- MAH / MGH wall-mount air conditioner control board (Modbus RTU)
Rooftop unit / packaged wall-mount air conditioner · Modbus register map
Marvair MAH / MGH wall-mount air conditioner control board (Modbus RTU) Modbus register map
Updated 19 November 2026
Marvair MAH and MGH packaged wall-mount air conditioners (electronic equipment shelters and process control rooms) carry an electronic control board with two RJ11 Modbus RTU ports. Over Modbus the board accepts thermostat calls, reports switch, relay and sensor states and an alarm word, and exposes fan-speed, economizer and calibration settings.
This page lists 72 Modbus registers for the Marvair MAH / MGH wall-mount air conditioner control board (Modbus RTU) — 35 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Marvair’s own free documentation (linked below) and checked against it.
- Manufacturer
- Marvair
- Model
- MAH / MGH wall-mount air conditioner control board (Modbus RTU)
- Equipment type
- Rooftop unit / packaged wall-mount air conditioner
- Registers
- 72 (35 writable)
- Transport
- Modbus RTU
- Default unit ID
- 1
- Default serial
- 19200 baud, 8N1
- Documented addressing
- 0-based (the number printed is the address on the wire)
- Also known as
- MAH1018A, MAH1024A, MAH1030A, MAH1036A, MAH1042A, MAH1048A, MAH1060A, MGH1072A, MAH2024A, MAH2030A, MAH2036A, MAH2042A, MAH2048A, MAH2060A, MGH2072A, Marvair MAH, Marvair MGH
Integration notes: Marvair MAH / MGH wall-mount air conditioner control board (Modbus RTU)
Set coil 17 = 1 (communicating mode; the map says it mirrors parameter P22), then drive the unit with the Y1/Y2/G/W2/humidity/O call coils (0-4, 24). Read temperatures, relay states, pressure switches and the alarm word (input register 18) to monitor it.
Minimum registers to map
Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.
| Register | Name | Type | Why | Access |
|---|---|---|---|---|
| CO 17 | Communicating thermostat mode | BIT | Communicating (Modbus) thermostat mode | Read/write |
| CO 0 | Y1 compressor call | BIT | Y1 cooling call | Read/write |
| CO 3 | G fan call | BIT | G fan call | Read/write |
| DI 13 | Compressor 1 relay output | BIT | Compressor 1 relay state | Read |
| IR 18 | Alarm status | BITMAP16 | Alarm status bits | Read |
| IR 14 | P1 temperature | UINT16 | P1 temperature | Read |
| IR 27 | Outdoor temperature | UINT16 | Outdoor temperature | Read |
| HR 8 | Modbus timeout | UINT16 | Modbus timeout (minutes) | Read/write |
Enable Modbus control & writes
Set menu item 23 (T'STAT Select) to C for a communicating thermostat via Modbus, or write coil 17 = 1 (the Modbus map says coil 17 reads and changes 'P22', the thermostat-type setting). The Modbus ID (item 24, 1-99, default 1) and baud (item 25: 9.6 or 19 = 9600/19200) are set in the board configuration menu.
Communication loss & watchdog
Register 8 / configuration item 26 sets the Modbus timeout (1-60 min, default 10). After that long without Modbus traffic the board falls back to hardware thermostat calls.
Byte order & addressing
- Only single-coil (05) and single-register (06) writes are accepted.
- Register reads are documented with function 04 only, including the writable ones.
- Temperature value 255 means no sensor or a failed sensor.
Network setup
- Default slave ID 1, 19200 baud, 8 data bits, no parity, 1 stop bit.
- The board has two RJ11 Modbus ports wired in parallel; both carry the same bus.
Watch out for
- Until the thermostat type is C (menu item 23, or coil 17 = 1) the board keeps following its hardwired thermostat inputs.
- After the Modbus timeout with no traffic the board switches back to its hardware thermostat inputs, so poll faster than the timeout.
Marvair MAH / MGH wall-mount air conditioner control board (Modbus RTU) Modbus registers
Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.
| Table | Address | Name | Description | Type | Order | Scale | Units | Access | Values / bits |
|---|---|---|---|---|---|---|---|---|---|
| CO | 0 | Y1 compressor call | Stage 1 cooling request | BIT | Read/write | 0 = No call; 1 = Call | |||
| CO | 1 | Y2 compressor call | Stage 2 cooling request | BIT | Read/write | 0 = No call; 1 = Call | |||
| CO | 2 | Humidity call | Dehumidification request | BIT | Read/write | 0 = No call; 1 = Call | |||
| CO | 3 | G fan call | Fan-only request | BIT | Read/write | 0 = No call; 1 = Call | |||
| CO | 4 | W2 electric heat call | BIT | Read/write | 0 = No call; 1 = Call | ||||
| CO | 17 | Communicating thermostat mode | Same as parameter P22: take calls from Modbus instead of hardware inputs | BIT | Read/write | 0 = Hardware calls (H); 1 = Comm/Modbus calls (C) | |||
| CO | 18 | Read hardware call inputs | 1 = still read hardware thermostat inputs while P22 = C | BIT | Read/write | 0 = Normal (per P22); 1 = Read hardware calls | |||
| CO | 24 | O reversing valve request | BIT | Read/write | 0 = No call; 1 = Call | ||||
| CO | 26 | Emergency ventilation request | BIT | Read/write | 0 = Off; 1 = On | ||||
| CO | 27 | Pulse reheat | Default on | BIT | Read/write | 0 = Off; 1 = On | |||
| DI | 5 | FCC call | BIT | Read | 0 = No call; 1 = Call | ||||
| DI | 6 | High pressure switch 1 | BIT | Read | 0 = Open; 1 = Closed | ||||
| DI | 7 | High pressure switch 2 | BIT | Read | 0 = Open; 1 = Closed | ||||
| DI | 8 | Low pressure switch 1 | AC manual labels it the HPS2 hardware input | BIT | Read | 0 = Open; 1 = Closed | |||
| DI | 9 | Low pressure switch 2 | BIT | Read | 0 = Open; 1 = Closed | ||||
| DI | 10 | OFM mode selection | Outdoor fan motor signal type | BIT | Read | 0 = PWM; 1 = 0-10 V | |||
| DI | 11 | IFM mode selection | Indoor fan motor signal type | BIT | Read | 0 = PWM; 1 = 0-10 V | |||
| DI | 12 | Technician speedup test mode | BIT | Read | 0 = Normal; 1 = Test mode | ||||
| DI | 13 | Compressor 1 relay output | BIT | Read | 0 = Off; 1 = Energized | ||||
| DI | 14 | Compressor 2 relay output | BIT | Read | 0 = Off; 1 = Energized | ||||
| DI | 15 | RH relay output | BIT | Read | 0 = Off; 1 = Energized | ||||
| DI | 16 | W2 relay output | BIT | Read | 0 = Off; 1 = Energized | ||||
| DI | 19 | AC / HP | Unit type | BIT | Read | 0 = AC; 1 = Heat pump | |||
| DI | 20 | EHDD | EHDD option setting | BIT | Read | 0 = No; 1 = Yes | |||
| DI | 21 | SCKT | SCKT option setting | BIT | Read | 0 = No; 1 = Yes | |||
| DI | 22 | Economizer enabled | BIT | Read | 0 = No; 1 = Yes | ||||
| DI | 23 | Economizer sensor type | BIT | Read | 0 = Dry bulb; 1 = Enthalpy | ||||
| DI | 25 | RV output | Reversing valve output | BIT | Read | 0 = Off; 1 = Energized | |||
| DI | 28 | Emergency ventilation status | BIT | Read | 0 = Off; 1 = On | ||||
| DI | 29 | EC relay output | BIT | Read | 0 = Off; 1 = On | ||||
| IR | 9 | Current OFM speed | 0-1023 | UINT16 | Read | ||||
| IR | 10 | Current IFM speed | 0-1023 | UINT16 | Read | ||||
| IR | 11 | Anti-short-cycle compressor 1 | 0-360 counts of 0.5 s | UINT16 | × 0.5 | s | Read | ||
| IR | 12 | Anti-short-cycle compressor 2 | 0-360 counts of 0.5 s | UINT16 | × 0.5 | s | Read | ||
| IR | 13 | Voltage reading | 0-1023; 1023 = above 20 V, 965 = 18 V cutoff | UINT16 | Read | ||||
| IR | 14 | P1 temperature | 0-160 °F; 255 = no sensor | UINT16 | °F | Read | 255 = No sensor | ||
| IR | 15 | P2 temperature | 0-160 °F; 255 = no sensor | UINT16 | °F | Read | 255 = No sensor | ||
| IR | 16 | Freeze sensor 1 temperature | 0-160 °F; 255 = no sensor | UINT16 | °F | Read | 255 = No sensor | ||
| IR | 17 | Freeze sensor 2 temperature | 0-160 °F; 255 = no sensor | UINT16 | °F | Read | 255 = No sensor | ||
| IR | 18 | Alarm status | 0 = no fault | BITMAP16 | Read | bit 0 = Freeze sensor fault; bit 1 = HPS1 fault; bit 2 = Low voltage; bit 6 = LPS1 fault; bit 14 = Y1 locked out; bit 15 = Y2 locked out | |||
| IR | 24 | Software version | Decimal | UINT16 | Read | ||||
| IR | 25 | Supply / mixed air temperature | 0-160 °F | UINT16 | °F | Read | |||
| IR | 27 | Outdoor temperature | 0-160 °F | UINT16 | °F | Read | |||
| IR | 29 | Suction line temperature (LPS1) | 0-160 °F; 255 = open or shorted sensor | UINT16 | °F | Read | 255 = Sensor open/shorted | ||
| IR | 31 | Liquid line temperature (FCC1) | 0-160 °F; 255 = open or shorted sensor | UINT16 | °F | Read | 255 = Sensor open/shorted | ||
| IR | 33 | Defrost sensor temperature | 0-160 °F | UINT16 | °F | Read | |||
| IR | 38 | Economizer output | 0 = off, 20-100 | UINT16 | Read | 0 = Off | |||
| HR | 0 | Heat set point | Reserved for future use; 45-100 °F | UINT16 | °F | Read/write | |||
| HR | 1 | Cool set point | Reserved for future use; 45-100 °F | UINT16 | °F | Read/write | |||
| HR | 2 | Temperature calibration | 0-18, default 9; correction = value - 9 | UINT16 | Read/write | ||||
| HR | 3 | W2 speed multiplier | Percent of Y2 fan speed, 0-100, default 80 | UINT16 | % | Read/write | |||
| HR | 4 | Dehumidification speed multiplier | Percent of Y2 fan speed, 0-100, default 80 | UINT16 | % | Read/write | |||
| HR | 5 | OFM set speed | Outdoor fan speed, 0-1023 | UINT16 | Read/write | ||||
| HR | 6 | IFM Y1 set speed | Indoor fan speed for Y1, 40-100, default 60 | UINT16 | Read/write | ||||
| HR | 7 | IFM Y2 set speed | Indoor fan speed for Y2, 40-100, default 60 | UINT16 | Read/write | ||||
| HR | 8 | Modbus timeout | Minutes without Modbus before reverting to hardware calls; 1-60, default 10 | UINT16 | min | Read/write | |||
| HR | 19 | Minimum position | Economizer minimum position: 20 = minimum, 20-100 = open % | UINT16 | % | Read/write | |||
| HR | 20 | Economizer dry bulb set point | 20-105 °F, default 70 | UINT16 | °F | Read/write | |||
| HR | 21 | ODS set | 0-70, default 50 | UINT16 | Read/write | ||||
| HR | 22 | Fan purge | 0 = no, 10-90 s, default 90 | UINT16 | s | Read/write | 0 = No purge | ||
| HR | 23 | Defrost timer | 30, 60 or 90 min (default 30) | UINT16 | min | Read/write | |||
| HR | 26 | SAS/MAS calibration | 0-18, default 9; correction = value - 9 | UINT16 | Read/write | ||||
| HR | 28 | ODS calibration | 0-18, default 9; correction = value - 9 | UINT16 | Read/write | ||||
| HR | 30 | Suction line temp calibration | 0-18, default 9; correction = value - 9 | UINT16 | Read/write | ||||
| HR | 32 | Liquid line temp calibration | 0-18, default 9; correction = value - 9 | UINT16 | Read/write | ||||
| HR | 34 | DS calibration | 0-18, default 9; correction = value - 9 | UINT16 | Read/write | ||||
| HR | 35 | Dehumidifier set point | 70-75 °F, default 72 | UINT16 | °F | Read/write | |||
| HR | 36 | Pulse reheat differential | 5-10 °F, default 5 | UINT16 | °F | Read/write | |||
| HR | 37 | Economizer enthalpy set point | Modes A..E as 0..4, default 3 (D) | UINT16 | Read/write | 0 = A; 1 = B; 2 = C; 3 = D; 4 = E | |||
| HR | 39 | Head pressure cutout temperature | 75-95, default 85 | UINT16 | Read/write | ||||
| HR | 40 | IFM G set speed | Indoor fan speed for fan-only, 30-100, default 60 | UINT16 | Read/write | ||||
| HR | 41 | OFM speed heating | Outdoor fan speed in heating (heat pumps), 65-100, default 85 | UINT16 | Read/write |
Notes on this map
- The manual prints two columns: a zero-based 'packet register ID' (used as the address here) and a one-based reference ID. Coils and registers each start at zero-based ID 0.
- Bit points: the board reads all of them with function 02 and writes the RW ones with function 05 (single coil only, no function 15). Coils and discrete inputs share one address space. RW bits are listed as coils, read-only bits as discrete inputs.
- Registers: the board reads them with function 04 and writes RW ones with function 06 (single register only, no function 16). RW registers are listed as holding registers so they can be written; the manual only documents reading them with function 04 at the same address. Whether function 01/03 reads work is not stated.
- Writes to read-only points return an error.
- Calibration registers hold 0-18 with 9 = no correction; the applied correction is the value minus 9.
- Heat and cool set points (registers 0-1) are writable but marked 'not currently used, for future use'.
- Anti-short-cycle timers count in 0.5 s steps (scale 0.5).
- This AC manual adds registers 39-41 (head pressure cutout, fan-only speed, heating outdoor fan speed) and gives the IFM Y1/Y2 speeds as 40-100 (default 60) instead of 0-1023; its alarm bit 0 reads 'freeze sensor fault'. The MAH heat pump manual prints a slightly different table (see the separate heat pump file).
- The configuration section gives the Modbus ID range as 1-99 in the table and 1-36161 in the text; the default is 1.
Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.
Questions about the Marvair MAH / MGH wall-mount air conditioner control board (Modbus RTU)
What Modbus registers does the Marvair MAH / MGH wall-mount air conditioner control board (Modbus RTU) have?
This map lists 72 registers: 10 coils, 20 discrete inputs, 17 input registers, 25 holding registers. 35 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.
Are the Marvair MAH / MGH wall-mount air conditioner control board (Modbus RTU) Modbus addresses 0-based or 1-based?
The manufacturer's document numbers registers 0-based (the number printed is the address on the wire). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. The map prints a zero-based packet ID next to a one-based reference ID (1, 2, 3...). The zero-based ID is the wire address.
What are the minimum Modbus registers to integrate the Marvair MAH / MGH wall-mount air conditioner control board (Modbus RTU)?
Start with CO 17 Communicating thermostat mode (Communicating (Modbus) thermostat mode); CO 0 Y1 compressor call (Y1 cooling call); CO 3 G fan call (G fan call); DI 13 Compressor 1 relay output (Compressor 1 relay state); IR 18 Alarm status (Alarm status bits); IR 14 P1 temperature (P1 temperature); IR 27 Outdoor temperature (Outdoor temperature); HR 8 Modbus timeout (Modbus timeout (minutes)).
How do I enable Modbus control of the Marvair MAH / MGH wall-mount air conditioner control board (Modbus RTU)?
Set menu item 23 (T'STAT Select) to C for a communicating thermostat via Modbus, or write coil 17 = 1 (the Modbus map says coil 17 reads and changes 'P22', the thermostat-type setting). The Modbus ID (item 24, 1-99, default 1) and baud (item 25: 9.6 or 19 = 9600/19200) are set in the board configuration menu.
What happens when the Marvair MAH / MGH wall-mount air conditioner control board (Modbus RTU) loses Modbus communication?
Register 8 / configuration item 26 sets the Modbus timeout (1-60 min, default 10). After that long without Modbus traffic the board falls back to hardware thermostat calls.
Where is the official Marvair MAH / MGH wall-mount air conditioner control board (Modbus RTU) Modbus documentation?
The source is MAH1018A-1060A, MGH1072A, MAH2024A-2060A & MGH2072A Wall-Mount AC Installation & Operation Manual (Rev. 7), revision 2026-05, published free by Marvair at https://marvair.com/doc/25/MAH1018A-1060A%20MGH1072A%20MAH2024A-2060A%20%20MGH2072A%20Wall-Mount%20AC%20Manual%20Rev%207.
More Marvair Modbus register maps
- Thermostat (shelter HVAC lead/lag controller)
Marvair CommStat 4 lead/lag controller via Modbus Interface Adapter
Marvair CommStat 4 controllers with protocol version 3 or later and software revision 67 or later, read through the Marvair Modbus Interface Adapter.
Also known as: CommStat 4, CommStat4, CommStat 4 Modbus Interface Adapter, P/03272 - Heat pump (packaged wall-mount / classroom unit)
Marvair MAH heat pump and VAH/VDH Vanguard control board (Modbus RTU)
Marvair MAH1020H-1060H and MAH2024H-2060H wall-mount heat pumps (I&O manual rev. 6); the GAH1024-1060 gas-heat AC manual (rev. 5) and the VAH/VDH Vanguard classroom unit appendices (08/2026) print the same table.
Also known as: MAH1020H, MAH1024H, MAH1030H, MAH1036H, MAH1042H, MAH1048H, MAH1060H, MAH2024H, MAH2030H, MAH2036H, MAH2042H, MAH2048H, MAH2060H, Vanguard VAH, Vanguard VDH, VAH2030, VDH2060, GAH1024, GAH1030, GAH1036, GAH1042, GAH1048, GAH1060, Marvair GAH, Scholar 2 VAH/VDH, Scholar QR VAH/VDH
Other hvac equipment register maps
- Air handler terminal (dual-duct VAV controller)
Neptronic EVCBM dual-duct VAV controller (Modbus communication module)
Neptronic EVCBM dual-duct VAV controllers (master + slave airflow) with the Modbus module, guide EVCBM Dual Duct-V500-Modbus Guide-180927-ESA.
Also known as: EVCBM Dual Duct, EVCB, Neptronic EVCBM Modbus - Thermostat / temperature and process PID controller
Omega CN2200 / CN2400 series temperature and process controllers (Modbus RTU)
Omega CN2200 and CN2400 series controllers with the Modbus comms option (CN2400 software 1.03-3.05, CN2200 1.00-2.10 per the handbook).
Also known as: CN2204, CN2208, CN2408 - Thermostat / room controller (chilled beam with measured airflow and CO2)
Swegon CONDUCTOR W4 room controller (airflow and water, Modbus RTU)
Swegon CONDUCTOR W4 room controller, software 1.12 (technical manual updated 2014-11-21).
Also known as: CONDUCTOR RE W4, CONDUCTOR RE W4 1, Conductor W4 - Air handler (computer room air conditioner)
Vertiv Liebert DS / CW / HPM / PeX / Challenger with iCOM v4 (IntelliSlot Modbus)
Liebert perimeter precision cooling units on the iCOM v4 controller (Challenger 3000, Challenger ITR, CW, Deluxe System/3, DS, PeX with iCOM firmware PA1.04.033.STD or later; HPM with iCOM), read through a Liebert IntelliSlot Modbus 485 or Modbus IP card.
Also known as: Liebert DS, Liebert CW, Liebert HPM, Liebert PeX, Liebert Challenger 3000, Liebert Challenger ITR, Liebert Deluxe System/3, Liebert iCOM v4, IS-485L, IS-IPBML - Air handler (in-row data-centre DX cooling unit)
APC (Schneider Electric) InRow RD direct-expansion cooling unit (Modbus register map 990-3576B)
APC / Schneider Electric InRow RD cooling units, register map part number 990-3576B (08/2015).
Also known as: InRow RD, 990-3576B, Schneider Electric InRow RD - Thermostat / heating controller (district heating and HVAC)
Danfoss ECL Comfort 210 / 296 / 310 heating controller (Modbus RTU / TCP)
ECL Comfort 210, 296 and 310 controllers (and B versions) with any application key; many parameters depend on the loaded application.
Also known as: ECL Comfort 210, ECL Comfort 296, ECL Comfort 310, ECL Comfort 210B, ECL Comfort 310B, 087H3020, 087H3024, 087H3030, 087H3034, 087H3040, 087H3044, 087H3050, 087H3054
All hvac equipment Modbus register maps →
Source: MAH1018A-1060A, MGH1072A, MAH2024A-2060A & MGH2072A Wall-Mount AC Installation & Operation Manual · Rev. 7 · rev. 2026-05. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.