Chiller (refrigerant chiller for Liebert XD rack cooling) · Modbus register map

Vertiv Liebert XDC refrigerant chiller for XD systems with iCOM v4 (IntelliSlot Modbus) Modbus register map

Updated 19 November 2026

Short answer

The Liebert XDC supplies pumped refrigerant to Liebert XD cooling modules. With a Liebert IntelliSlot Modbus card its iCOM controller exposes system on/off and status, pump and compressor states, supply refrigerant and external air temperatures, dew point, thresholds, per-XD-system fan, capacity and remote sensor values, and alarm bits.

This page lists 221 Modbus registers for the Vertiv Liebert XDC refrigerant chiller for XD systems with iCOM v4 (IntelliSlot Modbus) — 59 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Vertiv’s own free documentation (linked below) and checked against it.

Manufacturer
Vertiv
Model
Liebert XDC refrigerant chiller for XD systems with iCOM v4 (IntelliSlot Modbus)
Equipment type
Chiller (refrigerant chiller for Liebert XD rack cooling)
Registers
221 (59 writable)
Transport
Modbus RTU, Modbus TCP
Default unit ID
Not stated
Default serial
8N1
Documented addressing
Modicon 3xxxx/4xxxx (drop the prefix, subtract 1)
Also known as
Liebert XDC, XDC, Liebert XD chiller
Source document
Liebert IntelliSlot Modbus 485, Modbus IP and BACnet IP Reference Guide · SL-28170 Rev 9 · rev. 10-12 (printed as SL-28170_REV9_10-12) · unofficial copy
Download CSV all columns JSON Manufacturer PDF ↗

Integration notes: Vertiv Liebert XDC refrigerant chiller for XD systems with iCOM v4 (IntelliSlot Modbus)

Integration in brief

Read 30385-30424 for pumps, compressors, refrigerant and air temperatures and status; write 40426 to switch the XDC on/off. Per-XD-system data starts at 30444 / 40445 for system 1.

Minimum registers to map

Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.

RegisterNameTypeWhyAccess
HR 425System Information: System On/Off ControlUINT16System on/off controlRead/write
IR 388System Information: System Operating StateUINT16System operating stateRead
IR 421System Information: System StatusUINT16System statusRead
IR 386Supply Refrigerant TemperatureINT16Supply refrigerant temperatureRead
IR 399External Air: Dew Point TemperatureINT16Dew point temperatureRead
IR 384Pump 1 StateUINT16Pump 1 stateRead
IR 415Compressor 1A StateUINT16Compressor 1A stateRead
IR 448XD System 1: Cooling CapacityUINT16XD system 1 cooling capacityRead

Enable Modbus control & writes

Fit the Liebert IntelliSlot card the guide lists for the unit's controller (for iCOM v4 units: IS-485L for Modbus 485, IS-IPBML for Modbus IP / BACnet IP) and set its Modbus address and line speed on the card.

Byte order & addressing

Network setup

Watch out for

Vertiv Liebert XDC refrigerant chiller for XD systems with iCOM v4 (IntelliSlot Modbus) Modbus registers

Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.

221 of 221 shown
Vertiv Liebert XDC refrigerant chiller for XD systems with iCOM v4 (IntelliSlot Modbus) Modbus register map
TableAddressNameDescriptionTypeOrderScaleUnitsAccessValues / bits
DI0doc 10001Pump 1 Loss of FlowBITRead0 = Inactive; 1 = Active
DI1doc 10002Pump 2 Loss of FlowBITRead0 = Inactive; 1 = Active
DI2doc 10003System Events: Fan IssueBITRead0 = Inactive; 1 = Active
DI3doc 10004System Events: System Condensation DetectedBITRead0 = Inactive; 1 = Active
DI4doc 10005System Events: Customer Input 1BITRead0 = Inactive; 1 = Active
DI5doc 10006Refridgerant: Supply Refrigerant Over TempBITRead0 = Inactive; 1 = Active
DI6doc 10007Refridgerant: Supply Refrigerant Under TempBITRead0 = Inactive; 1 = Active
DI7doc 10008Refridgerant: Supply Refrigerant Temp Sensor IssueBITRead0 = Inactive; 1 = Active
DI8doc 10009External Air: Ext Air Sensor A Over TemperatureBITRead0 = Inactive; 1 = Active
DI9doc 10010External Air: Ext Air Sensor A Under TemperatureBITRead0 = Inactive; 1 = Active
DI10doc 10011External Air: Ext Air Sensor A IssueBITRead0 = Inactive; 1 = Active
DI11doc 10012External Air: Ext Air Sensor B Over TemperatureBITRead0 = Inactive; 1 = Active
DI12doc 10013External Air: Ext Air Sensor B Under TemperatureBITRead0 = Inactive; 1 = Active
DI13doc 10014External Air: Ext Air Sensor B IssueBITRead0 = Inactive; 1 = Active
DI14doc 10015External Air: Ext Dew Point Over TemperatureBITRead0 = Inactive; 1 = Active
DI15doc 10016Pump Short CycleBITRead0 = Inactive; 1 = Active
DI16doc 10017Compressor 1A High Head PressureBITRead0 = Inactive; 1 = Active
DI17doc 10018Compressor 1B High Head PressureBITRead0 = Inactive; 1 = Active
DI18doc 10019Compressor 2A High Head PressureBITRead0 = Inactive; 1 = Active
DI19doc 10020Compressor 2B High Head PressureBITRead0 = Inactive; 1 = Active
DI20doc 10021Compressor 1A Short CycleBITRead0 = Inactive; 1 = Active
DI21doc 10022Compressor 1B Short CycleBITRead0 = Inactive; 1 = Active
DI22doc 10023Compressor 2A Short CycleBITRead0 = Inactive; 1 = Active
DI23doc 10024Compressor 2B Short CycleBITRead0 = Inactive; 1 = Active
DI24doc 10025Compressor: Circuit 1 Low Suction PressureBITRead0 = Inactive; 1 = Active
DI25doc 10026Compressor: Circuit 2 Low Suction PressureBITRead0 = Inactive; 1 = Active
DI26doc 10027System Events: Shutdown - Loss Of PowerBITRead0 = Inactive; 1 = Active
DI27doc 10028System Events: Smoke DetectedBITRead0 = Inactive; 1 = Active
DI28doc 10029System Events: Water Under FloorBITRead0 = Inactive; 1 = Active
DI29doc 10030System Events: Service RequiredBITRead0 = Inactive; 1 = Active
DI39doc 10040Pump Hours 1: Pump Hours ExceededBITRead0 = Inactive; 1 = Active
DI45doc 10046Pump Hours 2: Pump Hours ExceededBITRead0 = Inactive; 1 = Active
DI51doc 10052XD System 1: Ext System Condensation DetectedBITRead0 = Inactive; 1 = Active
DI52doc 10053XD System 1: Ext Fan IssueBITRead0 = Inactive; 1 = Active
DI53doc 10054XD System 1: Sensor IssueBITRead0 = Inactive; 1 = Active
DI54doc 10055XD System 1: Ext Remote ShutdownBITRead0 = Inactive; 1 = Active
DI55doc 10056XD System 1: Hot Aisle Temp Out of RangeBITRead0 = Inactive; 1 = Active
DI56doc 10057XD System 1: Cold Aisle Temp Out of RangeBITRead0 = Inactive; 1 = Active
DI62doc 10063XD System 2: Ext System Condensation DetectedBITRead0 = Inactive; 1 = Active
DI63doc 10064XD System 2: Ext Fan IssueBITRead0 = Inactive; 1 = Active
DI64doc 10065XD System 2: Sensor IssueBITRead0 = Inactive; 1 = Active
DI65doc 10066XD System 2: Ext Remote ShutdownBITRead0 = Inactive; 1 = Active
DI66doc 10067XD System 2: Hot Aisle Temp Out of RangeBITRead0 = Inactive; 1 = Active
DI67doc 10068XD System 2: Cold Aisle Temp Out of RangeBITRead0 = Inactive; 1 = Active
DI260doc 10261XD System 20: Ext System Condensation DetectedBITRead0 = Inactive; 1 = Active
DI261doc 10262XD System 20: Ext Fan IssueBITRead0 = Inactive; 1 = Active
DI262doc 10263XD System 20: Sensor IssueBITRead0 = Inactive; 1 = Active
DI263doc 10264XD System 20: Ext Remote ShutdownBITRead0 = Inactive; 1 = Active
DI264doc 10265XD System 20: Hot Aisle Temp Out of RangeBITRead0 = Inactive; 1 = Active
DI265doc 10266XD System 20: Cold Aisle Temp Out of RangeBITRead0 = Inactive; 1 = Active
DI271doc 10272System Events: Unit Communication LostBITRead0 = Inactive; 1 = Active
DI272doc 10273System Events: RAM Battery IssueBITRead0 = Inactive; 1 = Active
DI273doc 10274System Events: Master Unit Communication LostBITRead0 = Inactive; 1 = Active
DI274doc 10275System Events: Remote ShutdownBITRead0 = Inactive; 1 = Active
DI275doc 10276System Events: Unit Code MissingBITRead0 = Inactive; 1 = Active
DI281doc 10282Messages: Unit OnBITRead0 = Inactive; 1 = Active
DI282doc 10283Messages: Unit OffBITRead0 = Inactive; 1 = Active
DI283doc 10284Messages: Unit StandbyBITRead0 = Inactive; 1 = Active
DI284doc 10285Messages: Unit Partial ShutdownBITRead0 = Inactive; 1 = Active
DI285doc 10286Messages: Unit ShutdownBITRead0 = Inactive; 1 = Active
DI286doc 10287Messages: Maintenance DueBITRead0 = Inactive; 1 = Active
DI287doc 10288Messages: Maintenance CompletedBITRead0 = Inactive; 1 = Active
IR384doc 30385Pump 1 StateUINT16Read0 = Off; 1 = On
IR385doc 30386Pump 2 StateUINT16Read0 = Off; 1 = On
IR386doc 30387Supply Refrigerant TemperatureINT16× 0.1deg CRead
IR388doc 30389System Information: System Operating StateUINT16Read0 = Off; 1 = On; 2 = Standby
IR389doc 30390External Air: Ext Air Sensor A TemperatureINT16× 0.1deg CRead
IR391doc 30392External Air: Ext Air Sensor A HumidityUINT16× 0.1% RHRead
IR392doc 30393External Air: Ext Air Sensor A Dew Point TempINT16× 0.1deg CRead
IR394doc 30395External Air: Ext Air Sensor B TemperatureINT16× 0.1deg CRead
IR396doc 30397External Air: Ext Air Sensor B HumidityUINT16× 0.1% RHRead
IR397doc 30398External Air: Ext Air Sensor B Dew Point TempINT16× 0.1deg CRead
IR399doc 30400External Air: Dew Point TemperatureINT16× 0.1deg CRead
IR411doc 30412Hot Gas Valve 1 Open PositionUINT16× 0.1%Read
IR412doc 30413Hot Gas Valve 2 Open PositionUINT16× 0.1%Read
IR413doc 30414Hot Gas Solenoid Valve 1 PositionUINT16Read0 = closed; 1 = open
IR414doc 30415Hot Gas Solenoid Valve 2 PositionUINT16Read0 = closed; 1 = open
IR415doc 30416Compressor 1A StateUINT16Read0 = off; 1 = on
IR416doc 30417Compressor 1B StateUINT16Read0 = off; 1 = on
IR417doc 30418Compressor 2A StateUINT16Read0 = off; 1 = on
IR418doc 30419Compressor 2B StateUINT16Read0 = off; 1 = on
IR419doc 30420System Information: Calculated Next Maintenance MonthUINT16Read
IR420doc 30421System Information: Calculated Next Maintenance YearUINT16Read
IR421doc 30422System Information: System StatusUINT16Read1 = Normal Operation; 2 = StartUp; 8 = Normal with Warning; 16 = Normal with Alarm; 32 = Abnormal Operation
IR422doc 30423System Information: System Control ModeUINT16Read0 = Internal (Auto); 1 = External (Manual)
IR423doc 30424System Information: Maintenance RampUINT16%Read
IR443doc 30444XD System 1: Communication StatusUINT16Read0 = Connected; 1 = Not Connected
IR445doc 30446XD System 1: Primary Fan Group StateUINT16Read0 = off; 1 = on; 2 = economy
IR448doc 30449XD System 1: Cooling CapacityUINT16%Read
IR449doc 30450XD System 1: Cooling CapacityUINT16kWRead
IR471doc 30472XD System 2: Communication StatusUINT16Read0 = Connected; 1 = Not Connected
IR473doc 30474XD System 2: Primary Fan Group StateUINT16Read0 = off; 1 = on; 2 = economy
IR476doc 30477XD System 2: Cooling CapacityUINT16%Read
IR477doc 30478XD System 2: Cooling CapacityUINT16kWRead
IR975doc 30976XD System 20: Communication StatusUINT16Read0 = Connected; 1 = Not Connected
IR977doc 30978XD System 20: Primary Fan Group StateUINT16Read0 = off; 1 = on; 2 = economy
IR980doc 30981XD System 20: Cooling CapacityUINT16%Read
IR981doc 30982XD System 20: Cooling CapacityUINT16kWRead
IR1003doc 31004XD System 1 Temperature Sensor 1: Remote Sensor TemperatureINT16× 0.1deg CRead
IR1010doc 31011XD System 1 Temperature Sensor 2: Remote Sensor TemperatureINT16× 0.1deg CRead
IR1024doc 31025XD System 1 Temperature Sensor 4: Remote Sensor TemperatureINT16× 0.1deg CRead
IR1031doc 31032XD System 2 Temperature Sensor 1: Remote Sensor TemperatureINT16× 0.1deg CRead
IR1038doc 31039XD System 2 Temperature Sensor 2: Remote Sensor TemperatureINT16× 0.1deg CRead
IR1052doc 31053XD System 2 Temperature Sensor 4: Remote Sensor TemperatureINT16× 0.1deg CRead
IR1059doc 31060XD System 3 Temperature Sensor 1: Remote Sensor TemperatureINT16× 0.1deg CRead
IR1066doc 31067XD System 3 Temperature Sensor 2: Remote Sensor TemperatureINT16× 0.1deg CRead
IR1080doc 31081XD System 3 Temperature Sensor 4: Remote Sensor TemperatureINT16× 0.1deg CRead
IR1087doc 31088XD System 4 Temperature Sensor 1: Remote Sensor TemperatureINT16× 0.1deg CRead
IR1094doc 31095XD System 4 Temperature Sensor 2: Remote Sensor TemperatureINT16× 0.1deg CRead
IR1108doc 31109XD System 4 Temperature Sensor 4: Remote Sensor TemperatureINT16× 0.1deg CRead
IR1115doc 31116XD System 5 Temperature Sensor 1: Remote Sensor TemperatureINT16× 0.1deg CRead
IR1122doc 31123XD System 5 Temperature Sensor 2: Remote Sensor TemperatureINT16× 0.1deg CRead
IR1136doc 31137XD System 5 Temperature Sensor 4: Remote Sensor TemperatureINT16× 0.1deg CRead
IR1143doc 31144XD System 6 Temperature Sensor 1: Remote Sensor TemperatureINT16× 0.1deg CRead
IR1150doc 31151XD System 6 Temperature Sensor 2: Remote Sensor TemperatureINT16× 0.1deg CRead
IR1164doc 31165XD System 6 Temperature Sensor 4: Remote Sensor TemperatureINT16× 0.1deg CRead
IR1171doc 31172XD System 7 Temperature Sensor 1: Remote Sensor TemperatureINT16× 0.1deg CRead
IR1178doc 31179XD System 7 Temperature Sensor 2: Remote Sensor TemperatureINT16× 0.1deg CRead
IR1192doc 31193XD System 7 Temperature Sensor 4: Remote Sensor TemperatureINT16× 0.1deg CRead
IR1199doc 31200XD System 8 Temperature Sensor 1: Remote Sensor TemperatureINT16× 0.1deg CRead
IR1206doc 31207XD System 8 Temperature Sensor 2: Remote Sensor TemperatureINT16× 0.1deg CRead
IR1220doc 31221XD System 8 Temperature Sensor 4: Remote Sensor TemperatureINT16× 0.1deg CRead
IR1227doc 31228XD System 9 Temperature Sensor 1: Remote Sensor TemperatureINT16× 0.1deg CRead
IR1234doc 31235XD System 9 Temperature Sensor 2: Remote Sensor TemperatureINT16× 0.1deg CRead
IR1248doc 31249XD System 9 Temperature Sensor 4: Remote Sensor TemperatureINT16× 0.1deg CRead
IR1255doc 31256XD System 10 Temperature Sensor 1: Remote Sensor TemperatureINT16× 0.1deg CRead
IR1262doc 31263XD System 10 Temperature Sensor 2: Remote Sensor TemperatureINT16× 0.1deg CRead
IR1276doc 31277XD System 10 Temperature Sensor 4: Remote Sensor TemperatureINT16× 0.1deg CRead
IR1283doc 31284XD System 11 Temperature Sensor 1: Remote Sensor TemperatureINT16× 0.1deg CRead
IR1290doc 31291XD System 11 Temperature Sensor 2: Remote Sensor TemperatureINT16× 0.1deg CRead
IR1304doc 31305XD System 11 Temperature Sensor 4: Remote Sensor TemperatureINT16× 0.1deg CRead
IR1311doc 31312XD System 12 Temperature Sensor 1: Remote Sensor TemperatureINT16× 0.1deg CRead
IR1318doc 31319XD System 12 Temperature Sensor 2: Remote Sensor TemperatureINT16× 0.1deg CRead
IR1332doc 31333XD System 12 Temperature Sensor 4: Remote Sensor TemperatureINT16× 0.1deg CRead
IR1339doc 31340XD System 13 Temperature Sensor 1: Remote Sensor TemperatureINT16× 0.1deg CRead
IR1346doc 31347XD System 13 Temperature Sensor 2: Remote Sensor TemperatureINT16× 0.1deg CRead
IR1360doc 31361XD System 13 Temperature Sensor 4: Remote Sensor TemperatureINT16× 0.1deg CRead
IR1367doc 31368XD System 14 Temperature Sensor 1: Remote Sensor TemperatureINT16× 0.1deg CRead
IR1374doc 31375XD System 14 Temperature Sensor 2: Remote Sensor TemperatureINT16× 0.1deg CRead
IR1388doc 31389XD System 14 Temperature Sensor 4: Remote Sensor TemperatureINT16× 0.1deg CRead
IR1395doc 31396XD System 15 Temperature Sensor 1: Remote Sensor TemperatureINT16× 0.1deg CRead
IR1402doc 31403XD System 15 Temperature Sensor 2: Remote Sensor TemperatureINT16× 0.1deg CRead
IR1416doc 31417XD System 15 Temperature Sensor 4: Remote Sensor TemperatureINT16× 0.1deg CRead
IR1423doc 31424XD System 16 Temperature Sensor 1: Remote Sensor TemperatureINT16× 0.1deg CRead
IR1430doc 31431XD System 16 Temperature Sensor 2: Remote Sensor TemperatureINT16× 0.1deg CRead
IR1444doc 31445XD System 16 Temperature Sensor 4: Remote Sensor TemperatureINT16× 0.1deg CRead
IR1451doc 31452XD System 17 Temperature Sensor 1: Remote Sensor TemperatureINT16× 0.1deg CRead
IR1458doc 31459XD System 17 Temperature Sensor 2: Remote Sensor TemperatureINT16× 0.1deg CRead
IR1472doc 31473XD System 17 Temperature Sensor 4: Remote Sensor TemperatureINT16× 0.1deg CRead
IR1479doc 31480XD System 18 Temperature Sensor 1: Remote Sensor TemperatureINT16× 0.1deg CRead
IR1486doc 31487XD System 18 Temperature Sensor 2: Remote Sensor TemperatureINT16× 0.1deg CRead
IR1500doc 31501XD System 18 Temperature Sensor 4: Remote Sensor TemperatureINT16× 0.1deg CRead
IR1507doc 31508XD System 19 Temperature Sensor 1: Remote Sensor TemperatureINT16× 0.1deg CRead
IR1514doc 31515XD System 19 Temperature Sensor 2: Remote Sensor TemperatureINT16× 0.1deg CRead
IR1528doc 31529XD System 19 Temperature Sensor 4: Remote Sensor TemperatureINT16× 0.1deg CRead
IR1535doc 31536XD System 20 Temperature Sensor 1: Remote Sensor TemperatureINT16× 0.1deg CRead
IR1542doc 31543XD System 20 Temperature Sensor 2: Remote Sensor TemperatureINT16× 0.1deg CRead
IR1556doc 31557XD System 20 Temperature Sensor 4: Remote Sensor TemperatureINT16× 0.1deg CRead
IR1563doc 31564Secondary Fans 1: Fan StateUINT16Read0 = off; 1 = on; 2 = economy
IR1570doc 31571Secondary Fans 2: Fan StateUINT16Read0 = off; 1 = on; 2 = economy
IR1696doc 31697Secondary Fans 20: Fan StateUINT16Read0 = off; 1 = on; 2 = economy
IR1703doc 31704System Information: System Operating State ReasonUINT16Read0 = Reason Unknown; 1 = Network Display; 2 = Alarm; 3 = Schedule; 4 = Remote System; 5 = External Input; 6 = Local Display
HR401doc 40402External Air: Minimum Room Temperature Set PointINT16× 0.1deg CRead/write
HR403doc 40404External Air: Ext Air Over Temp ThresholdINT16× 0.1deg CRead/write
HR405doc 40406External Air: Ext Air Under Temp ThresholdINT16× 0.1deg CRead/write
HR407doc 40408External Air: Ext Dew Point Over Temp ThresholdINT16× 0.1deg CRead/write
HR409doc 40410Refrigerant: Supply Refrig Over Temp ThresholdINT16× 0.1deg CRead/write
HR424doc 40425System Information: Auto Restart DelayUINT16secRead/write
HR425doc 40426System Information: System On/Off ControlUINT16Read/write0 = off; 1 = on
HR429doc 40430Pump Hours 1: Pump HoursUINT16hrRead/write
HR430doc 40431Pump Hours 1: Pump Hours ThresholdUINT16hrRead/write
HR436doc 40437Pump Hours 2: Pump HoursUINT16hrRead/write
HR437doc 40438Pump Hours 2: Pump Hours ThresholdUINT16hrRead/write
HR444doc 40445XD System 1: Fan On/Off ControlUINT16Read/write0 = off; 1 = on
HR446doc 40447XD System 1: Fan Button ControlUINT16Read/write0 = enabled; 1 = disabled
HR447doc 40448XD System 1: Visual ID ControlUINT16Read/write0 = disabled; 1 = enabled
HR450doc 40451XD System 1: Ext System Condensation Detected - Event ControlUINT16Read/write0 = disabled; 1 = enabled
HR451doc 40452XD System 1: Ext System Condensation Detected - Event TypeUINT16Read/write0 = Message; 1 = Warning; 2 = Alarm
HR452doc 40453XD System 1: Ext Fan Issue - Event ControlUINT16Read/write0 = disabled; 1 = enabled
HR453doc 40454XD System 1: Ext Fan Issue - Event TypeUINT16Read/write0 = Message; 1 = Warning; 2 = Alarm
HR454doc 40455XD System 1: Sensor Issue - Event ControlUINT16Read/write0 = disabled; 1 = enabled
HR455doc 40456XD System 1: Sensor Issue - Event TypeUINT16Read/write0 = Message; 1 = Warning; 2 = Alarm
HR456doc 40457XD System 1: Ext Remote Shutdown - Event ControlUINT16Read/write0 = disabled; 1 = enabled
HR457doc 40458XD System 1: Ext Remote Shutdown - Event TypeUINT16Read/write0 = Message; 1 = Warning; 2 = Alarm
HR458doc 40459XD System 1: Hot Aisle Over Temp ThresholdINT16deg CRead/write
HR460doc 40461XD System 1: Hot Aisle Under Temp ThresholdINT16deg CRead/write
HR462doc 40463XD System 1: Cold Aisle Over Temp ThresholdINT16deg CRead/write
HR464doc 40465XD System 1: Cold Aisle Under Temp ThresholdINT16deg CRead/write
HR472doc 40473XD System 2: Fan On/Off ControlUINT16Read/write0 = off; 1 = on
HR474doc 40475XD System 2: Fan Button ControlUINT16Read/write0 = enabled; 1 = disabled
HR475doc 40476XD System 2: Visual ID ControlUINT16Read/write0 = disabled; 1 = enabled
HR478doc 40479XD System 2: Ext System Condensation Detected - Event ControlUINT16Read/write0 = disabled; 1 = enabled
HR479doc 40480XD System 2: Ext System Condensation Detected - Event TypeUINT16Read/write0 = Message; 1 = Warning; 2 = Alarm
HR480doc 40481XD System 2: Ext Fan Issue - Event ControlUINT16Read/write0 = disabled; 1 = enabled
HR481doc 40482XD System 2: Ext Fan Issue - Event TypeUINT16Read/write0 = Message; 1 = Warning; 2 = Alarm
HR482doc 40483XD System 2: Sensor Issue - Event ControlUINT16Read/write0 = disabled; 1 = enabled
HR483doc 40484XD System 2: Sensor Issue - Event TypeUINT16Read/write0 = Message; 1 = Warning; 2 = Alarm
HR484doc 40485XD System 2: Ext Remote Shutdown - Event ControlUINT16Read/write0 = disabled; 1 = enabled
HR485doc 40486XD System 2: Ext Remote Shutdown - Event TypeUINT16Read/write0 = Message; 1 = Warning; 2 = Alarm
HR486doc 40487XD System 2: Hot Aisle Over Temp ThresholdINT16deg CRead/write
HR488doc 40489XD System 2: Hot Aisle Under Temp ThresholdINT16deg CRead/write
HR490doc 40491XD System 2: Cold Aisle Over Temp ThresholdINT16deg CRead/write
HR492doc 40493XD System 2: Cold Aisle Under Temp ThresholdINT16deg CRead/write
HR976doc 40977XD System 20: Fan On/Off ControlUINT16Read/write0 = off; 1 = on
HR978doc 40979XD System 20: Fan Button ControlUINT16Read/write0 = enabled; 1 = disabled
HR979doc 40980XD System 20: Visual ID ControlUINT16Read/write0 = disabled; 1 = enabled
HR982doc 40983XD System 20: Ext System Condensation Detected - Event ControlUINT16Read/write0 = disabled; 1 = enabled
HR983doc 40984XD System 20: Ext System Condensation Detected - Event TypeUINT16Read/write0 = Message; 1 = Warning; 2 = Alarm
HR984doc 40985XD System 20: Ext Fan Issue - Event ControlUINT16Read/write0 = disabled; 1 = enabled
HR985doc 40986XD System 20: Ext Fan Issue - Event TypeUINT16Read/write0 = Message; 1 = Warning; 2 = Alarm
HR986doc 40987XD System 20: Sensor Issue - Event ControlUINT16Read/write0 = disabled; 1 = enabled
HR987doc 40988XD System 20: Sensor Issue - Event TypeUINT16Read/write0 = Message; 1 = Warning; 2 = Alarm
HR988doc 40989XD System 20: Ext Remote Shutdown - Event ControlUINT16Read/write0 = disabled; 1 = enabled
HR989doc 40990XD System 20: Ext Remote Shutdown - Event TypeUINT16Read/write0 = Message; 1 = Warning; 2 = Alarm
HR990doc 40991XD System 20: Hot Aisle Over Temp ThresholdINT16deg CRead/write
HR992doc 40993XD System 20: Hot Aisle Under Temp ThresholdINT16deg CRead/write
HR994doc 40995XD System 20: Cold Aisle Over Temp ThresholdINT16deg CRead/write
HR996doc 40997XD System 20: Cold Aisle Under Temp ThresholdINT16deg CRead/write
HR1564doc 41565Secondary Fans 1: Fan Economy ModeUINT16Read/write0 = disabled; 1 = automatic; 2 = manual
HR1571doc 41572Secondary Fans 2: Fan Economy ModeUINT16Read/write0 = disabled; 1 = automatic; 2 = manual
HR1697doc 41698Secondary Fans 20: Fan Economy ModeUINT16Read/write0 = disabled; 1 = automatic; 2 = manual

Notes on this map

Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.

Questions about the Vertiv Liebert XDC refrigerant chiller for XD systems with iCOM v4 (IntelliSlot Modbus)

What Modbus registers does the Vertiv Liebert XDC refrigerant chiller for XD systems with iCOM v4 (IntelliSlot Modbus) have?

This map lists 221 registers: 62 discrete inputs, 100 input registers, 59 holding registers. 59 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.

Are the Vertiv Liebert XDC refrigerant chiller for XD systems with iCOM v4 (IntelliSlot Modbus) Modbus addresses 0-based or 1-based?

The manufacturer's document numbers registers Modicon 3xxxx/4xxxx (drop the prefix, subtract 1). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. The guide prints Modicon-style numbers: discrete inputs 1xxxx, input registers 3xxxx, holding registers 4xxxx. Its RTU example asks for holding register 40051 with start offset 50 (0x0032), so subtract 10001 / 30001 / 40001 to get the wire address. Coils are printed as plain numbers on the same scale as the discrete inputs (coil 25 sits beside status 10025), so coil n is wire address n-1.

What are the minimum Modbus registers to integrate the Vertiv Liebert XDC refrigerant chiller for XD systems with iCOM v4 (IntelliSlot Modbus)?

Start with HR 425 System Information: System On/Off Control (System on/off control); IR 388 System Information: System Operating State (System operating state); IR 421 System Information: System Status (System status); IR 386 Supply Refrigerant Temperature (Supply refrigerant temperature); IR 399 External Air: Dew Point Temperature (Dew point temperature); IR 384 Pump 1 State (Pump 1 state); IR 415 Compressor 1A State (Compressor 1A state); IR 448 XD System 1: Cooling Capacity (XD system 1 cooling capacity).

How do I enable Modbus control of the Vertiv Liebert XDC refrigerant chiller for XD systems with iCOM v4 (IntelliSlot Modbus)?

Fit the Liebert IntelliSlot card the guide lists for the unit's controller (for iCOM v4 units: IS-485L for Modbus 485, IS-IPBML for Modbus IP / BACnet IP) and set its Modbus address and line speed on the card.

Where is the official Vertiv Liebert XDC refrigerant chiller for XD systems with iCOM v4 (IntelliSlot Modbus) Modbus documentation?

The source is Liebert IntelliSlot Modbus 485, Modbus IP and BACnet IP Reference Guide (SL-28170 Rev 9), revision 10-12 (printed as SL-28170_REV9_10-12). Vertiv doesn't publish it on its own website, so this map was re-typed from a free copy at https://ccontrols.com/support/dp/Liebert.pdf. It may be an older revision, so check it against the live unit.

More Vertiv Modbus register maps

Other chillers & heat pumps register maps

All chillers & heat pumps Modbus register maps →

Source: Liebert IntelliSlot Modbus 485, Modbus IP and BACnet IP Reference Guide · SL-28170 Rev 9 · rev. 10-12 (printed as SL-28170_REV9_10-12) · unofficial copy. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.