  4. FUTURA L / M / S heat recovery ventilation unit (Modbus TCP)

Air handler (heat recovery ventilation unit) · Modbus register map

Jablotron FUTURA L / M / S heat recovery ventilation unit (Modbus TCP) Modbus register map

Updated 17 November 2026

Short answer

The FUTURA is a residential heat recovery ventilation unit with a built-in Modbus TCP server. Input registers give air temperatures, humidity, fan data, power and connected room-sensor values; holding registers set the ventilation mode, timed functions, setpoints and external sensor values. This page lists the 16-bit registers of the Futura L/M/S layout.

This page lists 162 Modbus registers for the Jablotron FUTURA L / M / S heat recovery ventilation unit (Modbus TCP) — 50 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Jablotron’s own free documentation (linked below) and checked against it.

Manufacturer
Jablotron
Model
FUTURA L / M / S heat recovery ventilation unit (Modbus TCP)
Equipment type
Air handler (heat recovery ventilation unit)
Registers
162 (50 writable)
Transport
Modbus TCP
Default unit ID
1
TCP port
502
Documented addressing
0-based (the number printed is the address on the wire)
Firmware
FUA.P.06.71 or later (Futura L/M/S)
Also known as
Futura L, Futura M, Futura S, JABLOTRON FUTURA
Source document
JABLOTRON FUTURA MODBUS TCP · Document version 5.0 · rev. 2025-10-13 · unofficial copy
Download CSV all columns JSON Manufacturer PDF ↗

Integration notes: Jablotron FUTURA L / M / S heat recovery ventilation unit (Modbus TCP)

Integration in brief

Connect over Modbus TCP to port 502, unit ID 1. Read input registers 30-48 with function 04 for temperatures, humidity and fans, and write holding register 0 for the ventilation mode or 1-5 to start timed boost, circulation, overpressure, night or party functions.

Minimum registers to map

Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.

RegisterNameTypeWhyAccess
IR 30Ambient air temperatureINT16Ambient (outdoor intake) air temperatureRead
IR 32Indoor air temperatureINT16Indoor air temperatureRead
IR 36Indoor air humidityINT16Indoor humidityRead
IR 40Filter wear levelUINT16Filter wearRead
IR 44Total air flowUINT16Total air flowRead
HR 0Ventilation modeUINT16Ventilation modeRead/write
HR 1Boost timerUINT16Boost timerRead/write
HR 10Preferred temperatureUINT16Temperature setpointRead/write

Enable Modbus control & writes

The Modbus TCP server is built in; no enable step is documented.

Byte order & addressing

Network setup

Watch out for

Jablotron FUTURA L / M / S heat recovery ventilation unit (Modbus TCP) Modbus registers

Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.

162 of 162 shown
Jablotron FUTURA L / M / S heat recovery ventilation unit (Modbus TCP) Modbus register map
TableAddressNameDescriptionTypeOrderScaleUnitsAccessValues / bits
IR0Product identificationAlways 39 on a Futura.UINT16Read
IR14Device modelUINT16Read0 = Futura L; 1 = Futura L; 2 = Futura M
IR15Available features (fut_config)BITMAP16Readbit 0 = Internal heating supported; bit 1 = CoolBreeze cooling available; bit 2 = CoolBreeze heating available; bit 3 = Bypass supported; bit 4 = VarioBreeze supported; bit 5 = Circulation supported; bit 6 = CoolBreeze supported; bit 7 = Exchanger control supported
IR30Ambient air temperatureINT16× 0.1°CRead
IR31Fresh air temperatureINT16× 0.1°CRead
IR32Indoor air temperatureINT16× 0.1°CRead
IR33Waste air temperatureINT16× 0.1°CRead
IR34Ambient air humidityRelative humidity.INT16× 0.1%Read
IR35Fresh air humidityRelative humidity.INT16× 0.1%Read
IR36Indoor air humidityRelative humidity.INT16× 0.1%Read
IR37Waste air humidityRelative humidity.INT16× 0.1%Read
IR38Outdoor NTC temperature-99 means the sensor is disconnected.INT16× 0.1°CRead
IR40Filter wear levelUINT16%Read
IR41Accumulated power consumptionUINT16WRead
IR42Heat recoveringUINT16WRead
IR43Internal heating powerUINT16WRead
IR44Total air flowSupply plus exhaust air flow.UINT16m3/hRead
IR45Supply fan powerUINT16%Read
IR46Exhaust fan powerUINT16%Read
IR47Supply fan speedUINT16rpmRead
IR48Exhaust fan speedUINT16rpmRead
IR49Universal input 1 voltageUINT16mVRead
IR50Universal input 2 voltageUINT16mVRead
IR51Digital inputsBITMAP16Readbit 0 = User button; bit 1 = Factory button; bit 2 = Boost input; bit 3 = Universal input 1; bit 4 = Universal input 2
IR66Connected wall controllersBits 0-2, one per wall-mounted controller.BITMAP16Readbit 0 = Wall controller 1 connected; bit 1 = Wall controller 2 connected; bit 2 = Wall controller 3 connected
IR69CoolBreeze connectedUINT16Read0 = No; 1 = Yes
IR74Connected buttonsBits 0-15, one per button.BITMAP16Readbit 0 = Button 1 connected; bit 1 = Button 2 connected; bit 2 = Button 3 connected; bit 3 = Button 4 connected; bit 4 = Button 5 connected; bit 5 = Button 6 connected; bit 6 = Button 7 connected; bit 7 = Button 8 connected; bit 8 = Button 9 connected; bit 9 = Button 10 connected; bit 10 = Button 11 connected; bit 11 = Button 12 connected; bit 12 = Button 13 connected; bit 13 = Button 14 connected; bit 14 = Button 15 connected; bit 15 = Button 16 connected
IR75Connected UI ALFA unitsBits 0-15, one per ALFA unit.BITMAP16Readbit 0 = UI ALFA 1 connected; bit 1 = UI ALFA 2 connected; bit 2 = UI ALFA 3 connected; bit 3 = UI ALFA 4 connected; bit 4 = UI ALFA 5 connected; bit 5 = UI ALFA 6 connected; bit 6 = UI ALFA 7 connected; bit 7 = UI ALFA 8 connected; bit 8 = UI ALFA 9 connected; bit 9 = UI ALFA 10 connected; bit 10 = UI ALFA 11 connected; bit 11 = UI ALFA 12 connected; bit 12 = UI ALFA 13 connected; bit 13 = UI ALFA 14 connected; bit 14 = UI ALFA 15 connected; bit 15 = UI ALFA 16 connected
IR100Wall UI 1 Modbus address0 = not connected.UINT16Read
IR102Wall UI 1 CO2UINT16ppmRead
IR103Wall UI 1 temperatureINT16× 0.1°CRead
IR104Wall UI 1 humidityUINT16× 0.1%Read
IR105Wall UI 2 Modbus address0 = not connected.UINT16Read
IR107Wall UI 2 CO2UINT16ppmRead
IR108Wall UI 2 temperatureINT16× 0.1°CRead
IR109Wall UI 2 humidityUINT16× 0.1%Read
IR110Wall UI 3 Modbus address0 = not connected.UINT16Read
IR112Wall UI 3 CO2UINT16ppmRead
IR113Wall UI 3 temperatureINT16× 0.1°CRead
IR114Wall UI 3 humidityUINT16× 0.1%Read
IR115Wall sensor 1 Modbus address0 = not connected.UINT16Read
IR117Wall sensor 1 CO2UINT16ppmRead
IR118Wall sensor 1 temperatureINT16× 0.1°CRead
IR119Wall sensor 1 humidityUINT16× 0.1%Read
IR120Wall sensor 2 Modbus address0 = not connected.UINT16Read
IR122Wall sensor 2 CO2UINT16ppmRead
IR123Wall sensor 2 temperatureINT16× 0.1°CRead
IR124Wall sensor 2 humidityUINT16× 0.1%Read
IR125Wall sensor 3 Modbus address0 = not connected.UINT16Read
IR127Wall sensor 3 CO2UINT16ppmRead
IR128Wall sensor 3 temperatureINT16× 0.1°CRead
IR129Wall sensor 3 humidityUINT16× 0.1%Read
IR130Wall sensor 4 Modbus address0 = not connected.UINT16Read
IR132Wall sensor 4 CO2UINT16ppmRead
IR133Wall sensor 4 temperatureINT16× 0.1°CRead
IR134Wall sensor 4 humidityUINT16× 0.1%Read
IR135Wall sensor 5 Modbus address0 = not connected.UINT16Read
IR137Wall sensor 5 CO2UINT16ppmRead
IR138Wall sensor 5 temperatureINT16× 0.1°CRead
IR139Wall sensor 5 humidityUINT16× 0.1%Read
IR140Wall sensor 6 Modbus address0 = not connected.UINT16Read
IR142Wall sensor 6 CO2UINT16ppmRead
IR143Wall sensor 6 temperatureINT16× 0.1°CRead
IR144Wall sensor 6 humidityUINT16× 0.1%Read
IR145Wall sensor 7 Modbus address0 = not connected.UINT16Read
IR147Wall sensor 7 CO2UINT16ppmRead
IR148Wall sensor 7 temperatureINT16× 0.1°CRead
IR149Wall sensor 7 humidityUINT16× 0.1%Read
IR150Wall sensor 8 Modbus address0 = not connected.UINT16Read
IR152Wall sensor 8 CO2UINT16ppmRead
IR153Wall sensor 8 temperatureINT16× 0.1°CRead
IR154Wall sensor 8 humidityUINT16× 0.1%Read
IR160ALFA 1 Modbus address0 = not connected.UINT16Read
IR162ALFA 1 CO2UINT16ppmRead
IR163ALFA 1 temperatureINT16× 0.1°CRead
IR164ALFA 1 humidityUINT16× 0.1%Read
IR165ALFA 1 NTC temperatureUINT16× 0.1°CRead
IR170ALFA 2 Modbus address0 = not connected.UINT16Read
IR172ALFA 2 CO2UINT16ppmRead
IR173ALFA 2 temperatureINT16× 0.1°CRead
IR174ALFA 2 humidityUINT16× 0.1%Read
IR175ALFA 2 NTC temperatureUINT16× 0.1°CRead
IR180ALFA 3 Modbus address0 = not connected.UINT16Read
IR182ALFA 3 CO2UINT16ppmRead
IR183ALFA 3 temperatureINT16× 0.1°CRead
IR184ALFA 3 humidityUINT16× 0.1%Read
IR185ALFA 3 NTC temperatureUINT16× 0.1°CRead
IR190ALFA 4 Modbus address0 = not connected.UINT16Read
IR192ALFA 4 CO2UINT16ppmRead
IR193ALFA 4 temperatureINT16× 0.1°CRead
IR194ALFA 4 humidityUINT16× 0.1%Read
IR195ALFA 4 NTC temperatureUINT16× 0.1°CRead
IR200ALFA 5 Modbus address0 = not connected.UINT16Read
IR202ALFA 5 CO2UINT16ppmRead
IR203ALFA 5 temperatureINT16× 0.1°CRead
IR204ALFA 5 humidityUINT16× 0.1%Read
IR205ALFA 5 NTC temperatureUINT16× 0.1°CRead
IR210ALFA 6 Modbus address0 = not connected.UINT16Read
IR212ALFA 6 CO2UINT16ppmRead
IR213ALFA 6 temperatureINT16× 0.1°CRead
IR214ALFA 6 humidityUINT16× 0.1%Read
IR215ALFA 6 NTC temperatureUINT16× 0.1°CRead
IR220ALFA 7 Modbus address0 = not connected.UINT16Read
IR222ALFA 7 CO2UINT16ppmRead
IR223ALFA 7 temperatureINT16× 0.1°CRead
IR224ALFA 7 humidityUINT16× 0.1%Read
IR225ALFA 7 NTC temperatureUINT16× 0.1°CRead
IR230ALFA 8 Modbus address0 = not connected.UINT16Read
IR232ALFA 8 CO2UINT16ppmRead
IR233ALFA 8 temperatureINT16× 0.1°CRead
IR234ALFA 8 humidityUINT16× 0.1%Read
IR235ALFA 8 NTC temperatureUINT16× 0.1°CRead
HR0Ventilation modeUINT16Read/write0 = Off; 1 = Manual 1; 2 = Manual 2; 3 = Manual 3; 4 = Manual 4; 5 = Manual 5; 6 = Auto
HR1Boost timerRead remaining time; write 0-7200 s to start.UINT16sRead/write
HR2Circulation timerRead remaining time; write 0-21600 s to start.UINT16sRead/write
HR3Overpressure timerRead remaining time; write 0-7200 s to start.UINT16sRead/write
HR4Night timerRead remaining time; write 0-28800 s to start.UINT16sRead/write
HR5Party timerRead remaining time; write 0-28800 s to start.UINT16sRead/write
HR10Preferred temperatureUINT16× 0.1°CRead/write
HR12Time program enableUINT16Read/write0 = Off; 1 = On
HR13Antiradon enableUINT16Read/write0 = Off; 1 = On
HR14Automatic bypass enableUINT16Read/write0 = Off; 1 = On
HR15Heating enableUINT16Read/write0 = Off; 1 = On
HR16Cooling enableUINT16Read/write0 = Off; 1 = On
HR17Comfort heating enableComfort heating only works with heating enabled.UINT16Read/write0 = Off; 1 = On
HR18Automatic circulation enableUINT16Read/write0 = Off; 1 = On
HR20Zone control priority with CoolBreezeUINT16Read/write0 = Temperature; 1 = CO2
HR21Kitchen hood normal positionUINT16Read/write0 = Closed; 1 = Open
HR22Zone boost volume per run50-150 m3/h, default 50.UINT16m3/hRead/write
HR23Kitchen hood volume per run50-150 m3/h, default 120.UINT16m3/hRead/write
HR300External sensor 1 presentUINT16Read/write0 = Off; 1 = On
HR302External sensor 1 temperatureValue written by the master; -20 to 100 °C.INT16× 0.1°CRead/write
HR303External sensor 1 humidityValue written by the master; 0-100 %.UINT16%Read/write
HR304External sensor 1 CO2Value written by the master; 0-10000 ppm.UINT16ppmRead/write
HR310External sensor 2 presentUINT16Read/write0 = Off; 1 = On
HR312External sensor 2 temperatureValue written by the master; -20 to 100 °C.INT16× 0.1°CRead/write
HR313External sensor 2 humidityValue written by the master; 0-100 %.UINT16%Read/write
HR314External sensor 2 CO2Value written by the master; 0-10000 ppm.UINT16ppmRead/write
HR320External sensor 3 presentUINT16Read/write0 = Off; 1 = On
HR322External sensor 3 temperatureValue written by the master; -20 to 100 °C.INT16× 0.1°CRead/write
HR323External sensor 3 humidityValue written by the master; 0-100 %.UINT16%Read/write
HR324External sensor 3 CO2Value written by the master; 0-10000 ppm.UINT16ppmRead/write
HR330External sensor 4 presentUINT16Read/write0 = Off; 1 = On
HR332External sensor 4 temperatureValue written by the master; -20 to 100 °C.INT16× 0.1°CRead/write
HR333External sensor 4 humidityValue written by the master; 0-100 %.UINT16%Read/write
HR334External sensor 4 CO2Value written by the master; 0-10000 ppm.UINT16ppmRead/write
HR340External sensor 5 presentUINT16Read/write0 = Off; 1 = On
HR342External sensor 5 temperatureValue written by the master; -20 to 100 °C.INT16× 0.1°CRead/write
HR343External sensor 5 humidityValue written by the master; 0-100 %.UINT16%Read/write
HR344External sensor 5 CO2Value written by the master; 0-10000 ppm.UINT16ppmRead/write
HR350External sensor 6 presentUINT16Read/write0 = Off; 1 = On
HR352External sensor 6 temperatureValue written by the master; -20 to 100 °C.INT16× 0.1°CRead/write
HR353External sensor 6 humidityValue written by the master; 0-100 %.UINT16%Read/write
HR354External sensor 6 CO2Value written by the master; 0-10000 ppm.UINT16ppmRead/write
HR360External sensor 7 presentUINT16Read/write0 = Off; 1 = On
HR362External sensor 7 temperatureValue written by the master; -20 to 100 °C.INT16× 0.1°CRead/write
HR363External sensor 7 humidityValue written by the master; 0-100 %.UINT16%Read/write
HR364External sensor 7 CO2Value written by the master; 0-10000 ppm.UINT16ppmRead/write
HR370External sensor 8 presentUINT16Read/write0 = Off; 1 = On
HR372External sensor 8 temperatureValue written by the master; -20 to 100 °C.INT16× 0.1°CRead/write
HR373External sensor 8 humidityValue written by the master; 0-100 %.UINT16%Read/write
HR374External sensor 8 CO2Value written by the master; 0-10000 ppm.UINT16ppmRead/write

Notes on this map

Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.

Questions about the Jablotron FUTURA L / M / S heat recovery ventilation unit (Modbus TCP)

What Modbus registers does the Jablotron FUTURA L / M / S heat recovery ventilation unit (Modbus TCP) have?

This map lists 162 registers: 112 input registers, 50 holding registers. 50 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.

Are the Jablotron FUTURA L / M / S heat recovery ventilation unit (Modbus TCP) Modbus addresses 0-based or 1-based?

The manufacturer's document numbers registers 0-based (the number printed is the address on the wire). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. Addresses are printed as protocol addresses and start at 0 (input register 0 is the product ID), so they are sent unchanged.

What are the minimum Modbus registers to integrate the Jablotron FUTURA L / M / S heat recovery ventilation unit (Modbus TCP)?

Start with IR 30 Ambient air temperature (Ambient (outdoor intake) air temperature); IR 32 Indoor air temperature (Indoor air temperature); IR 36 Indoor air humidity (Indoor humidity); IR 40 Filter wear level (Filter wear); IR 44 Total air flow (Total air flow); HR 0 Ventilation mode (Ventilation mode); HR 1 Boost timer (Boost timer); HR 10 Preferred temperature (Temperature setpoint).

How do I enable Modbus control of the Jablotron FUTURA L / M / S heat recovery ventilation unit (Modbus TCP)?

The Modbus TCP server is built in; no enable step is documented.

Where is the official Jablotron FUTURA L / M / S heat recovery ventilation unit (Modbus TCP) Modbus documentation?

The source is JABLOTRON FUTURA MODBUS TCP (Document version 5.0), revision 2025-10-13. Jablotron doesn't publish it on its own website, so this map was re-typed from a free copy at https://taphome.com/compatibility/devices/jablotron-futura/manufacturer/FU_TCP_TXT_EN.pdf. It may be an older revision, so check it against the live unit.