- CONDUCTOR W1 room controller (waterborne cooling/heating, Modbus RTU)
Thermostat / room controller (chilled beam, fan coil water circuits) · Modbus register map
Swegon CONDUCTOR W1 room controller (waterborne cooling/heating, Modbus RTU) Modbus register map
Updated 19 November 2026
CONDUCTOR W1 is Swegon's room controller for waterborne cooling and heating (chilled beams and similar terminals), working with wireless or wired CONDUCTOR room units. Its Modbus RTU slave port exposes alarms as discrete inputs, economy mode and reboot as coils, sensor temperatures and output signals as input registers, and the application-state request, configuration and PI tuning as holding registers. The temperature setpoints are left out because the manual does not give their scaling.
This page lists 98 Modbus registers for the Swegon CONDUCTOR W1 room controller (waterborne cooling/heating, Modbus RTU) — 24 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Swegon’s own free documentation (linked below) and checked against it.
- Manufacturer
- Swegon
- Model
- CONDUCTOR W1 room controller (waterborne cooling/heating, Modbus RTU)
- Registers
- 98 (24 writable)
- Transport
- Modbus RTU
- Default unit ID
- Not stated
- Documented addressing
- Modicon 3xxxx/4xxxx (drop the prefix, subtract 1)
- Firmware
- 1.38 and later
- Also known as
- CONDUCTOR RE W1, Conductor W1, 942334001
Integration notes: Swegon CONDUCTOR W1 room controller (waterborne cooling/heating, Modbus RTU)
Read input registers 3x0028-3x0030 (temperatures x10) and 3x0022 (application state); write 4x0002 to request a different application state. The setpoints are not in this map because the manual gives no scaling for them.
Minimum registers to map
Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.
| Register | Name | Type | Why | Access |
|---|---|---|---|---|
| IR 27 | Temp sensor regulator | UINT16 | Regulator temperature sensor x10 | Read |
| IR 28 | Temp sensor RU1 | UINT16 | Room unit 1 temperature x10 | Read |
| IR 21 | Application state | UINT16 | Application state | Read |
| HR 1 | Application transition | UINT16 | Application transition (state request) | Read/write |
| IR 52 | Cool Water | UINT16 | Cooling water valve output | Read |
| DI 5 | Active alarms | BIT | Active alarms | Read |
| IR 53 | Warm Water | UINT16 | Warm water valve output | Read |
| IR 62 | Copy of Input Status 1-16 | BITMAP16 | Packed copy of discrete inputs 1-16 | Read |
Enable Modbus control & writes
Set the BMS address, baud, parity and stop bits in system parameters P_101-P_104 from the room unit (service level).
Byte order & addressing
- Reference numbers use the 0x/1x/3x/4x prefix; subtract 1 inside each table.
- Status bits are also packed into 3x0063-3x0066 and coils into 4x0069 for block reads.
Network setup
- RS-485, Modbus RTU; the controller is a slave on the BMS bus.
- Changes to the BMS parameters are made from the CONDUCTOR room unit.
Watch out for
- Many values only matter in a given application state (manual, economy, night cool); check 3x0022 before writing.
- Register numbering differs between the W1, W3 and W4 tables; use the table for the exact model and software.
Swegon CONDUCTOR W1 room controller (waterborne cooling/heating, Modbus RTU) Modbus registers
Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.
| Table | Address | Name | Description | Type | Order | Scale | Units | Access | Values / bits |
|---|---|---|---|---|---|---|---|---|---|
| CO | 4doc 0x0005 | Economy mode | BIT | Read/write | 0 = Unavailable; 1 = Available | ||||
| CO | 7doc 0x0008 | Restart device | Write 1 to force a software reboot. | BIT | Read/write | ||||
| DI | 0doc 1x0001 | Condensation | BIT | Read | |||||
| DI | 1doc 1x0002 | Relay state | BIT | Read | |||||
| DI | 2doc 1x0003 | Occupancy switch | BIT | Read | |||||
| DI | 3doc 1x0004 | Window switch | BIT | Read | |||||
| DI | 4doc 1x0005 | Motion | BIT | Read | |||||
| DI | 5doc 1x0006 | Active alarms | BIT | Read | 0 = No active alarms; 1 = Active alarms | ||||
| DI | 6doc 1x0007 | No Room Unit 1 | Alarm; clears by itself. | BIT | Read | ||||
| DI | 7doc 1x0008 | No Room Unit 2 | Alarm; clears by itself. | BIT | Read | ||||
| DI | 8doc 1x0009 | No Pressure sensor | Alarm; clears by itself. | BIT | Read | ||||
| DI | 9doc 1x0010 | No Supply Flow sensor | Alarm; clears by itself. | BIT | Read | ||||
| DI | 10doc 1x0011 | No Exhaust Flow sensor | Alarm; clears by itself. | BIT | Read | ||||
| DI | 11doc 1x0012 | Room Unit 1 Temperature | Alarm; clears by itself. | BIT | Read | ||||
| DI | 12doc 1x0013 | Room Unit 2 Temperature | Alarm; clears by itself. | BIT | Read | ||||
| DI | 13doc 1x0014 | Regulator KTY short circuit | Alarm; clears by itself. | BIT | Read | ||||
| DI | 14doc 1x0015 | Regulator KTY open circuit | Alarm; clears by itself. | BIT | Read | ||||
| DI | 15doc 1x0016 | Room Unit Low Battery | Alarm; clears by itself. | BIT | Read | ||||
| DI | 16doc 1x0017 | PI-controller overload | Alarm; clears by itself. | BIT | Read | ||||
| DI | 17doc 1x0018 | Setpoint not reached | Alarm; clears by itself. | BIT | Read | ||||
| DI | 20doc 1x0021 | No device list | Alarm; clears by itself. | BIT | Read | ||||
| DI | 21doc 1x0022 | AC overload | Alarm; clears by itself. | BIT | Read | ||||
| DI | 22doc 1x0023 | System fault | Alarm. | BIT | Read | ||||
| DI | 23doc 1x0024 | No serial number | Alarm. | BIT | Read | ||||
| DI | 25doc 1x0026 | Short circuit X11 | Alarm; needs a hardware reset. | BIT | Read | ||||
| DI | 26doc 1x0027 | Short circuit X12 | Alarm; needs a hardware reset. | BIT | Read | ||||
| DI | 27doc 1x0028 | Short circuit X13 | Alarm; needs a hardware reset. | BIT | Read | ||||
| DI | 28doc 1x0029 | Short circuit X14 | Alarm; needs a hardware reset. | BIT | Read | ||||
| DI | 29doc 1x0030 | SPI Flash broken | Alarm; needs a hardware reset. | BIT | Read | ||||
| DI | 30doc 1x0031 | Radio chip broken | Alarm; needs a hardware reset. | BIT | Read | ||||
| DI | 31doc 1x0032 | Parameter file revision | Alarm; needs a hardware reset. | BIT | Read | ||||
| DI | 32doc 1x0033 | Parameter file format | Alarm; needs a hardware reset. | BIT | Read | ||||
| DI | 33doc 1x0034 | No ModBus ID | Alarm; needs a hardware reset. | BIT | Read | ||||
| DI | 34doc 1x0035 | No Application | Alarm; needs a hardware reset. | BIT | Read | ||||
| DI | 35doc 1x0036 | No parameters | Alarm; needs a hardware reset. | BIT | Read | ||||
| DI | 36doc 1x0037 | Parameter missing | Alarm; needs a hardware reset. | BIT | Read | ||||
| DI | 37doc 1x0038 | Parameter value error | Alarm; needs a hardware reset. | BIT | Read | ||||
| DI | 38doc 1x0039 | Parameter file size | Alarm; needs a hardware reset. | BIT | Read | ||||
| DI | 39doc 1x0040 | Wrong parameter file | Alarm; needs a hardware reset. | BIT | Read | ||||
| DI | 40doc 1x0041 | Check Duct Group SM | Alarm; clears once the parameters are corrected. | BIT | Read | ||||
| DI | 41doc 1x0042 | Check Duct Group DC | Alarm; clears once the parameters are corrected. | BIT | Read | ||||
| DI | 42doc 1x0043 | Previous parameters are lost | Alarm; needs a hardware reset. | BIT | Read | ||||
| DI | 43doc 1x0044 | Factory parameters take up | Alarm; needs a hardware reset. | BIT | Read | ||||
| DI | 46doc 1x0047 | No supply pressure from AHU | Alarm; clears by itself. | BIT | Read | ||||
| DI | 47doc 1x0048 | No exhaust pressure from AHU | Alarm; clears by itself. | BIT | Read | ||||
| DI | 48doc 1x0049 | Supply duct 100% open | Alarm; clears by itself. | BIT | Read | ||||
| DI | 49doc 1x0050 | Exhaust duct 100% open | Alarm; clears by itself. | BIT | Read | ||||
| DI | 50doc 1x0051 | Low voltage detect | Alarm; clears by itself. | BIT | Read | ||||
| DI | 52doc 1x0053 | Duct group member missing | Alarm; clears by itself. | BIT | Read | ||||
| DI | 53doc 1x0054 | Negative pressure | Alarm; clears by itself. | BIT | Read | ||||
| IR | 0doc 3x0001 | Component Name ID | Default 00003. Range 0 to 10. | UINT16 | Read | ||||
| IR | 21doc 3x0022 | Application state | UINT16 | Read | 0 = Init; 1 = Auto Normal; 2 = Auto Economy; 3 = Manual; 4 = Stand-by; 5 = Emengency; 6 = NightCool | ||||
| IR | 25doc 3x0026 | Time since last boot (Hours) | Range 0 to 8760. | UINT16 | h | Read | |||
| IR | 26doc 3x0027 | Time since last boot (Minutes) | Range 0 to 60. | UINT16 | min | Read | |||
| IR | 27doc 3x0028 | Temp sensor regulator | UINT16 | × 0.1 | °C | Read | |||
| IR | 28doc 3x0029 | Temp sensor RU1 | UINT16 | × 0.1 | °C | Read | |||
| IR | 29doc 3x0030 | Temp sensor RU2 | UINT16 | × 0.1 | °C | Read | |||
| IR | 32doc 3x0033 | Battery level RU | UINT16 | × 0.1 | V | Read | |||
| IR | 36doc 3x0037 | Input Analog 1 | Range 0 to 10000. | UINT16 | mV | Read | |||
| IR | 37doc 3x0038 | Input Analog 2 | Range 0 to 10000. | UINT16 | mV | Read | |||
| IR | 38doc 3x0039 | Input Analog 3 | Range 0 to 10000. | UINT16 | mV | Read | |||
| IR | 39doc 3x0040 | Input Analog 4 | Range 0 to 10000. | UINT16 | mV | Read | |||
| IR | 40doc 3x0041 | Output PWM 1 | Range 0 to 100. | UINT16 | % | Read | |||
| IR | 41doc 3x0042 | Output PWM 2 | Range 0 to 100. | UINT16 | % | Read | |||
| IR | 42doc 3x0043 | Output PWM 3 | Range 0 to 100. | UINT16 | % | Read | |||
| IR | 43doc 3x0044 | Output PWM 4 | Range 0 to 100. | UINT16 | % | Read | |||
| IR | 44doc 3x0045 | Output Analog 1 | Range 0 to 10000. | UINT16 | mV | Read | |||
| IR | 45doc 3x0046 | Output Analog 2 | Range 0 to 10000. | UINT16 | mV | Read | |||
| IR | 46doc 3x0047 | Output Analog 3 | Range 0 to 10000. | UINT16 | mV | Read | |||
| IR | 47doc 3x0048 | Output Analog 4 | Range 0 to 10000. | UINT16 | mV | Read | |||
| IR | 52doc 3x0053 | Cool Water | Range 0 to 100. | UINT16 | % | Read | |||
| IR | 53doc 3x0054 | Warm Water | Range 0 to 100. | UINT16 | % | Read | |||
| IR | 62doc 3x0063 | Copy of Input Status 1-16 | Same flags as the bit table, packed 16 per register (bit 0 = first item). | BITMAP16 | Read | ||||
| IR | 63doc 3x0064 | Copy of Input Status 17-32 | Same flags as the bit table, packed 16 per register (bit 0 = first item). | BITMAP16 | Read | ||||
| IR | 64doc 3x0065 | Copy of Input Status 33-48 | Same flags as the bit table, packed 16 per register (bit 0 = first item). | BITMAP16 | Read | ||||
| IR | 65doc 3x0066 | Copy of Input Status 49-64 | Same flags as the bit table, packed 16 per register (bit 0 = first item). | BITMAP16 | Read | ||||
| HR | 0doc 4x0001 | Relay in Emergency | UINT16 | Read/write | 0 = Close; 1 = Open; 2 = No Action | ||||
| HR | 1doc 4x0002 | Application transition | Requested application state. | UINT16 | Read/write | 1 = Normal; 3 = Manual; 4 = Stand-by; 5 = Emergency; 6 = NightCool | |||
| HR | 2doc 4x0003 | Room number | UINT16 | Read/write | |||||
| HR | 3doc 4x0004 | Valve exercise | Default 48. Range 0 to 72. | UINT16 | h | Read/write | |||
| HR | 4doc 4x0005 | Motion Timer | Default 20. Range 0 to 20. | UINT16 | min | Read/write | |||
| HR | 5doc 4x0006 | General warning time | Default 60. Range 0 to 60. | UINT16 | min | Read/write | |||
| HR | 6doc 4x0007 | PI-overload warning time | Default 120. Range 0 to 60. | UINT16 | min | Read/write | |||
| HR | 7doc 4x0008 | Set-point warning time | Default 60. Range 0 to 60. | UINT16 | min | Read/write | |||
| HR | 13doc 4x0014 | System type | Default 4. | UINT16 | Read/write | 1 = Heat; 2 = Cool; 3 = Change Over; 4 = Heat+Cool | |||
| HR | 14doc 4x0015 | Number of Room units | Default 1. | UINT16 | Read/write | 1 = One room unit; 2 = Two room units | |||
| HR | 15doc 4x0016 | Window switch | Default 0. | UINT16 | Read/write | 0 = Not used; 1 = Normaly Closed; 2 = Normaly Open | |||
| HR | 16doc 4x0017 | Occupancy switch | Default 0. | UINT16 | Read/write | 0 = Not used; 1 = Normaly Closed; 2 = Normaly Open | |||
| HR | 17doc 4x0018 | Actuator Type Cool | Default 1. | UINT16 | Read/write | 1 = NC; 2 = 0-10V; 3 = NO | |||
| HR | 18doc 4x0019 | Actuator Type Heat | Default 1. | UINT16 | Read/write | 1 = NC; 2 = 0-10V; 3 = NO | |||
| HR | 34doc 4x0035 | RU back to auto state | Default 480. Range 0 to 1200. | UINT16 | Read/write | ||||
| HR | 47doc 4x0048 | P term Heat | Default 3500. Range 10 to 10000. | UINT16 | × 0.01 | Read/write | |||
| HR | 48doc 4x0049 | I term Heat | Default 10. Range 10 to 10000. | UINT16 | × 0.01 | Read/write | |||
| HR | 49doc 4x0050 | P term Cool | Default 3500. Range 10 to 10000. | UINT16 | × 0.01 | Read/write | |||
| HR | 50doc 4x0051 | I term Cool | Default 10. Range 10 to 10000. | UINT16 | × 0.01 | Read/write | |||
| HR | 51doc 4x0052 | P term Change over | Default 5000. Range 10 to 10000. | UINT16 | × 0.01 | Read/write | |||
| HR | 52doc 4x0053 | I term Change over | Default 50. Range 10 to 10000. | UINT16 | × 0.01 | Read/write | |||
| HR | 68doc 4x0069 | Copy of Coil Status 1-16 | Same flags as the bit table, packed 16 per register (bit 0 = first item). | BITMAP16 | Read/write |
Notes on this map
- Addresses are printed in Modicon form (0x coils, 1x discrete inputs, 3x input registers, 4x holding registers); wire address = number - 1 within each table.
- Sensor temperatures and battery voltage carry an explicit 1:10 scaling. Room temperature (3x0060), changeover temperature (3x0061) and the room-unit setpoint/flow readings (3x0031/3x0032) give a unit but no scaling, so they are left out.
- Left out: every temperature setpoint in the holding table (frost guard 4x0023, TC1/TH1 normal and TC2/TH2 economy 4x0024-4x0027, night cool 4x0028, room-unit min/max 4x0029-4x0030, manual temperature 4x0063). The table gives a °C unit and ranges but no scaling for them, while the input temperatures are marked 1:10, so the raw format is not settled.
- Also left out: PID Water Out and PID ChangeOver Out (3x0049/3x0050), whose -100 to 100 % range needs a signed format the manual never states.
- Also left out: the 16-register component name (ASCII byte order not given), application ID, serial number, software version and boot-year registers (no format given), and every Not used row.
- BMS port settings are menu parameters P_101 (address 1-247), P_102 (baud 9.6/19.2/38.4 k), P_103 (parity odd/even/none) and P_104 (stop bits).
Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.
Questions about the Swegon CONDUCTOR W1 room controller (waterborne cooling/heating, Modbus RTU)
What Modbus registers does the Swegon CONDUCTOR W1 room controller (waterborne cooling/heating, Modbus RTU) have?
This map lists 98 registers: 2 coils, 48 discrete inputs, 26 input registers, 22 holding registers. 24 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.
Are the Swegon CONDUCTOR W1 room controller (waterborne cooling/heating, Modbus RTU) Modbus addresses 0-based or 1-based?
The manufacturer's document numbers registers Modicon 3xxxx/4xxxx (drop the prefix, subtract 1). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. Tables print 0x/1x/3x/4x reference numbers starting at 0001; subtract 1 for the wire address in each table (e.g. 4x0024 = holding register 23).
What are the minimum Modbus registers to integrate the Swegon CONDUCTOR W1 room controller (waterborne cooling/heating, Modbus RTU)?
Start with IR 27 Temp sensor regulator (Regulator temperature sensor x10); IR 28 Temp sensor RU1 (Room unit 1 temperature x10); IR 21 Application state (Application state); HR 1 Application transition (Application transition (state request)); IR 52 Cool Water (Cooling water valve output); DI 5 Active alarms (Active alarms); IR 53 Warm Water (Warm water valve output); IR 62 Copy of Input Status 1-16 (Packed copy of discrete inputs 1-16).
How do I enable Modbus control of the Swegon CONDUCTOR W1 room controller (waterborne cooling/heating, Modbus RTU)?
Set the BMS address, baud, parity and stop bits in system parameters P_101-P_104 from the room unit (service level).
Where is the official Swegon CONDUCTOR W1 room controller (waterborne cooling/heating, Modbus RTU) Modbus documentation?
The source is CONDUCTOR W1, CONDUCTOR W3 Technical Manual (cond_w1w3-sw138-m (SW version 1.38)), revision 2015-06-15, published free by Swegon at https://www.swegon.com/siteassets/_products-documents-archive/waterborne-climate-systems/control-equipment/_en/cond_w1w3-sw138-m.pdf.
More Swegon Modbus register maps
- Thermostat / room controller (chilled beam with supply and extract air dampers)
Swegon CONDUCTOR W3 room controller (air and water, Modbus RTU)
Swegon CONDUCTOR W3 room controller, software 1.38 and later (technical manual updated 2015-06-15).
Also known as: CONDUCTOR RE W3, Conductor W3 - Thermostat / room controller (chilled beam with measured airflow and CO2)
Swegon CONDUCTOR W4 room controller (airflow and water, Modbus RTU)
Swegon CONDUCTOR W4 room controller, software 1.12 (technical manual updated 2014-11-21).
Also known as: CONDUCTOR RE W4, CONDUCTOR RE W4 1, Conductor W4 - Actuator / valve (ventilation damper and VAV actuator)
Swegon REACT damper / VAV actuator (Modbus RTU, 2018 sheet)
Swegon REACT demand-controlled-ventilation dampers with the Modbus actuators named in the sheet (309C-024-150-MB/SL8/ST15/SWE, 227VM-024-**-MB/SWE), sheet dated 2018-11-08.
Also known as: REACT A, REACT Modbus, Swegon REACT damper, 309C-024-150-MB/SL8/ST15/SWE, 227VM-024-MB/SWE - Actuator / valve (comfort module air damper)
Swegon REACT Parasol Zenith with Belimo actuator (Modbus RTU)
Swegon REACT Parasol Zenith comfort modules fitted with the Belimo Modbus actuator; Swegon Modbus settings sheet dated 2022-08-10.
Also known as: Parasol Zenith REACT, REACT damper actuator - Air handler (rotary heat exchanger drive controller)
Swegon SILVER C / SILVER RX rotary heat exchanger controller (Modbus RTU)
The rotary heat exchanger (rotor) drive controller in Swegon SILVER C RX air handling units, per sheet SILVERCModbusHX.201115.
Also known as: SILVER RX heat exchanger controller, SILVER C RX rotor drive, DRHX, SILVERCModbusHX - Air handler fan motor control
Swegon SILVER C fan motor control (RX/PX/CX/SD, generation E/F)
The EC/FC fan motor controllers inside Swegon SILVER C air handling units, generation E/F, document SILVERCModbus.210809.
Also known as: SILVER C RX, SILVER C PX, SILVER C CX, SILVER C SD, SILVER C generation E, SILVER C generation F - Air handler (heat recovery unit controller)
Swegon TAC5 DG/DM/DT controller (Global HRglobal, HRup, HRflat, HRtotal, HRmural)
Swegon (Global) TAC5 DG, DM and DT regulation boards with the SAT MODBUS (RTU) or SAT WIFI/ETHERNET (TCP) satellite; TAC5 + MODBUS TABLE Cid 050338 (2021-09-20). The TAC5 SC/F single-flow boards use other registers and are not covered.
Also known as: TAC5 DG, TAC5 DM, TAC5 DT, Global HRglobal, Global HRup, Global HRflat, Global HRtotal, Global HRmural, SAT MODBUS - Air handler (heat recovery unit controller)
Swegon TAC6 controller (Global units)
Swegon (Global) units with the TAC6 regulation board and a Modbus satellite; TAC6 + MODBUS TABLE Cid 050360 (2021-05-20).
Also known as: Global TAC6, SAT WIFI-ETHERNET (TAC6)
Other hvac equipment register maps
- Air handler (residential heat recovery ventilation)
Vasco SAB RVU ventilation unit controller (D150 Compact, Energy Plus)
Vasco SAB RVU controller boards (models 0x52xx residential and 0x53xx Energy Plus) with protocol release 0x0006, manual 90.01.06.53.
Also known as: D150 Compact, Energy Plus ENY-P1, ENY-P2, ENY-P3, ENY-P4, ESP170V, ESP270, ESP360, ESP460 - Air handler (in-row data-centre cooling unit)
APC (Schneider Electric) InRow ACRD60x / ACRC60x cooling units (Modbus register map 990-5786)
APC / Schneider Electric InRow ACRD60x and ACRC60x in-row cooling units, register map part number 990-5786A.
Also known as: ACRD60x, ACRC60x, InRow ACRD60x, InRow ACRC60x, 990-5786 - Air handler humidifier (high-pressure room system)
Condair Vita high-pressure humidification system (Integrated Controller, Modbus RTU/TCP)
Condair Vita system with the Integrated Controller, per addendum 2603326-G.
Also known as: Condair Vita, Vita System Master - Rooftop unit / packaged wall-mount air conditioner
Eubank EAH / EGH wall-mount air conditioner control board (Modbus RTU)
Eubank EAH1020A-1060A, EGH1072A, EAH2024A-2060A and EGH2072A wall-mount air conditioners with the electronic control board (I&O manual rev. 7).
Also known as: EAH1020A, EAH1024A, EAH1030A, EAH1036A, EAH1042A, EAH1048A, EAH1060A, EGH1072A, EAH2024A, EAH2030A, EAH2036A, EAH2042A, EAH2048A, EAH2060A, EGH2072A, Eubank EAH, Eubank EGH - Thermostat
Johnson Controls PENN TC3224N9V refrigeration temperature controller (Modbus RTU)
PENN TC3224N9V electronic refrigeration controller with built-in Modbus RTU, per the TC3 Modbus Protocol Reference Guide LIT-12013523 (2020-04-28).
Also known as: TC3224N9V, TC3, PENN TC3, LIT-12013523, TC3224N9R, TC3224 - Thermostat / room controller (temperature, humidity, CO2, VOC)
Neptronic AROB series universal room controller (Modbus communication module)
Neptronic AROB24T / AROB24TH / AROB24TGH / AROB24TGVH universal room controllers with the Modbus module, ARO Modbus Guide_170824.
Also known as: AROB, AROB24T, AROB24TH, AROB24TGH, AROB24TGVH, ARO
All hvac equipment Modbus register maps →
Source: CONDUCTOR W1, CONDUCTOR W3 Technical Manual · cond_w1w3-sw138-m (SW version 1.38) · rev. 2015-06-15. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.