- FUTURA L / M / S heat recovery ventilation unit (Modbus TCP)
Air handler (heat recovery ventilation unit) · Modbus register map
Jablotron FUTURA L / M / S heat recovery ventilation unit (Modbus TCP) Modbus register map
Updated 17 November 2026
The FUTURA is a residential heat recovery ventilation unit with a built-in Modbus TCP server. Input registers give air temperatures, humidity, fan data, power and connected room-sensor values; holding registers set the ventilation mode, timed functions, setpoints and external sensor values. This page lists the 16-bit registers of the Futura L/M/S layout.
This page lists 162 Modbus registers for the Jablotron FUTURA L / M / S heat recovery ventilation unit (Modbus TCP) — 50 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Jablotron’s own free documentation (linked below) and checked against it.
- Manufacturer
- Jablotron
- Model
- FUTURA L / M / S heat recovery ventilation unit (Modbus TCP)
- Equipment type
- Air handler (heat recovery ventilation unit)
- Registers
- 162 (50 writable)
- Transport
- Modbus TCP
- Default unit ID
- 1
- TCP port
- 502
- Documented addressing
- 0-based (the number printed is the address on the wire)
- Firmware
- FUA.P.06.71 or later (Futura L/M/S)
- Also known as
- Futura L, Futura M, Futura S, JABLOTRON FUTURA
Integration notes: Jablotron FUTURA L / M / S heat recovery ventilation unit (Modbus TCP)
Connect over Modbus TCP to port 502, unit ID 1. Read input registers 30-48 with function 04 for temperatures, humidity and fans, and write holding register 0 for the ventilation mode or 1-5 to start timed boost, circulation, overpressure, night or party functions.
Minimum registers to map
Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.
| Register | Name | Type | Why | Access |
|---|---|---|---|---|
| IR 30 | Ambient air temperature | INT16 | Ambient (outdoor intake) air temperature | Read |
| IR 32 | Indoor air temperature | INT16 | Indoor air temperature | Read |
| IR 36 | Indoor air humidity | INT16 | Indoor humidity | Read |
| IR 40 | Filter wear level | UINT16 | Filter wear | Read |
| IR 44 | Total air flow | UINT16 | Total air flow | Read |
| HR 0 | Ventilation mode | UINT16 | Ventilation mode | Read/write |
| HR 1 | Boost timer | UINT16 | Boost timer | Read/write |
| HR 10 | Preferred temperature | UINT16 | Temperature setpoint | Read/write |
Enable Modbus control & writes
The Modbus TCP server is built in; no enable step is documented.
Byte order & addressing
- Only one TCP socket is available. A second client (another BMS or app gateway) blocks the connection.
- Multi-register values must be read or written in one request (function 03/04, or 16 to write); a partial read returns ILLEGAL DATA ADDRESS.
Network setup
- Unit ID 1, TCP port 502.
Watch out for
- The Futura L+ uses a different, shorter address layout; do not use these addresses on an L+.
Jablotron FUTURA L / M / S heat recovery ventilation unit (Modbus TCP) Modbus registers
Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.
| Table | Address | Name | Description | Type | Order | Scale | Units | Access | Values / bits |
|---|---|---|---|---|---|---|---|---|---|
| IR | 0 | Product identification | Always 39 on a Futura. | UINT16 | Read | ||||
| IR | 14 | Device model | UINT16 | Read | 0 = Futura L; 1 = Futura L; 2 = Futura M | ||||
| IR | 15 | Available features (fut_config) | BITMAP16 | Read | bit 0 = Internal heating supported; bit 1 = CoolBreeze cooling available; bit 2 = CoolBreeze heating available; bit 3 = Bypass supported; bit 4 = VarioBreeze supported; bit 5 = Circulation supported; bit 6 = CoolBreeze supported; bit 7 = Exchanger control supported | ||||
| IR | 30 | Ambient air temperature | INT16 | × 0.1 | °C | Read | |||
| IR | 31 | Fresh air temperature | INT16 | × 0.1 | °C | Read | |||
| IR | 32 | Indoor air temperature | INT16 | × 0.1 | °C | Read | |||
| IR | 33 | Waste air temperature | INT16 | × 0.1 | °C | Read | |||
| IR | 34 | Ambient air humidity | Relative humidity. | INT16 | × 0.1 | % | Read | ||
| IR | 35 | Fresh air humidity | Relative humidity. | INT16 | × 0.1 | % | Read | ||
| IR | 36 | Indoor air humidity | Relative humidity. | INT16 | × 0.1 | % | Read | ||
| IR | 37 | Waste air humidity | Relative humidity. | INT16 | × 0.1 | % | Read | ||
| IR | 38 | Outdoor NTC temperature | -99 means the sensor is disconnected. | INT16 | × 0.1 | °C | Read | ||
| IR | 40 | Filter wear level | UINT16 | % | Read | ||||
| IR | 41 | Accumulated power consumption | UINT16 | W | Read | ||||
| IR | 42 | Heat recovering | UINT16 | W | Read | ||||
| IR | 43 | Internal heating power | UINT16 | W | Read | ||||
| IR | 44 | Total air flow | Supply plus exhaust air flow. | UINT16 | m3/h | Read | |||
| IR | 45 | Supply fan power | UINT16 | % | Read | ||||
| IR | 46 | Exhaust fan power | UINT16 | % | Read | ||||
| IR | 47 | Supply fan speed | UINT16 | rpm | Read | ||||
| IR | 48 | Exhaust fan speed | UINT16 | rpm | Read | ||||
| IR | 49 | Universal input 1 voltage | UINT16 | mV | Read | ||||
| IR | 50 | Universal input 2 voltage | UINT16 | mV | Read | ||||
| IR | 51 | Digital inputs | BITMAP16 | Read | bit 0 = User button; bit 1 = Factory button; bit 2 = Boost input; bit 3 = Universal input 1; bit 4 = Universal input 2 | ||||
| IR | 66 | Connected wall controllers | Bits 0-2, one per wall-mounted controller. | BITMAP16 | Read | bit 0 = Wall controller 1 connected; bit 1 = Wall controller 2 connected; bit 2 = Wall controller 3 connected | |||
| IR | 69 | CoolBreeze connected | UINT16 | Read | 0 = No; 1 = Yes | ||||
| IR | 74 | Connected buttons | Bits 0-15, one per button. | BITMAP16 | Read | bit 0 = Button 1 connected; bit 1 = Button 2 connected; bit 2 = Button 3 connected; bit 3 = Button 4 connected; bit 4 = Button 5 connected; bit 5 = Button 6 connected; bit 6 = Button 7 connected; bit 7 = Button 8 connected; bit 8 = Button 9 connected; bit 9 = Button 10 connected; bit 10 = Button 11 connected; bit 11 = Button 12 connected; bit 12 = Button 13 connected; bit 13 = Button 14 connected; bit 14 = Button 15 connected; bit 15 = Button 16 connected | |||
| IR | 75 | Connected UI ALFA units | Bits 0-15, one per ALFA unit. | BITMAP16 | Read | bit 0 = UI ALFA 1 connected; bit 1 = UI ALFA 2 connected; bit 2 = UI ALFA 3 connected; bit 3 = UI ALFA 4 connected; bit 4 = UI ALFA 5 connected; bit 5 = UI ALFA 6 connected; bit 6 = UI ALFA 7 connected; bit 7 = UI ALFA 8 connected; bit 8 = UI ALFA 9 connected; bit 9 = UI ALFA 10 connected; bit 10 = UI ALFA 11 connected; bit 11 = UI ALFA 12 connected; bit 12 = UI ALFA 13 connected; bit 13 = UI ALFA 14 connected; bit 14 = UI ALFA 15 connected; bit 15 = UI ALFA 16 connected | |||
| IR | 100 | Wall UI 1 Modbus address | 0 = not connected. | UINT16 | Read | ||||
| IR | 102 | Wall UI 1 CO2 | UINT16 | ppm | Read | ||||
| IR | 103 | Wall UI 1 temperature | INT16 | × 0.1 | °C | Read | |||
| IR | 104 | Wall UI 1 humidity | UINT16 | × 0.1 | % | Read | |||
| IR | 105 | Wall UI 2 Modbus address | 0 = not connected. | UINT16 | Read | ||||
| IR | 107 | Wall UI 2 CO2 | UINT16 | ppm | Read | ||||
| IR | 108 | Wall UI 2 temperature | INT16 | × 0.1 | °C | Read | |||
| IR | 109 | Wall UI 2 humidity | UINT16 | × 0.1 | % | Read | |||
| IR | 110 | Wall UI 3 Modbus address | 0 = not connected. | UINT16 | Read | ||||
| IR | 112 | Wall UI 3 CO2 | UINT16 | ppm | Read | ||||
| IR | 113 | Wall UI 3 temperature | INT16 | × 0.1 | °C | Read | |||
| IR | 114 | Wall UI 3 humidity | UINT16 | × 0.1 | % | Read | |||
| IR | 115 | Wall sensor 1 Modbus address | 0 = not connected. | UINT16 | Read | ||||
| IR | 117 | Wall sensor 1 CO2 | UINT16 | ppm | Read | ||||
| IR | 118 | Wall sensor 1 temperature | INT16 | × 0.1 | °C | Read | |||
| IR | 119 | Wall sensor 1 humidity | UINT16 | × 0.1 | % | Read | |||
| IR | 120 | Wall sensor 2 Modbus address | 0 = not connected. | UINT16 | Read | ||||
| IR | 122 | Wall sensor 2 CO2 | UINT16 | ppm | Read | ||||
| IR | 123 | Wall sensor 2 temperature | INT16 | × 0.1 | °C | Read | |||
| IR | 124 | Wall sensor 2 humidity | UINT16 | × 0.1 | % | Read | |||
| IR | 125 | Wall sensor 3 Modbus address | 0 = not connected. | UINT16 | Read | ||||
| IR | 127 | Wall sensor 3 CO2 | UINT16 | ppm | Read | ||||
| IR | 128 | Wall sensor 3 temperature | INT16 | × 0.1 | °C | Read | |||
| IR | 129 | Wall sensor 3 humidity | UINT16 | × 0.1 | % | Read | |||
| IR | 130 | Wall sensor 4 Modbus address | 0 = not connected. | UINT16 | Read | ||||
| IR | 132 | Wall sensor 4 CO2 | UINT16 | ppm | Read | ||||
| IR | 133 | Wall sensor 4 temperature | INT16 | × 0.1 | °C | Read | |||
| IR | 134 | Wall sensor 4 humidity | UINT16 | × 0.1 | % | Read | |||
| IR | 135 | Wall sensor 5 Modbus address | 0 = not connected. | UINT16 | Read | ||||
| IR | 137 | Wall sensor 5 CO2 | UINT16 | ppm | Read | ||||
| IR | 138 | Wall sensor 5 temperature | INT16 | × 0.1 | °C | Read | |||
| IR | 139 | Wall sensor 5 humidity | UINT16 | × 0.1 | % | Read | |||
| IR | 140 | Wall sensor 6 Modbus address | 0 = not connected. | UINT16 | Read | ||||
| IR | 142 | Wall sensor 6 CO2 | UINT16 | ppm | Read | ||||
| IR | 143 | Wall sensor 6 temperature | INT16 | × 0.1 | °C | Read | |||
| IR | 144 | Wall sensor 6 humidity | UINT16 | × 0.1 | % | Read | |||
| IR | 145 | Wall sensor 7 Modbus address | 0 = not connected. | UINT16 | Read | ||||
| IR | 147 | Wall sensor 7 CO2 | UINT16 | ppm | Read | ||||
| IR | 148 | Wall sensor 7 temperature | INT16 | × 0.1 | °C | Read | |||
| IR | 149 | Wall sensor 7 humidity | UINT16 | × 0.1 | % | Read | |||
| IR | 150 | Wall sensor 8 Modbus address | 0 = not connected. | UINT16 | Read | ||||
| IR | 152 | Wall sensor 8 CO2 | UINT16 | ppm | Read | ||||
| IR | 153 | Wall sensor 8 temperature | INT16 | × 0.1 | °C | Read | |||
| IR | 154 | Wall sensor 8 humidity | UINT16 | × 0.1 | % | Read | |||
| IR | 160 | ALFA 1 Modbus address | 0 = not connected. | UINT16 | Read | ||||
| IR | 162 | ALFA 1 CO2 | UINT16 | ppm | Read | ||||
| IR | 163 | ALFA 1 temperature | INT16 | × 0.1 | °C | Read | |||
| IR | 164 | ALFA 1 humidity | UINT16 | × 0.1 | % | Read | |||
| IR | 165 | ALFA 1 NTC temperature | UINT16 | × 0.1 | °C | Read | |||
| IR | 170 | ALFA 2 Modbus address | 0 = not connected. | UINT16 | Read | ||||
| IR | 172 | ALFA 2 CO2 | UINT16 | ppm | Read | ||||
| IR | 173 | ALFA 2 temperature | INT16 | × 0.1 | °C | Read | |||
| IR | 174 | ALFA 2 humidity | UINT16 | × 0.1 | % | Read | |||
| IR | 175 | ALFA 2 NTC temperature | UINT16 | × 0.1 | °C | Read | |||
| IR | 180 | ALFA 3 Modbus address | 0 = not connected. | UINT16 | Read | ||||
| IR | 182 | ALFA 3 CO2 | UINT16 | ppm | Read | ||||
| IR | 183 | ALFA 3 temperature | INT16 | × 0.1 | °C | Read | |||
| IR | 184 | ALFA 3 humidity | UINT16 | × 0.1 | % | Read | |||
| IR | 185 | ALFA 3 NTC temperature | UINT16 | × 0.1 | °C | Read | |||
| IR | 190 | ALFA 4 Modbus address | 0 = not connected. | UINT16 | Read | ||||
| IR | 192 | ALFA 4 CO2 | UINT16 | ppm | Read | ||||
| IR | 193 | ALFA 4 temperature | INT16 | × 0.1 | °C | Read | |||
| IR | 194 | ALFA 4 humidity | UINT16 | × 0.1 | % | Read | |||
| IR | 195 | ALFA 4 NTC temperature | UINT16 | × 0.1 | °C | Read | |||
| IR | 200 | ALFA 5 Modbus address | 0 = not connected. | UINT16 | Read | ||||
| IR | 202 | ALFA 5 CO2 | UINT16 | ppm | Read | ||||
| IR | 203 | ALFA 5 temperature | INT16 | × 0.1 | °C | Read | |||
| IR | 204 | ALFA 5 humidity | UINT16 | × 0.1 | % | Read | |||
| IR | 205 | ALFA 5 NTC temperature | UINT16 | × 0.1 | °C | Read | |||
| IR | 210 | ALFA 6 Modbus address | 0 = not connected. | UINT16 | Read | ||||
| IR | 212 | ALFA 6 CO2 | UINT16 | ppm | Read | ||||
| IR | 213 | ALFA 6 temperature | INT16 | × 0.1 | °C | Read | |||
| IR | 214 | ALFA 6 humidity | UINT16 | × 0.1 | % | Read | |||
| IR | 215 | ALFA 6 NTC temperature | UINT16 | × 0.1 | °C | Read | |||
| IR | 220 | ALFA 7 Modbus address | 0 = not connected. | UINT16 | Read | ||||
| IR | 222 | ALFA 7 CO2 | UINT16 | ppm | Read | ||||
| IR | 223 | ALFA 7 temperature | INT16 | × 0.1 | °C | Read | |||
| IR | 224 | ALFA 7 humidity | UINT16 | × 0.1 | % | Read | |||
| IR | 225 | ALFA 7 NTC temperature | UINT16 | × 0.1 | °C | Read | |||
| IR | 230 | ALFA 8 Modbus address | 0 = not connected. | UINT16 | Read | ||||
| IR | 232 | ALFA 8 CO2 | UINT16 | ppm | Read | ||||
| IR | 233 | ALFA 8 temperature | INT16 | × 0.1 | °C | Read | |||
| IR | 234 | ALFA 8 humidity | UINT16 | × 0.1 | % | Read | |||
| IR | 235 | ALFA 8 NTC temperature | UINT16 | × 0.1 | °C | Read | |||
| HR | 0 | Ventilation mode | UINT16 | Read/write | 0 = Off; 1 = Manual 1; 2 = Manual 2; 3 = Manual 3; 4 = Manual 4; 5 = Manual 5; 6 = Auto | ||||
| HR | 1 | Boost timer | Read remaining time; write 0-7200 s to start. | UINT16 | s | Read/write | |||
| HR | 2 | Circulation timer | Read remaining time; write 0-21600 s to start. | UINT16 | s | Read/write | |||
| HR | 3 | Overpressure timer | Read remaining time; write 0-7200 s to start. | UINT16 | s | Read/write | |||
| HR | 4 | Night timer | Read remaining time; write 0-28800 s to start. | UINT16 | s | Read/write | |||
| HR | 5 | Party timer | Read remaining time; write 0-28800 s to start. | UINT16 | s | Read/write | |||
| HR | 10 | Preferred temperature | UINT16 | × 0.1 | °C | Read/write | |||
| HR | 12 | Time program enable | UINT16 | Read/write | 0 = Off; 1 = On | ||||
| HR | 13 | Antiradon enable | UINT16 | Read/write | 0 = Off; 1 = On | ||||
| HR | 14 | Automatic bypass enable | UINT16 | Read/write | 0 = Off; 1 = On | ||||
| HR | 15 | Heating enable | UINT16 | Read/write | 0 = Off; 1 = On | ||||
| HR | 16 | Cooling enable | UINT16 | Read/write | 0 = Off; 1 = On | ||||
| HR | 17 | Comfort heating enable | Comfort heating only works with heating enabled. | UINT16 | Read/write | 0 = Off; 1 = On | |||
| HR | 18 | Automatic circulation enable | UINT16 | Read/write | 0 = Off; 1 = On | ||||
| HR | 20 | Zone control priority with CoolBreeze | UINT16 | Read/write | 0 = Temperature; 1 = CO2 | ||||
| HR | 21 | Kitchen hood normal position | UINT16 | Read/write | 0 = Closed; 1 = Open | ||||
| HR | 22 | Zone boost volume per run | 50-150 m3/h, default 50. | UINT16 | m3/h | Read/write | |||
| HR | 23 | Kitchen hood volume per run | 50-150 m3/h, default 120. | UINT16 | m3/h | Read/write | |||
| HR | 300 | External sensor 1 present | UINT16 | Read/write | 0 = Off; 1 = On | ||||
| HR | 302 | External sensor 1 temperature | Value written by the master; -20 to 100 °C. | INT16 | × 0.1 | °C | Read/write | ||
| HR | 303 | External sensor 1 humidity | Value written by the master; 0-100 %. | UINT16 | % | Read/write | |||
| HR | 304 | External sensor 1 CO2 | Value written by the master; 0-10000 ppm. | UINT16 | ppm | Read/write | |||
| HR | 310 | External sensor 2 present | UINT16 | Read/write | 0 = Off; 1 = On | ||||
| HR | 312 | External sensor 2 temperature | Value written by the master; -20 to 100 °C. | INT16 | × 0.1 | °C | Read/write | ||
| HR | 313 | External sensor 2 humidity | Value written by the master; 0-100 %. | UINT16 | % | Read/write | |||
| HR | 314 | External sensor 2 CO2 | Value written by the master; 0-10000 ppm. | UINT16 | ppm | Read/write | |||
| HR | 320 | External sensor 3 present | UINT16 | Read/write | 0 = Off; 1 = On | ||||
| HR | 322 | External sensor 3 temperature | Value written by the master; -20 to 100 °C. | INT16 | × 0.1 | °C | Read/write | ||
| HR | 323 | External sensor 3 humidity | Value written by the master; 0-100 %. | UINT16 | % | Read/write | |||
| HR | 324 | External sensor 3 CO2 | Value written by the master; 0-10000 ppm. | UINT16 | ppm | Read/write | |||
| HR | 330 | External sensor 4 present | UINT16 | Read/write | 0 = Off; 1 = On | ||||
| HR | 332 | External sensor 4 temperature | Value written by the master; -20 to 100 °C. | INT16 | × 0.1 | °C | Read/write | ||
| HR | 333 | External sensor 4 humidity | Value written by the master; 0-100 %. | UINT16 | % | Read/write | |||
| HR | 334 | External sensor 4 CO2 | Value written by the master; 0-10000 ppm. | UINT16 | ppm | Read/write | |||
| HR | 340 | External sensor 5 present | UINT16 | Read/write | 0 = Off; 1 = On | ||||
| HR | 342 | External sensor 5 temperature | Value written by the master; -20 to 100 °C. | INT16 | × 0.1 | °C | Read/write | ||
| HR | 343 | External sensor 5 humidity | Value written by the master; 0-100 %. | UINT16 | % | Read/write | |||
| HR | 344 | External sensor 5 CO2 | Value written by the master; 0-10000 ppm. | UINT16 | ppm | Read/write | |||
| HR | 350 | External sensor 6 present | UINT16 | Read/write | 0 = Off; 1 = On | ||||
| HR | 352 | External sensor 6 temperature | Value written by the master; -20 to 100 °C. | INT16 | × 0.1 | °C | Read/write | ||
| HR | 353 | External sensor 6 humidity | Value written by the master; 0-100 %. | UINT16 | % | Read/write | |||
| HR | 354 | External sensor 6 CO2 | Value written by the master; 0-10000 ppm. | UINT16 | ppm | Read/write | |||
| HR | 360 | External sensor 7 present | UINT16 | Read/write | 0 = Off; 1 = On | ||||
| HR | 362 | External sensor 7 temperature | Value written by the master; -20 to 100 °C. | INT16 | × 0.1 | °C | Read/write | ||
| HR | 363 | External sensor 7 humidity | Value written by the master; 0-100 %. | UINT16 | % | Read/write | |||
| HR | 364 | External sensor 7 CO2 | Value written by the master; 0-10000 ppm. | UINT16 | ppm | Read/write | |||
| HR | 370 | External sensor 8 present | UINT16 | Read/write | 0 = Off; 1 = On | ||||
| HR | 372 | External sensor 8 temperature | Value written by the master; -20 to 100 °C. | INT16 | × 0.1 | °C | Read/write | ||
| HR | 373 | External sensor 8 humidity | Value written by the master; 0-100 %. | UINT16 | % | Read/write | |||
| HR | 374 | External sensor 8 CO2 | Value written by the master; 0-10000 ppm. | UINT16 | ppm | Read/write |
Notes on this map
- Jablotron does not appear to host this list publicly; the link is the unaltered maker document as mirrored by the integrator TapHome.
- Left out: every 32-bit register (serial number, firmware revision, operation-mode, error and warning words at 16-21, away start/end timestamps, Modbus counters, connected-device masks). The list does not say which register holds the high word.
- Left out: preferred humidity (holding 11), whose unit is printed as 0.1 % while its values are listed as 25/50/75; the backup battery voltage (unit printed as 0.001 mV); the per-device options bit registers; sensor corrections; external sensor invalidate and floor temperature; external buttons; and the service/password registers 900-922.
- Wall UI blocks repeat every 5 registers from 100 (3 units), wall sensors every 5 from 115 (8 units), ALFA units every 10 from 160 (8 units). External sensor values written by the master repeat every 10 from 300 (8 sensors). The zone CO2/temperature block at 100-173 exists only on the L+ and is not listed.
Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.
Questions about the Jablotron FUTURA L / M / S heat recovery ventilation unit (Modbus TCP)
What Modbus registers does the Jablotron FUTURA L / M / S heat recovery ventilation unit (Modbus TCP) have?
This map lists 162 registers: 112 input registers, 50 holding registers. 50 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.
Are the Jablotron FUTURA L / M / S heat recovery ventilation unit (Modbus TCP) Modbus addresses 0-based or 1-based?
The manufacturer's document numbers registers 0-based (the number printed is the address on the wire). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. Addresses are printed as protocol addresses and start at 0 (input register 0 is the product ID), so they are sent unchanged.
What are the minimum Modbus registers to integrate the Jablotron FUTURA L / M / S heat recovery ventilation unit (Modbus TCP)?
Start with IR 30 Ambient air temperature (Ambient (outdoor intake) air temperature); IR 32 Indoor air temperature (Indoor air temperature); IR 36 Indoor air humidity (Indoor humidity); IR 40 Filter wear level (Filter wear); IR 44 Total air flow (Total air flow); HR 0 Ventilation mode (Ventilation mode); HR 1 Boost timer (Boost timer); HR 10 Preferred temperature (Temperature setpoint).
How do I enable Modbus control of the Jablotron FUTURA L / M / S heat recovery ventilation unit (Modbus TCP)?
The Modbus TCP server is built in; no enable step is documented.
Where is the official Jablotron FUTURA L / M / S heat recovery ventilation unit (Modbus TCP) Modbus documentation?
The source is JABLOTRON FUTURA MODBUS TCP (Document version 5.0), revision 2025-10-13. Jablotron doesn't publish it on its own website, so this map was re-typed from a free copy at https://taphome.com/compatibility/devices/jablotron-futura/manufacturer/FU_TCP_TXT_EN.pdf. It may be an older revision, so check it against the live unit.
Other hvac equipment register maps
- Thermostat (room operating unit with sensors)
LOYTEC L-STAT network thermostat / room operating unit (Modbus RTU)
LSTAT-800/801/802 room operating units (all button layouts), user manual version 3.2.8 (document 88085811).
Also known as: L-STAT, LSTAT-800, LSTAT-801, LSTAT-802, LSTAT-800-Gx-Lx, LSTAT-801-Gx-Lx, LSTAT-802-Gx-Lx - Thermostat / fan coil controller
Neptronic EFCB Series networkable fan coil controller (Modbus RTU)
Neptronic EFCB Series fan coil controllers (24, 120 and 240 Vac; 2 or 4 relays) with the Modbus communication module, guide EFCB-Modbus Guide-260626.
Also known as: EFCB10TU2, EFCB10TU4, EFCB11TU2, EFCB11TU4, EFCB12TU2, EFCB12TU4, EFCB fan coil controller - Air handler evaporative cooler (adiabatic cooling / humidification)
Neptronic SKVF evaporative cooler / humidifier (Modbus communication module)
Neptronic SKVF series evaporative coolers with the Modbus communication module, guide SKVF-Modbus Guide-211025.
Also known as: SKVF Evaporative Cooler, SKVF Series, Neptronic SKVF Modbus - Thermostat / room controller (chilled beam, fan coil water circuits)
Swegon CONDUCTOR W1 room controller (waterborne cooling/heating, Modbus RTU)
Swegon CONDUCTOR W1 room controller, software 1.38 and later (technical manual updated 2015-06-15).
Also known as: CONDUCTOR RE W1, Conductor W1, 942334001 - Air handler (residential heat recovery ventilation)
Vasco SAB RVU ventilation unit controller (D150 Compact, Energy Plus)
Vasco SAB RVU controller boards (models 0x52xx residential and 0x53xx Energy Plus) with protocol release 0x0006, manual 90.01.06.53.
Also known as: D150 Compact, Energy Plus ENY-P1, ENY-P2, ENY-P3, ENY-P4, ESP170V, ESP270, ESP360, ESP460 - Air handler (in-row data-centre cooling unit)
APC (Schneider Electric) InRow ACRD60x / ACRC60x cooling units (Modbus register map 990-5786)
APC / Schneider Electric InRow ACRD60x and ACRC60x in-row cooling units, register map part number 990-5786A.
Also known as: ACRD60x, ACRC60x, InRow ACRD60x, InRow ACRC60x, 990-5786
All hvac equipment Modbus register maps →
Source: JABLOTRON FUTURA MODBUS TCP · Document version 5.0 · rev. 2025-10-13 · unofficial copy. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.