- CN2200 / CN2400 series temperature and process controllers (Modbus RTU)
Thermostat / temperature and process PID controller · Modbus register map
Omega CN2200 / CN2400 series temperature and process controllers (Modbus RTU) Modbus register map
Updated 17 November 2026
The CN2200 and CN2400 are Omega panel-mount PID temperature and process controllers. Every parameter has a 16-bit Modbus address, and a second 'IEEE region' gives the same parameter as a full-resolution 32-bit float. This map lists the loop values in the IEEE region (so no decimal-point scaling is needed) and the mode selectors and status words as plain 16-bit registers.
This page lists 29 Modbus registers for the Omega CN2200 / CN2400 series temperature and process controllers (Modbus RTU) — 19 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Omega’s own free documentation (linked below) and checked against it.
- Manufacturer
- Omega
- Model
- CN2200 / CN2400 series temperature and process controllers (Modbus RTU)
- Equipment type
- Thermostat / temperature and process PID controller
- Registers
- 29 (19 writable)
- Transport
- Modbus RTU
- Default unit ID
- Not stated
- Documented addressing
- 0-based (the number printed is the address on the wire)
- 32-bit word order
- ABCD high word first (big-endian)
- Firmware
- CN2400 1.03, 2.04, 3.04, 3.05; CN2200 1.00, 1.20, 1.30, 2.10
- Also known as
- CN2204, CN2208, CN2408
Integration notes: Omega CN2200 / CN2400 series temperature and process controllers (Modbus RTU)
Read PV, target setpoint and output as one 6-register block from 8002h (function 03), decode as ABCD floats, and write a new setpoint with function 16 to 8004h. Use 273 for auto/manual and 74 for alarm and sensor-break flags.
Minimum registers to map
Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.
| Register | Name | Type | Why | Access |
|---|---|---|---|---|
| HR 32770 | Process variable | FLOAT32 ABCD | Process variable (float) | Read |
| HR 32772 | Target setpoint | FLOAT32 ABCD | Target setpoint (float, write with FC16) | Read/write |
| HR 32774 | Output power | FLOAT32 ABCD | Output power (float) | Read/write |
| HR 32778 | Working setpoint | FLOAT32 ABCD | Working setpoint (float, read only) | Read |
| HR 273 | Auto/manual select | UINT16 | Auto/manual | Read/write |
| HR 74 | Fast status byte | BITMAP16 | Alarm and sensor-break flags | Read |
Enable Modbus control & writes
Comms hardware must be fitted: on the CN2400 the plug-in H module sets RS-232/422/485, while CN2200 comms is fixed when ordered. Set the slave address with Addr in the Cms list.
Byte order & addressing
- Two address spaces: plain 16-bit (scaled by display resolution) and IEEE floats at 2 x address + 8000h.
- Function 06 is refused in the IEEE region; use function 16.
Network setup
- Set the address in the Cms list (1-254) and match baud/parity on the master.
- RTU only, 8 data bits, 1 stop bit.
Watch out for
- Reading an unconfigured parameter returns an undefined value, not an exception.
- The handbook's manual-mode example selects manual (273 = 1) before changing output power at 3.
- Keep reads to 32 words on a CN2200 (125 on a CN2400).
Omega CN2200 / CN2400 series temperature and process controllers (Modbus RTU) Modbus registers
Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.
| Table | Address | Name | Description | Type | Order | Scale | Units | Access | Values / bits |
|---|---|---|---|---|---|---|---|---|---|
| HR | 15 | Setpoint select | SP1/SP2 standard; SP3-SP16 only on CN2400 16-setpoint option. | UINT16 | Read/write | 0 = SP1; 1 = SP2; 2 = SP3; 3 = SP4; 4 = SP5; 5 = SP6; 6 = SP7; 7 = SP8; 8 = SP9; 9 = SP10; 10 = SP11; 11 = SP12; 12 = SP13; 13 = SP14; 14 = SP15; 15 = SP16 | |||
| HR | 22 | Current program number | CN2400 programmer only. | UINT16 | Read | ||||
| HR | 23 | Program status | CN2400 programmer only. | UINT16 | Read | 1 = Reset; 2 = Run; 4 = Hold; 8 = Holdback; 16 = Complete | |||
| HR | 74 | Fast status byte | Alarm, manual, sensor and loop break flags; also via function 7. | BITMAP16 | Read | bit 0 = Alarm 1 active; bit 1 = Alarm 2 active; bit 2 = Alarm 3 active; bit 3 = Alarm 4 active; bit 4 = Manual mode; bit 5 = Sensor break; bit 6 = Loop break (open loop); bit 7 = Heater fail (load fault) | |||
| HR | 75 | Summary output status word | Bits 8, 11, 12 and 14 differ by model; see notes. | BITMAP16 | Read | bit 0 = Alarm 1 active; bit 1 = Alarm 2 active; bit 2 = Alarm 3 active; bit 3 = Alarm 4 active; bit 4 = Manual mode; bit 5 = Sensor break; bit 6 = Loop break (open loop); bit 7 = Heater fail (load fault); bit 9 = Ramp/program complete; bit 10 = PV out of table range; bit 13 = Remote input sensor break | |||
| HR | 76 | Control status word | Internal PID loop flags. | BITMAP16 | Read | bit 0 = Control algorithm freeze; bit 1 = PV input sensor broken; bit 2 = PV out of sensor range; bit 3 = Self tune failed; bit 4 = PID servo signal; bit 5 = PID debump signal; bit 6 = Loop break fault; bit 7 = Integral accumulator frozen; bit 8 = Tune completed; bit 9 = Direct/reverse acting; bit 10 = Algorithm initialization; bit 11 = PID demand limited; bit 13 = Adaptive tune enabled; bit 14 = Automatic droop compensation enabled; bit 15 = Manual/auto mode switch | |||
| HR | 77 | Instrument status word | CN2400 only. | BITMAP16 | Read | bit 0 = Config/operator mode switch; bit 1 = Limit checking disabled; bit 2 = SRL ramp running; bit 3 = Remote setpoint active; bit 4 = Alarm acknowledge | |||
| HR | 131 | Communications address | Slave address 1-254 (Addr in the Cms list). | UINT16 | Read/write | ||||
| HR | 270 | Autotune enable | UINT16 | Read/write | 0 = No tune; 1 = Tune | ||||
| HR | 272 | Automatic droop compensation | UINT16 | Read/write | 0 = Manual reset; 1 = Calculated | ||||
| HR | 273 | Auto/manual select | UINT16 | Read/write | 0 = Auto; 1 = Manual | ||||
| HR | 276 | Local/remote setpoint select | UINT16 | Read/write | 0 = Local; 1 = Remote | ||||
| HR | 32770doc 1 (IEEE region: 2 x 1 + 8000h) | Process variable | Measured value, full-resolution float. | FLOAT32 | ABCD | Read | |||
| HR | 32772doc 2 (IEEE region: 2 x 2 + 8000h) | Target setpoint | Setpoint in use; write to change it. | FLOAT32 | ABCD | Read/write | |||
| HR | 32774doc 3 (IEEE region: 2 x 3 + 8000h) | Output power | % output level; the handbook's example selects manual (273) before changing it. | FLOAT32 | ABCD | % | Read/write | ||
| HR | 32778doc 5 (IEEE region: 2 x 5 + 8000h) | Working setpoint | Setpoint the loop is actually using (read only). | FLOAT32 | ABCD | Read | |||
| HR | 32780doc 6 (IEEE region: 2 x 6 + 8000h) | Proportional band PID1 | FLOAT32 | ABCD | Read/write | ||||
| HR | 32794doc 13 (IEEE region: 2 x 13 + 8000h) | Alarm 1 setpoint | FLOAT32 | ABCD | Read/write | ||||
| HR | 32796doc 14 (IEEE region: 2 x 14 + 8000h) | Alarm 2 setpoint | FLOAT32 | ABCD | Read/write | ||||
| HR | 32816doc 24 (IEEE region: 2 x 24 + 8000h) | Setpoint 1 | FLOAT32 | ABCD | Read/write | ||||
| HR | 32818doc 25 (IEEE region: 2 x 25 + 8000h) | Setpoint 2 | FLOAT32 | ABCD | Read/write | ||||
| HR | 32828doc 30 (IEEE region: 2 x 30 + 8000h) | High power limit | FLOAT32 | ABCD | % | Read/write | |||
| HR | 32830doc 31 (IEEE region: 2 x 31 + 8000h) | Low power limit | FLOAT32 | ABCD | % | Read/write | |||
| HR | 32874doc 53 (IEEE region: 2 x 53 + 8000h) | Valve position | Valve position (CN2200 vPoS, CN2400 VP computed position). | FLOAT32 | ABCD | % | Read | ||
| HR | 32928doc 80 (IEEE region: 2 x 80 + 8000h) | Heater current | Load current with PDLINK mode 2. | FLOAT32 | ABCD | A | Read | ||
| HR | 32930doc 81 (IEEE region: 2 x 81 + 8000h) | Alarm 3 setpoint | FLOAT32 | ABCD | Read/write | ||||
| HR | 32932doc 82 (IEEE region: 2 x 82 + 8000h) | Alarm 4 setpoint | FLOAT32 | ABCD | Read/write | ||||
| HR | 32990doc 111 (IEEE region: 2 x 111 + 8000h) | Setpoint 1 high limit | FLOAT32 | ABCD | Read/write | ||||
| HR | 32992doc 112 (IEEE region: 2 x 112 + 8000h) | Setpoint 1 low limit | FLOAT32 | ABCD | Read/write |
Notes on this map
- Float parameters (PV, setpoints, output, alarm setpoints) are listed only in the IEEE region. In the normal 16-bit region their scaling depends on the controller's integer/full-resolution setting and the display decimal point, which the master must know, so those 16-bit forms are left out.
- IEEE floats are sent with bits 31-24 first in the lower address (example 1.001 = 3F 80 20 C5), i.e. ABCD. Both words must be read or written in one request.
- The IEEE region only accepts function 03/04 reads and function 16 writes; function 06 is rejected there. Start IEEE reads at even addresses.
- Summary output status word (75): bit 8 is Tune active on CN2400 but Load fail on CN2200; bit 11 is DC control module fault on CN2400 but SSR fail on CN2200; bit 12 is programmer segment sync on CN2400 but New alarm on CN2200; bit 14 is IP1 fault on CN2400 and reserved on CN2200. Only the common bits are listed.
- Configuration parameters are read only unless the controller is in configuration mode. A function 06 write to a read-only or unconfigured parameter is rejected, but a function 16 block whose only value lands on an unconfigured address looks successful and the value is discarded.
- The slave address (1-254) is the Addr parameter in the Cms list. Parity can be None, Odd or Even and every unit uses 1 stop bit; the handbook gives no factory defaults and only RTU mode is supported.
- Alarm hysteresis, PID times and other parameters are documented in the handbook but not listed; use address x 2 + 8000h to read any of them as a float.
- One read can return at most 125 words on a CN2400 and 32 words on a CN2200.
Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.
Questions about the Omega CN2200 / CN2400 series temperature and process controllers (Modbus RTU)
What Modbus registers does the Omega CN2200 / CN2400 series temperature and process controllers (Modbus RTU) have?
This map lists 29 registers: 29 holding registers. 19 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.
Are the Omega CN2200 / CN2400 series temperature and process controllers (Modbus RTU) Modbus addresses 0-based or 1-based?
The manufacturer's document numbers registers 0-based (the number printed is the address on the wire). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. The handbook's addresses go on the wire as printed: its example reads PV and setpoint starting at address 0001. For the float form of any parameter use address x 2 + 8000h, e.g. target setpoint 2 -> 8004h (32772).
What byte order does the Omega CN2200 / CN2400 series temperature and process controllers (Modbus RTU) use for 32-bit values?
Multi-register values in this map use ABCD (high word first (big-endian)). Set your client to this order for every 32/64-bit value in the table.
What are the minimum Modbus registers to integrate the Omega CN2200 / CN2400 series temperature and process controllers (Modbus RTU)?
Start with HR 32770 Process variable (Process variable (float)); HR 32772 Target setpoint (Target setpoint (float, write with FC16)); HR 32774 Output power (Output power (float)); HR 32778 Working setpoint (Working setpoint (float, read only)); HR 273 Auto/manual select (Auto/manual); HR 74 Fast status byte (Alarm and sensor-break flags).
How do I enable Modbus control of the Omega CN2200 / CN2400 series temperature and process controllers (Modbus RTU)?
Comms hardware must be fitted: on the CN2400 the plug-in H module sets RS-232/422/485, while CN2200 comms is fixed when ordered. Set the slave address with Addr in the Cms list.
Where is the official Omega CN2200 / CN2400 series temperature and process controllers (Modbus RTU) Modbus documentation?
The source is Series CN2200 and CN2400 Modbus and Digital Communications Handbook, published free by Omega at https://assets.dwyeromega.com/manuals/M3372.pdf.
Other hvac equipment register maps
- Thermostat / room controller (chilled beam with measured airflow and CO2)
Swegon CONDUCTOR W4 room controller (airflow and water, Modbus RTU)
Swegon CONDUCTOR W4 room controller, software 1.12 (technical manual updated 2014-11-21).
Also known as: CONDUCTOR RE W4, CONDUCTOR RE W4 1, Conductor W4 - Air handler (computer room air conditioner)
Vertiv Liebert DS / CW / HPM / PeX / Challenger with iCOM v4 (IntelliSlot Modbus)
Liebert perimeter precision cooling units on the iCOM v4 controller (Challenger 3000, Challenger ITR, CW, Deluxe System/3, DS, PeX with iCOM firmware PA1.04.033.STD or later; HPM with iCOM), read through a Liebert IntelliSlot Modbus 485 or Modbus IP card.
Also known as: Liebert DS, Liebert CW, Liebert HPM, Liebert PeX, Liebert Challenger 3000, Liebert Challenger ITR, Liebert Deluxe System/3, Liebert iCOM v4, IS-485L, IS-IPBML - Air handler (in-row data-centre DX cooling unit)
APC (Schneider Electric) InRow RD direct-expansion cooling unit (Modbus register map 990-3576B)
APC / Schneider Electric InRow RD cooling units, register map part number 990-3576B (08/2015).
Also known as: InRow RD, 990-3576B, Schneider Electric InRow RD - Thermostat / heating controller (district heating and HVAC)
Danfoss ECL Comfort 210 / 296 / 310 heating controller (Modbus RTU / TCP)
ECL Comfort 210, 296 and 310 controllers (and B versions) with any application key; many parameters depend on the loaded application.
Also known as: ECL Comfort 210, ECL Comfort 296, ECL Comfort 310, ECL Comfort 210B, ECL Comfort 310B, 087H3020, 087H3024, 087H3030, 087H3034, 087H3040, 087H3044, 087H3050, 087H3054 - Air handler (heat recovery ventilation unit)
Jablotron FUTURA L / M / S heat recovery ventilation unit (Modbus TCP)
Futura L/M/S from firmware FUA.P.06.71, register list v5.0 (13.10.2025). Futura L+ uses different addresses and is not covered.
Also known as: Futura L, Futura M, Futura S, JABLOTRON FUTURA - Thermostat (room operating unit with sensors)
LOYTEC L-STAT network thermostat / room operating unit (Modbus RTU)
LSTAT-800/801/802 room operating units (all button layouts), user manual version 3.2.8 (document 88085811).
Also known as: L-STAT, LSTAT-800, LSTAT-801, LSTAT-802, LSTAT-800-Gx-Lx, LSTAT-801-Gx-Lx, LSTAT-802-Gx-Lx
All hvac equipment Modbus register maps →
Source: Series CN2200 and CN2400 Modbus and Digital Communications Handbook. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.