Chiller · Modbus register map

Trane CenTraVac duplex centrifugal chiller (Symbio 800) Modbus register map

Updated 19 November 2026

Short answer

Trane's duplex CenTraVac pairs two centrifugal compressors on separate refrigerant circuits in one water-cooled chiller. With the Symbio 800 controller it serves BACnet and Modbus RTU/TCP from one points list. This map covers analog inputs for both circuits (water temperatures and flows, refrigerant and oil pressures, purge, starter/drive and energy values), BAS setpoints, binary status points, circuit lockouts, multi-state modes and the diagnostic flags.

This page lists 717 Modbus registers for the Trane CenTraVac duplex centrifugal chiller (Symbio 800) — 17 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Trane’s own free documentation (linked below) and checked against it.

Manufacturer
Trane
Model
CenTraVac duplex centrifugal chiller (Symbio 800)
Equipment type
Chiller
Registers
717 (17 writable)
Transport
Modbus RTU, Modbus TCP
Default unit ID
Not stated
Default serial
19200 baud, 8E1
Documented addressing
Modicon 3xxxx/4xxxx (drop the prefix, subtract 1)
32-bit word order
ABCD high word first (big-endian)
Also known as
CDHF, CDHG, CDHH, CenTraVac Duplex Symbio 800
Source document
Symbio 800 Integration Points List, BACnet/Modbus, CenTraVac · BAS-PTS009C-EN · rev. 2025-12-12
Download CSV all columns JSON Manufacturer PDF ↗

Integration notes: Trane CenTraVac duplex centrifugal chiller (Symbio 800)

Integration in brief

Read the analog inputs as pairs of input registers (float, high word first) and the binary/multi-state points as single registers. Write the BAS setpoints and command points in the 4xxxx holding range.

Minimum registers to map

Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.

RegisterNameTypeWhyAccess
IR 10Active Chilled Water SetpointFLOAT32 ABCDActive chilled water setpointRead
IR 22Evaporator Leaving Water TemperatureFLOAT32 ABCDEvaporator leaving water temperatureRead
IR 24Evaporator Entering Water TemperatureFLOAT32 ABCDEvaporator entering water temperatureRead
IR 2010Running ModeUINT16Running modeRead
IR 3020Chiller Running StateUINT16Chiller running stateRead
IR 3025Diagnostic PresentUINT16Diagnostic presentRead
HR 10Chilled Water SetpointFLOAT32 ABCDChilled water setpoint (BAS)Read/write
HR 2010Chiller Mode Command BASUINT16BAS chiller mode commandRead/write
HR 3014Chiller Auto Stop Command BASUINT16Chiller auto/stop command (BAS)Read/write
HR 3011Reset DiagnosticUINT16Reset diagnosticRead/write

Enable Modbus control & writes

On the Symbio 800 web interface go to Installation > Identification and Communications > Protocol Configuration and select Modbus RTU or Modbus TCP (per Trane's Symbio 800 integration guides).

Byte order & addressing

Network setup

Watch out for

Trane CenTraVac duplex centrifugal chiller (Symbio 800) Modbus registers

Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.

717 of 717 shown
Trane CenTraVac duplex centrifugal chiller (Symbio 800) Modbus register map
TableAddressNameDescriptionTypeOrderScaleUnitsAccessValues / bits
IR10doc 30011Active Chilled Water SetpointTemperature in the factory unit system (I-P or SI).FLOAT32ABCDRead
IR12doc 30013Chilled Water Setpoint StatusTemperature in the factory unit system (I-P or SI).FLOAT32ABCDRead
IR14doc 30015Active Base Loading SetpointNeeds: Base LoadingFLOAT32ABCD%Read
IR16doc 30017Hot Water Setpoint ActiveTemperature in the factory unit system (I-P or SI). Needs: Hot Water ControlFLOAT32ABCDRead
IR18doc 30019Calculated Chiller CapacityCooling capacity in the factory unit system (I-P or SI). Needs: Evap Water Flow SensingFLOAT32ABCDRead
IR20doc 30021Active Cool/Heat Setpoint TemperatureTemperature in the factory unit system (I-P or SI).FLOAT32ABCDRead
IR22doc 30023Evaporator Leaving Water TemperatureTemperature in the factory unit system (I-P or SI).FLOAT32ABCDRead
IR24doc 30025Evaporator Entering Water TemperatureTemperature in the factory unit system (I-P or SI).FLOAT32ABCDRead
IR26doc 30027Condenser Entering Water TemperatureTemperature in the factory unit system (I-P or SI).FLOAT32ABCDRead
IR28doc 30029Condenser Leaving Water TemperatureTemperature in the factory unit system (I-P or SI).FLOAT32ABCDRead
IR30doc 30031Evaporator Water Flow RateNeeds: Evap Water Flow SensingFLOAT32ABCDRead
IR32doc 30033Evaporator Differential Water PressureNeeds: Evap Water Flow Differential Pressure or Dual Pressure SensorsFLOAT32ABCDRead
IR34doc 30035Condenser Water Flow RateNeeds: Cond Water Flow SensingFLOAT32ABCDRead
IR36doc 30037Condenser Differential Water PressureNeeds: Cond Water Flow Differential Pressure or Dual Pressure SensorsFLOAT32ABCDRead
IR38doc 30039AFD Last Diagnostic Code Ckt1Needs: Unit Mount AFD (LF2) Remote Mount Comm AFD (PF7000) Remote Mount Comm AFD (PF6000)FLOAT32ABCDRead
IR40doc 30041Unit Source ID (Last Diagnostic Code)FLOAT32ABCDRead
IR42doc 30043Refrigerant MonitorRefrigerant concentration reading. Needs: Refrigerant MonitorFLOAT32ABCDRead
IR44doc 30045Evaporator Refrigerant Pressure Circuit 1Pressure in the factory unit system (I-P or SI).FLOAT32ABCDRead
IR46doc 30047Condenser Refrigerant Pressure Circuit 1Pressure in the factory unit system (I-P or SI).FLOAT32ABCDRead
IR48doc 30049Differential Refrigerant Pressure Circuit 1Differential pressure in the factory unit system (I-P or SI).FLOAT32ABCDRead
IR50doc 30051Low Side Oil Pressure - Compressor 1APressure in the factory unit system (I-P or SI).FLOAT32ABCDRead
IR52doc 30053High Side Oil Pressure - Compressor 1APressure in the factory unit system (I-P or SI).FLOAT32ABCDRead
IR54doc 30055Oil Differential Pressure Circuit 1Differential pressure in the factory unit system (I-P or SI).FLOAT32ABCDRead
IR56doc 30057Oil Temperature - Compressor 1ATemperature in the factory unit system (I-P or SI).FLOAT32ABCDRead
IR58doc 30059Evaporator Saturated Refrigerant Temperature Circuit 1Temperature in the factory unit system (I-P or SI).FLOAT32ABCDRead
IR60doc 30061Condenser Saturated Refrigerant Temperature Circuit 1Temperature in the factory unit system (I-P or SI).FLOAT32ABCDRead
IR62doc 30063Refrigerant Discharge Temperature - Compressor 1ATemperature in the factory unit system (I-P or SI). Needs: Compressor Refrigerant Discharge TemperatureFLOAT32ABCDRead
IR64doc 30065Inlet Guide Vane 1 Percent Open Circuit 1FLOAT32ABCD%Read
IR66doc 30067Inlet Guide Vane 2 Percent Open Circuit 1Needs: Dual IGVFLOAT32ABCD%Read
IR68doc 30069Purge Carbon Tank Temperature Circuit 1Temperature in the factory unit system (I-P or SI). Needs: Purge w/Carbon TankFLOAT32ABCDRead
IR70doc 30071Purge Liquid Temperature Circuit 1Temperature in the factory unit system (I-P or SI). Needs: PurgeFLOAT32ABCDRead
IR72doc 30073Purge Refrigerant Compressor Suction Temperature Circuit 1Temperature in the factory unit system (I-P or SI). Needs: PurgeFLOAT32ABCDRead
IR74doc 30075Time Until Next Purge Run Circuit 1 (in seconds)Needs: PurgeFLOAT32ABCDsRead
IR76doc 30077Purge Pumpout Chiller On % (7 Days) Circuit 1Needs: PurgeFLOAT32ABCD%Read
IR78doc 30079Purge Pumpout Chiller Off % (7 Days) Circuit 1Needs: PurgeFLOAT32ABCD%Read
IR80doc 30081Purge 24 Hour Pumpout Circuit 1 (in seconds)Needs: PurgeFLOAT32ABCDsRead
IR82doc 30083Purge Pumpout - Life Circuit 1 (in seconds)Needs: PurgeFLOAT32ABCDsRead
IR84doc 30085Refrigeration - Life Circuit 1 (in seconds)Needs: PurgeFLOAT32ABCDsRead
IR86doc 30087Starts - Compressor 1AFLOAT32ABCDRead
IR88doc 30089Run Time - Compressor 1A (in seconds)FLOAT32ABCDsRead
IR90doc 30091Phase AB Voltage - Compressor 1ADepends on starter/drive options; see the source configuration column.FLOAT32ABCDRead
IR92doc 30093Phase BC Voltage - Compressor 1ADepends on starter/drive options; see the source configuration column.FLOAT32ABCDRead
IR94doc 30095Phase CA Voltage - Compressor 1ADepends on starter/drive options; see the source configuration column.FLOAT32ABCDRead
IR96doc 30097Starter Average Phase Volt Circuit 1Depends on starter/drive options; see the source configuration column.FLOAT32ABCDRead
IR98doc 30099Line 1 Current - Compressor 1ADepends on starter/drive options; see the source configuration column.FLOAT32ABCDRead
IR100doc 30101Line 2 Current - Compressor 1ADepends on starter/drive options; see the source configuration column.FLOAT32ABCDRead
IR102doc 30103Line 3 Current - Compressor 1ADepends on starter/drive options; see the source configuration column.FLOAT32ABCDRead
IR104doc 30105Average Line Current Circuit 1Depends on starter/drive options; see the source configuration column.FLOAT32ABCDRead
IR106doc 30107Line 1 Current RLA - Compressor 1ADepends on starter/drive options; see the source configuration column.FLOAT32ABCD%Read
IR108doc 30109Line 2 Current RLA - Compressor 1ADepends on starter/drive options; see the source configuration column.FLOAT32ABCD%Read
IR110doc 30111Line 3 Current RLA - Compressor 1ADepends on starter/drive options; see the source configuration column.FLOAT32ABCD%Read
IR112doc 30113Actual Running CapacityDepends on starter/drive options; see the source configuration column.FLOAT32ABCD%Read
IR116doc 30117Starter Load Power Factor - Compressor 1ADepends on starter/drive options; see the source configuration column.FLOAT32ABCDRead
IR118doc 30119Inboard Bearing Temperature Circuit 1Temperature in the factory unit system (I-P or SI). Needs: Bearing Temperature SensorFLOAT32ABCDRead
IR120doc 30121Outboard Bearing Temperature Circuit 1Temperature in the factory unit system (I-P or SI). Needs: Bearing Temperature SensorFLOAT32ABCDRead
IR122doc 30123Motor Winding Temperature 1 Circuit 1Temperature in the factory unit system (I-P or SI).FLOAT32ABCDRead
IR124doc 30125Motor Winding Temperature 2 Circuit 1Temperature in the factory unit system (I-P or SI).FLOAT32ABCDRead
IR126doc 30127Motor Winding Temperature 3 Circuit 1Temperature in the factory unit system (I-P or SI).FLOAT32ABCDRead
IR128doc 30129AFD Frequency Circuit 1Depends on starter/drive options; see the source configuration column.FLOAT32ABCDRead
IR130doc 30131AFD Transistor Temperature Circuit 1Depends on starter/drive options; see the source configuration column.FLOAT32ABCDRead
IR132doc 30133Drive Average Line Current Circuit 1Depends on starter/drive options; see the source configuration column.FLOAT32ABCDRead
IR134doc 30135Drive Line Frequency Circuit 1Depends on starter/drive options; see the source configuration column.FLOAT32ABCDRead
IR136doc 30137Drive Motor Voltage Circuit 1Depends on starter/drive options; see the source configuration column.FLOAT32ABCDRead
IR138doc 30139Drive Inverter Base Temperature Circuit 1Needs: Unit Mount AFD (LF2) w/Line Side Items Remote Mount Comm AFD (PF7000) w/Line Side ItemsFLOAT32ABCDRead
IR140doc 30141Drive Rectifier Base Temperature Circuit 1Needs: Unit Mount AFD (LF2) w/Line Side Items Remote Mount Comm AFD (PF7000) w/Line Side ItemsFLOAT32ABCDRead
IR142doc 30143Drive Output Power Circuit 1Depends on starter/drive options; see the source configuration column.FLOAT32ABCDRead
IR144doc 30145Frequency Command Circuit 1Depends on starter/drive options; see the source configuration column.FLOAT32ABCDRead
IR146doc 30147Outboard Bearing Pad Temperature #1 Ckt1Temperature in the factory unit system (I-P or SI). Needs: CDHHFLOAT32ABCDRead
IR148doc 30149Outboard Bearing Pad Temperature #2 Ckt1Temperature in the factory unit system (I-P or SI). Needs: CDHHFLOAT32ABCDRead
IR150doc 30151Outboard Bearing Pad Temperature #3 Ckt1Temperature in the factory unit system (I-P or SI). Needs: CDHHFLOAT32ABCDRead
IR152doc 30153Restart Inhibit Time Remaining Circuit 1FLOAT32ABCDRead
IR154doc 30155Chiller Design CapacityCooling capacity in the factory unit system (I-P or SI).FLOAT32ABCDRead
IR156doc 30157Entering Condenser Water PressurePressure in the factory unit system (I-P or SI). Needs: Condenser Water Flow Differential Pressure SensorsFLOAT32ABCDRead
IR158doc 30159Entering Evaporator Water PressurePressure in the factory unit system (I-P or SI). Needs: Evaporator Water Flow Differential Pressure SensorsFLOAT32ABCDRead
IR160doc 30161Leaving Condenser Water PressurePressure in the factory unit system (I-P or SI). Needs: Condenser Water Flow Differential Pressure SensorsFLOAT32ABCDRead
IR162doc 30163Leaving Evaporator Water PressurePressure in the factory unit system (I-P or SI). Needs: Evaporator Water Flow Differential Pressure SensorsFLOAT32ABCDRead
IR164doc 30165Condenser Approach Temperature Circuit 1Temperature difference, factory unit system (I-P or SI).FLOAT32ABCDRead
IR166doc 30167Evaporator Approach Temperature Circuit 1Temperature difference, factory unit system (I-P or SI).FLOAT32ABCDRead
IR168doc 30169Drive DC Bus Voltage Circuit 1Depends on starter/drive options; see the source configuration column.FLOAT32ABCDRead
IR170doc 30171Drive Motor Average Current RLA Circuit 1Depends on starter/drive options; see the source configuration column.FLOAT32ABCD%Read
IR174doc 30175Active Demand Limit SetpointNeeds: Ice BuildingFLOAT32ABCD%Read
IR176doc 30177Active Demand Limit SetpointNeeds: Not Ice BuildingFLOAT32ABCD%Read
IR178doc 30179Demand Limit Setpoint StatusNeeds: Ice BuildingFLOAT32ABCD%Read
IR180doc 30181Number of CircuitsFLOAT32ABCDRead
IR182doc 30183Number of Compressors Circuit 1FLOAT32ABCDRead
IR184doc 30185Number of Compressors Circuit 2FLOAT32ABCDRead
IR186doc 30187Low Side Oil Pressure - Compressor 2APressure in the factory unit system (I-P or SI).FLOAT32ABCDRead
IR188doc 30189High Side Oil Pressure - Compressor 2APressure in the factory unit system (I-P or SI).FLOAT32ABCDRead
IR190doc 30191Oil Differential Pressure Circuit 2Differential pressure in the factory unit system (I-P or SI).FLOAT32ABCDRead
IR192doc 30193Oil Temperature - Compressor 2ATemperature in the factory unit system (I-P or SI).FLOAT32ABCDRead
IR194doc 30195Evaporator Saturated Refrigerant Temperature Circuit 2Temperature in the factory unit system (I-P or SI).FLOAT32ABCDRead
IR196doc 30197Condenser Saturated Refrigerant Temperature Circuit 2Temperature in the factory unit system (I-P or SI).FLOAT32ABCDRead
IR198doc 30199Refrigerant Discharge Temperature - Compressor 2ATemperature in the factory unit system (I-P or SI). Needs: Compressor Refrigerant Discharge TemperatureFLOAT32ABCDRead
IR200doc 30201Inlet Guide Vane 1 Percent Open Circuit 2FLOAT32ABCD%Read
IR202doc 30203Inlet Guide Vane 2 Percent Open Circuit 2Needs: IGV2FLOAT32ABCD%Read
IR204doc 30205Purge Carbon Tank Temperature Circuit 2Temperature in the factory unit system (I-P or SI). Needs: Purge w/Carbon TankFLOAT32ABCDRead
IR206doc 30207Purge Liquid Temperature Circuit 2Temperature in the factory unit system (I-P or SI). Needs: PurgeFLOAT32ABCDRead
IR208doc 30209Purge Refrigerant Compressor Suction Temperature Circuit 2Temperature in the factory unit system (I-P or SI). Needs: PurgeFLOAT32ABCDRead
IR210doc 30211Time Until Next Purge Run Circuit 2 (in seconds)Needs: PurgeFLOAT32ABCDsRead
IR212doc 30213Refrigeration - Life Circuit 2 (in seconds)Needs: PurgeFLOAT32ABCDsRead
IR214doc 30215Starts - Compressor 2AFLOAT32ABCDRead
IR216doc 30217Run Time - Compressor 2A (in seconds)FLOAT32ABCDsRead
IR218doc 30219Starter Average Phase Volt Circuit 2Needs: EM Starter Unit Mount AFD (LF2) Remote Mount Comm AFD (PF7000) Remote Mount Non-Communicating AFDFLOAT32ABCDRead
IR220doc 30221Line 1 Current - Compressor 2ADepends on starter/drive options; see the source configuration column.FLOAT32ABCDRead
IR222doc 30223Line 2 Current - Compressor 2ADepends on starter/drive options; see the source configuration column.FLOAT32ABCDRead
IR224doc 30225Line 3 Current - Compressor 2ADepends on starter/drive options; see the source configuration column.FLOAT32ABCDRead
IR226doc 30227Average Line Current Circuit 2Depends on starter/drive options; see the source configuration column.FLOAT32ABCDRead
IR228doc 30229Drive Average Line Current Circuit 2Depends on starter/drive options; see the source configuration column.FLOAT32ABCDRead
IR230doc 30231Starter Load Power Factor - Compressor 2ADepends on starter/drive options; see the source configuration column.FLOAT32ABCDRead
IR232doc 30233Inboard Bearing Temperature Circuit 2Temperature in the factory unit system (I-P or SI). Needs: Bearing Temperature SensorFLOAT32ABCDRead
IR234doc 30235Outboard Bearing Temperature Circuit 2Temperature in the factory unit system (I-P or SI). Needs: Bearing Temperature SensorFLOAT32ABCDRead
IR236doc 30237Motor Winding Temperature 1 Circuit 2Temperature in the factory unit system (I-P or SI).FLOAT32ABCDRead
IR238doc 30239Motor Winding Temperature 2 Circuit 2Temperature in the factory unit system (I-P or SI).FLOAT32ABCDRead
IR240doc 30241Motor Winding Temperature 3 Circuit 2Temperature in the factory unit system (I-P or SI).FLOAT32ABCDRead
IR242doc 30243AFD Transistor Temperature Circuit 2Depends on starter/drive options; see the source configuration column.FLOAT32ABCDRead
IR244doc 30245Heat Recovery Entering Water TempTemperature in the factory unit system (I-P or SI). Needs: Heat RecoveryFLOAT32ABCDRead
IR246doc 30247Heat Recovery Leaving Water TempTemperature in the factory unit system (I-P or SI). Needs: Heat RecoveryFLOAT32ABCDRead
IR248doc 30249Purge Pumpout Chiller On % (7 Days) Circuit 2Needs: PurgeFLOAT32ABCD%Read
IR250doc 30251Purge Pumpout Chiller Off % (7 Days) Circuit 2Needs: PurgeFLOAT32ABCD%Read
IR252doc 30253Purge 24 Hour Pumpout Circuit 2 (in seconds)Needs: PurgeFLOAT32ABCDsRead
IR254doc 30255Phase AB Voltage - Compressor 2ADepends on starter/drive options; see the source configuration column.FLOAT32ABCDRead
IR256doc 30257Phase BC Voltage - Compressor 2ADepends on starter/drive options; see the source configuration column.FLOAT32ABCDRead
IR258doc 30259Phase CA Voltage - Compressor 2ADepends on starter/drive options; see the source configuration column.FLOAT32ABCDRead
IR260doc 30261Purge Pumpout - Life Circuit 2 (in seconds)Needs: PurgeFLOAT32ABCDsRead
IR262doc 30263Drive Motor Average Current RLA Circuit 2Depends on starter/drive options; see the source configuration column.FLOAT32ABCD%Read
IR264doc 30265Drive Inverter Base Temperature Circuit 2Needs: Unit Mount AFD (LF2) w/Line Side Items Remote Mount Comm AFD (PF7000) w/Line Side ItemsFLOAT32ABCDRead
IR266doc 30267Drive Rectifier Base Temperature Circuit 2Needs: Unit Mount AFD (LF2) w/Line Side Items Remote Mount Comm AFD (PF7000) w/Line Side ItemsFLOAT32ABCDRead
IR268doc 30269Outboard Bearing Pad Temperature #1 Ckt2Temperature in the factory unit system (I-P or SI). Needs: CDHHFLOAT32ABCDRead
IR270doc 30271Outboard Bearing Pad Temperature #2 Ckt2Temperature in the factory unit system (I-P or SI). Needs: CDHHFLOAT32ABCDRead
IR272doc 30273Outboard Bearing Pad Temperature #3 Ckt2Temperature in the factory unit system (I-P or SI). Needs: CDHHFLOAT32ABCDRead
IR274doc 30275Evaporator Refrigerant Pressure Circuit 2Pressure in the factory unit system (I-P or SI).FLOAT32ABCDRead
IR276doc 30277Condenser Refrigerant Pressure Circuit 2Pressure in the factory unit system (I-P or SI).FLOAT32ABCDRead
IR278doc 30279Differential Refrigerant Pressure Circuit 2Differential pressure in the factory unit system (I-P or SI).FLOAT32ABCDRead
IR280doc 30281Restart Inhibit Time Remaining Circuit 2FLOAT32ABCDRead
IR282doc 30283AFD Frequency Circuit 2Depends on starter/drive options; see the source configuration column.FLOAT32ABCDRead
IR284doc 30285Drive Line Frequency Circuit 2Depends on starter/drive options; see the source configuration column.FLOAT32ABCDRead
IR286doc 30287Frequency Command Circuit 2Depends on starter/drive options; see the source configuration column.FLOAT32ABCDRead
IR288doc 30289Drive DC Bus Voltage Circuit 2Depends on starter/drive options; see the source configuration column.FLOAT32ABCDRead
IR290doc 30291Drive Output Power Circuit 2Depends on starter/drive options; see the source configuration column.FLOAT32ABCDRead
IR292doc 30293Line 1 Current RLA - Compressor 2ADepends on starter/drive options; see the source configuration column.FLOAT32ABCD%Read
IR294doc 30295Line 2 Current RLA - Compressor 2ADepends on starter/drive options; see the source configuration column.FLOAT32ABCD%Read
IR296doc 30297Line 3 Current RLA - Compressor 2ADepends on starter/drive options; see the source configuration column.FLOAT32ABCD%Read
IR298doc 30299Drive Current Line 1 Circuit 1Needs: Unit Mount AFD (LF2) w/Line Side Items Remote Mount Comm AFD (PF7000) w/Line Side ItemsFLOAT32ABCDRead
IR300doc 30301Drive Current Line 2 Circuit 1Needs: Unit Mount AFD (LF2) w/Line Side Items Remote Mount Comm AFD (PF7000) w/Line Side ItemsFLOAT32ABCDRead
IR302doc 30303Drive Current Line 3 Circuit 1Needs: Unit Mount AFD (LF2) w/Line Side Items Remote Mount Comm AFD (PF7000) w/Line Side ItemsFLOAT32ABCDRead
IR304doc 30305Drive Current Line 1 Circuit 2Needs: Unit Mount AFD (LF2) w/Line Side Items Remote Mount Comm AFD (PF7000) w/Line Side ItemsFLOAT32ABCDRead
IR306doc 30307Drive Current Line 2 Circuit 2Needs: Unit Mount AFD (LF2) w/Line Side Items Remote Mount Comm AFD (PF7000) w/Line Side ItemsFLOAT32ABCDRead
IR308doc 30309Drive Current Line 3 Circuit 2Needs: Unit Mount AFD (LF2) w/Line Side Items Remote Mount Comm AFD (PF7000) w/Line Side ItemsFLOAT32ABCDRead
IR310doc 30311Starter Input Power Consumption Ckt1Electrical power. Needs: EM Starter Unit Mount AFD (LF2) Remote Mount Comm AFD (PF7000)FLOAT32ABCDRead
IR312doc 30313Starter Input Power Consumption Ckt2Electrical power. Needs: EM Starter Unit Mount AFD (LF2) Remote Mount Comm AFD (PF7000)FLOAT32ABCDRead
IR314doc 30315Drive Motor Voltage Circuit 2Depends on starter/drive options; see the source configuration column.FLOAT32ABCDRead
IR316doc 30317Chiller Control SignalFLOAT32ABCD%Read
IR318doc 30319Head Pressure Control StatusNeeds: Head Pressure ControlFLOAT32ABCD%Read
IR320doc 30321AFD Last Diagnostic Code Ckt2Needs: Unit Mount AFD (LF2) Remote Mount Comm AFD (PF7000) Remote Mount Comm AFD (PF6000)FLOAT32ABCDRead
IR322doc 30323Voltage L1-L2 Circuit 1Voltage. Needs: Energy MeterFLOAT32ABCDRead
IR324doc 30325Voltage L1-L3 Circuit 1Voltage. Needs: Energy MeterFLOAT32ABCDRead
IR326doc 30327Voltage L2-L3 Circuit 1Voltage. Needs: Energy MeterFLOAT32ABCDRead
IR328doc 30329Voltage L1-L2 Circuit 2Voltage. Needs: Energy MeterFLOAT32ABCDRead
IR330doc 30331Voltage L1-L3 Circuit 2Voltage. Needs: Energy MeterFLOAT32ABCDRead
IR332doc 30333Voltage L2-L3 Circuit 2Voltage. Needs: Energy MeterFLOAT32ABCDRead
IR334doc 30335Average Line Voltage Circuit 1Voltage. Needs: Energy MeterFLOAT32ABCDRead
IR336doc 30337Average Line Voltage Circuit 2Voltage. Needs: Energy MeterFLOAT32ABCDRead
IR338doc 30339Line Current L1 Circuit 1Current. Needs: Energy MeterFLOAT32ABCDRead
IR340doc 30341Line Current L2 Circuit 1Current. Needs: Energy MeterFLOAT32ABCDRead
IR342doc 30343Line Current L3 Circuit 1Current. Needs: Energy MeterFLOAT32ABCDRead
IR344doc 30345Line Current L1 Circuit 2Current. Needs: Energy MeterFLOAT32ABCDRead
IR346doc 30347Line Current L2 Circuit 2Current. Needs: Energy MeterFLOAT32ABCDRead
IR348doc 30349Line Current L3 Circuit 2Current. Needs: Energy MeterFLOAT32ABCDRead
IR350doc 30351Unit Average Line Current Circuit 1Current. Needs: Energy MeterFLOAT32ABCDRead
IR352doc 30353Unit Average Line Current Circuit 2Current. Needs: Energy MeterFLOAT32ABCDRead
IR354doc 30355Line Frequency Circuit 1Needs: Energy MeterFLOAT32ABCDRead
IR356doc 30357Line Frequency Circuit 2Needs: Energy MeterFLOAT32ABCDRead
IR358doc 30359Power Factor Circuit 1Needs: Energy MeterFLOAT32ABCDRead
IR360doc 30361Power Factor Circuit 2Needs: Energy MeterFLOAT32ABCDRead
IR362doc 30363Power Demand Circuit 1Electrical power. Needs: Energy MeterFLOAT32ABCDRead
IR364doc 30365Power Demand Circuit 2Electrical power. Needs: Energy MeterFLOAT32ABCDRead
IR366doc 30367Total Real PowerElectrical power. Needs: Energy MeterFLOAT32ABCDRead
IR368doc 30369Unit Power ConsumptionDepends on starter/drive options; see the source configuration column.FLOAT32ABCDRead
IR370doc 30371Energy ConsumptionDepends on starter/drive options; see the source configuration column.FLOAT32ABCDRead
IR372doc 30373Energy Consumption LifetimeDepends on starter/drive options; see the source configuration column.FLOAT32ABCDRead
IR374doc 30375Condenser Approach Temperature Circuit 2Temperature difference, factory unit system (I-P or SI).FLOAT32ABCDRead
IR376doc 30377Evaporator Approach Temperature Circuit 2Temperature difference, factory unit system (I-P or SI).FLOAT32ABCDRead
IR378doc 30379Drive Input Voltage Calculated 1AVoltage. Needs: TR200 Modbus AFDFLOAT32ABCDRead
IR380doc 30381Drive Input Voltage Calculated 2AVoltage. Needs: TR200 Modbus AFDFLOAT32ABCDRead
IR382doc 30383Drive Heatsink Temperature Compressor 1ATemperature in the factory unit system (I-P or SI). Needs: TR200 Modbus AFDFLOAT32ABCDRead
IR384doc 30385Drive Heatsink Temperature Compressor 2ATemperature in the factory unit system (I-P or SI). Needs: TR200 Modbus AFDFLOAT32ABCDRead
IR386doc 30387Outdoor Air Temperature LocalTemperature in the factory unit system (I-P or SI). Needs: Outdoor Air TemperatureFLOAT32ABCDRead
IR388doc 30389Heat Recovery Differential Water PressureNeeds: Heat Recovery Water Flow Differential Pressure or Dual Pressure SensorsFLOAT32ABCDRead
IR390doc 30391Heat Recovery Water Flow RateNeeds: Heat Recovery Water Flow SensingFLOAT32ABCDRead
IR392doc 30393Heat Recovery Calculated CapacityNeeds: Heat Recovery Water Flow SensingFLOAT32ABCDRead
IR394doc 30395Heat Recovery Entering Water PressureNeeds: Heat Recovery Water Flow Dual Pressure SensorsFLOAT32ABCDRead
IR396doc 30397Heat Recovery Leaving Water PressureNeeds: Heat Recovery Water Flow Dual Pressure SensorsFLOAT32ABCDRead
IR398doc 30399Heat Recovery Approach Temperature Circuit 1Temperature difference, factory unit system (I-P or SI). Needs: Heat RecoveryFLOAT32ABCDRead
IR400doc 30401Heat Recovery Approach Temperature Circuit 2Temperature difference, factory unit system (I-P or SI). Needs: Heat RecoveryFLOAT32ABCDRead
IR402doc 30403High Side Oil Gauge Pressure - Compressor 1APressure in the factory unit system (I-P or SI).FLOAT32ABCDRead
IR404doc 30405Low Side Oil Gauge Pressure - Compressor 1APressure in the factory unit system (I-P or SI).FLOAT32ABCDRead
IR406doc 30407High Side Oil Gauge Pressure - Compressor 2APressure in the factory unit system (I-P or SI).FLOAT32ABCDRead
IR408doc 30409Low Side Oil Gauge Pressure - Compressor 2APressure in the factory unit system (I-P or SI).FLOAT32ABCDRead
IR410doc 30411Condenser Refrigerant Gauge Pressure Circuit 1Pressure in the factory unit system (I-P or SI).FLOAT32ABCDRead
IR412doc 30413Condenser Refrigerant Gauge Pressure Circuit 2Pressure in the factory unit system (I-P or SI).FLOAT32ABCDRead
IR414doc 30415Entering Condenser Water Gauge PressureNeeds: Cond Water Flow Differential Dual Pressure SensorsFLOAT32ABCDRead
IR416doc 30417Entering Evaporator Water Gauge PressureNeeds: Evap Water Flow Differential Dual Pressure SensorsFLOAT32ABCDRead
IR418doc 30419Evaporator Refrigerant Gauge Pressure Circuit 1Pressure in the factory unit system (I-P or SI).FLOAT32ABCDRead
IR420doc 30421Evaporator Refrigerant Gauge Pressure Circuit 2Pressure in the factory unit system (I-P or SI).FLOAT32ABCDRead
IR422doc 30423Heat Recovery Entering Water Gauge PressureNeeds: Heat Recovery Water Flow Dual Pressure SensorsFLOAT32ABCDRead
IR424doc 30425Heat Recovery Leaving Water Gauge PressureNeeds: Heat Recovery Water Flow Dual Pressure SensorsFLOAT32ABCDRead
IR426doc 30427Leaving Condenser Water Gauge PressureNeeds: Cond Water Flow Differential Dual Pressure SensorsFLOAT32ABCDRead
IR428doc 30429Leaving Evaporator Water Gauge PressureNeeds: Evap Water Flow Differential Dual Pressure SensorsFLOAT32ABCDRead
IR430doc 30431Compressor Discharge Superheat Circuit 1Temperature difference, factory unit system (I-P or SI). Needs: Compressor Refrigerant Discharge TemperatureFLOAT32ABCDRead
IR432doc 30433Compressor Discharge Superheat Circuit 2Temperature difference, factory unit system (I-P or SI). Needs: Compressor Refrigerant Discharge TemperatureFLOAT32ABCDRead
IR434doc 30435Unit Load CommandFLOAT32ABCD%Read
IR436doc 30437Drive Motor Current U RLA Circuit 1Needs: UM AFD w/o THD filter (Inovance) MV Remote Mount COMM AFD (Inovance)FLOAT32ABCD%Read
IR438doc 30439Drive Motor Current V RLA Circuit 1Needs: UM AFD w/o THD filter (Inovance) MV Remote Mount COMM AFD (Inovance)FLOAT32ABCD%Read
IR440doc 30441Drive Motor Current W RLA Circuit 1Needs: UM AFD w/o THD filter (Inovance) MV Remote Mount COMM AFD (Inovance)FLOAT32ABCD%Read
IR442doc 30443Drive Motor Current U Circuit 1Current. Needs: UM AFD w/o THD filter (Inovance) MV Remote Mount COMM AFD (Inovance)FLOAT32ABCDRead
IR444doc 30445Drive Motor Current V Circuit 1Current. Needs: UM AFD w/o THD filter (Inovance) MV Remote Mount COMM AFD (Inovance)FLOAT32ABCDRead
IR446doc 30447Drive Motor Current W Circuit 1Current. Needs: UM AFD w/o THD filter (Inovance) MV Remote Mount COMM AFD (Inovance)FLOAT32ABCDRead
IR448doc 30449Drive Motor Current U RLA Circuit 2Needs: UM AFD w/o THD filter (Inovance) MV Remote Mount COMM AFD (Inovance)FLOAT32ABCD%Read
IR450doc 30451Drive Motor Current V RLA Circuit 2Needs: UM AFD w/o THD filter (Inovance) MV Remote Mount COMM AFD (Inovance)FLOAT32ABCD%Read
IR452doc 30453Drive Motor Current W RLA Circuit 2Needs: UM AFD w/o THD filter (Inovance) MV Remote Mount COMM AFD (Inovance)FLOAT32ABCD%Read
IR454doc 30455Drive Motor Current U Circuit 2Current. Needs: UM AFD w/o THD filter (Inovance) MV Remote Mount COMM AFD (Inovance)FLOAT32ABCDRead
IR456doc 30457Drive Motor Current V Circuit 2Current. Needs: UM AFD w/o THD filter (Inovance) MV Remote Mount COMM AFD (Inovance)FLOAT32ABCDRead
IR458doc 30459Drive Motor Current W Circuit 2Current. Needs: UM AFD w/o THD filter (Inovance) MV Remote Mount COMM AFD (Inovance)FLOAT32ABCDRead
IR460doc 30461Active Cooling Differential to StartTemperature difference, factory unit system (I-P or SI).FLOAT32ABCDRead
IR462doc 30463Active Cooling Differential to StopTemperature difference, factory unit system (I-P or SI).FLOAT32ABCDRead
IR464doc 30465Active Heating Differential to StartTemperature difference, factory unit system (I-P or SI). Needs: Hot Water ControlFLOAT32ABCDRead
IR466doc 30467Active Heating Differential to StopTemperature difference, factory unit system (I-P or SI). Needs: Hot Water ControlFLOAT32ABCDRead
IR2010doc 32011Running ModeUINT16Read1 = Chiller Off; 2 = Chiller In Start Mode; 3 = Chiller In Run Mode; 4 = Chiller In Pre-Shutdown Mode; 5 = Chiller In Service Mode
IR2011doc 32012Operating ModeUINT16Read1 = Cool; 2 = Heat; 3 = Ice Making; 4 = Free Cooling
IR2012doc 32013Chiller Setpoint SourceUINT16Read1 = BAS; 2 = External; 3 = Front Panel
IR2013doc 32014Cooling TypeUINT16Read1 = Water Cooled
IR2014doc 32015Refrigerant TypeUINT16Read1 = R-11; 2 = R-12; 3 = R-22; 4 = R-123; 5 = R-134a; 8 = R-113; 9 = R-114; 10 = R-500; 11 = R-502; 13 = R-513A; 14 = R-1233zd(E); 15 = R-514A
IR2015doc 32016Manufacturing LocationUINT16Read1 = Field Applied; 2 = La Crosse; 15 = Taicang
IR2016doc 32017Model Information [GEN2]UINT16Read1 = CVHF; 2 = CVGF; 3 = CVHS; 11 = CDHF; 12 = CVR; 13 = CVHH; 14 = CDHH; 20 = CVHM; 38 = CVHE; 39 = CVHG; 40 = CVHL; 43 = CDHG
IR3010doc 33011Manual Override ExistsUINT16Read0 = Off; 1 = On
IR3011doc 33012Base Loading Request ActiveNeeds: Base LoadingUINT16Read0 = Inactive; 1 = Active
IR3012doc 33013Run EnabledUINT16Read0 = Run Not Enabled; 1 = Run Enabled
IR3013doc 33014Local Setpoint ControlUINT16Read0 = Remote Control; 1 = Local Control
IR3014doc 33015Maximum CapacityUINT16Read0 = Off; 1 = On
IR3015doc 33016Capacity LimitedUINT16Read0 = Not Limited; 1 = Limited
IR3016doc 33017Head Relief RequestUINT16Read0 = Off; 1 = On
IR3017doc 33018Purge Compressor Relay Circuit 1Needs: PurgeUINT16Read0 = Off; 1 = On
IR3018doc 33019Pump Out Relay Circuit 1Needs: PurgeUINT16Read0 = Off; 1 = On
IR3019doc 33020Purge Regenerating Valve Solenoid Circuit 1Needs: Purge w/Carbon TankUINT16Read0 = Off; 1 = On
IR3020doc 33021Chiller Running StateUINT16Read0 = Off; 1 = On
IR3021doc 33022Evaporator Water Pump RequestUINT16Read0 = Off; 1 = On
IR3022doc 33023Evaporator Water Flow StatusUINT16Read0 = No Flow; 1 = Flow
IR3023doc 33024Condenser Water Pump RequestUINT16Read0 = Off; 1 = On
IR3024doc 33025Condenser Water Flow StatusUINT16Read0 = No Flow; 1 = Flow
IR3025doc 33026Diagnostic PresentUINT16Read0 = Normal; 1 = In Alarm
IR3026doc 33027Diagnostic Shutdown PresentUINT16Read0 = Normal; 1 = In Alarm
IR3027doc 33028Diagnostic: Manual Reset RequiredUINT16Read0 = Normal; 1 = In Alarm
IR3028doc 33029Diagnostic: Local Manual Reset RequiredUINT16Read0 = Normal; 1 = In Alarm
IR3029doc 33030Diagnostic Present: InformationUINT16Read0 = Normal; 1 = In Alarm
IR3030doc 33031Diagnostic Present: AdvisoryUINT16Read0 = Normal; 1 = In Alarm
IR3031doc 33032Diagnostic Present: CriticalUINT16Read0 = Normal; 1 = In Alarm
IR3032doc 33033Diagnostic Present: Service RequiredUINT16Read0 = Normal; 1 = In Alarm
IR3033doc 33034Compressor 1A StatusUINT16Read0 = Off; 1 = Running
IR3034doc 33035Front Panel Auto StopUINT16Read0 = Stop; 1 = Auto
IR3035doc 33036External Auto Stop Input StatusUINT16Read0 = Stop; 1 = Auto
IR3036doc 33037Purge Compressor Relay Circuit 2Needs: PurgeUINT16Read0 = Off; 1 = On
IR3037doc 33038Purge Regenerating Valve Solenoid Circuit 2Needs: Purge w/Carbon TankUINT16Read0 = Off; 1 = On
IR3038doc 33039Pump Out Relay Circuit 2Needs: PurgeUINT16Read0 = Off; 1 = On
IR3039doc 33040Compressor 2A StatusUINT16Read0 = Off; 1 = Running
IR3040doc 33041Emergency StopUINT16Read0 = Auto; 1 = Emergency Stop - Manual Reset Required
IR3041doc 33042Circuit 1 Cooling AvailableUINT16Read0 = No; 1 = Yes
IR3042doc 33043Circuit 2 Cooling AvailableUINT16Read0 = No; 1 = Yes
IR3043doc 33044Circuit 1 Lockout Front PanelUINT16Read0 = Normal; 1 = Locked Out
IR3044doc 33045Circuit 2 Lockout Front PanelUINT16Read0 = Normal; 1 = Locked Out
IR3045doc 33046Circuit 1 Lockout ExternalUINT16Read0 = Normal; 1 = Locked Out
IR3046doc 33047Circuit 2 Lockout ExternalUINT16Read0 = Normal; 1 = Locked Out
IR3047doc 33048Circuit 1 Lockout ActiveUINT16Read0 = Normal; 1 = Locked Out
IR3048doc 33049Circuit 2 Lockout ActiveUINT16Read0 = Normal; 1 = Locked Out
IR3049doc 33050Diagnostic Shutdown Present: AFD/Starter Circuit 1UINT16Read0 = Normal; 1 = In Alarm
IR3050doc 33051Diagnostic Shutdown Present: AFD/Starter Circuit 2UINT16Read0 = Normal; 1 = In Alarm
IR3051doc 33052Heat Recovery Water Flow StatusNeeds: Heat RecoveryUINT16Read0 = No Flow; 1 = Flow
IR4000doc 34001Diagnostic: AFD Comm Loss: Main Processor Circuit 1Depends on starter/drive options; see the source configuration column.UINT16Read0 = Normal; 1 = In Alarm
IR4001doc 34002Diagnostic: AFD Comm Loss: Main Processor Circuit 2Depends on starter/drive options; see the source configuration column.UINT16Read0 = Normal; 1 = In Alarm
IR4002doc 34003Diagnostic: AFD Control Board Memory Error Type 2 Circuit 1Diagnostic flag. Needs: Unit Mount AFD - AFDD,E,F (LF2) Remote Mount Comm AFD - (PF7000)UINT16Read0 = Normal; 1 = In Alarm
IR4003doc 34004Diagnostic: AFD Control Board Memory Error Type 2 Circuit 2Diagnostic flag. Needs: Unit Mount AFD - AFDD,E,F (LF2) Remote Mount Comm AFD - (PF7000)UINT16Read0 = Normal; 1 = In Alarm
IR4004doc 34005Diagnostic: AFD DPI Communication Failure Circuit 1Diagnostic flag. Needs: Unit Mount AFD - AFDD,E,F (LF2) Remote Mount Comm AFD - (PF7000)UINT16Read0 = Normal; 1 = In Alarm
IR4005doc 34006Diagnostic: AFD DPI Communication Failure Circuit 2Diagnostic flag. Needs: Unit Mount AFD - AFDD,E,F (LF2) Remote Mount Comm AFD - (PF7000)UINT16Read0 = Normal; 1 = In Alarm
IR4006doc 34007Diagnostic: AFD Fatal Software Error Circuit 1Diagnostic flag. Needs: Unit Mount AFD - AFDD,E,F (LF2) Remote Mount Comm AFD - (PF7000)UINT16Read0 = Normal; 1 = In Alarm
IR4007doc 34008Diagnostic: AFD Fatal Software Error Circuit 2Diagnostic flag. Needs: Unit Mount AFD - AFDD,E,F (LF2) Remote Mount Comm AFD - (PF7000)UINT16Read0 = Normal; 1 = In Alarm
IR4008doc 34009Diagnostic: AFD General Failure Circuit 1Depends on starter/drive options; see the source configuration column.UINT16Read0 = Normal; 1 = In Alarm
IR4009doc 34010Diagnostic: AFD General Failure Circuit 2Depends on starter/drive options; see the source configuration column.UINT16Read0 = Normal; 1 = In Alarm
IR4010doc 34011Diagnostic: AFD Ground Fault Circuit 1Depends on starter/drive options; see the source configuration column.UINT16Read0 = Normal; 1 = In Alarm
IR4011doc 34012Diagnostic: AFD Ground Fault Circuit 2Depends on starter/drive options; see the source configuration column.UINT16Read0 = Normal; 1 = In Alarm
IR4012doc 34013Diagnostic: AFD High Bus Voltage Circuit 1Diagnostic flag. Needs: Unit Mount AFD - AFDD,E,F (LF2) Remote Mount Comm AFD - (PF7000)UINT16Read0 = Normal; 1 = In Alarm
IR4013doc 34014Diagnostic: AFD High Bus Voltage Circuit 2Diagnostic flag. Needs: Unit Mount AFD - AFDD,E,F (LF2) Remote Mount Comm AFD - (PF7000)UINT16Read0 = Normal; 1 = In Alarm
IR4014doc 34015Diagnostic: AFD High Temperature Circuit 1Diagnostic flag. Needs: Unit Mount AFD - AFDD,E,F (LF2) Remote Mount Comm AFD - (PF7000)UINT16Read0 = Normal; 1 = In Alarm
IR4015doc 34016Diagnostic: AFD High Temperature Circuit 2Diagnostic flag. Needs: Unit Mount AFD - AFDD,E,F (LF2) Remote Mount Comm AFD - (PF7000)UINT16Read0 = Normal; 1 = In Alarm
IR4016doc 34017Diagnostic: AFD I/O Board Failure Circuit 1Diagnostic flag. Needs: Unit Mount AFD - AFDD,E,F (LF2) Remote Mount Comm AFD - (PF7000)UINT16Read0 = Normal; 1 = In Alarm
IR4017doc 34018Diagnostic: AFD I/O Board Failure Circuit 2Diagnostic flag. Needs: Unit Mount AFD - AFDD,E,F (LF2) Remote Mount Comm AFD - (PF7000)UINT16Read0 = Normal; 1 = In Alarm
IR4018doc 34019Diagnostic: AFD Instantaneous Current Overload Circuit 1Depends on starter/drive options; see the source configuration column.UINT16Read0 = Normal; 1 = In Alarm
IR4019doc 34020Diagnostic: AFD Instantaneous Current Overload Circuit 2Depends on starter/drive options; see the source configuration column.UINT16Read0 = Normal; 1 = In Alarm
IR4020doc 34021Diagnostic: AFD Interrupt Failure Circuit 1Depends on starter/drive options; see the source configuration column.UINT16Read0 = Normal; 1 = In Alarm
IR4021doc 34022Diagnostic: AFD Interrupt Failure Circuit 2Depends on starter/drive options; see the source configuration column.UINT16Read0 = Normal; 1 = In Alarm
IR4022doc 34023Diagnostic: AFD Motor Current Overload Circuit 1Depends on starter/drive options; see the source configuration column.UINT16Read0 = Normal; 1 = In Alarm
IR4023doc 34024Diagnostic: AFD Motor Current Overload Circuit 2Depends on starter/drive options; see the source configuration column.UINT16Read0 = Normal; 1 = In Alarm
IR4024doc 34025Diagnostic: AFD Motor Short Circuit 1Diagnostic flag. Needs: Unit Mount AFD - AFDD,E,F (LF2) Remote Mount Comm AFD - (PF7000)UINT16Read0 = Normal; 1 = In Alarm
IR4025doc 34026Diagnostic: AFD Motor Short Circuit 2Diagnostic flag. Needs: Unit Mount AFD - AFDD,E,F (LF2) Remote Mount Comm AFD - (PF7000)UINT16Read0 = Normal; 1 = In Alarm
IR4026doc 34027Diagnostic: AFD Output Phase Loss Circuit 1Depends on starter/drive options; see the source configuration column.UINT16Read0 = Normal; 1 = In Alarm
IR4027doc 34028Diagnostic: AFD Output Phase Loss Circuit 2Depends on starter/drive options; see the source configuration column.UINT16Read0 = Normal; 1 = In Alarm
IR4028doc 34029Diagnostic: AFD Power Intfc Controller Board Failure Circuit 1Diagnostic flag. Needs: Unit Mount AFD - AFDD,E,F (LF2) Remote Mount Comm AFD - (PF7000)UINT16Read0 = Normal; 1 = In Alarm
IR4029doc 34030Diagnostic: AFD Power Intfc Controller Board Failure Circuit 2Diagnostic flag. Needs: Unit Mount AFD - AFDD,E,F (LF2) Remote Mount Comm AFD - (PF7000)UINT16Read0 = Normal; 1 = In Alarm
IR4030doc 34031Diagnostic: AFD Power Loss Circuit 1Depends on starter/drive options; see the source configuration column.UINT16Read0 = Normal; 1 = In Alarm
IR4031doc 34032Diagnostic: AFD Power Loss Circuit 2Depends on starter/drive options; see the source configuration column.UINT16Read0 = Normal; 1 = In Alarm
IR4032doc 34033Diagnostic: AFD Power Structure Board Failure Circuit 1Diagnostic flag. Needs: Unit Mount AFD - AFDD,E,F (LF2) Remote Mount Comm AFD - (PF7000)UINT16Read0 = Normal; 1 = In Alarm
IR4033doc 34034Diagnostic: AFD Power Structure Board Failure Circuit 2Diagnostic flag. Needs: Unit Mount AFD - AFDD,E,F (LF2) Remote Mount Comm AFD - (PF7000)UINT16Read0 = Normal; 1 = In Alarm
IR4034doc 34035Diagnostic: AFD RS485 Board Memory Error Type 2 Circuit 1Diagnostic flag. Needs: Unit Mount AFD - AFDD,E,F (LF2) Remote Mount Comm AFD - (PF7000)UINT16Read0 = Normal; 1 = In Alarm
IR4035doc 34036Diagnostic: AFD RS485 Board Memory Error Type 2 Circuit 2Diagnostic flag. Needs: Unit Mount AFD - AFDD,E,F (LF2) Remote Mount Comm AFD - (PF7000)UINT16Read0 = Normal; 1 = In Alarm
IR4038doc 34039Diagnostic: At Speed Input Opened Circuit 1Diagnostic flag. Needs: Remote Mount Non-Comm AFD Solid State StarterUINT16Read0 = Normal; 1 = In Alarm
IR4039doc 34040Diagnostic: At Speed Input Opened Circuit 2Diagnostic flag. Needs: Remote Mount Non-Comm AFD Solid State StarterUINT16Read0 = Normal; 1 = In Alarm
IR4040doc 34041Diagnostic: At Speed Input Shorted Circuit 1Diagnostic flag. Needs: Remote Mount Non-Comm AFD Solid State StarterUINT16Read0 = Normal; 1 = In Alarm
IR4041doc 34042Diagnostic: At Speed Input Shorted Circuit 2Diagnostic flag. Needs: Remote Mount Non-Comm AFD Solid State StarterUINT16Read0 = Normal; 1 = In Alarm
IR4042doc 34043Diagnostic: Check ClockDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4043doc 34044Diagnostic: Check Oil Filter Circuit 1Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4044doc 34045Diagnostic: Check Oil Filter Circuit 2Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4045doc 34046Diagnostic: Check Oil Heater Circuit 1Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4046doc 34047Diagnostic: Check Oil Heater Circuit 2Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4047doc 34048Comm Loss: Adaptive Frequency Drive Circuit 1Depends on starter/drive options; see the source configuration column.UINT16Read0 = Normal; 1 = In Alarm
IR4048doc 34049Comm Loss: Adaptive Frequency Drive Circuit 2Depends on starter/drive options; see the source configuration column.UINT16Read0 = Normal; 1 = In Alarm
IR4049doc 34050Comm Loss: AFD Speed Signal VDC Output Circuit 1Diagnostic flag. Needs: Remote Mount Non-Comm AFDUINT16Read0 = Normal; 1 = In Alarm
IR4050doc 34051Comm Loss: AFD Speed Signal VDC Output Circuit 2Diagnostic flag. Needs: Remote Mount Non-Comm AFDUINT16Read0 = Normal; 1 = In Alarm
IR4051doc 34052Comm Loss: Compressor Motor % RLA Output Circuit 1Diagnostic flag. Needs: % RLA OutputUINT16Read0 = Normal; 1 = In Alarm
IR4052doc 34053Comm Loss: Compressor Motor % RLA Output Circuit 2Diagnostic flag. Needs: % RLA OutputUINT16Read0 = Normal; 1 = In Alarm
IR4053doc 34054Comm Loss: Cond Diff Water PressureDiagnostic flag. Needs: Cond Water Flow MeasurementUINT16Read0 = Normal; 1 = In Alarm
IR4054doc 34055Comm Loss: Cond Head Press Cntrl OutputDiagnostic flag. Needs: Head Pressure ControlUINT16Read0 = Normal; 1 = In Alarm
IR4055doc 34056Comm Loss: Cond High Pressure Cutout Circuit 1Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4056doc 34057Comm Loss: Cond High Pressure Cutout Circuit 2Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4057doc 34058Comm Loss: Cond Refrigerant Pressure Circuit 1Diagnostic flag. Needs: Condenser Pressure SensorUINT16Read0 = Normal; 1 = In Alarm
IR4058doc 34059Comm Loss: Cond Refrigerant Pressure Circuit 2Diagnostic flag. Needs: Condenser Pressure SensorUINT16Read0 = Normal; 1 = In Alarm
IR4059doc 34060Comm Loss: Cond Rfgt Pressure Output Circuit 1Diagnostic flag. Needs: Condenser Refrigerant Pressure OutputUINT16Read0 = Normal; 1 = In Alarm
IR4060doc 34061Comm Loss: Cond Rfgt Pressure Output Circuit 2Diagnostic flag. Needs: Condenser Refrigerant Pressure OutputUINT16Read0 = Normal; 1 = In Alarm
IR4061doc 34062Comm Loss: Cond Saturated Rfgt Temp Circuit 1Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4062doc 34063Comm Loss: Cond Saturated Rfgt Temp Circuit 2Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4063doc 34064Comm Loss: Condenser Entering Water PressureDiagnostic flag. Needs: Cond Water Flow Measurement - Dual Pressure SensorsUINT16Read0 = Normal; 1 = In Alarm
IR4064doc 34065Comm Loss: Condenser Entering Water TempDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4065doc 34066Comm Loss: Condenser Leaving Water PressureDiagnostic flag. Needs: Cond Water Flow Measurement - Dual Pressure SensorsUINT16Read0 = Normal; 1 = In Alarm
IR4066doc 34067Comm Loss: Condenser Leaving Water TempDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4067doc 34068Comm Loss: Condenser Liquid Level Sensor Circuit 1Diagnostic flag. Needs: Economizer BypassUINT16Read0 = Normal; 1 = In Alarm
IR4068doc 34069Comm Loss: Condenser Liquid Level Sensor Circuit 2Diagnostic flag. Needs: Economizer BypassUINT16Read0 = Normal; 1 = In Alarm
IR4069doc 34070Comm Loss: Condenser Water Flow SwitchDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4070doc 34071Comm Loss: Condenser Water Pump RelayDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4071doc 34072Comm Loss: Cprsr Discharge Rfgt Temp Circuit 1Diagnostic flag. Needs: Compressor Refrigerant Discharge Temp SensorUINT16Read0 = Normal; 1 = In Alarm
IR4072doc 34073Comm Loss: Cprsr Discharge Rfgt Temp Circuit 2Diagnostic flag. Needs: Compressor Refrigerant Discharge Temp SensorUINT16Read0 = Normal; 1 = In Alarm
IR4073doc 34074Comm Loss: Economizer Bypass Valve Circuit 1Diagnostic flag. Needs: Economizer BypassUINT16Read0 = Normal; 1 = In Alarm
IR4074doc 34075Comm Loss: Economizer Bypass Valve Circuit 2Diagnostic flag. Needs: Economizer BypassUINT16Read0 = Normal; 1 = In Alarm
IR4075doc 34076Comm Loss: Emergency StopDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4076doc 34077Comm Loss: Energy Meter 1 Circuit 1Diagnostic flag. Needs: Energy MeterUINT16Read0 = Normal; 1 = In Alarm
IR4077doc 34078Comm Loss: Energy Meter 2 Circuit 2Diagnostic flag. Needs: Energy MeterUINT16Read0 = Normal; 1 = In Alarm
IR4078doc 34079Comm Loss: Evap Diff Water PressureDiagnostic flag. Needs: Evap Water Flow MeasurementUINT16Read0 = Normal; 1 = In Alarm
IR4079doc 34080Comm Loss: Evap Entering Water TempDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4080doc 34081Comm Loss: Evap Leaving Water TempDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4081doc 34082Comm Loss: Evap Refrigerant Pressure Circuit 1Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4082doc 34083Comm Loss: Evap Refrigerant Pressure Circuit 2Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4083doc 34084Comm Loss: Evap Sat Refrig Temp Circuit 1Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4084doc 34085Comm Loss: Evap Sat Refrig Temp Circuit 2Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4085doc 34086Comm Loss: Evaporator Entering Water PressureDiagnostic flag. Needs: Evap Water Flow Measurement - Dual Pressure SensorsUINT16Read0 = Normal; 1 = In Alarm
IR4086doc 34087Comm Loss: Evaporator Leaving Water PressureDiagnostic flag. Needs: Evap Water Flow Measurement - Dual Pressure SensorsUINT16Read0 = Normal; 1 = In Alarm
IR4087doc 34088Comm Loss: Evaporator Water Flow SwitchDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4088doc 34089Comm Loss: Evaporator Water Pump RelayDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4089doc 34090Comm Loss: Ext Base Loading CommandDiagnostic flag. Needs: Base LoadingUINT16Read0 = Normal; 1 = In Alarm
IR4090doc 34091Comm Loss: Ext Base Loading SetpointDiagnostic flag. Needs: Base LoadingUINT16Read0 = Normal; 1 = In Alarm
IR4091doc 34092Comm Loss: Ext Chilled/Hot Water SetpointDiagnostic flag. Needs: External Chilled Water SetpointUINT16Read0 = Normal; 1 = In Alarm
IR4092doc 34093Comm Loss: Ext Demand Limit SetpointDiagnostic flag. Needs: External Demand Limit SetpointUINT16Read0 = Normal; 1 = In Alarm
IR4093doc 34094Comm Loss: External Auto/StopDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4094doc 34095Comm Loss: External Ckt Lockout Circuit 1Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4095doc 34096Comm Loss: External Ckt Lockout Circuit 2Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4097doc 34098Comm Loss: External Hot Water CommandDiagnostic flag. Needs: Hot Water ControlUINT16Read0 = Normal; 1 = In Alarm
IR4098doc 34099Comm Loss: External Ice Building CommandDiagnostic flag. Needs: Ice BuildingUINT16Read0 = Normal; 1 = In Alarm
IR4099doc 34100Comm Loss: Generator Fault Input Circuit 1Diagnostic flag. Needs: Engine/GeneratorUINT16Read0 = Normal; 1 = In Alarm
IR4100doc 34101Comm Loss: Generator Fault Input Circuit 2Diagnostic flag. Needs: Engine/GeneratorUINT16Read0 = Normal; 1 = In Alarm
IR4101doc 34102Comm Loss: Generator Speed Signal Output Circuit 1Diagnostic flag. Needs: Engine/GeneratorUINT16Read0 = Normal; 1 = In Alarm
IR4102doc 34103Comm Loss: Generator Speed Signal Output Circuit 2Diagnostic flag. Needs: Engine/GeneratorUINT16Read0 = Normal; 1 = In Alarm
IR4103doc 34104Comm Loss: Generator Start/Stop Relay Circuit 1Diagnostic flag. Needs: Engine/GeneratorUINT16Read0 = Normal; 1 = In Alarm
IR4104doc 34105Comm Loss: Generator Start/Stop Relay Circuit 2Diagnostic flag. Needs: Engine/GeneratorUINT16Read0 = Normal; 1 = In Alarm
IR4105doc 34106Comm Loss: Generator Up To Speed Input Circuit 1Diagnostic flag. Needs: Engine/GeneratorUINT16Read0 = Normal; 1 = In Alarm
IR4106doc 34107Comm Loss: Generator Up To Speed Input Circuit 2Diagnostic flag. Needs: Engine/GeneratorUINT16Read0 = Normal; 1 = In Alarm
IR4107doc 34108Comm Loss: Heat Recovery Entering Water TempDiagnostic flag. Needs: Heat RecoveryUINT16Read0 = Normal; 1 = In Alarm
IR4108doc 34109Comm Loss: Heat Recovery Leaving Water TempDiagnostic flag. Needs: Heat RecoveryUINT16Read0 = Normal; 1 = In Alarm
IR4112doc 34113Comm Loss: Ice Building RelayDiagnostic flag. Needs: Ice BuildingUINT16Read0 = Normal; 1 = In Alarm
IR4113doc 34114Comm Loss: IGV First Stage Actuator Circuit 1Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4114doc 34115Comm Loss: IGV First Stage Actuator Circuit 2Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4115doc 34116Comm Loss: IGV Second Stage Actuator Circuit 1Diagnostic flag. Needs: IGV Actuator - DualUINT16Read0 = Normal; 1 = In Alarm
IR4116doc 34117Comm Loss: IGV Second Stage Actuator Circuit 2Diagnostic flag. Needs: IGV Actuator - DualUINT16Read0 = Normal; 1 = In Alarm
IR4117doc 34118Comm Loss: Inboard Bearing Temperature Circuit 1Diagnostic flag. Needs: Bearing Temp SensorsUINT16Read0 = Normal; 1 = In Alarm
IR4118doc 34119Comm Loss: Inboard Bearing Temperature Circuit 2Diagnostic flag. Needs: Bearing Temp SensorsUINT16Read0 = Normal; 1 = In Alarm
IR4119doc 34120Comm Loss: Motor Winding Temperature 1 Circuit 1Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4120doc 34121Comm Loss: Motor Winding Temperature 1 Circuit 2Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4121doc 34122Comm Loss: Motor Winding Temperature 2 Circuit 1Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4122doc 34123Comm Loss: Motor Winding Temperature 2 Circuit 2Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4123doc 34124Comm Loss: Motor Winding Temperature 3 Circuit 1Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4124doc 34125Comm Loss: Motor Winding Temperature 3 Circuit 2Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4125doc 34126Comm Loss: Oil Cooler Solenoid Circuit 1Diagnostic flag. Needs: Oil Cooler Solenoid ValveUINT16Read0 = Normal; 1 = In Alarm
IR4126doc 34127Comm Loss: Oil Cooler Solenoid Circuit 2Diagnostic flag. Needs: Oil Cooler Solenoid ValveUINT16Read0 = Normal; 1 = In Alarm
IR4127doc 34128Comm Loss: Oil Pump Discharge Pressure Circuit 1Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4128doc 34129Comm Loss: Oil Pump Discharge Pressure Circuit 2Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4129doc 34130Comm Loss: Oil Tank Heater 4E1 Relay Circuit 1Diagnostic flag. Needs: CDHHUINT16Read0 = Normal; 1 = In Alarm
IR4130doc 34131Comm Loss: Oil Tank Heater 4E1 Relay Circuit 2Diagnostic flag. Needs: CDHHUINT16Read0 = Normal; 1 = In Alarm
IR4131doc 34132Comm Loss: Oil Tank Heater 4E2 Relay Circuit 1Diagnostic flag. Needs: CDHHUINT16Read0 = Normal; 1 = In Alarm
IR4132doc 34133Comm Loss: Oil Tank Heater 4E2 Relay Circuit 2Diagnostic flag. Needs: CDHHUINT16Read0 = Normal; 1 = In Alarm
IR4133doc 34134Comm Loss: Oil Tank Heater Relay Circuit 1Diagnostic flag. Needs: CDHF,GUINT16Read0 = Normal; 1 = In Alarm
IR4134doc 34135Comm Loss: Oil Tank Heater Relay Circuit 2Diagnostic flag. Needs: CDHF,GUINT16Read0 = Normal; 1 = In Alarm
IR4135doc 34136Comm Loss: Oil Tank Pressure Circuit 1Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4136doc 34137Comm Loss: Oil Tank Pressure Circuit 2Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4137doc 34138Comm Loss: Oil Tank Temperature Circuit 1Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4138doc 34139Comm Loss: Oil Tank Temperature Circuit 2Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4139doc 34140Comm Loss: Oil Vent Line Circuit 1Diagnostic flag. Needs: CDHHUINT16Read0 = Normal; 1 = In Alarm
IR4140doc 34141Comm Loss: Oil Vent Line Circuit 2Diagnostic flag. Needs: CDHHUINT16Read0 = Normal; 1 = In Alarm
IR4141doc 34142Comm Loss: Oil/Refrigerant Pump Relay Circuit 1Diagnostic flag. Needs: CDHF,GUINT16Read0 = Normal; 1 = In Alarm
IR4142doc 34143Comm Loss: Oil/Refrigerant Pump Relay Circuit 2Diagnostic flag. Needs: CDHF,GUINT16Read0 = Normal; 1 = In Alarm
IR4143doc 34144Comm Loss: Outboard Bearing Pad Temp 1 Circuit 1Diagnostic flag. Needs: CDHHUINT16Read0 = Normal; 1 = In Alarm
IR4144doc 34145Comm Loss: Outboard Bearing Pad Temp 1 Circuit 2Diagnostic flag. Needs: CDHHUINT16Read0 = Normal; 1 = In Alarm
IR4145doc 34146Comm Loss: Outboard Bearing Pad Temp 2 Circuit 1Diagnostic flag. Needs: CDHHUINT16Read0 = Normal; 1 = In Alarm
IR4146doc 34147Comm Loss: Outboard Bearing Pad Temp 2 Circuit 2Diagnostic flag. Needs: CDHHUINT16Read0 = Normal; 1 = In Alarm
IR4147doc 34148Comm Loss: Outboard Bearing Pad Temp 3 Circuit 1Diagnostic flag. Needs: CDHHUINT16Read0 = Normal; 1 = In Alarm
IR4148doc 34149Comm Loss: Outboard Bearing Pad Temp 3 Circuit 2Diagnostic flag. Needs: CDHHUINT16Read0 = Normal; 1 = In Alarm
IR4149doc 34150Comm Loss: Outboard Bearing Temperature Circuit 1Diagnostic flag. Needs: Bearing Temp SensorsUINT16Read0 = Normal; 1 = In Alarm
IR4150doc 34151Comm Loss: Outboard Bearing Temperature Circuit 2Diagnostic flag. Needs: Bearing Temp SensorsUINT16Read0 = Normal; 1 = In Alarm
IR4151doc 34152Comm Loss: Outdoor Air TemperatureDiagnostic flag. Needs: Outdoor Air Temp SensorUINT16Read0 = Normal; 1 = In Alarm
IR4152doc 34153Comm Loss: Programmable Relay Board 1Diagnostic flag. Needs: Operating Status Programmable RelaysUINT16Read0 = Normal; 1 = In Alarm
IR4153doc 34154Comm Loss: Programmable Relay Board 2Diagnostic flag. Needs: Operating Status Programmable RelaysUINT16Read0 = Normal; 1 = In Alarm
IR4154doc 34155Comm Loss: Purge Alarm Relay Circuit 1Diagnostic flag. Needs: PurgeUINT16Read0 = Normal; 1 = In Alarm
IR4155doc 34156Comm Loss: Purge Alarm Relay Circuit 2Diagnostic flag. Needs: PurgeUINT16Read0 = Normal; 1 = In Alarm
IR4156doc 34157Comm Loss: Purge Carbon Tank Heater Rly Circuit 1Diagnostic flag. Needs: Purge w/Carbon tankUINT16Read0 = Normal; 1 = In Alarm
IR4157doc 34158Comm Loss: Purge Carbon Tank Heater Rly Circuit 2Diagnostic flag. Needs: Purge w/Carbon tankUINT16Read0 = Normal; 1 = In Alarm
IR4158doc 34159Comm Loss: Purge Carbon Tank Temperature Circuit 1Diagnostic flag. Needs: Purge w/Carbon tankUINT16Read0 = Normal; 1 = In Alarm
IR4159doc 34160Comm Loss: Purge Carbon Tank Temperature Circuit 2Diagnostic flag. Needs: Purge w/Carbon tankUINT16Read0 = Normal; 1 = In Alarm
IR4160doc 34161Comm Loss: Purge Condensing Unit Relay Circuit 1Diagnostic flag. Needs: PurgeUINT16Read0 = Normal; 1 = In Alarm
IR4161doc 34162Comm Loss: Purge Condensing Unit Relay Circuit 2Diagnostic flag. Needs: PurgeUINT16Read0 = Normal; 1 = In Alarm
IR4162doc 34163Comm Loss: Purge Cprsr Suction Rfgt Temp Circuit 1Diagnostic flag. Needs: PurgeUINT16Read0 = Normal; 1 = In Alarm
IR4163doc 34164Comm Loss: Purge Cprsr Suction Rfgt Temp Circuit 2Diagnostic flag. Needs: PurgeUINT16Read0 = Normal; 1 = In Alarm
IR4164doc 34165Comm Loss: Purge Exhaust Solenoid Output Circuit 1Diagnostic flag. Needs: PurgeUINT16Read0 = Normal; 1 = In Alarm
IR4165doc 34166Comm Loss: Purge Exhaust Solenoid Output Circuit 2Diagnostic flag. Needs: PurgeUINT16Read0 = Normal; 1 = In Alarm
IR4166doc 34167Comm Loss: Purge Liquid Level Switch Circuit 1Diagnostic flag. Needs: PurgeUINT16Read0 = Normal; 1 = In Alarm
IR4167doc 34168Comm Loss: Purge Liquid Level Switch Circuit 2Diagnostic flag. Needs: PurgeUINT16Read0 = Normal; 1 = In Alarm
IR4168doc 34169Comm Loss: Purge Liquid Temperature Circuit 1Diagnostic flag. Needs: PurgeUINT16Read0 = Normal; 1 = In Alarm
IR4169doc 34170Comm Loss: Purge Liquid Temperature Circuit 2Diagnostic flag. Needs: PurgeUINT16Read0 = Normal; 1 = In Alarm
IR4170doc 34171Comm Loss: Purge Pumpout Relay Circuit 1Diagnostic flag. Needs: PurgeUINT16Read0 = Normal; 1 = In Alarm
IR4171doc 34172Comm Loss: Purge Pumpout Relay Circuit 2Diagnostic flag. Needs: PurgeUINT16Read0 = Normal; 1 = In Alarm
IR4172doc 34173Comm Loss: Purge Pumpout Solenoid Output Circuit 1Diagnostic flag. Needs: PurgeUINT16Read0 = Normal; 1 = In Alarm
IR4173doc 34174Comm Loss: Purge Pumpout Solenoid Output Circuit 2Diagnostic flag. Needs: PurgeUINT16Read0 = Normal; 1 = In Alarm
IR4174doc 34175Comm Loss: Purge Regen Solenoid Relay Circuit 1Diagnostic flag. Needs: Purge w/Carbon tankUINT16Read0 = Normal; 1 = In Alarm
IR4175doc 34176Comm Loss: Purge Regen Solenoid Relay Circuit 2Diagnostic flag. Needs: Purge w/Carbon tankUINT16Read0 = Normal; 1 = In Alarm
IR4176doc 34177Comm Loss: Refrigerant Monitor InputDiagnostic flag. Needs: Refrigerant MonitorUINT16Read0 = Normal; 1 = In Alarm
IR4177doc 34178Comm Loss: Starter Circuit 1Depends on starter/drive options; see the source configuration column.UINT16Read0 = Normal; 1 = In Alarm
IR4178doc 34179Comm Loss: Starter Circuit 2Depends on starter/drive options; see the source configuration column.UINT16Read0 = Normal; 1 = In Alarm
IR4179doc 34180Comm Loss: Starter Fault Circuit 1Diagnostic flag. Needs: Solid State Starters Remote Mount Non-Comm AFDUINT16Read0 = Normal; 1 = In Alarm
IR4180doc 34181Comm Loss: Starter Fault Circuit 2Diagnostic flag. Needs: Solid State Starters Remote Mount Non-Comm AFDUINT16Read0 = Normal; 1 = In Alarm
IR4181doc 34182Comm Loss: Unit Purge Alarm RelayDiagnostic flag. Needs: PurgeUINT16Read0 = Normal; 1 = In Alarm
IR4182doc 34183Diagnostic: Compressor Did Not Accelerate: Shutdown Circuit 1Diagnostic flag. Needs: EM Starters Solid State Starters Remote Mount Non-Comm AFDUINT16Read0 = Normal; 1 = In Alarm
IR4183doc 34184Diagnostic: Compressor Did Not Accelerate: Shutdown Circuit 2Diagnostic flag. Needs: EM Starters Solid State Starters Remote Mount Non-Comm AFDUINT16Read0 = Normal; 1 = In Alarm
IR4184doc 34185Diagnostic: Cond Saturated Refrigerant Temp Sensor Circuit 1Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4185doc 34186Diagnostic: Cond Saturated Refrigerant Temp Sensor Circuit 2Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4186doc 34187Diagnostic: Condenser Diff Water Pressure XdcrDiagnostic flag. Needs: Cond Water Flow Measurement - Differential PressureUINT16Read0 = Normal; 1 = In Alarm
IR4187doc 34188Diagnostic: Condenser Entering Water PressureDiagnostic flag. Needs: Cond Water Flow Measurement - Dual Pressure SensorsUINT16Read0 = Normal; 1 = In Alarm
IR4188doc 34189Diagnostic: Condenser Entering Water Temp SensorDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4189doc 34190Diagnostic: Condenser High Pressure Cutout Circuit 1Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4190doc 34191Diagnostic: Condenser High Pressure Cutout Circuit 2Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4191doc 34192Diagnostic: Condenser Leaving Water PressureDiagnostic flag. Needs: Cond Water Flow Measurement - Dual Pressure SensorsUINT16Read0 = Normal; 1 = In Alarm
IR4192doc 34193Diagnostic: Condenser Leaving Water Temp SensorDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4193doc 34194Diagnostic: Condenser Liquid Level Sensor Circuit 1Diagnostic flag. Needs: Economizer BypassUINT16Read0 = Normal; 1 = In Alarm
IR4194doc 34195Diagnostic: Condenser Liquid Level Sensor Circuit 2Diagnostic flag. Needs: Economizer BypassUINT16Read0 = Normal; 1 = In Alarm
IR4195doc 34196Diagnostic: Condenser Refrigerant Pressure Xdcr Circuit 1Diagnostic flag. Needs: Cond Pressure SensorUINT16Read0 = Normal; 1 = In Alarm
IR4196doc 34197Diagnostic: Condenser Refrigerant Pressure Xdcr Circuit 2Diagnostic flag. Needs: Cond Pressure SensorUINT16Read0 = Normal; 1 = In Alarm
IR4197doc 34198Diagnostic: Condenser Water Flow LostDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4198doc 34199Diagnostic: Condenser Water Flow OverdueDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4199doc 34200Diagnostic: Cprsr Did Not Accelerate: Transition Circuit 1Diagnostic flag. Needs: EM Starters Solid State Starters Remote Mount Non-Comm AFDUINT16Read0 = Normal; 1 = In Alarm
IR4200doc 34201Diagnostic: Cprsr Did Not Accelerate: Transition Circuit 2Diagnostic flag. Needs: EM Starters Solid State Starters Remote Mount Non-Comm AFDUINT16Read0 = Normal; 1 = In Alarm
IR4201doc 34202Diagnostic: Cprsr Discharge Refrigerant Temp Sensor Circuit 1Diagnostic flag. Needs: Compressor Refrigerant Discharge Temp SensorUINT16Read0 = Normal; 1 = In Alarm
IR4202doc 34203Diagnostic: Cprsr Discharge Refrigerant Temp Sensor Circuit 2Diagnostic flag. Needs: Compressor Refrigerant Discharge Temp SensorUINT16Read0 = Normal; 1 = In Alarm
IR4203doc 34204Diagnostic: Differential Oil Pressure Overdue Circuit 1Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4204doc 34205Diagnostic: Differential Oil Pressure Overdue Circuit 2Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4206doc 34207Diagnostic: Emergency StopDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4207doc 34208Diagnostic: Evap Saturated Refrigerant Temp Sensor Circuit 1Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4208doc 34209Diagnostic: Evap Saturated Refrigerant Temp Sensor Circuit 2Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4209doc 34210Diagnostic: Evaporator Diff Water Pressure XdcrDiagnostic flag. Needs: Evap Water Flow Measurement - Differential PressureUINT16Read0 = Normal; 1 = In Alarm
IR4210doc 34211Diagnostic: Evaporator Entering Water PressureDiagnostic flag. Needs: Evap Water Flow Measurement - Dual Pressure SensorsUINT16Read0 = Normal; 1 = In Alarm
IR4211doc 34212Diagnostic: Evaporator Entering Water Temp SensorDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4212doc 34213Diagnostic: Evaporator Leaving Water PressureDiagnostic flag. Needs: Evap Water Flow Measurement - Dual Pressure SensorsUINT16Read0 = Normal; 1 = In Alarm
IR4213doc 34214Diagnostic: Evaporator Leaving Water Temp SensorDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4214doc 34215Diagnostic: Evaporator Refrigerant Pressure Xdcr Circuit 1Diagnostic flag. Needs: Evap Pressure SensorUINT16Read0 = Normal; 1 = In Alarm
IR4215doc 34216Diagnostic: Evaporator Refrigerant Pressure Xdcr Circuit 2Diagnostic flag. Needs: Evap Pressure SensorUINT16Read0 = Normal; 1 = In Alarm
IR4216doc 34217Diagnostic: Evaporator Water Flow LostDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4217doc 34218Diagnostic: Evaporator Water Flow OverdueDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4218doc 34219Diagnostic: Excessive Loss of CommunicationDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4221doc 34222Diagnostic: Extended Compressor Surge Circuit 1Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4222doc 34223Diagnostic: Extended Compressor Surge Circuit 2Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4223doc 34224Diagnostic: External Base Loading SetpointDiagnostic flag. Needs: Base LoadingUINT16Read0 = Normal; 1 = In Alarm
IR4224doc 34225Diagnostic: External Chilled/Hot Water SetpointDiagnostic flag. Needs: External Chilled Water SetpointUINT16Read0 = Normal; 1 = In Alarm
IR4225doc 34226Diagnostic: External Demand Limit SetpointDiagnostic flag. Needs: External Demand Limit SetpointUINT16Read0 = Normal; 1 = In Alarm
IR4230doc 34231Diagnostic: Generator Fault Relay Open Circuit 1Diagnostic flag. Needs: Engine/GeneratorUINT16Read0 = Normal; 1 = In Alarm
IR4231doc 34232Diagnostic: Generator Fault Relay Open Circuit 2Diagnostic flag. Needs: Engine/GeneratorUINT16Read0 = Normal; 1 = In Alarm
IR4232doc 34233Diagnostic: Generator Ready Signal Overdue Circuit 1Diagnostic flag. Needs: Engine/GeneratorUINT16Read0 = Normal; 1 = In Alarm
IR4233doc 34234Diagnostic: Generator Ready Signal Overdue Circuit 2Diagnostic flag. Needs: Engine/GeneratorUINT16Read0 = Normal; 1 = In Alarm
IR4234doc 34235Diagnostic: Heat Recovery Entering Water Temp SensorDiagnostic flag. Needs: Heat RecoveryUINT16Read0 = Normal; 1 = In Alarm
IR4235doc 34236Diagnostic: Heat Recovery Leaving Water Temp SensorDiagnostic flag. Needs: Heat RecoveryUINT16Read0 = Normal; 1 = In Alarm
IR4236doc 34237Diagnostic: High Cprsr Rfgt Discharge Temperature Circuit 1Diagnostic flag. Needs: Compressor Refrigerant Discharge Temp SensorUINT16Read0 = Normal; 1 = In Alarm
IR4237doc 34238Diagnostic: High Cprsr Rfgt Discharge Temperature Circuit 2Diagnostic flag. Needs: Compressor Refrigerant Discharge Temp SensorUINT16Read0 = Normal; 1 = In Alarm
IR4238doc 34239Diagnostic: High Differential Refrigerant Pressure Circuit 1Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4239doc 34240Diagnostic: High Differential Refrigerant Pressure Circuit 2Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4240doc 34241Diagnostic: High Evaporator Refrigerant Temperature Circuit 1Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4241doc 34242Diagnostic: High Evaporator Refrigerant Temperature Circuit 2Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4242doc 34243Diagnostic: High Evaporator Water TemperatureDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4243doc 34244Diagnostic: High Inboard Bearing Temperature Circuit 1Diagnostic flag. Needs: Bearing Temp SensorsUINT16Read0 = Normal; 1 = In Alarm
IR4244doc 34245Diagnostic: High Inboard Bearing Temperature Circuit 2Diagnostic flag. Needs: Bearing Temp SensorsUINT16Read0 = Normal; 1 = In Alarm
IR4245doc 34246Diagnostic: High Motor Winding Temperature 1 Circuit 1Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4246doc 34247Diagnostic: High Motor Winding Temperature 1 Circuit 2Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4247doc 34248Diagnostic: High Motor Winding Temperature 2 Circuit 1Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4248doc 34249Diagnostic: High Motor Winding Temperature 2 Circuit 2Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4249doc 34250Diagnostic: High Motor Winding Temperature 3 Circuit 1Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4250doc 34251Diagnostic: High Motor Winding Temperature 3 Circuit 2Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4251doc 34252Diagnostic: High Oil Temperature Circuit 1Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4252doc 34253Diagnostic: High Oil Temperature Circuit 2Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4253doc 34254Diagnostic: High Outboard Bearing Pad Temperature 1 Circuit 1Diagnostic flag. Needs: CDHHUINT16Read0 = Normal; 1 = In Alarm
IR4254doc 34255Diagnostic: High Outboard Bearing Pad Temperature 1 Circuit 2Diagnostic flag. Needs: CDHHUINT16Read0 = Normal; 1 = In Alarm
IR4255doc 34256Diagnostic: High Outboard Bearing Pad Temperature 2 Circuit 1Diagnostic flag. Needs: CDHHUINT16Read0 = Normal; 1 = In Alarm
IR4256doc 34257Diagnostic: High Outboard Bearing Pad Temperature 2 Circuit 2Diagnostic flag. Needs: CDHHUINT16Read0 = Normal; 1 = In Alarm
IR4257doc 34258Diagnostic: High Outboard Bearing Pad Temperature 3 Circuit 1Diagnostic flag. Needs: CDHHUINT16Read0 = Normal; 1 = In Alarm
IR4258doc 34259Diagnostic: High Outboard Bearing Pad Temperature 3 Circuit 2Diagnostic flag. Needs: CDHHUINT16Read0 = Normal; 1 = In Alarm
IR4259doc 34260Diagnostic: High Outboard Bearing Temp Circuit 1Diagnostic flag. Needs: Bearing Temp SensorsUINT16Read0 = Normal; 1 = In Alarm
IR4260doc 34261Diagnostic: High Outboard Bearing Temp Circuit 2Diagnostic flag. Needs: Bearing Temp SensorsUINT16Read0 = Normal; 1 = In Alarm
IR4261doc 34262Diagnostic: High Vacuum Lockout Circuit 1Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4262doc 34263Diagnostic: High Vacuum Lockout Circuit 2Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4266doc 34267Diagnostic: HPC/High AFD Heat Sink Water Pressure Circuit 1Diagnostic flag. Needs: Unit Mount AFD - AFDD,E,F (LF2) Remote Mount Comm AFD - (PF7000)UINT16Read0 = Normal; 1 = In Alarm
IR4267doc 34268Diagnostic: HPC/High AFD Heat Sink Water Pressure Circuit 2Diagnostic flag. Needs: Unit Mount AFD - AFDD,E,F (LF2) Remote Mount Comm AFD - (PF7000)UINT16Read0 = Normal; 1 = In Alarm
IR4268doc 34269Diagnostic: Inboard Bearing Temp Sensor Circuit 1Diagnostic flag. Needs: Bearing Temp SensorsUINT16Read0 = Normal; 1 = In Alarm
IR4269doc 34270Diagnostic: Inboard Bearing Temp Sensor Circuit 2Diagnostic flag. Needs: Bearing Temp SensorsUINT16Read0 = Normal; 1 = In Alarm
IR4270doc 34271Diagnostic: Inverted Condenser Water TemperatureDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4271doc 34272Diagnostic: Inverted Evaporator Water TemperatureDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4272doc 34273Diagnostic: Loss of Economizer Bypass Valve Control Circuit 1Diagnostic flag. Needs: Economizer BypassUINT16Read0 = Normal; 1 = In Alarm
IR4273doc 34274Diagnostic: Loss of Economizer Bypass Valve Control Circuit 2Diagnostic flag. Needs: Economizer BypassUINT16Read0 = Normal; 1 = In Alarm
IR4274doc 34275Diagnostic: Low Differential Oil Pressure Circuit 1Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4275doc 34276Diagnostic: Low Differential Oil Pressure Circuit 2Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4276doc 34277Diagnostic: Low Evap Leaving Water Temp: Unit OffDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4277doc 34278Diagnostic: Low Evap Leaving Water Temp: Unit OnDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4278doc 34279Diagnostic: Low Evaporator Refrigerant Temperature Circuit 1Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4279doc 34280Diagnostic: Low Evaporator Refrigerant Temperature Circuit 2Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4280doc 34281Diagnostic: Low Evaporator Water FlowDiagnostic flag. Needs: Evap Water Flow MeasurementUINT16Read0 = Normal; 1 = In Alarm
IR4281doc 34282Diagnostic: Low Oil Temperature Circuit 1Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4282doc 34283Diagnostic: Low Oil Temperature Circuit 2Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4283doc 34284Diagnostic: Momentary Power Loss Circuit 1Diagnostic flag. Needs: Momentary Power LossUINT16Read0 = Normal; 1 = In Alarm
IR4284doc 34285Diagnostic: Momentary Power Loss Circuit 2Diagnostic flag. Needs: Momentary Power LossUINT16Read0 = Normal; 1 = In Alarm
IR4285doc 34286Diagnostic: Motor Current Overload Circuit 1Diagnostic flag. Needs: EM Starters Solid State Starters Remote Mount Non-Comm AFDUINT16Read0 = Normal; 1 = In Alarm
IR4286doc 34287Diagnostic: Motor Current Overload Circuit 2Diagnostic flag. Needs: EM Starters Solid State Starters Remote Mount Non-Comm AFDUINT16Read0 = Normal; 1 = In Alarm
IR4287doc 34288Diagnostic: Motor Winding Temperature 1 Sensor Circuit 1Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4288doc 34289Diagnostic: Motor Winding Temperature 1 Sensor Circuit 2Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4289doc 34290Diagnostic: Motor Winding Temperature 2 Sensor Circuit 1Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4290doc 34291Diagnostic: Motor Winding Temperature 2 Sensor Circuit 2Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4291doc 34292Diagnostic: Motor Winding Temperature 3 Sensor Circuit 1Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4292doc 34293Diagnostic: Motor Winding Temperature 3 Sensor Circuit 2Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4293doc 34294Diagnostic: MP: Invalid ConfigurationDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4294doc 34295Diagnostic: MP: Reset Has OccurredDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4295doc 34296Diagnostic: Oil Pressure Sensor Calibration Circuit 1Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4296doc 34297Diagnostic: Oil Pressure Sensor Calibration Circuit 2Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4297doc 34298Diagnostic: Oil Pump Discharge Pressure Transducer Circuit 1Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4298doc 34299Diagnostic: Oil Pump Discharge Pressure Transducer Circuit 2Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4299doc 34300Diagnostic: Oil Tank Pressure Transducer Circuit 1Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4300doc 34301Diagnostic: Oil Tank Pressure Transducer Circuit 2Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4301doc 34302Diagnostic: Oil Tank Temperature Sensor Circuit 1Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4302doc 34303Diagnostic: Oil Tank Temperature Sensor Circuit 2Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4303doc 34304Diagnostic: Outboard Bearing Pad Temp 1 Sensor Circuit 1Diagnostic flag. Needs: CDHHUINT16Read0 = Normal; 1 = In Alarm
IR4304doc 34305Diagnostic: Outboard Bearing Pad Temp 1 Sensor Circuit 2Diagnostic flag. Needs: CDHHUINT16Read0 = Normal; 1 = In Alarm
IR4305doc 34306Diagnostic: Outboard Bearing Pad Temp 2 Sensor Circuit 1Diagnostic flag. Needs: CDHHUINT16Read0 = Normal; 1 = In Alarm
IR4306doc 34307Diagnostic: Outboard Bearing Pad Temp 2 Sensor Circuit 2Diagnostic flag. Needs: CDHHUINT16Read0 = Normal; 1 = In Alarm
IR4307doc 34308Diagnostic: Outboard Bearing Pad Temp 3 Sensor Circuit 1Diagnostic flag. Needs: CDHHUINT16Read0 = Normal; 1 = In Alarm
IR4308doc 34309Diagnostic: Outboard Bearing Pad Temp 3 Sensor Circuit 2Diagnostic flag. Needs: CDHHUINT16Read0 = Normal; 1 = In Alarm
IR4309doc 34310Diagnostic: Outboard Bearing Temperature Sensor Circuit 1Diagnostic flag. Needs: CDHHUINT16Read0 = Normal; 1 = In Alarm
IR4310doc 34311Diagnostic: Outboard Bearing Temperature Sensor Circuit 2Diagnostic flag. Needs: CDHHUINT16Read0 = Normal; 1 = In Alarm
IR4311doc 34312Diagnostic: Outdoor Air Temperature SensorDiagnostic flag. Needs: Outdoor Air Temp SensorUINT16Read0 = Normal; 1 = In Alarm
IR4312doc 34313Diagnostic: Over Voltage Circuit 1Diagnostic flag. Needs: Line Voltage SensingUINT16Read0 = Normal; 1 = In Alarm
IR4313doc 34314Diagnostic: Over Voltage Circuit 2Diagnostic flag. Needs: Line Voltage SensingUINT16Read0 = Normal; 1 = In Alarm
IR4314doc 34315Diagnostic: Phase Loss Circuit 1Diagnostic flag. Needs: EM Starters Solid State Starters Remote Mount Non-Comm AFDUINT16Read0 = Normal; 1 = In Alarm
IR4315doc 34316Diagnostic: Phase Loss Circuit 2Diagnostic flag. Needs: EM Starters Solid State Starters Remote Mount Non-Comm AFDUINT16Read0 = Normal; 1 = In Alarm
IR4316doc 34317Diagnostic: Phase Reversal Circuit 1Diagnostic flag. Needs: EM Starters Solid State Starters Remote Mount Non-Comm AFDUINT16Read0 = Normal; 1 = In Alarm
IR4317doc 34318Diagnostic: Phase Reversal Circuit 2Diagnostic flag. Needs: EM Starters Solid State Starters Remote Mount Non-Comm AFDUINT16Read0 = Normal; 1 = In Alarm
IR4318doc 34319Diagnostic: Power Loss Circuit 1Diagnostic flag. Needs: EM Starters Solid State Starters Remote Mount Non-Comm AFDUINT16Read0 = Normal; 1 = In Alarm
IR4319doc 34320Diagnostic: Power Loss Circuit 2Diagnostic flag. Needs: EM Starters Solid State Starters Remote Mount Non-Comm AFDUINT16Read0 = Normal; 1 = In Alarm
IR4320doc 34321Diagnostic: Purge Carbon Regen Temp Limit Exceeded Circuit 1Diagnostic flag. Needs: Purge w/Carbon tankUINT16Read0 = Normal; 1 = In Alarm
IR4321doc 34322Diagnostic: Purge Carbon Regen Temp Limit Exceeded Circuit 2Diagnostic flag. Needs: Purge w/Carbon tankUINT16Read0 = Normal; 1 = In Alarm
IR4322doc 34323Diagnostic: Purge Carbon Regen Temp Not Satisfied Circuit 1Diagnostic flag. Needs: Purge w/Carbon tankUINT16Read0 = Normal; 1 = In Alarm
IR4323doc 34324Diagnostic: Purge Carbon Regen Temp Not Satisfied Circuit 2Diagnostic flag. Needs: Purge w/Carbon tankUINT16Read0 = Normal; 1 = In Alarm
IR4324doc 34325Diagnostic: Purge Carbon Regen Temperature Too Low Circuit 1Diagnostic flag. Needs: Purge w/Carbon tankUINT16Read0 = Normal; 1 = In Alarm
IR4325doc 34326Diagnostic: Purge Carbon Regen Temperature Too Low Circuit 2Diagnostic flag. Needs: Purge w/Carbon tankUINT16Read0 = Normal; 1 = In Alarm
IR4326doc 34327Diagnostic: Purge Carbon Tank Temperature Sensor Circuit 1Diagnostic flag. Needs: Purge w/Carbon tankUINT16Read0 = Normal; 1 = In Alarm
IR4327doc 34328Diagnostic: Purge Carbon Tank Temperature Sensor Circuit 2Diagnostic flag. Needs: Purge w/Carbon tankUINT16Read0 = Normal; 1 = In Alarm
IR4328doc 34329Diagnostic: Purge Cprsr Suction Rfgt Temp Sensor Circuit 1Diagnostic flag. Needs: PurgeUINT16Read0 = Normal; 1 = In Alarm
IR4329doc 34330Diagnostic: Purge Cprsr Suction Rfgt Temp Sensor Circuit 2Diagnostic flag. Needs: PurgeUINT16Read0 = Normal; 1 = In Alarm
IR4330doc 34331Diagnostic: Purge Daily Pumpout Limit Exceeded Circuit 1Diagnostic flag. Needs: PurgeUINT16Read0 = Normal; 1 = In Alarm
IR4331doc 34332Diagnostic: Purge Daily Pumpout Limit Exceeded Circuit 2Diagnostic flag. Needs: PurgeUINT16Read0 = Normal; 1 = In Alarm
IR4332doc 34333Diagnostic: Purge Liquid Level Too High Continuously Circuit 1Diagnostic flag. Needs: PurgeUINT16Read0 = Normal; 1 = In Alarm
IR4333doc 34334Diagnostic: Purge Liquid Level Too High Continuously Circuit 2Diagnostic flag. Needs: PurgeUINT16Read0 = Normal; 1 = In Alarm
IR4334doc 34335Diagnostic: Purge Liquid Level Too High Warning Circuit 1Diagnostic flag. Needs: PurgeUINT16Read0 = Normal; 1 = In Alarm
IR4335doc 34336Diagnostic: Purge Liquid Level Too High Warning Circuit 2Diagnostic flag. Needs: PurgeUINT16Read0 = Normal; 1 = In Alarm
IR4336doc 34337Diagnostic: Purge Liquid Temperature Sensor Circuit 1Diagnostic flag. Needs: PurgeUINT16Read0 = Normal; 1 = In Alarm
IR4337doc 34338Diagnostic: Purge Liquid Temperature Sensor Circuit 2Diagnostic flag. Needs: PurgeUINT16Read0 = Normal; 1 = In Alarm
IR4338doc 34339Diagnostic: Purge Regen Cooldown Temp Too High Circuit 1Diagnostic flag. Needs: Purge w/Carbon tankUINT16Read0 = Normal; 1 = In Alarm
IR4339doc 34340Diagnostic: Purge Regen Cooldown Temp Too High Circuit 2Diagnostic flag. Needs: Purge w/Carbon tankUINT16Read0 = Normal; 1 = In Alarm
IR4341doc 34342Diagnostic: Refrigerant Monitor InputDiagnostic flag. Needs: Refrigerant MonitorUINT16Read0 = Normal; 1 = In Alarm
IR4342doc 34343Diagnostic: Restart Inhibit Circuit 1Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4343doc 34344Diagnostic: Restart Inhibit Circuit 2Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4344doc 34345Diagnostic: Severe Current Unbalance Circuit 1Diagnostic flag. Needs: Line Voltage SensingUINT16Read0 = Normal; 1 = In Alarm
IR4345doc 34346Diagnostic: Severe Current Unbalance Circuit 2Diagnostic flag. Needs: Line Voltage SensingUINT16Read0 = Normal; 1 = In Alarm
IR4346doc 34347Diagnostic: Software Error 1001: Call Trane ServiceDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4347doc 34348Diagnostic: Software Error 1004: Call Trane ServiceDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4348doc 34349Diagnostic: Starter Comm Loss: Main Processor Circuit 1Diagnostic flag. Needs: EM Starters Solid State Starters Remote Mount Non-Comm AFDUINT16Read0 = Normal; 1 = In Alarm
IR4349doc 34350Diagnostic: Starter Comm Loss: Main Processor Circuit 2Diagnostic flag. Needs: EM Starters Solid State Starters Remote Mount Non-Comm AFDUINT16Read0 = Normal; 1 = In Alarm
IR4350doc 34351Diagnostic: Starter Contactor Interrupt Failure Circuit 1Diagnostic flag. Needs: EM Starters Solid State Starters Remote Mount Non-Comm AFDUINT16Read0 = Normal; 1 = In Alarm
IR4351doc 34352Diagnostic: Starter Contactor Interrupt Failure Circuit 2Diagnostic flag. Needs: EM Starters Solid State Starters Remote Mount Non-Comm AFDUINT16Read0 = Normal; 1 = In Alarm
IR4352doc 34353Diagnostic: Starter Did Not Fully Accelerate Circuit 1Diagnostic flag. Needs: EM Starters Solid State Starters Remote Mount Non-Comm AFDUINT16Read0 = Normal; 1 = In Alarm
IR4353doc 34354Diagnostic: Starter Did Not Fully Accelerate Circuit 2Diagnostic flag. Needs: EM Starters Solid State Starters Remote Mount Non-Comm AFDUINT16Read0 = Normal; 1 = In Alarm
IR4354doc 34355Diagnostic: Starter Did Not Transition Circuit 1Diagnostic flag. Needs: EM Starters Solid State Starters Remote Mount Non-Comm AFDUINT16Read0 = Normal; 1 = In Alarm
IR4355doc 34356Diagnostic: Starter Did Not Transition Circuit 2Diagnostic flag. Needs: EM Starters Solid State Starters Remote Mount Non-Comm AFDUINT16Read0 = Normal; 1 = In Alarm
IR4356doc 34357Diagnostic: Starter Dry Run Test Circuit 1Diagnostic flag. Needs: EM Starters Solid State Starters Remote Mount Non-Comm AFDUINT16Read0 = Normal; 1 = In Alarm
IR4357doc 34358Diagnostic: Starter Dry Run Test Circuit 2Diagnostic flag. Needs: EM Starters Solid State Starters Remote Mount Non-Comm AFDUINT16Read0 = Normal; 1 = In Alarm
IR4358doc 34359Diagnostic: Starter Failed to Arm/ Start Circuit 1Depends on starter/drive options; see the source configuration column.UINT16Read0 = Normal; 1 = In Alarm
IR4359doc 34360Diagnostic: Starter Failed to Arm/ Start Circuit 2Depends on starter/drive options; see the source configuration column.UINT16Read0 = Normal; 1 = In Alarm
IR4360doc 34361Diagnostic: Starter Fault Circuit 1Diagnostic flag. Needs: EM Starters Solid State Starters Remote Mount Non-Comm AFDUINT16Read0 = Normal; 1 = In Alarm
IR4361doc 34362Diagnostic: Starter Fault Circuit 2Diagnostic flag. Needs: EM Starters Solid State Starters Remote Mount Non-Comm AFDUINT16Read0 = Normal; 1 = In Alarm
IR4362doc 34363Diagnostic: Starter Fault Type I Circuit 1Diagnostic flag. Needs: EM Starters Solid State Starters Remote Mount Non-Comm AFDUINT16Read0 = Normal; 1 = In Alarm
IR4363doc 34364Diagnostic: Starter Fault Type I Circuit 2Diagnostic flag. Needs: EM Starters Solid State Starters Remote Mount Non-Comm AFDUINT16Read0 = Normal; 1 = In Alarm
IR4364doc 34365Diagnostic: Starter Fault Type II Circuit 1Diagnostic flag. Needs: EM Starters Solid State Starters Remote Mount Non-Comm AFDUINT16Read0 = Normal; 1 = In Alarm
IR4365doc 34366Diagnostic: Starter Fault Type II Circuit 2Diagnostic flag. Needs: EM Starters Solid State Starters Remote Mount Non-Comm AFDUINT16Read0 = Normal; 1 = In Alarm
IR4366doc 34367Diagnostic: Starter Fault Type III Circuit 1Diagnostic flag. Needs: EM Starters Solid State Starters Remote Mount Non-Comm AFDUINT16Read0 = Normal; 1 = In Alarm
IR4367doc 34368Diagnostic: Starter Fault Type III Circuit 2Diagnostic flag. Needs: EM Starters Solid State Starters Remote Mount Non-Comm AFDUINT16Read0 = Normal; 1 = In Alarm
IR4368doc 34369Diagnostic: Starter Module Memory Error Type 1 Circuit 1Diagnostic flag. Needs: EM Starters Solid State Starters Remote Mount Non-Comm AFDUINT16Read0 = Normal; 1 = In Alarm
IR4369doc 34370Diagnostic: Starter Module Memory Error Type 1 Circuit 2Diagnostic flag. Needs: EM Starters Solid State Starters Remote Mount Non-Comm AFDUINT16Read0 = Normal; 1 = In Alarm
IR4370doc 34371Diagnostic: Starter Module Memory Error Type 2 Circuit 1Diagnostic flag. Needs: EM Starters Solid State Starters Remote Mount Non-Comm AFDUINT16Read0 = Normal; 1 = In Alarm
IR4371doc 34372Diagnostic: Starter Module Memory Error Type 2 Circuit 2Diagnostic flag. Needs: EM Starters Solid State Starters Remote Mount Non-Comm AFDUINT16Read0 = Normal; 1 = In Alarm
IR4372doc 34373Diagnostic: Transition Complete Input Opened Circuit 1Diagnostic flag. Needs: EM Starters Solid State Starters Remote Mount Non-Comm AFDUINT16Read0 = Normal; 1 = In Alarm
IR4373doc 34374Diagnostic: Transition Complete Input Opened Circuit 2Diagnostic flag. Needs: EM Starters Solid State Starters Remote Mount Non-Comm AFDUINT16Read0 = Normal; 1 = In Alarm
IR4374doc 34375Diagnostic: Transition Complete Input Shorted Circuit 1Diagnostic flag. Needs: EM Starters Solid State Starters Remote Mount Non-Comm AFDUINT16Read0 = Normal; 1 = In Alarm
IR4375doc 34376Diagnostic: Transition Complete Input Shorted Circuit 2Diagnostic flag. Needs: EM Starters Solid State Starters Remote Mount Non-Comm AFDUINT16Read0 = Normal; 1 = In Alarm
IR4376doc 34377Diagnostic: Under Voltage Circuit 1Diagnostic flag. Needs: Line Voltage SensingUINT16Read0 = Normal; 1 = In Alarm
IR4377doc 34378Diagnostic: Under Voltage Circuit 2Diagnostic flag. Needs: Line Voltage SensingUINT16Read0 = Normal; 1 = In Alarm
IR4378doc 34379Diagnostic: Unexpected Differential Oil Pressure Circuit 1Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4379doc 34380Diagnostic: Unexpected Differential Oil Pressure Circuit 2Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4380doc 34381Diagnostic: Unexpected Starter Shutdown Circuit 1Depends on starter/drive options; see the source configuration column.UINT16Read0 = Normal; 1 = In Alarm
IR4381doc 34382Diagnostic: Unexpected Starter Shutdown Circuit 2Depends on starter/drive options; see the source configuration column.UINT16Read0 = Normal; 1 = In Alarm
IR4382doc 34383Diagnostic: AFD Bus Over Voltage Circuit 1Depends on starter/drive options; see the source configuration column.UINT16Read0 = Normal; 1 = In Alarm
IR4383doc 34384Diagnostic: AFD Bus Over Voltage Circuit 2Depends on starter/drive options; see the source configuration column.UINT16Read0 = Normal; 1 = In Alarm
IR4384doc 34385Diagnostic: AFD Bus Under Voltage Circuit 1Depends on starter/drive options; see the source configuration column.UINT16Read0 = Normal; 1 = In Alarm
IR4385doc 34386Diagnostic: AFD Bus Under Voltage Circuit 2Depends on starter/drive options; see the source configuration column.UINT16Read0 = Normal; 1 = In Alarm
IR4386doc 34387Diagnostic: AFD Motor Fault Circuit 1Diagnostic flag. Needs: Remote Mount Comm AFD - VFDB (PF6000)UINT16Read0 = Normal; 1 = In Alarm
IR4387doc 34388Diagnostic: AFD Motor Fault Circuit 2Diagnostic flag. Needs: Remote Mount Comm AFD - VFDB (PF6000)UINT16Read0 = Normal; 1 = In Alarm
IR4388doc 34389Diagnostic: AFD Precharge Fault Circuit 1Diagnostic flag. Needs: Remote Mount Comm AFD - VFDB (PF6000)UINT16Read0 = Normal; 1 = In Alarm
IR4389doc 34390Diagnostic: AFD Precharge Fault Circuit 2Diagnostic flag. Needs: Remote Mount Comm AFD - VFDB (PF6000)UINT16Read0 = Normal; 1 = In Alarm
IR4390doc 34391Diagnostic: AFD Over Temperature Circuit 1Diagnostic flag. Needs: Remote Mount Comm AFD - VFDB (PF6000)UINT16Read0 = Normal; 1 = In Alarm
IR4391doc 34392Diagnostic: AFD Over Temperature Circuit 2Diagnostic flag. Needs: Remote Mount Comm AFD - VFDB (PF6000)UINT16Read0 = Normal; 1 = In Alarm
IR4392doc 34393Diagnostic: AFD Mains Phase Loss Circuit 1Diagnostic flag. Needs: TR200 Modbus AFDUINT16Read0 = Normal; 1 = In Alarm
IR4393doc 34394Diagnostic: AFD Mains Phase Loss Circuit 2Diagnostic flag. Needs: TR200 Modbus AFDUINT16Read0 = Normal; 1 = In Alarm
IR4394doc 34395Diagnostic: AFD Motor Current Overload Circuit 1Diagnostic flag. Needs: TR200 Modbus AFDUINT16Read0 = Normal; 1 = In Alarm
IR4395doc 34396Diagnostic: AFD Motor Current Overload Circuit 2Diagnostic flag. Needs: TR200 Modbus AFDUINT16Read0 = Normal; 1 = In Alarm
IR4396doc 34397Diagnostic: AFD Ground Fault Circuit 1Diagnostic flag. Needs: TR200 Modbus AFDUINT16Read0 = Normal; 1 = In Alarm
IR4397doc 34398Diagnostic: AFD Ground Fault Circuit 2Diagnostic flag. Needs: TR200 Modbus AFDUINT16Read0 = Normal; 1 = In Alarm
IR4398doc 34399Diagnostic: AFD Short Circuit Circuit 1Diagnostic flag. Needs: TR200 Modbus AFDUINT16Read0 = Normal; 1 = In Alarm
IR4399doc 34400Diagnostic: AFD Short Circuit Circuit 2Diagnostic flag. Needs: TR200 Modbus AFDUINT16Read0 = Normal; 1 = In Alarm
IR4400doc 34401Diagnostic: AFD Safe Stop Circuit 1Diagnostic flag. Needs: TR200 Modbus AFDUINT16Read0 = Normal; 1 = In Alarm
IR4401doc 34402Diagnostic: AFD Safe Stop Circuit 2Diagnostic flag. Needs: TR200 Modbus AFDUINT16Read0 = Normal; 1 = In Alarm
IR4402doc 34403Diagnostic: AFD Fault Circuit 1Diagnostic flag. Needs: TR200 Modbus AFDUINT16Read0 = Normal; 1 = In Alarm
IR4403doc 34404Diagnostic: AFD Fault Circuit 2Diagnostic flag. Needs: TR200 Modbus AFDUINT16Read0 = Normal; 1 = In Alarm
IR4404doc 34405Diagnostic: AFD Speed Configuration Mismatch Circuit 1Diagnostic flag. Needs: TR200 Modbus AFDUINT16Read0 = Normal; 1 = In Alarm
IR4405doc 34406Diagnostic: AFD Speed Configuration Mismatch Circuit 2Diagnostic flag. Needs: TR200 Modbus AFDUINT16Read0 = Normal; 1 = In Alarm
IR4406doc 34407Diagnostic: AFD General Failure Circuit 1Diagnostic flag. Needs: TR200 Modbus AFDUINT16Read0 = Normal; 1 = In Alarm
IR4407doc 34408Diagnostic: AFD General Failure Circuit 2Diagnostic flag. Needs: TR200 Modbus AFDUINT16Read0 = Normal; 1 = In Alarm
IR4408doc 34409Comm Loss: Heat Recovery Differential Water PressureDiagnostic flag. Needs: Heat RecoveryUINT16Read0 = Normal; 1 = In Alarm
IR4409doc 34410Comm Loss: Heat Recovery Entering Water PressureDiagnostic flag. Needs: Heat RecoveryUINT16Read0 = Normal; 1 = In Alarm
IR4410doc 34411Comm Loss: Heat Recovery Leaving Water PressureDiagnostic flag. Needs: Heat RecoveryUINT16Read0 = Normal; 1 = In Alarm
IR4411doc 34412Comm Loss: Heat Recovery Water Flow SwitchDiagnostic flag. Needs: Heat RecoveryUINT16Read0 = Normal; 1 = In Alarm
IR4412doc 34413Comm Loss: External Diagnostic ResetDiagnostic flag. Needs: External Diagnostic ResetUINT16Read0 = Normal; 1 = In Alarm
IR4413doc 34414Diagnostic: Heat Recovery Diff Water PressureDiagnostic flag. Needs: Heat RecoveryUINT16Read0 = Normal; 1 = In Alarm
IR4414doc 34415Diagnostic: Heat Recovery Entering Water PressureDiagnostic flag. Needs: Heat RecoveryUINT16Read0 = Normal; 1 = In Alarm
IR4415doc 34416Diagnostic: Heat Recovery Leaving Water PressureDiagnostic flag. Needs: Heat RecoveryUINT16Read0 = Normal; 1 = In Alarm
IR4416doc 34417Diagnostic: Inverted Heat Recovery Water TemperatureDiagnostic flag. Needs: Heat RecoveryUINT16Read0 = Normal; 1 = In Alarm
IR4417doc 34418Comm Loss: Condenser Rfgt Valve Feedback Circuit 1Diagnostic flag. Needs: 6" Control ValvesUINT16Read0 = Normal; 1 = In Alarm
IR4418doc 34419Comm Loss: Condenser Rfgt Valve Feedback Circuit 2Diagnostic flag. Needs: 6" Control ValvesUINT16Read0 = Normal; 1 = In Alarm
IR4419doc 34420Comm Loss: Economizer Rfgt Valve Feedback Circuit 1Diagnostic flag. Needs: 6" Control ValvesUINT16Read0 = Normal; 1 = In Alarm
IR4420doc 34421Comm Loss: Economizer Rfgt Valve Feedback Circuit 2Diagnostic flag. Needs: 6" Control ValvesUINT16Read0 = Normal; 1 = In Alarm
IR4421doc 34422Comm Loss: Economizer Refrigerant Pressure Circuit 1Diagnostic flag. Needs: 6" or 8" Control ValvesUINT16Read0 = Normal; 1 = In Alarm
IR4422doc 34423Comm Loss: Economizer Refrigerant Pressure Circuit 2Diagnostic flag. Needs: 6" or 8" Control ValvesUINT16Read0 = Normal; 1 = In Alarm
IR4423doc 34424Diagnostic: Economizer Rfgt Valve Loss of Control Circuit 1Diagnostic flag. Needs: 6" or 8" Control ValvesUINT16Read0 = Normal; 1 = In Alarm
IR4424doc 34425Diagnostic: Economizer Rfgt Valve Loss of Control Circuit 2Diagnostic flag. Needs: 6" or 8" Control ValvesUINT16Read0 = Normal; 1 = In Alarm
IR4425doc 34426Diagnostic: Condenser Rfgt Valve Loss of Control Circuit 1Diagnostic flag. Needs: 6" or 8" Control ValvesUINT16Read0 = Normal; 1 = In Alarm
IR4426doc 34427Diagnostic: Condenser Rfgt Valve Loss of Control Circuit 2Diagnostic flag. Needs: 6" or 8" Control ValvesUINT16Read0 = Normal; 1 = In Alarm
IR4427doc 34428Diagnostic: Low Condenser Water FlowDiagnostic flag. Needs: Hot Water ControlUINT16Read0 = Normal; 1 = In Alarm
IR4428doc 34429Diagnostic: Low Heat Recovery Water FlowDiagnostic flag. Needs: Heat RecoveryUINT16Read0 = Normal; 1 = In Alarm
IR4429doc 34430Diagnostic: Economizer Refrigerant Pressure Circuit 1Diagnostic flag. Needs: 6" or 8" Control ValvesUINT16Read0 = Normal; 1 = In Alarm
IR4430doc 34431Diagnostic: Economizer Refrigerant Pressure Circuit 2Diagnostic flag. Needs: 6" or 8" Control ValvesUINT16Read0 = Normal; 1 = In Alarm
IR4431doc 34432Diagnostic: AFD Inverter Heatsink Over Temp Circuit 1Diagnostic flag. Needs: UM AFD w/o THD filter (Inovance) MV Remote Mount COMM AFD (Inovance)UINT16Read0 = Normal; 1 = In Alarm
IR4432doc 34433Diagnostic: AFD Emergency Stop Fault Circuit 1Diagnostic flag. Needs: UM AFD w/o THD filter (Inovance) MV Remote Mount COMM AFD (Inovance)UINT16Read0 = Normal; 1 = In Alarm
IR4433doc 34434Diagnostic: AFD Drive Fault Circuit 1Diagnostic flag. Needs: UM AFD w/o THD filter (Inovance) MV Remote Mount COMM AFD (Inovance)UINT16Read0 = Normal; 1 = In Alarm
IR4434doc 34435Diagnostic: AFD Inverter Heatsink Over Temp Circuit 2Diagnostic flag. Needs: UM AFD w/o THD filter (Inovance) MV Remote Mount COMM AFD (Inovance)UINT16Read0 = Normal; 1 = In Alarm
IR4435doc 34436Diagnostic: AFD Emergency Stop Fault Circuit 2Diagnostic flag. Needs: UM AFD w/o THD filter (Inovance) MV Remote Mount COMM AFD (Inovance)UINT16Read0 = Normal; 1 = In Alarm
IR4436doc 34437Diagnostic: AFD Drive Fault Circuit 2Diagnostic flag. Needs: UM AFD w/o THD filter (Inovance) MV Remote Mount COMM AFD (Inovance)UINT16Read0 = Normal; 1 = In Alarm
IR4437doc 34438Comm Loss: Condenser Rfgt Valve Circuit 1Diagnostic flag. Needs: 8" Control ValvesUINT16Read0 = Normal; 1 = In Alarm
IR4438doc 34439Comm Loss: Condenser Rfgt Valve Circuit 2Diagnostic flag. Needs: 8" Control ValvesUINT16Read0 = Normal; 1 = In Alarm
IR4439doc 34440Comm Loss: Economizer Rfgt Valve Circuit 1Diagnostic flag. Needs: 8" Control ValvesUINT16Read0 = Normal; 1 = In Alarm
IR4440doc 34441Comm Loss: Economizer Rfgt Valve Circuit 2Diagnostic flag. Needs: 8" Control ValvesUINT16Read0 = Normal; 1 = In Alarm
HR10doc 40011Chilled Water SetpointTemperature in the factory unit system (I-P or SI).FLOAT32ABCDRead/write
HR12doc 40013Demand Limit SetpointFLOAT32ABCD%Read/write
HR14doc 40015Hot Water SetpointTemperature in the factory unit system (I-P or SI). Needs: Hot Water ControlFLOAT32ABCDRead/write
HR16doc 40017Base Loading SetpointNeeds: Base LoadingFLOAT32ABCD%Read/write
HR18doc 40019BAS Cooling Differential to StartTemperature difference, factory unit system (I-P or SI).FLOAT32ABCDRead/write
HR20doc 40021BAS Cooling Differential to StopTemperature difference, factory unit system (I-P or SI).FLOAT32ABCDRead/write
HR22doc 40023BAS Heating Differential to StartTemperature difference, factory unit system (I-P or SI). Needs: Hot Water ControlFLOAT32ABCDRead/write
HR24doc 40025BAS Heating Differential to StopTemperature difference, factory unit system (I-P or SI). Needs: Hot Water ControlFLOAT32ABCDRead/write
HR2010doc 42011Chiller Mode Command BASUINT16Read/write1 = Cool; 2 = Heat; 3 = Ice Making; 4 = Free Cooling
HR3010doc 43011Base Loading RequestNeeds: Base LoadingUINT16Read/write0 = Off; 1 = On
HR3011doc 43012Reset DiagnosticUINT16Read/write0 = Normal; 1 = Reset
HR3012doc 43013Evaporator Water Pump Request BASUINT16Read/write0 = Auto; 1 = On
HR3013doc 43014Condenser Water Pump Request BASUINT16Read/write0 = Auto; 1 = On
HR3014doc 43015Chiller Auto Stop Command BASUINT16Read/write0 = Stop; 1 = Auto
HR3015doc 43016Circuit 1 Lockout BASUINT16Read/write0 = Normal; 1 = Locked Out
HR3016doc 43017Circuit 2 Lockout BASUINT16Read/write0 = Normal; 1 = Locked Out
HR3017doc 43018Energy Consumption ResetDepends on starter/drive options; see the source configuration column.UINT16Read/write0 = Accumulating; 1 = Reset

Notes on this map

Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.

Questions about the Trane CenTraVac duplex centrifugal chiller (Symbio 800)

What Modbus registers does the Trane CenTraVac duplex centrifugal chiller (Symbio 800) have?

This map lists 717 registers: 700 input registers, 17 holding registers. 17 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.

Are the Trane CenTraVac duplex centrifugal chiller (Symbio 800) Modbus addresses 0-based or 1-based?

The manufacturer's document numbers registers Modicon 3xxxx/4xxxx (drop the prefix, subtract 1). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. The list prints Modicon register numbers: 3xxxx are input registers and 4xxxx holding registers, so 30011 is input register address 10 and 42011 is holding register address 2010.

What byte order does the Trane CenTraVac duplex centrifugal chiller (Symbio 800) use for 32-bit values?

Multi-register values in this map use ABCD (high word first (big-endian)). Set your client to this order for every 32/64-bit value in the table.

What are the minimum Modbus registers to integrate the Trane CenTraVac duplex centrifugal chiller (Symbio 800)?

Start with IR 10 Active Chilled Water Setpoint (Active chilled water setpoint); IR 22 Evaporator Leaving Water Temperature (Evaporator leaving water temperature); IR 24 Evaporator Entering Water Temperature (Evaporator entering water temperature); IR 2010 Running Mode (Running mode); IR 3020 Chiller Running State (Chiller running state); IR 3025 Diagnostic Present (Diagnostic present); HR 10 Chilled Water Setpoint (Chilled water setpoint (BAS)); HR 2010 Chiller Mode Command BAS (BAS chiller mode command); HR 3014 Chiller Auto Stop Command BAS (Chiller auto/stop command (BAS)); HR 3011 Reset Diagnostic (Reset diagnostic).

How do I enable Modbus control of the Trane CenTraVac duplex centrifugal chiller (Symbio 800)?

On the Symbio 800 web interface go to Installation > Identification and Communications > Protocol Configuration and select Modbus RTU or Modbus TCP (per Trane's Symbio 800 integration guides).

Where is the official Trane CenTraVac duplex centrifugal chiller (Symbio 800) Modbus documentation?

The source is Symbio 800 Integration Points List, BACnet/Modbus, CenTraVac (BAS-PTS009C-EN), revision 2025-12-12, published free by Trane at https://elibrary.tranetechnologies.com/public/commercial-hvac/Literature/Points%20List/BAS-PTS009C-EN_12122025.pdf.

More Trane Modbus register maps

Other chillers & heat pumps register maps

All chillers & heat pumps Modbus register maps →

Source: Symbio 800 Integration Points List, BACnet/Modbus, CenTraVac · BAS-PTS009C-EN · rev. 2025-12-12. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.