 are relays 4-5 and coils 3-5 are relays 1-3.
Network setup
- RS-485 half duplex, A(+) and B(-).
- 8 data bits, no parity, 1 stop bit; 9600 or 4800 baud.
Watch out for
- The application and model set which relays drive fan, valve, floor heater or TiO2/ESP; check the output mapping table.
- Fahrenheit mode (register 21) changes the display unit; the table only documents Celsius scaling.
Johnson Controls T7000 series fan coil thermostat (Modbus RTU) Modbus registers
Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.
| Table | Address | Name | Description | Type | Order | Scale | Units | Access | Values / bits |
|---|---|---|---|---|---|---|---|---|---|
| CO | 0doc 1 | Relay 4 | BIT | Read | 0 = Off; 1 = On | ||||
| CO | 1doc 2 | Relay 5 | BIT | Read | 0 = Off; 1 = On | ||||
| CO | 2doc 3 | Relay 1 | BIT | Read | 0 = Off; 1 = On | ||||
| CO | 3doc 4 | Relay 2 | BIT | Read | 0 = Off; 1 = On | ||||
| CO | 4doc 5 | Relay 3 | BIT | Read | 0 = Off; 1 = On | ||||
| IR | 0doc 1 | Model + application | High byte = model number, low byte = application. | UINT16 | Read | ||||
| IR | 1doc 2 | Room temperature | Temperature x10 (26.5 °C = 265). | UINT16 | × 0.1 | °C | Read | ||
| IR | 2doc 3 | Occupancy status | UINT16 | Read | 0 = Unoccupied; 1 = Occupied | ||||
| IR | 3doc 4 | Error | UINT16 | Read | 1 = Internal sensor shorted; 2 = Internal sensor open; 3 = High temperature (room above 55 °C); 4 = Low temperature (room below 0 °C); 5 = Remote sensor shorted; 6 = Remote sensor open; 7 = Dew risk | ||||
| HR | 0doc 1 | Model + application | High byte = model number, low byte = application. | UINT16 | Read | ||||
| HR | 1doc 2 | Room temperature | Temperature x10 (26.5 °C = 265). | UINT16 | × 0.1 | °C | Read | ||
| HR | 2doc 3 | Occupancy status | UINT16 | Read | 0 = Unoccupied; 1 = Occupied | ||||
| HR | 3doc 4 | Error | UINT16 | Read | 1 = Internal sensor shorted; 2 = Internal sensor open; 3 = High temperature (room above 55 °C); 4 = Low temperature (room below 0 °C); 5 = Remote sensor shorted; 6 = Remote sensor open; 7 = Dew risk | ||||
| HR | 4doc 5 | Power | UINT16 | Read/write | 0 = Off; 1 = On | ||||
| HR | 5doc 6 | Mode | UINT16 | Read/write | 0 = Cooling; 1 = Heating; 2 = Ventilation | ||||
| HR | 6doc 7 | Setpoint | Range 0-40 °C, x10. | UINT16 | × 0.1 | °C | Read/write | ||
| HR | 7doc 8 | Fan speed | Not on T7600-TB21-..JA0. | UINT16 | Read/write | 0 = Low; 1 = Medium; 2 = High; 3 = Auto | |||
| HR | 8doc 9 | Upper setpoint limit | Range 2-40 °C, x10. | UINT16 | × 0.1 | °C | Read/write | ||
| HR | 9doc 10 | Lower setpoint limit | Range 0-38 °C, x10. | UINT16 | × 0.1 | °C | Read/write | ||
| HR | 10doc 11 | Unoccupied cooling setpoint | Range 22-32 °C, x10. Not on T7603. | UINT16 | × 0.1 | °C | Read/write | ||
| HR | 11doc 12 | Unoccupied heating setpoint | Range 10-21 °C, x10. | UINT16 | × 0.1 | °C | Read/write | ||
| HR | 12doc 13 | Frost protection | Note the inverted coding: 0 = on. | UINT16 | Read/write | 0 = On; 1 = Off | |||
| HR | 13doc 14 | Frost protection setpoint | Range 0-20 °C, x10. | UINT16 | × 0.1 | °C | Read/write | ||
| HR | 14doc 15 | Fan in deadband | Not on T7603. | UINT16 | Read/write | 0 = Off; 1 = Low | |||
| HR | 15doc 16 | Unoccupied fan speed | Not on T7603. | UINT16 | Read/write | 0 = Low; 1 = Set speed | |||
| HR | 16doc 17 | Power recovery after restart | UINT16 | Read/write | 0 = Keep last status; 1 = On; 2 = Off | ||||
| HR | 17doc 18 | Key lock | UINT16 | Read/write | 0 = No lock; 1 = Lock all keys; 2 = Lock all but fan speed and temperature keys; 3 = Lock the ON/OFF and clock keys; 4 = Lock all but the ON/OFF key | ||||
| HR | 18doc 19 | Screen display | UINT16 | Read/write | 0 = Room temperature; 1 = Setpoint | ||||
| HR | 19doc 20 | BI function | Meaning of the binary input contact. | UINT16 | Read/write | 0 = Key card, open = occupied; 1 = Key card, closed = occupied; 2 = Dew point risk when closed; 3 = Dew point risk when open; 4 = Open = occupied; closed = unoccupied, fan and valve off; 5 = Filter alarm when closed; 6 = Filter alarm when open | |||
| HR | 20doc 21 | Temperature unit | UINT16 | Read/write | 0 = Celsius; 1 = Fahrenheit | ||||
| HR | 22doc 23 | Fan speed limit | Not on T7603. | UINT16 | Read/write | 0 = 3 speed; 1 = 2 speed; 2 = 1 speed; 3 = No fan | |||
| HR | 23doc 24 | Language | UINT16 | Read/write | 0 = Chinese; 1 = English | ||||
| HR | 24doc 25 | Mode selection | Not on T7603. | UINT16 | Read/write | 0 = Cooling/heating/ventilation; 1 = Cooling only; 2 = Heating only | |||
| HR | 25doc 26 | LCD backlight time | Backlight turns off after this many idle seconds (5-60). | UINT16 | s | Read/write | |||
| HR | 27doc 28 | Remote sensor type | UINT16 | Read/write | 0 = China market 10K NTC; 1 = JCI type II 10K NTC | ||||
| HR | 28doc 29 | Deadband | Range 0-10 °C, x10. | UINT16 | × 0.1 | °C | Read/write | ||
| HR | 29doc 30 | Auto changeover | Not on T7603. | UINT16 | Read/write | 0 = Disable; 1 = Enable | |||
| HR | 30doc 31 | ECM fan minimum voltage | T7601-TF20 only. 0-10 V in 0.5 V steps, x10. | UINT16 | × 0.1 | V | Read/write | ||
| HR | 31doc 32 | ECM fan maximum voltage | T7601-TF20 only. 0-10 V, x10. | UINT16 | × 0.1 | V | Read/write | ||
| HR | 32doc 33 | ECM relay | T7601-TF20 only. | UINT16 | Read/write | 0 = Disable; 1 = Enable | |||
| HR | 36doc 37 | Floor heater inter-stage difference | T7600-TF20 / T7601-TF20 only. 0-10 °C, x10. | UINT16 | × 0.1 | °C | Read/write | ||
| HR | 37doc 38 | Floor heater heating stages | T7600-TF20 / T7601-TF20 only. | UINT16 | Read/write | 0 = Two stage; 1 = One stage | |||
| HR | 38doc 39 | TiO2/ESP control | T7600-TF20 / T7601-TF20 only. | UINT16 | Read/write | 0 = Controlled separately; 1 = Runs with the FCU | |||
| HR | 42doc 43 | TiO2/ESP relay | UINT16 | Read/write | 0 = Off; 1 = On | ||||
| HR | 43doc 44 | AO1 output | PWM duty 0-100 %. T7600-TF21, T7601-TF20, T7600-TB21 only. | UINT16 | % | Read |
Notes on this map
- Supported functions 01, 03, 04, 06 and 16. Holding registers 1-4 repeat input registers 1-4.
- All temperatures are x10 (26.5 °C is stored as 265).
- Left out: sample time, P and I (registers 34-36) and AO2/AI (45), whose footnote says they are x10 values while their printed ranges read like plain integers; the sensor offset (22), because its -5 to 5 °C range needs a signed encoding the table never states; register 27 was deleted in revision 2.2.
- Many registers apply only to some models (marked in descriptions). Relay roles per model/application are in the output mapping table of the source.
- Address range 1-64; baud 9600 or 4800 (the table does not say which is the default); 8 data bits, no parity, 1 stop bit.
Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.
Questions about the Johnson Controls T7000 series fan coil thermostat (Modbus RTU)
What Modbus registers does the Johnson Controls T7000 series fan coil thermostat (Modbus RTU) have?
This map lists 45 registers: 5 coils, 4 input registers, 36 holding registers. 31 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.
Are the Johnson Controls T7000 series fan coil thermostat (Modbus RTU) Modbus addresses 0-based or 1-based?
The manufacturer's document numbers registers 1-based (subtract 1 for the wire address). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. The table numbers points from 1. The demo frames settle it: reading room temperature (address 2) sends start address 00 01, and powering on (address 5) writes to 00 04, so wire address = listed address - 1.
What are the minimum Modbus registers to integrate the Johnson Controls T7000 series fan coil thermostat (Modbus RTU)?
Start with IR 1 Room temperature (Room temperature x10); HR 4 Power (Power on/off); HR 5 Mode (Mode); HR 6 Setpoint (Setpoint x10); HR 7 Fan speed (Fan speed); IR 3 Error (Error code); CO 2 Relay 1 (Relay 1 (fan low on most applications)).
How do I enable Modbus control of the Johnson Controls T7000 series fan coil thermostat (Modbus RTU)?
Set the Modbus address (1-64) and baud rate on the thermostat; no separate enable is described.
Where is the official Johnson Controls T7000 series fan coil thermostat (Modbus RTU) Modbus documentation?
The source is T7000 Thermostat Modbus Data Table (Revision 2.4), revision 2019-12-23, published free by Johnson Controls at https://docs.johnsoncontrols.com/bas/api/khub/documents/hw6JWFAKzTKFpujvU7eW7g/content.
More Johnson Controls Modbus register maps
- Sensor
Johnson Controls GS3000 indoor Modbus carbon monoxide transmitter
Johnson Controls GS3000 / GS3001 electrochemical CO transmitters with RS-485 Modbus RTU, per installation guide 24-11484-00021 (2020-10-01).
Also known as: GS3000, GS3001, 24-11484-00021 - Thermostat
Johnson Controls PENN System 450 with C450CRN-1 Modbus communications control module
PENN System 450 modular temperature, pressure and humidity control systems built around a C450CRN-1 Modbus RTU control module (up to 3 sensors and 10 relay/analog outputs), per LIT-12011826 (2021-01-14).
Also known as: C450CRN-1, C450CRN, System 450, PENN System 450, LIT-12011826 - Thermostat
Johnson Controls PENN TC3221 refrigeration temperature controller (Modbus RTU)
PENN TC3221 electronic refrigeration controller with built-in Modbus RTU, per the TC3 Modbus Protocol Reference Guide LIT-12013523 (2020-04-28).
Also known as: TC3221, TC3, PENN TC3, LIT-12013523 - Thermostat
Johnson Controls PENN TC3222 refrigeration temperature controller (Modbus RTU)
PENN TC3222 electronic refrigeration controller with built-in Modbus RTU, per the TC3 Modbus Protocol Reference Guide LIT-12013523 (2020-04-28).
Also known as: TC3222, TC3, PENN TC3, LIT-12013523 - Thermostat
Johnson Controls PENN TC3223 refrigeration temperature controller (Modbus RTU)
PENN TC3223 electronic refrigeration controller with built-in Modbus RTU, per the TC3 Modbus Protocol Reference Guide LIT-12013523 (2020-04-28).
Also known as: TC3223, TC3, PENN TC3, LIT-12013523 - Thermostat
Johnson Controls PENN TC3224N9V refrigeration temperature controller (Modbus RTU)
PENN TC3224N9V electronic refrigeration controller with built-in Modbus RTU, per the TC3 Modbus Protocol Reference Guide LIT-12013523 (2020-04-28).
Also known as: TC3224N9V, TC3, PENN TC3, LIT-12013523, TC3224N9R, TC3224 - Variable frequency drive
Johnson Controls VFD68 variable frequency drive (VFD68Bxx / VFD68Cxx, Modbus RTU)
Johnson Controls / PENN VFD68Bxx (200-240 V) and VFD68Cxx (380-480 V) drives on their RJ45 PU port with Modbus RTU selected (P.549 = 1), per the VFD68 Variable Frequency Drives Technical Bulletin, Appendix 4.
Also known as: VFD68Bxx, VFD68Cxx, VFD68BDC-2C, VFD68CDF-2C, PENN VFD68
Other hvac equipment register maps
- Air handler (compact make-up air unit)
Neptronic CMU compact make-up air unit (Modbus communication module)
Neptronic CMU compact make-up air units with the Modbus communication module, guide CMU-Modbus Guide-211125.
Also known as: Compact Make-up Air Unit, Neptronic CMU, CMU Series - Air handler humidifier (steam-to-steam)
Neptronic SKS4 steam-to-steam humidifier (Modbus communication module)
Neptronic SKS4 series steam-to-steam humidifiers with the Modbus communication module, guide SKS4-Modbus Guide-220509 (V2.03).
Also known as: SKS4-E, SKS4-N, SKS4 Steam to Steam Humidifier, Neptronic SKS4 Modbus - Thermostat
Smart Temp SMT-770 thermostat with EC-02 module (Modbus RTU)
SMT-770 thermostat (with or without a paired EC-02 module), communications addendum v4.6 for firmware 2.31.
Also known as: SMT-770 Chameleon, EC-02, SMT770 - Sensor (HVAC humidity, temperature and CO2 transmitter)
Vaisala Origo10 transmitters for HVAC (Origo10A, Modbus RTU)
Origo10A duct and wall transmitters ordered with the Modbus RTU output (user guide M213293EN-B). Origo10L has no Modbus.
Also known as: Origo10, Origo10A, Origo 10, Vaisala Origo10 duct transmitter, Vaisala Origo10 wall transmitter - Air handler (in-row chilled-water cooling unit)
APC (Schneider Electric) InRow ACRC30x chilled-water cooling unit (300 mm)
APC by Schneider Electric InRow ACRC30x (300 mm chilled water) units, per register map part number 990-4742B.
Also known as: ACRC30x, ACRC300, ACRC301, InRow RC 300 mm - Air handler humidifier (resistive steam)
Condair RS II resistive steam humidifier (Integrated Controller, Modbus RTU/TCP)
Condair RS with the Integrated Controller (cylinders A and B), per addendum 2603326-G.
Also known as: Condair RS, Condair RS II, RS
All hvac equipment Modbus register maps →
Source: T7000 Thermostat Modbus Data Table · Revision 2.4 · rev. 2019-12-23. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.