- Home
- Modbus register maps
- Marvair
- CommStat 4 lead/lag controller via Modbus Interface Adapter
Thermostat (shelter HVAC lead/lag controller) · Modbus register map
Marvair CommStat 4 lead/lag controller via Modbus Interface Adapter Modbus register map
Updated 19 November 2026
The CommStat 4 is a Marvair HVAC controller for equipment shelters; a master controller and an optional slave controller each run two HVAC units in lead/lag. A separate Marvair adapter plugs into a CommStat 4 master communications port and acts as a Modbus TCP and Modbus RTU slave. The map gives the controller settings, inputs, unit outputs, lockouts and stage, plus a second register block used to push new settings.
This page lists 107 Modbus registers for the Marvair CommStat 4 lead/lag controller via Modbus Interface Adapter — 43 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Marvair’s own free documentation (linked below) and checked against it.
- Manufacturer
- Marvair
- Model
- CommStat 4 lead/lag controller via Modbus Interface Adapter
- Equipment type
- Thermostat (shelter HVAC lead/lag controller)
- Registers
- 107 (43 writable)
- Transport
- Modbus TCP, Modbus RTU
- Default unit ID
- Not stated
- Default serial
- 9600 baud, 8N1
- TCP port
- 502
- Documented addressing
- Modicon 3xxxx/4xxxx (drop the prefix, subtract 1)
- Firmware
- CommStat 4 protocol 3+, software rev 67+
- Also known as
- CommStat 4, CommStat4, CommStat 4 Modbus Interface Adapter, P/03272
Integration notes: Marvair CommStat 4 lead/lag controller via Modbus Interface Adapter
Poll 40001-40068 over TCP port 502 (or RTU 9600 8N1): 40057 temperature, 40056 stage, 40055/40068 lockouts, 40044 alarms and 40047/40048 unit outputs. Change settings only through the 40101 handshake.
Minimum registers to map
Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.
| Register | Name | Type | Why | Access |
|---|---|---|---|---|
| HR 56 | Current temperature | UINT16 | Current temperature | Read |
| HR 55 | Current stage | UINT16 | Current heating/cooling stage | Read |
| HR 54 | Master controller lockout status | BITMAP16 | Master lockout flags | Read |
| HR 43 | Master controller inputs | BITMAP16 | Smoke / hydrogen / generator alarms | Read |
| HR 46 | Master unit #1 outputs | BITMAP16 | Master unit 1 outputs | Read |
| HR 40 | Lead unit | UINT16 | Lead unit | Read |
| HR 100 | Write control | UINT16 | Write handshake | Read/write |
Enable Modbus control & writes
Install the Marvair Modbus Interface Adapter and plug its RJ11 cable into one of the master communication ports on the CommStat 4 board. Set the adapter IP through its web page.
Byte order & addressing
- Writes go to a separate block (40101 up) and only take effect after the 40101 handshake.
- Current temperature 240 means sensor fault; slave sensor value 0 means sensor fault.
Network setup
- Default IP 192.168.1.19 (static); browse to it to set DHCP or a new static address, then the adapter reboots in about 60 s.
- A reset button on the adapter board restores the default IP.
- RTU terminal: RS-485 A/B, 9600 N 8 1.
- The adapter needs 24-60 V DC and must be mounted inside the shelter.
Watch out for
- Only CommStat 4 protocol version 3+ with software revision 67+ is supported.
- In a two-controller shelter one master port may already carry the master/slave link.
Marvair CommStat 4 lead/lag controller via Modbus Interface Adapter Modbus registers
Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.
| Table | Address | Name | Description | Type | Order | Scale | Units | Access | Values / bits |
|---|---|---|---|---|---|---|---|---|---|
| HR | 0doc 40001 | Master firmware revision | Below 255 | UINT16 | Read | ||||
| HR | 1doc 40002 | Protocol version number | 3 or 4 | UINT16 | Read | ||||
| HR | 2doc 40003 | Setting #2: F/C | Display temperature unit | UINT16 | Read | 0 = Celsius; 1 = Fahrenheit | |||
| HR | 3doc 40004 | Setting #3: Changeover days | Lead/lag changeover interval in half days (1-14) | UINT16 | Read | ||||
| HR | 4doc 40005 | Setting #4: Cool set point | Raw setting; the adapter guide refers to the CommStat 4 manual | UINT16 | Read | ||||
| HR | 5doc 40006 | Setting #5: Heat set point | Raw setting; the adapter guide refers to the CommStat 4 manual | UINT16 | Read | ||||
| HR | 6doc 40007 | Setting #6: High building temp 1 set point | Raw setting; the adapter guide refers to the CommStat 4 manual | UINT16 | Read | ||||
| HR | 7doc 40008 | Setting #7: High building temp 2 set point | Raw setting; the adapter guide refers to the CommStat 4 manual | UINT16 | Read | ||||
| HR | 8doc 40009 | Setting #8: Low building temp set point | Raw setting; the adapter guide refers to the CommStat 4 manual | UINT16 | Read | ||||
| HR | 9doc 40010 | Setting #9: Blower on | Continuous blower | UINT16 | Read | 0 = Off; 1 = On | |||
| HR | 10doc 40011 | Setting #10: High voltage input enable / alarm output enable | UINT16 | Read | |||||
| HR | 11doc 40012 | Setting #11: Anti-short cycle timer | Number of minutes (see the CommStat 4 manual) | UINT16 | min | Read | |||
| HR | 12doc 40013 | Setting #12: Stage 1 differential | Raw setting; the adapter guide refers to the CommStat 4 manual | UINT16 | Read | ||||
| HR | 13doc 40014 | Setting #13: Stage 2 differential | Raw setting; the adapter guide refers to the CommStat 4 manual | UINT16 | Read | ||||
| HR | 14doc 40015 | Setting #14: Off differential | Raw setting; the adapter guide refers to the CommStat 4 manual | UINT16 | Read | ||||
| HR | 15doc 40016 | Setting #15: Blower off time delay | Raw setting; the adapter guide refers to the CommStat 4 manual | UINT16 | Read | ||||
| HR | 16doc 40017 | Setting #16: Operational units when generator is used | UINT16 | Read | |||||
| HR | 17doc 40018 | Setting #17: Smoke auto reset | 0 = manual reset; 3 to 10 = minutes until automatic reset | UINT16 | Read | 0 = Manual reset | |||
| HR | 18doc 40019 | Setting #18: Smoke relay | UINT16 | Read | 0 = Normally open; 1 = Normally closed | ||||
| HR | 19doc 40020 | Setting #19: ECON mode enable | UINT16 | Read | 0 = No; 1 = Yes; 2 = Verizon special setting | ||||
| HR | 20doc 40021 | Setting #20: Multiple sensors | UINT16 | Read | 0 = No; 1 = Yes | ||||
| HR | 21doc 40022 | Setting #21: Aux 1 relay | UINT16 | Read | 0 = Normally open; 1 = Normally closed; 2 = Off | ||||
| HR | 22doc 40023 | Setting #22: Aux 2 relay | UINT16 | Read | 0 = Normally open; 1 = Normally closed; 2 = Off | ||||
| HR | 23doc 40024 | Setting #23: Excessive cycle | 0 = off; otherwise cycles allowed per 2-hour period | UINT16 | Read | 0 = Off | |||
| HR | 24doc 40025 | Setting #24: Language | UINT16 | Read | 0 = English; 1 = Spanish; 2 = French | ||||
| HR | 25doc 40026 | Setting #25: AC / HP system | UINT16 | Read | 0 = Heat pump; 1 = One AC; 2 = Two AC | ||||
| HR | 26doc 40027 | Setting #26: Master/slave | Role of this controller | UINT16 | Read | 0 = Slave; 1 = Master | |||
| HR | 27doc 40028 | Setting #27: Stage 3 differential | Raw setting; the adapter guide refers to the CommStat 4 manual | UINT16 | Read | ||||
| HR | 28doc 40029 | Setting #28: Stage 4 differential | Raw setting; the adapter guide refers to the CommStat 4 manual | UINT16 | Read | ||||
| HR | 29doc 40030 | Setting #29: Stage 5 differential | Raw setting; the adapter guide refers to the CommStat 4 manual | UINT16 | Read | ||||
| HR | 30doc 40031 | Setting #30: Stage 6 differential | Raw setting; the adapter guide refers to the CommStat 4 manual | UINT16 | Read | ||||
| HR | 31doc 40032 | Setting #31: Stage 7 differential | Raw setting; the adapter guide refers to the CommStat 4 manual | UINT16 | Read | ||||
| HR | 32doc 40033 | Setting #32: Stage 8 differential | Raw setting; the adapter guide refers to the CommStat 4 manual | UINT16 | Read | ||||
| HR | 33doc 40034 | Setting #33: Stage 9 differential | Raw setting; the adapter guide refers to the CommStat 4 manual | UINT16 | Read | ||||
| HR | 34doc 40035 | Setting #34: Stage 10 differential | Raw setting; the adapter guide refers to the CommStat 4 manual | UINT16 | Read | ||||
| HR | 35doc 40036 | Setting #35: Stage 11 differential | Raw setting; the adapter guide refers to the CommStat 4 manual | UINT16 | Read | ||||
| HR | 36doc 40037 | Setting #36: Stage 12 differential | Raw setting; the adapter guide refers to the CommStat 4 manual | UINT16 | Read | ||||
| HR | 37doc 40038 | Setting #37: Total number of units | UINT16 | Read | |||||
| HR | 38doc 40039 | Setting #38: Stage 2 differential in econ cooling mode | Raw setting; the adapter guide refers to the CommStat 4 manual | UINT16 | Read | ||||
| HR | 39doc 40040 | Controller on/off | UINT16 | Read | 0 = Off; 1 = On | ||||
| HR | 40doc 40041 | Lead unit | Which unit currently leads | UINT16 | Read | 0 = Master #1; 1 = Master #2; 2 = Slave #1; 3 = Slave #2 | |||
| HR | 41doc 40042 | Password #1 | Password = (password #1 x 4) + password #2 | UINT16 | Read | ||||
| HR | 42doc 40043 | Password #2 | Password = (password #1 x 4) + password #2 | UINT16 | Read | ||||
| HR | 43doc 40044 | Master controller inputs | Smoke, hydrogen, generator and aux inputs at the master | BITMAP16 | Read | bit 0 = Aux 2 signal present; bit 1 = Aux 1 signal present; bit 2 = Generator in use; bit 3 = High hydrogen level; bit 4 = Smoke detected | |||
| HR | 44doc 40045 | Master unit #1 inputs | Voltage, lockout and economizer state of master unit 1 | BITMAP16 | Read | bit 0 = Running in economizer mode; bit 1 = Running in AC mode; bit 2 = Unit locked out; bit 3 = 230 V present; bit 4 = 24 V present | |||
| HR | 45doc 40046 | Master unit #2 inputs | Voltage, lockout and economizer state of master unit 2 | BITMAP16 | Read | bit 0 = Running in economizer mode; bit 1 = Running in AC mode; bit 2 = Unit locked out; bit 3 = 230 V present; bit 4 = 24 V present | |||
| HR | 46doc 40047 | Master unit #1 outputs | BITMAP16 | Read | bit 0 = DCAMR output on; bit 1 = MAR output on; bit 2 = G output on; bit 3 = W output on; bit 4 = O output on; bit 5 = 2 output on; bit 6 = Y output on | ||||
| HR | 47doc 40048 | Master unit #2 outputs | BITMAP16 | Read | bit 0 = DCAMR output on; bit 1 = MAR output on; bit 2 = G output on; bit 3 = W output on; bit 4 = O output on; bit 5 = 2 output on; bit 6 = Y output on | ||||
| HR | 48doc 40049 | Output command master to slave unit #1 | BITMAP16 | Read | bit 0 = DCAMR output on; bit 1 = MAR output on; bit 2 = G output on; bit 3 = W output on; bit 4 = O output on; bit 5 = 2 output on; bit 6 = Y output on | ||||
| HR | 49doc 40050 | Output command master to slave unit #2 | BITMAP16 | Read | bit 0 = DCAMR output on; bit 1 = MAR output on; bit 2 = G output on; bit 3 = W output on; bit 4 = O output on; bit 5 = 2 output on; bit 6 = Y output on | ||||
| HR | 54doc 40055 | Master controller lockout status | BITMAP16 | Read | bit 0 = Master unit 1 locked out; bit 1 = Master unit 2 locked out; bit 2 = Slave unit 1 locked out; bit 3 = Slave unit 2 locked out; bit 4 = Master in smoke alarm lockout; bit 5 = Master in low building temp lockout; bit 6 = Master in high building temp 1 lockout; bit 7 = Master in high building temp 2 lockout | ||||
| HR | 55doc 40056 | Current stage | Cooling/heating stage now active | UINT16 | Read | 0 = Stage 12 cooling; 1 = Stage 11 cooling; 2 = Stage 10 cooling; 3 = Stage 9 cooling; 4 = Stage 8 cooling; 5 = Stage 7 cooling; 6 = Stage 6 cooling; 7 = Stage 5 cooling; 8 = Stage 4 cooling; 9 = Stage 3 cooling; 10 = Stage 2 cooling; 11 = Stage 1 cooling; 12 = Stage 0 (idle); 13 = Stage 1 heating; 14 = Stage 2 heating; 15 = Stage 3 heating; 16 = Stage 4 heating | |||
| HR | 56doc 40057 | Current temperature | 240 = sensor fault; below 240 = temperature (unit not stated in the adapter guide) | UINT16 | Read | 240 = Sensor fault | |||
| HR | 57doc 40058 | Comfort mode time left | Minutes left in comfort mode divided by 3 | UINT16 | Read | ||||
| HR | 58doc 40059 | Slave firmware revision | Below 255 | UINT16 | Read | ||||
| HR | 59doc 40060 | Slave controller inputs | BITMAP16 | Read | bit 0 = Aux 2 signal present; bit 1 = Aux 1 signal present; bit 2 = Generator in use; bit 3 = High hydrogen level; bit 4 = Smoke detected | ||||
| HR | 60doc 40061 | Slave unit #1 inputs | BITMAP16 | Read | bit 0 = Running in economizer mode; bit 1 = Running in AC mode; bit 2 = Unit locked out; bit 3 = 230 V present; bit 4 = 24 V present | ||||
| HR | 61doc 40062 | Slave unit #2 inputs | BITMAP16 | Read | bit 0 = Running in economizer mode; bit 1 = Running in AC mode; bit 2 = Unit locked out; bit 3 = 230 V present; bit 4 = 24 V present | ||||
| HR | 62doc 40063 | Slave temp sensor #1 | 0 = sensor fault; 30-150 = temperature | UINT16 | °F | Read | 0 = Sensor fault | ||
| HR | 63doc 40064 | Slave temp sensor #2 | 0 = sensor fault; 30-150 = temperature | UINT16 | °F | Read | 0 = Sensor fault | ||
| HR | 64doc 40065 | Slave temp sensor #3 | 0 = sensor fault; 30-150 = temperature | UINT16 | °F | Read | 0 = Sensor fault | ||
| HR | 65doc 40066 | Slave unit #1 output status | BITMAP16 | Read | bit 0 = DCAMR output on; bit 1 = MAR output on; bit 2 = G output on; bit 3 = W output on; bit 4 = O output on; bit 5 = 2 output on; bit 6 = Y output on | ||||
| HR | 66doc 40067 | Slave unit #2 output status | BITMAP16 | Read | bit 0 = DCAMR output on; bit 1 = MAR output on; bit 2 = G output on; bit 3 = W output on; bit 4 = O output on; bit 5 = 2 output on; bit 6 = Y output on | ||||
| HR | 67doc 40068 | Slave controller lockout status | BITMAP16 | Read | bit 0 = Master unit 1 locked out; bit 1 = Master unit 2 locked out; bit 2 = Slave unit 1 locked out; bit 3 = Slave unit 2 locked out; bit 4 = Slave in smoke alarm lockout; bit 5 = Slave in low building temp lockout; bit 6 = Slave in high building temp 1 lockout; bit 7 = Slave in high building temp 2 lockout | ||||
| HR | 100doc 40101 | Write control | Handshake for pushing new settings; see notes | UINT16 | Read/write | 0 = Normal / write complete (adapter); 1 = Client: hold new-value registers for editing; 2 = Client: send new values to CommStat 4; 3 = Adapter: write accepted, waiting for cycle | |||
| HR | 101doc 40102 | New setting #2: F/C | New value, sent when 40101 = 2 | UINT16 | Read/write | 0 = Celsius; 1 = Fahrenheit | |||
| HR | 102doc 40103 | New setting #3: Changeover days | New value, sent when 40101 = 2 | UINT16 | Read/write | ||||
| HR | 103doc 40104 | New setting #4: Cool set point | New value, sent when 40101 = 2 | UINT16 | Read/write | ||||
| HR | 104doc 40105 | New setting #5: Heat set point | New value, sent when 40101 = 2 | UINT16 | Read/write | ||||
| HR | 105doc 40106 | New setting #6: High building temp 1 set point | New value, sent when 40101 = 2 | UINT16 | Read/write | ||||
| HR | 106doc 40107 | New setting #7: High building temp 2 set point | New value, sent when 40101 = 2 | UINT16 | Read/write | ||||
| HR | 107doc 40108 | New setting #8: Low building temp set point | New value, sent when 40101 = 2 | UINT16 | Read/write | ||||
| HR | 108doc 40109 | New setting #9: Blower on | New value, sent when 40101 = 2 | UINT16 | Read/write | 0 = Off; 1 = On | |||
| HR | 109doc 40110 | New setting #10: High voltage input enable / alarm output enable | New value, sent when 40101 = 2 | UINT16 | Read/write | ||||
| HR | 110doc 40111 | New setting #11: Anti-short cycle timer | New value, sent when 40101 = 2 | UINT16 | min | Read/write | |||
| HR | 111doc 40112 | New setting #12: Stage 1 differential | New value, sent when 40101 = 2 | UINT16 | Read/write | ||||
| HR | 112doc 40113 | New setting #13: Stage 2 differential | New value, sent when 40101 = 2 | UINT16 | Read/write | ||||
| HR | 113doc 40114 | New setting #14: Off differential | New value, sent when 40101 = 2 | UINT16 | Read/write | ||||
| HR | 114doc 40115 | New setting #15: Blower off time delay | New value, sent when 40101 = 2 | UINT16 | Read/write | ||||
| HR | 115doc 40116 | New setting #16: Operational units when generator is used | New value, sent when 40101 = 2 | UINT16 | Read/write | ||||
| HR | 116doc 40117 | New setting #17: Smoke auto reset | New value, sent when 40101 = 2 | UINT16 | Read/write | 0 = Manual reset | |||
| HR | 117doc 40118 | New setting #18: Smoke relay | New value, sent when 40101 = 2 | UINT16 | Read/write | 0 = Normally open; 1 = Normally closed | |||
| HR | 118doc 40119 | New setting #19: ECON mode enable | New value, sent when 40101 = 2 | UINT16 | Read/write | 0 = No; 1 = Yes; 2 = Verizon special setting | |||
| HR | 119doc 40120 | New setting #20: Multiple sensors | New value, sent when 40101 = 2 | UINT16 | Read/write | 0 = No; 1 = Yes | |||
| HR | 120doc 40121 | New setting #21: Aux 1 relay | New value, sent when 40101 = 2 | UINT16 | Read/write | 0 = Normally open; 1 = Normally closed; 2 = Off | |||
| HR | 121doc 40122 | New setting #22: Aux 2 relay | New value, sent when 40101 = 2 | UINT16 | Read/write | 0 = Normally open; 1 = Normally closed; 2 = Off | |||
| HR | 122doc 40123 | New setting #23: Excessive cycle | New value, sent when 40101 = 2 | UINT16 | Read/write | 0 = Off | |||
| HR | 123doc 40124 | New setting #24: Language | New value, sent when 40101 = 2 | UINT16 | Read/write | 0 = English; 1 = Spanish; 2 = French | |||
| HR | 124doc 40125 | New setting #25: AC / HP system | New value, sent when 40101 = 2 | UINT16 | Read/write | 0 = Heat pump; 1 = One AC; 2 = Two AC | |||
| HR | 125doc 40126 | New setting #26: Master/slave | New value, sent when 40101 = 2 | UINT16 | Read/write | 0 = Slave; 1 = Master | |||
| HR | 126doc 40127 | New setting #27: Stage 3 differential | New value, sent when 40101 = 2 | UINT16 | Read/write | ||||
| HR | 127doc 40128 | New setting #28: Stage 4 differential | New value, sent when 40101 = 2 | UINT16 | Read/write | ||||
| HR | 128doc 40129 | New setting #29: Stage 5 differential | New value, sent when 40101 = 2 | UINT16 | Read/write | ||||
| HR | 129doc 40130 | New setting #30: Stage 6 differential | New value, sent when 40101 = 2 | UINT16 | Read/write | ||||
| HR | 130doc 40131 | New setting #31: Stage 7 differential | New value, sent when 40101 = 2 | UINT16 | Read/write | ||||
| HR | 131doc 40132 | New setting #32: Stage 8 differential | New value, sent when 40101 = 2 | UINT16 | Read/write | ||||
| HR | 132doc 40133 | New setting #33: Stage 9 differential | New value, sent when 40101 = 2 | UINT16 | Read/write | ||||
| HR | 133doc 40134 | New setting #34: Stage 10 differential | New value, sent when 40101 = 2 | UINT16 | Read/write | ||||
| HR | 134doc 40135 | New setting #35: Stage 11 differential | New value, sent when 40101 = 2 | UINT16 | Read/write | ||||
| HR | 135doc 40136 | New setting #36: Stage 12 differential | New value, sent when 40101 = 2 | UINT16 | Read/write | ||||
| HR | 136doc 40137 | New setting #37: Total number of units | New value, sent when 40101 = 2 | UINT16 | Read/write | ||||
| HR | 137doc 40138 | New setting #38: Stage 2 differential in econ cooling mode | New value, sent when 40101 = 2 | UINT16 | Read/write | ||||
| HR | 138doc 40139 | New controller on/off | Sent when 40101 = 2 | UINT16 | Read/write | 0 = Off; 1 = On | |||
| HR | 139doc 40140 | New lead unit | Sent when 40101 = 2 | UINT16 | Read/write | 0 = Master #1; 1 = Master #2; 2 = Slave #1; 3 = Slave #2 | |||
| HR | 140doc 40141 | New password #1 | UINT16 | Read/write | |||||
| HR | 141doc 40142 | New password #2 | UINT16 | Read/write | |||||
| HR | 142doc 40143 | Function code | Purpose of this write (codes not listed in the guide) | UINT16 | Read/write |
Notes on this map
- All values are single registers. The bit notes only define bits 0-7.
- The adapter guide gives no units or scaling for the set points and differentials; it only says to see the CommStat 4 manual. They are listed here as raw values. Only the slave sensor readings 40063-40065 are labelled °F.
- Registers 40051-40054 (saved output values) are marked internal use and are left out.
- Write procedure: write 1 to 40101 so the adapter stops refreshing the new-value block, write the new values to 40102-40143, then write 2 to 40101. The adapter shows 3 while waiting and returns to 0 when the CommStat 4 has taken the values.
- The guide does not list the function-code values for 40143 or the value meanings of settings #10 and #16.
- The guide states a default Modbus RTU setting of 9600 N 8 1 but no RTU slave address.
- The guide does not name the read function code; by the usual Modicon convention, 4xxxx numbers are holding registers (function 03).
Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.
Questions about the Marvair CommStat 4 lead/lag controller via Modbus Interface Adapter
What Modbus registers does the Marvair CommStat 4 lead/lag controller via Modbus Interface Adapter have?
This map lists 107 registers: 107 holding registers. 43 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.
Are the Marvair CommStat 4 lead/lag controller via Modbus Interface Adapter Modbus addresses 0-based or 1-based?
The manufacturer's document numbers registers Modicon 3xxxx/4xxxx (drop the prefix, subtract 1). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. Registers are printed as 40001-40068 (read) and 40101-40143 (write), Modicon holding-register style. Request 40001 as wire address 0 and 40101 as wire address 100.
What are the minimum Modbus registers to integrate the Marvair CommStat 4 lead/lag controller via Modbus Interface Adapter?
Start with HR 56 Current temperature (Current temperature); HR 55 Current stage (Current heating/cooling stage); HR 54 Master controller lockout status (Master lockout flags); HR 43 Master controller inputs (Smoke / hydrogen / generator alarms); HR 46 Master unit #1 outputs (Master unit 1 outputs); HR 40 Lead unit (Lead unit); HR 100 Write control (Write handshake).
How do I enable Modbus control of the Marvair CommStat 4 lead/lag controller via Modbus Interface Adapter?
Install the Marvair Modbus Interface Adapter and plug its RJ11 cable into one of the master communication ports on the CommStat 4 board. Set the adapter IP through its web page.
Where is the official Marvair CommStat 4 lead/lag controller via Modbus Interface Adapter Modbus documentation?
The source is CommStat 4 Modbus Interface Adapter Installation and Operation Manual (P/03272 rev. 5), revision 2021-12, published free by Marvair at https://marvair.com/doc/121/CommStat%204%20Modbus%20Adapter%20Manual.
More Marvair Modbus register maps
- Rooftop unit / packaged wall-mount air conditioner
Marvair MAH / MGH wall-mount air conditioner control board (Modbus RTU)
Marvair MAH1018A-1060A, MGH1072A, MAH2024A-2060A and MGH2072A wall-mount air conditioners with the electronic control board (I&O manual rev. 7).
Also known as: MAH1018A, MAH1024A, MAH1030A, MAH1036A, MAH1042A, MAH1048A, MAH1060A, MGH1072A, MAH2024A, MAH2030A, MAH2036A, MAH2042A, MAH2048A, MAH2060A, MGH2072A, Marvair MAH, Marvair MGH - Heat pump (packaged wall-mount / classroom unit)
Marvair MAH heat pump and VAH/VDH Vanguard control board (Modbus RTU)
Marvair MAH1020H-1060H and MAH2024H-2060H wall-mount heat pumps (I&O manual rev. 6); the GAH1024-1060 gas-heat AC manual (rev. 5) and the VAH/VDH Vanguard classroom unit appendices (08/2026) print the same table.
Also known as: MAH1020H, MAH1024H, MAH1030H, MAH1036H, MAH1042H, MAH1048H, MAH1060H, MAH2024H, MAH2030H, MAH2036H, MAH2042H, MAH2048H, MAH2060H, Vanguard VAH, Vanguard VDH, VAH2030, VDH2060, GAH1024, GAH1030, GAH1036, GAH1042, GAH1048, GAH1060, Marvair GAH, Scholar 2 VAH/VDH, Scholar QR VAH/VDH
Other hvac equipment register maps
- Thermostat / fan coil controller
Neptronic EFCB-OE1 Series networkable fan coil controller (Modbus RTU)
Neptronic EFCB-OE1 Series fan coil controllers (24 or 240 Vac; 0, 2 or 4 relays), guide EFCB1x-OE1-Modbus Guide (V2.16)-260626.
Also known as: EFCB10T-OE1, EFCB12T-OE1, EFCB10TU2-OE1, EFCB10TU4-OE1, EFCB12TU2-OE1, EFCB12TU4-OE1, EFCB1x-OE1 - Thermostat / fan coil and unitary controller
Neptronic TSUB Series universal wall-mount controller (Modbus RTU)
Neptronic TSUB Series universal wall-mount controllers with Modbus, guide TSUB-Modbus Guide-250829 (V1.13).
Also known as: TSUB Series, TSUB universal wall-mount controller - Thermostat / room controller (chilled beam with supply and extract air dampers)
Swegon CONDUCTOR W3 room controller (air and water, Modbus RTU)
Swegon CONDUCTOR W3 room controller, software 1.38 and later (technical manual updated 2015-06-15).
Also known as: CONDUCTOR RE W3, Conductor W3 - Air handler (in-row computer room cooling unit)
Vertiv Liebert CRV in-row cooling unit with iCOM v4 (IntelliSlot Modbus)
Liebert CRV row-based cooling units (DX and chilled water) on the iCOM v4 controller with a Liebert IntelliSlot Modbus 485 or Modbus IP card.
Also known as: Liebert CRV, CRV, Liebert CRV iCOM - Air handler (in-row self-contained DX cooling unit)
APC (Schneider Electric) InRow ACSC 100 Series self-contained DX cooling unit
APC by Schneider Electric InRow SC (ACSC 100 series) self-contained cooling units, per register map part number 990-3027D.
Also known as: ACSC100, InRow SC, InRow ACSC - Rooftop unit
Daikin Applied Rebel / Rebel Applied rooftop (MicroTech 4 controller)
Daikin Applied Rebel Applied (DPSA, R-410A/R-32) and Rebel (DPS, R-32) packaged rooftops with MicroTech 4 controller and Modbus RTU module, per ED 19133-2 (Oct 2025).
Also known as: DPSA, DPS, Rebel Applied, Rebel, MicroTech 4 rooftop, ED 19133-2
All hvac equipment Modbus register maps →
Source: CommStat 4 Modbus Interface Adapter Installation and Operation Manual · P/03272 rev. 5 · rev. 2021-12. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.