Thermostat / temperature and process PID controller · Modbus register map

Omega CN2200 / CN2400 series temperature and process controllers (Modbus RTU) Modbus register map

Updated 17 November 2026

Short answer

The CN2200 and CN2400 are Omega panel-mount PID temperature and process controllers. Every parameter has a 16-bit Modbus address, and a second 'IEEE region' gives the same parameter as a full-resolution 32-bit float. This map lists the loop values in the IEEE region (so no decimal-point scaling is needed) and the mode selectors and status words as plain 16-bit registers.

This page lists 29 Modbus registers for the Omega CN2200 / CN2400 series temperature and process controllers (Modbus RTU) — 19 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Omega’s own free documentation (linked below) and checked against it.

Manufacturer
Omega
Model
CN2200 / CN2400 series temperature and process controllers (Modbus RTU)
Equipment type
Thermostat / temperature and process PID controller
Registers
29 (19 writable)
Transport
Modbus RTU
Default unit ID
Not stated
Documented addressing
0-based (the number printed is the address on the wire)
32-bit word order
ABCD high word first (big-endian)
Firmware
CN2400 1.03, 2.04, 3.04, 3.05; CN2200 1.00, 1.20, 1.30, 2.10
Also known as
CN2204, CN2208, CN2408
Source document
Series CN2200 and CN2400 Modbus and Digital Communications Handbook
Download CSV all columns JSON Manufacturer PDF ↗

Integration notes: Omega CN2200 / CN2400 series temperature and process controllers (Modbus RTU)

Integration in brief

Read PV, target setpoint and output as one 6-register block from 8002h (function 03), decode as ABCD floats, and write a new setpoint with function 16 to 8004h. Use 273 for auto/manual and 74 for alarm and sensor-break flags.

Minimum registers to map

Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.

RegisterNameTypeWhyAccess
HR 32770Process variableFLOAT32 ABCDProcess variable (float)Read
HR 32772Target setpointFLOAT32 ABCDTarget setpoint (float, write with FC16)Read/write
HR 32774Output powerFLOAT32 ABCDOutput power (float)Read/write
HR 32778Working setpointFLOAT32 ABCDWorking setpoint (float, read only)Read
HR 273Auto/manual selectUINT16Auto/manualRead/write
HR 74Fast status byteBITMAP16Alarm and sensor-break flagsRead

Enable Modbus control & writes

Comms hardware must be fitted: on the CN2400 the plug-in H module sets RS-232/422/485, while CN2200 comms is fixed when ordered. Set the slave address with Addr in the Cms list.

Byte order & addressing

Network setup

Watch out for

Omega CN2200 / CN2400 series temperature and process controllers (Modbus RTU) Modbus registers

Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.

29 of 29 shown
Omega CN2200 / CN2400 series temperature and process controllers (Modbus RTU) Modbus register map
TableAddressNameDescriptionTypeOrderScaleUnitsAccessValues / bits
HR15Setpoint selectSP1/SP2 standard; SP3-SP16 only on CN2400 16-setpoint option.UINT16Read/write0 = SP1; 1 = SP2; 2 = SP3; 3 = SP4; 4 = SP5; 5 = SP6; 6 = SP7; 7 = SP8; 8 = SP9; 9 = SP10; 10 = SP11; 11 = SP12; 12 = SP13; 13 = SP14; 14 = SP15; 15 = SP16
HR22Current program numberCN2400 programmer only.UINT16Read
HR23Program statusCN2400 programmer only.UINT16Read1 = Reset; 2 = Run; 4 = Hold; 8 = Holdback; 16 = Complete
HR74Fast status byteAlarm, manual, sensor and loop break flags; also via function 7.BITMAP16Readbit 0 = Alarm 1 active; bit 1 = Alarm 2 active; bit 2 = Alarm 3 active; bit 3 = Alarm 4 active; bit 4 = Manual mode; bit 5 = Sensor break; bit 6 = Loop break (open loop); bit 7 = Heater fail (load fault)
HR75Summary output status wordBits 8, 11, 12 and 14 differ by model; see notes.BITMAP16Readbit 0 = Alarm 1 active; bit 1 = Alarm 2 active; bit 2 = Alarm 3 active; bit 3 = Alarm 4 active; bit 4 = Manual mode; bit 5 = Sensor break; bit 6 = Loop break (open loop); bit 7 = Heater fail (load fault); bit 9 = Ramp/program complete; bit 10 = PV out of table range; bit 13 = Remote input sensor break
HR76Control status wordInternal PID loop flags.BITMAP16Readbit 0 = Control algorithm freeze; bit 1 = PV input sensor broken; bit 2 = PV out of sensor range; bit 3 = Self tune failed; bit 4 = PID servo signal; bit 5 = PID debump signal; bit 6 = Loop break fault; bit 7 = Integral accumulator frozen; bit 8 = Tune completed; bit 9 = Direct/reverse acting; bit 10 = Algorithm initialization; bit 11 = PID demand limited; bit 13 = Adaptive tune enabled; bit 14 = Automatic droop compensation enabled; bit 15 = Manual/auto mode switch
HR77Instrument status wordCN2400 only.BITMAP16Readbit 0 = Config/operator mode switch; bit 1 = Limit checking disabled; bit 2 = SRL ramp running; bit 3 = Remote setpoint active; bit 4 = Alarm acknowledge
HR131Communications addressSlave address 1-254 (Addr in the Cms list).UINT16Read/write
HR270Autotune enableUINT16Read/write0 = No tune; 1 = Tune
HR272Automatic droop compensationUINT16Read/write0 = Manual reset; 1 = Calculated
HR273Auto/manual selectUINT16Read/write0 = Auto; 1 = Manual
HR276Local/remote setpoint selectUINT16Read/write0 = Local; 1 = Remote
HR32770doc 1 (IEEE region: 2 x 1 + 8000h)Process variableMeasured value, full-resolution float.FLOAT32ABCDRead
HR32772doc 2 (IEEE region: 2 x 2 + 8000h)Target setpointSetpoint in use; write to change it.FLOAT32ABCDRead/write
HR32774doc 3 (IEEE region: 2 x 3 + 8000h)Output power% output level; the handbook's example selects manual (273) before changing it.FLOAT32ABCD%Read/write
HR32778doc 5 (IEEE region: 2 x 5 + 8000h)Working setpointSetpoint the loop is actually using (read only).FLOAT32ABCDRead
HR32780doc 6 (IEEE region: 2 x 6 + 8000h)Proportional band PID1FLOAT32ABCDRead/write
HR32794doc 13 (IEEE region: 2 x 13 + 8000h)Alarm 1 setpointFLOAT32ABCDRead/write
HR32796doc 14 (IEEE region: 2 x 14 + 8000h)Alarm 2 setpointFLOAT32ABCDRead/write
HR32816doc 24 (IEEE region: 2 x 24 + 8000h)Setpoint 1FLOAT32ABCDRead/write
HR32818doc 25 (IEEE region: 2 x 25 + 8000h)Setpoint 2FLOAT32ABCDRead/write
HR32828doc 30 (IEEE region: 2 x 30 + 8000h)High power limitFLOAT32ABCD%Read/write
HR32830doc 31 (IEEE region: 2 x 31 + 8000h)Low power limitFLOAT32ABCD%Read/write
HR32874doc 53 (IEEE region: 2 x 53 + 8000h)Valve positionValve position (CN2200 vPoS, CN2400 VP computed position).FLOAT32ABCD%Read
HR32928doc 80 (IEEE region: 2 x 80 + 8000h)Heater currentLoad current with PDLINK mode 2.FLOAT32ABCDARead
HR32930doc 81 (IEEE region: 2 x 81 + 8000h)Alarm 3 setpointFLOAT32ABCDRead/write
HR32932doc 82 (IEEE region: 2 x 82 + 8000h)Alarm 4 setpointFLOAT32ABCDRead/write
HR32990doc 111 (IEEE region: 2 x 111 + 8000h)Setpoint 1 high limitFLOAT32ABCDRead/write
HR32992doc 112 (IEEE region: 2 x 112 + 8000h)Setpoint 1 low limitFLOAT32ABCDRead/write

Notes on this map

Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.

Questions about the Omega CN2200 / CN2400 series temperature and process controllers (Modbus RTU)

What Modbus registers does the Omega CN2200 / CN2400 series temperature and process controllers (Modbus RTU) have?

This map lists 29 registers: 29 holding registers. 19 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.

Are the Omega CN2200 / CN2400 series temperature and process controllers (Modbus RTU) Modbus addresses 0-based or 1-based?

The manufacturer's document numbers registers 0-based (the number printed is the address on the wire). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. The handbook's addresses go on the wire as printed: its example reads PV and setpoint starting at address 0001. For the float form of any parameter use address x 2 + 8000h, e.g. target setpoint 2 -> 8004h (32772).

What byte order does the Omega CN2200 / CN2400 series temperature and process controllers (Modbus RTU) use for 32-bit values?

Multi-register values in this map use ABCD (high word first (big-endian)). Set your client to this order for every 32/64-bit value in the table.

What are the minimum Modbus registers to integrate the Omega CN2200 / CN2400 series temperature and process controllers (Modbus RTU)?

Start with HR 32770 Process variable (Process variable (float)); HR 32772 Target setpoint (Target setpoint (float, write with FC16)); HR 32774 Output power (Output power (float)); HR 32778 Working setpoint (Working setpoint (float, read only)); HR 273 Auto/manual select (Auto/manual); HR 74 Fast status byte (Alarm and sensor-break flags).

How do I enable Modbus control of the Omega CN2200 / CN2400 series temperature and process controllers (Modbus RTU)?

Comms hardware must be fitted: on the CN2400 the plug-in H module sets RS-232/422/485, while CN2200 comms is fixed when ordered. Set the slave address with Addr in the Cms list.

Where is the official Omega CN2200 / CN2400 series temperature and process controllers (Modbus RTU) Modbus documentation?

The source is Series CN2200 and CN2400 Modbus and Digital Communications Handbook, published free by Omega at https://assets.dwyeromega.com/manuals/M3372.pdf.

Other hvac equipment register maps

All hvac equipment Modbus register maps →

Source: Series CN2200 and CN2400 Modbus and Digital Communications Handbook. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.