- EWAT-B / EWAFT-B / EWAT-C / EWAFT-C air-cooled inverter chillers (Microtech 4, ARES software)
Chiller (air-cooled) · Modbus register map
Daikin Applied EWAT-B / EWAFT-B / EWAT-C / EWAFT-C air-cooled inverter chillers (Microtech 4, ARES software) Modbus register map
Updated 17 November 2026
Daikin Applied Europe's EWA(F)T-B/C air-cooled inverter chillers run a Microtech 4 controller that acts as a Modbus RTU slave over RS-485, either through a POL902 plug-in module or a licensed on-board software option. Every point is a 16-bit holding register: unit and circuit status, water and refrigerant temperatures and pressures, setpoints, compressor and pump states, free-cooling status and individual alarm flags.
This page lists 190 Modbus registers for the Daikin Applied EWAT-B / EWAFT-B / EWAT-C / EWAFT-C air-cooled inverter chillers (Microtech 4, ARES software) — 31 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Daikin Applied’s own free documentation (linked below) and checked against it.
- Manufacturer
- Daikin Applied
- Model
- EWAT-B / EWAFT-B / EWAT-C / EWAFT-C air-cooled inverter chillers (Microtech 4, ARES software)
- Equipment type
- Chiller (air-cooled)
- Registers
- 190 (31 writable)
- Transport
- Modbus RTU
- Default unit ID
- Not stated
- Default serial
- 19200 baud, 8N1
- Documented addressing
- 1-based (subtract 1 for the wire address)
- Firmware
- ARES control software (no version printed)
- Also known as
- EWAT-B, EWAFT-B, EWAT-C, EWAFT-C, EWA(F)T-B-C, EWAT~B, EWAFT~B, Daikin EWAT, ARES
Integration notes: Daikin Applied EWAT-B / EWAFT-B / EWAT-C / EWAFT-C air-cooled inverter chillers (Microtech 4, ARES software)
Read holding registers from wire address 0: Unit Status (col 15), leaving water temperature (col 17) and capacity (col 13). Enable the unit with col 9 and send the cooling setpoint to col 35 (tenths of °C).
Minimum registers to map
Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.
| Register | Name | Type | Why | Access |
|---|---|---|---|---|
| HR 14 | Unit - Status | UINT16 | Unit status (Off/Start/Run/...) | Read |
| HR 16 | Evaporator Leaving Water Temperature | INT16 | Evaporator leaving water temperature | Read |
| HR 12 | Unit - Actual Capacity | UINT16 | Actual capacity | Read |
| HR 8 | Unit - Enable Setpoint | UINT16 | Unit enable command | Read/write |
| HR 34 | Unit - Cool Temperature Setpoint | INT16 | Cooling temperature setpoint | Read/write |
| HR 32 | Unit Alarm - Fault Code | UINT16 | Active fault code | Read |
| HR 0 | Unit - Control Source | UINT16 | Control source (network or local) | Read |
Enable Modbus control & writes
Either fit a POL902 module and set address/parity/stop bits/baud under Main menu > Commissioning > Modbus (service password), or switch on software option #1 'Modbus Slave MSTP' under Commissioning > Configuration > Software Options with its unlock password, then set the parameters under Commissioning > SW Modbus MSTP.
Byte order & addressing
- Addresses are Modicon-style: subtract 1 from the guide's column value.
- Gains of 0.1 apply to temperatures, pressures and percentages.
Network setup
- POL902 module defaults: address 1, no parity, 2 stop bits, 19200 baud, 5 ms response delay; port T2 passive.
- Software-option defaults: 19200 baud, no parity, 1 stop bit (2StopBits = No), 100 ms delay and response timeout; address varies.
Watch out for
- Stop-bit defaults differ between the POL902 module (2) and the software option (1).
- The software option needs an unlock password from Daikin.
Daikin Applied EWAT-B / EWAFT-B / EWAT-C / EWAFT-C air-cooled inverter chillers (Microtech 4, ARES software) Modbus registers
Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.
| Table | Address | Name | Description | Type | Order | Scale | Units | Access | Values / bits |
|---|---|---|---|---|---|---|---|---|---|
| HR | 0doc 1 | Unit - Control Source | UINT16 | Read | 0 = Network; 1 = Local | ||||
| HR | 1doc 2 | Unit - Enabled State | UINT16 | Read | 0 = Disabled; 1 = Enabled | ||||
| HR | 2doc 3 | Unit - Run Allowed | UINT16 | Read | 0 = Off; 1 = Allowed | ||||
| HR | 3doc 4 | Unit - Capacity Limited | UINT16 | Read | 0 = NotLimited; 1 = Limited | ||||
| HR | 4doc 5 | Unit - Generic Status | UINT16 | Read | 0 = Off; 1 = On | ||||
| HR | 5doc 6 | Evaporator - Water Flow State | UINT16 | Read | 0 = NoFlow; 1 = Flow | ||||
| HR | 7doc 8 | Unit - Operating State | UINT16 | Read | 0 = ThermoOff; 1 = ThermoOn | ||||
| HR | 8doc 9 | Unit - Enable Setpoint | Network command at priority 8. | UINT16 | Read/write | 0 = Disable; 1 = Enable | |||
| HR | 9doc 10 | Unit - Alarm Reset Setpoint | Network command at priority 8. | UINT16 | Read/write | 0 = None; 1 = Clear | |||
| HR | 10doc 11 | Unit - Active Operation Mode | UINT16 | Read | 1 = Ice; 2 = Cool; 3 = Heat; 4 = Pursuit | ||||
| HR | 11doc 12 | Unit - Active Temperature Setpoint | INT16 | × 0.1 | °C | Read | |||
| HR | 12doc 13 | Unit - Actual Capacity | UINT16 | × 0.1 | % | Read | |||
| HR | 13doc 14 | Unit - Active Capacity Limit | UINT16 | × 0.1 | % | Read | |||
| HR | 14doc 15 | Unit - Status | UINT16 | Read | 1 = Off; 2 = Start; 3 = Run; 4 = PreShutdown; 5 = Service | ||||
| HR | 15doc 16 | Evaporator Entering Water Temperature | INT16 | × 0.1 | °C | Read | |||
| HR | 16doc 17 | Evaporator Leaving Water Temperature | INT16 | × 0.1 | °C | Read | |||
| HR | 17doc 18 | Heat Recovery - Enable Setpoint | Network command at priority 8. | UINT16 | Read/write | 0 = Disable; 1 = Enable | |||
| HR | 21doc 22 | Heat Recovery - Entering Water Temperature | INT16 | × 0.1 | °C | Read | |||
| HR | 22doc 23 | Heat Recovery - Leaving Water Temperature | INT16 | × 0.1 | °C | Read | |||
| HR | 23doc 24 | Outside Air Temperature | INT16 | × 0.1 | °C | Read | |||
| HR | 24doc 25 | Unit - Average Current | UINT16 | A | Read | ||||
| HR | 25doc 26 | Unit - Average Voltage | UINT16 | × 0.1 | V | Read | |||
| HR | 26doc 27 | Unit - Active Power | UINT16 | × 0.1 | kW | Read | |||
| HR | 27doc 28 | Unit Alarm - Warning Index | Numeric code; see the alarm code and index table in section 5.1. | UINT16 | Read | ||||
| HR | 28doc 29 | Unit Alarm - Problem Index | Numeric code; see the alarm code and index table in section 5.1. | UINT16 | Read | ||||
| HR | 29doc 30 | Unit Alarm - Fault Index | Numeric code; see the alarm code and index table in section 5.1. | UINT16 | Read | ||||
| HR | 30doc 31 | Unit Alarm - Warning Code | Numeric code; see the alarm code and index table in section 5.1. | UINT16 | Read | ||||
| HR | 31doc 32 | Unit Alarm - Problem Code | Numeric code; see the alarm code and index table in section 5.1. | UINT16 | Read | ||||
| HR | 32doc 33 | Unit Alarm - Fault Code | Numeric code; see the alarm code and index table in section 5.1. | UINT16 | Read | ||||
| HR | 33doc 34 | Unit - Operation Mode Setpoint | Network command at priority 8. | UINT16 | Read/write | 0 = NULL; 1 = Ice; 2 = Cool; 3 = Heat; 4 = Pursuit | |||
| HR | 34doc 35 | Unit - Cool Temperature Setpoint | INT16 | × 0.1 | °C | Read/write | |||
| HR | 35doc 36 | Unit - Ice Temperature Setpoint | INT16 | × 0.1 | °C | Read/write | |||
| HR | 36doc 37 | Unit - Heat Temperature Setpoint | INT16 | × 0.1 | °C | Read/write | |||
| HR | 37doc 38 | Unit - Capacity Limit Setpoint | UINT16 | × 0.1 | % | Read/write | |||
| HR | 38doc 39 | Circuit 1 - Condenser Refrigerant Pressure | INT16 | × 0.1 | kPa | Read | |||
| HR | 39doc 40 | Circuit 1 - Condeser Saturated Temperature | INT16 | × 0.1 | °C | Read | |||
| HR | 40doc 41 | Circuit 1 - Evaporator Refrigerant Pressure | INT16 | × 0.1 | kPa | Read | |||
| HR | 41doc 42 | Circuit 1 - Evaporator Saturated Temperature | INT16 | × 0.1 | °C | Read | |||
| HR | 42doc 43 | Circuit 2 - Condenser Refrigerant Pressure | INT16 | × 0.1 | kPa | Read | |||
| HR | 43doc 44 | Circuit 2 - Condeser Saturated Temperature | INT16 | × 0.1 | °C | Read | |||
| HR | 44doc 45 | Circuit 2 - Evaporator Refrigerant Pressure | INT16 | × 0.1 | kPa | Read | |||
| HR | 45doc 46 | Circuit 2 - Evaporator Saturated Temperature | INT16 | × 0.1 | °C | Read | |||
| HR | 50doc 51 | Circuit 1 - Shutdown Alarm | UINT16 | Read | 0 = NoAlarm; 1 = Alarm | ||||
| HR | 51doc 52 | Circuit 2 - Shutdown Alarm | UINT16 | Read | 0 = NoAlarm; 1 = Alarm | ||||
| HR | 53doc 54 | Unit - Shutdown Alarm | UINT16 | Read | 0 = NoAlarm; 1 = Alarm | ||||
| HR | 58doc 59 | Heat Recovery - Temperature Setpoint | INT16 | × 0.1 | °C | Read/write | |||
| HR | 59doc 60 | Heat Recovery - Operating State | UINT16 | Read | 1 = Off; 2 = Recirculation; 3 = Regulation | ||||
| HR | 64doc 65 | Circ 1 Compressor 1 - Suction Temperature | INT16 | × 0.1 | °C | Read | |||
| HR | 66doc 67 | Circ 1 - Discharge Temperature | INT16 | × 0.1 | °C | Read | |||
| HR | 67doc 68 | Circ 1 Compressor 1 - Discharge Temperature | INT16 | × 0.1 | °C | Read | |||
| HR | 72doc 73 | Circ 1 Compressor 1 - Number of Starts | UINT16 | Read/write | |||||
| HR | 80doc 81 | Circ 1 Compressor 2 - Discharge Temperature | INT16 | × 0.1 | °C | Read | |||
| HR | 85doc 86 | Circ 1 Compressor 2 - Number of Starts | UINT16 | Read/write | |||||
| HR | 93doc 94 | Circ 1 Compressor 3 - Discharge Temperature | INT16 | × 0.1 | °C | Read | |||
| HR | 98doc 99 | Circ 1 Compressor 3 - Number of Starts | UINT16 | Read/write | |||||
| HR | 103doc 104 | Circ 2 Compressor 1 - Suction Temperature | INT16 | × 0.1 | °C | Read | |||
| HR | 105doc 106 | Circ 2 - Discharge Temperature | INT16 | × 0.1 | °C | Read | |||
| HR | 106doc 107 | Circ 2 Compressor 1 - Discharge Temperature | INT16 | × 0.1 | °C | Read | |||
| HR | 111doc 112 | Circ 2 Compressor 1 - Number of Starts | UINT16 | Read/write | |||||
| HR | 119doc 120 | Circ 2 Compressor 2 - Discharge Temperature | INT16 | × 0.1 | °C | Read | |||
| HR | 124doc 125 | Circ 2 Compressor 2 - Number of Starts | UINT16 | Read/write | |||||
| HR | 132doc 133 | Circ 2 Compressor 3 - Discharge Temperature | INT16 | × 0.1 | °C | Read | |||
| HR | 137doc 138 | Circ 2 Compressor 3 - Number of Starts | UINT16 | Read/write | |||||
| HR | 158doc 159 | Circ 1 Compressor 4 - Discharge Temperature | INT16 | × 0.1 | °C | Read | |||
| HR | 163doc 164 | Circ 1 Compressor 4 - Number of Starts | UINT16 | Read/write | |||||
| HR | 197doc 198 | Circ 2 Compressor 4 - Discharge Temperature | INT16 | × 0.1 | °C | Read | |||
| HR | 202doc 203 | Circ 2 Compressor 4 - Number of Starts | UINT16 | Read/write | |||||
| HR | 249doc 250 | Freecooling - Enable Setpoint | Network command at priority 8. | UINT16 | Read/write | 0 = Disable; 1 = Enable | |||
| HR | 250doc 251 | Freecooling - Status | UINT16 | Read | 1 = Off; 2 = Full; 3 = Mixed; 4 = Mechanical | ||||
| HR | 251doc 252 | Freeccoling - Enabled State | UINT16 | Read | 1 = Off; 2 = Run | ||||
| HR | 252doc 253 | Freecooling - Circuit 1 Mode | UINT16 | Read | 1 = Mechanical; 2 = Switching; 3 = Switching; 4 = FreeCooling; 5 = FC Pumpdown; 6 = FC Off | ||||
| HR | 253doc 254 | Freecooling - Circuit 2 Mode | UINT16 | Read | 1 = Mechanical; 2 = Switching; 3 = Switching; 4 = FreeCooling; 5 = FC Pumpdown; 6 = FC Off | ||||
| HR | 263doc 264 | Performance - Unit Efficiency | UINT16 | × 0.01 | Read | ||||
| HR | 295doc 296 | Evaporator Pump - Speed | UINT16 | % | Read | ||||
| HR | 304doc 305 | Evaporator Pump 1 - Operating State | UINT16 | Read | 0 = Stop; 1 = Run | ||||
| HR | 307doc 308 | Evaporator Pump 2 - Operating State | UINT16 | Read | 0 = Stop; 1 = Run | ||||
| HR | 315doc 316 | Unit - Measurement unit setpoint | UINT16 | Read/write | 0 = English; 1 = Metric | ||||
| HR | 365doc 366 | Unit Alarm - Evaporator Entering Temperature Sensor Fault | UINT16 | Read | 0 = NoAlarm; 1 = Alarm | ||||
| HR | 376doc 377 | Unit Warning - Setpoint Reset Input Out of Range | UINT16 | Read | 0 = NoAlarm; 1 = Alarm | ||||
| HR | 377doc 378 | Unit Warning - Demand Limit Input Out of Range | UINT16 | Read | 0 = NoAlarm; 1 = Alarm | ||||
| HR | 387doc 388 | Unit Warning - Inhibition for Low Ambient Temperature | UINT16 | Read | 0 = NoAlarm; 1 = Alarm | ||||
| HR | 394doc 395 | Circuit 1 Warning - Unload for Condenser High Pressure | UINT16 | Read | 0 = NoAlarm; 1 = Alarm | ||||
| HR | 395doc 396 | Circuit 2 Warning - Unload for Condenser High Pressure | UINT16 | Read | 0 = NoAlarm; 1 = Alarm | ||||
| HR | 410doc 411 | Circuit 1 Warning - Inhibition for Evaporator Low Pressure | UINT16 | Read | 0 = NoAlarm; 1 = Alarm | ||||
| HR | 411doc 412 | Circuit 2 Warning - Inhibition for Evaporator Low Pressure | UINT16 | Read | 0 = NoAlarm; 1 = Alarm | ||||
| HR | 415doc 416 | Circuit 1 Warning - Unload for Evaporator Low Pressure | UINT16 | Read | 0 = NoAlarm; 1 = Alarm | ||||
| HR | 416doc 417 | Circuit 2 Warning - Unload for Evaporator Low Pressure | UINT16 | Read | 0 = NoAlarm; 1 = Alarm | ||||
| HR | 429doc 430 | Evaporator Pump 1 - Fault | UINT16 | Read | 0 = NoAlarm; 1 = Alarm | ||||
| HR | 430doc 431 | Evaporator Pump 2 - Fault | UINT16 | Read | 0 = NoAlarm; 1 = Alarm | ||||
| HR | 439doc 440 | Circ 1 Comp 1 Alarm - Low Pressure Ratio | UINT16 | Read | 0 = NoAlarm; 1 = Alarm | ||||
| HR | 441doc 442 | Circ 2 Comp 1 Alarm - Low Pressure Ratio | UINT16 | Read | 0 = NoAlarm; 1 = Alarm | ||||
| HR | 445doc 446 | Unit Alarm - Outside Air Temperature Sensor Fault | UINT16 | Read | 0 = NoAlarm; 1 = Alarm | ||||
| HR | 465doc 466 | Circ 1 Comp 1 Alarm - Motor Protection | UINT16 | Read | 0 = NoAlarm; 1 = Alarm | ||||
| HR | 466doc 467 | Circ 1 Comp 2 Alarm - Motor Protection | UINT16 | Read | 0 = NoAlarm; 1 = Alarm | ||||
| HR | 467doc 468 | Circ 2 Comp 1 Alarm - Motor Protection | UINT16 | Read | 0 = NoAlarm; 1 = Alarm | ||||
| HR | 468doc 469 | Circ 2 Comp 2 Alarm - Motor Protection | UINT16 | Read | 0 = NoAlarm; 1 = Alarm | ||||
| HR | 469doc 470 | Circ 1 Comp 3 Alarm - Motor Protection | UINT16 | Read | 0 = NoAlarm; 1 = Alarm | ||||
| HR | 470doc 471 | Circ 2 Comp 3 Alarm - Motor Protection | UINT16 | Read | 0 = NoAlarm; 1 = Alarm | ||||
| HR | 471doc 472 | Circ 1 Comp 4 Alarm - Motor Protection | UINT16 | Read | 0 = NoAlarm; 1 = Alarm | ||||
| HR | 472doc 473 | Circ 2 Comp 4 Alarm - Motor Protection | UINT16 | Read | 0 = NoAlarm; 1 = Alarm | ||||
| HR | 508doc 509 | Circuit 1 Alarm - Condenser Pressure Sensor Fault | UINT16 | Read | 0 = NoAlarm; 1 = Alarm | ||||
| HR | 510doc 511 | Circuit 2 Alarm - Condenser Pressure Sensor Fault | UINT16 | Read | 0 = NoAlarm; 1 = Alarm | ||||
| HR | 516doc 517 | Circuit 1 Alarm - Condenser High Pressure | UINT16 | Read | 0 = NoAlarm; 1 = Alarm | ||||
| HR | 518doc 519 | Circuit 2 Alarm - Condenser High Pressure | UINT16 | Read | 0 = NoAlarm; 1 = Alarm | ||||
| HR | 528doc 529 | Circuit 1 Alarm - Discharge Temperature Sensor Fault | UINT16 | Read | 0 = NoAlarm; 1 = Alarm | ||||
| HR | 530doc 531 | Circuit 2 Alarm - Discharge Temperature Sensor Fault | UINT16 | Read | 0 = NoAlarm; 1 = Alarm | ||||
| HR | 541doc 542 | Unit Alarm - Evaporator Water Flow Loss | UINT16 | Read | 0 = NoAlarm; 1 = Alarm | ||||
| HR | 542doc 543 | Unit Alarm - Evaporator Water Freeze | UINT16 | Read | 0 = NoAlarm; 1 = Alarm | ||||
| HR | 544doc 545 | Circuit 1 Alarm - Evaporator Pressure Low | UINT16 | Read | 0 = NoAlarm; 1 = Alarm | ||||
| HR | 546doc 547 | Circuit 2 Alarm - Evaporator Pressure Low | UINT16 | Read | 0 = NoAlarm; 1 = Alarm | ||||
| HR | 551doc 552 | Circuit 1 Alarm - Evaporator Pressure Sensor Failure | UINT16 | Read | 0 = NoAlarm; 1 = Alarm | ||||
| HR | 553doc 554 | Circuit 2 Alarm - Evaporator Pressure Sensor Failure | UINT16 | Read | 0 = NoAlarm; 1 = Alarm | ||||
| HR | 582doc 583 | Circuit 1 Alarm - Too many restart | UINT16 | Read | 0 = NoAlarm; 1 = Alarm | ||||
| HR | 584doc 585 | Circuit 2 Alarm - Too many restart | UINT16 | Read | 0 = NoAlarm; 1 = Alarm | ||||
| HR | 588doc 589 | Unit Alarm - Evaporator Leaving Temperature Sensor Fault | UINT16 | Read | 0 = NoAlarm; 1 = Alarm | ||||
| HR | 600doc 601 | Circuit 1 Alarm - Mechanical High Pressure | UINT16 | Read | 0 = NoAlarm; 1 = Alarm | ||||
| HR | 602doc 603 | Circuit 2 Alarm - Mechanical High Pressure | UINT16 | Read | 0 = NoAlarm; 1 = Alarm | ||||
| HR | 651doc 652 | Circuit 1 Alarm - Liquid Temperature Sensor Failure | UINT16 | Read | 0 = NoAlarm; 1 = Alarm | ||||
| HR | 654doc 655 | Circuit 2 Alarm - Liquid Temperature Sensor Failure | UINT16 | Read | 0 = NoAlarm; 1 = Alarm | ||||
| HR | 697doc 698 | Circ 1 Comp 1 Alarm - Suction Temperature Sensor Fault | UINT16 | Read | 0 = NoAlarm; 1 = Alarm | ||||
| HR | 699doc 700 | Circ 2 Comp 1 Alarm - Suction Temperature Sensor Fault | UINT16 | Read | 0 = NoAlarm; 1 = Alarm | ||||
| HR | 721doc 722 | Controller Alarm - Main Controller Board Offline | UINT16 | Read | 0 = NoAlarm; 1 = Alarm | ||||
| HR | 722doc 723 | Controller Alarm - Circuit 1 Board Offline | UINT16 | Read | 0 = NoAlarm; 1 = Alarm | ||||
| HR | 723doc 724 | Controller Alarm - Circuit 2 Board Offline | UINT16 | Read | 0 = NoAlarm; 1 = Alarm | ||||
| HR | 731doc 732 | Controller Alarm - Pol945 Board Offline | UINT16 | Read | 0 = NoAlarm; 1 = Alarm | ||||
| HR | 732doc 733 | Controller Alarm - DLT Board Offline | UINT16 | Read | 0 = NoAlarm; 1 = Alarm | ||||
| HR | 740doc 741 | Circuit 1 Alarm - Pumpdown Failure | UINT16 | Read | 0 = NoAlarm; 1 = Alarm | ||||
| HR | 741doc 742 | Circuit 2 Alarm - Pumpdown Failure | UINT16 | Read | 0 = NoAlarm; 1 = Alarm | ||||
| HR | 744doc 745 | Unit Alarm - External Event | UINT16 | Read | 0 = NoAlarm; 1 = Alarm | ||||
| HR | 746doc 747 | Circuit 1 Alarm - No Pressure change at Start | UINT16 | Read | 0 = NoAlarm; 1 = Alarm | ||||
| HR | 747doc 748 | Circuit 2 Alarm - No Pressure change at Start | UINT16 | Read | 0 = NoAlarm; 1 = Alarm | ||||
| HR | 797doc 798 | Unit Alarm - Emergency Stop Switch | UINT16 | Read | 0 = NoAlarm; 1 = Alarm | ||||
| HR | 798doc 799 | Unit Alarm - Evaporator Temperature Sensors Inverted | UINT16 | Read | 0 = NoAlarm; 1 = Alarm | ||||
| HR | 799doc 800 | Unit Alarm - External Alarm | UINT16 | Read | 0 = NoAlarm; 1 = Alarm | ||||
| HR | 800doc 801 | Unit Alarm - Heat Recovery Temperature Sensors Inverted | UINT16 | Read | 0 = NoAlarm; 1 = Alarm | ||||
| HR | 815doc 816 | Unit Alarm - Wrong Phase Voltage | UINT16 | Read | 0 = NoAlarm; 1 = Alarm | ||||
| HR | 843doc 844 | Circuit 1 Alarm - Gas Leakage | UINT16 | Read | 0 = NoAlarm; 1 = Alarm | ||||
| HR | 844doc 845 | Circuit 2 Alarm - Gas Leakage | UINT16 | Read | 0 = NoAlarm; 1 = Alarm | ||||
| HR | 849doc 850 | Unit - Electrical Panel Temperature | INT16 | × 0.1 | °C | Read | |||
| HR | 850doc 851 | Unit Warning - Electrical Panel Temp Sensor Fault | UINT16 | Read | 0 = NoAlarm; 1 = Alarm | ||||
| HR | 851doc 852 | Unit Warning - Electrical Panel High Temperature | UINT16 | Read | 0 = NoAlarm; 1 = Alarm | ||||
| HR | 897doc 898 | Controller Alarm - Energy Meter Communication Failure | UINT16 | Read | 0 = NoAlarm; 1 = Alarm | ||||
| HR | 900doc 901 | Circuit 1 Alarm - Fan Fault | UINT16 | Read | 0 = NoAlarm; 1 = Alarm | ||||
| HR | 901doc 902 | Circuit 2 Alarm - Fan Fault | UINT16 | Read | 0 = NoAlarm; 1 = Alarm | ||||
| HR | 907doc 908 | Circuit 1 Alarm - Fan Communication Failure | UINT16 | Read | 0 = NoAlarm; 1 = Alarm | ||||
| HR | 908doc 909 | Circuit 2 Alarm - Fan Communication Failure | UINT16 | Read | 0 = NoAlarm; 1 = Alarm | ||||
| HR | 1709doc 1710 | Circ 2 Compressor 4 - OffAuto Setpoint | UINT16 | Read/write | 0 = Off; 1 = Auto | ||||
| HR | 1720doc 1721 | Circ 2 Compressor 4 - Operating State | UINT16 | Read | 0 = Off; 1 = On | ||||
| HR | 1748doc 1749 | Circ 1 Compressor 4 - OffAuto Setpoint | UINT16 | Read/write | 0 = Off; 1 = Auto | ||||
| HR | 1759doc 1760 | Circ 1 Compressor 4 - Operating State | UINT16 | Read | 0 = Off; 1 = On | ||||
| HR | 1774doc 1775 | Circ 2 Compressor 3 - OffAuto Setpoint | UINT16 | Read/write | 0 = Off; 1 = Auto | ||||
| HR | 1785doc 1786 | Circ 2 Compressor 3 - Operating State | UINT16 | Read | 0 = Off; 1 = On | ||||
| HR | 1787doc 1788 | Circ 2 Compressor 2 - OffAuto Setpoint | UINT16 | Read/write | 0 = Off; 1 = Auto | ||||
| HR | 1798doc 1799 | Circ 2 Compressor 2 - Operating State | UINT16 | Read | 0 = Off; 1 = On | ||||
| HR | 1799doc 1800 | Circ 2 Compressor 1 - Actual Capacity | UINT16 | × 0.1 | % | Read | |||
| HR | 1800doc 1801 | Circ 2 Compressor 1 - OffAuto Setpoint | UINT16 | Read/write | 0 = Off; 1 = Auto | ||||
| HR | 1811doc 1812 | Circ 2 Compressor 1 - Operating State | UINT16 | Read | 0 = Off; 1 = On | ||||
| HR | 1813doc 1814 | Circ 1 Compressor 3 - OffAuto Setpoint | UINT16 | Read/write | 0 = Off; 1 = Auto | ||||
| HR | 1824doc 1825 | Circ 1 Compressor 3 - Operating State | UINT16 | Read | 0 = Off; 1 = On | ||||
| HR | 1826doc 1827 | Circ 1 Compressor 2 - OffAuto Setpoint | UINT16 | Read/write | 0 = Off; 1 = Auto | ||||
| HR | 1837doc 1838 | Circ 1 Compressor 2 - Operating State | UINT16 | Read | 0 = Off; 1 = On | ||||
| HR | 1839doc 1840 | Circ 1 Compressor 1 - Actual Capacity | UINT16 | × 0.1 | % | Read | |||
| HR | 1840doc 1841 | Circ 1 Compressor 1 - OffAuto Setpoint | UINT16 | Read/write | 0 = Off; 1 = Auto | ||||
| HR | 1851doc 1852 | Circ 1 Compressor 1 - Operating State | UINT16 | Read | 0 = Off; 1 = On | ||||
| HR | 1854doc 1855 | Unit - Number of Circuits | Range 1-2. | UINT16 | Read | ||||
| HR | 1855doc 1856 | Unit - Number of Compressors | Range 1-3. | UINT16 | Read | ||||
| HR | 1856doc 1857 | Unit - Number of Tons | UINT16 | tons | Read | ||||
| HR | 1895doc 1896 | Circuit 2 - Evaporator Superheat Active Setpoint | INT16 | × 0.1 | dK | Read | |||
| HR | 1896doc 1897 | Circuit 1 - Evaporator Superheat Active Setpoint | INT16 | × 0.1 | dK | Read | |||
| HR | 1897doc 1898 | Circuit 2 - Evaporator Superheat Temperature | INT16 | × 0.1 | dK | Read | |||
| HR | 1898doc 1899 | Circuit 1 - Evaporator Superheat Temperature | INT16 | × 0.1 | dK | Read | |||
| HR | 1901doc 1902 | Unit - Power Factor | INT16 | × 0.01 | Read | ||||
| HR | 1904doc 1905 | Variable Flow - Plant Differential Pressure | INT16 | × 0.1 | kPa | Read/write | |||
| HR | 1905doc 1906 | Varibale Flow - Water Bypass Valve State | UINT16 | Read | 1 = Closed; 2 = Opened | ||||
| HR | 1908doc 1909 | Varibale Flow - Plant Differential Pressure setpoint | UINT16 | × 0.1 | kPa | Read/write | |||
| HR | 1910doc 1911 | Variable Flow - Plant Delta Temperature | Temperature difference (printed as °Dc). | INT16 | × 0.1 | °C | Read | ||
| HR | 1912doc 1913 | Variable Flow - Plant Delta Temperature Setpoint | Temperature difference (printed as °Dc). | INT16 | × 0.1 | °C | Read/write | ||
| HR | 1914doc 1915 | Varibale Flow - Evaporator Fixed Speed Setpoint | INT16 | % | Read/write | ||||
| HR | 1965doc 1966 | Circuit 2 - Expansion Valve Position | UINT16 | % | Read | ||||
| HR | 1969doc 1970 | Circuit 2 - Fan Speed | UINT16 | % | Read | ||||
| HR | 1970doc 1971 | Circuit 2 - Condenser Approach Temperature | INT16 | × 0.1 | dK | Read | |||
| HR | 1971doc 1972 | Circuit 2 - Evaporator Approach Temperature | INT16 | × 0.1 | dK | Read | |||
| HR | 1980doc 1981 | Circuit 2 - Fan Staging | UINT16 | Read | |||||
| HR | 1981doc 1982 | Circuit 1 - Expansion Valve Position | UINT16 | % | Read | ||||
| HR | 1983doc 1984 | Circuit 1 - Liquid Line Refrigerant Temperature | INT16 | × 0.1 | °C | Read | |||
| HR | 1984doc 1985 | Circuit 2 - Liquid Line Refrigerant Temperature | INT16 | × 0.1 | °C | Read | |||
| HR | 1985doc 1986 | Circuit 1 - Fan Speed | UINT16 | % | Read | ||||
| HR | 1986doc 1987 | Circuit 1 - Condenser Approach Temperature | INT16 | × 0.1 | dK | Read | |||
| HR | 1987doc 1988 | Circuit 1 - Evaporator Approach Temperature | INT16 | × 0.1 | dK | Read | |||
| HR | 1996doc 1997 | Circuit 1 - Fan Staging | UINT16 | Read |
Notes on this map
- Addressing: the guide says every point is a holding register addressed as 4xxxx plus the number in its Address column, i.e. Modicon references (1 = 40001). On the wire that is the column value minus 1. Registers are listed here with that wire address; the documented field keeps the guide's column value.
- Values are 16-bit words; 'Gain' is the multiplier (0.1 means tenths of a unit). Temperatures and pressures are shown in metric units; the 'Measurement unit setpoint' register (column 316) switches the unit system between English and Metric.
- The Read/Write column only uses R and W; W points are taken as writable (and readable) and listed as RW. Points marked 'Prio 8' are commanded at priority 8 per the guide.
- Left out: every 'UNSIGNED DOUBLE' (32-bit) point (74-75 Circ 1 Compressor 1 - Number of Running Hours (32-bit); 87-88 Circ 1 Compressor 2 - Number of Running Hours (32-bit); 100-102 Circ 1 Compressor 3 - Number of Running Hours (32-bit); 113-114 Circ 2 Compressor 1 - Number of Running Hours (32-bit); 126-127 Circ 2 Compressor 2 - Number of Running Hours (32-bit); 139-140 Circ 2 Compressor 3 - Number of Running Hours (32-bit); 165-166 Circ 1 Compressor 4 - Number of Running Hours (32-bit); 204-205 Circ 2 Compressor 4 - Number of Running Hours (32-bit); 260-261 Performance - Unit Thermal Capacity (32-bit); 262-263 Performance - Unit Power Input (32-bit); 266-267 Performance - Unit Thermal Energy (32-bit); 268-268 Performance - Unit Electrical Energy (32-bit); 303-304 Evaporator Pump 1 - Number of Running Hours (32-bit); 306-307 Evaporator Pump 2 - Number of Running Hours (32-bit); 1900-1901 Unit - Active Energy (32-bit)). The guide does not say which word is high, and some address spans are misprinted, so they cannot be decoded safely from this document.
- Left out: the alarm code/index table in section 5.1; the Warning/Problem/Fault Index and Code registers are listed, but their meanings need that table.
- Free-cooling registers (columns 250-254) only apply to EWAFT (free-cooling) units.
Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.
Questions about the Daikin Applied EWAT-B / EWAFT-B / EWAT-C / EWAFT-C air-cooled inverter chillers (Microtech 4, ARES software)
What Modbus registers does the Daikin Applied EWAT-B / EWAFT-B / EWAT-C / EWAFT-C air-cooled inverter chillers (Microtech 4, ARES software) have?
This map lists 190 registers: 190 holding registers. 31 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.
Are the Daikin Applied EWAT-B / EWAFT-B / EWAT-C / EWAFT-C air-cooled inverter chillers (Microtech 4, ARES software) Modbus addresses 0-based or 1-based?
The manufacturer's document numbers registers 1-based (subtract 1 for the wire address). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. The guide says each holding register address is 4xxxx plus the Address column value, so column 1 = 40001 = wire address 0. Subtract 1 from the column value for the PDU address; in a Modicon-style tool enter 40000 + column.
What are the minimum Modbus registers to integrate the Daikin Applied EWAT-B / EWAFT-B / EWAT-C / EWAFT-C air-cooled inverter chillers (Microtech 4, ARES software)?
Start with HR 14 Unit - Status (Unit status (Off/Start/Run/...)); HR 16 Evaporator Leaving Water Temperature (Evaporator leaving water temperature); HR 12 Unit - Actual Capacity (Actual capacity); HR 8 Unit - Enable Setpoint (Unit enable command); HR 34 Unit - Cool Temperature Setpoint (Cooling temperature setpoint); HR 32 Unit Alarm - Fault Code (Active fault code); HR 0 Unit - Control Source (Control source (network or local)).
How do I enable Modbus control of the Daikin Applied EWAT-B / EWAFT-B / EWAT-C / EWAFT-C air-cooled inverter chillers (Microtech 4, ARES software)?
Either fit a POL902 module and set address/parity/stop bits/baud under Main menu > Commissioning > Modbus (service password), or switch on software option #1 'Modbus Slave MSTP' under Commissioning > Configuration > Software Options with its unlock password, then set the parameters under Commissioning > SW Modbus MSTP.
Where is the official Daikin Applied EWAT-B / EWAFT-B / EWAT-C / EWAFT-C air-cooled inverter chillers (Microtech 4, ARES software) Modbus documentation?
The source is BAS integration guide - Modbus protocol, EWA(F)T-B-C (ARES) (D-EIGOC00207-24_05EN), published free by Daikin Applied at https://www.daikinapplied.eu/hubfs/portale-documentale/D_EIGOC00207_24_05EN_EWA_F_T_B_C.pdf.
More Daikin Applied Modbus register maps
- Chiller
Daikin Applied ADS air-cooled global screw chiller (MicroTech controller)
Daikin Applied model ADS air-cooled global screw chillers with the MicroTech chiller unit controller and Modbus communication module, per ED 15121-13.
Also known as: ADS, Daikin ADS, Air-cooled Global Screw Chiller, ED 15121 - Heat pump
Daikin Applied EWAK-CZ / EWYK-CZ air-cooled chiller and heat pump (MicroTech 4, ICARO software)
Daikin Applied Europe EWAK-CZ / EWYK-CZ units with MicroTech 4 controller, ICARO software and POL902 Modbus module, per D-EIGOC00204-26_00EN.
Also known as: EWYK-CZ, EWAK-CZ, EWA(Y)K-CZ, ICARO, D-EIGOC00204 - Chiller (water-cooled)
Daikin Applied EWWD-VZ / EWWH-VZ / EWWS-VZ water-cooled inverter screw chillers (Microtech, Adam software)
EWWD-VZ, EWWH-VZ and EWWS-VZ water-cooled inverter screw chillers with Microtech III or Microtech 4 controller running Adam software, per D-EIGOC00201-22_03EN.
Also known as: EWWD-VZ, EWWH-VZ, EWWS-VZ, EWWD(H)(S)_VZ, EWWD~VZ, EWWH~VZ, Daikin EWWD VZ, Adam - Chiller
Daikin Applied Magnitude WMC-E magnetic-bearing centrifugal chiller (MicroTech controller)
Daikin Applied Magnitude WMC E-vintage water-cooled magnetic-bearing centrifugal chillers with the MicroTech unit controller and BACnet/Modbus communication module set to Modbus, per ED 19131-1.
Also known as: WMC-E, WMC E-Vintage, Magnitude WMC, Daikin WMC, ED 19131 - Chiller
Daikin Applied Magnitude WME B-vintage magnetic-bearing centrifugal chiller (MicroTech controller)
Daikin Applied Magnitude WME B-vintage water-cooled magnetic-bearing centrifugal chillers with the MicroTech chiller unit controller and Modbus communication module, per ED 15121-13.
Also known as: WME-B, WME B-Vintage, Magnitude WME B, ED 15121 - Chiller (water-cooled, magnetic-bearing centrifugal)
Daikin Applied Magnitude WME magnetic-bearing chiller (MicroTech, Modbus)
Magnitude WME C- and D-vintage and WME-C QUAD chillers with the MicroTech unit controller and Modbus communication module, per ED 19111-4.
Also known as: WME-C, WME-D, WME-C QUAD, Magnitude WME, Daikin WME - Chiller
Daikin Applied Magnitude WMT magnetic-bearing centrifugal chiller (MicroTech controller)
Daikin Applied Magnitude WMT water-cooled magnetic-bearing centrifugal chillers with the MicroTech unit controller and BACnet/Modbus communication module set to Modbus, per ED 19131-1.
Also known as: WMT, Magnitude WMT, Daikin WMT, ED 19131 - Chiller
Daikin Applied MicroTech II centrifugal chillers WSC/WDC/WPV/WMC/WCC/HSC/HDC/TSC (Modbus module)
McQuay/Daikin Applied water-cooled centrifugal chillers with the MicroTech II unit controller and Modbus Communication Module: WSC, WDC, WPV, WMC (magnetic bearing), WCC, HSC/HDC heat recovery and TSC Templifier, per ED 15063-2 (Dec 2005).
Also known as: WSC, WDC, WPV, WMC, WCC, HSC, HDC, TSC, McQuay centrifugal Modbus, MicroTech II chiller, ED 15063 - Chiller
Daikin Applied MicroTech II scroll and screw chillers AGZ/ACZ/WGZ/AGS/WGS (Modbus module)
McQuay/Daikin Applied AGZ air-cooled and WGZ water-cooled global scroll chillers, ACZ scroll condensing units, and AGS/WGS global screw chillers with the MicroTech II controller and Modbus Communication Module, per ED 15063-2 (Dec 2005).
Also known as: AGZ-A, AGZ-B, ACZ-A, ACZ-B, WGZ, AGS-B, AGS-C, WGS, AGZ, ACZ, AGS, McQuay global scroll Modbus, McQuay global screw Modbus, ED 15063 - Chiller
Daikin Applied Navigator WWV / TWV water-cooled screw chiller (MicroTech controller)
Daikin Applied Navigator WWV and TWV water-cooled screw chillers with the MicroTech chiller unit controller and Modbus communication module, per ED 15121-13.
Also known as: WWV, TWV, Navigator WWV, Navigator TWV, Daikin Navigator, ED 15121 - Chiller
Daikin Applied Pathfinder AWS air-cooled screw chiller (MicroTech controller)
Daikin Applied Pathfinder AWS air-cooled screw chillers with the MicroTech chiller unit controller and Modbus communication module, per ED 15121-13 (both application-version columns, 2507500204 and earlier / 2507500205 and later, mark the same data points).
Also known as: AWS, Pathfinder AWS, Daikin AWS, ED 15121 - Chiller
Daikin Applied Pathfinder AWV air-cooled screw chiller (MicroTech controller)
Daikin Applied Pathfinder AWV variable-speed air-cooled screw chillers with the MicroTech chiller unit controller and Modbus communication module, per ED 15121-13 (application 263220504 baseline; some points need newer code, marked per register).
Also known as: AWV, Pathfinder AWV, Pathfinder VFD air-cooled screw, MicroTech chiller unit controller, ED 15121 - Rooftop unit
Daikin Applied Rebel / Rebel Applied rooftop (MicroTech 4 controller)
Daikin Applied Rebel Applied (DPSA, R-410A/R-32) and Rebel (DPS, R-32) packaged rooftops with MicroTech 4 controller and Modbus RTU module, per ED 19133-2 (Oct 2025).
Also known as: DPSA, DPS, Rebel Applied, Rebel, MicroTech 4 rooftop, ED 19133-2 - Chiller
Daikin Applied Trailblazer AGZ-D / AGZ-E air-cooled scroll chiller (MicroTech controller)
Daikin Applied Trailblazer AGZ-D and AGZ-E air-cooled scroll chillers with the MicroTech chiller unit controller and Modbus communication module, per ED 15121-13.
Also known as: AGZ-D, AGZ-E, AGZ D-Vintage, AGZ E-Vintage, ED 15121, Trailblazer AGZ-D, Trailblazer AGZ-E - Chiller
Daikin Applied Trailblazer AGZ-F air-cooled scroll chiller (MicroTech controller)
Daikin Applied Trailblazer AGZ F-vintage air-cooled scroll chillers with the MicroTech unit controller and BACnet/Modbus communication module set to Modbus, per ED 19131-1 (application 1.2.0 and later).
Also known as: AGZ-F, AGZ F-Vintage, Trailblazer AGZ, Trailblazer AGZ-F, ED 19131 - Chiller
Daikin Applied Trailblazer AMZ air-cooled scroll chiller (MicroTech controller)
Daikin Applied Trailblazer AMZ air-cooled scroll chillers with the MicroTech chiller unit controller and Modbus communication module, per ED 15121-13.
Also known as: AMZ, Trailblazer AMZ, Daikin AMZ, ED 15121
Other chillers & heat pumps register maps
- Chiller
Trane Agility water-cooled centrifugal chiller (Symbio 800)
Trane Agility water-cooled chillers with Symbio 800 controls, as listed in BAS-PTS007C-EN (6/30/2026).
Also known as: Agility, HDWA, Agility water-cooled chiller - Chiller
Trane RTAC air-cooled helical-rotary chiller (Symbio 800)
Trane RTAC air-cooled helical-rotary chillers with the Symbio 800 controller, as listed in BAS-PTS023A-EN (11/8/2024).
Also known as: RTAC, Series R RTAC - Chiller (refrigerant chiller for Liebert XD rack cooling)
Vertiv Liebert XDC refrigerant chiller for XD systems with iCOM v4 (IntelliSlot Modbus)
Liebert XDC units (the compressorised refrigerant chiller that feeds Liebert XD rack and ceiling cooling modules) on the iCOM v4 controller with a Liebert IntelliSlot Modbus card.
Also known as: Liebert XDC, XDC, Liebert XD chiller - Chiller
Trane CenTraVac duplex centrifugal chiller (Symbio 800)
Trane dual-compressor (duplex) CenTraVac water-cooled centrifugal chillers fitted with the Symbio 800 controller, as listed in the Duplex tables of BAS-PTS009C-EN (12/12/2025).
Also known as: CDHF, CDHG, CDHH, CenTraVac Duplex Symbio 800 - Chiller
Trane Sintesis RTAF air-cooled screw chiller (Symbio 800)
Trane Sintesis RTAF air-cooled helical-rotary chillers with the Symbio 800 controller, as listed in BAS-PTS013B-EN (4/7/2026).
Also known as: RTAF, Sintesis RTAF, Sintesis air-cooled chiller - Chiller
Trane Ascend ACR Series C air-cooled chiller (Symbio 800)
Trane Ascend model ACR Series C air-cooled chillers with the Symbio 800 controller, as listed in BAS-PTS021A-EN (11/15/2024).
Also known as: ACR, Ascend ACR, ACR Series C, Ascend air-cooled chiller ACR
All chillers & heat pumps Modbus register maps →
Source: BAS integration guide - Modbus protocol, EWA(F)T-B-C (ARES) · D-EIGOC00207-24_05EN. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.