Air handler (heat recovery unit controller) · Modbus register map
Swegon TAC6 controller (Global units) Modbus register map
Updated 17 November 2026
TAC6 is the newer controller of Swegon/Global heat recovery units. All data is in signed 16-bit holding registers: identification, working mode and speed, fan flows, pressures and RPM, temperatures T1-T8, input/output states, run and maintenance hours, alarm bitmaps and the Modbus control block for speed, airflows, bypass, boost and fire alarm. This map lists the registers an integrator needs, not every setup parameter.
This page lists 93 Modbus registers for the Swegon TAC6 controller (Global units) — 19 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Swegon’s own free documentation (linked below) and checked against it.
- Manufacturer
- Swegon
- Model
- TAC6 controller (Global units)
- Equipment type
- Air handler (heat recovery unit controller)
- Registers
- 93 (19 writable)
- Transport
- Modbus TCP
- Default unit ID
- 1
- TCP port
- 502
- Documented addressing
- Modicon 3xxxx/4xxxx (drop the prefix, subtract 1)
- 32-bit word order
- CDAB low word first (word-swapped)
- Also known as
- Global TAC6, SAT WIFI-ETHERNET (TAC6)
Integration notes: Swegon TAC6 controller (Global units)
Connect over Modbus TCP (port 502, unit ID 1). Set 40200 = 1 and write 0-3 to 40201 for stop/I/II/III, or set 40200 = 3 and write supply/exhaust flows to 40204/40205. Read 40052/40053 for mode and speed, 40155-40162 for temperatures and 40300-40304 for alarms; write 1 to 40250 to reset alarms.
Minimum registers to map
Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.
| Register | Name | Type | Why | Access |
|---|---|---|---|---|
| HR 199 | Control master | INT16 | Control master | Read/write |
| HR 200 | Speed selection via Modbus | INT16 | Speed via Modbus | Read/write |
| HR 51 | Current working mode | INT16 | Current working mode | Read |
| HR 52 | Current speed | INT16 | Current speed | Read |
| HR 154 | Temperature T1 | INT16 | Temperature T1 | Read |
| HR 158 | Temperature T5 | INT16 | Temperature T5 | Read |
| HR 299 | Alarms 1 | BITMAP16 | Alarm bitmap 1 | Read |
| HR 249 | Reset | INT16 | Alarm reset | Read/write |
Enable Modbus control & writes
Fit the TAC6 Modbus satellite (SAT WIFI-ETHERNET for Modbus TCP) and set 40200 to give Modbus control of the speed or airflows.
Byte order & addressing
- Only holding registers are used (FC 03, 06, 16).
- All registers are signed 16-bit.
- 32-bit values are low word first (CDAB).
Network setup
- Use unit ID 1 in Modbus TCP requests; the SAT WIFI-ETHERNET accepts only that address because it is not a gateway to RTU.
- Default satellite IP is 192.168.1.1/255.255.255.0; set DHCP or a fixed IP from the TACtouch advanced menu or TACsimulator, then reset the control board.
- At most 3 TCP clients can connect at once.
Watch out for
- Writing EEPROM-backed setup values often wears out the memory.
Swegon TAC6 controller (Global units) Modbus registers
Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.
| Table | Address | Name | Description | Type | Order | Scale | Units | Access | Values / bits |
|---|---|---|---|---|---|---|---|---|---|
| HR | 0doc 40001 | Magic number | Two words: 19533, 20051 (ASCII 'LMNS'); identifies a Swegon product. | INT32 | CDAB | Read | |||
| HR | 2doc 40003 | Product identification code (CID) | INT16 | Read | |||||
| HR | 3doc 40004 | Modbus mapping version | Major x 100 + minor. | INT16 | Read | ||||
| HR | 4doc 40005 | Software version, major | INT16 | Read | |||||
| HR | 5doc 40006 | Software version, minor | INT16 | Read | |||||
| HR | 6doc 40007 | Software version, revision | INT16 | Read | |||||
| HR | 7doc 40008 | Controller reset flag | 1 after a controller reset; the master may write 0. | INT16 | Read/write | 0 = No reset seen; 1 = Controller has reset | |||
| HR | 8doc 40009 | Software build number | INT16 | Read | |||||
| HR | 21doc 40022 | Factory option: preheat | INT16 | Read | 0 = Off; 1 = KWin | ||||
| HR | 22doc 40023 | Factory option: postheat | INT16 | Read | 0 = Off; 1 = KWout; 2 = IBA | ||||
| HR | 23doc 40024 | Factory option: CT IN damper | INT16 | Read | 0 = No; 1 = Yes | ||||
| HR | 24doc 40025 | Proportional bypass fitted | INT16 | Read | 0 = No; 1 = Yes | ||||
| HR | 25doc 40026 | Backward fans | INT16 | Read | 0 = No; 1 = Yes | ||||
| HR | 26doc 40027 | Heat wheel | INT16 | Read | 0 = No; 1 = Yes | ||||
| HR | 27doc 40028 | TQ mode | INT16 | Read | 0 = No; 1 = Yes | ||||
| HR | 51doc 40052 | Current working mode | INT16 | Read | 0 = Off; 1 = CA; 2 = LS; 4 = CPs; 5 = CAs; 6 = TQ; 9 = INIT | ||||
| HR | 52doc 40053 | Current speed | INT16 | Read | 0 = Stop; 1 = Low / I; 2 = Medium / II; 3 = High / III | ||||
| HR | 53doc 40054 | Current set point (SET VAL) | Unit given by 40055. | INT16 | Read | ||||
| HR | 54doc 40055 | Current set point unit | INT16 | Read | 0 = m³/h; 1 = Pa; 2 = 0.1 V; 3 = % of max torque | ||||
| HR | 55doc 40056 | Current set point supply fans F1/F2 | m³/h, Pa, 0.1 V or %. | INT16 | Read | ||||
| HR | 56doc 40057 | Current set point exhaust fans F3/F4 | m³/h, Pa, 0.1 V or %. | INT16 | Read | ||||
| HR | 57doc 40058 | Preheat set point | INT16 | × 0.1 | °C | Read | |||
| HR | 58doc 40059 | Current comfort temperature set point | 0 = supply heating and cooling off. | INT16 | × 0.1 | °C | Read | ||
| HR | 59doc 40060 | Exhaust/supply ratio | Unbalance between flows, 5-999 %. | INT16 | % | Read | |||
| HR | 64doc 40065 | Fan 1 (supply 1) flow or torque | m³/h or % torque. | INT16 | Read | ||||
| HR | 65doc 40066 | Fan 1 pressure | INT16 | Pa | Read | ||||
| HR | 66doc 40067 | Fan 1 sent torque | 0-255 (127 = 50 %). | INT16 | Read | ||||
| HR | 67doc 40068 | Fan 1 RPM | INT16 | rpm | Read | ||||
| HR | 68doc 40069 | Fan 2 (supply 2) flow or torque | m³/h or % torque. | INT16 | Read | ||||
| HR | 69doc 40070 | Fan 2 pressure | INT16 | Pa | Read | ||||
| HR | 70doc 40071 | Fan 2 sent torque | 0-255 (127 = 50 %). | INT16 | Read | ||||
| HR | 71doc 40072 | Fan 2 RPM | INT16 | rpm | Read | ||||
| HR | 72doc 40073 | Fan 3 (exhaust 1) flow or torque | m³/h or % torque. | INT16 | Read | ||||
| HR | 73doc 40074 | Fan 3 pressure | INT16 | Pa | Read | ||||
| HR | 74doc 40075 | Fan 3 sent torque | 0-255 (127 = 50 %). | INT16 | Read | ||||
| HR | 75doc 40076 | Fan 3 RPM | INT16 | rpm | Read | ||||
| HR | 76doc 40077 | Fan 4 (exhaust 2) flow or torque | m³/h or % torque. | INT16 | Read | ||||
| HR | 77doc 40078 | Fan 4 pressure | INT16 | Pa | Read | ||||
| HR | 78doc 40079 | Fan 4 sent torque | 0-255 (127 = 50 %). | INT16 | Read | ||||
| HR | 79doc 40080 | Fan 4 RPM | INT16 | rpm | Read | ||||
| HR | 80doc 40081 | Run time | Unit working hours, 0-999999. | INT32 | CDAB | h | Read | ||
| HR | 82doc 40083 | Antifreeze status, integrated exchangers | INT16 | Read | 0 = Off; 1 = Air-air exchanger antifreeze; 2 = Warm water exchanger antifreeze | ||||
| HR | 83doc 40084 | Bypass status | INT16 | Read | 0 = Inactive; 1 = Active; 2 = Partially active | ||||
| HR | 84doc 40085 | CTin damper status | INT16 | Read | 0 = Closed or closing; 1 = Opening; 2 = Open | ||||
| HR | 85doc 40086 | Post ventilation status | INT16 | Read | 0 = No; 1 = Active | ||||
| HR | 86doc 40087 | Current control mode | What is driving the airflows. | INT16 | Read | 1 = Fatal error (fans stopped); 2 = Fire alarm; 3 = User interface; 4 = External contacts K1-K3; 6 = Time scheduler; 7 = Modbus 40201; 8 = Bypass; 9 = Boost; 10 = Modbus 40204/40205; 11 = KNX | |||
| HR | 88doc 40089 | Comfort heating set point | 0 = heating off. | INT16 | × 0.1 | °C | Read | ||
| HR | 89doc 40090 | Comfort cooling set point | 0 = cooling off. | INT16 | × 0.1 | °C | Read | ||
| HR | 90doc 40091 | Bypass valve position | 0 = closed, 100 = fully open. | INT16 | % | Read | |||
| HR | 95doc 40096 | Minor maintenance hours | INT32 | CDAB | h | Read | |||
| HR | 97doc 40098 | Changeover status | INT16 | Read | 0 = Inactive; 1 = Heating; 2 = Cooling | ||||
| HR | 98doc 40099 | Defrost state | INT16 | Read | 0 = Idle; 1 = Active; 2 = Stop to drain water | ||||
| HR | 108doc 40109 | Major maintenance hours | INT32 | CDAB | h | Read | |||
| HR | 149doc 40150 | Digital inputs block 0 | 1 = input on. | BITMAP16 | Read | bit 0 = K1; bit 1 = K2 (on/off); bit 2 = K3 (on/off); bit 3 = IN1 fire alarm; bit 4 = IN2 boost; bit 5 = IN3 bypass on; bit 6 = IN4 drain pan full; bit 7 = ADI1 rotor speed feedback; bit 8 = ADI2 supply dPa switch; bit 9 = ADI3 exhaust dPa switch; bit 12 = SATIO IN5 master selection; bit 13 = SATIO IN6 heat/cool select | |||
| HR | 151doc 40152 | K1 analogue voltage | INT16 | × 0.1 | V | Read | |||
| HR | 152doc 40153 | K2 analogue voltage | INT16 | × 0.1 | V | Read | |||
| HR | 153doc 40154 | K3 analogue voltage | INT16 | × 0.1 | V | Read | |||
| HR | 154doc 40155 | Temperature T1 | -999 open circuit, +999 short circuit. | INT16 | × 0.1 | °C | Read | ||
| HR | 155doc 40156 | Temperature T2 | -999 open circuit, +999 short circuit. | INT16 | × 0.1 | °C | Read | ||
| HR | 156doc 40157 | Temperature T3 | -999 open circuit, +999 short circuit. | INT16 | × 0.1 | °C | Read | ||
| HR | 157doc 40158 | Temperature T4 | -999 open circuit, +999 short circuit. | INT16 | × 0.1 | °C | Read | ||
| HR | 158doc 40159 | Temperature T5 | -999 open circuit, +999 short circuit. | INT16 | × 0.1 | °C | Read | ||
| HR | 159doc 40160 | Temperature T6 | -999 open circuit, +999 short circuit. | INT16 | × 0.1 | °C | Read | ||
| HR | 160doc 40161 | Temperature T7 | -999 open circuit, +999 short circuit. | INT16 | × 0.1 | °C | Read | ||
| HR | 161doc 40162 | Temperature T8 | -999 open circuit, +999 short circuit. | INT16 | × 0.1 | °C | Read | ||
| HR | 167doc 40168 | Digital outputs block 0 | 1 = output on. | BITMAP16 | Read | bit 0 = DO9 alarm; bit 1 = Linear bypass moving forward; bit 2 = Linear bypass moving backward; bit 3 = CT; bit 4 = KWin; bit 5 = KWout; bit 6 = DO10 pressure alarm; bit 7 = DO11 fan on; bit 8 = DO7 heat output; bit 9 = SAT IO OR3 bypass on; bit 10 = DO7 cool output; bit 11 = SAT IO DO16 | |||
| HR | 185doc 40186 | Preheat KWin power | INT16 | % | Read | ||||
| HR | 186doc 40187 | Postheat KWout power | INT16 | % | Read | ||||
| HR | 187doc 40188 | External KW coil power | INT16 | % | Read | ||||
| HR | 188doc 40189 | Heat wheel measured RPM | INT16 | × 0.1 | rpm | Read | |||
| HR | 199doc 40200 | Control master | Who sets the speed. | INT16 | Read/write | 0 = User interface; 1 = Modbus via 40201; 2 = Time table; 3 = Modbus airflows via 40204/40205 | |||
| HR | 200doc 40201 | Speed selection via Modbus | Only when 40200 = 1. | INT16 | Read/write | 0 = Stop; 1 = Low / I; 2 = Medium / II; 3 = High / III | |||
| HR | 203doc 40204 | Supply airflow/torque via Modbus | Only when 40200 = 3; 0-9999. | INT16 | Read/write | ||||
| HR | 204doc 40205 | Exhaust airflow/torque via Modbus | Only when 40200 = 3; 0-9999. | INT16 | Read/write | ||||
| HR | 220doc 40221 | External pressure alarm | INT16 | Read/write | 0 = No alarm; 1 = Pressure alarm active | ||||
| HR | 221doc 40222 | Fire alarm | INT16 | Read/write | 0 = No alarm; 1 = Fire alarm active | ||||
| HR | 222doc 40223 | Bypass override | INT16 | Read/write | 0 = Auto (T1/T2); 1 = Force bypass active; 2 = Force bypass inactive | ||||
| HR | 223doc 40224 | Force automatic mode | 1 = force automatic mode. | INT16 | Read/write | ||||
| HR | 224doc 40225 | Post heating disable | INT16 | Read/write | 0 = Allowed; 1 = Not allowed | ||||
| HR | 227doc 40228 | Boost control | INT16 | Read/write | 0 = Off; 1 = Boost active | ||||
| HR | 228doc 40229 | Post cooling disable | INT16 | Read/write | 0 = Allowed; 1 = Not allowed | ||||
| HR | 229doc 40230 | Cooling or heating selection | INT16 | Read/write | 0 = Heating; 1 = Cooling | ||||
| HR | 249doc 40250 | Reset | Write 1 to clear alarms and resume; reads 0. | INT16 | Read/write | ||||
| HR | 251doc 40252 | Reset run time | Write 1 to zero the run time. | INT16 | Read/write | ||||
| HR | 257doc 40258 | Bypass position override | -1 = no override, 0-100 % position. | INT16 | % | Read/write | |||
| HR | 299doc 40300 | Alarms 1 | 1 = alarm active. | BITMAP16 | Read | bit 0 = Program error; bit 1 = Data error; bit 2 = Fan 1; bit 3 = Fan 2; bit 4 = Fan 3; bit 5 = Fan 4; bit 6 = Pressure F1; bit 7 = Pressure F3; bit 8 = T1 open; bit 9 = T1 short; bit 10 = T2 open; bit 11 = T2 short; bit 12 = T3 open; bit 13 = T3 short; bit 14 = T4 open; bit 15 = T4 short | |||
| HR | 300doc 40301 | Alarms 2 | 1 = alarm active. | BITMAP16 | Read | bit 0 = T5 open; bit 1 = T5 short; bit 2 = T6 open; bit 3 = T6 short; bit 4 = T7 open; bit 5 = T7 short; bit 6 = T8 open; bit 7 = T8 short; bit 8 = CP fan 1 high; bit 9 = CP fan 1 low; bit 10 = CP fan 3 high; bit 11 = CP fan 3 low; bit 12 = LS fan 1 low; bit 13 = LS fan 1 high; bit 14 = LS fan 2 low; bit 15 = LS fan 2 high | |||
| HR | 301doc 40302 | Alarms 3 | 1 = alarm active. | BITMAP16 | Read | bit 0 = LS fan 3 low; bit 1 = LS fan 3 high; bit 2 = LS fan 4 low; bit 3 = LS fan 4 high; bit 4 = CA fan 1 low; bit 5 = CA fan 1 high; bit 6 = CA fan 2 low; bit 7 = CA fan 2 high; bit 8 = CA fan 3 low; bit 9 = CA fan 3 high; bit 10 = CA fan 4 low; bit 11 = CA fan 4 high; bit 12 = Pa init F1 not stable; bit 13 = Pa init F3 not stable; bit 14 = Pa init F1 too low; bit 15 = Pa init F3 too low | |||
| HR | 302doc 40303 | Alarms 4 | 1 = alarm active. | BITMAP16 | Read | bit 0 = Pa init F1 not achieved; bit 1 = Pa init F3 not achieved; bit 2 = Pa init F1 too high; bit 3 = Pa init F3 too high; bit 4 = Maintenance warning; bit 5 = Maintenance fatal; bit 6 = dPa; bit 7 = Fire; bit 8 = End of fire alarm; bit 9 = V lower than Vlow; bit 10 = V higher than Vhigh; bit 11 = Preheat reduced; bit 12 = Preheat stop; bit 13 = Antifreeze reduced; bit 14 = Antifreeze stop; bit 15 = Postheat set point (comfort too low) | |||
| HR | 303doc 40304 | Alarms 5 | 1 = alarm active. | BITMAP16 | Read | bit 0 = Postcooling set point (comfort too high); bit 2 = Condensate drain pan full; bit 3 = T5 antifreeze stop; bit 4 = Heat wheel RPM out of range; bit 5 = Proportional bypass position; bit 6 = Antifreeze IBA stop; bit 7 = Antifreeze EBA+ stop; bit 8 = Antifreeze EBA- stop; bit 9 = Antifreeze EBA+/- stop; bit 10 = Minor maintenance; bit 11 = Defrost alarm; bit 12 = Modbus communication error; bit 13 = Major maintenance | |||
| HR | 425doc 40426 | Fans working mode | Setup value. | INT16 | Read/write | 0 = Off; 1 = CA constant airflow; 2 = LS 0-10 V linked; 4 = CPs constant pressure; 6 = TQ constant torque; 9 = INIT | |||
| HR | 426doc 40427 | Exhaust/supply flows ratio | 5-999 %. | INT16 | % | Read/write | |||
| HR | 542doc 40543 | Modbus address | 1-247. | INT16 | Read/write |
Notes on this map
- Addressing and word order come from Swegon's French manual 'TAC6 + MODBUS TCP/IP' (050325, 2023-07-14), which is written for TAC6 boards in GLOBAL/ESENSA units; the register table itself does not repeat them.
- The TAC6 TCP/IP manual states that all values are signed and that 32-bit values are sent low word first, then high word (Val32 = HIGH x 65536 + LOW), so 32-bit registers here are INT32 CDAB. When writing a 32-bit value, write the low word first; the value updates when the high word arrives.
- Only a selection is listed: the general info, visualization, control and alarm blocks plus the working mode, flow ratio and Modbus address setup registers. Setup, advanced setup and time-table registers (40400-41xxx) are left out; see the source table.
- The TAC6 TCP/IP manual says setup parameters are stored in EEPROM rated for about 1,000,000 write cycles; the TAC6 table does not mark which registers these are, so do not write setup values cyclically.
- Flow values are m³/h or % of maximum torque depending on the working mode (CA vs TQ); 40055 gives the unit of 40054.
- The TAC6 table does not give where each probe T1-T8 sits in the unit. The digital input/output bitmaps differ from TAC5.
Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.
Questions about the Swegon TAC6 controller (Global units)
What Modbus registers does the Swegon TAC6 controller (Global units) have?
This map lists 93 registers: 93 holding registers. 19 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.
Are the Swegon TAC6 controller (Global units) Modbus addresses 0-based or 1-based?
The manufacturer's document numbers registers Modicon 3xxxx/4xxxx (drop the prefix, subtract 1). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. The table prints 4xxxx registers. Swegon's TAC6 + Modbus TCP/IP manual (French) says the leading 4 is only a type prefix and that document numbering is one-based while the address sent is zero-based (register 41001 is sent as 1000). So 40201 is holding register 200 on the wire.
What byte order does the Swegon TAC6 controller (Global units) use for 32-bit values?
Multi-register values in this map use CDAB (low word first (word-swapped)). Set your client to this order for every 32/64-bit value in the table.
What are the minimum Modbus registers to integrate the Swegon TAC6 controller (Global units)?
Start with HR 199 Control master (Control master); HR 200 Speed selection via Modbus (Speed via Modbus); HR 51 Current working mode (Current working mode); HR 52 Current speed (Current speed); HR 154 Temperature T1 (Temperature T1); HR 158 Temperature T5 (Temperature T5); HR 299 Alarms 1 (Alarm bitmap 1); HR 249 Reset (Alarm reset).
How do I enable Modbus control of the Swegon TAC6 controller (Global units)?
Fit the TAC6 Modbus satellite (SAT WIFI-ETHERNET for Modbus TCP) and set 40200 to give Modbus control of the speed or airflows.
Where is the official Swegon TAC6 controller (Global units) Modbus documentation?
The source is TAC6 + MODBUS TABLE - Installation and user's manual (Cid 050360), revision 2021-05-20, published free by Swegon at https://pre.swegon.com/globalassets/digizuite/11951-en-global_tac6_modbustable_regulation_installation_en.pdf.
More Swegon Modbus register maps
- Thermostat / room controller (chilled beam, fan coil water circuits)
Swegon CONDUCTOR W1 room controller (waterborne cooling/heating, Modbus RTU)
Swegon CONDUCTOR W1 room controller, software 1.38 and later (technical manual updated 2015-06-15).
Also known as: CONDUCTOR RE W1, Conductor W1, 942334001 - Thermostat / room controller (chilled beam with supply and extract air dampers)
Swegon CONDUCTOR W3 room controller (air and water, Modbus RTU)
Swegon CONDUCTOR W3 room controller, software 1.38 and later (technical manual updated 2015-06-15).
Also known as: CONDUCTOR RE W3, Conductor W3 - Thermostat / room controller (chilled beam with measured airflow and CO2)
Swegon CONDUCTOR W4 room controller (airflow and water, Modbus RTU)
Swegon CONDUCTOR W4 room controller, software 1.12 (technical manual updated 2014-11-21).
Also known as: CONDUCTOR RE W4, CONDUCTOR RE W4 1, Conductor W4 - Actuator / valve (ventilation damper and VAV actuator)
Swegon REACT damper / VAV actuator (Modbus RTU, 2018 sheet)
Swegon REACT demand-controlled-ventilation dampers with the Modbus actuators named in the sheet (309C-024-150-MB/SL8/ST15/SWE, 227VM-024-**-MB/SWE), sheet dated 2018-11-08.
Also known as: REACT A, REACT Modbus, Swegon REACT damper, 309C-024-150-MB/SL8/ST15/SWE, 227VM-024-MB/SWE - Actuator / valve (comfort module air damper)
Swegon REACT Parasol Zenith with Belimo actuator (Modbus RTU)
Swegon REACT Parasol Zenith comfort modules fitted with the Belimo Modbus actuator; Swegon Modbus settings sheet dated 2022-08-10.
Also known as: Parasol Zenith REACT, REACT damper actuator - Air handler (rotary heat exchanger drive controller)
Swegon SILVER C / SILVER RX rotary heat exchanger controller (Modbus RTU)
The rotary heat exchanger (rotor) drive controller in Swegon SILVER C RX air handling units, per sheet SILVERCModbusHX.201115.
Also known as: SILVER RX heat exchanger controller, SILVER C RX rotor drive, DRHX, SILVERCModbusHX - Air handler fan motor control
Swegon SILVER C fan motor control (RX/PX/CX/SD, generation E/F)
The EC/FC fan motor controllers inside Swegon SILVER C air handling units, generation E/F, document SILVERCModbus.210809.
Also known as: SILVER C RX, SILVER C PX, SILVER C CX, SILVER C SD, SILVER C generation E, SILVER C generation F - Air handler (heat recovery unit controller)
Swegon TAC5 DG/DM/DT controller (Global HRglobal, HRup, HRflat, HRtotal, HRmural)
Swegon (Global) TAC5 DG, DM and DT regulation boards with the SAT MODBUS (RTU) or SAT WIFI/ETHERNET (TCP) satellite; TAC5 + MODBUS TABLE Cid 050338 (2021-09-20). The TAC5 SC/F single-flow boards use other registers and are not covered.
Also known as: TAC5 DG, TAC5 DM, TAC5 DT, Global HRglobal, Global HRup, Global HRflat, Global HRtotal, Global HRmural, SAT MODBUS
Other hvac equipment register maps
- Air handler (heat recovery ventilation unit)
Airflow Developments Entro-V heat recovery unit controller (Basic / Digital controller, Modbus RTU)
Airflow Entro-V MVHR units with the Entro-V control board (Basic controller 90001308 / Digital controller 90001299), per controls manual 80001022 Issue 1 (08/20).
Also known as: Entro-V Basic Controller, Entro-V Digital Controller, 90001308, 90001299, DuplexVent Entro-V - Air handler humidifier (evaporative)
Condair ME II evaporative humidifier / cooler (Integrated Controller, Modbus RTU/TCP)
Condair ME with the Integrated Controller, per addendum 2603326-G.
Also known as: Condair ME, Condair ME II, ME - Air handler (demand-controlled ventilation unit)
Duco DucoBox ventilation units / IQ unit (Modbus RTU, master node)
DucoBox Silent Connect, Focus, Energy (all variants) and ECO with the Communication Print option, and the Duco IQ unit (Modbus standard), per information sheet L8000009-B.
Also known as: DucoBox Silent Connect, DucoBox Focus, DucoBox Energy, DucoBox Energy Premium, DucoBox ECO, Duco IQ unit, L8000009 - Thermostat
Johnson Controls PENN TC3222 refrigeration temperature controller (Modbus RTU)
PENN TC3222 electronic refrigeration controller with built-in Modbus RTU, per the TC3 Modbus Protocol Reference Guide LIT-12013523 (2020-04-28).
Also known as: TC3222, TC3, PENN TC3, LIT-12013523 - Air handler (heat recovery ventilation unit)
Mitsubishi Electric MelcoBEMS MINI (A1M+ / A1M) gateway for Lossnay heat recovery ventilators (LGH and VL series)
Procon MelcoBEMS MINI A1M+ (manual v1.0.3, firmware 4.1.1) on Lossnay LGH-15..200RVX-E1, LGH-150..250RVXT-E1 and VL-250..500CZPVU-R/L-E; the older A1M (manual v1.1.11) prints the identical Lossnay table.
Also known as: A1M+ Lossnay, MelcoBEMS MINI Lossnay, Procon A1M+, Procon A1M, A1M, Lossnay LGH-RVX Modbus, LGH-15RVX-E1, LGH-200RVX-E1, LGH-150RVXT-E1, LGH-250RVXT-E1, VL-250CZPVU-R-E, VL-500CZPVU-L-E, Lossnay VL Vertical - Air handler humidifier (electric steam)
Neptronic SKE4 electric steam humidifier (Modbus communication module)
Neptronic SKE4 series electric steam humidifiers with the Modbus communication module, guide SKE4-Modbus Guide-240531 (V2.07).
Also known as: SKE4-E, SKE4-N, SKE4 Steam Humidifier, Neptronic SKE4 Modbus
All hvac equipment Modbus register maps →
Source: TAC6 + MODBUS TABLE - Installation and user's manual · Cid 050360 · rev. 2021-05-20. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.