Thermostat (shelter HVAC lead/lag controller) · Modbus register map

Marvair CommStat 4 lead/lag controller via Modbus Interface Adapter Modbus register map

Updated 19 November 2026

Short answer

The CommStat 4 is a Marvair HVAC controller for equipment shelters; a master controller and an optional slave controller each run two HVAC units in lead/lag. A separate Marvair adapter plugs into a CommStat 4 master communications port and acts as a Modbus TCP and Modbus RTU slave. The map gives the controller settings, inputs, unit outputs, lockouts and stage, plus a second register block used to push new settings.

This page lists 107 Modbus registers for the Marvair CommStat 4 lead/lag controller via Modbus Interface Adapter — 43 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Marvair’s own free documentation (linked below) and checked against it.

Manufacturer
Marvair
Model
CommStat 4 lead/lag controller via Modbus Interface Adapter
Equipment type
Thermostat (shelter HVAC lead/lag controller)
Registers
107 (43 writable)
Transport
Modbus TCP, Modbus RTU
Default unit ID
Not stated
Default serial
9600 baud, 8N1
TCP port
502
Documented addressing
Modicon 3xxxx/4xxxx (drop the prefix, subtract 1)
Firmware
CommStat 4 protocol 3+, software rev 67+
Also known as
CommStat 4, CommStat4, CommStat 4 Modbus Interface Adapter, P/03272
Source document
CommStat 4 Modbus Interface Adapter Installation and Operation Manual · P/03272 rev. 5 · rev. 2021-12
Download CSV all columns JSON Manufacturer PDF ↗

Integration notes: Marvair CommStat 4 lead/lag controller via Modbus Interface Adapter

Integration in brief

Poll 40001-40068 over TCP port 502 (or RTU 9600 8N1): 40057 temperature, 40056 stage, 40055/40068 lockouts, 40044 alarms and 40047/40048 unit outputs. Change settings only through the 40101 handshake.

Minimum registers to map

Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.

RegisterNameTypeWhyAccess
HR 56Current temperatureUINT16Current temperatureRead
HR 55Current stageUINT16Current heating/cooling stageRead
HR 54Master controller lockout statusBITMAP16Master lockout flagsRead
HR 43Master controller inputsBITMAP16Smoke / hydrogen / generator alarmsRead
HR 46Master unit #1 outputsBITMAP16Master unit 1 outputsRead
HR 40Lead unitUINT16Lead unitRead
HR 100Write controlUINT16Write handshakeRead/write

Enable Modbus control & writes

Install the Marvair Modbus Interface Adapter and plug its RJ11 cable into one of the master communication ports on the CommStat 4 board. Set the adapter IP through its web page.

Byte order & addressing

Network setup

Watch out for

Marvair CommStat 4 lead/lag controller via Modbus Interface Adapter Modbus registers

Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.

107 of 107 shown
Marvair CommStat 4 lead/lag controller via Modbus Interface Adapter Modbus register map
TableAddressNameDescriptionTypeOrderScaleUnitsAccessValues / bits
HR0doc 40001Master firmware revisionBelow 255UINT16Read
HR1doc 40002Protocol version number3 or 4UINT16Read
HR2doc 40003Setting #2: F/CDisplay temperature unitUINT16Read0 = Celsius; 1 = Fahrenheit
HR3doc 40004Setting #3: Changeover daysLead/lag changeover interval in half days (1-14)UINT16Read
HR4doc 40005Setting #4: Cool set pointRaw setting; the adapter guide refers to the CommStat 4 manualUINT16Read
HR5doc 40006Setting #5: Heat set pointRaw setting; the adapter guide refers to the CommStat 4 manualUINT16Read
HR6doc 40007Setting #6: High building temp 1 set pointRaw setting; the adapter guide refers to the CommStat 4 manualUINT16Read
HR7doc 40008Setting #7: High building temp 2 set pointRaw setting; the adapter guide refers to the CommStat 4 manualUINT16Read
HR8doc 40009Setting #8: Low building temp set pointRaw setting; the adapter guide refers to the CommStat 4 manualUINT16Read
HR9doc 40010Setting #9: Blower onContinuous blowerUINT16Read0 = Off; 1 = On
HR10doc 40011Setting #10: High voltage input enable / alarm output enableUINT16Read
HR11doc 40012Setting #11: Anti-short cycle timerNumber of minutes (see the CommStat 4 manual)UINT16minRead
HR12doc 40013Setting #12: Stage 1 differentialRaw setting; the adapter guide refers to the CommStat 4 manualUINT16Read
HR13doc 40014Setting #13: Stage 2 differentialRaw setting; the adapter guide refers to the CommStat 4 manualUINT16Read
HR14doc 40015Setting #14: Off differentialRaw setting; the adapter guide refers to the CommStat 4 manualUINT16Read
HR15doc 40016Setting #15: Blower off time delayRaw setting; the adapter guide refers to the CommStat 4 manualUINT16Read
HR16doc 40017Setting #16: Operational units when generator is usedUINT16Read
HR17doc 40018Setting #17: Smoke auto reset0 = manual reset; 3 to 10 = minutes until automatic resetUINT16Read0 = Manual reset
HR18doc 40019Setting #18: Smoke relayUINT16Read0 = Normally open; 1 = Normally closed
HR19doc 40020Setting #19: ECON mode enableUINT16Read0 = No; 1 = Yes; 2 = Verizon special setting
HR20doc 40021Setting #20: Multiple sensorsUINT16Read0 = No; 1 = Yes
HR21doc 40022Setting #21: Aux 1 relayUINT16Read0 = Normally open; 1 = Normally closed; 2 = Off
HR22doc 40023Setting #22: Aux 2 relayUINT16Read0 = Normally open; 1 = Normally closed; 2 = Off
HR23doc 40024Setting #23: Excessive cycle0 = off; otherwise cycles allowed per 2-hour periodUINT16Read0 = Off
HR24doc 40025Setting #24: LanguageUINT16Read0 = English; 1 = Spanish; 2 = French
HR25doc 40026Setting #25: AC / HP systemUINT16Read0 = Heat pump; 1 = One AC; 2 = Two AC
HR26doc 40027Setting #26: Master/slaveRole of this controllerUINT16Read0 = Slave; 1 = Master
HR27doc 40028Setting #27: Stage 3 differentialRaw setting; the adapter guide refers to the CommStat 4 manualUINT16Read
HR28doc 40029Setting #28: Stage 4 differentialRaw setting; the adapter guide refers to the CommStat 4 manualUINT16Read
HR29doc 40030Setting #29: Stage 5 differentialRaw setting; the adapter guide refers to the CommStat 4 manualUINT16Read
HR30doc 40031Setting #30: Stage 6 differentialRaw setting; the adapter guide refers to the CommStat 4 manualUINT16Read
HR31doc 40032Setting #31: Stage 7 differentialRaw setting; the adapter guide refers to the CommStat 4 manualUINT16Read
HR32doc 40033Setting #32: Stage 8 differentialRaw setting; the adapter guide refers to the CommStat 4 manualUINT16Read
HR33doc 40034Setting #33: Stage 9 differentialRaw setting; the adapter guide refers to the CommStat 4 manualUINT16Read
HR34doc 40035Setting #34: Stage 10 differentialRaw setting; the adapter guide refers to the CommStat 4 manualUINT16Read
HR35doc 40036Setting #35: Stage 11 differentialRaw setting; the adapter guide refers to the CommStat 4 manualUINT16Read
HR36doc 40037Setting #36: Stage 12 differentialRaw setting; the adapter guide refers to the CommStat 4 manualUINT16Read
HR37doc 40038Setting #37: Total number of unitsUINT16Read
HR38doc 40039Setting #38: Stage 2 differential in econ cooling modeRaw setting; the adapter guide refers to the CommStat 4 manualUINT16Read
HR39doc 40040Controller on/offUINT16Read0 = Off; 1 = On
HR40doc 40041Lead unitWhich unit currently leadsUINT16Read0 = Master #1; 1 = Master #2; 2 = Slave #1; 3 = Slave #2
HR41doc 40042Password #1Password = (password #1 x 4) + password #2UINT16Read
HR42doc 40043Password #2Password = (password #1 x 4) + password #2UINT16Read
HR43doc 40044Master controller inputsSmoke, hydrogen, generator and aux inputs at the masterBITMAP16Readbit 0 = Aux 2 signal present; bit 1 = Aux 1 signal present; bit 2 = Generator in use; bit 3 = High hydrogen level; bit 4 = Smoke detected
HR44doc 40045Master unit #1 inputsVoltage, lockout and economizer state of master unit 1BITMAP16Readbit 0 = Running in economizer mode; bit 1 = Running in AC mode; bit 2 = Unit locked out; bit 3 = 230 V present; bit 4 = 24 V present
HR45doc 40046Master unit #2 inputsVoltage, lockout and economizer state of master unit 2BITMAP16Readbit 0 = Running in economizer mode; bit 1 = Running in AC mode; bit 2 = Unit locked out; bit 3 = 230 V present; bit 4 = 24 V present
HR46doc 40047Master unit #1 outputsBITMAP16Readbit 0 = DCAMR output on; bit 1 = MAR output on; bit 2 = G output on; bit 3 = W output on; bit 4 = O output on; bit 5 = 2 output on; bit 6 = Y output on
HR47doc 40048Master unit #2 outputsBITMAP16Readbit 0 = DCAMR output on; bit 1 = MAR output on; bit 2 = G output on; bit 3 = W output on; bit 4 = O output on; bit 5 = 2 output on; bit 6 = Y output on
HR48doc 40049Output command master to slave unit #1BITMAP16Readbit 0 = DCAMR output on; bit 1 = MAR output on; bit 2 = G output on; bit 3 = W output on; bit 4 = O output on; bit 5 = 2 output on; bit 6 = Y output on
HR49doc 40050Output command master to slave unit #2BITMAP16Readbit 0 = DCAMR output on; bit 1 = MAR output on; bit 2 = G output on; bit 3 = W output on; bit 4 = O output on; bit 5 = 2 output on; bit 6 = Y output on
HR54doc 40055Master controller lockout statusBITMAP16Readbit 0 = Master unit 1 locked out; bit 1 = Master unit 2 locked out; bit 2 = Slave unit 1 locked out; bit 3 = Slave unit 2 locked out; bit 4 = Master in smoke alarm lockout; bit 5 = Master in low building temp lockout; bit 6 = Master in high building temp 1 lockout; bit 7 = Master in high building temp 2 lockout
HR55doc 40056Current stageCooling/heating stage now activeUINT16Read0 = Stage 12 cooling; 1 = Stage 11 cooling; 2 = Stage 10 cooling; 3 = Stage 9 cooling; 4 = Stage 8 cooling; 5 = Stage 7 cooling; 6 = Stage 6 cooling; 7 = Stage 5 cooling; 8 = Stage 4 cooling; 9 = Stage 3 cooling; 10 = Stage 2 cooling; 11 = Stage 1 cooling; 12 = Stage 0 (idle); 13 = Stage 1 heating; 14 = Stage 2 heating; 15 = Stage 3 heating; 16 = Stage 4 heating
HR56doc 40057Current temperature240 = sensor fault; below 240 = temperature (unit not stated in the adapter guide)UINT16Read240 = Sensor fault
HR57doc 40058Comfort mode time leftMinutes left in comfort mode divided by 3UINT16Read
HR58doc 40059Slave firmware revisionBelow 255UINT16Read
HR59doc 40060Slave controller inputsBITMAP16Readbit 0 = Aux 2 signal present; bit 1 = Aux 1 signal present; bit 2 = Generator in use; bit 3 = High hydrogen level; bit 4 = Smoke detected
HR60doc 40061Slave unit #1 inputsBITMAP16Readbit 0 = Running in economizer mode; bit 1 = Running in AC mode; bit 2 = Unit locked out; bit 3 = 230 V present; bit 4 = 24 V present
HR61doc 40062Slave unit #2 inputsBITMAP16Readbit 0 = Running in economizer mode; bit 1 = Running in AC mode; bit 2 = Unit locked out; bit 3 = 230 V present; bit 4 = 24 V present
HR62doc 40063Slave temp sensor #10 = sensor fault; 30-150 = temperatureUINT16°FRead0 = Sensor fault
HR63doc 40064Slave temp sensor #20 = sensor fault; 30-150 = temperatureUINT16°FRead0 = Sensor fault
HR64doc 40065Slave temp sensor #30 = sensor fault; 30-150 = temperatureUINT16°FRead0 = Sensor fault
HR65doc 40066Slave unit #1 output statusBITMAP16Readbit 0 = DCAMR output on; bit 1 = MAR output on; bit 2 = G output on; bit 3 = W output on; bit 4 = O output on; bit 5 = 2 output on; bit 6 = Y output on
HR66doc 40067Slave unit #2 output statusBITMAP16Readbit 0 = DCAMR output on; bit 1 = MAR output on; bit 2 = G output on; bit 3 = W output on; bit 4 = O output on; bit 5 = 2 output on; bit 6 = Y output on
HR67doc 40068Slave controller lockout statusBITMAP16Readbit 0 = Master unit 1 locked out; bit 1 = Master unit 2 locked out; bit 2 = Slave unit 1 locked out; bit 3 = Slave unit 2 locked out; bit 4 = Slave in smoke alarm lockout; bit 5 = Slave in low building temp lockout; bit 6 = Slave in high building temp 1 lockout; bit 7 = Slave in high building temp 2 lockout
HR100doc 40101Write controlHandshake for pushing new settings; see notesUINT16Read/write0 = Normal / write complete (adapter); 1 = Client: hold new-value registers for editing; 2 = Client: send new values to CommStat 4; 3 = Adapter: write accepted, waiting for cycle
HR101doc 40102New setting #2: F/CNew value, sent when 40101 = 2UINT16Read/write0 = Celsius; 1 = Fahrenheit
HR102doc 40103New setting #3: Changeover daysNew value, sent when 40101 = 2UINT16Read/write
HR103doc 40104New setting #4: Cool set pointNew value, sent when 40101 = 2UINT16Read/write
HR104doc 40105New setting #5: Heat set pointNew value, sent when 40101 = 2UINT16Read/write
HR105doc 40106New setting #6: High building temp 1 set pointNew value, sent when 40101 = 2UINT16Read/write
HR106doc 40107New setting #7: High building temp 2 set pointNew value, sent when 40101 = 2UINT16Read/write
HR107doc 40108New setting #8: Low building temp set pointNew value, sent when 40101 = 2UINT16Read/write
HR108doc 40109New setting #9: Blower onNew value, sent when 40101 = 2UINT16Read/write0 = Off; 1 = On
HR109doc 40110New setting #10: High voltage input enable / alarm output enableNew value, sent when 40101 = 2UINT16Read/write
HR110doc 40111New setting #11: Anti-short cycle timerNew value, sent when 40101 = 2UINT16minRead/write
HR111doc 40112New setting #12: Stage 1 differentialNew value, sent when 40101 = 2UINT16Read/write
HR112doc 40113New setting #13: Stage 2 differentialNew value, sent when 40101 = 2UINT16Read/write
HR113doc 40114New setting #14: Off differentialNew value, sent when 40101 = 2UINT16Read/write
HR114doc 40115New setting #15: Blower off time delayNew value, sent when 40101 = 2UINT16Read/write
HR115doc 40116New setting #16: Operational units when generator is usedNew value, sent when 40101 = 2UINT16Read/write
HR116doc 40117New setting #17: Smoke auto resetNew value, sent when 40101 = 2UINT16Read/write0 = Manual reset
HR117doc 40118New setting #18: Smoke relayNew value, sent when 40101 = 2UINT16Read/write0 = Normally open; 1 = Normally closed
HR118doc 40119New setting #19: ECON mode enableNew value, sent when 40101 = 2UINT16Read/write0 = No; 1 = Yes; 2 = Verizon special setting
HR119doc 40120New setting #20: Multiple sensorsNew value, sent when 40101 = 2UINT16Read/write0 = No; 1 = Yes
HR120doc 40121New setting #21: Aux 1 relayNew value, sent when 40101 = 2UINT16Read/write0 = Normally open; 1 = Normally closed; 2 = Off
HR121doc 40122New setting #22: Aux 2 relayNew value, sent when 40101 = 2UINT16Read/write0 = Normally open; 1 = Normally closed; 2 = Off
HR122doc 40123New setting #23: Excessive cycleNew value, sent when 40101 = 2UINT16Read/write0 = Off
HR123doc 40124New setting #24: LanguageNew value, sent when 40101 = 2UINT16Read/write0 = English; 1 = Spanish; 2 = French
HR124doc 40125New setting #25: AC / HP systemNew value, sent when 40101 = 2UINT16Read/write0 = Heat pump; 1 = One AC; 2 = Two AC
HR125doc 40126New setting #26: Master/slaveNew value, sent when 40101 = 2UINT16Read/write0 = Slave; 1 = Master
HR126doc 40127New setting #27: Stage 3 differentialNew value, sent when 40101 = 2UINT16Read/write
HR127doc 40128New setting #28: Stage 4 differentialNew value, sent when 40101 = 2UINT16Read/write
HR128doc 40129New setting #29: Stage 5 differentialNew value, sent when 40101 = 2UINT16Read/write
HR129doc 40130New setting #30: Stage 6 differentialNew value, sent when 40101 = 2UINT16Read/write
HR130doc 40131New setting #31: Stage 7 differentialNew value, sent when 40101 = 2UINT16Read/write
HR131doc 40132New setting #32: Stage 8 differentialNew value, sent when 40101 = 2UINT16Read/write
HR132doc 40133New setting #33: Stage 9 differentialNew value, sent when 40101 = 2UINT16Read/write
HR133doc 40134New setting #34: Stage 10 differentialNew value, sent when 40101 = 2UINT16Read/write
HR134doc 40135New setting #35: Stage 11 differentialNew value, sent when 40101 = 2UINT16Read/write
HR135doc 40136New setting #36: Stage 12 differentialNew value, sent when 40101 = 2UINT16Read/write
HR136doc 40137New setting #37: Total number of unitsNew value, sent when 40101 = 2UINT16Read/write
HR137doc 40138New setting #38: Stage 2 differential in econ cooling modeNew value, sent when 40101 = 2UINT16Read/write
HR138doc 40139New controller on/offSent when 40101 = 2UINT16Read/write0 = Off; 1 = On
HR139doc 40140New lead unitSent when 40101 = 2UINT16Read/write0 = Master #1; 1 = Master #2; 2 = Slave #1; 3 = Slave #2
HR140doc 40141New password #1UINT16Read/write
HR141doc 40142New password #2UINT16Read/write
HR142doc 40143Function codePurpose of this write (codes not listed in the guide)UINT16Read/write

Notes on this map

Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.

Questions about the Marvair CommStat 4 lead/lag controller via Modbus Interface Adapter

What Modbus registers does the Marvair CommStat 4 lead/lag controller via Modbus Interface Adapter have?

This map lists 107 registers: 107 holding registers. 43 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.

Are the Marvair CommStat 4 lead/lag controller via Modbus Interface Adapter Modbus addresses 0-based or 1-based?

The manufacturer's document numbers registers Modicon 3xxxx/4xxxx (drop the prefix, subtract 1). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. Registers are printed as 40001-40068 (read) and 40101-40143 (write), Modicon holding-register style. Request 40001 as wire address 0 and 40101 as wire address 100.

What are the minimum Modbus registers to integrate the Marvair CommStat 4 lead/lag controller via Modbus Interface Adapter?

Start with HR 56 Current temperature (Current temperature); HR 55 Current stage (Current heating/cooling stage); HR 54 Master controller lockout status (Master lockout flags); HR 43 Master controller inputs (Smoke / hydrogen / generator alarms); HR 46 Master unit #1 outputs (Master unit 1 outputs); HR 40 Lead unit (Lead unit); HR 100 Write control (Write handshake).

How do I enable Modbus control of the Marvair CommStat 4 lead/lag controller via Modbus Interface Adapter?

Install the Marvair Modbus Interface Adapter and plug its RJ11 cable into one of the master communication ports on the CommStat 4 board. Set the adapter IP through its web page.

Where is the official Marvair CommStat 4 lead/lag controller via Modbus Interface Adapter Modbus documentation?

The source is CommStat 4 Modbus Interface Adapter Installation and Operation Manual (P/03272 rev. 5), revision 2021-12, published free by Marvair at https://marvair.com/doc/121/CommStat%204%20Modbus%20Adapter%20Manual.

More Marvair Modbus register maps

Other hvac equipment register maps

All hvac equipment Modbus register maps →

Source: CommStat 4 Modbus Interface Adapter Installation and Operation Manual · P/03272 rev. 5 · rev. 2021-12. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.