Air handler (heat recovery unit controller) · Modbus register map

Swegon TAC5 DG/DM/DT controller (Global HRglobal, HRup, HRflat, HRtotal, HRmural) Modbus register map

Updated 17 November 2026

Short answer

TAC5 is the controller in Swegon/Global heat recovery units. With a SAT MODBUS or SAT WIFI/ETHERNET satellite it exposes everything as holding registers: identification, working mode and speed, fan flows, pressures and RPM, temperatures T1-T8, input/output states, run and maintenance hours, alarm bitmaps and the Modbus control block for speed, airflows, bypass, boost and fire alarm. This map covers the counter-flow (DG/DM/DT) registers an integrator needs, not every setup parameter.

This page lists 91 Modbus registers for the Swegon TAC5 DG/DM/DT controller (Global HRglobal, HRup, HRflat, HRtotal, HRmural) — 19 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Swegon’s own free documentation (linked below) and checked against it.

Manufacturer
Swegon
Model
TAC5 DG/DM/DT controller (Global HRglobal, HRup, HRflat, HRtotal, HRmural)
Equipment type
Air handler (heat recovery unit controller)
Registers
91 (19 writable)
Transport
Modbus RTU, Modbus TCP
Default unit ID
1
Default serial
9600 baud, 8N1
Documented addressing
Modicon 3xxxx/4xxxx (drop the prefix, subtract 1)
32-bit word order
CDAB low word first (word-swapped)
Also known as
TAC5 DG, TAC5 DM, TAC5 DT, Global HRglobal, Global HRup, Global HRflat, Global HRtotal, Global HRmural, SAT MODBUS
Source document
TAC5 + MODBUS TABLE - Installation and user's manual · Cid 050338 · rev. 2021-09-20
Download CSV all columns JSON Manufacturer PDF ↗

Integration notes: Swegon TAC5 DG/DM/DT controller (Global HRglobal, HRup, HRflat, HRtotal, HRmural)

Integration in brief

Set 40200 = 1 and write 0-3 to 40201 for stop/I/II/III, or 40200 = 3 and write supply/exhaust flows to 40204/40205. Read 40052/40053 for mode and speed, 40155-40162 for temperatures and 40300-40304 for alarms; write 1 to 40250 to reset alarms.

Minimum registers to map

Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.

RegisterNameTypeWhyAccess
HR 199Control masterINT16Control masterRead/write
HR 200Speed selection via ModbusINT16Speed via ModbusRead/write
HR 51Current working modeINT16Current working modeRead
HR 52Current speedINT16Current speedRead
HR 154Temperature T1 (fresh air in)INT16Fresh air temperature T1Read
HR 158Temperature T5 (supply after exchanger)INT16Supply temperature T5Read
HR 299Alarms 1BITMAP16Alarm bitmap 1Read
HR 249ResetINT16Alarm resetRead/write

Enable Modbus control & writes

Fit the SAT MODBUS satellite on the TAC5 board (power off) for RTU, or SAT WIFI / SAT ETHERNET for TCP. Then set 40200 to give Modbus control of the speed or airflows.

Byte order & addressing

Network setup

Watch out for

Swegon TAC5 DG/DM/DT controller (Global HRglobal, HRup, HRflat, HRtotal, HRmural) Modbus registers

Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.

91 of 91 shown
Swegon TAC5 DG/DM/DT controller (Global HRglobal, HRup, HRflat, HRtotal, HRmural) Modbus register map
TableAddressNameDescriptionTypeOrderScaleUnitsAccessValues / bits
HR0doc 40001Magic numberTwo words: 19533, 20051 (ASCII 'LMNS'); identifies a Swegon product.INT32CDABRead
HR2doc 40003Product identification code (CID)INT16Read
HR3doc 40004Modbus mapping versionMajor x 100 + minor.INT16Read
HR4doc 40005Software version, majorINT16Read
HR5doc 40006Software version, minorINT16Read
HR6doc 40007Software version, revisionINT16Read
HR7doc 40008Controller reset flag1 after a controller reset; the master may write 0.INT16Read/write0 = No reset seen; 1 = Controller has reset
HR8doc 40009Software build numberINT16Read
HR21doc 40022Factory option: preheatINT16Read0 = Off; 1 = KWin
HR22doc 40023Factory option: postheatINT16Read0 = Off; 1 = KWout; 2 = NV
HR23doc 40024Factory option: CT IN damperINT16Read0 = No; 1 = Yes
HR24doc 40025Proportional bypass fittedINT16Read0 = No; 1 = Yes
HR25doc 40026Backward fansINT16Read0 = No; 1 = Yes
HR26doc 40027Heat wheelINT16Read0 = No; 1 = Yes
HR27doc 40028TQ modeINT16Read0 = No; 1 = Yes
HR51doc 40052Current working modeINT16Read0 = Off; 1 = CA; 2 = LS; 4 = CPs; 5 = CAs; 6 = TQ; 9 = INIT
HR52doc 40053Current speedINT16Read0 = Stop; 1 = Low / I; 2 = Medium / II; 3 = High / III
HR53doc 40054Current set point (SET VAL)Unit given by 40055.INT16Read
HR54doc 40055Current set point unitINT16Read0 = m³/h; 1 = Pa; 2 = 0.1 V; 3 = % of max torque
HR55doc 40056Current set point supply fans F1/F2m³/h, Pa, 0.1 V or %.INT16Read
HR56doc 40057Current set point exhaust fans F3/F4m³/h, Pa, 0.1 V or %.INT16Read
HR57doc 40058Preheat set pointINT16× 0.1°CRead
HR58doc 40059Current comfort temperature set point0 = supply heating and cooling off.INT16× 0.1°CRead
HR59doc 40060Exhaust/supply ratioUnbalance between flows, 5-999 %.INT16%Read
HR64doc 40065Fan 1 (supply 1) flow or torquem³/h or % torque.INT16Read
HR65doc 40066Fan 1 pressureINT16PaRead
HR66doc 40067Fan 1 sent torque0-255 (127 = 50 %).INT16Read
HR67doc 40068Fan 1 RPMINT16rpmRead
HR68doc 40069Fan 2 (supply 2) flow or torquem³/h or % torque.INT16Read
HR69doc 40070Fan 2 pressureINT16PaRead
HR70doc 40071Fan 2 sent torque0-255 (127 = 50 %).INT16Read
HR71doc 40072Fan 2 RPMINT16rpmRead
HR72doc 40073Fan 3 (exhaust 1) flow or torquem³/h or % torque.INT16Read
HR73doc 40074Fan 3 pressureINT16PaRead
HR74doc 40075Fan 3 sent torque0-255 (127 = 50 %).INT16Read
HR75doc 40076Fan 3 RPMINT16rpmRead
HR76doc 40077Fan 4 (exhaust 2) flow or torquem³/h or % torque.INT16Read
HR77doc 40078Fan 4 pressureINT16PaRead
HR78doc 40079Fan 4 sent torque0-255 (127 = 50 %).INT16Read
HR79doc 40080Fan 4 RPMINT16rpmRead
HR80doc 40081Run timeUnit working hours, 0-999999.INT32CDABhRead
HR82doc 40083Antifreeze status, integrated exchangersINT16Read0 = Off; 1 = Air-air exchanger antifreeze; 2 = Warm water exchanger antifreeze
HR83doc 40084Bypass statusINT16Read0 = Closed; 1 = Open; 2 = Partially open
HR84doc 40085CTin damper statusINT16Read0 = Closed or closing; 1 = Opening; 2 = Open
HR85doc 40086Post ventilation statusINT16Read0 = No; 1 = Active
HR86doc 40087Current control modeWhat is driving the airflows.INT16Read1 = Fatal error (fans stopped); 2 = Fire alarm; 3 = RC TAC5 remote; 4 = External contacts K1-K3; 5 = Time scheduler (RC TAC5); 6 = Time scheduler (Modbus/GRC); 7 = Modbus 40201; 8 = Bypass; 9 = Boost; 10 = Modbus 40204/40205; 11 = KNX
HR88doc 40089Comfort heating set point0 = heating off.INT16× 0.1°CRead
HR89doc 40090Comfort cooling set point0 = cooling off.INT16× 0.1°CRead
HR90doc 40091Bypass valve position0 = closed, 100 = fully open.INT16%Read
HR95doc 40096Minor maintenance hoursINT32CDABhRead
HR97doc 40098Changeover statusINT16Read0 = Inactive; 1 = Heating; 2 = Cooling
HR98doc 40099Defrost stateINT16Read0 = Idle; 1 = Active; 2 = Stop to drain water
HR108doc 40109Major maintenance hoursINT32CDABhRead
HR149doc 40150Digital inputs block 01 = input on.BITMAP16Readbit 0 = K1; bit 1 = K2 (on/off); bit 2 = K3 (on/off); bit 3 = IN1 master selection; bit 4 = IN2; bit 5 = IN3; bit 6 = IN4; bit 7 = IN5; bit 8 = IN6; bit 9 = IN7; bit 10 = IN8; bit 11 = IN9; bit 12 = IN10 (SATBA post cooling off); bit 13 = IN11 (SATBA heat/cool select); bit 14 = IN12
HR151doc 40152K1 analogue voltageINT16× 0.1VRead
HR152doc 40153K2 analogue voltageINT16× 0.1VRead
HR153doc 40154K3 analogue voltageINT16× 0.1VRead
HR154doc 40155Temperature T1 (fresh air in)-999 open circuit, +999 short circuit.INT16× 0.1°CRead
HR155doc 40156Temperature T2 (extract air in)-999 open circuit, +999 short circuit.INT16× 0.1°CRead
HR156doc 40157Temperature T3 (exhaust after exchanger)-999 open circuit, +999 short circuit.INT16× 0.1°CRead
HR157doc 40158Temperature T4 (water coil, NV option)-999 open circuit, +999 short circuit.INT16× 0.1°CRead
HR158doc 40159Temperature T5 (supply after exchanger)-999 open circuit, +999 short circuit.INT16× 0.1°CRead
HR160doc 40161Temperature T7 (hot water coil)-999 open circuit, +999 short circuit.INT16× 0.1°CRead
HR161doc 40162Temperature T8 (cold water coil)-999 open circuit, +999 short circuit.INT16× 0.1°CRead
HR167doc 40168Digital outputs block 01 = output on.BITMAP16Readbit 0 = AL1 alarm; bit 1 = BYPASS 1; bit 2 = BYPASS 2; bit 3 = CT; bit 4 = KWin; bit 5 = KWout; bit 6 = OR1 SAT pressure alarm; bit 7 = OR2 SAT fan on; bit 8 = OR3 SAT water pump NV; bit 9 = OR4 SAT bypass on; bit 10 = SATBA WP; bit 11 = SATBA OUT9 KWext
HR185doc 40186Preheat KWin powerINT16%Read
HR186doc 40187Postheat KWout powerINT16%Read
HR188doc 40189Heat wheel measured RPMINT16× 0.1rpmRead
HR199doc 40200Control masterWho sets the speed.INT16Read/write0 = RC TAC5 remote; 1 = Modbus via 40201; 2 = Time table; 3 = Modbus airflows via 40204/40205
HR200doc 40201Speed selection via ModbusOnly when 40200 = 1.INT16Read/write0 = Stop; 1 = Low / I; 2 = Medium / II; 3 = High / III
HR203doc 40204Supply airflow/torque via ModbusOnly when 40200 = 3; 0-9999.INT16Read/write
HR204doc 40205Exhaust airflow/torque via ModbusOnly when 40200 = 3; 0-9999.INT16Read/write
HR220doc 40221External pressure alarmINT16Read/write0 = No alarm; 1 = Pressure alarm active
HR221doc 40222Fire alarmINT16Read/write0 = No alarm; 1 = Fire alarm active
HR222doc 40223Bypass overrideINT16Read/write0 = Auto (T1/T2); 1 = Force open; 2 = Force closed
HR223doc 40224Force automatic mode1 = force automatic mode.INT16Read/write
HR224doc 40225Post heating disableINT16Read/write0 = Allowed; 1 = Not allowed
HR227doc 40228Boost controlINT16Read/write0 = Off; 1 = Boost active
HR228doc 40229Post cooling disableINT16Read/write0 = Allowed; 1 = Not allowed
HR229doc 40230Cooling or heating selectionINT16Read/write0 = Heating; 1 = Cooling
HR249doc 40250ResetWrite 1 to clear alarms and resume; reads 0.INT16Read/write
HR251doc 40252Reset run timeWrite 1 to zero the run time.INT16Read/write
HR257doc 40258Bypass position override-1 = no override, 0-100 % position.INT16%Read/write
HR299doc 40300Alarms 11 = alarm active.BITMAP16Readbit 0 = Program error; bit 1 = Data error; bit 2 = Fan 1; bit 3 = Fan 2; bit 4 = Fan 3; bit 5 = Fan 4; bit 6 = Pressure F1; bit 7 = Pressure F3; bit 8 = T1 open; bit 9 = T1 short; bit 10 = T2 open; bit 11 = T2 short; bit 12 = T3 open; bit 13 = T3 short; bit 14 = T4 open; bit 15 = T4 short
HR300doc 40301Alarms 21 = alarm active.BITMAP16Readbit 0 = T5 open; bit 1 = T5 short; bit 4 = T7 open; bit 5 = T7 short; bit 6 = T8 open; bit 7 = T8 short; bit 8 = CP fan 1 high; bit 9 = CP fan 1 low; bit 10 = CP fan 3 high; bit 11 = CP fan 3 low; bit 12 = LS fan 1 low; bit 13 = LS fan 1 high; bit 14 = LS fan 2 low; bit 15 = LS fan 2 high
HR301doc 40302Alarms 31 = alarm active.BITMAP16Readbit 0 = LS fan 3 low; bit 1 = LS fan 3 high; bit 2 = LS fan 4 low; bit 3 = LS fan 4 high; bit 4 = CA fan 1 low; bit 5 = CA fan 1 high; bit 6 = CA fan 2 low; bit 7 = CA fan 2 high; bit 8 = CA fan 3 low; bit 9 = CA fan 3 high; bit 10 = CA fan 4 low; bit 11 = CA fan 4 high; bit 12 = Pa init F1 not stable; bit 13 = Pa init F3 not stable; bit 14 = Pa init F1 too low; bit 15 = Pa init F3 too low
HR302doc 40303Alarms 41 = alarm active.BITMAP16Readbit 0 = Pa init F1 not achieved; bit 1 = Pa init F3 not achieved; bit 2 = Pa init F1 too high; bit 3 = Pa init F3 too high; bit 4 = Maintenance warning; bit 5 = Maintenance fatal; bit 6 = dPa; bit 7 = Fire; bit 8 = End of fire alarm; bit 9 = V lower than Vlow; bit 10 = V higher than Vhigh; bit 11 = Preheat reduced; bit 12 = Preheat stop; bit 13 = Antifreeze reduced; bit 14 = Antifreeze stop; bit 15 = Postheat set point (comfort too low)
HR303doc 40304Alarms 51 = alarm active.BITMAP16Readbit 0 = Postcooling set point (comfort too high); bit 1 = SAT-BA module not responding; bit 2 = Condensate drain pan full; bit 3 = T5 antifreeze stop; bit 4 = Heat wheel RPM out of range; bit 5 = Proportional bypass position; bit 6 = Antifreeze NV stop; bit 7 = Antifreeze BA+ stop; bit 8 = Antifreeze BA- stop; bit 9 = Antifreeze BA+/- stop; bit 10 = Minor maintenance; bit 11 = Defrost alarm; bit 12 = Modbus communication error; bit 13 = Major maintenance
HR425doc 40426Fans working modeSetup value.INT16Read/write0 = Off; 1 = CA constant airflow; 2 = LS 0-10 V linked; 4 = CPs constant pressure; 6 = TQ constant torque; 9 = INIT
HR426doc 40427Exhaust/supply flows ratio5-999 %.INT16%Read/write
HR542doc 40543Modbus address1-247.INT16Read/write

Notes on this map

Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.

Questions about the Swegon TAC5 DG/DM/DT controller (Global HRglobal, HRup, HRflat, HRtotal, HRmural)

What Modbus registers does the Swegon TAC5 DG/DM/DT controller (Global HRglobal, HRup, HRflat, HRtotal, HRmural) have?

This map lists 91 registers: 91 holding registers. 19 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.

Are the Swegon TAC5 DG/DM/DT controller (Global HRglobal, HRup, HRflat, HRtotal, HRmural) Modbus addresses 0-based or 1-based?

The manufacturer's document numbers registers Modicon 3xxxx/4xxxx (drop the prefix, subtract 1). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. The table prints 4xxxx registers. Swegon's TAC5 + Modbus RTU manual says the leading 4 is not part of the address and that addresses are one-based in the documents but zero-based on the wire (register 41001 is sent as 1000). So 40201 is holding register 200 on the wire.

What byte order does the Swegon TAC5 DG/DM/DT controller (Global HRglobal, HRup, HRflat, HRtotal, HRmural) use for 32-bit values?

Multi-register values in this map use CDAB (low word first (word-swapped)). Set your client to this order for every 32/64-bit value in the table.

What are the minimum Modbus registers to integrate the Swegon TAC5 DG/DM/DT controller (Global HRglobal, HRup, HRflat, HRtotal, HRmural)?

Start with HR 199 Control master (Control master); HR 200 Speed selection via Modbus (Speed via Modbus); HR 51 Current working mode (Current working mode); HR 52 Current speed (Current speed); HR 154 Temperature T1 (fresh air in) (Fresh air temperature T1); HR 158 Temperature T5 (supply after exchanger) (Supply temperature T5); HR 299 Alarms 1 (Alarm bitmap 1); HR 249 Reset (Alarm reset).

How do I enable Modbus control of the Swegon TAC5 DG/DM/DT controller (Global HRglobal, HRup, HRflat, HRtotal, HRmural)?

Fit the SAT MODBUS satellite on the TAC5 board (power off) for RTU, or SAT WIFI / SAT ETHERNET for TCP. Then set 40200 to give Modbus control of the speed or airflows.

Where is the official Swegon TAC5 DG/DM/DT controller (Global HRglobal, HRup, HRflat, HRtotal, HRmural) Modbus documentation?

The source is TAC5 + MODBUS TABLE - Installation and user's manual (Cid 050338), revision 2021-09-20, published free by Swegon at https://pre.swegon.com/globalassets/digizuite/11944-en-global_tac5_modbustable_regulation_installation_en.pdf.