Chiller (air-cooled) · Modbus register map

Daikin Applied EWAT-B / EWAFT-B / EWAT-C / EWAFT-C air-cooled inverter chillers (Microtech 4, ARES software) Modbus register map

Updated 17 November 2026

Short answer

Daikin Applied Europe's EWA(F)T-B/C air-cooled inverter chillers run a Microtech 4 controller that acts as a Modbus RTU slave over RS-485, either through a POL902 plug-in module or a licensed on-board software option. Every point is a 16-bit holding register: unit and circuit status, water and refrigerant temperatures and pressures, setpoints, compressor and pump states, free-cooling status and individual alarm flags.

This page lists 190 Modbus registers for the Daikin Applied EWAT-B / EWAFT-B / EWAT-C / EWAFT-C air-cooled inverter chillers (Microtech 4, ARES software) — 31 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Daikin Applied’s own free documentation (linked below) and checked against it.

Manufacturer
Daikin Applied
Model
EWAT-B / EWAFT-B / EWAT-C / EWAFT-C air-cooled inverter chillers (Microtech 4, ARES software)
Equipment type
Chiller (air-cooled)
Registers
190 (31 writable)
Transport
Modbus RTU
Default unit ID
Not stated
Default serial
19200 baud, 8N1
Documented addressing
1-based (subtract 1 for the wire address)
Firmware
ARES control software (no version printed)
Also known as
EWAT-B, EWAFT-B, EWAT-C, EWAFT-C, EWA(F)T-B-C, EWAT~B, EWAFT~B, Daikin EWAT, ARES
Source document
BAS integration guide - Modbus protocol, EWA(F)T-B-C (ARES) · D-EIGOC00207-24_05EN
Download CSV all columns JSON Manufacturer PDF ↗

Integration notes: Daikin Applied EWAT-B / EWAFT-B / EWAT-C / EWAFT-C air-cooled inverter chillers (Microtech 4, ARES software)

Integration in brief

Read holding registers from wire address 0: Unit Status (col 15), leaving water temperature (col 17) and capacity (col 13). Enable the unit with col 9 and send the cooling setpoint to col 35 (tenths of °C).

Minimum registers to map

Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.

RegisterNameTypeWhyAccess
HR 14Unit - StatusUINT16Unit status (Off/Start/Run/...)Read
HR 16Evaporator Leaving Water TemperatureINT16Evaporator leaving water temperatureRead
HR 12Unit - Actual CapacityUINT16Actual capacityRead
HR 8Unit - Enable SetpointUINT16Unit enable commandRead/write
HR 34Unit - Cool Temperature SetpointINT16Cooling temperature setpointRead/write
HR 32Unit Alarm - Fault CodeUINT16Active fault codeRead
HR 0Unit - Control SourceUINT16Control source (network or local)Read

Enable Modbus control & writes

Either fit a POL902 module and set address/parity/stop bits/baud under Main menu > Commissioning > Modbus (service password), or switch on software option #1 'Modbus Slave MSTP' under Commissioning > Configuration > Software Options with its unlock password, then set the parameters under Commissioning > SW Modbus MSTP.

Byte order & addressing

Network setup

Watch out for

Daikin Applied EWAT-B / EWAFT-B / EWAT-C / EWAFT-C air-cooled inverter chillers (Microtech 4, ARES software) Modbus registers

Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.

190 of 190 shown
Daikin Applied EWAT-B / EWAFT-B / EWAT-C / EWAFT-C air-cooled inverter chillers (Microtech 4, ARES software) Modbus register map
TableAddressNameDescriptionTypeOrderScaleUnitsAccessValues / bits
HR0doc 1Unit - Control SourceUINT16Read0 = Network; 1 = Local
HR1doc 2Unit - Enabled StateUINT16Read0 = Disabled; 1 = Enabled
HR2doc 3Unit - Run AllowedUINT16Read0 = Off; 1 = Allowed
HR3doc 4Unit - Capacity LimitedUINT16Read0 = NotLimited; 1 = Limited
HR4doc 5Unit - Generic StatusUINT16Read0 = Off; 1 = On
HR5doc 6Evaporator - Water Flow StateUINT16Read0 = NoFlow; 1 = Flow
HR7doc 8Unit - Operating StateUINT16Read0 = ThermoOff; 1 = ThermoOn
HR8doc 9Unit - Enable SetpointNetwork command at priority 8.UINT16Read/write0 = Disable; 1 = Enable
HR9doc 10Unit - Alarm Reset SetpointNetwork command at priority 8.UINT16Read/write0 = None; 1 = Clear
HR10doc 11Unit - Active Operation ModeUINT16Read1 = Ice; 2 = Cool; 3 = Heat; 4 = Pursuit
HR11doc 12Unit - Active Temperature SetpointINT16× 0.1°CRead
HR12doc 13Unit - Actual CapacityUINT16× 0.1%Read
HR13doc 14Unit - Active Capacity LimitUINT16× 0.1%Read
HR14doc 15Unit - StatusUINT16Read1 = Off; 2 = Start; 3 = Run; 4 = PreShutdown; 5 = Service
HR15doc 16Evaporator Entering Water TemperatureINT16× 0.1°CRead
HR16doc 17Evaporator Leaving Water TemperatureINT16× 0.1°CRead
HR17doc 18Heat Recovery - Enable SetpointNetwork command at priority 8.UINT16Read/write0 = Disable; 1 = Enable
HR21doc 22Heat Recovery - Entering Water TemperatureINT16× 0.1°CRead
HR22doc 23Heat Recovery - Leaving Water TemperatureINT16× 0.1°CRead
HR23doc 24Outside Air TemperatureINT16× 0.1°CRead
HR24doc 25Unit - Average CurrentUINT16ARead
HR25doc 26Unit - Average VoltageUINT16× 0.1VRead
HR26doc 27Unit - Active PowerUINT16× 0.1kWRead
HR27doc 28Unit Alarm - Warning IndexNumeric code; see the alarm code and index table in section 5.1.UINT16Read
HR28doc 29Unit Alarm - Problem IndexNumeric code; see the alarm code and index table in section 5.1.UINT16Read
HR29doc 30Unit Alarm - Fault IndexNumeric code; see the alarm code and index table in section 5.1.UINT16Read
HR30doc 31Unit Alarm - Warning CodeNumeric code; see the alarm code and index table in section 5.1.UINT16Read
HR31doc 32Unit Alarm - Problem CodeNumeric code; see the alarm code and index table in section 5.1.UINT16Read
HR32doc 33Unit Alarm - Fault CodeNumeric code; see the alarm code and index table in section 5.1.UINT16Read
HR33doc 34Unit - Operation Mode SetpointNetwork command at priority 8.UINT16Read/write0 = NULL; 1 = Ice; 2 = Cool; 3 = Heat; 4 = Pursuit
HR34doc 35Unit - Cool Temperature SetpointINT16× 0.1°CRead/write
HR35doc 36Unit - Ice Temperature SetpointINT16× 0.1°CRead/write
HR36doc 37Unit - Heat Temperature SetpointINT16× 0.1°CRead/write
HR37doc 38Unit - Capacity Limit SetpointUINT16× 0.1%Read/write
HR38doc 39Circuit 1 - Condenser Refrigerant PressureINT16× 0.1kPaRead
HR39doc 40Circuit 1 - Condeser Saturated TemperatureINT16× 0.1°CRead
HR40doc 41Circuit 1 - Evaporator Refrigerant PressureINT16× 0.1kPaRead
HR41doc 42Circuit 1 - Evaporator Saturated TemperatureINT16× 0.1°CRead
HR42doc 43Circuit 2 - Condenser Refrigerant PressureINT16× 0.1kPaRead
HR43doc 44Circuit 2 - Condeser Saturated TemperatureINT16× 0.1°CRead
HR44doc 45Circuit 2 - Evaporator Refrigerant PressureINT16× 0.1kPaRead
HR45doc 46Circuit 2 - Evaporator Saturated TemperatureINT16× 0.1°CRead
HR50doc 51Circuit 1 - Shutdown AlarmUINT16Read0 = NoAlarm; 1 = Alarm
HR51doc 52Circuit 2 - Shutdown AlarmUINT16Read0 = NoAlarm; 1 = Alarm
HR53doc 54Unit - Shutdown AlarmUINT16Read0 = NoAlarm; 1 = Alarm
HR58doc 59Heat Recovery - Temperature SetpointINT16× 0.1°CRead/write
HR59doc 60Heat Recovery - Operating StateUINT16Read1 = Off; 2 = Recirculation; 3 = Regulation
HR64doc 65Circ 1 Compressor 1 - Suction TemperatureINT16× 0.1°CRead
HR66doc 67Circ 1 - Discharge TemperatureINT16× 0.1°CRead
HR67doc 68Circ 1 Compressor 1 - Discharge TemperatureINT16× 0.1°CRead
HR72doc 73Circ 1 Compressor 1 - Number of StartsUINT16Read/write
HR80doc 81Circ 1 Compressor 2 - Discharge TemperatureINT16× 0.1°CRead
HR85doc 86Circ 1 Compressor 2 - Number of StartsUINT16Read/write
HR93doc 94Circ 1 Compressor 3 - Discharge TemperatureINT16× 0.1°CRead
HR98doc 99Circ 1 Compressor 3 - Number of StartsUINT16Read/write
HR103doc 104Circ 2 Compressor 1 - Suction TemperatureINT16× 0.1°CRead
HR105doc 106Circ 2 - Discharge TemperatureINT16× 0.1°CRead
HR106doc 107Circ 2 Compressor 1 - Discharge TemperatureINT16× 0.1°CRead
HR111doc 112Circ 2 Compressor 1 - Number of StartsUINT16Read/write
HR119doc 120Circ 2 Compressor 2 - Discharge TemperatureINT16× 0.1°CRead
HR124doc 125Circ 2 Compressor 2 - Number of StartsUINT16Read/write
HR132doc 133Circ 2 Compressor 3 - Discharge TemperatureINT16× 0.1°CRead
HR137doc 138Circ 2 Compressor 3 - Number of StartsUINT16Read/write
HR158doc 159Circ 1 Compressor 4 - Discharge TemperatureINT16× 0.1°CRead
HR163doc 164Circ 1 Compressor 4 - Number of StartsUINT16Read/write
HR197doc 198Circ 2 Compressor 4 - Discharge TemperatureINT16× 0.1°CRead
HR202doc 203Circ 2 Compressor 4 - Number of StartsUINT16Read/write
HR249doc 250Freecooling - Enable SetpointNetwork command at priority 8.UINT16Read/write0 = Disable; 1 = Enable
HR250doc 251Freecooling - StatusUINT16Read1 = Off; 2 = Full; 3 = Mixed; 4 = Mechanical
HR251doc 252Freeccoling - Enabled StateUINT16Read1 = Off; 2 = Run
HR252doc 253Freecooling - Circuit 1 ModeUINT16Read1 = Mechanical; 2 = Switching; 3 = Switching; 4 = FreeCooling; 5 = FC Pumpdown; 6 = FC Off
HR253doc 254Freecooling - Circuit 2 ModeUINT16Read1 = Mechanical; 2 = Switching; 3 = Switching; 4 = FreeCooling; 5 = FC Pumpdown; 6 = FC Off
HR263doc 264Performance - Unit EfficiencyUINT16× 0.01Read
HR295doc 296Evaporator Pump - SpeedUINT16%Read
HR304doc 305Evaporator Pump 1 - Operating StateUINT16Read0 = Stop; 1 = Run
HR307doc 308Evaporator Pump 2 - Operating StateUINT16Read0 = Stop; 1 = Run
HR315doc 316Unit - Measurement unit setpointUINT16Read/write0 = English; 1 = Metric
HR365doc 366Unit Alarm - Evaporator Entering Temperature Sensor FaultUINT16Read0 = NoAlarm; 1 = Alarm
HR376doc 377Unit Warning - Setpoint Reset Input Out of RangeUINT16Read0 = NoAlarm; 1 = Alarm
HR377doc 378Unit Warning - Demand Limit Input Out of RangeUINT16Read0 = NoAlarm; 1 = Alarm
HR387doc 388Unit Warning - Inhibition for Low Ambient TemperatureUINT16Read0 = NoAlarm; 1 = Alarm
HR394doc 395Circuit 1 Warning - Unload for Condenser High PressureUINT16Read0 = NoAlarm; 1 = Alarm
HR395doc 396Circuit 2 Warning - Unload for Condenser High PressureUINT16Read0 = NoAlarm; 1 = Alarm
HR410doc 411Circuit 1 Warning - Inhibition for Evaporator Low PressureUINT16Read0 = NoAlarm; 1 = Alarm
HR411doc 412Circuit 2 Warning - Inhibition for Evaporator Low PressureUINT16Read0 = NoAlarm; 1 = Alarm
HR415doc 416Circuit 1 Warning - Unload for Evaporator Low PressureUINT16Read0 = NoAlarm; 1 = Alarm
HR416doc 417Circuit 2 Warning - Unload for Evaporator Low PressureUINT16Read0 = NoAlarm; 1 = Alarm
HR429doc 430Evaporator Pump 1 - FaultUINT16Read0 = NoAlarm; 1 = Alarm
HR430doc 431Evaporator Pump 2 - FaultUINT16Read0 = NoAlarm; 1 = Alarm
HR439doc 440Circ 1 Comp 1 Alarm - Low Pressure RatioUINT16Read0 = NoAlarm; 1 = Alarm
HR441doc 442Circ 2 Comp 1 Alarm - Low Pressure RatioUINT16Read0 = NoAlarm; 1 = Alarm
HR445doc 446Unit Alarm - Outside Air Temperature Sensor FaultUINT16Read0 = NoAlarm; 1 = Alarm
HR465doc 466Circ 1 Comp 1 Alarm - Motor ProtectionUINT16Read0 = NoAlarm; 1 = Alarm
HR466doc 467Circ 1 Comp 2 Alarm - Motor ProtectionUINT16Read0 = NoAlarm; 1 = Alarm
HR467doc 468Circ 2 Comp 1 Alarm - Motor ProtectionUINT16Read0 = NoAlarm; 1 = Alarm
HR468doc 469Circ 2 Comp 2 Alarm - Motor ProtectionUINT16Read0 = NoAlarm; 1 = Alarm
HR469doc 470Circ 1 Comp 3 Alarm - Motor ProtectionUINT16Read0 = NoAlarm; 1 = Alarm
HR470doc 471Circ 2 Comp 3 Alarm - Motor ProtectionUINT16Read0 = NoAlarm; 1 = Alarm
HR471doc 472Circ 1 Comp 4 Alarm - Motor ProtectionUINT16Read0 = NoAlarm; 1 = Alarm
HR472doc 473Circ 2 Comp 4 Alarm - Motor ProtectionUINT16Read0 = NoAlarm; 1 = Alarm
HR508doc 509Circuit 1 Alarm - Condenser Pressure Sensor FaultUINT16Read0 = NoAlarm; 1 = Alarm
HR510doc 511Circuit 2 Alarm - Condenser Pressure Sensor FaultUINT16Read0 = NoAlarm; 1 = Alarm
HR516doc 517Circuit 1 Alarm - Condenser High PressureUINT16Read0 = NoAlarm; 1 = Alarm
HR518doc 519Circuit 2 Alarm - Condenser High PressureUINT16Read0 = NoAlarm; 1 = Alarm
HR528doc 529Circuit 1 Alarm - Discharge Temperature Sensor FaultUINT16Read0 = NoAlarm; 1 = Alarm
HR530doc 531Circuit 2 Alarm - Discharge Temperature Sensor FaultUINT16Read0 = NoAlarm; 1 = Alarm
HR541doc 542Unit Alarm - Evaporator Water Flow LossUINT16Read0 = NoAlarm; 1 = Alarm
HR542doc 543Unit Alarm - Evaporator Water FreezeUINT16Read0 = NoAlarm; 1 = Alarm
HR544doc 545Circuit 1 Alarm - Evaporator Pressure LowUINT16Read0 = NoAlarm; 1 = Alarm
HR546doc 547Circuit 2 Alarm - Evaporator Pressure LowUINT16Read0 = NoAlarm; 1 = Alarm
HR551doc 552Circuit 1 Alarm - Evaporator Pressure Sensor FailureUINT16Read0 = NoAlarm; 1 = Alarm
HR553doc 554Circuit 2 Alarm - Evaporator Pressure Sensor FailureUINT16Read0 = NoAlarm; 1 = Alarm
HR582doc 583Circuit 1 Alarm - Too many restartUINT16Read0 = NoAlarm; 1 = Alarm
HR584doc 585Circuit 2 Alarm - Too many restartUINT16Read0 = NoAlarm; 1 = Alarm
HR588doc 589Unit Alarm - Evaporator Leaving Temperature Sensor FaultUINT16Read0 = NoAlarm; 1 = Alarm
HR600doc 601Circuit 1 Alarm - Mechanical High PressureUINT16Read0 = NoAlarm; 1 = Alarm
HR602doc 603Circuit 2 Alarm - Mechanical High PressureUINT16Read0 = NoAlarm; 1 = Alarm
HR651doc 652Circuit 1 Alarm - Liquid Temperature Sensor FailureUINT16Read0 = NoAlarm; 1 = Alarm
HR654doc 655Circuit 2 Alarm - Liquid Temperature Sensor FailureUINT16Read0 = NoAlarm; 1 = Alarm
HR697doc 698Circ 1 Comp 1 Alarm - Suction Temperature Sensor FaultUINT16Read0 = NoAlarm; 1 = Alarm
HR699doc 700Circ 2 Comp 1 Alarm - Suction Temperature Sensor FaultUINT16Read0 = NoAlarm; 1 = Alarm
HR721doc 722Controller Alarm - Main Controller Board OfflineUINT16Read0 = NoAlarm; 1 = Alarm
HR722doc 723Controller Alarm - Circuit 1 Board OfflineUINT16Read0 = NoAlarm; 1 = Alarm
HR723doc 724Controller Alarm - Circuit 2 Board OfflineUINT16Read0 = NoAlarm; 1 = Alarm
HR731doc 732Controller Alarm - Pol945 Board OfflineUINT16Read0 = NoAlarm; 1 = Alarm
HR732doc 733Controller Alarm - DLT Board OfflineUINT16Read0 = NoAlarm; 1 = Alarm
HR740doc 741Circuit 1 Alarm - Pumpdown FailureUINT16Read0 = NoAlarm; 1 = Alarm
HR741doc 742Circuit 2 Alarm - Pumpdown FailureUINT16Read0 = NoAlarm; 1 = Alarm
HR744doc 745Unit Alarm - External EventUINT16Read0 = NoAlarm; 1 = Alarm
HR746doc 747Circuit 1 Alarm - No Pressure change at StartUINT16Read0 = NoAlarm; 1 = Alarm
HR747doc 748Circuit 2 Alarm - No Pressure change at StartUINT16Read0 = NoAlarm; 1 = Alarm
HR797doc 798Unit Alarm - Emergency Stop SwitchUINT16Read0 = NoAlarm; 1 = Alarm
HR798doc 799Unit Alarm - Evaporator Temperature Sensors InvertedUINT16Read0 = NoAlarm; 1 = Alarm
HR799doc 800Unit Alarm - External AlarmUINT16Read0 = NoAlarm; 1 = Alarm
HR800doc 801Unit Alarm - Heat Recovery Temperature Sensors InvertedUINT16Read0 = NoAlarm; 1 = Alarm
HR815doc 816Unit Alarm - Wrong Phase VoltageUINT16Read0 = NoAlarm; 1 = Alarm
HR843doc 844Circuit 1 Alarm - Gas LeakageUINT16Read0 = NoAlarm; 1 = Alarm
HR844doc 845Circuit 2 Alarm - Gas LeakageUINT16Read0 = NoAlarm; 1 = Alarm
HR849doc 850Unit - Electrical Panel TemperatureINT16× 0.1°CRead
HR850doc 851Unit Warning - Electrical Panel Temp Sensor FaultUINT16Read0 = NoAlarm; 1 = Alarm
HR851doc 852Unit Warning - Electrical Panel High TemperatureUINT16Read0 = NoAlarm; 1 = Alarm
HR897doc 898Controller Alarm - Energy Meter Communication FailureUINT16Read0 = NoAlarm; 1 = Alarm
HR900doc 901Circuit 1 Alarm - Fan FaultUINT16Read0 = NoAlarm; 1 = Alarm
HR901doc 902Circuit 2 Alarm - Fan FaultUINT16Read0 = NoAlarm; 1 = Alarm
HR907doc 908Circuit 1 Alarm - Fan Communication FailureUINT16Read0 = NoAlarm; 1 = Alarm
HR908doc 909Circuit 2 Alarm - Fan Communication FailureUINT16Read0 = NoAlarm; 1 = Alarm
HR1709doc 1710Circ 2 Compressor 4 - OffAuto SetpointUINT16Read/write0 = Off; 1 = Auto
HR1720doc 1721Circ 2 Compressor 4 - Operating StateUINT16Read0 = Off; 1 = On
HR1748doc 1749Circ 1 Compressor 4 - OffAuto SetpointUINT16Read/write0 = Off; 1 = Auto
HR1759doc 1760Circ 1 Compressor 4 - Operating StateUINT16Read0 = Off; 1 = On
HR1774doc 1775Circ 2 Compressor 3 - OffAuto SetpointUINT16Read/write0 = Off; 1 = Auto
HR1785doc 1786Circ 2 Compressor 3 - Operating StateUINT16Read0 = Off; 1 = On
HR1787doc 1788Circ 2 Compressor 2 - OffAuto SetpointUINT16Read/write0 = Off; 1 = Auto
HR1798doc 1799Circ 2 Compressor 2 - Operating StateUINT16Read0 = Off; 1 = On
HR1799doc 1800Circ 2 Compressor 1 - Actual CapacityUINT16× 0.1%Read
HR1800doc 1801Circ 2 Compressor 1 - OffAuto SetpointUINT16Read/write0 = Off; 1 = Auto
HR1811doc 1812Circ 2 Compressor 1 - Operating StateUINT16Read0 = Off; 1 = On
HR1813doc 1814Circ 1 Compressor 3 - OffAuto SetpointUINT16Read/write0 = Off; 1 = Auto
HR1824doc 1825Circ 1 Compressor 3 - Operating StateUINT16Read0 = Off; 1 = On
HR1826doc 1827Circ 1 Compressor 2 - OffAuto SetpointUINT16Read/write0 = Off; 1 = Auto
HR1837doc 1838Circ 1 Compressor 2 - Operating StateUINT16Read0 = Off; 1 = On
HR1839doc 1840Circ 1 Compressor 1 - Actual CapacityUINT16× 0.1%Read
HR1840doc 1841Circ 1 Compressor 1 - OffAuto SetpointUINT16Read/write0 = Off; 1 = Auto
HR1851doc 1852Circ 1 Compressor 1 - Operating StateUINT16Read0 = Off; 1 = On
HR1854doc 1855Unit - Number of CircuitsRange 1-2.UINT16Read
HR1855doc 1856Unit - Number of CompressorsRange 1-3.UINT16Read
HR1856doc 1857Unit - Number of TonsUINT16tonsRead
HR1895doc 1896Circuit 2 - Evaporator Superheat Active SetpointINT16× 0.1dKRead
HR1896doc 1897Circuit 1 - Evaporator Superheat Active SetpointINT16× 0.1dKRead
HR1897doc 1898Circuit 2 - Evaporator Superheat TemperatureINT16× 0.1dKRead
HR1898doc 1899Circuit 1 - Evaporator Superheat TemperatureINT16× 0.1dKRead
HR1901doc 1902Unit - Power FactorINT16× 0.01Read
HR1904doc 1905Variable Flow - Plant Differential PressureINT16× 0.1kPaRead/write
HR1905doc 1906Varibale Flow - Water Bypass Valve StateUINT16Read1 = Closed; 2 = Opened
HR1908doc 1909Varibale Flow - Plant Differential Pressure setpointUINT16× 0.1kPaRead/write
HR1910doc 1911Variable Flow - Plant Delta TemperatureTemperature difference (printed as °Dc).INT16× 0.1°CRead
HR1912doc 1913Variable Flow - Plant Delta Temperature SetpointTemperature difference (printed as °Dc).INT16× 0.1°CRead/write
HR1914doc 1915Varibale Flow - Evaporator Fixed Speed SetpointINT16%Read/write
HR1965doc 1966Circuit 2 - Expansion Valve PositionUINT16%Read
HR1969doc 1970Circuit 2 - Fan SpeedUINT16%Read
HR1970doc 1971Circuit 2 - Condenser Approach TemperatureINT16× 0.1dKRead
HR1971doc 1972Circuit 2 - Evaporator Approach TemperatureINT16× 0.1dKRead
HR1980doc 1981Circuit 2 - Fan StagingUINT16Read
HR1981doc 1982Circuit 1 - Expansion Valve PositionUINT16%Read
HR1983doc 1984Circuit 1 - Liquid Line Refrigerant TemperatureINT16× 0.1°CRead
HR1984doc 1985Circuit 2 - Liquid Line Refrigerant TemperatureINT16× 0.1°CRead
HR1985doc 1986Circuit 1 - Fan SpeedUINT16%Read
HR1986doc 1987Circuit 1 - Condenser Approach TemperatureINT16× 0.1dKRead
HR1987doc 1988Circuit 1 - Evaporator Approach TemperatureINT16× 0.1dKRead
HR1996doc 1997Circuit 1 - Fan StagingUINT16Read

Notes on this map

Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.

Questions about the Daikin Applied EWAT-B / EWAFT-B / EWAT-C / EWAFT-C air-cooled inverter chillers (Microtech 4, ARES software)

What Modbus registers does the Daikin Applied EWAT-B / EWAFT-B / EWAT-C / EWAFT-C air-cooled inverter chillers (Microtech 4, ARES software) have?

This map lists 190 registers: 190 holding registers. 31 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.

Are the Daikin Applied EWAT-B / EWAFT-B / EWAT-C / EWAFT-C air-cooled inverter chillers (Microtech 4, ARES software) Modbus addresses 0-based or 1-based?

The manufacturer's document numbers registers 1-based (subtract 1 for the wire address). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. The guide says each holding register address is 4xxxx plus the Address column value, so column 1 = 40001 = wire address 0. Subtract 1 from the column value for the PDU address; in a Modicon-style tool enter 40000 + column.

What are the minimum Modbus registers to integrate the Daikin Applied EWAT-B / EWAFT-B / EWAT-C / EWAFT-C air-cooled inverter chillers (Microtech 4, ARES software)?

Start with HR 14 Unit - Status (Unit status (Off/Start/Run/...)); HR 16 Evaporator Leaving Water Temperature (Evaporator leaving water temperature); HR 12 Unit - Actual Capacity (Actual capacity); HR 8 Unit - Enable Setpoint (Unit enable command); HR 34 Unit - Cool Temperature Setpoint (Cooling temperature setpoint); HR 32 Unit Alarm - Fault Code (Active fault code); HR 0 Unit - Control Source (Control source (network or local)).

How do I enable Modbus control of the Daikin Applied EWAT-B / EWAFT-B / EWAT-C / EWAFT-C air-cooled inverter chillers (Microtech 4, ARES software)?

Either fit a POL902 module and set address/parity/stop bits/baud under Main menu > Commissioning > Modbus (service password), or switch on software option #1 'Modbus Slave MSTP' under Commissioning > Configuration > Software Options with its unlock password, then set the parameters under Commissioning > SW Modbus MSTP.

Where is the official Daikin Applied EWAT-B / EWAFT-B / EWAT-C / EWAFT-C air-cooled inverter chillers (Microtech 4, ARES software) Modbus documentation?

The source is BAS integration guide - Modbus protocol, EWA(F)T-B-C (ARES) (D-EIGOC00207-24_05EN), published free by Daikin Applied at https://www.daikinapplied.eu/hubfs/portale-documentale/D_EIGOC00207_24_05EN_EWA_F_T_B_C.pdf.

More Daikin Applied Modbus register maps

Other chillers & heat pumps register maps

All chillers & heat pumps Modbus register maps →

Source: BAS integration guide - Modbus protocol, EWA(F)T-B-C (ARES) · D-EIGOC00207-24_05EN. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.