- Liebert CRV in-row cooling unit with iCOM v4 (IntelliSlot Modbus)
Air handler (in-row computer room cooling unit) · Modbus register map
Vertiv Liebert CRV in-row cooling unit with iCOM v4 (IntelliSlot Modbus) Modbus register map
Updated 19 November 2026
The Liebert CRV is a row-based precision cooling unit that sits between IT racks. Through a Liebert IntelliSlot Modbus card its iCOM v4 controller is a Modbus RTU / TCP slave. The map covers supply and return air temperatures, dew point and humidity, remote rack sensors, setpoints and alarm thresholds, fan speed and capacity, condenser data, system on/off and status, and the event bits.
This page lists 176 Modbus registers for the Vertiv Liebert CRV in-row cooling unit with iCOM v4 (IntelliSlot Modbus) — 41 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Vertiv’s own free documentation (linked below) and checked against it.
- Manufacturer
- Vertiv
- Model
- Liebert CRV in-row cooling unit with iCOM v4 (IntelliSlot Modbus)
- Equipment type
- Air handler (in-row computer room cooling unit)
- Registers
- 176 (41 writable)
- Transport
- Modbus RTU, Modbus TCP
- Default unit ID
- Not stated
- Default serial
- 8N1
- Documented addressing
- Modicon 3xxxx/4xxxx (drop the prefix, subtract 1)
- Also known as
- Liebert CRV, CRV, Liebert CRV iCOM
Integration notes: Vertiv Liebert CRV in-row cooling unit with iCOM v4 (IntelliSlot Modbus)
Read 30385-30395 for air temperatures, 30474-30477 for status and 30451-30455 for fan and capacity. Write 40478 to switch the unit on/off and 40397 for the air temperature setpoint in tenths of deg C.
Minimum registers to map
Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.
| Register | Name | Type | Why | Access |
|---|---|---|---|---|
| HR 477 | System On/Off Control | UINT16 | System on/off control | Read/write |
| IR 474 | System Operating State | UINT16 | System operating state | Read |
| IR 473 | System Status | UINT16 | System status | Read |
| IR 384 | Supply Air Temperature | INT16 | Supply air temperature | Read |
| IR 386 | Return Air Temperature | INT16 | Return air temperature | Read |
| IR 411 | Return Humidity | UINT16 | Return humidity | Read |
| HR 396 | Air Temperature Set Point | INT16 | Air temperature setpoint | Read/write |
| IR 450 | Fan Speed | UINT16 | Fan speed | Read |
| HR 499 | System Event Acknowledge/Reset | UINT16 | Acknowledge / reset events | Read/write |
Enable Modbus control & writes
Fit the Liebert IntelliSlot card the guide lists for the unit's controller (for iCOM v4 units: IS-485L for Modbus 485, IS-IPBML for Modbus IP / BACnet IP) and set its Modbus address and line speed on the card.
Communication loss & watchdog
Holding register 40448 'BMS Timeout Period' (minutes) sets how long the unit waits for BMS communication before a timeout event; the resulting action is not described in this guide.
Byte order & addressing
- Modicon numbering: subtract 40001 / 30001 / 10001 for the wire address.
- On/off is a holding register here (40478), not a coil.
- Low-noise-mode day selections (40494, 40495) are bit masks: bit 0 Monday ... bit 6 Sunday.
Network setup
- RS-485 (2-wire) RTU settings for the IntelliSlot 485 card: 9600, 19200 or 38400 baud, 8 data bits, no parity, 1 stop bit.
- Each unit needs a unique Modbus slave address on the RS-485 line.
- For Modbus IP, use the IntelliSlot Modbus IP / BACnet IP card listed for the unit's controller in the guide's compatibility table.
Watch out for
- Humidity setpoint and humidification/dehumidification bands (40413-40415) are whole %RH, while the humidity dead band and thresholds (40416-40418) are tenths.
Vertiv Liebert CRV in-row cooling unit with iCOM v4 (IntelliSlot Modbus) Modbus registers
Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.
| Table | Address | Name | Description | Type | Order | Scale | Units | Access | Values / bits |
|---|---|---|---|---|---|---|---|---|---|
| DI | 0doc 10001 | Supply Air Over Temperature | BIT | Read | 0 = Inactive; 1 = Active | ||||
| DI | 1doc 10002 | Supply Air Under Temperature | BIT | Read | 0 = Inactive; 1 = Active | ||||
| DI | 2doc 10003 | Return Air Over Temperature | BIT | Read | 0 = Inactive; 1 = Active | ||||
| DI | 3doc 10004 | Supply Air Sensor Issue | BIT | Read | 0 = Inactive; 1 = Active | ||||
| DI | 4doc 10005 | High Return Humidity | BIT | Read | 0 = Inactive; 1 = Active | ||||
| DI | 5doc 10006 | Low Return Humidity | BIT | Read | 0 = Inactive; 1 = Active | ||||
| DI | 6doc 10007 | Humidifier Hours Exceeded | BIT | Read | 0 = Inactive; 1 = Active | ||||
| DI | 7doc 10008 | Dehumidifier Hours Exceeded | BIT | Read | 0 = Inactive; 1 = Active | ||||
| DI | 8doc 10009 | Humidifier Under Current | BIT | Read | 0 = Inactive; 1 = Active | ||||
| DI | 9doc 10010 | Humidifier Over Current | BIT | Read | 0 = Inactive; 1 = Active | ||||
| DI | 10doc 10011 | Humidifier Low Water | BIT | Read | 0 = Inactive; 1 = Active | ||||
| DI | 11doc 10012 | Humidifier Cylinder Worn | BIT | Read | 0 = Inactive; 1 = Active | ||||
| DI | 12doc 10013 | Humidifier Issue | BIT | Read | 0 = Inactive; 1 = Active | ||||
| DI | 13doc 10014 | Ext Humidifier Lockout | BIT | Read | 0 = Inactive; 1 = Active | ||||
| DI | 14doc 10015 | Humidifier Control Board Not Detected | BIT | Read | 0 = Inactive; 1 = Active | ||||
| DI | 15doc 10016 | Return Humidity Out Of Proportional Band | BIT | Read | 0 = Inactive; 1 = Active | ||||
| DI | 16doc 10017 | Loss of Air Flow | BIT | Read | 0 = Inactive; 1 = Active | ||||
| DI | 17doc 10018 | Fan Hours Exceeded | BIT | Read | 0 = Inactive; 1 = Active | ||||
| DI | 18doc 10019 | Top Fan Issue | BIT | Read | 0 = Inactive; 1 = Active | ||||
| DI | 19doc 10020 | Bottom Fan Issue | BIT | Read | 0 = Inactive; 1 = Active | ||||
| DI | 20doc 10021 | Remote Sensor Issue 1 | BIT | Read | 0 = Inactive; 1 = Active | ||||
| DI | 21doc 10022 | Remote Sensor Issue 2 | BIT | Read | 0 = Inactive; 1 = Active | ||||
| DI | 22doc 10023 | Remote Sensor Issue 3 | BIT | Read | 0 = Inactive; 1 = Active | ||||
| DI | 23doc 10024 | Remote Sensor Issue 4 | BIT | Read | 0 = Inactive; 1 = Active | ||||
| DI | 24doc 10025 | Remote Sensor Issue 5 | BIT | Read | 0 = Inactive; 1 = Active | ||||
| DI | 25doc 10026 | Remote Sensor Issue 6 | BIT | Read | 0 = Inactive; 1 = Active | ||||
| DI | 26doc 10027 | Remote Sensor Issue 7 | BIT | Read | 0 = Inactive; 1 = Active | ||||
| DI | 27doc 10028 | Remote Sensor Issue 8 | BIT | Read | 0 = Inactive; 1 = Active | ||||
| DI | 28doc 10029 | Remote Sensor Issue 9 | BIT | Read | 0 = Inactive; 1 = Active | ||||
| DI | 29doc 10030 | Remote Sensor Issue 10 | BIT | Read | 0 = Inactive; 1 = Active | ||||
| DI | 30doc 10031 | Compressor 1 High Head Pressure | BIT | Read | 0 = Inactive; 1 = Active | ||||
| DI | 31doc 10032 | Compressor 1 Low Suction Pressure | BIT | Read | 0 = Inactive; 1 = Active | ||||
| DI | 32doc 10033 | Compressor 1 Hours Exceeded | BIT | Read | 0 = Inactive; 1 = Active | ||||
| DI | 33doc 10034 | Dig Scroll Comp 1 Temp Sensor Issue | BIT | Read | 0 = Inactive; 1 = Active | ||||
| DI | 34doc 10035 | Dig Scroll Comp 1 Over Temp | BIT | Read | 0 = Inactive; 1 = Active | ||||
| DI | 35doc 10036 | Compressor 1 Low Pressure Transducer Issue | BIT | Read | 0 = Inactive; 1 = Active | ||||
| DI | 36doc 10037 | Ext Compressor Lockout | BIT | Read | 0 = Inactive; 1 = Active | ||||
| DI | 37doc 10038 | Compressor 1 Short Cycle | BIT | Read | 0 = Inactive; 1 = Active | ||||
| DI | 38doc 10039 | Compressor 1 High Pressure Transducer Issue | BIT | Read | 0 = Inactive; 1 = Active | ||||
| DI | 39doc 10040 | Compressor 1 Pump Down Issue | BIT | Read | 0 = Inactive; 1 = Active | ||||
| DI | 40doc 10041 | Reheater Over Temperature | BIT | Read | 0 = Inactive; 1 = Active | ||||
| DI | 41doc 10042 | Electric Reheater Hours Exceeded | BIT | Read | 0 = Inactive; 1 = Active | ||||
| DI | 42doc 10043 | Ext Reheat Lockout | BIT | Read | 0 = Inactive; 1 = Active | ||||
| DI | 43doc 10044 | Condenser 1 Issue | BIT | Read | 0 = Inactive; 1 = Active | ||||
| DI | 44doc 10045 | Condenser VFD Issue | BIT | Read | 0 = Inactive; 1 = Active | ||||
| DI | 45doc 10046 | Condenser TVSS Issue | BIT | Read | 0 = Inactive; 1 = Active | ||||
| DI | 46doc 10047 | Supply Chilled Water Over Temp | BIT | Read | 0 = Inactive; 1 = Active | ||||
| DI | 47doc 10048 | Chilled Water Control Valve Failure | BIT | Read | 0 = Inactive; 1 = Active | ||||
| DI | 48doc 10049 | Supply Chilled Water Loss of Flow | BIT | Read | 0 = Inactive; 1 = Active | ||||
| DI | 49doc 10050 | Supply Fluid Temp Sensor Issue | BIT | Read | 0 = Inactive; 1 = Active | ||||
| DI | 50doc 10051 | Customer Input 1 | BIT | Read | 0 = Inactive; 1 = Active | ||||
| DI | 51doc 10052 | Customer Input 2 | BIT | Read | 0 = Inactive; 1 = Active | ||||
| DI | 52doc 10053 | Customer Input 3 | BIT | Read | 0 = Inactive; 1 = Active | ||||
| DI | 53doc 10054 | Customer Input 4 | BIT | Read | 0 = Inactive; 1 = Active | ||||
| DI | 54doc 10055 | Smoke Detected | BIT | Read | 0 = Inactive; 1 = Active | ||||
| DI | 55doc 10056 | Water Under Floor | BIT | Read | 0 = Inactive; 1 = Active | ||||
| DI | 56doc 10057 | Service Required | BIT | Read | 0 = Inactive; 1 = Active | ||||
| DI | 57doc 10058 | Shutdown - Loss Of Power | BIT | Read | 0 = Inactive; 1 = Active | ||||
| DI | 58doc 10059 | Ext Over Temperature | BIT | Read | 0 = Inactive; 1 = Active | ||||
| DI | 59doc 10060 | Ext Loss of Flow | BIT | Read | 0 = Inactive; 1 = Active | ||||
| DI | 60doc 10061 | Ext Condenser Pump High Water | BIT | Read | 0 = Inactive; 1 = Active | ||||
| DI | 61doc 10062 | Ext Standby Glycol Pump On | BIT | Read | 0 = Inactive; 1 = Active | ||||
| DI | 62doc 10063 | External Fire Detected | BIT | Read | 0 = Inactive; 1 = Active | ||||
| DI | 63doc 10064 | Unit On | BIT | Read | 0 = Inactive; 1 = Active | ||||
| DI | 64doc 10065 | Unit Off | BIT | Read | 0 = Inactive; 1 = Active | ||||
| DI | 65doc 10066 | Unit Standby | BIT | Read | 0 = Inactive; 1 = Active | ||||
| DI | 66doc 10067 | Unit Partial Shutdown | BIT | Read | 0 = Inactive; 1 = Active | ||||
| DI | 67doc 10068 | Unit Shutdown | BIT | Read | 0 = Inactive; 1 = Active | ||||
| DI | 68doc 10069 | Water Leakage Detector Sensor Issue | BIT | Read | 0 = Inactive; 1 = Active | ||||
| DI | 69doc 10070 | BMS Communications Timeout | BIT | Read | 0 = Inactive; 1 = Active | ||||
| DI | 70doc 10071 | Maintenance Due | BIT | Read | 0 = Inactive; 1 = Active | ||||
| DI | 71doc 10072 | Maintenance Completed | BIT | Read | 0 = Inactive; 1 = Active | ||||
| DI | 72doc 10073 | Clogged Air Filter | BIT | Read | 0 = Inactive; 1 = Active | ||||
| DI | 73doc 10074 | RAM Battery Issue | BIT | Read | 0 = Inactive; 1 = Active | ||||
| DI | 74doc 10075 | Master Unit Communication Lost | BIT | Read | 0 = Inactive; 1 = Active | ||||
| DI | 75doc 10076 | High Power Shutdown | BIT | Read | 0 = Inactive; 1 = Active | ||||
| DI | 76doc 10077 | Return Air Sensor Issue | BIT | Read | 0 = Inactive; 1 = Active | ||||
| DI | 77doc 10078 | Condenser Outside Air Temp Sensor Issue | BIT | Read | 0 = Inactive; 1 = Active | ||||
| DI | 78doc 10079 | Condenser Outside Air Temp Out of Operating Range | BIT | Read | 0 = Inactive; 1 = Active | ||||
| DI | 79doc 10080 | Condenser Control Board Issue | BIT | Read | 0 = Inactive; 1 = Active | ||||
| DI | 80doc 10081 | Condenser Refrigerant Pressure Over Threshold | BIT | Read | 0 = Inactive; 1 = Active | ||||
| DI | 81doc 10082 | Condenser Refrigerant Pressure Under Threshold | BIT | Read | 0 = Inactive; 1 = Active | ||||
| DI | 82doc 10083 | Condenser Refrigerant Pressure Sensor Issue | BIT | Read | 0 = Inactive; 1 = Active | ||||
| DI | 83doc 10084 | Condenser Supply Refrigerant Over Temp | BIT | Read | 0 = Inactive; 1 = Active | ||||
| DI | 84doc 10085 | Condenser Supply Refrigerant Under Temp | BIT | Read | 0 = Inactive; 1 = Active | ||||
| DI | 85doc 10086 | Condenser Supply Refrigerant Temp Sensor Issue | BIT | Read | 0 = Inactive; 1 = Active | ||||
| DI | 86doc 10087 | Condenser Max Fan Speed Override | BIT | Read | 0 = Inactive; 1 = Active | ||||
| DI | 87doc 10088 | Condenser Fan Issue 1 | BIT | Read | 0 = Inactive; 1 = Active | ||||
| DI | 88doc 10089 | Condenser Fan Issue 2 | BIT | Read | 0 = Inactive; 1 = Active | ||||
| DI | 89doc 10090 | Condenser Fan Issue 3 | BIT | Read | 0 = Inactive; 1 = Active | ||||
| DI | 90doc 10091 | Condenser Fan Issue 4 | BIT | Read | 0 = Inactive; 1 = Active | ||||
| IR | 384doc 30385 | Supply Air Temperature | INT16 | × 0.1 | deg C | Read | |||
| IR | 386doc 30387 | Return Air Temperature | INT16 | × 0.1 | deg C | Read | |||
| IR | 388doc 30389 | Return Dew Point | INT16 | × 0.1 | deg C | Read | |||
| IR | 390doc 30391 | Remote Sensor Minimum Temperature | INT16 | × 0.1 | deg C | Read | |||
| IR | 392doc 30393 | Remote Sensor Maximum Temperature | INT16 | × 0.1 | deg C | Read | |||
| IR | 394doc 30395 | Remote Sensor Average Temperature | INT16 | × 0.1 | deg C | Read | |||
| IR | 410doc 30411 | Supply Humidity | UINT16 | × 0.1 | % RH | Read | |||
| IR | 411doc 30412 | Return Humidity | UINT16 | × 0.1 | % RH | Read | |||
| IR | 423doc 30424 | Remote Sensor Temperature 1 | INT16 | × 0.1 | deg C | Read | |||
| IR | 424doc 30425 | Remote Sensor Temperature 2 | INT16 | × 0.1 | deg C | Read | |||
| IR | 425doc 30426 | Remote Sensor Temperature 3 | INT16 | × 0.1 | deg C | Read | |||
| IR | 426doc 30427 | Remote Sensor Temperature 4 | INT16 | × 0.1 | deg C | Read | |||
| IR | 427doc 30428 | Remote Sensor Temperature 5 | INT16 | × 0.1 | deg C | Read | |||
| IR | 428doc 30429 | Remote Sensor Temperature 6 | INT16 | × 0.1 | deg C | Read | |||
| IR | 429doc 30430 | Remote Sensor Temperature 7 | INT16 | × 0.1 | deg C | Read | |||
| IR | 430doc 30431 | Remote Sensor Temperature 8 | INT16 | × 0.1 | deg C | Read | |||
| IR | 431doc 30432 | Remote Sensor Temperature 9 | INT16 | × 0.1 | deg C | Read | |||
| IR | 432doc 30433 | Remote Sensor Temperature 10 | INT16 | × 0.1 | deg C | Read | |||
| IR | 443doc 30444 | Supply Chilled Water Temperature | INT16 | × 0.1 | deg C | Read | |||
| IR | 449doc 30450 | Operating Efficiency | UINT16 | % | Read | ||||
| IR | 450doc 30451 | Fan Speed | UINT16 | % | Read | ||||
| IR | 451doc 30452 | Cooling Capacity (Primary) | UINT16 | % | Read | ||||
| IR | 452doc 30453 | Dehumidifier Utilization | UINT16 | % | Read | ||||
| IR | 453doc 30454 | Reheat Utilization | UINT16 | % | Read | ||||
| IR | 454doc 30455 | Humidifier Utilization | UINT16 | % | Read | ||||
| IR | 455doc 30456 | Calculated Next Maintenance Month | UINT16 | Read | |||||
| IR | 456doc 30457 | Calculated Next Maintenance Year | UINT16 | Read | |||||
| IR | 457doc 30458 | Maintenance Ramp | UINT16 | % | Read | ||||
| IR | 458doc 30459 | Server Class | UINT16 | Read | 1 = UPS; 2 = AIR; 3 = PMP; 4 = PDU | ||||
| IR | 473doc 30474 | System Status | UINT16 | Read | 1 = Normal Operation; 2 = StartUp; 8 = Normal with Warning; 16 = Normal with Alarm; 32 = Abnormal Operation | ||||
| IR | 474doc 30475 | System Operating State | UINT16 | Read | 0 = off; 1 = on; 2 = standby | ||||
| IR | 475doc 30476 | System Control Mode | UINT16 | Read | 0 = Internal (Auto); 1 = External (Manual) | ||||
| IR | 476doc 30477 | System Operating State Reason | UINT16 | Read | 0 = Reason Unknown; 1 = Network Display; 2 = Alarm; 3 = Schedule; 4 = Remote System; 5 = External Input; 6 = Local Display | ||||
| IR | 478doc 30479 | Condenser Refrigerant Type | UINT16 | Read | 0 = R22; 1 = R407C; 2 = R410A | ||||
| IR | 479doc 30480 | Condenser Outside Air Temperature | INT16 | × 0.1 | deg C | Read | |||
| IR | 481doc 30482 | Condenser Fan Speed 1 | UINT16 | % | Read | ||||
| IR | 482doc 30483 | Condenser Fan Speed 2 | UINT16 | % | Read | ||||
| IR | 483doc 30484 | Condenser Fan Speed 3 | UINT16 | % | Read | ||||
| IR | 484doc 30485 | Condenser Fan Speed 4 | UINT16 | % | Read | ||||
| IR | 485doc 30486 | Condenser Fan Power 1 | UINT16 | × 0.1 | kW | Read | |||
| IR | 486doc 30487 | Condenser Fan Power 2 | UINT16 | × 0.1 | kW | Read | |||
| IR | 487doc 30488 | Condenser Fan Power 3 | UINT16 | × 0.1 | kW | Read | |||
| IR | 488doc 30489 | Condenser Fan Power 4 | UINT16 | × 0.1 | kW | Read | |||
| IR | 489doc 30490 | Condenser Low Noise Mode State | UINT16 | Read | 0 = Inactive; 1 = Active (Interval); 2 = Active (Full Day) | ||||
| HR | 396doc 40397 | Air Temperature Set Point | INT16 | × 0.1 | deg C | Read/write | |||
| HR | 398doc 40399 | Cooling Proportional Band | INT16 | × 0.1 | deg C | Read/write | |||
| HR | 400doc 40401 | Heating Proportional Band | INT16 | × 0.1 | deg C | Read/write | |||
| HR | 402doc 40403 | Air Temperature Dead Band | INT16 | × 0.1 | deg C | Read/write | |||
| HR | 404doc 40405 | Supply Air Over Temp Threshold | INT16 | × 0.1 | deg C | Read/write | |||
| HR | 406doc 40407 | Supply Air Under Temp Threshold | INT16 | × 0.1 | deg C | Read/write | |||
| HR | 408doc 40409 | Return Air Over Temp Threshold | INT16 | × 0.1 | deg C | Read/write | |||
| HR | 412doc 40413 | Humidity Set Point | UINT16 | % RH | Read/write | ||||
| HR | 413doc 40414 | Humidification Proportional Band | UINT16 | % RH | Read/write | ||||
| HR | 414doc 40415 | Dehumidification Proportional Band | UINT16 | % RH | Read/write | ||||
| HR | 415doc 40416 | Humidity Dead Band | UINT16 | × 0.1 | % RH | Read/write | |||
| HR | 416doc 40417 | High Return Humidity Threshold | UINT16 | × 0.1 | % RH | Read/write | |||
| HR | 417doc 40418 | Low Return Humidity Threshold | UINT16 | × 0.1 | % RH | Read/write | |||
| HR | 418doc 40419 | Fan Speed Proportional Band | INT16 | × 0.1 | deg C | Read/write | |||
| HR | 420doc 40421 | Fan Speed Manual Set Point | UINT16 | % | Read/write | ||||
| HR | 421doc 40422 | Fan Speed Maximum Set Point | UINT16 | % | Read/write | ||||
| HR | 422doc 40423 | Fan Speed Minimum Set Point | UINT16 | % | Read/write | ||||
| HR | 445doc 40446 | Supply Chilled Water Over Temp Threshold | INT16 | × 0.1 | deg C | Read/write | |||
| HR | 447doc 40448 | BMS Timeout Period | UINT16 | min | Read/write | ||||
| HR | 448doc 40449 | Auto Restart Delay | UINT16 | sec | Read/write | ||||
| HR | 459doc 40460 | Air Temperature Control Sensor | UINT16 | Read/write | 0 = Supply; 1 = Remote; 2 = Return | ||||
| HR | 460doc 40461 | Remote Sensor Temperature Calculation | UINT16 | Read/write | 0 = Average; 1 = Maximum | ||||
| HR | 461doc 40462 | Fan Control Mode | UINT16 | Read/write | 0 = Internal (Auto); 1 = External (Manual) | ||||
| HR | 462doc 40463 | Fan Control Sensor | UINT16 | Read/write | 0 = Supply; 1 = Remote; 2 = Return | ||||
| HR | 463doc 40464 | Remote Sensor Function 1 | UINT16 | Read/write | 0 = Disable; 1 = Reference; 2 = Control | ||||
| HR | 464doc 40465 | Remote Sensor Function 2 | UINT16 | Read/write | 0 = Disable; 1 = Reference; 2 = Control | ||||
| HR | 465doc 40466 | Remote Sensor Function 3 | UINT16 | Read/write | 0 = Disable; 1 = Reference; 2 = Control | ||||
| HR | 466doc 40467 | Remote Sensor Function 4 | UINT16 | Read/write | 0 = Disable; 1 = Reference; 2 = Control | ||||
| HR | 467doc 40468 | Remote Sensor Function 5 | UINT16 | Read/write | 0 = Disable; 1 = Reference; 2 = Control | ||||
| HR | 468doc 40469 | Remote Sensor Function 6 | UINT16 | Read/write | 0 = Disable; 1 = Reference; 2 = Control | ||||
| HR | 469doc 40470 | Remote Sensor Function 7 | UINT16 | Read/write | 0 = Disable; 1 = Reference; 2 = Control | ||||
| HR | 470doc 40471 | Remote Sensor Function 8 | UINT16 | Read/write | 0 = Disable; 1 = Reference; 2 = Control | ||||
| HR | 471doc 40472 | Remote Sensor Function 9 | UINT16 | Read/write | 0 = Disable; 1 = Reference; 2 = Control | ||||
| HR | 472doc 40473 | Remote Sensor Function 10 | UINT16 | Read/write | 0 = Disable; 1 = Reference; 2 = Control | ||||
| HR | 477doc 40478 | System On/Off Control | UINT16 | Read/write | 0 = off; 1 = on | ||||
| HR | 490doc 40491 | Condenser Low Noise Mode Schedule Control | UINT16 | Read/write | 0 = disabled; 1 = enabled | ||||
| HR | 491doc 40492 | Condenser Low Noise Mode Max Fan Speed | UINT16 | % | Read/write | ||||
| HR | 492doc 40493 | Condenser Normal Mode Max Fan Speed | UINT16 | % | Read/write | ||||
| HR | 493doc 40494 | Condenser Low Noise Mode - Interval Days | BITMAP16 | Read/write | bit 0 = Monday; bit 1 = Tuesday; bit 2 = Wednesday; bit 3 = Thursday; bit 4 = Friday; bit 5 = Saturday; bit 6 = Sunday | ||||
| HR | 494doc 40495 | Condenser Low Noise Mode - Full Days | BITMAP16 | Read/write | bit 0 = Monday; bit 1 = Tuesday; bit 2 = Wednesday; bit 3 = Thursday; bit 4 = Friday; bit 5 = Saturday; bit 6 = Sunday | ||||
| HR | 499doc 40500 | System Event Acknowledge/Reset | UINT16 | Read/write | 2 = Reset; 4 = Acknowledge |
Notes on this map
- Source: Emerson Network Power / Liebert reference guide SL-28170 (Rev 9). Vertiv does not host this guide publicly; the linked copy is the unaltered PDF on the Contemporary Controls support site.
- Scale column: 'x / 10' means the raw value is tenths (scale 0.1); '-' or blank means no scaling. Some temperature setpoints are printed without a scale while similar points use x / 10; they are transcribed exactly as printed.
- Most temperatures exist twice: once in deg C and once in deg F at a different register. Only the deg C registers are listed here.
- Points that the guide lists with both an input register (3xxxx) and a holding register (4xxxx) are the writable settings; we list the holding register (read/write). The same value can also be read at the matching 3xxxx input register (same offset).
- Signedness is not stated in the guide. Temperature values are listed as INT16 (they can be below zero); everything else as UINT16.
- Points that take two registers (date/time and schedule start/stop times, 32-bit values) are left out because the guide does not state their word order.
- Event/alarm discrete inputs read 1 while the event is active ('Active on Alarm').
- Event acknowledge/reset (40500) is a holding register only; write 2 to reset or 4 to acknowledge, per the guide.
Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.
Questions about the Vertiv Liebert CRV in-row cooling unit with iCOM v4 (IntelliSlot Modbus)
What Modbus registers does the Vertiv Liebert CRV in-row cooling unit with iCOM v4 (IntelliSlot Modbus) have?
This map lists 176 registers: 91 discrete inputs, 44 input registers, 41 holding registers. 41 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.
Are the Vertiv Liebert CRV in-row cooling unit with iCOM v4 (IntelliSlot Modbus) Modbus addresses 0-based or 1-based?
The manufacturer's document numbers registers Modicon 3xxxx/4xxxx (drop the prefix, subtract 1). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. The guide prints Modicon-style numbers: discrete inputs 1xxxx, input registers 3xxxx, holding registers 4xxxx. Its RTU example asks for holding register 40051 with start offset 50 (0x0032), so subtract 10001 / 30001 / 40001 to get the wire address. Coils are printed as plain numbers on the same scale as the discrete inputs (coil 25 sits beside status 10025), so coil n is wire address n-1.
What are the minimum Modbus registers to integrate the Vertiv Liebert CRV in-row cooling unit with iCOM v4 (IntelliSlot Modbus)?
Start with HR 477 System On/Off Control (System on/off control); IR 474 System Operating State (System operating state); IR 473 System Status (System status); IR 384 Supply Air Temperature (Supply air temperature); IR 386 Return Air Temperature (Return air temperature); IR 411 Return Humidity (Return humidity); HR 396 Air Temperature Set Point (Air temperature setpoint); IR 450 Fan Speed (Fan speed); HR 499 System Event Acknowledge/Reset (Acknowledge / reset events).
How do I enable Modbus control of the Vertiv Liebert CRV in-row cooling unit with iCOM v4 (IntelliSlot Modbus)?
Fit the Liebert IntelliSlot card the guide lists for the unit's controller (for iCOM v4 units: IS-485L for Modbus 485, IS-IPBML for Modbus IP / BACnet IP) and set its Modbus address and line speed on the card.
What happens when the Vertiv Liebert CRV in-row cooling unit with iCOM v4 (IntelliSlot Modbus) loses Modbus communication?
Holding register 40448 'BMS Timeout Period' (minutes) sets how long the unit waits for BMS communication before a timeout event; the resulting action is not described in this guide.
Where is the official Vertiv Liebert CRV in-row cooling unit with iCOM v4 (IntelliSlot Modbus) Modbus documentation?
The source is Liebert IntelliSlot Modbus 485, Modbus IP and BACnet IP Reference Guide (SL-28170 Rev 9), revision 10-12 (printed as SL-28170_REV9_10-12). Vertiv doesn't publish it on its own website, so this map was re-typed from a free copy at https://ccontrols.com/support/dp/Liebert.pdf. It may be an older revision, so check it against the live unit.
More Vertiv Modbus register maps
- Sensor (battery monitoring system)
Vertiv (Alber) Alber MPM-100 and BDS series battery monitors (Modbus ASCII)
Alber MPM-100 (firmware 1.20+) and BDS series (controller firmware 2.20+) battery monitors with BMDM software 4.10+, per protocol document SL-29417 Rev 7.05.
Also known as: Alber MPM-100, Alber BDS, BDS-40, BDS40, MPM100, Vertiv Alber battery monitor, SL-29417 - Air handler (computer room air conditioner)
Vertiv Liebert DS / CW / HPM / PeX / Challenger with iCOM v4 (IntelliSlot Modbus)
Liebert perimeter precision cooling units on the iCOM v4 controller (Challenger 3000, Challenger ITR, CW, Deluxe System/3, DS, PeX with iCOM firmware PA1.04.033.STD or later; HPM with iCOM), read through a Liebert IntelliSlot Modbus 485 or Modbus IP card.
Also known as: Liebert DS, Liebert CW, Liebert HPM, Liebert PeX, Liebert Challenger 3000, Liebert Challenger ITR, Liebert Deluxe System/3, Liebert iCOM v4, IS-485L, IS-IPBML - Chiller (air-cooled chiller for data centres)
Vertiv Liebert HPC chiller with iCOM v4 (IntelliSlot Modbus)
Liebert HPC chillers on the iCOM v4 controller (iCOM_SC31 / iCOM_SC100 applications) with a Liebert IntelliSlot Modbus card.
Also known as: Liebert HPC, HPC chiller, Liebert HPC iCOM - Chiller (refrigerant chiller for Liebert XD rack cooling)
Vertiv Liebert XDC refrigerant chiller for XD systems with iCOM v4 (IntelliSlot Modbus)
Liebert XDC units (the compressorised refrigerant chiller that feeds Liebert XD rack and ceiling cooling modules) on the iCOM v4 controller with a Liebert IntelliSlot Modbus card.
Also known as: Liebert XDC, XDC, Liebert XD chiller - Pump (refrigerant pumping unit for Liebert XD rack cooling)
Vertiv Liebert XDP pumping unit for XD systems with iCOM v4 (IntelliSlot Modbus)
Liebert XDP pumping units on the iCOM v4 controller with a Liebert IntelliSlot Modbus card.
Also known as: Liebert XDP, XDP, Liebert XD pumping unit
Other hvac equipment register maps
- Air handler (in-row self-contained DX cooling unit)
APC (Schneider Electric) InRow ACSC 100 Series self-contained DX cooling unit
APC by Schneider Electric InRow SC (ACSC 100 series) self-contained cooling units, per register map part number 990-3027D.
Also known as: ACSC100, InRow SC, InRow ACSC - Rooftop unit
Daikin Applied Rebel / Rebel Applied rooftop (MicroTech 4 controller)
Daikin Applied Rebel Applied (DPSA, R-410A/R-32) and Rebel (DPS, R-32) packaged rooftops with MicroTech 4 controller and Modbus RTU module, per ED 19133-2 (Oct 2025).
Also known as: DPSA, DPS, Rebel Applied, Rebel, MicroTech 4 rooftop, ED 19133-2 - Air handler
Flexit Nordic residential air handling unit (Flexit GO, built-in Modbus)
Flexit NORDIC series residential ventilation units with Flexit GO control and built-in Modbus RTU (cable harness 116405), per the 'Modbus Nordic Basic' register sheet and instruction 117989-01 (2020-01). Not EcoNordic, which has its own register sheet.
Also known as: Nordic S2, Nordic S3, Nordic S4, Nordic CL2, Nordic CL3, Nordic CL4, Flexit GO, Modbus Nordic Basic, 117989 - Thermostat (fan coil)
Johnson Controls T7000 series fan coil thermostat (Modbus RTU)
Johnson Controls T7000 series Modbus thermostats listed in the data table: T7600-TF21, T7601-TF20 (ECM fan), T7600-TF20 (relay), T7603-T000 (single-stage heating) and T7600-TB21 (with AI); data table revision 2.4 (2019-12-23).
Also known as: T7600-TF21-9JS0, T7601-TF20-9JS0, T7600-TF20-9JS0, T7603-T000-9JF0, T7600-TF21-1JS0, T7601-TF20-1JS0, T7600-TF20-1JS0, T7603-T000-1JF0, T7600-TB21-9JA0, T7600, T7601, T7603 - Air handler (compact make-up air unit)
Neptronic CMU compact make-up air unit (Modbus communication module)
Neptronic CMU compact make-up air units with the Modbus communication module, guide CMU-Modbus Guide-211125.
Also known as: Compact Make-up Air Unit, Neptronic CMU, CMU Series - Air handler humidifier (steam-to-steam)
Neptronic SKS4 steam-to-steam humidifier (Modbus communication module)
Neptronic SKS4 series steam-to-steam humidifiers with the Modbus communication module, guide SKS4-Modbus Guide-220509 (V2.03).
Also known as: SKS4-E, SKS4-N, SKS4 Steam to Steam Humidifier, Neptronic SKS4 Modbus
All hvac equipment Modbus register maps →
Source: Liebert IntelliSlot Modbus 485, Modbus IP and BACnet IP Reference Guide · SL-28170 Rev 9 · rev. 10-12 (printed as SL-28170_REV9_10-12) · unofficial copy. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.