Air handler (in-row computer room cooling unit) · Modbus register map

Vertiv Liebert CRV in-row cooling unit with iCOM v4 (IntelliSlot Modbus) Modbus register map

Updated 19 November 2026

Short answer

The Liebert CRV is a row-based precision cooling unit that sits between IT racks. Through a Liebert IntelliSlot Modbus card its iCOM v4 controller is a Modbus RTU / TCP slave. The map covers supply and return air temperatures, dew point and humidity, remote rack sensors, setpoints and alarm thresholds, fan speed and capacity, condenser data, system on/off and status, and the event bits.

This page lists 176 Modbus registers for the Vertiv Liebert CRV in-row cooling unit with iCOM v4 (IntelliSlot Modbus) — 41 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Vertiv’s own free documentation (linked below) and checked against it.

Manufacturer
Vertiv
Model
Liebert CRV in-row cooling unit with iCOM v4 (IntelliSlot Modbus)
Equipment type
Air handler (in-row computer room cooling unit)
Registers
176 (41 writable)
Transport
Modbus RTU, Modbus TCP
Default unit ID
Not stated
Default serial
8N1
Documented addressing
Modicon 3xxxx/4xxxx (drop the prefix, subtract 1)
Also known as
Liebert CRV, CRV, Liebert CRV iCOM
Source document
Liebert IntelliSlot Modbus 485, Modbus IP and BACnet IP Reference Guide · SL-28170 Rev 9 · rev. 10-12 (printed as SL-28170_REV9_10-12) · unofficial copy
Download CSV all columns JSON Manufacturer PDF ↗

Integration notes: Vertiv Liebert CRV in-row cooling unit with iCOM v4 (IntelliSlot Modbus)

Integration in brief

Read 30385-30395 for air temperatures, 30474-30477 for status and 30451-30455 for fan and capacity. Write 40478 to switch the unit on/off and 40397 for the air temperature setpoint in tenths of deg C.

Minimum registers to map

Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.

RegisterNameTypeWhyAccess
HR 477System On/Off ControlUINT16System on/off controlRead/write
IR 474System Operating StateUINT16System operating stateRead
IR 473System StatusUINT16System statusRead
IR 384Supply Air TemperatureINT16Supply air temperatureRead
IR 386Return Air TemperatureINT16Return air temperatureRead
IR 411Return HumidityUINT16Return humidityRead
HR 396Air Temperature Set PointINT16Air temperature setpointRead/write
IR 450Fan SpeedUINT16Fan speedRead
HR 499System Event Acknowledge/ResetUINT16Acknowledge / reset eventsRead/write

Enable Modbus control & writes

Fit the Liebert IntelliSlot card the guide lists for the unit's controller (for iCOM v4 units: IS-485L for Modbus 485, IS-IPBML for Modbus IP / BACnet IP) and set its Modbus address and line speed on the card.

Communication loss & watchdog

Holding register 40448 'BMS Timeout Period' (minutes) sets how long the unit waits for BMS communication before a timeout event; the resulting action is not described in this guide.

Byte order & addressing

Network setup

Watch out for

Vertiv Liebert CRV in-row cooling unit with iCOM v4 (IntelliSlot Modbus) Modbus registers

Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.

176 of 176 shown
Vertiv Liebert CRV in-row cooling unit with iCOM v4 (IntelliSlot Modbus) Modbus register map
TableAddressNameDescriptionTypeOrderScaleUnitsAccessValues / bits
DI0doc 10001Supply Air Over TemperatureBITRead0 = Inactive; 1 = Active
DI1doc 10002Supply Air Under TemperatureBITRead0 = Inactive; 1 = Active
DI2doc 10003Return Air Over TemperatureBITRead0 = Inactive; 1 = Active
DI3doc 10004Supply Air Sensor IssueBITRead0 = Inactive; 1 = Active
DI4doc 10005High Return HumidityBITRead0 = Inactive; 1 = Active
DI5doc 10006Low Return HumidityBITRead0 = Inactive; 1 = Active
DI6doc 10007Humidifier Hours ExceededBITRead0 = Inactive; 1 = Active
DI7doc 10008Dehumidifier Hours ExceededBITRead0 = Inactive; 1 = Active
DI8doc 10009Humidifier Under CurrentBITRead0 = Inactive; 1 = Active
DI9doc 10010Humidifier Over CurrentBITRead0 = Inactive; 1 = Active
DI10doc 10011Humidifier Low WaterBITRead0 = Inactive; 1 = Active
DI11doc 10012Humidifier Cylinder WornBITRead0 = Inactive; 1 = Active
DI12doc 10013Humidifier IssueBITRead0 = Inactive; 1 = Active
DI13doc 10014Ext Humidifier LockoutBITRead0 = Inactive; 1 = Active
DI14doc 10015Humidifier Control Board Not DetectedBITRead0 = Inactive; 1 = Active
DI15doc 10016Return Humidity Out Of Proportional BandBITRead0 = Inactive; 1 = Active
DI16doc 10017Loss of Air FlowBITRead0 = Inactive; 1 = Active
DI17doc 10018Fan Hours ExceededBITRead0 = Inactive; 1 = Active
DI18doc 10019Top Fan IssueBITRead0 = Inactive; 1 = Active
DI19doc 10020Bottom Fan IssueBITRead0 = Inactive; 1 = Active
DI20doc 10021Remote Sensor Issue 1BITRead0 = Inactive; 1 = Active
DI21doc 10022Remote Sensor Issue 2BITRead0 = Inactive; 1 = Active
DI22doc 10023Remote Sensor Issue 3BITRead0 = Inactive; 1 = Active
DI23doc 10024Remote Sensor Issue 4BITRead0 = Inactive; 1 = Active
DI24doc 10025Remote Sensor Issue 5BITRead0 = Inactive; 1 = Active
DI25doc 10026Remote Sensor Issue 6BITRead0 = Inactive; 1 = Active
DI26doc 10027Remote Sensor Issue 7BITRead0 = Inactive; 1 = Active
DI27doc 10028Remote Sensor Issue 8BITRead0 = Inactive; 1 = Active
DI28doc 10029Remote Sensor Issue 9BITRead0 = Inactive; 1 = Active
DI29doc 10030Remote Sensor Issue 10BITRead0 = Inactive; 1 = Active
DI30doc 10031Compressor 1 High Head PressureBITRead0 = Inactive; 1 = Active
DI31doc 10032Compressor 1 Low Suction PressureBITRead0 = Inactive; 1 = Active
DI32doc 10033Compressor 1 Hours ExceededBITRead0 = Inactive; 1 = Active
DI33doc 10034Dig Scroll Comp 1 Temp Sensor IssueBITRead0 = Inactive; 1 = Active
DI34doc 10035Dig Scroll Comp 1 Over TempBITRead0 = Inactive; 1 = Active
DI35doc 10036Compressor 1 Low Pressure Transducer IssueBITRead0 = Inactive; 1 = Active
DI36doc 10037Ext Compressor LockoutBITRead0 = Inactive; 1 = Active
DI37doc 10038Compressor 1 Short CycleBITRead0 = Inactive; 1 = Active
DI38doc 10039Compressor 1 High Pressure Transducer IssueBITRead0 = Inactive; 1 = Active
DI39doc 10040Compressor 1 Pump Down IssueBITRead0 = Inactive; 1 = Active
DI40doc 10041Reheater Over TemperatureBITRead0 = Inactive; 1 = Active
DI41doc 10042Electric Reheater Hours ExceededBITRead0 = Inactive; 1 = Active
DI42doc 10043Ext Reheat LockoutBITRead0 = Inactive; 1 = Active
DI43doc 10044Condenser 1 IssueBITRead0 = Inactive; 1 = Active
DI44doc 10045Condenser VFD IssueBITRead0 = Inactive; 1 = Active
DI45doc 10046Condenser TVSS IssueBITRead0 = Inactive; 1 = Active
DI46doc 10047Supply Chilled Water Over TempBITRead0 = Inactive; 1 = Active
DI47doc 10048Chilled Water Control Valve FailureBITRead0 = Inactive; 1 = Active
DI48doc 10049Supply Chilled Water Loss of FlowBITRead0 = Inactive; 1 = Active
DI49doc 10050Supply Fluid Temp Sensor IssueBITRead0 = Inactive; 1 = Active
DI50doc 10051Customer Input 1BITRead0 = Inactive; 1 = Active
DI51doc 10052Customer Input 2BITRead0 = Inactive; 1 = Active
DI52doc 10053Customer Input 3BITRead0 = Inactive; 1 = Active
DI53doc 10054Customer Input 4BITRead0 = Inactive; 1 = Active
DI54doc 10055Smoke DetectedBITRead0 = Inactive; 1 = Active
DI55doc 10056Water Under FloorBITRead0 = Inactive; 1 = Active
DI56doc 10057Service RequiredBITRead0 = Inactive; 1 = Active
DI57doc 10058Shutdown - Loss Of PowerBITRead0 = Inactive; 1 = Active
DI58doc 10059Ext Over TemperatureBITRead0 = Inactive; 1 = Active
DI59doc 10060Ext Loss of FlowBITRead0 = Inactive; 1 = Active
DI60doc 10061Ext Condenser Pump High WaterBITRead0 = Inactive; 1 = Active
DI61doc 10062Ext Standby Glycol Pump OnBITRead0 = Inactive; 1 = Active
DI62doc 10063External Fire DetectedBITRead0 = Inactive; 1 = Active
DI63doc 10064Unit OnBITRead0 = Inactive; 1 = Active
DI64doc 10065Unit OffBITRead0 = Inactive; 1 = Active
DI65doc 10066Unit StandbyBITRead0 = Inactive; 1 = Active
DI66doc 10067Unit Partial ShutdownBITRead0 = Inactive; 1 = Active
DI67doc 10068Unit ShutdownBITRead0 = Inactive; 1 = Active
DI68doc 10069Water Leakage Detector Sensor IssueBITRead0 = Inactive; 1 = Active
DI69doc 10070BMS Communications TimeoutBITRead0 = Inactive; 1 = Active
DI70doc 10071Maintenance DueBITRead0 = Inactive; 1 = Active
DI71doc 10072Maintenance CompletedBITRead0 = Inactive; 1 = Active
DI72doc 10073Clogged Air FilterBITRead0 = Inactive; 1 = Active
DI73doc 10074RAM Battery IssueBITRead0 = Inactive; 1 = Active
DI74doc 10075Master Unit Communication LostBITRead0 = Inactive; 1 = Active
DI75doc 10076High Power ShutdownBITRead0 = Inactive; 1 = Active
DI76doc 10077Return Air Sensor IssueBITRead0 = Inactive; 1 = Active
DI77doc 10078Condenser Outside Air Temp Sensor IssueBITRead0 = Inactive; 1 = Active
DI78doc 10079Condenser Outside Air Temp Out of Operating RangeBITRead0 = Inactive; 1 = Active
DI79doc 10080Condenser Control Board IssueBITRead0 = Inactive; 1 = Active
DI80doc 10081Condenser Refrigerant Pressure Over ThresholdBITRead0 = Inactive; 1 = Active
DI81doc 10082Condenser Refrigerant Pressure Under ThresholdBITRead0 = Inactive; 1 = Active
DI82doc 10083Condenser Refrigerant Pressure Sensor IssueBITRead0 = Inactive; 1 = Active
DI83doc 10084Condenser Supply Refrigerant Over TempBITRead0 = Inactive; 1 = Active
DI84doc 10085Condenser Supply Refrigerant Under TempBITRead0 = Inactive; 1 = Active
DI85doc 10086Condenser Supply Refrigerant Temp Sensor IssueBITRead0 = Inactive; 1 = Active
DI86doc 10087Condenser Max Fan Speed OverrideBITRead0 = Inactive; 1 = Active
DI87doc 10088Condenser Fan Issue 1BITRead0 = Inactive; 1 = Active
DI88doc 10089Condenser Fan Issue 2BITRead0 = Inactive; 1 = Active
DI89doc 10090Condenser Fan Issue 3BITRead0 = Inactive; 1 = Active
DI90doc 10091Condenser Fan Issue 4BITRead0 = Inactive; 1 = Active
IR384doc 30385Supply Air TemperatureINT16× 0.1deg CRead
IR386doc 30387Return Air TemperatureINT16× 0.1deg CRead
IR388doc 30389Return Dew PointINT16× 0.1deg CRead
IR390doc 30391Remote Sensor Minimum TemperatureINT16× 0.1deg CRead
IR392doc 30393Remote Sensor Maximum TemperatureINT16× 0.1deg CRead
IR394doc 30395Remote Sensor Average TemperatureINT16× 0.1deg CRead
IR410doc 30411Supply HumidityUINT16× 0.1% RHRead
IR411doc 30412Return HumidityUINT16× 0.1% RHRead
IR423doc 30424Remote Sensor Temperature 1INT16× 0.1deg CRead
IR424doc 30425Remote Sensor Temperature 2INT16× 0.1deg CRead
IR425doc 30426Remote Sensor Temperature 3INT16× 0.1deg CRead
IR426doc 30427Remote Sensor Temperature 4INT16× 0.1deg CRead
IR427doc 30428Remote Sensor Temperature 5INT16× 0.1deg CRead
IR428doc 30429Remote Sensor Temperature 6INT16× 0.1deg CRead
IR429doc 30430Remote Sensor Temperature 7INT16× 0.1deg CRead
IR430doc 30431Remote Sensor Temperature 8INT16× 0.1deg CRead
IR431doc 30432Remote Sensor Temperature 9INT16× 0.1deg CRead
IR432doc 30433Remote Sensor Temperature 10INT16× 0.1deg CRead
IR443doc 30444Supply Chilled Water TemperatureINT16× 0.1deg CRead
IR449doc 30450Operating EfficiencyUINT16%Read
IR450doc 30451Fan SpeedUINT16%Read
IR451doc 30452Cooling Capacity (Primary)UINT16%Read
IR452doc 30453Dehumidifier UtilizationUINT16%Read
IR453doc 30454Reheat UtilizationUINT16%Read
IR454doc 30455Humidifier UtilizationUINT16%Read
IR455doc 30456Calculated Next Maintenance MonthUINT16Read
IR456doc 30457Calculated Next Maintenance YearUINT16Read
IR457doc 30458Maintenance RampUINT16%Read
IR458doc 30459Server ClassUINT16Read1 = UPS; 2 = AIR; 3 = PMP; 4 = PDU
IR473doc 30474System StatusUINT16Read1 = Normal Operation; 2 = StartUp; 8 = Normal with Warning; 16 = Normal with Alarm; 32 = Abnormal Operation
IR474doc 30475System Operating StateUINT16Read0 = off; 1 = on; 2 = standby
IR475doc 30476System Control ModeUINT16Read0 = Internal (Auto); 1 = External (Manual)
IR476doc 30477System Operating State ReasonUINT16Read0 = Reason Unknown; 1 = Network Display; 2 = Alarm; 3 = Schedule; 4 = Remote System; 5 = External Input; 6 = Local Display
IR478doc 30479Condenser Refrigerant TypeUINT16Read0 = R22; 1 = R407C; 2 = R410A
IR479doc 30480Condenser Outside Air TemperatureINT16× 0.1deg CRead
IR481doc 30482Condenser Fan Speed 1UINT16%Read
IR482doc 30483Condenser Fan Speed 2UINT16%Read
IR483doc 30484Condenser Fan Speed 3UINT16%Read
IR484doc 30485Condenser Fan Speed 4UINT16%Read
IR485doc 30486Condenser Fan Power 1UINT16× 0.1kWRead
IR486doc 30487Condenser Fan Power 2UINT16× 0.1kWRead
IR487doc 30488Condenser Fan Power 3UINT16× 0.1kWRead
IR488doc 30489Condenser Fan Power 4UINT16× 0.1kWRead
IR489doc 30490Condenser Low Noise Mode StateUINT16Read0 = Inactive; 1 = Active (Interval); 2 = Active (Full Day)
HR396doc 40397Air Temperature Set PointINT16× 0.1deg CRead/write
HR398doc 40399Cooling Proportional BandINT16× 0.1deg CRead/write
HR400doc 40401Heating Proportional BandINT16× 0.1deg CRead/write
HR402doc 40403Air Temperature Dead BandINT16× 0.1deg CRead/write
HR404doc 40405Supply Air Over Temp ThresholdINT16× 0.1deg CRead/write
HR406doc 40407Supply Air Under Temp ThresholdINT16× 0.1deg CRead/write
HR408doc 40409Return Air Over Temp ThresholdINT16× 0.1deg CRead/write
HR412doc 40413Humidity Set PointUINT16% RHRead/write
HR413doc 40414Humidification Proportional BandUINT16% RHRead/write
HR414doc 40415Dehumidification Proportional BandUINT16% RHRead/write
HR415doc 40416Humidity Dead BandUINT16× 0.1% RHRead/write
HR416doc 40417High Return Humidity ThresholdUINT16× 0.1% RHRead/write
HR417doc 40418Low Return Humidity ThresholdUINT16× 0.1% RHRead/write
HR418doc 40419Fan Speed Proportional BandINT16× 0.1deg CRead/write
HR420doc 40421Fan Speed Manual Set PointUINT16%Read/write
HR421doc 40422Fan Speed Maximum Set PointUINT16%Read/write
HR422doc 40423Fan Speed Minimum Set PointUINT16%Read/write
HR445doc 40446Supply Chilled Water Over Temp ThresholdINT16× 0.1deg CRead/write
HR447doc 40448BMS Timeout PeriodUINT16minRead/write
HR448doc 40449Auto Restart DelayUINT16secRead/write
HR459doc 40460Air Temperature Control SensorUINT16Read/write0 = Supply; 1 = Remote; 2 = Return
HR460doc 40461Remote Sensor Temperature CalculationUINT16Read/write0 = Average; 1 = Maximum
HR461doc 40462Fan Control ModeUINT16Read/write0 = Internal (Auto); 1 = External (Manual)
HR462doc 40463Fan Control SensorUINT16Read/write0 = Supply; 1 = Remote; 2 = Return
HR463doc 40464Remote Sensor Function 1UINT16Read/write0 = Disable; 1 = Reference; 2 = Control
HR464doc 40465Remote Sensor Function 2UINT16Read/write0 = Disable; 1 = Reference; 2 = Control
HR465doc 40466Remote Sensor Function 3UINT16Read/write0 = Disable; 1 = Reference; 2 = Control
HR466doc 40467Remote Sensor Function 4UINT16Read/write0 = Disable; 1 = Reference; 2 = Control
HR467doc 40468Remote Sensor Function 5UINT16Read/write0 = Disable; 1 = Reference; 2 = Control
HR468doc 40469Remote Sensor Function 6UINT16Read/write0 = Disable; 1 = Reference; 2 = Control
HR469doc 40470Remote Sensor Function 7UINT16Read/write0 = Disable; 1 = Reference; 2 = Control
HR470doc 40471Remote Sensor Function 8UINT16Read/write0 = Disable; 1 = Reference; 2 = Control
HR471doc 40472Remote Sensor Function 9UINT16Read/write0 = Disable; 1 = Reference; 2 = Control
HR472doc 40473Remote Sensor Function 10UINT16Read/write0 = Disable; 1 = Reference; 2 = Control
HR477doc 40478System On/Off ControlUINT16Read/write0 = off; 1 = on
HR490doc 40491Condenser Low Noise Mode Schedule ControlUINT16Read/write0 = disabled; 1 = enabled
HR491doc 40492Condenser Low Noise Mode Max Fan SpeedUINT16%Read/write
HR492doc 40493Condenser Normal Mode Max Fan SpeedUINT16%Read/write
HR493doc 40494Condenser Low Noise Mode - Interval DaysBITMAP16Read/writebit 0 = Monday; bit 1 = Tuesday; bit 2 = Wednesday; bit 3 = Thursday; bit 4 = Friday; bit 5 = Saturday; bit 6 = Sunday
HR494doc 40495Condenser Low Noise Mode - Full DaysBITMAP16Read/writebit 0 = Monday; bit 1 = Tuesday; bit 2 = Wednesday; bit 3 = Thursday; bit 4 = Friday; bit 5 = Saturday; bit 6 = Sunday
HR499doc 40500System Event Acknowledge/ResetUINT16Read/write2 = Reset; 4 = Acknowledge

Notes on this map

Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.

Questions about the Vertiv Liebert CRV in-row cooling unit with iCOM v4 (IntelliSlot Modbus)

What Modbus registers does the Vertiv Liebert CRV in-row cooling unit with iCOM v4 (IntelliSlot Modbus) have?

This map lists 176 registers: 91 discrete inputs, 44 input registers, 41 holding registers. 41 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.

Are the Vertiv Liebert CRV in-row cooling unit with iCOM v4 (IntelliSlot Modbus) Modbus addresses 0-based or 1-based?

The manufacturer's document numbers registers Modicon 3xxxx/4xxxx (drop the prefix, subtract 1). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. The guide prints Modicon-style numbers: discrete inputs 1xxxx, input registers 3xxxx, holding registers 4xxxx. Its RTU example asks for holding register 40051 with start offset 50 (0x0032), so subtract 10001 / 30001 / 40001 to get the wire address. Coils are printed as plain numbers on the same scale as the discrete inputs (coil 25 sits beside status 10025), so coil n is wire address n-1.

What are the minimum Modbus registers to integrate the Vertiv Liebert CRV in-row cooling unit with iCOM v4 (IntelliSlot Modbus)?

Start with HR 477 System On/Off Control (System on/off control); IR 474 System Operating State (System operating state); IR 473 System Status (System status); IR 384 Supply Air Temperature (Supply air temperature); IR 386 Return Air Temperature (Return air temperature); IR 411 Return Humidity (Return humidity); HR 396 Air Temperature Set Point (Air temperature setpoint); IR 450 Fan Speed (Fan speed); HR 499 System Event Acknowledge/Reset (Acknowledge / reset events).

How do I enable Modbus control of the Vertiv Liebert CRV in-row cooling unit with iCOM v4 (IntelliSlot Modbus)?

Fit the Liebert IntelliSlot card the guide lists for the unit's controller (for iCOM v4 units: IS-485L for Modbus 485, IS-IPBML for Modbus IP / BACnet IP) and set its Modbus address and line speed on the card.

What happens when the Vertiv Liebert CRV in-row cooling unit with iCOM v4 (IntelliSlot Modbus) loses Modbus communication?

Holding register 40448 'BMS Timeout Period' (minutes) sets how long the unit waits for BMS communication before a timeout event; the resulting action is not described in this guide.

Where is the official Vertiv Liebert CRV in-row cooling unit with iCOM v4 (IntelliSlot Modbus) Modbus documentation?

The source is Liebert IntelliSlot Modbus 485, Modbus IP and BACnet IP Reference Guide (SL-28170 Rev 9), revision 10-12 (printed as SL-28170_REV9_10-12). Vertiv doesn't publish it on its own website, so this map was re-typed from a free copy at https://ccontrols.com/support/dp/Liebert.pdf. It may be an older revision, so check it against the live unit.

More Vertiv Modbus register maps

Other hvac equipment register maps

All hvac equipment Modbus register maps →

Source: Liebert IntelliSlot Modbus 485, Modbus IP and BACnet IP Reference Guide · SL-28170 Rev 9 · rev. 10-12 (printed as SL-28170_REV9_10-12) · unofficial copy. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.