Chiller · Modbus register map
Trane CenTraVac duplex centrifugal chiller (Symbio 800) Modbus register map
Updated 19 November 2026
Trane's duplex CenTraVac pairs two centrifugal compressors on separate refrigerant circuits in one water-cooled chiller. With the Symbio 800 controller it serves BACnet and Modbus RTU/TCP from one points list. This map covers analog inputs for both circuits (water temperatures and flows, refrigerant and oil pressures, purge, starter/drive and energy values), BAS setpoints, binary status points, circuit lockouts, multi-state modes and the diagnostic flags.
This page lists 717 Modbus registers for the Trane CenTraVac duplex centrifugal chiller (Symbio 800) — 17 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Trane’s own free documentation (linked below) and checked against it.
- Manufacturer
- Trane
- Model
- CenTraVac duplex centrifugal chiller (Symbio 800)
- Equipment type
- Chiller
- Registers
- 717 (17 writable)
- Transport
- Modbus RTU, Modbus TCP
- Default unit ID
- Not stated
- Default serial
- 19200 baud, 8E1
- Documented addressing
- Modicon 3xxxx/4xxxx (drop the prefix, subtract 1)
- 32-bit word order
- ABCD high word first (big-endian)
- Also known as
- CDHF, CDHG, CDHH, CenTraVac Duplex Symbio 800
Integration notes: Trane CenTraVac duplex centrifugal chiller (Symbio 800)
Read the analog inputs as pairs of input registers (float, high word first) and the binary/multi-state points as single registers. Write the BAS setpoints and command points in the 4xxxx holding range.
Minimum registers to map
Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.
| Register | Name | Type | Why | Access |
|---|---|---|---|---|
| IR 10 | Active Chilled Water Setpoint | FLOAT32 ABCD | Active chilled water setpoint | Read |
| IR 22 | Evaporator Leaving Water Temperature | FLOAT32 ABCD | Evaporator leaving water temperature | Read |
| IR 24 | Evaporator Entering Water Temperature | FLOAT32 ABCD | Evaporator entering water temperature | Read |
| IR 2010 | Running Mode | UINT16 | Running mode | Read |
| IR 3020 | Chiller Running State | UINT16 | Chiller running state | Read |
| IR 3025 | Diagnostic Present | UINT16 | Diagnostic present | Read |
| HR 10 | Chilled Water Setpoint | FLOAT32 ABCD | Chilled water setpoint (BAS) | Read/write |
| HR 2010 | Chiller Mode Command BAS | UINT16 | BAS chiller mode command | Read/write |
| HR 3014 | Chiller Auto Stop Command BAS | UINT16 | Chiller auto/stop command (BAS) | Read/write |
| HR 3011 | Reset Diagnostic | UINT16 | Reset diagnostic | Read/write |
Enable Modbus control & writes
On the Symbio 800 web interface go to Installation > Identification and Communications > Protocol Configuration and select Modbus RTU or Modbus TCP (per Trane's Symbio 800 integration guides).
Byte order & addressing
- Analog values are 32-bit floats in two consecutive registers, high word first.
- 0xFFFF in a binary or multi-state register and NaN in an analog register mean the value is invalid or not present.
Network setup
- The Modbus RTU address comes from the controller's rotary dials (1-247); address 000 disables Modbus RTU.
- Serial defaults are 19200 bps, even parity, 1 stop bit (set in the web interface's Protocol Configuration tab); wire RS-485 to the P1 link.
- Modbus TCP uses Ethernet port 1 (port 2 is reserved for the touch screen) and the IP address set on the IP Configuration tab; the rotary address is ignored for TCP and the Wi-Fi module is not supported for Modbus TCP.
Watch out for
- Points not supported by the unit's configuration are absent; confirm the configuration dependencies before mapping.
Trane CenTraVac duplex centrifugal chiller (Symbio 800) Modbus registers
Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.
| Table | Address | Name | Description | Type | Order | Scale | Units | Access | Values / bits |
|---|---|---|---|---|---|---|---|---|---|
| IR | 10doc 30011 | Active Chilled Water Setpoint | Temperature in the factory unit system (I-P or SI). | FLOAT32 | ABCD | Read | |||
| IR | 12doc 30013 | Chilled Water Setpoint Status | Temperature in the factory unit system (I-P or SI). | FLOAT32 | ABCD | Read | |||
| IR | 14doc 30015 | Active Base Loading Setpoint | Needs: Base Loading | FLOAT32 | ABCD | % | Read | ||
| IR | 16doc 30017 | Hot Water Setpoint Active | Temperature in the factory unit system (I-P or SI). Needs: Hot Water Control | FLOAT32 | ABCD | Read | |||
| IR | 18doc 30019 | Calculated Chiller Capacity | Cooling capacity in the factory unit system (I-P or SI). Needs: Evap Water Flow Sensing | FLOAT32 | ABCD | Read | |||
| IR | 20doc 30021 | Active Cool/Heat Setpoint Temperature | Temperature in the factory unit system (I-P or SI). | FLOAT32 | ABCD | Read | |||
| IR | 22doc 30023 | Evaporator Leaving Water Temperature | Temperature in the factory unit system (I-P or SI). | FLOAT32 | ABCD | Read | |||
| IR | 24doc 30025 | Evaporator Entering Water Temperature | Temperature in the factory unit system (I-P or SI). | FLOAT32 | ABCD | Read | |||
| IR | 26doc 30027 | Condenser Entering Water Temperature | Temperature in the factory unit system (I-P or SI). | FLOAT32 | ABCD | Read | |||
| IR | 28doc 30029 | Condenser Leaving Water Temperature | Temperature in the factory unit system (I-P or SI). | FLOAT32 | ABCD | Read | |||
| IR | 30doc 30031 | Evaporator Water Flow Rate | Needs: Evap Water Flow Sensing | FLOAT32 | ABCD | Read | |||
| IR | 32doc 30033 | Evaporator Differential Water Pressure | Needs: Evap Water Flow Differential Pressure or Dual Pressure Sensors | FLOAT32 | ABCD | Read | |||
| IR | 34doc 30035 | Condenser Water Flow Rate | Needs: Cond Water Flow Sensing | FLOAT32 | ABCD | Read | |||
| IR | 36doc 30037 | Condenser Differential Water Pressure | Needs: Cond Water Flow Differential Pressure or Dual Pressure Sensors | FLOAT32 | ABCD | Read | |||
| IR | 38doc 30039 | AFD Last Diagnostic Code Ckt1 | Needs: Unit Mount AFD (LF2) Remote Mount Comm AFD (PF7000) Remote Mount Comm AFD (PF6000) | FLOAT32 | ABCD | Read | |||
| IR | 40doc 30041 | Unit Source ID (Last Diagnostic Code) | FLOAT32 | ABCD | Read | ||||
| IR | 42doc 30043 | Refrigerant Monitor | Refrigerant concentration reading. Needs: Refrigerant Monitor | FLOAT32 | ABCD | Read | |||
| IR | 44doc 30045 | Evaporator Refrigerant Pressure Circuit 1 | Pressure in the factory unit system (I-P or SI). | FLOAT32 | ABCD | Read | |||
| IR | 46doc 30047 | Condenser Refrigerant Pressure Circuit 1 | Pressure in the factory unit system (I-P or SI). | FLOAT32 | ABCD | Read | |||
| IR | 48doc 30049 | Differential Refrigerant Pressure Circuit 1 | Differential pressure in the factory unit system (I-P or SI). | FLOAT32 | ABCD | Read | |||
| IR | 50doc 30051 | Low Side Oil Pressure - Compressor 1A | Pressure in the factory unit system (I-P or SI). | FLOAT32 | ABCD | Read | |||
| IR | 52doc 30053 | High Side Oil Pressure - Compressor 1A | Pressure in the factory unit system (I-P or SI). | FLOAT32 | ABCD | Read | |||
| IR | 54doc 30055 | Oil Differential Pressure Circuit 1 | Differential pressure in the factory unit system (I-P or SI). | FLOAT32 | ABCD | Read | |||
| IR | 56doc 30057 | Oil Temperature - Compressor 1A | Temperature in the factory unit system (I-P or SI). | FLOAT32 | ABCD | Read | |||
| IR | 58doc 30059 | Evaporator Saturated Refrigerant Temperature Circuit 1 | Temperature in the factory unit system (I-P or SI). | FLOAT32 | ABCD | Read | |||
| IR | 60doc 30061 | Condenser Saturated Refrigerant Temperature Circuit 1 | Temperature in the factory unit system (I-P or SI). | FLOAT32 | ABCD | Read | |||
| IR | 62doc 30063 | Refrigerant Discharge Temperature - Compressor 1A | Temperature in the factory unit system (I-P or SI). Needs: Compressor Refrigerant Discharge Temperature | FLOAT32 | ABCD | Read | |||
| IR | 64doc 30065 | Inlet Guide Vane 1 Percent Open Circuit 1 | FLOAT32 | ABCD | % | Read | |||
| IR | 66doc 30067 | Inlet Guide Vane 2 Percent Open Circuit 1 | Needs: Dual IGV | FLOAT32 | ABCD | % | Read | ||
| IR | 68doc 30069 | Purge Carbon Tank Temperature Circuit 1 | Temperature in the factory unit system (I-P or SI). Needs: Purge w/Carbon Tank | FLOAT32 | ABCD | Read | |||
| IR | 70doc 30071 | Purge Liquid Temperature Circuit 1 | Temperature in the factory unit system (I-P or SI). Needs: Purge | FLOAT32 | ABCD | Read | |||
| IR | 72doc 30073 | Purge Refrigerant Compressor Suction Temperature Circuit 1 | Temperature in the factory unit system (I-P or SI). Needs: Purge | FLOAT32 | ABCD | Read | |||
| IR | 74doc 30075 | Time Until Next Purge Run Circuit 1 (in seconds) | Needs: Purge | FLOAT32 | ABCD | s | Read | ||
| IR | 76doc 30077 | Purge Pumpout Chiller On % (7 Days) Circuit 1 | Needs: Purge | FLOAT32 | ABCD | % | Read | ||
| IR | 78doc 30079 | Purge Pumpout Chiller Off % (7 Days) Circuit 1 | Needs: Purge | FLOAT32 | ABCD | % | Read | ||
| IR | 80doc 30081 | Purge 24 Hour Pumpout Circuit 1 (in seconds) | Needs: Purge | FLOAT32 | ABCD | s | Read | ||
| IR | 82doc 30083 | Purge Pumpout - Life Circuit 1 (in seconds) | Needs: Purge | FLOAT32 | ABCD | s | Read | ||
| IR | 84doc 30085 | Refrigeration - Life Circuit 1 (in seconds) | Needs: Purge | FLOAT32 | ABCD | s | Read | ||
| IR | 86doc 30087 | Starts - Compressor 1A | FLOAT32 | ABCD | Read | ||||
| IR | 88doc 30089 | Run Time - Compressor 1A (in seconds) | FLOAT32 | ABCD | s | Read | |||
| IR | 90doc 30091 | Phase AB Voltage - Compressor 1A | Depends on starter/drive options; see the source configuration column. | FLOAT32 | ABCD | Read | |||
| IR | 92doc 30093 | Phase BC Voltage - Compressor 1A | Depends on starter/drive options; see the source configuration column. | FLOAT32 | ABCD | Read | |||
| IR | 94doc 30095 | Phase CA Voltage - Compressor 1A | Depends on starter/drive options; see the source configuration column. | FLOAT32 | ABCD | Read | |||
| IR | 96doc 30097 | Starter Average Phase Volt Circuit 1 | Depends on starter/drive options; see the source configuration column. | FLOAT32 | ABCD | Read | |||
| IR | 98doc 30099 | Line 1 Current - Compressor 1A | Depends on starter/drive options; see the source configuration column. | FLOAT32 | ABCD | Read | |||
| IR | 100doc 30101 | Line 2 Current - Compressor 1A | Depends on starter/drive options; see the source configuration column. | FLOAT32 | ABCD | Read | |||
| IR | 102doc 30103 | Line 3 Current - Compressor 1A | Depends on starter/drive options; see the source configuration column. | FLOAT32 | ABCD | Read | |||
| IR | 104doc 30105 | Average Line Current Circuit 1 | Depends on starter/drive options; see the source configuration column. | FLOAT32 | ABCD | Read | |||
| IR | 106doc 30107 | Line 1 Current RLA - Compressor 1A | Depends on starter/drive options; see the source configuration column. | FLOAT32 | ABCD | % | Read | ||
| IR | 108doc 30109 | Line 2 Current RLA - Compressor 1A | Depends on starter/drive options; see the source configuration column. | FLOAT32 | ABCD | % | Read | ||
| IR | 110doc 30111 | Line 3 Current RLA - Compressor 1A | Depends on starter/drive options; see the source configuration column. | FLOAT32 | ABCD | % | Read | ||
| IR | 112doc 30113 | Actual Running Capacity | Depends on starter/drive options; see the source configuration column. | FLOAT32 | ABCD | % | Read | ||
| IR | 116doc 30117 | Starter Load Power Factor - Compressor 1A | Depends on starter/drive options; see the source configuration column. | FLOAT32 | ABCD | Read | |||
| IR | 118doc 30119 | Inboard Bearing Temperature Circuit 1 | Temperature in the factory unit system (I-P or SI). Needs: Bearing Temperature Sensor | FLOAT32 | ABCD | Read | |||
| IR | 120doc 30121 | Outboard Bearing Temperature Circuit 1 | Temperature in the factory unit system (I-P or SI). Needs: Bearing Temperature Sensor | FLOAT32 | ABCD | Read | |||
| IR | 122doc 30123 | Motor Winding Temperature 1 Circuit 1 | Temperature in the factory unit system (I-P or SI). | FLOAT32 | ABCD | Read | |||
| IR | 124doc 30125 | Motor Winding Temperature 2 Circuit 1 | Temperature in the factory unit system (I-P or SI). | FLOAT32 | ABCD | Read | |||
| IR | 126doc 30127 | Motor Winding Temperature 3 Circuit 1 | Temperature in the factory unit system (I-P or SI). | FLOAT32 | ABCD | Read | |||
| IR | 128doc 30129 | AFD Frequency Circuit 1 | Depends on starter/drive options; see the source configuration column. | FLOAT32 | ABCD | Read | |||
| IR | 130doc 30131 | AFD Transistor Temperature Circuit 1 | Depends on starter/drive options; see the source configuration column. | FLOAT32 | ABCD | Read | |||
| IR | 132doc 30133 | Drive Average Line Current Circuit 1 | Depends on starter/drive options; see the source configuration column. | FLOAT32 | ABCD | Read | |||
| IR | 134doc 30135 | Drive Line Frequency Circuit 1 | Depends on starter/drive options; see the source configuration column. | FLOAT32 | ABCD | Read | |||
| IR | 136doc 30137 | Drive Motor Voltage Circuit 1 | Depends on starter/drive options; see the source configuration column. | FLOAT32 | ABCD | Read | |||
| IR | 138doc 30139 | Drive Inverter Base Temperature Circuit 1 | Needs: Unit Mount AFD (LF2) w/Line Side Items Remote Mount Comm AFD (PF7000) w/Line Side Items | FLOAT32 | ABCD | Read | |||
| IR | 140doc 30141 | Drive Rectifier Base Temperature Circuit 1 | Needs: Unit Mount AFD (LF2) w/Line Side Items Remote Mount Comm AFD (PF7000) w/Line Side Items | FLOAT32 | ABCD | Read | |||
| IR | 142doc 30143 | Drive Output Power Circuit 1 | Depends on starter/drive options; see the source configuration column. | FLOAT32 | ABCD | Read | |||
| IR | 144doc 30145 | Frequency Command Circuit 1 | Depends on starter/drive options; see the source configuration column. | FLOAT32 | ABCD | Read | |||
| IR | 146doc 30147 | Outboard Bearing Pad Temperature #1 Ckt1 | Temperature in the factory unit system (I-P or SI). Needs: CDHH | FLOAT32 | ABCD | Read | |||
| IR | 148doc 30149 | Outboard Bearing Pad Temperature #2 Ckt1 | Temperature in the factory unit system (I-P or SI). Needs: CDHH | FLOAT32 | ABCD | Read | |||
| IR | 150doc 30151 | Outboard Bearing Pad Temperature #3 Ckt1 | Temperature in the factory unit system (I-P or SI). Needs: CDHH | FLOAT32 | ABCD | Read | |||
| IR | 152doc 30153 | Restart Inhibit Time Remaining Circuit 1 | FLOAT32 | ABCD | Read | ||||
| IR | 154doc 30155 | Chiller Design Capacity | Cooling capacity in the factory unit system (I-P or SI). | FLOAT32 | ABCD | Read | |||
| IR | 156doc 30157 | Entering Condenser Water Pressure | Pressure in the factory unit system (I-P or SI). Needs: Condenser Water Flow Differential Pressure Sensors | FLOAT32 | ABCD | Read | |||
| IR | 158doc 30159 | Entering Evaporator Water Pressure | Pressure in the factory unit system (I-P or SI). Needs: Evaporator Water Flow Differential Pressure Sensors | FLOAT32 | ABCD | Read | |||
| IR | 160doc 30161 | Leaving Condenser Water Pressure | Pressure in the factory unit system (I-P or SI). Needs: Condenser Water Flow Differential Pressure Sensors | FLOAT32 | ABCD | Read | |||
| IR | 162doc 30163 | Leaving Evaporator Water Pressure | Pressure in the factory unit system (I-P or SI). Needs: Evaporator Water Flow Differential Pressure Sensors | FLOAT32 | ABCD | Read | |||
| IR | 164doc 30165 | Condenser Approach Temperature Circuit 1 | Temperature difference, factory unit system (I-P or SI). | FLOAT32 | ABCD | Read | |||
| IR | 166doc 30167 | Evaporator Approach Temperature Circuit 1 | Temperature difference, factory unit system (I-P or SI). | FLOAT32 | ABCD | Read | |||
| IR | 168doc 30169 | Drive DC Bus Voltage Circuit 1 | Depends on starter/drive options; see the source configuration column. | FLOAT32 | ABCD | Read | |||
| IR | 170doc 30171 | Drive Motor Average Current RLA Circuit 1 | Depends on starter/drive options; see the source configuration column. | FLOAT32 | ABCD | % | Read | ||
| IR | 174doc 30175 | Active Demand Limit Setpoint | Needs: Ice Building | FLOAT32 | ABCD | % | Read | ||
| IR | 176doc 30177 | Active Demand Limit Setpoint | Needs: Not Ice Building | FLOAT32 | ABCD | % | Read | ||
| IR | 178doc 30179 | Demand Limit Setpoint Status | Needs: Ice Building | FLOAT32 | ABCD | % | Read | ||
| IR | 180doc 30181 | Number of Circuits | FLOAT32 | ABCD | Read | ||||
| IR | 182doc 30183 | Number of Compressors Circuit 1 | FLOAT32 | ABCD | Read | ||||
| IR | 184doc 30185 | Number of Compressors Circuit 2 | FLOAT32 | ABCD | Read | ||||
| IR | 186doc 30187 | Low Side Oil Pressure - Compressor 2A | Pressure in the factory unit system (I-P or SI). | FLOAT32 | ABCD | Read | |||
| IR | 188doc 30189 | High Side Oil Pressure - Compressor 2A | Pressure in the factory unit system (I-P or SI). | FLOAT32 | ABCD | Read | |||
| IR | 190doc 30191 | Oil Differential Pressure Circuit 2 | Differential pressure in the factory unit system (I-P or SI). | FLOAT32 | ABCD | Read | |||
| IR | 192doc 30193 | Oil Temperature - Compressor 2A | Temperature in the factory unit system (I-P or SI). | FLOAT32 | ABCD | Read | |||
| IR | 194doc 30195 | Evaporator Saturated Refrigerant Temperature Circuit 2 | Temperature in the factory unit system (I-P or SI). | FLOAT32 | ABCD | Read | |||
| IR | 196doc 30197 | Condenser Saturated Refrigerant Temperature Circuit 2 | Temperature in the factory unit system (I-P or SI). | FLOAT32 | ABCD | Read | |||
| IR | 198doc 30199 | Refrigerant Discharge Temperature - Compressor 2A | Temperature in the factory unit system (I-P or SI). Needs: Compressor Refrigerant Discharge Temperature | FLOAT32 | ABCD | Read | |||
| IR | 200doc 30201 | Inlet Guide Vane 1 Percent Open Circuit 2 | FLOAT32 | ABCD | % | Read | |||
| IR | 202doc 30203 | Inlet Guide Vane 2 Percent Open Circuit 2 | Needs: IGV2 | FLOAT32 | ABCD | % | Read | ||
| IR | 204doc 30205 | Purge Carbon Tank Temperature Circuit 2 | Temperature in the factory unit system (I-P or SI). Needs: Purge w/Carbon Tank | FLOAT32 | ABCD | Read | |||
| IR | 206doc 30207 | Purge Liquid Temperature Circuit 2 | Temperature in the factory unit system (I-P or SI). Needs: Purge | FLOAT32 | ABCD | Read | |||
| IR | 208doc 30209 | Purge Refrigerant Compressor Suction Temperature Circuit 2 | Temperature in the factory unit system (I-P or SI). Needs: Purge | FLOAT32 | ABCD | Read | |||
| IR | 210doc 30211 | Time Until Next Purge Run Circuit 2 (in seconds) | Needs: Purge | FLOAT32 | ABCD | s | Read | ||
| IR | 212doc 30213 | Refrigeration - Life Circuit 2 (in seconds) | Needs: Purge | FLOAT32 | ABCD | s | Read | ||
| IR | 214doc 30215 | Starts - Compressor 2A | FLOAT32 | ABCD | Read | ||||
| IR | 216doc 30217 | Run Time - Compressor 2A (in seconds) | FLOAT32 | ABCD | s | Read | |||
| IR | 218doc 30219 | Starter Average Phase Volt Circuit 2 | Needs: EM Starter Unit Mount AFD (LF2) Remote Mount Comm AFD (PF7000) Remote Mount Non-Communicating AFD | FLOAT32 | ABCD | Read | |||
| IR | 220doc 30221 | Line 1 Current - Compressor 2A | Depends on starter/drive options; see the source configuration column. | FLOAT32 | ABCD | Read | |||
| IR | 222doc 30223 | Line 2 Current - Compressor 2A | Depends on starter/drive options; see the source configuration column. | FLOAT32 | ABCD | Read | |||
| IR | 224doc 30225 | Line 3 Current - Compressor 2A | Depends on starter/drive options; see the source configuration column. | FLOAT32 | ABCD | Read | |||
| IR | 226doc 30227 | Average Line Current Circuit 2 | Depends on starter/drive options; see the source configuration column. | FLOAT32 | ABCD | Read | |||
| IR | 228doc 30229 | Drive Average Line Current Circuit 2 | Depends on starter/drive options; see the source configuration column. | FLOAT32 | ABCD | Read | |||
| IR | 230doc 30231 | Starter Load Power Factor - Compressor 2A | Depends on starter/drive options; see the source configuration column. | FLOAT32 | ABCD | Read | |||
| IR | 232doc 30233 | Inboard Bearing Temperature Circuit 2 | Temperature in the factory unit system (I-P or SI). Needs: Bearing Temperature Sensor | FLOAT32 | ABCD | Read | |||
| IR | 234doc 30235 | Outboard Bearing Temperature Circuit 2 | Temperature in the factory unit system (I-P or SI). Needs: Bearing Temperature Sensor | FLOAT32 | ABCD | Read | |||
| IR | 236doc 30237 | Motor Winding Temperature 1 Circuit 2 | Temperature in the factory unit system (I-P or SI). | FLOAT32 | ABCD | Read | |||
| IR | 238doc 30239 | Motor Winding Temperature 2 Circuit 2 | Temperature in the factory unit system (I-P or SI). | FLOAT32 | ABCD | Read | |||
| IR | 240doc 30241 | Motor Winding Temperature 3 Circuit 2 | Temperature in the factory unit system (I-P or SI). | FLOAT32 | ABCD | Read | |||
| IR | 242doc 30243 | AFD Transistor Temperature Circuit 2 | Depends on starter/drive options; see the source configuration column. | FLOAT32 | ABCD | Read | |||
| IR | 244doc 30245 | Heat Recovery Entering Water Temp | Temperature in the factory unit system (I-P or SI). Needs: Heat Recovery | FLOAT32 | ABCD | Read | |||
| IR | 246doc 30247 | Heat Recovery Leaving Water Temp | Temperature in the factory unit system (I-P or SI). Needs: Heat Recovery | FLOAT32 | ABCD | Read | |||
| IR | 248doc 30249 | Purge Pumpout Chiller On % (7 Days) Circuit 2 | Needs: Purge | FLOAT32 | ABCD | % | Read | ||
| IR | 250doc 30251 | Purge Pumpout Chiller Off % (7 Days) Circuit 2 | Needs: Purge | FLOAT32 | ABCD | % | Read | ||
| IR | 252doc 30253 | Purge 24 Hour Pumpout Circuit 2 (in seconds) | Needs: Purge | FLOAT32 | ABCD | s | Read | ||
| IR | 254doc 30255 | Phase AB Voltage - Compressor 2A | Depends on starter/drive options; see the source configuration column. | FLOAT32 | ABCD | Read | |||
| IR | 256doc 30257 | Phase BC Voltage - Compressor 2A | Depends on starter/drive options; see the source configuration column. | FLOAT32 | ABCD | Read | |||
| IR | 258doc 30259 | Phase CA Voltage - Compressor 2A | Depends on starter/drive options; see the source configuration column. | FLOAT32 | ABCD | Read | |||
| IR | 260doc 30261 | Purge Pumpout - Life Circuit 2 (in seconds) | Needs: Purge | FLOAT32 | ABCD | s | Read | ||
| IR | 262doc 30263 | Drive Motor Average Current RLA Circuit 2 | Depends on starter/drive options; see the source configuration column. | FLOAT32 | ABCD | % | Read | ||
| IR | 264doc 30265 | Drive Inverter Base Temperature Circuit 2 | Needs: Unit Mount AFD (LF2) w/Line Side Items Remote Mount Comm AFD (PF7000) w/Line Side Items | FLOAT32 | ABCD | Read | |||
| IR | 266doc 30267 | Drive Rectifier Base Temperature Circuit 2 | Needs: Unit Mount AFD (LF2) w/Line Side Items Remote Mount Comm AFD (PF7000) w/Line Side Items | FLOAT32 | ABCD | Read | |||
| IR | 268doc 30269 | Outboard Bearing Pad Temperature #1 Ckt2 | Temperature in the factory unit system (I-P or SI). Needs: CDHH | FLOAT32 | ABCD | Read | |||
| IR | 270doc 30271 | Outboard Bearing Pad Temperature #2 Ckt2 | Temperature in the factory unit system (I-P or SI). Needs: CDHH | FLOAT32 | ABCD | Read | |||
| IR | 272doc 30273 | Outboard Bearing Pad Temperature #3 Ckt2 | Temperature in the factory unit system (I-P or SI). Needs: CDHH | FLOAT32 | ABCD | Read | |||
| IR | 274doc 30275 | Evaporator Refrigerant Pressure Circuit 2 | Pressure in the factory unit system (I-P or SI). | FLOAT32 | ABCD | Read | |||
| IR | 276doc 30277 | Condenser Refrigerant Pressure Circuit 2 | Pressure in the factory unit system (I-P or SI). | FLOAT32 | ABCD | Read | |||
| IR | 278doc 30279 | Differential Refrigerant Pressure Circuit 2 | Differential pressure in the factory unit system (I-P or SI). | FLOAT32 | ABCD | Read | |||
| IR | 280doc 30281 | Restart Inhibit Time Remaining Circuit 2 | FLOAT32 | ABCD | Read | ||||
| IR | 282doc 30283 | AFD Frequency Circuit 2 | Depends on starter/drive options; see the source configuration column. | FLOAT32 | ABCD | Read | |||
| IR | 284doc 30285 | Drive Line Frequency Circuit 2 | Depends on starter/drive options; see the source configuration column. | FLOAT32 | ABCD | Read | |||
| IR | 286doc 30287 | Frequency Command Circuit 2 | Depends on starter/drive options; see the source configuration column. | FLOAT32 | ABCD | Read | |||
| IR | 288doc 30289 | Drive DC Bus Voltage Circuit 2 | Depends on starter/drive options; see the source configuration column. | FLOAT32 | ABCD | Read | |||
| IR | 290doc 30291 | Drive Output Power Circuit 2 | Depends on starter/drive options; see the source configuration column. | FLOAT32 | ABCD | Read | |||
| IR | 292doc 30293 | Line 1 Current RLA - Compressor 2A | Depends on starter/drive options; see the source configuration column. | FLOAT32 | ABCD | % | Read | ||
| IR | 294doc 30295 | Line 2 Current RLA - Compressor 2A | Depends on starter/drive options; see the source configuration column. | FLOAT32 | ABCD | % | Read | ||
| IR | 296doc 30297 | Line 3 Current RLA - Compressor 2A | Depends on starter/drive options; see the source configuration column. | FLOAT32 | ABCD | % | Read | ||
| IR | 298doc 30299 | Drive Current Line 1 Circuit 1 | Needs: Unit Mount AFD (LF2) w/Line Side Items Remote Mount Comm AFD (PF7000) w/Line Side Items | FLOAT32 | ABCD | Read | |||
| IR | 300doc 30301 | Drive Current Line 2 Circuit 1 | Needs: Unit Mount AFD (LF2) w/Line Side Items Remote Mount Comm AFD (PF7000) w/Line Side Items | FLOAT32 | ABCD | Read | |||
| IR | 302doc 30303 | Drive Current Line 3 Circuit 1 | Needs: Unit Mount AFD (LF2) w/Line Side Items Remote Mount Comm AFD (PF7000) w/Line Side Items | FLOAT32 | ABCD | Read | |||
| IR | 304doc 30305 | Drive Current Line 1 Circuit 2 | Needs: Unit Mount AFD (LF2) w/Line Side Items Remote Mount Comm AFD (PF7000) w/Line Side Items | FLOAT32 | ABCD | Read | |||
| IR | 306doc 30307 | Drive Current Line 2 Circuit 2 | Needs: Unit Mount AFD (LF2) w/Line Side Items Remote Mount Comm AFD (PF7000) w/Line Side Items | FLOAT32 | ABCD | Read | |||
| IR | 308doc 30309 | Drive Current Line 3 Circuit 2 | Needs: Unit Mount AFD (LF2) w/Line Side Items Remote Mount Comm AFD (PF7000) w/Line Side Items | FLOAT32 | ABCD | Read | |||
| IR | 310doc 30311 | Starter Input Power Consumption Ckt1 | Electrical power. Needs: EM Starter Unit Mount AFD (LF2) Remote Mount Comm AFD (PF7000) | FLOAT32 | ABCD | Read | |||
| IR | 312doc 30313 | Starter Input Power Consumption Ckt2 | Electrical power. Needs: EM Starter Unit Mount AFD (LF2) Remote Mount Comm AFD (PF7000) | FLOAT32 | ABCD | Read | |||
| IR | 314doc 30315 | Drive Motor Voltage Circuit 2 | Depends on starter/drive options; see the source configuration column. | FLOAT32 | ABCD | Read | |||
| IR | 316doc 30317 | Chiller Control Signal | FLOAT32 | ABCD | % | Read | |||
| IR | 318doc 30319 | Head Pressure Control Status | Needs: Head Pressure Control | FLOAT32 | ABCD | % | Read | ||
| IR | 320doc 30321 | AFD Last Diagnostic Code Ckt2 | Needs: Unit Mount AFD (LF2) Remote Mount Comm AFD (PF7000) Remote Mount Comm AFD (PF6000) | FLOAT32 | ABCD | Read | |||
| IR | 322doc 30323 | Voltage L1-L2 Circuit 1 | Voltage. Needs: Energy Meter | FLOAT32 | ABCD | Read | |||
| IR | 324doc 30325 | Voltage L1-L3 Circuit 1 | Voltage. Needs: Energy Meter | FLOAT32 | ABCD | Read | |||
| IR | 326doc 30327 | Voltage L2-L3 Circuit 1 | Voltage. Needs: Energy Meter | FLOAT32 | ABCD | Read | |||
| IR | 328doc 30329 | Voltage L1-L2 Circuit 2 | Voltage. Needs: Energy Meter | FLOAT32 | ABCD | Read | |||
| IR | 330doc 30331 | Voltage L1-L3 Circuit 2 | Voltage. Needs: Energy Meter | FLOAT32 | ABCD | Read | |||
| IR | 332doc 30333 | Voltage L2-L3 Circuit 2 | Voltage. Needs: Energy Meter | FLOAT32 | ABCD | Read | |||
| IR | 334doc 30335 | Average Line Voltage Circuit 1 | Voltage. Needs: Energy Meter | FLOAT32 | ABCD | Read | |||
| IR | 336doc 30337 | Average Line Voltage Circuit 2 | Voltage. Needs: Energy Meter | FLOAT32 | ABCD | Read | |||
| IR | 338doc 30339 | Line Current L1 Circuit 1 | Current. Needs: Energy Meter | FLOAT32 | ABCD | Read | |||
| IR | 340doc 30341 | Line Current L2 Circuit 1 | Current. Needs: Energy Meter | FLOAT32 | ABCD | Read | |||
| IR | 342doc 30343 | Line Current L3 Circuit 1 | Current. Needs: Energy Meter | FLOAT32 | ABCD | Read | |||
| IR | 344doc 30345 | Line Current L1 Circuit 2 | Current. Needs: Energy Meter | FLOAT32 | ABCD | Read | |||
| IR | 346doc 30347 | Line Current L2 Circuit 2 | Current. Needs: Energy Meter | FLOAT32 | ABCD | Read | |||
| IR | 348doc 30349 | Line Current L3 Circuit 2 | Current. Needs: Energy Meter | FLOAT32 | ABCD | Read | |||
| IR | 350doc 30351 | Unit Average Line Current Circuit 1 | Current. Needs: Energy Meter | FLOAT32 | ABCD | Read | |||
| IR | 352doc 30353 | Unit Average Line Current Circuit 2 | Current. Needs: Energy Meter | FLOAT32 | ABCD | Read | |||
| IR | 354doc 30355 | Line Frequency Circuit 1 | Needs: Energy Meter | FLOAT32 | ABCD | Read | |||
| IR | 356doc 30357 | Line Frequency Circuit 2 | Needs: Energy Meter | FLOAT32 | ABCD | Read | |||
| IR | 358doc 30359 | Power Factor Circuit 1 | Needs: Energy Meter | FLOAT32 | ABCD | Read | |||
| IR | 360doc 30361 | Power Factor Circuit 2 | Needs: Energy Meter | FLOAT32 | ABCD | Read | |||
| IR | 362doc 30363 | Power Demand Circuit 1 | Electrical power. Needs: Energy Meter | FLOAT32 | ABCD | Read | |||
| IR | 364doc 30365 | Power Demand Circuit 2 | Electrical power. Needs: Energy Meter | FLOAT32 | ABCD | Read | |||
| IR | 366doc 30367 | Total Real Power | Electrical power. Needs: Energy Meter | FLOAT32 | ABCD | Read | |||
| IR | 368doc 30369 | Unit Power Consumption | Depends on starter/drive options; see the source configuration column. | FLOAT32 | ABCD | Read | |||
| IR | 370doc 30371 | Energy Consumption | Depends on starter/drive options; see the source configuration column. | FLOAT32 | ABCD | Read | |||
| IR | 372doc 30373 | Energy Consumption Lifetime | Depends on starter/drive options; see the source configuration column. | FLOAT32 | ABCD | Read | |||
| IR | 374doc 30375 | Condenser Approach Temperature Circuit 2 | Temperature difference, factory unit system (I-P or SI). | FLOAT32 | ABCD | Read | |||
| IR | 376doc 30377 | Evaporator Approach Temperature Circuit 2 | Temperature difference, factory unit system (I-P or SI). | FLOAT32 | ABCD | Read | |||
| IR | 378doc 30379 | Drive Input Voltage Calculated 1A | Voltage. Needs: TR200 Modbus AFD | FLOAT32 | ABCD | Read | |||
| IR | 380doc 30381 | Drive Input Voltage Calculated 2A | Voltage. Needs: TR200 Modbus AFD | FLOAT32 | ABCD | Read | |||
| IR | 382doc 30383 | Drive Heatsink Temperature Compressor 1A | Temperature in the factory unit system (I-P or SI). Needs: TR200 Modbus AFD | FLOAT32 | ABCD | Read | |||
| IR | 384doc 30385 | Drive Heatsink Temperature Compressor 2A | Temperature in the factory unit system (I-P or SI). Needs: TR200 Modbus AFD | FLOAT32 | ABCD | Read | |||
| IR | 386doc 30387 | Outdoor Air Temperature Local | Temperature in the factory unit system (I-P or SI). Needs: Outdoor Air Temperature | FLOAT32 | ABCD | Read | |||
| IR | 388doc 30389 | Heat Recovery Differential Water Pressure | Needs: Heat Recovery Water Flow Differential Pressure or Dual Pressure Sensors | FLOAT32 | ABCD | Read | |||
| IR | 390doc 30391 | Heat Recovery Water Flow Rate | Needs: Heat Recovery Water Flow Sensing | FLOAT32 | ABCD | Read | |||
| IR | 392doc 30393 | Heat Recovery Calculated Capacity | Needs: Heat Recovery Water Flow Sensing | FLOAT32 | ABCD | Read | |||
| IR | 394doc 30395 | Heat Recovery Entering Water Pressure | Needs: Heat Recovery Water Flow Dual Pressure Sensors | FLOAT32 | ABCD | Read | |||
| IR | 396doc 30397 | Heat Recovery Leaving Water Pressure | Needs: Heat Recovery Water Flow Dual Pressure Sensors | FLOAT32 | ABCD | Read | |||
| IR | 398doc 30399 | Heat Recovery Approach Temperature Circuit 1 | Temperature difference, factory unit system (I-P or SI). Needs: Heat Recovery | FLOAT32 | ABCD | Read | |||
| IR | 400doc 30401 | Heat Recovery Approach Temperature Circuit 2 | Temperature difference, factory unit system (I-P or SI). Needs: Heat Recovery | FLOAT32 | ABCD | Read | |||
| IR | 402doc 30403 | High Side Oil Gauge Pressure - Compressor 1A | Pressure in the factory unit system (I-P or SI). | FLOAT32 | ABCD | Read | |||
| IR | 404doc 30405 | Low Side Oil Gauge Pressure - Compressor 1A | Pressure in the factory unit system (I-P or SI). | FLOAT32 | ABCD | Read | |||
| IR | 406doc 30407 | High Side Oil Gauge Pressure - Compressor 2A | Pressure in the factory unit system (I-P or SI). | FLOAT32 | ABCD | Read | |||
| IR | 408doc 30409 | Low Side Oil Gauge Pressure - Compressor 2A | Pressure in the factory unit system (I-P or SI). | FLOAT32 | ABCD | Read | |||
| IR | 410doc 30411 | Condenser Refrigerant Gauge Pressure Circuit 1 | Pressure in the factory unit system (I-P or SI). | FLOAT32 | ABCD | Read | |||
| IR | 412doc 30413 | Condenser Refrigerant Gauge Pressure Circuit 2 | Pressure in the factory unit system (I-P or SI). | FLOAT32 | ABCD | Read | |||
| IR | 414doc 30415 | Entering Condenser Water Gauge Pressure | Needs: Cond Water Flow Differential Dual Pressure Sensors | FLOAT32 | ABCD | Read | |||
| IR | 416doc 30417 | Entering Evaporator Water Gauge Pressure | Needs: Evap Water Flow Differential Dual Pressure Sensors | FLOAT32 | ABCD | Read | |||
| IR | 418doc 30419 | Evaporator Refrigerant Gauge Pressure Circuit 1 | Pressure in the factory unit system (I-P or SI). | FLOAT32 | ABCD | Read | |||
| IR | 420doc 30421 | Evaporator Refrigerant Gauge Pressure Circuit 2 | Pressure in the factory unit system (I-P or SI). | FLOAT32 | ABCD | Read | |||
| IR | 422doc 30423 | Heat Recovery Entering Water Gauge Pressure | Needs: Heat Recovery Water Flow Dual Pressure Sensors | FLOAT32 | ABCD | Read | |||
| IR | 424doc 30425 | Heat Recovery Leaving Water Gauge Pressure | Needs: Heat Recovery Water Flow Dual Pressure Sensors | FLOAT32 | ABCD | Read | |||
| IR | 426doc 30427 | Leaving Condenser Water Gauge Pressure | Needs: Cond Water Flow Differential Dual Pressure Sensors | FLOAT32 | ABCD | Read | |||
| IR | 428doc 30429 | Leaving Evaporator Water Gauge Pressure | Needs: Evap Water Flow Differential Dual Pressure Sensors | FLOAT32 | ABCD | Read | |||
| IR | 430doc 30431 | Compressor Discharge Superheat Circuit 1 | Temperature difference, factory unit system (I-P or SI). Needs: Compressor Refrigerant Discharge Temperature | FLOAT32 | ABCD | Read | |||
| IR | 432doc 30433 | Compressor Discharge Superheat Circuit 2 | Temperature difference, factory unit system (I-P or SI). Needs: Compressor Refrigerant Discharge Temperature | FLOAT32 | ABCD | Read | |||
| IR | 434doc 30435 | Unit Load Command | FLOAT32 | ABCD | % | Read | |||
| IR | 436doc 30437 | Drive Motor Current U RLA Circuit 1 | Needs: UM AFD w/o THD filter (Inovance) MV Remote Mount COMM AFD (Inovance) | FLOAT32 | ABCD | % | Read | ||
| IR | 438doc 30439 | Drive Motor Current V RLA Circuit 1 | Needs: UM AFD w/o THD filter (Inovance) MV Remote Mount COMM AFD (Inovance) | FLOAT32 | ABCD | % | Read | ||
| IR | 440doc 30441 | Drive Motor Current W RLA Circuit 1 | Needs: UM AFD w/o THD filter (Inovance) MV Remote Mount COMM AFD (Inovance) | FLOAT32 | ABCD | % | Read | ||
| IR | 442doc 30443 | Drive Motor Current U Circuit 1 | Current. Needs: UM AFD w/o THD filter (Inovance) MV Remote Mount COMM AFD (Inovance) | FLOAT32 | ABCD | Read | |||
| IR | 444doc 30445 | Drive Motor Current V Circuit 1 | Current. Needs: UM AFD w/o THD filter (Inovance) MV Remote Mount COMM AFD (Inovance) | FLOAT32 | ABCD | Read | |||
| IR | 446doc 30447 | Drive Motor Current W Circuit 1 | Current. Needs: UM AFD w/o THD filter (Inovance) MV Remote Mount COMM AFD (Inovance) | FLOAT32 | ABCD | Read | |||
| IR | 448doc 30449 | Drive Motor Current U RLA Circuit 2 | Needs: UM AFD w/o THD filter (Inovance) MV Remote Mount COMM AFD (Inovance) | FLOAT32 | ABCD | % | Read | ||
| IR | 450doc 30451 | Drive Motor Current V RLA Circuit 2 | Needs: UM AFD w/o THD filter (Inovance) MV Remote Mount COMM AFD (Inovance) | FLOAT32 | ABCD | % | Read | ||
| IR | 452doc 30453 | Drive Motor Current W RLA Circuit 2 | Needs: UM AFD w/o THD filter (Inovance) MV Remote Mount COMM AFD (Inovance) | FLOAT32 | ABCD | % | Read | ||
| IR | 454doc 30455 | Drive Motor Current U Circuit 2 | Current. Needs: UM AFD w/o THD filter (Inovance) MV Remote Mount COMM AFD (Inovance) | FLOAT32 | ABCD | Read | |||
| IR | 456doc 30457 | Drive Motor Current V Circuit 2 | Current. Needs: UM AFD w/o THD filter (Inovance) MV Remote Mount COMM AFD (Inovance) | FLOAT32 | ABCD | Read | |||
| IR | 458doc 30459 | Drive Motor Current W Circuit 2 | Current. Needs: UM AFD w/o THD filter (Inovance) MV Remote Mount COMM AFD (Inovance) | FLOAT32 | ABCD | Read | |||
| IR | 460doc 30461 | Active Cooling Differential to Start | Temperature difference, factory unit system (I-P or SI). | FLOAT32 | ABCD | Read | |||
| IR | 462doc 30463 | Active Cooling Differential to Stop | Temperature difference, factory unit system (I-P or SI). | FLOAT32 | ABCD | Read | |||
| IR | 464doc 30465 | Active Heating Differential to Start | Temperature difference, factory unit system (I-P or SI). Needs: Hot Water Control | FLOAT32 | ABCD | Read | |||
| IR | 466doc 30467 | Active Heating Differential to Stop | Temperature difference, factory unit system (I-P or SI). Needs: Hot Water Control | FLOAT32 | ABCD | Read | |||
| IR | 2010doc 32011 | Running Mode | UINT16 | Read | 1 = Chiller Off; 2 = Chiller In Start Mode; 3 = Chiller In Run Mode; 4 = Chiller In Pre-Shutdown Mode; 5 = Chiller In Service Mode | ||||
| IR | 2011doc 32012 | Operating Mode | UINT16 | Read | 1 = Cool; 2 = Heat; 3 = Ice Making; 4 = Free Cooling | ||||
| IR | 2012doc 32013 | Chiller Setpoint Source | UINT16 | Read | 1 = BAS; 2 = External; 3 = Front Panel | ||||
| IR | 2013doc 32014 | Cooling Type | UINT16 | Read | 1 = Water Cooled | ||||
| IR | 2014doc 32015 | Refrigerant Type | UINT16 | Read | 1 = R-11; 2 = R-12; 3 = R-22; 4 = R-123; 5 = R-134a; 8 = R-113; 9 = R-114; 10 = R-500; 11 = R-502; 13 = R-513A; 14 = R-1233zd(E); 15 = R-514A | ||||
| IR | 2015doc 32016 | Manufacturing Location | UINT16 | Read | 1 = Field Applied; 2 = La Crosse; 15 = Taicang | ||||
| IR | 2016doc 32017 | Model Information [GEN2] | UINT16 | Read | 1 = CVHF; 2 = CVGF; 3 = CVHS; 11 = CDHF; 12 = CVR; 13 = CVHH; 14 = CDHH; 20 = CVHM; 38 = CVHE; 39 = CVHG; 40 = CVHL; 43 = CDHG | ||||
| IR | 3010doc 33011 | Manual Override Exists | UINT16 | Read | 0 = Off; 1 = On | ||||
| IR | 3011doc 33012 | Base Loading Request Active | Needs: Base Loading | UINT16 | Read | 0 = Inactive; 1 = Active | |||
| IR | 3012doc 33013 | Run Enabled | UINT16 | Read | 0 = Run Not Enabled; 1 = Run Enabled | ||||
| IR | 3013doc 33014 | Local Setpoint Control | UINT16 | Read | 0 = Remote Control; 1 = Local Control | ||||
| IR | 3014doc 33015 | Maximum Capacity | UINT16 | Read | 0 = Off; 1 = On | ||||
| IR | 3015doc 33016 | Capacity Limited | UINT16 | Read | 0 = Not Limited; 1 = Limited | ||||
| IR | 3016doc 33017 | Head Relief Request | UINT16 | Read | 0 = Off; 1 = On | ||||
| IR | 3017doc 33018 | Purge Compressor Relay Circuit 1 | Needs: Purge | UINT16 | Read | 0 = Off; 1 = On | |||
| IR | 3018doc 33019 | Pump Out Relay Circuit 1 | Needs: Purge | UINT16 | Read | 0 = Off; 1 = On | |||
| IR | 3019doc 33020 | Purge Regenerating Valve Solenoid Circuit 1 | Needs: Purge w/Carbon Tank | UINT16 | Read | 0 = Off; 1 = On | |||
| IR | 3020doc 33021 | Chiller Running State | UINT16 | Read | 0 = Off; 1 = On | ||||
| IR | 3021doc 33022 | Evaporator Water Pump Request | UINT16 | Read | 0 = Off; 1 = On | ||||
| IR | 3022doc 33023 | Evaporator Water Flow Status | UINT16 | Read | 0 = No Flow; 1 = Flow | ||||
| IR | 3023doc 33024 | Condenser Water Pump Request | UINT16 | Read | 0 = Off; 1 = On | ||||
| IR | 3024doc 33025 | Condenser Water Flow Status | UINT16 | Read | 0 = No Flow; 1 = Flow | ||||
| IR | 3025doc 33026 | Diagnostic Present | UINT16 | Read | 0 = Normal; 1 = In Alarm | ||||
| IR | 3026doc 33027 | Diagnostic Shutdown Present | UINT16 | Read | 0 = Normal; 1 = In Alarm | ||||
| IR | 3027doc 33028 | Diagnostic: Manual Reset Required | UINT16 | Read | 0 = Normal; 1 = In Alarm | ||||
| IR | 3028doc 33029 | Diagnostic: Local Manual Reset Required | UINT16 | Read | 0 = Normal; 1 = In Alarm | ||||
| IR | 3029doc 33030 | Diagnostic Present: Information | UINT16 | Read | 0 = Normal; 1 = In Alarm | ||||
| IR | 3030doc 33031 | Diagnostic Present: Advisory | UINT16 | Read | 0 = Normal; 1 = In Alarm | ||||
| IR | 3031doc 33032 | Diagnostic Present: Critical | UINT16 | Read | 0 = Normal; 1 = In Alarm | ||||
| IR | 3032doc 33033 | Diagnostic Present: Service Required | UINT16 | Read | 0 = Normal; 1 = In Alarm | ||||
| IR | 3033doc 33034 | Compressor 1A Status | UINT16 | Read | 0 = Off; 1 = Running | ||||
| IR | 3034doc 33035 | Front Panel Auto Stop | UINT16 | Read | 0 = Stop; 1 = Auto | ||||
| IR | 3035doc 33036 | External Auto Stop Input Status | UINT16 | Read | 0 = Stop; 1 = Auto | ||||
| IR | 3036doc 33037 | Purge Compressor Relay Circuit 2 | Needs: Purge | UINT16 | Read | 0 = Off; 1 = On | |||
| IR | 3037doc 33038 | Purge Regenerating Valve Solenoid Circuit 2 | Needs: Purge w/Carbon Tank | UINT16 | Read | 0 = Off; 1 = On | |||
| IR | 3038doc 33039 | Pump Out Relay Circuit 2 | Needs: Purge | UINT16 | Read | 0 = Off; 1 = On | |||
| IR | 3039doc 33040 | Compressor 2A Status | UINT16 | Read | 0 = Off; 1 = Running | ||||
| IR | 3040doc 33041 | Emergency Stop | UINT16 | Read | 0 = Auto; 1 = Emergency Stop - Manual Reset Required | ||||
| IR | 3041doc 33042 | Circuit 1 Cooling Available | UINT16 | Read | 0 = No; 1 = Yes | ||||
| IR | 3042doc 33043 | Circuit 2 Cooling Available | UINT16 | Read | 0 = No; 1 = Yes | ||||
| IR | 3043doc 33044 | Circuit 1 Lockout Front Panel | UINT16 | Read | 0 = Normal; 1 = Locked Out | ||||
| IR | 3044doc 33045 | Circuit 2 Lockout Front Panel | UINT16 | Read | 0 = Normal; 1 = Locked Out | ||||
| IR | 3045doc 33046 | Circuit 1 Lockout External | UINT16 | Read | 0 = Normal; 1 = Locked Out | ||||
| IR | 3046doc 33047 | Circuit 2 Lockout External | UINT16 | Read | 0 = Normal; 1 = Locked Out | ||||
| IR | 3047doc 33048 | Circuit 1 Lockout Active | UINT16 | Read | 0 = Normal; 1 = Locked Out | ||||
| IR | 3048doc 33049 | Circuit 2 Lockout Active | UINT16 | Read | 0 = Normal; 1 = Locked Out | ||||
| IR | 3049doc 33050 | Diagnostic Shutdown Present: AFD/Starter Circuit 1 | UINT16 | Read | 0 = Normal; 1 = In Alarm | ||||
| IR | 3050doc 33051 | Diagnostic Shutdown Present: AFD/Starter Circuit 2 | UINT16 | Read | 0 = Normal; 1 = In Alarm | ||||
| IR | 3051doc 33052 | Heat Recovery Water Flow Status | Needs: Heat Recovery | UINT16 | Read | 0 = No Flow; 1 = Flow | |||
| IR | 4000doc 34001 | Diagnostic: AFD Comm Loss: Main Processor Circuit 1 | Depends on starter/drive options; see the source configuration column. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4001doc 34002 | Diagnostic: AFD Comm Loss: Main Processor Circuit 2 | Depends on starter/drive options; see the source configuration column. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4002doc 34003 | Diagnostic: AFD Control Board Memory Error Type 2 Circuit 1 | Diagnostic flag. Needs: Unit Mount AFD - AFDD,E,F (LF2) Remote Mount Comm AFD - (PF7000) | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4003doc 34004 | Diagnostic: AFD Control Board Memory Error Type 2 Circuit 2 | Diagnostic flag. Needs: Unit Mount AFD - AFDD,E,F (LF2) Remote Mount Comm AFD - (PF7000) | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4004doc 34005 | Diagnostic: AFD DPI Communication Failure Circuit 1 | Diagnostic flag. Needs: Unit Mount AFD - AFDD,E,F (LF2) Remote Mount Comm AFD - (PF7000) | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4005doc 34006 | Diagnostic: AFD DPI Communication Failure Circuit 2 | Diagnostic flag. Needs: Unit Mount AFD - AFDD,E,F (LF2) Remote Mount Comm AFD - (PF7000) | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4006doc 34007 | Diagnostic: AFD Fatal Software Error Circuit 1 | Diagnostic flag. Needs: Unit Mount AFD - AFDD,E,F (LF2) Remote Mount Comm AFD - (PF7000) | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4007doc 34008 | Diagnostic: AFD Fatal Software Error Circuit 2 | Diagnostic flag. Needs: Unit Mount AFD - AFDD,E,F (LF2) Remote Mount Comm AFD - (PF7000) | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4008doc 34009 | Diagnostic: AFD General Failure Circuit 1 | Depends on starter/drive options; see the source configuration column. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4009doc 34010 | Diagnostic: AFD General Failure Circuit 2 | Depends on starter/drive options; see the source configuration column. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4010doc 34011 | Diagnostic: AFD Ground Fault Circuit 1 | Depends on starter/drive options; see the source configuration column. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4011doc 34012 | Diagnostic: AFD Ground Fault Circuit 2 | Depends on starter/drive options; see the source configuration column. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4012doc 34013 | Diagnostic: AFD High Bus Voltage Circuit 1 | Diagnostic flag. Needs: Unit Mount AFD - AFDD,E,F (LF2) Remote Mount Comm AFD - (PF7000) | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4013doc 34014 | Diagnostic: AFD High Bus Voltage Circuit 2 | Diagnostic flag. Needs: Unit Mount AFD - AFDD,E,F (LF2) Remote Mount Comm AFD - (PF7000) | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4014doc 34015 | Diagnostic: AFD High Temperature Circuit 1 | Diagnostic flag. Needs: Unit Mount AFD - AFDD,E,F (LF2) Remote Mount Comm AFD - (PF7000) | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4015doc 34016 | Diagnostic: AFD High Temperature Circuit 2 | Diagnostic flag. Needs: Unit Mount AFD - AFDD,E,F (LF2) Remote Mount Comm AFD - (PF7000) | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4016doc 34017 | Diagnostic: AFD I/O Board Failure Circuit 1 | Diagnostic flag. Needs: Unit Mount AFD - AFDD,E,F (LF2) Remote Mount Comm AFD - (PF7000) | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4017doc 34018 | Diagnostic: AFD I/O Board Failure Circuit 2 | Diagnostic flag. Needs: Unit Mount AFD - AFDD,E,F (LF2) Remote Mount Comm AFD - (PF7000) | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4018doc 34019 | Diagnostic: AFD Instantaneous Current Overload Circuit 1 | Depends on starter/drive options; see the source configuration column. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4019doc 34020 | Diagnostic: AFD Instantaneous Current Overload Circuit 2 | Depends on starter/drive options; see the source configuration column. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4020doc 34021 | Diagnostic: AFD Interrupt Failure Circuit 1 | Depends on starter/drive options; see the source configuration column. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4021doc 34022 | Diagnostic: AFD Interrupt Failure Circuit 2 | Depends on starter/drive options; see the source configuration column. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4022doc 34023 | Diagnostic: AFD Motor Current Overload Circuit 1 | Depends on starter/drive options; see the source configuration column. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4023doc 34024 | Diagnostic: AFD Motor Current Overload Circuit 2 | Depends on starter/drive options; see the source configuration column. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4024doc 34025 | Diagnostic: AFD Motor Short Circuit 1 | Diagnostic flag. Needs: Unit Mount AFD - AFDD,E,F (LF2) Remote Mount Comm AFD - (PF7000) | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4025doc 34026 | Diagnostic: AFD Motor Short Circuit 2 | Diagnostic flag. Needs: Unit Mount AFD - AFDD,E,F (LF2) Remote Mount Comm AFD - (PF7000) | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4026doc 34027 | Diagnostic: AFD Output Phase Loss Circuit 1 | Depends on starter/drive options; see the source configuration column. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4027doc 34028 | Diagnostic: AFD Output Phase Loss Circuit 2 | Depends on starter/drive options; see the source configuration column. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4028doc 34029 | Diagnostic: AFD Power Intfc Controller Board Failure Circuit 1 | Diagnostic flag. Needs: Unit Mount AFD - AFDD,E,F (LF2) Remote Mount Comm AFD - (PF7000) | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4029doc 34030 | Diagnostic: AFD Power Intfc Controller Board Failure Circuit 2 | Diagnostic flag. Needs: Unit Mount AFD - AFDD,E,F (LF2) Remote Mount Comm AFD - (PF7000) | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4030doc 34031 | Diagnostic: AFD Power Loss Circuit 1 | Depends on starter/drive options; see the source configuration column. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4031doc 34032 | Diagnostic: AFD Power Loss Circuit 2 | Depends on starter/drive options; see the source configuration column. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4032doc 34033 | Diagnostic: AFD Power Structure Board Failure Circuit 1 | Diagnostic flag. Needs: Unit Mount AFD - AFDD,E,F (LF2) Remote Mount Comm AFD - (PF7000) | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4033doc 34034 | Diagnostic: AFD Power Structure Board Failure Circuit 2 | Diagnostic flag. Needs: Unit Mount AFD - AFDD,E,F (LF2) Remote Mount Comm AFD - (PF7000) | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4034doc 34035 | Diagnostic: AFD RS485 Board Memory Error Type 2 Circuit 1 | Diagnostic flag. Needs: Unit Mount AFD - AFDD,E,F (LF2) Remote Mount Comm AFD - (PF7000) | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4035doc 34036 | Diagnostic: AFD RS485 Board Memory Error Type 2 Circuit 2 | Diagnostic flag. Needs: Unit Mount AFD - AFDD,E,F (LF2) Remote Mount Comm AFD - (PF7000) | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4038doc 34039 | Diagnostic: At Speed Input Opened Circuit 1 | Diagnostic flag. Needs: Remote Mount Non-Comm AFD Solid State Starter | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4039doc 34040 | Diagnostic: At Speed Input Opened Circuit 2 | Diagnostic flag. Needs: Remote Mount Non-Comm AFD Solid State Starter | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4040doc 34041 | Diagnostic: At Speed Input Shorted Circuit 1 | Diagnostic flag. Needs: Remote Mount Non-Comm AFD Solid State Starter | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4041doc 34042 | Diagnostic: At Speed Input Shorted Circuit 2 | Diagnostic flag. Needs: Remote Mount Non-Comm AFD Solid State Starter | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4042doc 34043 | Diagnostic: Check Clock | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4043doc 34044 | Diagnostic: Check Oil Filter Circuit 1 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4044doc 34045 | Diagnostic: Check Oil Filter Circuit 2 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4045doc 34046 | Diagnostic: Check Oil Heater Circuit 1 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4046doc 34047 | Diagnostic: Check Oil Heater Circuit 2 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4047doc 34048 | Comm Loss: Adaptive Frequency Drive Circuit 1 | Depends on starter/drive options; see the source configuration column. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4048doc 34049 | Comm Loss: Adaptive Frequency Drive Circuit 2 | Depends on starter/drive options; see the source configuration column. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4049doc 34050 | Comm Loss: AFD Speed Signal VDC Output Circuit 1 | Diagnostic flag. Needs: Remote Mount Non-Comm AFD | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4050doc 34051 | Comm Loss: AFD Speed Signal VDC Output Circuit 2 | Diagnostic flag. Needs: Remote Mount Non-Comm AFD | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4051doc 34052 | Comm Loss: Compressor Motor % RLA Output Circuit 1 | Diagnostic flag. Needs: % RLA Output | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4052doc 34053 | Comm Loss: Compressor Motor % RLA Output Circuit 2 | Diagnostic flag. Needs: % RLA Output | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4053doc 34054 | Comm Loss: Cond Diff Water Pressure | Diagnostic flag. Needs: Cond Water Flow Measurement | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4054doc 34055 | Comm Loss: Cond Head Press Cntrl Output | Diagnostic flag. Needs: Head Pressure Control | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4055doc 34056 | Comm Loss: Cond High Pressure Cutout Circuit 1 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4056doc 34057 | Comm Loss: Cond High Pressure Cutout Circuit 2 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4057doc 34058 | Comm Loss: Cond Refrigerant Pressure Circuit 1 | Diagnostic flag. Needs: Condenser Pressure Sensor | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4058doc 34059 | Comm Loss: Cond Refrigerant Pressure Circuit 2 | Diagnostic flag. Needs: Condenser Pressure Sensor | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4059doc 34060 | Comm Loss: Cond Rfgt Pressure Output Circuit 1 | Diagnostic flag. Needs: Condenser Refrigerant Pressure Output | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4060doc 34061 | Comm Loss: Cond Rfgt Pressure Output Circuit 2 | Diagnostic flag. Needs: Condenser Refrigerant Pressure Output | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4061doc 34062 | Comm Loss: Cond Saturated Rfgt Temp Circuit 1 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4062doc 34063 | Comm Loss: Cond Saturated Rfgt Temp Circuit 2 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4063doc 34064 | Comm Loss: Condenser Entering Water Pressure | Diagnostic flag. Needs: Cond Water Flow Measurement - Dual Pressure Sensors | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4064doc 34065 | Comm Loss: Condenser Entering Water Temp | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4065doc 34066 | Comm Loss: Condenser Leaving Water Pressure | Diagnostic flag. Needs: Cond Water Flow Measurement - Dual Pressure Sensors | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4066doc 34067 | Comm Loss: Condenser Leaving Water Temp | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4067doc 34068 | Comm Loss: Condenser Liquid Level Sensor Circuit 1 | Diagnostic flag. Needs: Economizer Bypass | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4068doc 34069 | Comm Loss: Condenser Liquid Level Sensor Circuit 2 | Diagnostic flag. Needs: Economizer Bypass | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4069doc 34070 | Comm Loss: Condenser Water Flow Switch | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4070doc 34071 | Comm Loss: Condenser Water Pump Relay | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4071doc 34072 | Comm Loss: Cprsr Discharge Rfgt Temp Circuit 1 | Diagnostic flag. Needs: Compressor Refrigerant Discharge Temp Sensor | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4072doc 34073 | Comm Loss: Cprsr Discharge Rfgt Temp Circuit 2 | Diagnostic flag. Needs: Compressor Refrigerant Discharge Temp Sensor | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4073doc 34074 | Comm Loss: Economizer Bypass Valve Circuit 1 | Diagnostic flag. Needs: Economizer Bypass | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4074doc 34075 | Comm Loss: Economizer Bypass Valve Circuit 2 | Diagnostic flag. Needs: Economizer Bypass | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4075doc 34076 | Comm Loss: Emergency Stop | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4076doc 34077 | Comm Loss: Energy Meter 1 Circuit 1 | Diagnostic flag. Needs: Energy Meter | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4077doc 34078 | Comm Loss: Energy Meter 2 Circuit 2 | Diagnostic flag. Needs: Energy Meter | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4078doc 34079 | Comm Loss: Evap Diff Water Pressure | Diagnostic flag. Needs: Evap Water Flow Measurement | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4079doc 34080 | Comm Loss: Evap Entering Water Temp | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4080doc 34081 | Comm Loss: Evap Leaving Water Temp | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4081doc 34082 | Comm Loss: Evap Refrigerant Pressure Circuit 1 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4082doc 34083 | Comm Loss: Evap Refrigerant Pressure Circuit 2 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4083doc 34084 | Comm Loss: Evap Sat Refrig Temp Circuit 1 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4084doc 34085 | Comm Loss: Evap Sat Refrig Temp Circuit 2 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4085doc 34086 | Comm Loss: Evaporator Entering Water Pressure | Diagnostic flag. Needs: Evap Water Flow Measurement - Dual Pressure Sensors | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4086doc 34087 | Comm Loss: Evaporator Leaving Water Pressure | Diagnostic flag. Needs: Evap Water Flow Measurement - Dual Pressure Sensors | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4087doc 34088 | Comm Loss: Evaporator Water Flow Switch | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4088doc 34089 | Comm Loss: Evaporator Water Pump Relay | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4089doc 34090 | Comm Loss: Ext Base Loading Command | Diagnostic flag. Needs: Base Loading | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4090doc 34091 | Comm Loss: Ext Base Loading Setpoint | Diagnostic flag. Needs: Base Loading | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4091doc 34092 | Comm Loss: Ext Chilled/Hot Water Setpoint | Diagnostic flag. Needs: External Chilled Water Setpoint | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4092doc 34093 | Comm Loss: Ext Demand Limit Setpoint | Diagnostic flag. Needs: External Demand Limit Setpoint | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4093doc 34094 | Comm Loss: External Auto/Stop | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4094doc 34095 | Comm Loss: External Ckt Lockout Circuit 1 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4095doc 34096 | Comm Loss: External Ckt Lockout Circuit 2 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4097doc 34098 | Comm Loss: External Hot Water Command | Diagnostic flag. Needs: Hot Water Control | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4098doc 34099 | Comm Loss: External Ice Building Command | Diagnostic flag. Needs: Ice Building | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4099doc 34100 | Comm Loss: Generator Fault Input Circuit 1 | Diagnostic flag. Needs: Engine/Generator | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4100doc 34101 | Comm Loss: Generator Fault Input Circuit 2 | Diagnostic flag. Needs: Engine/Generator | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4101doc 34102 | Comm Loss: Generator Speed Signal Output Circuit 1 | Diagnostic flag. Needs: Engine/Generator | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4102doc 34103 | Comm Loss: Generator Speed Signal Output Circuit 2 | Diagnostic flag. Needs: Engine/Generator | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4103doc 34104 | Comm Loss: Generator Start/Stop Relay Circuit 1 | Diagnostic flag. Needs: Engine/Generator | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4104doc 34105 | Comm Loss: Generator Start/Stop Relay Circuit 2 | Diagnostic flag. Needs: Engine/Generator | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4105doc 34106 | Comm Loss: Generator Up To Speed Input Circuit 1 | Diagnostic flag. Needs: Engine/Generator | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4106doc 34107 | Comm Loss: Generator Up To Speed Input Circuit 2 | Diagnostic flag. Needs: Engine/Generator | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4107doc 34108 | Comm Loss: Heat Recovery Entering Water Temp | Diagnostic flag. Needs: Heat Recovery | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4108doc 34109 | Comm Loss: Heat Recovery Leaving Water Temp | Diagnostic flag. Needs: Heat Recovery | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4112doc 34113 | Comm Loss: Ice Building Relay | Diagnostic flag. Needs: Ice Building | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4113doc 34114 | Comm Loss: IGV First Stage Actuator Circuit 1 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4114doc 34115 | Comm Loss: IGV First Stage Actuator Circuit 2 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4115doc 34116 | Comm Loss: IGV Second Stage Actuator Circuit 1 | Diagnostic flag. Needs: IGV Actuator - Dual | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4116doc 34117 | Comm Loss: IGV Second Stage Actuator Circuit 2 | Diagnostic flag. Needs: IGV Actuator - Dual | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4117doc 34118 | Comm Loss: Inboard Bearing Temperature Circuit 1 | Diagnostic flag. Needs: Bearing Temp Sensors | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4118doc 34119 | Comm Loss: Inboard Bearing Temperature Circuit 2 | Diagnostic flag. Needs: Bearing Temp Sensors | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4119doc 34120 | Comm Loss: Motor Winding Temperature 1 Circuit 1 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4120doc 34121 | Comm Loss: Motor Winding Temperature 1 Circuit 2 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4121doc 34122 | Comm Loss: Motor Winding Temperature 2 Circuit 1 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4122doc 34123 | Comm Loss: Motor Winding Temperature 2 Circuit 2 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4123doc 34124 | Comm Loss: Motor Winding Temperature 3 Circuit 1 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4124doc 34125 | Comm Loss: Motor Winding Temperature 3 Circuit 2 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4125doc 34126 | Comm Loss: Oil Cooler Solenoid Circuit 1 | Diagnostic flag. Needs: Oil Cooler Solenoid Valve | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4126doc 34127 | Comm Loss: Oil Cooler Solenoid Circuit 2 | Diagnostic flag. Needs: Oil Cooler Solenoid Valve | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4127doc 34128 | Comm Loss: Oil Pump Discharge Pressure Circuit 1 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4128doc 34129 | Comm Loss: Oil Pump Discharge Pressure Circuit 2 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4129doc 34130 | Comm Loss: Oil Tank Heater 4E1 Relay Circuit 1 | Diagnostic flag. Needs: CDHH | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4130doc 34131 | Comm Loss: Oil Tank Heater 4E1 Relay Circuit 2 | Diagnostic flag. Needs: CDHH | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4131doc 34132 | Comm Loss: Oil Tank Heater 4E2 Relay Circuit 1 | Diagnostic flag. Needs: CDHH | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4132doc 34133 | Comm Loss: Oil Tank Heater 4E2 Relay Circuit 2 | Diagnostic flag. Needs: CDHH | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4133doc 34134 | Comm Loss: Oil Tank Heater Relay Circuit 1 | Diagnostic flag. Needs: CDHF,G | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4134doc 34135 | Comm Loss: Oil Tank Heater Relay Circuit 2 | Diagnostic flag. Needs: CDHF,G | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4135doc 34136 | Comm Loss: Oil Tank Pressure Circuit 1 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4136doc 34137 | Comm Loss: Oil Tank Pressure Circuit 2 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4137doc 34138 | Comm Loss: Oil Tank Temperature Circuit 1 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4138doc 34139 | Comm Loss: Oil Tank Temperature Circuit 2 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4139doc 34140 | Comm Loss: Oil Vent Line Circuit 1 | Diagnostic flag. Needs: CDHH | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4140doc 34141 | Comm Loss: Oil Vent Line Circuit 2 | Diagnostic flag. Needs: CDHH | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4141doc 34142 | Comm Loss: Oil/Refrigerant Pump Relay Circuit 1 | Diagnostic flag. Needs: CDHF,G | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4142doc 34143 | Comm Loss: Oil/Refrigerant Pump Relay Circuit 2 | Diagnostic flag. Needs: CDHF,G | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4143doc 34144 | Comm Loss: Outboard Bearing Pad Temp 1 Circuit 1 | Diagnostic flag. Needs: CDHH | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4144doc 34145 | Comm Loss: Outboard Bearing Pad Temp 1 Circuit 2 | Diagnostic flag. Needs: CDHH | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4145doc 34146 | Comm Loss: Outboard Bearing Pad Temp 2 Circuit 1 | Diagnostic flag. Needs: CDHH | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4146doc 34147 | Comm Loss: Outboard Bearing Pad Temp 2 Circuit 2 | Diagnostic flag. Needs: CDHH | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4147doc 34148 | Comm Loss: Outboard Bearing Pad Temp 3 Circuit 1 | Diagnostic flag. Needs: CDHH | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4148doc 34149 | Comm Loss: Outboard Bearing Pad Temp 3 Circuit 2 | Diagnostic flag. Needs: CDHH | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4149doc 34150 | Comm Loss: Outboard Bearing Temperature Circuit 1 | Diagnostic flag. Needs: Bearing Temp Sensors | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4150doc 34151 | Comm Loss: Outboard Bearing Temperature Circuit 2 | Diagnostic flag. Needs: Bearing Temp Sensors | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4151doc 34152 | Comm Loss: Outdoor Air Temperature | Diagnostic flag. Needs: Outdoor Air Temp Sensor | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4152doc 34153 | Comm Loss: Programmable Relay Board 1 | Diagnostic flag. Needs: Operating Status Programmable Relays | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4153doc 34154 | Comm Loss: Programmable Relay Board 2 | Diagnostic flag. Needs: Operating Status Programmable Relays | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4154doc 34155 | Comm Loss: Purge Alarm Relay Circuit 1 | Diagnostic flag. Needs: Purge | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4155doc 34156 | Comm Loss: Purge Alarm Relay Circuit 2 | Diagnostic flag. Needs: Purge | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4156doc 34157 | Comm Loss: Purge Carbon Tank Heater Rly Circuit 1 | Diagnostic flag. Needs: Purge w/Carbon tank | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4157doc 34158 | Comm Loss: Purge Carbon Tank Heater Rly Circuit 2 | Diagnostic flag. Needs: Purge w/Carbon tank | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4158doc 34159 | Comm Loss: Purge Carbon Tank Temperature Circuit 1 | Diagnostic flag. Needs: Purge w/Carbon tank | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4159doc 34160 | Comm Loss: Purge Carbon Tank Temperature Circuit 2 | Diagnostic flag. Needs: Purge w/Carbon tank | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4160doc 34161 | Comm Loss: Purge Condensing Unit Relay Circuit 1 | Diagnostic flag. Needs: Purge | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4161doc 34162 | Comm Loss: Purge Condensing Unit Relay Circuit 2 | Diagnostic flag. Needs: Purge | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4162doc 34163 | Comm Loss: Purge Cprsr Suction Rfgt Temp Circuit 1 | Diagnostic flag. Needs: Purge | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4163doc 34164 | Comm Loss: Purge Cprsr Suction Rfgt Temp Circuit 2 | Diagnostic flag. Needs: Purge | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4164doc 34165 | Comm Loss: Purge Exhaust Solenoid Output Circuit 1 | Diagnostic flag. Needs: Purge | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4165doc 34166 | Comm Loss: Purge Exhaust Solenoid Output Circuit 2 | Diagnostic flag. Needs: Purge | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4166doc 34167 | Comm Loss: Purge Liquid Level Switch Circuit 1 | Diagnostic flag. Needs: Purge | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4167doc 34168 | Comm Loss: Purge Liquid Level Switch Circuit 2 | Diagnostic flag. Needs: Purge | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4168doc 34169 | Comm Loss: Purge Liquid Temperature Circuit 1 | Diagnostic flag. Needs: Purge | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4169doc 34170 | Comm Loss: Purge Liquid Temperature Circuit 2 | Diagnostic flag. Needs: Purge | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4170doc 34171 | Comm Loss: Purge Pumpout Relay Circuit 1 | Diagnostic flag. Needs: Purge | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4171doc 34172 | Comm Loss: Purge Pumpout Relay Circuit 2 | Diagnostic flag. Needs: Purge | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4172doc 34173 | Comm Loss: Purge Pumpout Solenoid Output Circuit 1 | Diagnostic flag. Needs: Purge | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4173doc 34174 | Comm Loss: Purge Pumpout Solenoid Output Circuit 2 | Diagnostic flag. Needs: Purge | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4174doc 34175 | Comm Loss: Purge Regen Solenoid Relay Circuit 1 | Diagnostic flag. Needs: Purge w/Carbon tank | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4175doc 34176 | Comm Loss: Purge Regen Solenoid Relay Circuit 2 | Diagnostic flag. Needs: Purge w/Carbon tank | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4176doc 34177 | Comm Loss: Refrigerant Monitor Input | Diagnostic flag. Needs: Refrigerant Monitor | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4177doc 34178 | Comm Loss: Starter Circuit 1 | Depends on starter/drive options; see the source configuration column. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4178doc 34179 | Comm Loss: Starter Circuit 2 | Depends on starter/drive options; see the source configuration column. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4179doc 34180 | Comm Loss: Starter Fault Circuit 1 | Diagnostic flag. Needs: Solid State Starters Remote Mount Non-Comm AFD | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4180doc 34181 | Comm Loss: Starter Fault Circuit 2 | Diagnostic flag. Needs: Solid State Starters Remote Mount Non-Comm AFD | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4181doc 34182 | Comm Loss: Unit Purge Alarm Relay | Diagnostic flag. Needs: Purge | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4182doc 34183 | Diagnostic: Compressor Did Not Accelerate: Shutdown Circuit 1 | Diagnostic flag. Needs: EM Starters Solid State Starters Remote Mount Non-Comm AFD | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4183doc 34184 | Diagnostic: Compressor Did Not Accelerate: Shutdown Circuit 2 | Diagnostic flag. Needs: EM Starters Solid State Starters Remote Mount Non-Comm AFD | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4184doc 34185 | Diagnostic: Cond Saturated Refrigerant Temp Sensor Circuit 1 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4185doc 34186 | Diagnostic: Cond Saturated Refrigerant Temp Sensor Circuit 2 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4186doc 34187 | Diagnostic: Condenser Diff Water Pressure Xdcr | Diagnostic flag. Needs: Cond Water Flow Measurement - Differential Pressure | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4187doc 34188 | Diagnostic: Condenser Entering Water Pressure | Diagnostic flag. Needs: Cond Water Flow Measurement - Dual Pressure Sensors | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4188doc 34189 | Diagnostic: Condenser Entering Water Temp Sensor | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4189doc 34190 | Diagnostic: Condenser High Pressure Cutout Circuit 1 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4190doc 34191 | Diagnostic: Condenser High Pressure Cutout Circuit 2 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4191doc 34192 | Diagnostic: Condenser Leaving Water Pressure | Diagnostic flag. Needs: Cond Water Flow Measurement - Dual Pressure Sensors | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4192doc 34193 | Diagnostic: Condenser Leaving Water Temp Sensor | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4193doc 34194 | Diagnostic: Condenser Liquid Level Sensor Circuit 1 | Diagnostic flag. Needs: Economizer Bypass | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4194doc 34195 | Diagnostic: Condenser Liquid Level Sensor Circuit 2 | Diagnostic flag. Needs: Economizer Bypass | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4195doc 34196 | Diagnostic: Condenser Refrigerant Pressure Xdcr Circuit 1 | Diagnostic flag. Needs: Cond Pressure Sensor | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4196doc 34197 | Diagnostic: Condenser Refrigerant Pressure Xdcr Circuit 2 | Diagnostic flag. Needs: Cond Pressure Sensor | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4197doc 34198 | Diagnostic: Condenser Water Flow Lost | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4198doc 34199 | Diagnostic: Condenser Water Flow Overdue | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4199doc 34200 | Diagnostic: Cprsr Did Not Accelerate: Transition Circuit 1 | Diagnostic flag. Needs: EM Starters Solid State Starters Remote Mount Non-Comm AFD | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4200doc 34201 | Diagnostic: Cprsr Did Not Accelerate: Transition Circuit 2 | Diagnostic flag. Needs: EM Starters Solid State Starters Remote Mount Non-Comm AFD | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4201doc 34202 | Diagnostic: Cprsr Discharge Refrigerant Temp Sensor Circuit 1 | Diagnostic flag. Needs: Compressor Refrigerant Discharge Temp Sensor | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4202doc 34203 | Diagnostic: Cprsr Discharge Refrigerant Temp Sensor Circuit 2 | Diagnostic flag. Needs: Compressor Refrigerant Discharge Temp Sensor | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4203doc 34204 | Diagnostic: Differential Oil Pressure Overdue Circuit 1 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4204doc 34205 | Diagnostic: Differential Oil Pressure Overdue Circuit 2 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4206doc 34207 | Diagnostic: Emergency Stop | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4207doc 34208 | Diagnostic: Evap Saturated Refrigerant Temp Sensor Circuit 1 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4208doc 34209 | Diagnostic: Evap Saturated Refrigerant Temp Sensor Circuit 2 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4209doc 34210 | Diagnostic: Evaporator Diff Water Pressure Xdcr | Diagnostic flag. Needs: Evap Water Flow Measurement - Differential Pressure | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4210doc 34211 | Diagnostic: Evaporator Entering Water Pressure | Diagnostic flag. Needs: Evap Water Flow Measurement - Dual Pressure Sensors | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4211doc 34212 | Diagnostic: Evaporator Entering Water Temp Sensor | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4212doc 34213 | Diagnostic: Evaporator Leaving Water Pressure | Diagnostic flag. Needs: Evap Water Flow Measurement - Dual Pressure Sensors | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4213doc 34214 | Diagnostic: Evaporator Leaving Water Temp Sensor | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4214doc 34215 | Diagnostic: Evaporator Refrigerant Pressure Xdcr Circuit 1 | Diagnostic flag. Needs: Evap Pressure Sensor | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4215doc 34216 | Diagnostic: Evaporator Refrigerant Pressure Xdcr Circuit 2 | Diagnostic flag. Needs: Evap Pressure Sensor | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4216doc 34217 | Diagnostic: Evaporator Water Flow Lost | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4217doc 34218 | Diagnostic: Evaporator Water Flow Overdue | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4218doc 34219 | Diagnostic: Excessive Loss of Communication | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4221doc 34222 | Diagnostic: Extended Compressor Surge Circuit 1 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4222doc 34223 | Diagnostic: Extended Compressor Surge Circuit 2 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4223doc 34224 | Diagnostic: External Base Loading Setpoint | Diagnostic flag. Needs: Base Loading | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4224doc 34225 | Diagnostic: External Chilled/Hot Water Setpoint | Diagnostic flag. Needs: External Chilled Water Setpoint | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4225doc 34226 | Diagnostic: External Demand Limit Setpoint | Diagnostic flag. Needs: External Demand Limit Setpoint | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4230doc 34231 | Diagnostic: Generator Fault Relay Open Circuit 1 | Diagnostic flag. Needs: Engine/Generator | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4231doc 34232 | Diagnostic: Generator Fault Relay Open Circuit 2 | Diagnostic flag. Needs: Engine/Generator | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4232doc 34233 | Diagnostic: Generator Ready Signal Overdue Circuit 1 | Diagnostic flag. Needs: Engine/Generator | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4233doc 34234 | Diagnostic: Generator Ready Signal Overdue Circuit 2 | Diagnostic flag. Needs: Engine/Generator | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4234doc 34235 | Diagnostic: Heat Recovery Entering Water Temp Sensor | Diagnostic flag. Needs: Heat Recovery | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4235doc 34236 | Diagnostic: Heat Recovery Leaving Water Temp Sensor | Diagnostic flag. Needs: Heat Recovery | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4236doc 34237 | Diagnostic: High Cprsr Rfgt Discharge Temperature Circuit 1 | Diagnostic flag. Needs: Compressor Refrigerant Discharge Temp Sensor | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4237doc 34238 | Diagnostic: High Cprsr Rfgt Discharge Temperature Circuit 2 | Diagnostic flag. Needs: Compressor Refrigerant Discharge Temp Sensor | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4238doc 34239 | Diagnostic: High Differential Refrigerant Pressure Circuit 1 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4239doc 34240 | Diagnostic: High Differential Refrigerant Pressure Circuit 2 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4240doc 34241 | Diagnostic: High Evaporator Refrigerant Temperature Circuit 1 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4241doc 34242 | Diagnostic: High Evaporator Refrigerant Temperature Circuit 2 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4242doc 34243 | Diagnostic: High Evaporator Water Temperature | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4243doc 34244 | Diagnostic: High Inboard Bearing Temperature Circuit 1 | Diagnostic flag. Needs: Bearing Temp Sensors | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4244doc 34245 | Diagnostic: High Inboard Bearing Temperature Circuit 2 | Diagnostic flag. Needs: Bearing Temp Sensors | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4245doc 34246 | Diagnostic: High Motor Winding Temperature 1 Circuit 1 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4246doc 34247 | Diagnostic: High Motor Winding Temperature 1 Circuit 2 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4247doc 34248 | Diagnostic: High Motor Winding Temperature 2 Circuit 1 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4248doc 34249 | Diagnostic: High Motor Winding Temperature 2 Circuit 2 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4249doc 34250 | Diagnostic: High Motor Winding Temperature 3 Circuit 1 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4250doc 34251 | Diagnostic: High Motor Winding Temperature 3 Circuit 2 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4251doc 34252 | Diagnostic: High Oil Temperature Circuit 1 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4252doc 34253 | Diagnostic: High Oil Temperature Circuit 2 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4253doc 34254 | Diagnostic: High Outboard Bearing Pad Temperature 1 Circuit 1 | Diagnostic flag. Needs: CDHH | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4254doc 34255 | Diagnostic: High Outboard Bearing Pad Temperature 1 Circuit 2 | Diagnostic flag. Needs: CDHH | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4255doc 34256 | Diagnostic: High Outboard Bearing Pad Temperature 2 Circuit 1 | Diagnostic flag. Needs: CDHH | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4256doc 34257 | Diagnostic: High Outboard Bearing Pad Temperature 2 Circuit 2 | Diagnostic flag. Needs: CDHH | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4257doc 34258 | Diagnostic: High Outboard Bearing Pad Temperature 3 Circuit 1 | Diagnostic flag. Needs: CDHH | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4258doc 34259 | Diagnostic: High Outboard Bearing Pad Temperature 3 Circuit 2 | Diagnostic flag. Needs: CDHH | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4259doc 34260 | Diagnostic: High Outboard Bearing Temp Circuit 1 | Diagnostic flag. Needs: Bearing Temp Sensors | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4260doc 34261 | Diagnostic: High Outboard Bearing Temp Circuit 2 | Diagnostic flag. Needs: Bearing Temp Sensors | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4261doc 34262 | Diagnostic: High Vacuum Lockout Circuit 1 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4262doc 34263 | Diagnostic: High Vacuum Lockout Circuit 2 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4266doc 34267 | Diagnostic: HPC/High AFD Heat Sink Water Pressure Circuit 1 | Diagnostic flag. Needs: Unit Mount AFD - AFDD,E,F (LF2) Remote Mount Comm AFD - (PF7000) | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4267doc 34268 | Diagnostic: HPC/High AFD Heat Sink Water Pressure Circuit 2 | Diagnostic flag. Needs: Unit Mount AFD - AFDD,E,F (LF2) Remote Mount Comm AFD - (PF7000) | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4268doc 34269 | Diagnostic: Inboard Bearing Temp Sensor Circuit 1 | Diagnostic flag. Needs: Bearing Temp Sensors | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4269doc 34270 | Diagnostic: Inboard Bearing Temp Sensor Circuit 2 | Diagnostic flag. Needs: Bearing Temp Sensors | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4270doc 34271 | Diagnostic: Inverted Condenser Water Temperature | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4271doc 34272 | Diagnostic: Inverted Evaporator Water Temperature | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4272doc 34273 | Diagnostic: Loss of Economizer Bypass Valve Control Circuit 1 | Diagnostic flag. Needs: Economizer Bypass | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4273doc 34274 | Diagnostic: Loss of Economizer Bypass Valve Control Circuit 2 | Diagnostic flag. Needs: Economizer Bypass | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4274doc 34275 | Diagnostic: Low Differential Oil Pressure Circuit 1 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4275doc 34276 | Diagnostic: Low Differential Oil Pressure Circuit 2 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4276doc 34277 | Diagnostic: Low Evap Leaving Water Temp: Unit Off | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4277doc 34278 | Diagnostic: Low Evap Leaving Water Temp: Unit On | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4278doc 34279 | Diagnostic: Low Evaporator Refrigerant Temperature Circuit 1 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4279doc 34280 | Diagnostic: Low Evaporator Refrigerant Temperature Circuit 2 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4280doc 34281 | Diagnostic: Low Evaporator Water Flow | Diagnostic flag. Needs: Evap Water Flow Measurement | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4281doc 34282 | Diagnostic: Low Oil Temperature Circuit 1 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4282doc 34283 | Diagnostic: Low Oil Temperature Circuit 2 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4283doc 34284 | Diagnostic: Momentary Power Loss Circuit 1 | Diagnostic flag. Needs: Momentary Power Loss | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4284doc 34285 | Diagnostic: Momentary Power Loss Circuit 2 | Diagnostic flag. Needs: Momentary Power Loss | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4285doc 34286 | Diagnostic: Motor Current Overload Circuit 1 | Diagnostic flag. Needs: EM Starters Solid State Starters Remote Mount Non-Comm AFD | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4286doc 34287 | Diagnostic: Motor Current Overload Circuit 2 | Diagnostic flag. Needs: EM Starters Solid State Starters Remote Mount Non-Comm AFD | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4287doc 34288 | Diagnostic: Motor Winding Temperature 1 Sensor Circuit 1 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4288doc 34289 | Diagnostic: Motor Winding Temperature 1 Sensor Circuit 2 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4289doc 34290 | Diagnostic: Motor Winding Temperature 2 Sensor Circuit 1 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4290doc 34291 | Diagnostic: Motor Winding Temperature 2 Sensor Circuit 2 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4291doc 34292 | Diagnostic: Motor Winding Temperature 3 Sensor Circuit 1 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4292doc 34293 | Diagnostic: Motor Winding Temperature 3 Sensor Circuit 2 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4293doc 34294 | Diagnostic: MP: Invalid Configuration | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4294doc 34295 | Diagnostic: MP: Reset Has Occurred | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4295doc 34296 | Diagnostic: Oil Pressure Sensor Calibration Circuit 1 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4296doc 34297 | Diagnostic: Oil Pressure Sensor Calibration Circuit 2 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4297doc 34298 | Diagnostic: Oil Pump Discharge Pressure Transducer Circuit 1 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4298doc 34299 | Diagnostic: Oil Pump Discharge Pressure Transducer Circuit 2 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4299doc 34300 | Diagnostic: Oil Tank Pressure Transducer Circuit 1 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4300doc 34301 | Diagnostic: Oil Tank Pressure Transducer Circuit 2 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4301doc 34302 | Diagnostic: Oil Tank Temperature Sensor Circuit 1 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4302doc 34303 | Diagnostic: Oil Tank Temperature Sensor Circuit 2 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4303doc 34304 | Diagnostic: Outboard Bearing Pad Temp 1 Sensor Circuit 1 | Diagnostic flag. Needs: CDHH | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4304doc 34305 | Diagnostic: Outboard Bearing Pad Temp 1 Sensor Circuit 2 | Diagnostic flag. Needs: CDHH | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4305doc 34306 | Diagnostic: Outboard Bearing Pad Temp 2 Sensor Circuit 1 | Diagnostic flag. Needs: CDHH | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4306doc 34307 | Diagnostic: Outboard Bearing Pad Temp 2 Sensor Circuit 2 | Diagnostic flag. Needs: CDHH | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4307doc 34308 | Diagnostic: Outboard Bearing Pad Temp 3 Sensor Circuit 1 | Diagnostic flag. Needs: CDHH | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4308doc 34309 | Diagnostic: Outboard Bearing Pad Temp 3 Sensor Circuit 2 | Diagnostic flag. Needs: CDHH | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4309doc 34310 | Diagnostic: Outboard Bearing Temperature Sensor Circuit 1 | Diagnostic flag. Needs: CDHH | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4310doc 34311 | Diagnostic: Outboard Bearing Temperature Sensor Circuit 2 | Diagnostic flag. Needs: CDHH | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4311doc 34312 | Diagnostic: Outdoor Air Temperature Sensor | Diagnostic flag. Needs: Outdoor Air Temp Sensor | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4312doc 34313 | Diagnostic: Over Voltage Circuit 1 | Diagnostic flag. Needs: Line Voltage Sensing | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4313doc 34314 | Diagnostic: Over Voltage Circuit 2 | Diagnostic flag. Needs: Line Voltage Sensing | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4314doc 34315 | Diagnostic: Phase Loss Circuit 1 | Diagnostic flag. Needs: EM Starters Solid State Starters Remote Mount Non-Comm AFD | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4315doc 34316 | Diagnostic: Phase Loss Circuit 2 | Diagnostic flag. Needs: EM Starters Solid State Starters Remote Mount Non-Comm AFD | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4316doc 34317 | Diagnostic: Phase Reversal Circuit 1 | Diagnostic flag. Needs: EM Starters Solid State Starters Remote Mount Non-Comm AFD | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4317doc 34318 | Diagnostic: Phase Reversal Circuit 2 | Diagnostic flag. Needs: EM Starters Solid State Starters Remote Mount Non-Comm AFD | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4318doc 34319 | Diagnostic: Power Loss Circuit 1 | Diagnostic flag. Needs: EM Starters Solid State Starters Remote Mount Non-Comm AFD | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4319doc 34320 | Diagnostic: Power Loss Circuit 2 | Diagnostic flag. Needs: EM Starters Solid State Starters Remote Mount Non-Comm AFD | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4320doc 34321 | Diagnostic: Purge Carbon Regen Temp Limit Exceeded Circuit 1 | Diagnostic flag. Needs: Purge w/Carbon tank | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4321doc 34322 | Diagnostic: Purge Carbon Regen Temp Limit Exceeded Circuit 2 | Diagnostic flag. Needs: Purge w/Carbon tank | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4322doc 34323 | Diagnostic: Purge Carbon Regen Temp Not Satisfied Circuit 1 | Diagnostic flag. Needs: Purge w/Carbon tank | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4323doc 34324 | Diagnostic: Purge Carbon Regen Temp Not Satisfied Circuit 2 | Diagnostic flag. Needs: Purge w/Carbon tank | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4324doc 34325 | Diagnostic: Purge Carbon Regen Temperature Too Low Circuit 1 | Diagnostic flag. Needs: Purge w/Carbon tank | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4325doc 34326 | Diagnostic: Purge Carbon Regen Temperature Too Low Circuit 2 | Diagnostic flag. Needs: Purge w/Carbon tank | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4326doc 34327 | Diagnostic: Purge Carbon Tank Temperature Sensor Circuit 1 | Diagnostic flag. Needs: Purge w/Carbon tank | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4327doc 34328 | Diagnostic: Purge Carbon Tank Temperature Sensor Circuit 2 | Diagnostic flag. Needs: Purge w/Carbon tank | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4328doc 34329 | Diagnostic: Purge Cprsr Suction Rfgt Temp Sensor Circuit 1 | Diagnostic flag. Needs: Purge | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4329doc 34330 | Diagnostic: Purge Cprsr Suction Rfgt Temp Sensor Circuit 2 | Diagnostic flag. Needs: Purge | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4330doc 34331 | Diagnostic: Purge Daily Pumpout Limit Exceeded Circuit 1 | Diagnostic flag. Needs: Purge | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4331doc 34332 | Diagnostic: Purge Daily Pumpout Limit Exceeded Circuit 2 | Diagnostic flag. Needs: Purge | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4332doc 34333 | Diagnostic: Purge Liquid Level Too High Continuously Circuit 1 | Diagnostic flag. Needs: Purge | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4333doc 34334 | Diagnostic: Purge Liquid Level Too High Continuously Circuit 2 | Diagnostic flag. Needs: Purge | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4334doc 34335 | Diagnostic: Purge Liquid Level Too High Warning Circuit 1 | Diagnostic flag. Needs: Purge | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4335doc 34336 | Diagnostic: Purge Liquid Level Too High Warning Circuit 2 | Diagnostic flag. Needs: Purge | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4336doc 34337 | Diagnostic: Purge Liquid Temperature Sensor Circuit 1 | Diagnostic flag. Needs: Purge | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4337doc 34338 | Diagnostic: Purge Liquid Temperature Sensor Circuit 2 | Diagnostic flag. Needs: Purge | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4338doc 34339 | Diagnostic: Purge Regen Cooldown Temp Too High Circuit 1 | Diagnostic flag. Needs: Purge w/Carbon tank | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4339doc 34340 | Diagnostic: Purge Regen Cooldown Temp Too High Circuit 2 | Diagnostic flag. Needs: Purge w/Carbon tank | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4341doc 34342 | Diagnostic: Refrigerant Monitor Input | Diagnostic flag. Needs: Refrigerant Monitor | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4342doc 34343 | Diagnostic: Restart Inhibit Circuit 1 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4343doc 34344 | Diagnostic: Restart Inhibit Circuit 2 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4344doc 34345 | Diagnostic: Severe Current Unbalance Circuit 1 | Diagnostic flag. Needs: Line Voltage Sensing | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4345doc 34346 | Diagnostic: Severe Current Unbalance Circuit 2 | Diagnostic flag. Needs: Line Voltage Sensing | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4346doc 34347 | Diagnostic: Software Error 1001: Call Trane Service | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4347doc 34348 | Diagnostic: Software Error 1004: Call Trane Service | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4348doc 34349 | Diagnostic: Starter Comm Loss: Main Processor Circuit 1 | Diagnostic flag. Needs: EM Starters Solid State Starters Remote Mount Non-Comm AFD | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4349doc 34350 | Diagnostic: Starter Comm Loss: Main Processor Circuit 2 | Diagnostic flag. Needs: EM Starters Solid State Starters Remote Mount Non-Comm AFD | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4350doc 34351 | Diagnostic: Starter Contactor Interrupt Failure Circuit 1 | Diagnostic flag. Needs: EM Starters Solid State Starters Remote Mount Non-Comm AFD | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4351doc 34352 | Diagnostic: Starter Contactor Interrupt Failure Circuit 2 | Diagnostic flag. Needs: EM Starters Solid State Starters Remote Mount Non-Comm AFD | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4352doc 34353 | Diagnostic: Starter Did Not Fully Accelerate Circuit 1 | Diagnostic flag. Needs: EM Starters Solid State Starters Remote Mount Non-Comm AFD | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4353doc 34354 | Diagnostic: Starter Did Not Fully Accelerate Circuit 2 | Diagnostic flag. Needs: EM Starters Solid State Starters Remote Mount Non-Comm AFD | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4354doc 34355 | Diagnostic: Starter Did Not Transition Circuit 1 | Diagnostic flag. Needs: EM Starters Solid State Starters Remote Mount Non-Comm AFD | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4355doc 34356 | Diagnostic: Starter Did Not Transition Circuit 2 | Diagnostic flag. Needs: EM Starters Solid State Starters Remote Mount Non-Comm AFD | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4356doc 34357 | Diagnostic: Starter Dry Run Test Circuit 1 | Diagnostic flag. Needs: EM Starters Solid State Starters Remote Mount Non-Comm AFD | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4357doc 34358 | Diagnostic: Starter Dry Run Test Circuit 2 | Diagnostic flag. Needs: EM Starters Solid State Starters Remote Mount Non-Comm AFD | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4358doc 34359 | Diagnostic: Starter Failed to Arm/ Start Circuit 1 | Depends on starter/drive options; see the source configuration column. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4359doc 34360 | Diagnostic: Starter Failed to Arm/ Start Circuit 2 | Depends on starter/drive options; see the source configuration column. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4360doc 34361 | Diagnostic: Starter Fault Circuit 1 | Diagnostic flag. Needs: EM Starters Solid State Starters Remote Mount Non-Comm AFD | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4361doc 34362 | Diagnostic: Starter Fault Circuit 2 | Diagnostic flag. Needs: EM Starters Solid State Starters Remote Mount Non-Comm AFD | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4362doc 34363 | Diagnostic: Starter Fault Type I Circuit 1 | Diagnostic flag. Needs: EM Starters Solid State Starters Remote Mount Non-Comm AFD | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4363doc 34364 | Diagnostic: Starter Fault Type I Circuit 2 | Diagnostic flag. Needs: EM Starters Solid State Starters Remote Mount Non-Comm AFD | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4364doc 34365 | Diagnostic: Starter Fault Type II Circuit 1 | Diagnostic flag. Needs: EM Starters Solid State Starters Remote Mount Non-Comm AFD | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4365doc 34366 | Diagnostic: Starter Fault Type II Circuit 2 | Diagnostic flag. Needs: EM Starters Solid State Starters Remote Mount Non-Comm AFD | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4366doc 34367 | Diagnostic: Starter Fault Type III Circuit 1 | Diagnostic flag. Needs: EM Starters Solid State Starters Remote Mount Non-Comm AFD | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4367doc 34368 | Diagnostic: Starter Fault Type III Circuit 2 | Diagnostic flag. Needs: EM Starters Solid State Starters Remote Mount Non-Comm AFD | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4368doc 34369 | Diagnostic: Starter Module Memory Error Type 1 Circuit 1 | Diagnostic flag. Needs: EM Starters Solid State Starters Remote Mount Non-Comm AFD | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4369doc 34370 | Diagnostic: Starter Module Memory Error Type 1 Circuit 2 | Diagnostic flag. Needs: EM Starters Solid State Starters Remote Mount Non-Comm AFD | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4370doc 34371 | Diagnostic: Starter Module Memory Error Type 2 Circuit 1 | Diagnostic flag. Needs: EM Starters Solid State Starters Remote Mount Non-Comm AFD | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4371doc 34372 | Diagnostic: Starter Module Memory Error Type 2 Circuit 2 | Diagnostic flag. Needs: EM Starters Solid State Starters Remote Mount Non-Comm AFD | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4372doc 34373 | Diagnostic: Transition Complete Input Opened Circuit 1 | Diagnostic flag. Needs: EM Starters Solid State Starters Remote Mount Non-Comm AFD | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4373doc 34374 | Diagnostic: Transition Complete Input Opened Circuit 2 | Diagnostic flag. Needs: EM Starters Solid State Starters Remote Mount Non-Comm AFD | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4374doc 34375 | Diagnostic: Transition Complete Input Shorted Circuit 1 | Diagnostic flag. Needs: EM Starters Solid State Starters Remote Mount Non-Comm AFD | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4375doc 34376 | Diagnostic: Transition Complete Input Shorted Circuit 2 | Diagnostic flag. Needs: EM Starters Solid State Starters Remote Mount Non-Comm AFD | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4376doc 34377 | Diagnostic: Under Voltage Circuit 1 | Diagnostic flag. Needs: Line Voltage Sensing | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4377doc 34378 | Diagnostic: Under Voltage Circuit 2 | Diagnostic flag. Needs: Line Voltage Sensing | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4378doc 34379 | Diagnostic: Unexpected Differential Oil Pressure Circuit 1 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4379doc 34380 | Diagnostic: Unexpected Differential Oil Pressure Circuit 2 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4380doc 34381 | Diagnostic: Unexpected Starter Shutdown Circuit 1 | Depends on starter/drive options; see the source configuration column. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4381doc 34382 | Diagnostic: Unexpected Starter Shutdown Circuit 2 | Depends on starter/drive options; see the source configuration column. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4382doc 34383 | Diagnostic: AFD Bus Over Voltage Circuit 1 | Depends on starter/drive options; see the source configuration column. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4383doc 34384 | Diagnostic: AFD Bus Over Voltage Circuit 2 | Depends on starter/drive options; see the source configuration column. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4384doc 34385 | Diagnostic: AFD Bus Under Voltage Circuit 1 | Depends on starter/drive options; see the source configuration column. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4385doc 34386 | Diagnostic: AFD Bus Under Voltage Circuit 2 | Depends on starter/drive options; see the source configuration column. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4386doc 34387 | Diagnostic: AFD Motor Fault Circuit 1 | Diagnostic flag. Needs: Remote Mount Comm AFD - VFDB (PF6000) | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4387doc 34388 | Diagnostic: AFD Motor Fault Circuit 2 | Diagnostic flag. Needs: Remote Mount Comm AFD - VFDB (PF6000) | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4388doc 34389 | Diagnostic: AFD Precharge Fault Circuit 1 | Diagnostic flag. Needs: Remote Mount Comm AFD - VFDB (PF6000) | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4389doc 34390 | Diagnostic: AFD Precharge Fault Circuit 2 | Diagnostic flag. Needs: Remote Mount Comm AFD - VFDB (PF6000) | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4390doc 34391 | Diagnostic: AFD Over Temperature Circuit 1 | Diagnostic flag. Needs: Remote Mount Comm AFD - VFDB (PF6000) | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4391doc 34392 | Diagnostic: AFD Over Temperature Circuit 2 | Diagnostic flag. Needs: Remote Mount Comm AFD - VFDB (PF6000) | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4392doc 34393 | Diagnostic: AFD Mains Phase Loss Circuit 1 | Diagnostic flag. Needs: TR200 Modbus AFD | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4393doc 34394 | Diagnostic: AFD Mains Phase Loss Circuit 2 | Diagnostic flag. Needs: TR200 Modbus AFD | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4394doc 34395 | Diagnostic: AFD Motor Current Overload Circuit 1 | Diagnostic flag. Needs: TR200 Modbus AFD | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4395doc 34396 | Diagnostic: AFD Motor Current Overload Circuit 2 | Diagnostic flag. Needs: TR200 Modbus AFD | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4396doc 34397 | Diagnostic: AFD Ground Fault Circuit 1 | Diagnostic flag. Needs: TR200 Modbus AFD | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4397doc 34398 | Diagnostic: AFD Ground Fault Circuit 2 | Diagnostic flag. Needs: TR200 Modbus AFD | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4398doc 34399 | Diagnostic: AFD Short Circuit Circuit 1 | Diagnostic flag. Needs: TR200 Modbus AFD | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4399doc 34400 | Diagnostic: AFD Short Circuit Circuit 2 | Diagnostic flag. Needs: TR200 Modbus AFD | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4400doc 34401 | Diagnostic: AFD Safe Stop Circuit 1 | Diagnostic flag. Needs: TR200 Modbus AFD | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4401doc 34402 | Diagnostic: AFD Safe Stop Circuit 2 | Diagnostic flag. Needs: TR200 Modbus AFD | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4402doc 34403 | Diagnostic: AFD Fault Circuit 1 | Diagnostic flag. Needs: TR200 Modbus AFD | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4403doc 34404 | Diagnostic: AFD Fault Circuit 2 | Diagnostic flag. Needs: TR200 Modbus AFD | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4404doc 34405 | Diagnostic: AFD Speed Configuration Mismatch Circuit 1 | Diagnostic flag. Needs: TR200 Modbus AFD | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4405doc 34406 | Diagnostic: AFD Speed Configuration Mismatch Circuit 2 | Diagnostic flag. Needs: TR200 Modbus AFD | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4406doc 34407 | Diagnostic: AFD General Failure Circuit 1 | Diagnostic flag. Needs: TR200 Modbus AFD | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4407doc 34408 | Diagnostic: AFD General Failure Circuit 2 | Diagnostic flag. Needs: TR200 Modbus AFD | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4408doc 34409 | Comm Loss: Heat Recovery Differential Water Pressure | Diagnostic flag. Needs: Heat Recovery | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4409doc 34410 | Comm Loss: Heat Recovery Entering Water Pressure | Diagnostic flag. Needs: Heat Recovery | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4410doc 34411 | Comm Loss: Heat Recovery Leaving Water Pressure | Diagnostic flag. Needs: Heat Recovery | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4411doc 34412 | Comm Loss: Heat Recovery Water Flow Switch | Diagnostic flag. Needs: Heat Recovery | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4412doc 34413 | Comm Loss: External Diagnostic Reset | Diagnostic flag. Needs: External Diagnostic Reset | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4413doc 34414 | Diagnostic: Heat Recovery Diff Water Pressure | Diagnostic flag. Needs: Heat Recovery | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4414doc 34415 | Diagnostic: Heat Recovery Entering Water Pressure | Diagnostic flag. Needs: Heat Recovery | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4415doc 34416 | Diagnostic: Heat Recovery Leaving Water Pressure | Diagnostic flag. Needs: Heat Recovery | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4416doc 34417 | Diagnostic: Inverted Heat Recovery Water Temperature | Diagnostic flag. Needs: Heat Recovery | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4417doc 34418 | Comm Loss: Condenser Rfgt Valve Feedback Circuit 1 | Diagnostic flag. Needs: 6" Control Valves | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4418doc 34419 | Comm Loss: Condenser Rfgt Valve Feedback Circuit 2 | Diagnostic flag. Needs: 6" Control Valves | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4419doc 34420 | Comm Loss: Economizer Rfgt Valve Feedback Circuit 1 | Diagnostic flag. Needs: 6" Control Valves | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4420doc 34421 | Comm Loss: Economizer Rfgt Valve Feedback Circuit 2 | Diagnostic flag. Needs: 6" Control Valves | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4421doc 34422 | Comm Loss: Economizer Refrigerant Pressure Circuit 1 | Diagnostic flag. Needs: 6" or 8" Control Valves | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4422doc 34423 | Comm Loss: Economizer Refrigerant Pressure Circuit 2 | Diagnostic flag. Needs: 6" or 8" Control Valves | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4423doc 34424 | Diagnostic: Economizer Rfgt Valve Loss of Control Circuit 1 | Diagnostic flag. Needs: 6" or 8" Control Valves | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4424doc 34425 | Diagnostic: Economizer Rfgt Valve Loss of Control Circuit 2 | Diagnostic flag. Needs: 6" or 8" Control Valves | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4425doc 34426 | Diagnostic: Condenser Rfgt Valve Loss of Control Circuit 1 | Diagnostic flag. Needs: 6" or 8" Control Valves | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4426doc 34427 | Diagnostic: Condenser Rfgt Valve Loss of Control Circuit 2 | Diagnostic flag. Needs: 6" or 8" Control Valves | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4427doc 34428 | Diagnostic: Low Condenser Water Flow | Diagnostic flag. Needs: Hot Water Control | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4428doc 34429 | Diagnostic: Low Heat Recovery Water Flow | Diagnostic flag. Needs: Heat Recovery | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4429doc 34430 | Diagnostic: Economizer Refrigerant Pressure Circuit 1 | Diagnostic flag. Needs: 6" or 8" Control Valves | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4430doc 34431 | Diagnostic: Economizer Refrigerant Pressure Circuit 2 | Diagnostic flag. Needs: 6" or 8" Control Valves | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4431doc 34432 | Diagnostic: AFD Inverter Heatsink Over Temp Circuit 1 | Diagnostic flag. Needs: UM AFD w/o THD filter (Inovance) MV Remote Mount COMM AFD (Inovance) | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4432doc 34433 | Diagnostic: AFD Emergency Stop Fault Circuit 1 | Diagnostic flag. Needs: UM AFD w/o THD filter (Inovance) MV Remote Mount COMM AFD (Inovance) | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4433doc 34434 | Diagnostic: AFD Drive Fault Circuit 1 | Diagnostic flag. Needs: UM AFD w/o THD filter (Inovance) MV Remote Mount COMM AFD (Inovance) | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4434doc 34435 | Diagnostic: AFD Inverter Heatsink Over Temp Circuit 2 | Diagnostic flag. Needs: UM AFD w/o THD filter (Inovance) MV Remote Mount COMM AFD (Inovance) | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4435doc 34436 | Diagnostic: AFD Emergency Stop Fault Circuit 2 | Diagnostic flag. Needs: UM AFD w/o THD filter (Inovance) MV Remote Mount COMM AFD (Inovance) | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4436doc 34437 | Diagnostic: AFD Drive Fault Circuit 2 | Diagnostic flag. Needs: UM AFD w/o THD filter (Inovance) MV Remote Mount COMM AFD (Inovance) | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4437doc 34438 | Comm Loss: Condenser Rfgt Valve Circuit 1 | Diagnostic flag. Needs: 8" Control Valves | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4438doc 34439 | Comm Loss: Condenser Rfgt Valve Circuit 2 | Diagnostic flag. Needs: 8" Control Valves | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4439doc 34440 | Comm Loss: Economizer Rfgt Valve Circuit 1 | Diagnostic flag. Needs: 8" Control Valves | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4440doc 34441 | Comm Loss: Economizer Rfgt Valve Circuit 2 | Diagnostic flag. Needs: 8" Control Valves | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| HR | 10doc 40011 | Chilled Water Setpoint | Temperature in the factory unit system (I-P or SI). | FLOAT32 | ABCD | Read/write | |||
| HR | 12doc 40013 | Demand Limit Setpoint | FLOAT32 | ABCD | % | Read/write | |||
| HR | 14doc 40015 | Hot Water Setpoint | Temperature in the factory unit system (I-P or SI). Needs: Hot Water Control | FLOAT32 | ABCD | Read/write | |||
| HR | 16doc 40017 | Base Loading Setpoint | Needs: Base Loading | FLOAT32 | ABCD | % | Read/write | ||
| HR | 18doc 40019 | BAS Cooling Differential to Start | Temperature difference, factory unit system (I-P or SI). | FLOAT32 | ABCD | Read/write | |||
| HR | 20doc 40021 | BAS Cooling Differential to Stop | Temperature difference, factory unit system (I-P or SI). | FLOAT32 | ABCD | Read/write | |||
| HR | 22doc 40023 | BAS Heating Differential to Start | Temperature difference, factory unit system (I-P or SI). Needs: Hot Water Control | FLOAT32 | ABCD | Read/write | |||
| HR | 24doc 40025 | BAS Heating Differential to Stop | Temperature difference, factory unit system (I-P or SI). Needs: Hot Water Control | FLOAT32 | ABCD | Read/write | |||
| HR | 2010doc 42011 | Chiller Mode Command BAS | UINT16 | Read/write | 1 = Cool; 2 = Heat; 3 = Ice Making; 4 = Free Cooling | ||||
| HR | 3010doc 43011 | Base Loading Request | Needs: Base Loading | UINT16 | Read/write | 0 = Off; 1 = On | |||
| HR | 3011doc 43012 | Reset Diagnostic | UINT16 | Read/write | 0 = Normal; 1 = Reset | ||||
| HR | 3012doc 43013 | Evaporator Water Pump Request BAS | UINT16 | Read/write | 0 = Auto; 1 = On | ||||
| HR | 3013doc 43014 | Condenser Water Pump Request BAS | UINT16 | Read/write | 0 = Auto; 1 = On | ||||
| HR | 3014doc 43015 | Chiller Auto Stop Command BAS | UINT16 | Read/write | 0 = Stop; 1 = Auto | ||||
| HR | 3015doc 43016 | Circuit 1 Lockout BAS | UINT16 | Read/write | 0 = Normal; 1 = Locked Out | ||||
| HR | 3016doc 43017 | Circuit 2 Lockout BAS | UINT16 | Read/write | 0 = Normal; 1 = Locked Out | ||||
| HR | 3017doc 43018 | Energy Consumption Reset | Depends on starter/drive options; see the source configuration column. | UINT16 | Read/write | 0 = Accumulating; 1 = Reset |
Notes on this map
- Register format table: analog points are 32-bit floats sent high word / high byte first (NaN = invalid); binary and multi-state points are unsigned 16-bit integers (0xFFFF = invalid).
- Values are sent in the unit system ordered from the factory (I-P is the usual default, SI optional); the list names only the quantity, so temperature/pressure/flow units are left blank here.
- Not every point exists on every unit: the controller builds its point set from the unit's configuration. Descriptions name the configuration a point depends on.
- Register numbers are printed in 5-digit Modicon form (3xxxx input registers, 4xxxx holding registers) and converted here to wire addresses (30011 = input register 10).
- Controller setup, serial defaults and the I-P/SI units statement come from the list's named reference document, Trane's Symbio 800 BACnet and Modbus integration guide BAS-SVP083B-EN (15 Nov 2024, https://elibrary.tranetechnologies.com/public/commercial-hvac/Literature/Integration/BAS-SVP083B-EN_11152024.pdf).
- The document carries separate Simplex and Duplex tables that reuse the same register numbers for different points; do not mix them.
- The 'Diagnostic Codes' pages (code number to text for the Last Diagnostic Code points) are not reproduced.
- This is the Symbio 800 register set. Duplex CenTraVacs with the older UC800/Tracer AdaptiView controller use a different native map (see centravac-duplex-uc800).
Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.
Questions about the Trane CenTraVac duplex centrifugal chiller (Symbio 800)
What Modbus registers does the Trane CenTraVac duplex centrifugal chiller (Symbio 800) have?
This map lists 717 registers: 700 input registers, 17 holding registers. 17 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.
Are the Trane CenTraVac duplex centrifugal chiller (Symbio 800) Modbus addresses 0-based or 1-based?
The manufacturer's document numbers registers Modicon 3xxxx/4xxxx (drop the prefix, subtract 1). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. The list prints Modicon register numbers: 3xxxx are input registers and 4xxxx holding registers, so 30011 is input register address 10 and 42011 is holding register address 2010.
What byte order does the Trane CenTraVac duplex centrifugal chiller (Symbio 800) use for 32-bit values?
Multi-register values in this map use ABCD (high word first (big-endian)). Set your client to this order for every 32/64-bit value in the table.
What are the minimum Modbus registers to integrate the Trane CenTraVac duplex centrifugal chiller (Symbio 800)?
Start with IR 10 Active Chilled Water Setpoint (Active chilled water setpoint); IR 22 Evaporator Leaving Water Temperature (Evaporator leaving water temperature); IR 24 Evaporator Entering Water Temperature (Evaporator entering water temperature); IR 2010 Running Mode (Running mode); IR 3020 Chiller Running State (Chiller running state); IR 3025 Diagnostic Present (Diagnostic present); HR 10 Chilled Water Setpoint (Chilled water setpoint (BAS)); HR 2010 Chiller Mode Command BAS (BAS chiller mode command); HR 3014 Chiller Auto Stop Command BAS (Chiller auto/stop command (BAS)); HR 3011 Reset Diagnostic (Reset diagnostic).
How do I enable Modbus control of the Trane CenTraVac duplex centrifugal chiller (Symbio 800)?
On the Symbio 800 web interface go to Installation > Identification and Communications > Protocol Configuration and select Modbus RTU or Modbus TCP (per Trane's Symbio 800 integration guides).
Where is the official Trane CenTraVac duplex centrifugal chiller (Symbio 800) Modbus documentation?
The source is Symbio 800 Integration Points List, BACnet/Modbus, CenTraVac (BAS-PTS009C-EN), revision 2025-12-12, published free by Trane at https://elibrary.tranetechnologies.com/public/commercial-hvac/Literature/Points%20List/BAS-PTS009C-EN_12122025.pdf.
More Trane Modbus register maps
- Chiller
Trane Agility water-cooled centrifugal chiller (Symbio 800)
Trane Agility water-cooled chillers with Symbio 800 controls, as listed in BAS-PTS007C-EN (6/30/2026).
Also known as: Agility, HDWA, Agility water-cooled chiller - Chiller
Trane Ascend ACR Series C air-cooled chiller (Symbio 800)
Trane Ascend model ACR Series C air-cooled chillers with the Symbio 800 controller, as listed in BAS-PTS021A-EN (11/15/2024).
Also known as: ACR, Ascend ACR, ACR Series C, Ascend air-cooled chiller ACR - Chiller
Trane Ascend ACS / ACX air-cooled scroll chiller and heat pump (Symbio 800)
Trane Ascend ACS air-cooled scroll chillers and ACX air-to-water heat pumps with the Symbio 800 controller, as listed in BAS-PTS011A-EN (11/15/2024).
Also known as: ACS, ACX, Ascend ACS, Ascend ACX, Ascend air-cooled chiller, Ascend air-to-water heat pump - Chiller
Trane CenTraVac CTV-Duplex water-cooled centrifugal chiller (UC800 native Modbus)
Trane Duplex CenTraVac (two-compressor) water-cooled centrifugal chillers with the Tracer UC800 controller, as listed in the Modbus section of BAS-PTS030A-EN (12/6/2024).
Also known as: CTV-Duplex, CTVD, CenTraVac Duplex, Duplex CenTraVac UC800 - Chiller
Trane CenTraVac simplex centrifugal chiller (Symbio 800)
Trane single-compressor (simplex) CenTraVac water-cooled centrifugal chillers fitted with the Symbio 800 controller, as listed in the Simplex tables of BAS-PTS009C-EN (12/12/2025).
Also known as: CVHE, CVHF, CVHG, CVHH, CVHL, CVHM, CVHS, CVGF, CVR, CVZA, CVXA, CenTraVac Simplex Symbio 800, CenTraVac simplex - Chiller
Trane CGAM air-cooled scroll chiller (Symbio 800)
Trane CGAM air-cooled scroll chillers with the Symbio 800 controller, as listed in BAS-PTS019A-EN (11/15/2024).
Also known as: CGAM, Trane CGAM, CGAM air-cooled scroll chiller - Chiller
Trane RTAC air-cooled helical-rotary chiller (Symbio 800)
Trane RTAC air-cooled helical-rotary chillers with the Symbio 800 controller, as listed in BAS-PTS023A-EN (11/8/2024).
Also known as: RTAC, Series R RTAC - Chiller
Trane RTAC air-cooled helical-rotary chiller (UC800 native Modbus profile)
Trane RTAC air-cooled chillers on the Tracer UC800 controller using the UC800 native Modbus map in the Modbus section of BAS-PTS032A-EN (12/6/2024). Not the same register set as the Symbio 800 RTAC list (BAS-PTS023A-EN).
Also known as: RTAC UC800 native Modbus profile, Series R RTAC UC800 native Modbus, BAS-PTS032A-EN - Chiller
Trane Series R RTHD water-cooled helical-rotary chiller (Symbio 800)
Trane Series R model RTHD water-cooled helical-rotary chillers with the Symbio 800 controller, as listed in BAS-PTS015A-EN (11/15/2024).
Also known as: RTHD, Series R RTHD - Chiller
Trane Series R RTWD water-cooled helical-rotary chiller (Symbio 800)
Trane Series R model RTWD water-cooled helical-rotary chillers with the Symbio 800 controller, as listed in BAS-PTS017A-EN (11/15/2024).
Also known as: RTWD, Series R RTWD, RTUD - Chiller
Trane Sintesis RTAF air-cooled screw chiller (Symbio 800)
Trane Sintesis RTAF air-cooled helical-rotary chillers with the Symbio 800 controller, as listed in BAS-PTS013B-EN (4/7/2026).
Also known as: RTAF, Sintesis RTAF, Sintesis air-cooled chiller - Pump (data-centre coolant distribution unit)
Trane TCDU coolant distribution unit (data-centre liquid cooling)
Trane Coolant Distribution Unit (TCDU) for direct-to-chip liquid cooling, as documented in IOM DC-SVX001A-EN (April 2025).
Also known as: TCDU, Trane CDU, Trane Coolant Distribution Unit, DC-SVX001A - Sensor (refrigerant leak monitor for chiller plant rooms)
Trane TruSense RMWH refrigerant monitor (up to 16 points)
Trane TruSense RMWH multipoint photoacoustic refrigerant monitor with Modbus RTU selected, per IOM PART-SVX008A-EN (30 Sep 2025, preliminary).
Also known as: TruSense, RMWH, Trane refrigerant monitor, PART-SVX008A, RMWH-SVX001
Other chillers & heat pumps register maps
- Chiller (water-cooled)
Daikin Applied EWWD-VZ / EWWH-VZ / EWWS-VZ water-cooled inverter screw chillers (Microtech, Adam software)
EWWD-VZ, EWWH-VZ and EWWS-VZ water-cooled inverter screw chillers with Microtech III or Microtech 4 controller running Adam software, per D-EIGOC00201-22_03EN.
Also known as: EWWD-VZ, EWWH-VZ, EWWS-VZ, EWWD(H)(S)_VZ, EWWD~VZ, EWWH~VZ, Daikin EWWD VZ, Adam - Chiller
Daikin Applied Navigator WWV / TWV water-cooled screw chiller (MicroTech controller)
Daikin Applied Navigator WWV and TWV water-cooled screw chillers with the MicroTech chiller unit controller and Modbus communication module, per ED 15121-13.
Also known as: WWV, TWV, Navigator WWV, Navigator TWV, Daikin Navigator, ED 15121 - Chiller
Aermec WTX water-cooled chiller with Turbocor compressors (pCO5+ BMS)
Aermec WTX oil-free (Danfoss Turbocor) water-cooled chillers with the pCO5+ controller, via the AER485P1 RS485 card or AERNET; BMS manual for WTX 5009100_00 (1705).
Also known as: WTX, TBX - Chiller
Daikin Applied Magnitude WMT magnetic-bearing centrifugal chiller (MicroTech controller)
Daikin Applied Magnitude WMT water-cooled magnetic-bearing centrifugal chillers with the MicroTech unit controller and BACnet/Modbus communication module set to Modbus, per ED 19131-1.
Also known as: WMT, Magnitude WMT, Daikin WMT, ED 19131 - Chiller
Daikin Applied Trailblazer AGZ-F air-cooled scroll chiller (MicroTech controller)
Daikin Applied Trailblazer AGZ F-vintage air-cooled scroll chillers with the MicroTech unit controller and BACnet/Modbus communication module set to Modbus, per ED 19131-1 (application 1.2.0 and later).
Also known as: AGZ-F, AGZ F-Vintage, Trailblazer AGZ, Trailblazer AGZ-F, ED 19131 - Chiller
Daikin Applied Magnitude WMC-E magnetic-bearing centrifugal chiller (MicroTech controller)
Daikin Applied Magnitude WMC E-vintage water-cooled magnetic-bearing centrifugal chillers with the MicroTech unit controller and BACnet/Modbus communication module set to Modbus, per ED 19131-1.
Also known as: WMC-E, WMC E-Vintage, Magnitude WMC, Daikin WMC, ED 19131
All chillers & heat pumps Modbus register maps →
Source: Symbio 800 Integration Points List, BACnet/Modbus, CenTraVac · BAS-PTS009C-EN · rev. 2025-12-12. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.