- Home
- Modbus register maps
- Daikin Applied
- Magnitude WMC-E magnetic-bearing centrifugal chiller (MicroTech controller)
Chiller · Modbus register map
Daikin Applied Magnitude WMC-E magnetic-bearing centrifugal chiller (MicroTech controller) Modbus register map
Updated 19 November 2026
Water-cooled magnetic-bearing centrifugal chiller (Magnitude WMC, E vintage) on the MicroTech unit controller. A plug-in BAS module set to Modbus RTU exposes 16-bit holding registers: evaporator, condenser and heat-recovery water temperatures, refrigerant pressures and temperatures per compressor, compressor amps/volts/kW, pump status and hours, enable/mode/heat-setpoint commands, status enums and alarm index/module registers. Values follow an English/Metric setting.
This page lists 79 Modbus registers for the Daikin Applied Magnitude WMC-E magnetic-bearing centrifugal chiller (MicroTech controller) — 5 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Daikin Applied’s own free documentation (linked below) and checked against it.
- Manufacturer
- Daikin Applied
- Model
- Magnitude WMC-E magnetic-bearing centrifugal chiller (MicroTech controller)
- Equipment type
- Chiller
- Registers
- 79 (5 writable)
- Transport
- Modbus RTU
- Default unit ID
- 1
- Default serial
- 19200 baud, 8N1
- Documented addressing
- 1-based (subtract 1 for the wire address)
- 32-bit word order
- ABCD high word first (big-endian)
- Also known as
- WMC-E, WMC E-Vintage, Magnitude WMC, Daikin WMC, ED 19131
Integration notes: Daikin Applied Magnitude WMC-E magnetic-bearing centrifugal chiller (MicroTech controller)
Plug in the BAS module, set BAS Network Protocol = Modbus with address, baud, parity and stop bits on the HMI, cycle power, then set Control Source = BAS. Poll with function 03; use 9 to enable, 34 for mode, 37 for the heating setpoint, 38 for capacity limit and 5/28-30 for alarms.
Minimum registers to map
Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.
| Register | Name | Type | Why | Access |
|---|---|---|---|---|
| HR 0 | Chiller Local/Network | UINT16 | Local/Network state | Read |
| HR 14 | Chiller Status | UINT16 | Chiller status | Read |
| HR 16 | Evaporator Leaving Fluid Temperature | INT16 | Leaving chilled water temperature | Read |
| HR 12 | Actual Capacity | UINT16 | Actual capacity | Read |
| HR 8 | Chiller Enable Setpoint | UINT16 | Network enable command | Read/write |
| HR 37 | Capacity Limit Setpoint - Network | UINT16 | Capacity limit command | Read/write |
| HR 4 | Alarm Digital Output | UINT16 | Any alarm active | Read |
| HR 29 | Fault Alarm Index | UINT16 | Active fault index | Read |
| HR 315 | Units (English/Metric) | UINT16 | English/Metric flag | Read |
| HR 36 | Heat Setpoint - Network | UINT16 | Heating setpoint command | Read/write |
Enable Modbus control & writes
On the HMI (Manager password 2526): Configuration > BAS Configuration > BAS Module Connected = Yes, then cycle power; Protocol tab BAS Network Protocol = Modbus and set units; Settings tab Address, Baud Rate, Parity and Modbus Stop Bits; cycle power again. Finally Configuration > Commission > Control Source = BAS, otherwise enable, setpoint, mode, capacity-limit and clear-alarm writes are ignored.
Byte order & addressing
- Printed register numbers are 1-based without the 4xxxx prefix: subtract 1 for the wire address.
- 32-bit counters are high word first (ABCD).
- Most analog values are x10 and follow the English/Metric setting; the multiplier does not change.
- Each alarm class has four registers: index (28-30) plus module type, module ID and payload (2001-2009).
Network setup
- Address 0-247 (default 1); baud 9600/19200/38400/57600/76800 (default 19200); parity Even/Odd/None (default None); stop bits 1 or 2 (default 1).
- RS-485 lands on the module's 'J3 Disp' 4-pin connector, using only + and -. End-of-line and bias resistors are field-supplied.
- The same module also does BACnet IP and MS/TP; one protocol is active, chosen by BAS Network Protocol (default None/LON).
Watch out for
- Nothing answers until BAS Module Connected = Yes and the panel has been power-cycled.
- Control Source = Local or Remote Switch silently ignores network commands; register 1 shows Local/Remote.
Daikin Applied Magnitude WMC-E magnetic-bearing centrifugal chiller (MicroTech controller) Modbus registers
Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.
| Table | Address | Name | Description | Type | Order | Scale | Units | Access | Values / bits |
|---|---|---|---|---|---|---|---|---|---|
| HR | 0doc 1 | Chiller Local/Network | Network commands are ignored while Local. | UINT16 | Read | 0 = Remote; 1 = Local | |||
| HR | 1doc 2 | Chiller Enable Output | UINT16 | Read | 0 = Disable; 1 = Enable | ||||
| HR | 2doc 3 | Run Enabled | UINT16 | Read | 0 = Off; 1 = Run allowed | ||||
| HR | 3doc 4 | Chiller Capacity Limited | UINT16 | Read | 0 = Not limited; 1 = Limited | ||||
| HR | 4doc 5 | Alarm Digital Output | Poll this for any active alarm. | UINT16 | Read | 0 = No alarm; 1 = Alarm | |||
| HR | 5doc 6 | Evaporator Flow Switch Status | UINT16 | Read | 0 = No flow; 1 = Flow | ||||
| HR | 6doc 7 | Condenser Flow Switch Status | UINT16 | Read | 0 = Off; 1 = On | ||||
| HR | 7doc 8 | Chiller On/Off | UINT16 | Read | 0 = Off; 1 = On | ||||
| HR | 8doc 9 | Chiller Enable Setpoint | Network enable; used only when Control Source = BAS. | UINT16 | Read/write | 0 = Disable; 1 = Enable; 2 = Null | |||
| HR | 9doc 10 | Clear Alarm - Network | Write 1 to clear; returns to Normal. | UINT16 | Read/write | 0 = Normal; 1 = Clear alarms; 2 = Null | |||
| HR | 10doc 11 | Chiller Mode Output | UINT16 | Read | 1 = Ice; 2 = Cool; 3 = Heat; 4 = Cool/Heat Recovery | ||||
| HR | 11doc 12 | Active Setpoint | Leaving water setpoint in use, °F x10. | INT16 | × 0.1 | °F | Read | ||
| HR | 12doc 13 | Actual Capacity | Percent of maximum capacity, x10. | UINT16 | × 0.1 | % | Read | ||
| HR | 13doc 14 | Active Capacity Limit Output | Lowest of all active capacity limits, x10. | UINT16 | × 0.1 | % | Read | ||
| HR | 14doc 15 | Chiller Status | UINT16 | Read | 1 = Off; 2 = Start; 3 = Run; 4 = Pre Shutdown; 5 = Service | ||||
| HR | 15doc 16 | Evaporator Entering Fluid Temperature | °F x10 (°C x10 when Units = Metric). | INT16 | × 0.1 | °F | Read | ||
| HR | 16doc 17 | Evaporator Leaving Fluid Temperature | °F x10 (°C x10 when Units = Metric). | INT16 | × 0.1 | °F | Read | ||
| HR | 18doc 19 | Condenser Entering Fluid Temperature | °F x10 (°C x10 when Units = Metric). | INT16 | × 0.1 | °F | Read | ||
| HR | 19doc 20 | Condenser Leaving Fluid Temperature | °F x10 (°C x10 when Units = Metric). | INT16 | × 0.1 | °F | Read | ||
| HR | 21doc 22 | Heat Recovery Entering Fluid Temperature | °F x10 (°C x10 when Units = Metric). | INT16 | × 0.1 | °F | Read | ||
| HR | 22doc 23 | Heat Recovery Leaving Fluid Temperature | °F x10 (°C x10 when Units = Metric). | INT16 | × 0.1 | °F | Read | ||
| HR | 27doc 28 | Warning Alarm Index | Highest active warning index; 0 = none. | UINT16 | Read | ||||
| HR | 28doc 29 | Problem Alarm Index | Highest active problem index; 0 = none. | UINT16 | Read | ||||
| HR | 29doc 30 | Fault Alarm Index | Highest active fault index; 0 = none. | UINT16 | Read | ||||
| HR | 33doc 34 | Chiller Mode Setpoint - Network | Default Cool. Used only when Control Source = BAS. | UINT16 | Read/write | 1 = Ice; 2 = Cool; 3 = Heat; 4 = Cool/Heat Recovery | |||
| HR | 36doc 37 | Heat Setpoint - Network | Leaving condenser fluid setpoint 100-150 °F x10; default varies by model. | UINT16 | × 0.1 | °F | Read/write | ||
| HR | 37doc 38 | Capacity Limit Setpoint - Network | 0-100 % x10; default 100 %. Used only when Control Source = BAS. | UINT16 | × 0.1 | % | Read/write | ||
| HR | 38doc 39 | Circuit 1 Condenser Refrigerant Pressure | psi x10 (kPa x10 in Metric); range printed for R-1233zd(E) and R-32. | INT16 | × 0.1 | psi | Read | ||
| HR | 39doc 40 | Circuit 1 Condenser Saturated Refrigerant Temperature | °F x10 (°C x10 when Units = Metric). | INT16 | × 0.1 | °F | Read | ||
| HR | 40doc 41 | Circuit 1 Evaporator Refrigerant Pressure | psi x10 (kPa x10 in Metric); range printed for R-1233zd(E) and R-32. | INT16 | × 0.1 | psi | Read | ||
| HR | 41doc 42 | Circuit 1 Evaporator Saturated Refrigerant Temperature | °F x10 (°C x10 when Units = Metric). | INT16 | × 0.1 | °F | Read | ||
| HR | 42doc 43 | Circuit 2 Condenser Refrigerant Pressure | psi x10 (kPa x10 in Metric); range printed for R-1233zd(E) and R-32. | INT16 | × 0.1 | psi | Read | ||
| HR | 43doc 44 | Circuit 2 Condenser Saturated Refrigerant Temperature | °F x10 (°C x10 when Units = Metric). | INT16 | × 0.1 | °F | Read | ||
| HR | 44doc 45 | Circuit 2 Evaporator Refrigerant Pressure | psi x10 (kPa x10 in Metric); range printed for R-1233zd(E) and R-32. | INT16 | × 0.1 | psi | Read | ||
| HR | 45doc 46 | Circuit 2 Evaporator Saturated Refrigerant Temperature | °F x10 (°C x10 when Units = Metric). | INT16 | × 0.1 | °F | Read | ||
| HR | 62doc 63 | Circuit 1 Compressor 1 Suction Refrigerant Pressure | psi x10 (kPa x10 in Metric); range printed for R-1233zd(E). | INT16 | × 0.1 | psi | Read | ||
| HR | 63doc 64 | Circuit 1 Compressor 1 Suction Saturated Refrigerant Temperature | °F x10 (°C x10 when Units = Metric). | INT16 | × 0.1 | °F | Read | ||
| HR | 64doc 65 | Circuit 1 Compressor 1 Suction Refrigerant Temperature | °F x10 (°C x10 when Units = Metric). | INT16 | × 0.1 | °F | Read | ||
| HR | 65doc 66 | Circuit 1 Compressor 1 Discharge Refrigerant Pressure | psi x10 (kPa x10 in Metric); range printed for R-1233zd(E). | INT16 | × 0.1 | psi | Read | ||
| HR | 66doc 67 | Circuit 1 Compressor 1 Discharge Saturated Refrigerant Temperature | °F x10 (°C x10 when Units = Metric). | INT16 | × 0.1 | °F | Read | ||
| HR | 67doc 68 | Circuit 1 Compressor 1 Discharge Refrigerant Temperature | °F x10 (°C x10 when Units = Metric). | INT16 | × 0.1 | °F | Read | ||
| HR | 68doc 69 | Circuit 1 Compressor 1 Percent RLA | Percent of rated load amps, 0-100 %. | UINT16 | % | Read | |||
| HR | 69doc 70 | Circuit 1 Compressor 1 Current | Average motor current, 0-10000 A. | UINT16 | A | Read | |||
| HR | 70doc 71 | Circuit 1 Compressor 1 Voltage | Average motor voltage, 0-15000 VAC. | UINT16 | V | Read | |||
| HR | 71doc 72 | Circuit 1 Compressor 1 Power | Motor power, 0-3500 kW. | UINT16 | kW | Read | |||
| HR | 72doc 73 | Circuit 1 Compressor 1 Starts | 0-65535. | UINT16 | Read | ||||
| HR | 73doc 74-75 | Circuit 1 Compressor 1 Run Hours | 0-999,999 h; high word in 74. | UINT32 | ABCD | h | Read | ||
| HR | 75doc 76 | Circuit 1 Compressor 2 Suction Refrigerant Pressure | psi x10 (kPa x10 in Metric); range printed for R-1233zd(E). | INT16 | × 0.1 | psi | Read | ||
| HR | 76doc 77 | Circuit 1 Compressor 2 Suction Saturated Refrigerant Temperature | °F x10 (°C x10 when Units = Metric). | INT16 | × 0.1 | °F | Read | ||
| HR | 77doc 78 | Circuit 1 Compressor 2 Suction Refrigerant Temperature | °F x10 (°C x10 when Units = Metric). | INT16 | × 0.1 | °F | Read | ||
| HR | 78doc 79 | Circuit 1 Compressor 2 Discharge Refrigerant Pressure | psi x10 (kPa x10 in Metric); range printed for R-1233zd(E). | INT16 | × 0.1 | psi | Read | ||
| HR | 79doc 80 | Circuit 1 Compressor 2 Discharge Saturated Refrigerant Temperature | °F x10 (°C x10 when Units = Metric). | INT16 | × 0.1 | °F | Read | ||
| HR | 80doc 81 | Circuit 1 Compressor 2 Discharge Refrigerant Temperature | °F x10 (°C x10 when Units = Metric). | INT16 | × 0.1 | °F | Read | ||
| HR | 81doc 82 | Circuit 1 Compressor 2 Percent RLA | Percent of rated load amps, 0-100 %. | UINT16 | % | Read | |||
| HR | 82doc 83 | Circuit 1 Compressor 2 Current | Average motor current, 0-10000 A. | UINT16 | A | Read | |||
| HR | 83doc 84 | Circuit 1 Compressor 2 Voltage | Average motor voltage, 0-15000 VAC. | UINT16 | V | Read | |||
| HR | 84doc 85 | Circuit 1 Compressor 2 Power | Motor power, 0-3500 kW. | UINT16 | kW | Read | |||
| HR | 85doc 86 | Circuit 1 Compressor 2 Starts | 0-65535. | UINT16 | Read | ||||
| HR | 86doc 87-88 | Circuit 1 Compressor 2 Run Hours | 0-999,999 h; high word in 87. | UINT32 | ABCD | h | Read | ||
| HR | 296doc 297-298 | Condenser Pump 1 Run Hours | 0-999,999 h; high word in 297. | UINT32 | ABCD | h | Read | ||
| HR | 298doc 299 | Condenser Pump 1 Status | UINT16 | Read | 0 = Pump off request; 1 = Pump on request | ||||
| HR | 299doc 300-301 | Condenser Pump 2 Run Hours | 0-999,999 h; high word in 300. | UINT32 | ABCD | h | Read | ||
| HR | 301doc 302 | Condenser Pump 2 Status | UINT16 | Read | 0 = Pump off request; 1 = Pump on request | ||||
| HR | 302doc 303-304 | Evaporator Pump 1 Run Hours | 0-999,999 h; high word in 303. | UINT32 | ABCD | h | Read | ||
| HR | 304doc 305 | Evaporator Pump 1 Status | UINT16 | Read | 0 = Pump off request; 1 = Pump on request | ||||
| HR | 305doc 306-307 | Evaporator Pump 2 Run Hours | 0-999,999 h; high word in 306. | UINT32 | ABCD | h | Read | ||
| HR | 307doc 308 | Evaporator Pump 2 Status | UINT16 | Read | 0 = Pump off request; 1 = Pump on request | ||||
| HR | 315doc 316 | Units (English/Metric) | Unit system for network values; default English. Set at the HMI. | UINT16 | Read | 0 = English; 1 = Metric | |||
| HR | 1605doc 1606 | Refrigerant Type | UINT16 | Read | 1 = R22; 2 = R134a; 3 = R407c; 4 = R410a; 5 = R32; 6 = R454C; 7 = R513A; 8 = R515B; 9 = R1233zd(E); 10 = R1234ze(E) | ||||
| HR | 1983doc 1984 | Circuit 1 Liquid Line Refrigerant Temperature | °F x10 (°C x10 when Units = Metric). | INT16 | × 0.1 | °F | Read | ||
| HR | 2000doc 2001 | Warning Alarm Module Type | Module type behind the active warning. | UINT16 | Read | 0 = No alarms; 1 = Unit; 2 = Compressor; 3 = Fan; 4 = cpCOe expansion module; 5 = Sensor; 6 = EXV; 7 = BAS expansion module; 8 = Circuit; 9 = Peripherals Modbus; 10 = VFD; 11 = MBC; 12 = IGV; 13 = Pump; 14 = Purge unit; 15 = Harmonic filter; 100 = PC | |||
| HR | 2001doc 2002 | Warning Alarm Module ID | Which module (compressor, fan, VFD number) is in warning. | UINT16 | Read | ||||
| HR | 2002doc 2003 | Warning Alarm Module Payload | Hardware-specific code (VFD, fan) for the warning, where used. | UINT16 | Read | ||||
| HR | 2003doc 2004 | Problem Alarm Module Type | Module type behind the active problem alarm. | UINT16 | Read | 0 = No alarms; 1 = Unit; 2 = Compressor; 3 = Fan; 4 = cpCOe expansion module; 5 = Sensor; 6 = EXV; 7 = BAS expansion module; 8 = Circuit; 9 = Peripherals Modbus; 10 = VFD; 11 = MBC; 12 = IGV; 13 = Pump; 14 = Purge unit; 15 = Harmonic filter; 100 = PC | |||
| HR | 2004doc 2005 | Problem Alarm Module ID | Which module is in problem alarm. | UINT16 | Read | ||||
| HR | 2005doc 2006 | Problem Alarm Module Payload | Hardware-specific code for the problem alarm, where used. | UINT16 | Read | ||||
| HR | 2006doc 2007 | Fault Alarm Module Type | Module type behind the active fault. | UINT16 | Read | 0 = No alarms; 1 = Unit; 2 = Compressor; 3 = Fan; 4 = cpCOe expansion module; 5 = Sensor; 6 = EXV; 7 = BAS expansion module; 8 = Circuit; 9 = Peripherals Modbus; 10 = VFD; 11 = MBC; 12 = IGV; 13 = Pump; 14 = Purge unit; 15 = Harmonic filter; 100 = PC | |||
| HR | 2007doc 2008 | Fault Alarm Module ID | Which module is in fault. | UINT16 | Read | ||||
| HR | 2008doc 2009 | Fault Alarm Module Payload | Hardware-specific code for the fault, where used. | UINT16 | Read |
Notes on this map
- Network setup and parameter ranges come from the companion manual IM 1283-1, BACnet and Modbus Chiller Unit Controller (Mar 2024), pp. 36-39: https://tahoeweb.daikinapplied.com/api/general/DownloadDocumentByName/media/IM1283-1.pdf/
- Two-register counters: the document's worked example (99900 = 0x0001863C stored as 74 = 0x0001, 75 = 0x863C) puts the high word first, so they are ABCD.
- The document never defines 'x 10'. Its ranges and defaults ('Default: 100% x 10', '-40-230°F x 10') only make sense as raw = value x 10, so those registers use scale 0.1.
- Signedness is not stated. Temperatures and refrigerant pressures are INT16 because their published ranges go negative (the pressure rows include sub-atmospheric R-1233zd(E) ranges); counters, percentages and enums are UINT16.
- Units follow the HMI 'BAS Measurement Units' setting, readable at register 316 (English default). Units shown are English (°F, psi); Metric uses °C and kPa with the same multiplier.
- Units (316) shows 'RW Holding Register' in the data-type column but 'R' in the access column; it is listed read-only (change it at the HMI).
- Compressor points are listed for the Circuit 1 Compressor 1 and Compressor 2 slots that Table 12 gives for current, %RLA, power, voltage and pressures; run hours and starts use the same two slots.
- Left out: evaporator and condenser flow rates (18, 21). They are printed as 0-65,535 GPM / 0-4134.6 L/S with no multiplier, so the Metric scaling is not settled.
- Alarm index meanings (pp. 32-33) are not reproduced; the module-type value list is the same for all classes.
- ED 19131 is shared with AGZ-F and WMT chillers. Only points that Table 5 marks in the WMC-E column are listed.
- Left out: Cool Setpoint - Network (35). Table 5 marks it for WMC-E, but its range cell gives only WMT and AGZ-F ranges, so the WMC-E scaling is not printed. The setpoint in use can still be read at Active Setpoint (12).
- Heat Setpoint - Network (37) shows 'RO Holding Register' in the data-type column but 'R/W' access, and is described as changing the setpoint from the network; it is listed RW.
- Left out: points Table 5 does not mark for WMC-E (ice setpoint, outdoor air temperature).
Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.
Questions about the Daikin Applied Magnitude WMC-E magnetic-bearing centrifugal chiller (MicroTech controller)
What Modbus registers does the Daikin Applied Magnitude WMC-E magnetic-bearing centrifugal chiller (MicroTech controller) have?
This map lists 79 registers: 79 holding registers. 5 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.
Are the Daikin Applied Magnitude WMC-E magnetic-bearing centrifugal chiller (MicroTech controller) Modbus addresses 0-based or 1-based?
The manufacturer's document numbers registers 1-based (subtract 1 for the wire address). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. ED 19131 prints holding registers without the 4xxxx prefix (register 8 = 40008) and states the module is zero-based: 40002 is sent as 0001. Wire address = printed number - 1.
What byte order does the Daikin Applied Magnitude WMC-E magnetic-bearing centrifugal chiller (MicroTech controller) use for 32-bit values?
Multi-register values in this map use ABCD (high word first (big-endian)). Set your client to this order for every 32/64-bit value in the table.
What are the minimum Modbus registers to integrate the Daikin Applied Magnitude WMC-E magnetic-bearing centrifugal chiller (MicroTech controller)?
Start with HR 0 Chiller Local/Network (Local/Network state); HR 14 Chiller Status (Chiller status); HR 16 Evaporator Leaving Fluid Temperature (Leaving chilled water temperature); HR 12 Actual Capacity (Actual capacity); HR 8 Chiller Enable Setpoint (Network enable command); HR 37 Capacity Limit Setpoint - Network (Capacity limit command); HR 4 Alarm Digital Output (Any alarm active); HR 29 Fault Alarm Index (Active fault index); HR 315 Units (English/Metric) (English/Metric flag); HR 36 Heat Setpoint - Network (Heating setpoint command).
How do I enable Modbus control of the Daikin Applied Magnitude WMC-E magnetic-bearing centrifugal chiller (MicroTech controller)?
On the HMI (Manager password 2526): Configuration > BAS Configuration > BAS Module Connected = Yes, then cycle power; Protocol tab BAS Network Protocol = Modbus and set units; Settings tab Address, Baud Rate, Parity and Modbus Stop Bits; cycle power again. Finally Configuration > Commission > Control Source = BAS, otherwise enable, setpoint, mode, capacity-limit and clear-alarm writes are ignored.
Where is the official Daikin Applied Magnitude WMC-E magnetic-bearing centrifugal chiller (MicroTech controller) Modbus documentation?
The source is MicroTech Unit Controller Protocol Information - BACnet and Modbus Networks, Chiller Models AGZ-F, WMC-E and WMT (ED 19131-1) (ED 19131-1), revision 2026-04, published free by Daikin Applied at https://tahoeweb.daikinapplied.com/api/general/DownloadDocumentByName/media/ED%2019131-1.pdf/.
More Daikin Applied Modbus register maps
- Chiller
Daikin Applied ADS air-cooled global screw chiller (MicroTech controller)
Daikin Applied model ADS air-cooled global screw chillers with the MicroTech chiller unit controller and Modbus communication module, per ED 15121-13.
Also known as: ADS, Daikin ADS, Air-cooled Global Screw Chiller, ED 15121 - Heat pump
Daikin Applied EWAK-CZ / EWYK-CZ air-cooled chiller and heat pump (MicroTech 4, ICARO software)
Daikin Applied Europe EWAK-CZ / EWYK-CZ units with MicroTech 4 controller, ICARO software and POL902 Modbus module, per D-EIGOC00204-26_00EN.
Also known as: EWYK-CZ, EWAK-CZ, EWA(Y)K-CZ, ICARO, D-EIGOC00204 - Chiller (air-cooled)
Daikin Applied EWAT-B / EWAFT-B / EWAT-C / EWAFT-C air-cooled inverter chillers (Microtech 4, ARES software)
EWA(F)T-B and -C air-cooled chillers (F = free-cooling) with a Microtech 4 controller running ARES software, per D-EIGOC00207-24_05EN.
Also known as: EWAT-B, EWAFT-B, EWAT-C, EWAFT-C, EWA(F)T-B-C, EWAT~B, EWAFT~B, Daikin EWAT, ARES - Chiller (water-cooled)
Daikin Applied EWWD-VZ / EWWH-VZ / EWWS-VZ water-cooled inverter screw chillers (Microtech, Adam software)
EWWD-VZ, EWWH-VZ and EWWS-VZ water-cooled inverter screw chillers with Microtech III or Microtech 4 controller running Adam software, per D-EIGOC00201-22_03EN.
Also known as: EWWD-VZ, EWWH-VZ, EWWS-VZ, EWWD(H)(S)_VZ, EWWD~VZ, EWWH~VZ, Daikin EWWD VZ, Adam - Chiller
Daikin Applied Magnitude WME B-vintage magnetic-bearing centrifugal chiller (MicroTech controller)
Daikin Applied Magnitude WME B-vintage water-cooled magnetic-bearing centrifugal chillers with the MicroTech chiller unit controller and Modbus communication module, per ED 15121-13.
Also known as: WME-B, WME B-Vintage, Magnitude WME B, ED 15121 - Chiller (water-cooled, magnetic-bearing centrifugal)
Daikin Applied Magnitude WME magnetic-bearing chiller (MicroTech, Modbus)
Magnitude WME C- and D-vintage and WME-C QUAD chillers with the MicroTech unit controller and Modbus communication module, per ED 19111-4.
Also known as: WME-C, WME-D, WME-C QUAD, Magnitude WME, Daikin WME - Chiller
Daikin Applied Magnitude WMT magnetic-bearing centrifugal chiller (MicroTech controller)
Daikin Applied Magnitude WMT water-cooled magnetic-bearing centrifugal chillers with the MicroTech unit controller and BACnet/Modbus communication module set to Modbus, per ED 19131-1.
Also known as: WMT, Magnitude WMT, Daikin WMT, ED 19131 - Chiller
Daikin Applied MicroTech II centrifugal chillers WSC/WDC/WPV/WMC/WCC/HSC/HDC/TSC (Modbus module)
McQuay/Daikin Applied water-cooled centrifugal chillers with the MicroTech II unit controller and Modbus Communication Module: WSC, WDC, WPV, WMC (magnetic bearing), WCC, HSC/HDC heat recovery and TSC Templifier, per ED 15063-2 (Dec 2005).
Also known as: WSC, WDC, WPV, WMC, WCC, HSC, HDC, TSC, McQuay centrifugal Modbus, MicroTech II chiller, ED 15063 - Chiller
Daikin Applied MicroTech II scroll and screw chillers AGZ/ACZ/WGZ/AGS/WGS (Modbus module)
McQuay/Daikin Applied AGZ air-cooled and WGZ water-cooled global scroll chillers, ACZ scroll condensing units, and AGS/WGS global screw chillers with the MicroTech II controller and Modbus Communication Module, per ED 15063-2 (Dec 2005).
Also known as: AGZ-A, AGZ-B, ACZ-A, ACZ-B, WGZ, AGS-B, AGS-C, WGS, AGZ, ACZ, AGS, McQuay global scroll Modbus, McQuay global screw Modbus, ED 15063 - Chiller
Daikin Applied Navigator WWV / TWV water-cooled screw chiller (MicroTech controller)
Daikin Applied Navigator WWV and TWV water-cooled screw chillers with the MicroTech chiller unit controller and Modbus communication module, per ED 15121-13.
Also known as: WWV, TWV, Navigator WWV, Navigator TWV, Daikin Navigator, ED 15121 - Chiller
Daikin Applied Pathfinder AWS air-cooled screw chiller (MicroTech controller)
Daikin Applied Pathfinder AWS air-cooled screw chillers with the MicroTech chiller unit controller and Modbus communication module, per ED 15121-13 (both application-version columns, 2507500204 and earlier / 2507500205 and later, mark the same data points).
Also known as: AWS, Pathfinder AWS, Daikin AWS, ED 15121 - Chiller
Daikin Applied Pathfinder AWV air-cooled screw chiller (MicroTech controller)
Daikin Applied Pathfinder AWV variable-speed air-cooled screw chillers with the MicroTech chiller unit controller and Modbus communication module, per ED 15121-13 (application 263220504 baseline; some points need newer code, marked per register).
Also known as: AWV, Pathfinder AWV, Pathfinder VFD air-cooled screw, MicroTech chiller unit controller, ED 15121 - Rooftop unit
Daikin Applied Rebel / Rebel Applied rooftop (MicroTech 4 controller)
Daikin Applied Rebel Applied (DPSA, R-410A/R-32) and Rebel (DPS, R-32) packaged rooftops with MicroTech 4 controller and Modbus RTU module, per ED 19133-2 (Oct 2025).
Also known as: DPSA, DPS, Rebel Applied, Rebel, MicroTech 4 rooftop, ED 19133-2 - Chiller
Daikin Applied Trailblazer AGZ-D / AGZ-E air-cooled scroll chiller (MicroTech controller)
Daikin Applied Trailblazer AGZ-D and AGZ-E air-cooled scroll chillers with the MicroTech chiller unit controller and Modbus communication module, per ED 15121-13.
Also known as: AGZ-D, AGZ-E, AGZ D-Vintage, AGZ E-Vintage, ED 15121, Trailblazer AGZ-D, Trailblazer AGZ-E - Chiller
Daikin Applied Trailblazer AGZ-F air-cooled scroll chiller (MicroTech controller)
Daikin Applied Trailblazer AGZ F-vintage air-cooled scroll chillers with the MicroTech unit controller and BACnet/Modbus communication module set to Modbus, per ED 19131-1 (application 1.2.0 and later).
Also known as: AGZ-F, AGZ F-Vintage, Trailblazer AGZ, Trailblazer AGZ-F, ED 19131 - Chiller
Daikin Applied Trailblazer AMZ air-cooled scroll chiller (MicroTech controller)
Daikin Applied Trailblazer AMZ air-cooled scroll chillers with the MicroTech chiller unit controller and Modbus communication module, per ED 15121-13.
Also known as: AMZ, Trailblazer AMZ, Daikin AMZ, ED 15121
Other chillers & heat pumps register maps
- Chiller
Trane Ascend ACS / ACX air-cooled scroll chiller and heat pump (Symbio 800)
Trane Ascend ACS air-cooled scroll chillers and ACX air-to-water heat pumps with the Symbio 800 controller, as listed in BAS-PTS011A-EN (11/15/2024).
Also known as: ACS, ACX, Ascend ACS, Ascend ACX, Ascend air-cooled chiller, Ascend air-to-water heat pump - Chiller
Trane Series R RTHD water-cooled helical-rotary chiller (Symbio 800)
Trane Series R model RTHD water-cooled helical-rotary chillers with the Symbio 800 controller, as listed in BAS-PTS015A-EN (11/15/2024).
Also known as: RTHD, Series R RTHD - Chiller
Trane CGAM air-cooled scroll chiller (Symbio 800)
Trane CGAM air-cooled scroll chillers with the Symbio 800 controller, as listed in BAS-PTS019A-EN (11/15/2024).
Also known as: CGAM, Trane CGAM, CGAM air-cooled scroll chiller - Chiller (air-cooled chiller for data centres)
Vertiv Liebert HPC chiller with iCOM v4 (IntelliSlot Modbus)
Liebert HPC chillers on the iCOM v4 controller (iCOM_SC31 / iCOM_SC100 applications) with a Liebert IntelliSlot Modbus card.
Also known as: Liebert HPC, HPC chiller, Liebert HPC iCOM - Chiller
Trane CenTraVac CTV-Duplex water-cooled centrifugal chiller (UC800 native Modbus)
Trane Duplex CenTraVac (two-compressor) water-cooled centrifugal chillers with the Tracer UC800 controller, as listed in the Modbus section of BAS-PTS030A-EN (12/6/2024).
Also known as: CTV-Duplex, CTVD, CenTraVac Duplex, Duplex CenTraVac UC800 - Chiller
Trane Series R RTWD water-cooled helical-rotary chiller (Symbio 800)
Trane Series R model RTWD water-cooled helical-rotary chillers with the Symbio 800 controller, as listed in BAS-PTS017A-EN (11/15/2024).
Also known as: RTWD, Series R RTWD, RTUD
All chillers & heat pumps Modbus register maps →
Source: MicroTech Unit Controller Protocol Information - BACnet and Modbus Networks, Chiller Models AGZ-F, WMC-E and WMT (ED 19131-1) · ED 19131-1 · rev. 2026-04. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.