- Liebert XDC refrigerant chiller for XD systems with iCOM v4 (IntelliSlot Modbus)
Chiller (refrigerant chiller for Liebert XD rack cooling) · Modbus register map
Vertiv Liebert XDC refrigerant chiller for XD systems with iCOM v4 (IntelliSlot Modbus) Modbus register map
Updated 19 November 2026
The Liebert XDC supplies pumped refrigerant to Liebert XD cooling modules. With a Liebert IntelliSlot Modbus card its iCOM controller exposes system on/off and status, pump and compressor states, supply refrigerant and external air temperatures, dew point, thresholds, per-XD-system fan, capacity and remote sensor values, and alarm bits.
This page lists 221 Modbus registers for the Vertiv Liebert XDC refrigerant chiller for XD systems with iCOM v4 (IntelliSlot Modbus) — 59 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Vertiv’s own free documentation (linked below) and checked against it.
- Manufacturer
- Vertiv
- Model
- Liebert XDC refrigerant chiller for XD systems with iCOM v4 (IntelliSlot Modbus)
- Registers
- 221 (59 writable)
- Transport
- Modbus RTU, Modbus TCP
- Default unit ID
- Not stated
- Default serial
- 8N1
- Documented addressing
- Modicon 3xxxx/4xxxx (drop the prefix, subtract 1)
- Also known as
- Liebert XDC, XDC, Liebert XD chiller
Integration notes: Vertiv Liebert XDC refrigerant chiller for XD systems with iCOM v4 (IntelliSlot Modbus)
Read 30385-30424 for pumps, compressors, refrigerant and air temperatures and status; write 40426 to switch the XDC on/off. Per-XD-system data starts at 30444 / 40445 for system 1.
Minimum registers to map
Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.
| Register | Name | Type | Why | Access |
|---|---|---|---|---|
| HR 425 | System Information: System On/Off Control | UINT16 | System on/off control | Read/write |
| IR 388 | System Information: System Operating State | UINT16 | System operating state | Read |
| IR 421 | System Information: System Status | UINT16 | System status | Read |
| IR 386 | Supply Refrigerant Temperature | INT16 | Supply refrigerant temperature | Read |
| IR 399 | External Air: Dew Point Temperature | INT16 | Dew point temperature | Read |
| IR 384 | Pump 1 State | UINT16 | Pump 1 state | Read |
| IR 415 | Compressor 1A State | UINT16 | Compressor 1A state | Read |
| IR 448 | XD System 1: Cooling Capacity | UINT16 | XD system 1 cooling capacity | Read |
Enable Modbus control & writes
Fit the Liebert IntelliSlot card the guide lists for the unit's controller (for iCOM v4 units: IS-485L for Modbus 485, IS-IPBML for Modbus IP / BACnet IP) and set its Modbus address and line speed on the card.
Byte order & addressing
- Modicon numbering: subtract 40001 / 30001 / 10001 for the wire address.
- The guide prints the XD-system blocks for systems 1, 2 and 20 only (and remote sensors 1, 2 and 4 per system); other systems follow the same layout but are not printed, so they are not listed here.
Network setup
- RS-485 (2-wire) RTU settings for the IntelliSlot 485 card: 9600, 19200 or 38400 baud, 8 data bits, no parity, 1 stop bit.
- Each unit needs a unique Modbus slave address on the RS-485 line.
- For Modbus IP, use the IntelliSlot Modbus IP / BACnet IP card listed for the unit's controller in the guide's compatibility table.
Watch out for
- Hot/cold aisle thresholds (40459-40465 etc.) are printed without a scale, unlike most other temperatures.
Vertiv Liebert XDC refrigerant chiller for XD systems with iCOM v4 (IntelliSlot Modbus) Modbus registers
Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.
| Table | Address | Name | Description | Type | Order | Scale | Units | Access | Values / bits |
|---|---|---|---|---|---|---|---|---|---|
| DI | 0doc 10001 | Pump 1 Loss of Flow | BIT | Read | 0 = Inactive; 1 = Active | ||||
| DI | 1doc 10002 | Pump 2 Loss of Flow | BIT | Read | 0 = Inactive; 1 = Active | ||||
| DI | 2doc 10003 | System Events: Fan Issue | BIT | Read | 0 = Inactive; 1 = Active | ||||
| DI | 3doc 10004 | System Events: System Condensation Detected | BIT | Read | 0 = Inactive; 1 = Active | ||||
| DI | 4doc 10005 | System Events: Customer Input 1 | BIT | Read | 0 = Inactive; 1 = Active | ||||
| DI | 5doc 10006 | Refridgerant: Supply Refrigerant Over Temp | BIT | Read | 0 = Inactive; 1 = Active | ||||
| DI | 6doc 10007 | Refridgerant: Supply Refrigerant Under Temp | BIT | Read | 0 = Inactive; 1 = Active | ||||
| DI | 7doc 10008 | Refridgerant: Supply Refrigerant Temp Sensor Issue | BIT | Read | 0 = Inactive; 1 = Active | ||||
| DI | 8doc 10009 | External Air: Ext Air Sensor A Over Temperature | BIT | Read | 0 = Inactive; 1 = Active | ||||
| DI | 9doc 10010 | External Air: Ext Air Sensor A Under Temperature | BIT | Read | 0 = Inactive; 1 = Active | ||||
| DI | 10doc 10011 | External Air: Ext Air Sensor A Issue | BIT | Read | 0 = Inactive; 1 = Active | ||||
| DI | 11doc 10012 | External Air: Ext Air Sensor B Over Temperature | BIT | Read | 0 = Inactive; 1 = Active | ||||
| DI | 12doc 10013 | External Air: Ext Air Sensor B Under Temperature | BIT | Read | 0 = Inactive; 1 = Active | ||||
| DI | 13doc 10014 | External Air: Ext Air Sensor B Issue | BIT | Read | 0 = Inactive; 1 = Active | ||||
| DI | 14doc 10015 | External Air: Ext Dew Point Over Temperature | BIT | Read | 0 = Inactive; 1 = Active | ||||
| DI | 15doc 10016 | Pump Short Cycle | BIT | Read | 0 = Inactive; 1 = Active | ||||
| DI | 16doc 10017 | Compressor 1A High Head Pressure | BIT | Read | 0 = Inactive; 1 = Active | ||||
| DI | 17doc 10018 | Compressor 1B High Head Pressure | BIT | Read | 0 = Inactive; 1 = Active | ||||
| DI | 18doc 10019 | Compressor 2A High Head Pressure | BIT | Read | 0 = Inactive; 1 = Active | ||||
| DI | 19doc 10020 | Compressor 2B High Head Pressure | BIT | Read | 0 = Inactive; 1 = Active | ||||
| DI | 20doc 10021 | Compressor 1A Short Cycle | BIT | Read | 0 = Inactive; 1 = Active | ||||
| DI | 21doc 10022 | Compressor 1B Short Cycle | BIT | Read | 0 = Inactive; 1 = Active | ||||
| DI | 22doc 10023 | Compressor 2A Short Cycle | BIT | Read | 0 = Inactive; 1 = Active | ||||
| DI | 23doc 10024 | Compressor 2B Short Cycle | BIT | Read | 0 = Inactive; 1 = Active | ||||
| DI | 24doc 10025 | Compressor: Circuit 1 Low Suction Pressure | BIT | Read | 0 = Inactive; 1 = Active | ||||
| DI | 25doc 10026 | Compressor: Circuit 2 Low Suction Pressure | BIT | Read | 0 = Inactive; 1 = Active | ||||
| DI | 26doc 10027 | System Events: Shutdown - Loss Of Power | BIT | Read | 0 = Inactive; 1 = Active | ||||
| DI | 27doc 10028 | System Events: Smoke Detected | BIT | Read | 0 = Inactive; 1 = Active | ||||
| DI | 28doc 10029 | System Events: Water Under Floor | BIT | Read | 0 = Inactive; 1 = Active | ||||
| DI | 29doc 10030 | System Events: Service Required | BIT | Read | 0 = Inactive; 1 = Active | ||||
| DI | 39doc 10040 | Pump Hours 1: Pump Hours Exceeded | BIT | Read | 0 = Inactive; 1 = Active | ||||
| DI | 45doc 10046 | Pump Hours 2: Pump Hours Exceeded | BIT | Read | 0 = Inactive; 1 = Active | ||||
| DI | 51doc 10052 | XD System 1: Ext System Condensation Detected | BIT | Read | 0 = Inactive; 1 = Active | ||||
| DI | 52doc 10053 | XD System 1: Ext Fan Issue | BIT | Read | 0 = Inactive; 1 = Active | ||||
| DI | 53doc 10054 | XD System 1: Sensor Issue | BIT | Read | 0 = Inactive; 1 = Active | ||||
| DI | 54doc 10055 | XD System 1: Ext Remote Shutdown | BIT | Read | 0 = Inactive; 1 = Active | ||||
| DI | 55doc 10056 | XD System 1: Hot Aisle Temp Out of Range | BIT | Read | 0 = Inactive; 1 = Active | ||||
| DI | 56doc 10057 | XD System 1: Cold Aisle Temp Out of Range | BIT | Read | 0 = Inactive; 1 = Active | ||||
| DI | 62doc 10063 | XD System 2: Ext System Condensation Detected | BIT | Read | 0 = Inactive; 1 = Active | ||||
| DI | 63doc 10064 | XD System 2: Ext Fan Issue | BIT | Read | 0 = Inactive; 1 = Active | ||||
| DI | 64doc 10065 | XD System 2: Sensor Issue | BIT | Read | 0 = Inactive; 1 = Active | ||||
| DI | 65doc 10066 | XD System 2: Ext Remote Shutdown | BIT | Read | 0 = Inactive; 1 = Active | ||||
| DI | 66doc 10067 | XD System 2: Hot Aisle Temp Out of Range | BIT | Read | 0 = Inactive; 1 = Active | ||||
| DI | 67doc 10068 | XD System 2: Cold Aisle Temp Out of Range | BIT | Read | 0 = Inactive; 1 = Active | ||||
| DI | 260doc 10261 | XD System 20: Ext System Condensation Detected | BIT | Read | 0 = Inactive; 1 = Active | ||||
| DI | 261doc 10262 | XD System 20: Ext Fan Issue | BIT | Read | 0 = Inactive; 1 = Active | ||||
| DI | 262doc 10263 | XD System 20: Sensor Issue | BIT | Read | 0 = Inactive; 1 = Active | ||||
| DI | 263doc 10264 | XD System 20: Ext Remote Shutdown | BIT | Read | 0 = Inactive; 1 = Active | ||||
| DI | 264doc 10265 | XD System 20: Hot Aisle Temp Out of Range | BIT | Read | 0 = Inactive; 1 = Active | ||||
| DI | 265doc 10266 | XD System 20: Cold Aisle Temp Out of Range | BIT | Read | 0 = Inactive; 1 = Active | ||||
| DI | 271doc 10272 | System Events: Unit Communication Lost | BIT | Read | 0 = Inactive; 1 = Active | ||||
| DI | 272doc 10273 | System Events: RAM Battery Issue | BIT | Read | 0 = Inactive; 1 = Active | ||||
| DI | 273doc 10274 | System Events: Master Unit Communication Lost | BIT | Read | 0 = Inactive; 1 = Active | ||||
| DI | 274doc 10275 | System Events: Remote Shutdown | BIT | Read | 0 = Inactive; 1 = Active | ||||
| DI | 275doc 10276 | System Events: Unit Code Missing | BIT | Read | 0 = Inactive; 1 = Active | ||||
| DI | 281doc 10282 | Messages: Unit On | BIT | Read | 0 = Inactive; 1 = Active | ||||
| DI | 282doc 10283 | Messages: Unit Off | BIT | Read | 0 = Inactive; 1 = Active | ||||
| DI | 283doc 10284 | Messages: Unit Standby | BIT | Read | 0 = Inactive; 1 = Active | ||||
| DI | 284doc 10285 | Messages: Unit Partial Shutdown | BIT | Read | 0 = Inactive; 1 = Active | ||||
| DI | 285doc 10286 | Messages: Unit Shutdown | BIT | Read | 0 = Inactive; 1 = Active | ||||
| DI | 286doc 10287 | Messages: Maintenance Due | BIT | Read | 0 = Inactive; 1 = Active | ||||
| DI | 287doc 10288 | Messages: Maintenance Completed | BIT | Read | 0 = Inactive; 1 = Active | ||||
| IR | 384doc 30385 | Pump 1 State | UINT16 | Read | 0 = Off; 1 = On | ||||
| IR | 385doc 30386 | Pump 2 State | UINT16 | Read | 0 = Off; 1 = On | ||||
| IR | 386doc 30387 | Supply Refrigerant Temperature | INT16 | × 0.1 | deg C | Read | |||
| IR | 388doc 30389 | System Information: System Operating State | UINT16 | Read | 0 = Off; 1 = On; 2 = Standby | ||||
| IR | 389doc 30390 | External Air: Ext Air Sensor A Temperature | INT16 | × 0.1 | deg C | Read | |||
| IR | 391doc 30392 | External Air: Ext Air Sensor A Humidity | UINT16 | × 0.1 | % RH | Read | |||
| IR | 392doc 30393 | External Air: Ext Air Sensor A Dew Point Temp | INT16 | × 0.1 | deg C | Read | |||
| IR | 394doc 30395 | External Air: Ext Air Sensor B Temperature | INT16 | × 0.1 | deg C | Read | |||
| IR | 396doc 30397 | External Air: Ext Air Sensor B Humidity | UINT16 | × 0.1 | % RH | Read | |||
| IR | 397doc 30398 | External Air: Ext Air Sensor B Dew Point Temp | INT16 | × 0.1 | deg C | Read | |||
| IR | 399doc 30400 | External Air: Dew Point Temperature | INT16 | × 0.1 | deg C | Read | |||
| IR | 411doc 30412 | Hot Gas Valve 1 Open Position | UINT16 | × 0.1 | % | Read | |||
| IR | 412doc 30413 | Hot Gas Valve 2 Open Position | UINT16 | × 0.1 | % | Read | |||
| IR | 413doc 30414 | Hot Gas Solenoid Valve 1 Position | UINT16 | Read | 0 = closed; 1 = open | ||||
| IR | 414doc 30415 | Hot Gas Solenoid Valve 2 Position | UINT16 | Read | 0 = closed; 1 = open | ||||
| IR | 415doc 30416 | Compressor 1A State | UINT16 | Read | 0 = off; 1 = on | ||||
| IR | 416doc 30417 | Compressor 1B State | UINT16 | Read | 0 = off; 1 = on | ||||
| IR | 417doc 30418 | Compressor 2A State | UINT16 | Read | 0 = off; 1 = on | ||||
| IR | 418doc 30419 | Compressor 2B State | UINT16 | Read | 0 = off; 1 = on | ||||
| IR | 419doc 30420 | System Information: Calculated Next Maintenance Month | UINT16 | Read | |||||
| IR | 420doc 30421 | System Information: Calculated Next Maintenance Year | UINT16 | Read | |||||
| IR | 421doc 30422 | System Information: System Status | UINT16 | Read | 1 = Normal Operation; 2 = StartUp; 8 = Normal with Warning; 16 = Normal with Alarm; 32 = Abnormal Operation | ||||
| IR | 422doc 30423 | System Information: System Control Mode | UINT16 | Read | 0 = Internal (Auto); 1 = External (Manual) | ||||
| IR | 423doc 30424 | System Information: Maintenance Ramp | UINT16 | % | Read | ||||
| IR | 443doc 30444 | XD System 1: Communication Status | UINT16 | Read | 0 = Connected; 1 = Not Connected | ||||
| IR | 445doc 30446 | XD System 1: Primary Fan Group State | UINT16 | Read | 0 = off; 1 = on; 2 = economy | ||||
| IR | 448doc 30449 | XD System 1: Cooling Capacity | UINT16 | % | Read | ||||
| IR | 449doc 30450 | XD System 1: Cooling Capacity | UINT16 | kW | Read | ||||
| IR | 471doc 30472 | XD System 2: Communication Status | UINT16 | Read | 0 = Connected; 1 = Not Connected | ||||
| IR | 473doc 30474 | XD System 2: Primary Fan Group State | UINT16 | Read | 0 = off; 1 = on; 2 = economy | ||||
| IR | 476doc 30477 | XD System 2: Cooling Capacity | UINT16 | % | Read | ||||
| IR | 477doc 30478 | XD System 2: Cooling Capacity | UINT16 | kW | Read | ||||
| IR | 975doc 30976 | XD System 20: Communication Status | UINT16 | Read | 0 = Connected; 1 = Not Connected | ||||
| IR | 977doc 30978 | XD System 20: Primary Fan Group State | UINT16 | Read | 0 = off; 1 = on; 2 = economy | ||||
| IR | 980doc 30981 | XD System 20: Cooling Capacity | UINT16 | % | Read | ||||
| IR | 981doc 30982 | XD System 20: Cooling Capacity | UINT16 | kW | Read | ||||
| IR | 1003doc 31004 | XD System 1 Temperature Sensor 1: Remote Sensor Temperature | INT16 | × 0.1 | deg C | Read | |||
| IR | 1010doc 31011 | XD System 1 Temperature Sensor 2: Remote Sensor Temperature | INT16 | × 0.1 | deg C | Read | |||
| IR | 1024doc 31025 | XD System 1 Temperature Sensor 4: Remote Sensor Temperature | INT16 | × 0.1 | deg C | Read | |||
| IR | 1031doc 31032 | XD System 2 Temperature Sensor 1: Remote Sensor Temperature | INT16 | × 0.1 | deg C | Read | |||
| IR | 1038doc 31039 | XD System 2 Temperature Sensor 2: Remote Sensor Temperature | INT16 | × 0.1 | deg C | Read | |||
| IR | 1052doc 31053 | XD System 2 Temperature Sensor 4: Remote Sensor Temperature | INT16 | × 0.1 | deg C | Read | |||
| IR | 1059doc 31060 | XD System 3 Temperature Sensor 1: Remote Sensor Temperature | INT16 | × 0.1 | deg C | Read | |||
| IR | 1066doc 31067 | XD System 3 Temperature Sensor 2: Remote Sensor Temperature | INT16 | × 0.1 | deg C | Read | |||
| IR | 1080doc 31081 | XD System 3 Temperature Sensor 4: Remote Sensor Temperature | INT16 | × 0.1 | deg C | Read | |||
| IR | 1087doc 31088 | XD System 4 Temperature Sensor 1: Remote Sensor Temperature | INT16 | × 0.1 | deg C | Read | |||
| IR | 1094doc 31095 | XD System 4 Temperature Sensor 2: Remote Sensor Temperature | INT16 | × 0.1 | deg C | Read | |||
| IR | 1108doc 31109 | XD System 4 Temperature Sensor 4: Remote Sensor Temperature | INT16 | × 0.1 | deg C | Read | |||
| IR | 1115doc 31116 | XD System 5 Temperature Sensor 1: Remote Sensor Temperature | INT16 | × 0.1 | deg C | Read | |||
| IR | 1122doc 31123 | XD System 5 Temperature Sensor 2: Remote Sensor Temperature | INT16 | × 0.1 | deg C | Read | |||
| IR | 1136doc 31137 | XD System 5 Temperature Sensor 4: Remote Sensor Temperature | INT16 | × 0.1 | deg C | Read | |||
| IR | 1143doc 31144 | XD System 6 Temperature Sensor 1: Remote Sensor Temperature | INT16 | × 0.1 | deg C | Read | |||
| IR | 1150doc 31151 | XD System 6 Temperature Sensor 2: Remote Sensor Temperature | INT16 | × 0.1 | deg C | Read | |||
| IR | 1164doc 31165 | XD System 6 Temperature Sensor 4: Remote Sensor Temperature | INT16 | × 0.1 | deg C | Read | |||
| IR | 1171doc 31172 | XD System 7 Temperature Sensor 1: Remote Sensor Temperature | INT16 | × 0.1 | deg C | Read | |||
| IR | 1178doc 31179 | XD System 7 Temperature Sensor 2: Remote Sensor Temperature | INT16 | × 0.1 | deg C | Read | |||
| IR | 1192doc 31193 | XD System 7 Temperature Sensor 4: Remote Sensor Temperature | INT16 | × 0.1 | deg C | Read | |||
| IR | 1199doc 31200 | XD System 8 Temperature Sensor 1: Remote Sensor Temperature | INT16 | × 0.1 | deg C | Read | |||
| IR | 1206doc 31207 | XD System 8 Temperature Sensor 2: Remote Sensor Temperature | INT16 | × 0.1 | deg C | Read | |||
| IR | 1220doc 31221 | XD System 8 Temperature Sensor 4: Remote Sensor Temperature | INT16 | × 0.1 | deg C | Read | |||
| IR | 1227doc 31228 | XD System 9 Temperature Sensor 1: Remote Sensor Temperature | INT16 | × 0.1 | deg C | Read | |||
| IR | 1234doc 31235 | XD System 9 Temperature Sensor 2: Remote Sensor Temperature | INT16 | × 0.1 | deg C | Read | |||
| IR | 1248doc 31249 | XD System 9 Temperature Sensor 4: Remote Sensor Temperature | INT16 | × 0.1 | deg C | Read | |||
| IR | 1255doc 31256 | XD System 10 Temperature Sensor 1: Remote Sensor Temperature | INT16 | × 0.1 | deg C | Read | |||
| IR | 1262doc 31263 | XD System 10 Temperature Sensor 2: Remote Sensor Temperature | INT16 | × 0.1 | deg C | Read | |||
| IR | 1276doc 31277 | XD System 10 Temperature Sensor 4: Remote Sensor Temperature | INT16 | × 0.1 | deg C | Read | |||
| IR | 1283doc 31284 | XD System 11 Temperature Sensor 1: Remote Sensor Temperature | INT16 | × 0.1 | deg C | Read | |||
| IR | 1290doc 31291 | XD System 11 Temperature Sensor 2: Remote Sensor Temperature | INT16 | × 0.1 | deg C | Read | |||
| IR | 1304doc 31305 | XD System 11 Temperature Sensor 4: Remote Sensor Temperature | INT16 | × 0.1 | deg C | Read | |||
| IR | 1311doc 31312 | XD System 12 Temperature Sensor 1: Remote Sensor Temperature | INT16 | × 0.1 | deg C | Read | |||
| IR | 1318doc 31319 | XD System 12 Temperature Sensor 2: Remote Sensor Temperature | INT16 | × 0.1 | deg C | Read | |||
| IR | 1332doc 31333 | XD System 12 Temperature Sensor 4: Remote Sensor Temperature | INT16 | × 0.1 | deg C | Read | |||
| IR | 1339doc 31340 | XD System 13 Temperature Sensor 1: Remote Sensor Temperature | INT16 | × 0.1 | deg C | Read | |||
| IR | 1346doc 31347 | XD System 13 Temperature Sensor 2: Remote Sensor Temperature | INT16 | × 0.1 | deg C | Read | |||
| IR | 1360doc 31361 | XD System 13 Temperature Sensor 4: Remote Sensor Temperature | INT16 | × 0.1 | deg C | Read | |||
| IR | 1367doc 31368 | XD System 14 Temperature Sensor 1: Remote Sensor Temperature | INT16 | × 0.1 | deg C | Read | |||
| IR | 1374doc 31375 | XD System 14 Temperature Sensor 2: Remote Sensor Temperature | INT16 | × 0.1 | deg C | Read | |||
| IR | 1388doc 31389 | XD System 14 Temperature Sensor 4: Remote Sensor Temperature | INT16 | × 0.1 | deg C | Read | |||
| IR | 1395doc 31396 | XD System 15 Temperature Sensor 1: Remote Sensor Temperature | INT16 | × 0.1 | deg C | Read | |||
| IR | 1402doc 31403 | XD System 15 Temperature Sensor 2: Remote Sensor Temperature | INT16 | × 0.1 | deg C | Read | |||
| IR | 1416doc 31417 | XD System 15 Temperature Sensor 4: Remote Sensor Temperature | INT16 | × 0.1 | deg C | Read | |||
| IR | 1423doc 31424 | XD System 16 Temperature Sensor 1: Remote Sensor Temperature | INT16 | × 0.1 | deg C | Read | |||
| IR | 1430doc 31431 | XD System 16 Temperature Sensor 2: Remote Sensor Temperature | INT16 | × 0.1 | deg C | Read | |||
| IR | 1444doc 31445 | XD System 16 Temperature Sensor 4: Remote Sensor Temperature | INT16 | × 0.1 | deg C | Read | |||
| IR | 1451doc 31452 | XD System 17 Temperature Sensor 1: Remote Sensor Temperature | INT16 | × 0.1 | deg C | Read | |||
| IR | 1458doc 31459 | XD System 17 Temperature Sensor 2: Remote Sensor Temperature | INT16 | × 0.1 | deg C | Read | |||
| IR | 1472doc 31473 | XD System 17 Temperature Sensor 4: Remote Sensor Temperature | INT16 | × 0.1 | deg C | Read | |||
| IR | 1479doc 31480 | XD System 18 Temperature Sensor 1: Remote Sensor Temperature | INT16 | × 0.1 | deg C | Read | |||
| IR | 1486doc 31487 | XD System 18 Temperature Sensor 2: Remote Sensor Temperature | INT16 | × 0.1 | deg C | Read | |||
| IR | 1500doc 31501 | XD System 18 Temperature Sensor 4: Remote Sensor Temperature | INT16 | × 0.1 | deg C | Read | |||
| IR | 1507doc 31508 | XD System 19 Temperature Sensor 1: Remote Sensor Temperature | INT16 | × 0.1 | deg C | Read | |||
| IR | 1514doc 31515 | XD System 19 Temperature Sensor 2: Remote Sensor Temperature | INT16 | × 0.1 | deg C | Read | |||
| IR | 1528doc 31529 | XD System 19 Temperature Sensor 4: Remote Sensor Temperature | INT16 | × 0.1 | deg C | Read | |||
| IR | 1535doc 31536 | XD System 20 Temperature Sensor 1: Remote Sensor Temperature | INT16 | × 0.1 | deg C | Read | |||
| IR | 1542doc 31543 | XD System 20 Temperature Sensor 2: Remote Sensor Temperature | INT16 | × 0.1 | deg C | Read | |||
| IR | 1556doc 31557 | XD System 20 Temperature Sensor 4: Remote Sensor Temperature | INT16 | × 0.1 | deg C | Read | |||
| IR | 1563doc 31564 | Secondary Fans 1: Fan State | UINT16 | Read | 0 = off; 1 = on; 2 = economy | ||||
| IR | 1570doc 31571 | Secondary Fans 2: Fan State | UINT16 | Read | 0 = off; 1 = on; 2 = economy | ||||
| IR | 1696doc 31697 | Secondary Fans 20: Fan State | UINT16 | Read | 0 = off; 1 = on; 2 = economy | ||||
| IR | 1703doc 31704 | System Information: System Operating State Reason | UINT16 | Read | 0 = Reason Unknown; 1 = Network Display; 2 = Alarm; 3 = Schedule; 4 = Remote System; 5 = External Input; 6 = Local Display | ||||
| HR | 401doc 40402 | External Air: Minimum Room Temperature Set Point | INT16 | × 0.1 | deg C | Read/write | |||
| HR | 403doc 40404 | External Air: Ext Air Over Temp Threshold | INT16 | × 0.1 | deg C | Read/write | |||
| HR | 405doc 40406 | External Air: Ext Air Under Temp Threshold | INT16 | × 0.1 | deg C | Read/write | |||
| HR | 407doc 40408 | External Air: Ext Dew Point Over Temp Threshold | INT16 | × 0.1 | deg C | Read/write | |||
| HR | 409doc 40410 | Refrigerant: Supply Refrig Over Temp Threshold | INT16 | × 0.1 | deg C | Read/write | |||
| HR | 424doc 40425 | System Information: Auto Restart Delay | UINT16 | sec | Read/write | ||||
| HR | 425doc 40426 | System Information: System On/Off Control | UINT16 | Read/write | 0 = off; 1 = on | ||||
| HR | 429doc 40430 | Pump Hours 1: Pump Hours | UINT16 | hr | Read/write | ||||
| HR | 430doc 40431 | Pump Hours 1: Pump Hours Threshold | UINT16 | hr | Read/write | ||||
| HR | 436doc 40437 | Pump Hours 2: Pump Hours | UINT16 | hr | Read/write | ||||
| HR | 437doc 40438 | Pump Hours 2: Pump Hours Threshold | UINT16 | hr | Read/write | ||||
| HR | 444doc 40445 | XD System 1: Fan On/Off Control | UINT16 | Read/write | 0 = off; 1 = on | ||||
| HR | 446doc 40447 | XD System 1: Fan Button Control | UINT16 | Read/write | 0 = enabled; 1 = disabled | ||||
| HR | 447doc 40448 | XD System 1: Visual ID Control | UINT16 | Read/write | 0 = disabled; 1 = enabled | ||||
| HR | 450doc 40451 | XD System 1: Ext System Condensation Detected - Event Control | UINT16 | Read/write | 0 = disabled; 1 = enabled | ||||
| HR | 451doc 40452 | XD System 1: Ext System Condensation Detected - Event Type | UINT16 | Read/write | 0 = Message; 1 = Warning; 2 = Alarm | ||||
| HR | 452doc 40453 | XD System 1: Ext Fan Issue - Event Control | UINT16 | Read/write | 0 = disabled; 1 = enabled | ||||
| HR | 453doc 40454 | XD System 1: Ext Fan Issue - Event Type | UINT16 | Read/write | 0 = Message; 1 = Warning; 2 = Alarm | ||||
| HR | 454doc 40455 | XD System 1: Sensor Issue - Event Control | UINT16 | Read/write | 0 = disabled; 1 = enabled | ||||
| HR | 455doc 40456 | XD System 1: Sensor Issue - Event Type | UINT16 | Read/write | 0 = Message; 1 = Warning; 2 = Alarm | ||||
| HR | 456doc 40457 | XD System 1: Ext Remote Shutdown - Event Control | UINT16 | Read/write | 0 = disabled; 1 = enabled | ||||
| HR | 457doc 40458 | XD System 1: Ext Remote Shutdown - Event Type | UINT16 | Read/write | 0 = Message; 1 = Warning; 2 = Alarm | ||||
| HR | 458doc 40459 | XD System 1: Hot Aisle Over Temp Threshold | INT16 | deg C | Read/write | ||||
| HR | 460doc 40461 | XD System 1: Hot Aisle Under Temp Threshold | INT16 | deg C | Read/write | ||||
| HR | 462doc 40463 | XD System 1: Cold Aisle Over Temp Threshold | INT16 | deg C | Read/write | ||||
| HR | 464doc 40465 | XD System 1: Cold Aisle Under Temp Threshold | INT16 | deg C | Read/write | ||||
| HR | 472doc 40473 | XD System 2: Fan On/Off Control | UINT16 | Read/write | 0 = off; 1 = on | ||||
| HR | 474doc 40475 | XD System 2: Fan Button Control | UINT16 | Read/write | 0 = enabled; 1 = disabled | ||||
| HR | 475doc 40476 | XD System 2: Visual ID Control | UINT16 | Read/write | 0 = disabled; 1 = enabled | ||||
| HR | 478doc 40479 | XD System 2: Ext System Condensation Detected - Event Control | UINT16 | Read/write | 0 = disabled; 1 = enabled | ||||
| HR | 479doc 40480 | XD System 2: Ext System Condensation Detected - Event Type | UINT16 | Read/write | 0 = Message; 1 = Warning; 2 = Alarm | ||||
| HR | 480doc 40481 | XD System 2: Ext Fan Issue - Event Control | UINT16 | Read/write | 0 = disabled; 1 = enabled | ||||
| HR | 481doc 40482 | XD System 2: Ext Fan Issue - Event Type | UINT16 | Read/write | 0 = Message; 1 = Warning; 2 = Alarm | ||||
| HR | 482doc 40483 | XD System 2: Sensor Issue - Event Control | UINT16 | Read/write | 0 = disabled; 1 = enabled | ||||
| HR | 483doc 40484 | XD System 2: Sensor Issue - Event Type | UINT16 | Read/write | 0 = Message; 1 = Warning; 2 = Alarm | ||||
| HR | 484doc 40485 | XD System 2: Ext Remote Shutdown - Event Control | UINT16 | Read/write | 0 = disabled; 1 = enabled | ||||
| HR | 485doc 40486 | XD System 2: Ext Remote Shutdown - Event Type | UINT16 | Read/write | 0 = Message; 1 = Warning; 2 = Alarm | ||||
| HR | 486doc 40487 | XD System 2: Hot Aisle Over Temp Threshold | INT16 | deg C | Read/write | ||||
| HR | 488doc 40489 | XD System 2: Hot Aisle Under Temp Threshold | INT16 | deg C | Read/write | ||||
| HR | 490doc 40491 | XD System 2: Cold Aisle Over Temp Threshold | INT16 | deg C | Read/write | ||||
| HR | 492doc 40493 | XD System 2: Cold Aisle Under Temp Threshold | INT16 | deg C | Read/write | ||||
| HR | 976doc 40977 | XD System 20: Fan On/Off Control | UINT16 | Read/write | 0 = off; 1 = on | ||||
| HR | 978doc 40979 | XD System 20: Fan Button Control | UINT16 | Read/write | 0 = enabled; 1 = disabled | ||||
| HR | 979doc 40980 | XD System 20: Visual ID Control | UINT16 | Read/write | 0 = disabled; 1 = enabled | ||||
| HR | 982doc 40983 | XD System 20: Ext System Condensation Detected - Event Control | UINT16 | Read/write | 0 = disabled; 1 = enabled | ||||
| HR | 983doc 40984 | XD System 20: Ext System Condensation Detected - Event Type | UINT16 | Read/write | 0 = Message; 1 = Warning; 2 = Alarm | ||||
| HR | 984doc 40985 | XD System 20: Ext Fan Issue - Event Control | UINT16 | Read/write | 0 = disabled; 1 = enabled | ||||
| HR | 985doc 40986 | XD System 20: Ext Fan Issue - Event Type | UINT16 | Read/write | 0 = Message; 1 = Warning; 2 = Alarm | ||||
| HR | 986doc 40987 | XD System 20: Sensor Issue - Event Control | UINT16 | Read/write | 0 = disabled; 1 = enabled | ||||
| HR | 987doc 40988 | XD System 20: Sensor Issue - Event Type | UINT16 | Read/write | 0 = Message; 1 = Warning; 2 = Alarm | ||||
| HR | 988doc 40989 | XD System 20: Ext Remote Shutdown - Event Control | UINT16 | Read/write | 0 = disabled; 1 = enabled | ||||
| HR | 989doc 40990 | XD System 20: Ext Remote Shutdown - Event Type | UINT16 | Read/write | 0 = Message; 1 = Warning; 2 = Alarm | ||||
| HR | 990doc 40991 | XD System 20: Hot Aisle Over Temp Threshold | INT16 | deg C | Read/write | ||||
| HR | 992doc 40993 | XD System 20: Hot Aisle Under Temp Threshold | INT16 | deg C | Read/write | ||||
| HR | 994doc 40995 | XD System 20: Cold Aisle Over Temp Threshold | INT16 | deg C | Read/write | ||||
| HR | 996doc 40997 | XD System 20: Cold Aisle Under Temp Threshold | INT16 | deg C | Read/write | ||||
| HR | 1564doc 41565 | Secondary Fans 1: Fan Economy Mode | UINT16 | Read/write | 0 = disabled; 1 = automatic; 2 = manual | ||||
| HR | 1571doc 41572 | Secondary Fans 2: Fan Economy Mode | UINT16 | Read/write | 0 = disabled; 1 = automatic; 2 = manual | ||||
| HR | 1697doc 41698 | Secondary Fans 20: Fan Economy Mode | UINT16 | Read/write | 0 = disabled; 1 = automatic; 2 = manual |
Notes on this map
- Source: Emerson Network Power / Liebert reference guide SL-28170 (Rev 9). Vertiv does not host this guide publicly; the linked copy is the unaltered PDF on the Contemporary Controls support site.
- Scale column: 'x / 10' means the raw value is tenths (scale 0.1); '-' or blank means no scaling. Some temperature setpoints are printed without a scale while similar points use x / 10; they are transcribed exactly as printed.
- Most temperatures exist twice: once in deg C and once in deg F at a different register. Only the deg C registers are listed here.
- Points that the guide lists with both an input register (3xxxx) and a holding register (4xxxx) are the writable settings; we list the holding register (read/write). The same value can also be read at the matching 3xxxx input register (same offset).
- Signedness is not stated in the guide. Temperature values are listed as INT16 (they can be below zero); everything else as UINT16.
- Points that take two registers (date/time and schedule start/stop times, 32-bit values) are left out because the guide does not state their word order.
- Event/alarm discrete inputs read 1 while the event is active ('Active on Alarm').
- The 'SFA' rows in the guide (reserved/special-function points, including discrete inputs 18000-18024) are left out.
Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.
Questions about the Vertiv Liebert XDC refrigerant chiller for XD systems with iCOM v4 (IntelliSlot Modbus)
What Modbus registers does the Vertiv Liebert XDC refrigerant chiller for XD systems with iCOM v4 (IntelliSlot Modbus) have?
This map lists 221 registers: 62 discrete inputs, 100 input registers, 59 holding registers. 59 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.
Are the Vertiv Liebert XDC refrigerant chiller for XD systems with iCOM v4 (IntelliSlot Modbus) Modbus addresses 0-based or 1-based?
The manufacturer's document numbers registers Modicon 3xxxx/4xxxx (drop the prefix, subtract 1). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. The guide prints Modicon-style numbers: discrete inputs 1xxxx, input registers 3xxxx, holding registers 4xxxx. Its RTU example asks for holding register 40051 with start offset 50 (0x0032), so subtract 10001 / 30001 / 40001 to get the wire address. Coils are printed as plain numbers on the same scale as the discrete inputs (coil 25 sits beside status 10025), so coil n is wire address n-1.
What are the minimum Modbus registers to integrate the Vertiv Liebert XDC refrigerant chiller for XD systems with iCOM v4 (IntelliSlot Modbus)?
Start with HR 425 System Information: System On/Off Control (System on/off control); IR 388 System Information: System Operating State (System operating state); IR 421 System Information: System Status (System status); IR 386 Supply Refrigerant Temperature (Supply refrigerant temperature); IR 399 External Air: Dew Point Temperature (Dew point temperature); IR 384 Pump 1 State (Pump 1 state); IR 415 Compressor 1A State (Compressor 1A state); IR 448 XD System 1: Cooling Capacity (XD system 1 cooling capacity).
How do I enable Modbus control of the Vertiv Liebert XDC refrigerant chiller for XD systems with iCOM v4 (IntelliSlot Modbus)?
Fit the Liebert IntelliSlot card the guide lists for the unit's controller (for iCOM v4 units: IS-485L for Modbus 485, IS-IPBML for Modbus IP / BACnet IP) and set its Modbus address and line speed on the card.
Where is the official Vertiv Liebert XDC refrigerant chiller for XD systems with iCOM v4 (IntelliSlot Modbus) Modbus documentation?
The source is Liebert IntelliSlot Modbus 485, Modbus IP and BACnet IP Reference Guide (SL-28170 Rev 9), revision 10-12 (printed as SL-28170_REV9_10-12). Vertiv doesn't publish it on its own website, so this map was re-typed from a free copy at https://ccontrols.com/support/dp/Liebert.pdf. It may be an older revision, so check it against the live unit.
More Vertiv Modbus register maps
- Sensor (battery monitoring system)
Vertiv (Alber) Alber MPM-100 and BDS series battery monitors (Modbus ASCII)
Alber MPM-100 (firmware 1.20+) and BDS series (controller firmware 2.20+) battery monitors with BMDM software 4.10+, per protocol document SL-29417 Rev 7.05.
Also known as: Alber MPM-100, Alber BDS, BDS-40, BDS40, MPM100, Vertiv Alber battery monitor, SL-29417 - Air handler (in-row computer room cooling unit)
Vertiv Liebert CRV in-row cooling unit with iCOM v4 (IntelliSlot Modbus)
Liebert CRV row-based cooling units (DX and chilled water) on the iCOM v4 controller with a Liebert IntelliSlot Modbus 485 or Modbus IP card.
Also known as: Liebert CRV, CRV, Liebert CRV iCOM - Air handler (computer room air conditioner)
Vertiv Liebert DS / CW / HPM / PeX / Challenger with iCOM v4 (IntelliSlot Modbus)
Liebert perimeter precision cooling units on the iCOM v4 controller (Challenger 3000, Challenger ITR, CW, Deluxe System/3, DS, PeX with iCOM firmware PA1.04.033.STD or later; HPM with iCOM), read through a Liebert IntelliSlot Modbus 485 or Modbus IP card.
Also known as: Liebert DS, Liebert CW, Liebert HPM, Liebert PeX, Liebert Challenger 3000, Liebert Challenger ITR, Liebert Deluxe System/3, Liebert iCOM v4, IS-485L, IS-IPBML - Chiller (air-cooled chiller for data centres)
Vertiv Liebert HPC chiller with iCOM v4 (IntelliSlot Modbus)
Liebert HPC chillers on the iCOM v4 controller (iCOM_SC31 / iCOM_SC100 applications) with a Liebert IntelliSlot Modbus card.
Also known as: Liebert HPC, HPC chiller, Liebert HPC iCOM - Pump (refrigerant pumping unit for Liebert XD rack cooling)
Vertiv Liebert XDP pumping unit for XD systems with iCOM v4 (IntelliSlot Modbus)
Liebert XDP pumping units on the iCOM v4 controller with a Liebert IntelliSlot Modbus card.
Also known as: Liebert XDP, XDP, Liebert XD pumping unit
Other chillers & heat pumps register maps
- Chiller (water-cooled, magnetic-bearing centrifugal)
Daikin Applied Magnitude WME magnetic-bearing chiller (MicroTech, Modbus)
Magnitude WME C- and D-vintage and WME-C QUAD chillers with the MicroTech unit controller and Modbus communication module, per ED 19111-4.
Also known as: WME-C, WME-D, WME-C QUAD, Magnitude WME, Daikin WME - Chiller
Daikin Applied Trailblazer AGZ-D / AGZ-E air-cooled scroll chiller (MicroTech controller)
Daikin Applied Trailblazer AGZ-D and AGZ-E air-cooled scroll chillers with the MicroTech chiller unit controller and Modbus communication module, per ED 15121-13.
Also known as: AGZ-D, AGZ-E, AGZ D-Vintage, AGZ E-Vintage, ED 15121, Trailblazer AGZ-D, Trailblazer AGZ-E - Chiller
Trane CenTraVac duplex centrifugal chiller (Symbio 800)
Trane dual-compressor (duplex) CenTraVac water-cooled centrifugal chillers fitted with the Symbio 800 controller, as listed in the Duplex tables of BAS-PTS009C-EN (12/12/2025).
Also known as: CDHF, CDHG, CDHH, CenTraVac Duplex Symbio 800 - Chiller
Trane Sintesis RTAF air-cooled screw chiller (Symbio 800)
Trane Sintesis RTAF air-cooled helical-rotary chillers with the Symbio 800 controller, as listed in BAS-PTS013B-EN (4/7/2026).
Also known as: RTAF, Sintesis RTAF, Sintesis air-cooled chiller - Chiller (water-cooled)
Daikin Applied EWWD-VZ / EWWH-VZ / EWWS-VZ water-cooled inverter screw chillers (Microtech, Adam software)
EWWD-VZ, EWWH-VZ and EWWS-VZ water-cooled inverter screw chillers with Microtech III or Microtech 4 controller running Adam software, per D-EIGOC00201-22_03EN.
Also known as: EWWD-VZ, EWWH-VZ, EWWS-VZ, EWWD(H)(S)_VZ, EWWD~VZ, EWWH~VZ, Daikin EWWD VZ, Adam - Chiller
Daikin Applied Navigator WWV / TWV water-cooled screw chiller (MicroTech controller)
Daikin Applied Navigator WWV and TWV water-cooled screw chillers with the MicroTech chiller unit controller and Modbus communication module, per ED 15121-13.
Also known as: WWV, TWV, Navigator WWV, Navigator TWV, Daikin Navigator, ED 15121
All chillers & heat pumps Modbus register maps →
Source: Liebert IntelliSlot Modbus 485, Modbus IP and BACnet IP Reference Guide · SL-28170 Rev 9 · rev. 10-12 (printed as SL-28170_REV9_10-12) · unofficial copy. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.