Easy Modbus
  1. Home
  2. Modbus register maps
  3. Johnson Controls
  4. PENN TC3221 refrigeration temperature controller (Modbus RTU)

Thermostat · Modbus register map

Johnson Controls PENN TC3221 refrigeration temperature controller (Modbus RTU) Modbus register map

Updated 17 November 2026

Short answer

Electronic refrigeration temperature controller with 2 probe inputs and 1 relay output. Everything is a holding register: probe readings in tenths, relay and digital-input bits, alarm flags, on/standby and defrost commands, and the full parameter list (setpoint, differential, compressor protection, defrost, alarm, door input, energy saving, real-time-clock defrosts and Modbus address/baud).

This page lists 91 Modbus registers for the Johnson Controls PENN TC3221 refrigeration temperature controller (Modbus RTU) — 83 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Johnson Controls’s own free documentation (linked below) and checked against it.

Manufacturer
Johnson Controls
Model
PENN TC3221 refrigeration temperature controller (Modbus RTU)
Equipment type
Thermostat
Registers
91 (83 writable)
Transport
Modbus RTU
Default unit ID
Not stated
Documented addressing
hexadecimal, 0-based
Also known as
TC3221, TC3, PENN TC3, LIT-12013523
Source document
TC3 Modbus Protocol Reference Guide (TC3221, TC3222, TC3223, TC3224N9R) · LIT-12013523 · rev. 2020-04-28
Download CSV all columns JSON Manufacturer PDF ↗

Integration notes: Johnson Controls PENN TC3221 refrigeration temperature controller (Modbus RTU)

Integration in brief

Set the LA (address) and Lb (baud) parameters, then poll holding registers with function 03: Probe 1 at 0x0201 (tenths), relay bits at 0x0181 and alarm bits at 0x0301. Write On/Standby (0x0501), the setpoint SP (0x0601, tenths) and trigger defrosts through 0x28B0.

Minimum registers to map

Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.

RegisterNameTypeWhyAccess
HR 513Probe 1INT16Cabinet probe temperatureRead
HR 1537Setpoint (SP)INT16Control setpointRead/write
HR 1281On or standbyUINT16Run / standby commandRead/write
HR 385Digital outputsBITMAP16Relay output statesRead
HR 769Alarm flagsBITMAP16Alarm and probe-failure flagsRead
HR 10416Defrost commandUINT16Start/stop a defrost (0Dh/0Ch)Write
HR 1544Celsius or Fahrenheit (P2)UINT16Temperature unitRead/write

Enable Modbus control & writes

Modbus RTU is built in; set the Modbus address (LA) and baud rate (Lb) parameters at the controller.

Byte order & addressing

Network setup

Watch out for

Johnson Controls PENN TC3221 refrigeration temperature controller (Modbus RTU) Modbus registers

Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.

91 of 91 shown
Johnson Controls PENN TC3221 refrigeration temperature controller (Modbus RTU) Modbus register map
TableAddressNameDescriptionTypeOrderScaleUnitsAccessValues / bits
HR257doc 0101h (HR:258)Digital inputsBITMAP16Readbit 2 = Digital input
HR385doc 0181h (HR:386)Digital outputsBITMAP16Readbit 0 = Compressor output
HR513doc 0201h (HR:514)Probe 1Probe reading in tenths; °C or °F per parameter P2.INT16× 0.1Read
HR514doc 0202h (HR:515)Probe 2Probe reading in tenths; °C or °F per parameter P2.INT16× 0.1Read
HR769doc 0301h (HR:770)Alarm flags1 = active.BITMAP16Readbit 0 = Cabinet probe failure (Pr1); bit 1 = Evaporator probe failure (Pr2); bit 2 = Condenser probe failure (Pr3); bit 3 = Maximum temperature alarm (AH); bit 4 = Minimum temperature alarm (AL); bit 5 = Global thermal switch alarm (th); bit 6 = Multifunction input alarm (iA); bit 7 = Door alarm (id); bit 9 = Condenser overheating alarm (COH); bit 10 = Compressor blocked alarm (CSd); bit 11 = Defrost ended by timeout (dFd); bit 12 = Compressor thermal switch alarm (Cth); bit 13 = Real-time clock error (rtc)
HR1281doc 0501h (HR:1282)On or standbyUINT16Read/write0 = Standby mode; 1 = On
HR1368doc 0558h (HR:1369)SetpointINT16× 0.1°CRead
HR1537doc 0601h (HR:1538)Setpoint (SP)Range -99 to 199 °C.INT16× 0.1°CRead/write
HR1539doc 0603h (HR:1540)Calibration Probe 1 (CA1)Range -25 to 25 °C.INT16× 0.1°CRead/write
HR1540doc 0604h (HR:1541)Calibration Probe 2 (CA2)Range -25 to 25 °C.INT16× 0.1°CRead/write
HR1542doc 0606h (HR:1543)Type of probe (P0)UINT16Read/write0 = positive temperature coefficient (PTC); 1 = negative temperature coefficient (NTC)
HR1543doc 0607h (HR:1544)Decimal point (P1)UINT16Read/write0 = No; 1 = Yes
HR1544doc 0608h (HR:1545)Celsius or Fahrenheit (P2)UINT16Read/write0 = °C; 1 = °F
HR1545doc 0609h (HR:1546)Second probe configuration (P4)UINT16Read/write0 = Digital input; 1 = Defrost; 2 = Condenser
HR1546doc 060Ah (HR:1547)Value displayed in the main display (P5)UINT16Read/write0 = Probe; 1 = Setpoint; 2 = Second probe
HR1548doc 060Ch (HR:1549)Display refresh time (P8)Printed range 0 to 250 in units of 1/10 sec.UINT16× 0.1sRead/write
HR1549doc 060Dh (HR:1550)Setpoint differential (r0)Range 0.1 to 15 °C.INT16× 0.1°CRead/write
HR1550doc 060Eh (HR:1551)Minimum setpoint (r1)Range -99 to 199 °C.INT16× 0.1°CRead/write
HR1551doc 060Fh (HR:1552)Maximum setpoint (r2)Range -99 to 199 °C.INT16× 0.1°CRead/write
HR1552doc 0610h (HR:1553)Energy saving set point, relative (r4)Range 0 to 99 °C.INT16× 0.1°CRead/write
HR1553doc 0611h (HR:1554)Cooling or heating operaton (r5)UINT16Read/write0 = Cooling; 1 = Heating
HR1554doc 0612h (HR:1555)Setpoint offset in overcooling or overheating (r6)Range 0 to 99 °C.INT16× 0.1°CRead/write
HR1555doc 0613h (HR:1556)Overcooling or overheating duration (r7)Range 0 to 240 min.UINT16minRead/write
HR1556doc 0614h (HR:1557)Down key configuration (r8)UINT16Read/write0 = None; 1 = Overcooling or overheating; 2 = Energy saving
HR1557doc 0615h (HR:1558)r0 type (r12)UINT16Read/write0 = asymmetric; 1 = symmetric
HR1559doc 0617h (HR:1560)Power-on delay (C0)Range 0 to 240 min.UINT16minRead/write
HR1560doc 0618h (HR:1561)Delay since last deactivation (C2)Range 0 to 240 min.UINT16minRead/write
HR1561doc 0619h (HR:1562)Minimum time compressor on (C3)Range 0 to 240 s.UINT16sRead/write
HR1562doc 061Ah (HR:1563)Time compressor turned off during probe failure (C4)Range 0 to 240 min.UINT16minRead/write
HR1563doc 061Bh (HR:1564)Time compressor turned on during probe failure (C5)Range 0 to 240 min.UINT16minRead/write
HR1564doc 061Ch (HR:1565)Set point for COH alarm (C6)Range 0 to 199 °C.INT16× 0.1°CRead/write
HR1565doc 061Dh (HR:1566)Set point for CSd alarm (C7)Range 0 to 199 °C.INT16× 0.1°CRead/write
HR1566doc 061Eh (HR:1567)CSd alarm delay (C8)Range 0 to 15 min.UINT16minRead/write
HR1567doc 061Fh (HR:1568)Compressor hours for service request (C10)Printed range 0 to 999 in units of 100h.UINT16× 100hRead/write
HR1570doc 0622h (HR:1571)Defrost lag (d0)Range 0 to 99 h.UINT16hRead/write
HR1572doc 0624h (HR:1573)Defrost cutoff temperature (d2)Range -99 to 99 °C.INT16× 0.1°CRead/write
HR1573doc 0625h (HR:1574)Defrost maximum time (d3)Range 0 to 99 min.UINT16minRead/write
HR1574doc 0626h (HR:1575)Defrost from power-on (d4)UINT16Read/write0 = No; 1 = Yes
HR1575doc 0627h (HR:1576)Defrost delay after power-on (d5)Range 0 to 99 min.UINT16minRead/write
HR1576doc 0628h (HR:1577)Data displayed during defrost (d6)UINT16Read/write0 = Probe; 1 = Limited in defrost; 2 = Label from the dEF parameter
HR1577doc 0629h (HR:1578)Dripping time (d7)Range 0 to 15 min.UINT16minRead/write
HR1578doc 062Ah (HR:1579)Type of defrost interval (d8)UINT16Read/write0 = Time; 1 = Compressor hours; 2 = d9 threshold; 3 = Adaptive; 4 = Real time
HR1579doc 062Bh (HR:1580)Stop counter threshold (d9)Range -99 to 99 °C.INT16× 0.1°CRead/write
HR1580doc 062Ch (HR:1581)Enable defrost timeout alarm (d11)UINT16Read/write0 = Disabled; 1 = Enabled
HR1583doc 062Fh (HR:1584)Time for adaptive defrost, d8=3 (d18)Range 0 to 999 min.UINT16minRead/write
HR1584doc 0630h (HR:1585)Temperature threshold for adaptive defrost, d8=3 (d19)Range 0 to 40 °C.INT16× 0.1°CRead/write
HR1585doc 0631h (HR:1586)Maximum time for safety defrost in normal operation (d20)Range 0 to 999 min.UINT16minRead/write
HR1586doc 0632h (HR:1587)Maximum time for safety defrost in pull down (d21)Range 0 to 500 min.UINT16minRead/write
HR1587doc 0633h (HR:1588)Evaporation threshold for adaptive defrost interval counting, relative to optimal evaporation temperature (d22)Range -10 to 10 °C.INT16× 0.1°CRead/write
HR1588doc 0634h (HR:1589)Alarm probe (AA)UINT16Read/write0 = Cabinet probe; 1 = Second probe
HR1589doc 0635h (HR:1590)Minimum alarm threshold (A1)Range -99 to 99 °C.INT16× 0.1°CRead/write
HR1590doc 0636h (HR:1591)Minimum alarm type (A2)UINT16Read/write0 = Disabled; 1 = Relative; 2 = Absolute
HR1591doc 0637h (HR:1592)Maximum alarm threshold (A4)Range -99 to 99 °C.INT16× 0.1°CRead/write
HR1592doc 0638h (HR:1593)Maximum alarm type (A5)UINT16Read/write0 = Disabled; 1 = Relative; 2 = Absolute
HR1593doc 0639h (HR:1594)Alarm delay from power-on (A6)Printed range 0 to 99 in units of 10 Minutes.UINT16× 10minRead/write
HR1594doc 063Ah (HR:1595)Alarm delay (A7)Range 0 to 240 min.UINT16minRead/write
HR1595doc 063Bh (HR:1596)High temperature alarm delay after defrost (A8)Range 0 to 240 min.UINT16minRead/write
HR1596doc 063Ch (HR:1597)High temperature alarm delay after door closing (A9)Range 0 to 240 min.UINT16minRead/write
HR1597doc 063Dh (HR:1598)Minimum time for power failure alarm (A10)Range 0 to 240 min.UINT16minRead/write
HR1598doc 063Eh (HR:1599)Histeresys alarms regulator (A11)Range 0.1 to 15 °C.INT16× 0.1°CRead/write
HR1599doc 063Fh (HR:1600)High or low temperature alarms reset differential (A12)UINT16Read/write0 = LED; 1 = LED, power failure label, and buzzer; 2 = LED and power failure label; buzzer if the duration is more than A10
HR1600doc 0640h (HR:1601)Buzzer configuration (A13)UINT16Read/write0 = Disabled; 1 = Enabled
HR1613doc 064Dh (HR:1614)Digital input 1 action (i0)UINT16Read/write0 = None; 1 = cmp_off; 2 = Reserved; 3 = Reserved; 4 = Reserved; 5 = Reserved; 6 = Reserved; 7 = Energy saving; 8 = Warning; 9 = Standby mode; 10 = Cth alarm; 11 = th alarm
HR1614doc 064Eh (HR:1615)Digital input 1 polarity (i1)UINT16Read/write0 = Active contact closed; 1 = Active contact opened
HR1615doc 064Fh (HR:1616)Open door alarm delay (i2)Range -1 to 120 min.INT16minRead/write
HR1616doc 0650h (HR:1617)Maximum duration of door switch (i3)Range -1 to 120 min.INT16minRead/write
HR1617doc 0651h (HR:1618)Multifunction alarm delay (i7)Range -1 to 120 min.INT16minRead/write
HR1618doc 0652h (HR:1619)Duration with door closed before energy saving starts (i10)Range 0 to 999 min.UINT16minRead/write
HR1619doc 0653h (HR:1620)Number of door openings before safety defrost starts (i13)Range 0 to 240.UINT16Read/write
HR1620doc 0654h (HR:1621)Duration with door open before safety defrost starts (i14)Range 0 to 240 min.UINT16minRead/write
HR1626doc 065Ah (HR:1627)Energy saving maximum duration (HE2)Range 0 to 999 min.UINT16minRead/write
HR1627doc 065Bh (HR:1628)Energy saving time (H01)Range 0 to 23 h.UINT16hRead/write
HR1628doc 065Ch (HR:1629)Energy saving duration (H02)Range 0 to 24 h.UINT16hRead/write
HR1629doc 065Dh (HR:1630)Holiday (HEd)UINT16Read/write0 = Monday; 1 = Tuesday; 2 = Wednesday; 3 = Thursday; 4 = Friday; 5 = Saturday; 6 = Sunday; 7 = None
HR1630doc 065Eh (HR:1631)Defrost 1 starting time (Hd1)Range 0 to 24 h.UINT16hRead/write
HR1631doc 065Fh (HR:1632)Defrost 2 starting time (Hd2)Range 0 to 24 h.UINT16hRead/write
HR1632doc 0660h (HR:1633)Defrost 3 starting time (Hd3)Range 0 to 24 h.UINT16hRead/write
HR1633doc 0661h (HR:1634)Defrost 4 starting time (Hd4)Range 0 to 24 h.UINT16hRead/write
HR1634doc 0662h (HR:1635)Defrost 5 starting time (Hd5)Range 0 to 24 h.UINT16hRead/write
HR1635doc 0663h (HR:1636)Defrost 6 starting time (Hd6)Range 0 to 24 h.UINT16hRead/write
HR1636doc 0664h (HR:1637)Enable On/ standby key (POF)UINT16Read/write0 = Disabled; 1 = Enabled
HR1638doc 0666h (HR:1639)RTC configuration (Hr0)UINT16Read/write0 = Disabled; 1 = Enabled
HR1639doc 0667h (HR:1640)Address (LA)Range 1 to 247.UINT16Read/write
HR1640doc 0668h (HR:1641)Baud rate (Lb)UINT16Read/write0 = 2400; 1 = 4800; 2 = 9600; 3 = 19200
HR10374doc 2886h (HR:10375)Next defrost counterRange 0 to 65535.UINT16Read/write
HR10416doc 28B0h (HR:10417)Defrost commandUINT16Write12 = Stop defrost; 13 = Start defrost
HR10436doc 28C4h (HR:10437)Status flags HR:10437BITMAP16Read/writebit 9 = Energy saving for door inactivity; bit 10 = Pull down done; bit 11 = Setpoint reached; bit 14 = Adaptive defrost calibration done
HR10438doc 28C6h (HR:10439)Status flags HR:10439BITMAP16Read/writebit 1 = Energy saving; bit 10 = Service request; bit 12 = Overcooling
HR10503doc 2907h (HR:10504)Remote energy savingUINT16Read/write0 = Inactive; 1 = Active
HR65288doc FF08h (HR:65289)Firmware identifierUINT16Read
HR65290doc FF0Ah (HR:65291)Firmware programUINT16Read

Notes on this map

Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.

Questions about the Johnson Controls PENN TC3221 refrigeration temperature controller (Modbus RTU)

What Modbus registers does the Johnson Controls PENN TC3221 refrigeration temperature controller (Modbus RTU) have?

This map lists 91 registers: 91 holding registers. 83 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.

Are the Johnson Controls PENN TC3221 refrigeration temperature controller (Modbus RTU) Modbus addresses 0-based or 1-based?

The manufacturer's document numbers registers hexadecimal, 0-based. Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. The guide prints every point twice: a hex 'Base 0' address (0201h) and a decimal 'Base 1' holding-register number (HR:514). The wire address is the Base 0 value (0x0201 = 513 = HR:514 - 1). Bit points are given as register.BitN.

What are the minimum Modbus registers to integrate the Johnson Controls PENN TC3221 refrigeration temperature controller (Modbus RTU)?

Start with HR 513 Probe 1 (Cabinet probe temperature); HR 1537 Setpoint (SP) (Control setpoint); HR 1281 On or standby (Run / standby command); HR 385 Digital outputs (Relay output states); HR 769 Alarm flags (Alarm and probe-failure flags); HR 10416 Defrost command (Start/stop a defrost (0Dh/0Ch)); HR 1544 Celsius or Fahrenheit (P2) (Temperature unit).

How do I enable Modbus control of the Johnson Controls PENN TC3221 refrigeration temperature controller (Modbus RTU)?

Modbus RTU is built in; set the Modbus address (LA) and baud rate (Lb) parameters at the controller.

Where is the official Johnson Controls PENN TC3221 refrigeration temperature controller (Modbus RTU) Modbus documentation?

The source is TC3 Modbus Protocol Reference Guide (TC3221, TC3222, TC3223, TC3224N9R) (LIT-12013523), revision 2020-04-28, published free by Johnson Controls at https://docs.johnsoncontrols.com/bas/r/PENN-Controls/en-US/TC3-Modbus-Protocol-Reference-Guide.

More Johnson Controls Modbus register maps

Other hvac equipment register maps

All hvac equipment Modbus register maps →

Source: TC3 Modbus Protocol Reference Guide (TC3221, TC3222, TC3223, TC3224N9R) · LIT-12013523 · rev. 2020-04-28. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.