Trane Agility water-cooled centrifugal chiller (Symbio 800) Modbus register map

Updated 17 November 2026

Short answer

Trane's Agility is a compact water-cooled centrifugal chiller with an adaptive-frequency drive. Its Symbio 800 controller serves BACnet and Modbus RTU/TCP from one points list. This map covers the analog inputs (setpoints, drive values, flows, temperatures, pressures, energy meter), BAS setpoints, binary status and diagnostic flags and the multi-state mode points.

This page lists 412 Modbus registers for the Trane Agility water-cooled centrifugal chiller (Symbio 800) — 17 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Trane’s own free documentation (linked below) and checked against it.

Manufacturer
Trane
Model
Agility water-cooled centrifugal chiller (Symbio 800)
Equipment type
Chiller
Registers
412 (17 writable)
Transport
Modbus RTU, Modbus TCP
Default unit ID
Not stated
Default serial
19200 baud, 8E1
Documented addressing
Modicon 3xxxx/4xxxx (drop the prefix, subtract 1)
32-bit word order
ABCD high word first (big-endian)
Also known as
Agility, HDWA, Agility water-cooled chiller
Source document
Symbio 800 Integration Points List, BACnet/Modbus, Agility Water-Cooled Chillers · BAS-PTS007C-EN · rev. 2026-06-30
Download CSV all columns JSON Manufacturer PDF ↗

Integration notes: Trane Agility water-cooled centrifugal chiller (Symbio 800)

Integration in brief

Read the analog inputs as pairs of input registers (float, high word first) and the binary/multi-state points as single registers. Write the BAS setpoints and command points in the 4xxxx holding range.

Minimum registers to map

Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.

RegisterNameTypeWhyAccess
IR 10Active Chilled Water SetpointFLOAT32 ABCDActive chilled water setpointRead
IR 22Chilled Water Setpoint StatusFLOAT32 ABCDChilled water setpoint statusRead
IR 48Drive Speed Status PercentFLOAT32 ABCDDrive speed %Read
IR 3019Chiller Running StateUINT16Chiller running stateRead
IR 3010Diagnostic PresentUINT16Diagnostic presentRead
HR 10Chilled Water SetpointFLOAT32 ABCDChilled water setpoint (BAS)Read/write
HR 2010Chiller Mode Command BASUINT16Chiller mode commandRead/write
HR 3010Base Loading RequestUINT16Base loading requestRead/write

Enable Modbus control & writes

On the Symbio 800 web interface (USB connection) go to Installation > Identification and Communications > Protocol Configuration and select Modbus RTU or Modbus TCP; for TCP set the IP address on the IP Configuration tab.

Byte order & addressing

Network setup

Watch out for

Trane Agility water-cooled centrifugal chiller (Symbio 800) Modbus registers

Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.

412 of 412 shown
Trane Agility water-cooled centrifugal chiller (Symbio 800) Modbus register map
TableAddressNameDescriptionTypeOrderScaleUnitsAccessValues / bits
IR10doc 30011Active Chilled Water SetpointTemperature in the unit system set at the factory (I-P or SI).FLOAT32ABCDRead
IR12doc 30013Active Base Loading SetpointNeeds: Base LoadingFLOAT32ABCD%Read
IR14doc 30015Active Cool/Heat Setpoint TemperatureTemperature in the unit system set at the factory (I-P or SI).FLOAT32ABCDRead
IR16doc 30017Active Hot Water SetpointTemperature in the unit system set at the factory (I-P or SI). Needs: Hot Water ControlFLOAT32ABCDRead
IR18doc 30019Active Demand Limit SetpointFLOAT32ABCD%Read
IR20doc 30021Demand Limit Setpoint StatusNeeds: Ice BuildingFLOAT32ABCD%Read
IR22doc 30023Chilled Water Setpoint StatusTemperature in the unit system set at the factory (I-P or SI).FLOAT32ABCDRead
IR24doc 30025Drive Motor Average Current RLA Circuit 1FLOAT32ABCD%Read
IR26doc 30027Drive Motor VoltageVoltage.FLOAT32ABCDRead
IR28doc 30029Drive DC Bus Voltage Circuit 1Voltage.FLOAT32ABCDRead
IR30doc 30031AFD Frequency Circuit 1FLOAT32ABCDRead
IR32doc 30033AFD Transistor Temperature Circuit 1Temperature in the unit system set at the factory (I-P or SI).FLOAT32ABCDRead
IR34doc 30035Drive Motor Current U Circuit 1Current.FLOAT32ABCDRead
IR36doc 30037Drive Motor Current U RLA Circuit 1FLOAT32ABCD%Read
IR38doc 30039Drive Motor Current V Circuit 1Current.FLOAT32ABCDRead
IR40doc 30041Drive Motor Current V RLA Circuit 1FLOAT32ABCD%Read
IR42doc 30043Drive Motor Current W Circuit 1Current.FLOAT32ABCDRead
IR44doc 30045Drive Motor Current W RLA Circuit 1FLOAT32ABCD%Read
IR46doc 30047Drive Output Power Circuit 1Electrical power.FLOAT32ABCDRead
IR48doc 30049Drive Speed Status PercentFLOAT32ABCD%Read
IR50doc 30051Condenser Water Flow RateFlow in the factory unit system (I-P or SI). Needs: Cond Water Flow MeasurementFLOAT32ABCDRead
IR52doc 30053Evaporator Water Flow RateFlow in the factory unit system (I-P or SI). Needs: Evap Water Flow MeasurementFLOAT32ABCDRead
IR54doc 30055Calculated Chiller CapacityCooling capacity in the factory unit system (I-P or SI). Needs: Evap Water Flow MeasurementFLOAT32ABCDRead
IR56doc 30057Compressor Bearing Temperature 1 - Compressor 1ATemperature in the unit system set at the factory (I-P or SI).FLOAT32ABCDRead
IR58doc 30059Compressor Bearing Temperature 2 - Compressor 1ATemperature in the unit system set at the factory (I-P or SI).FLOAT32ABCDRead
IR60doc 30061Refrigerant Discharge Temperature - Compressor 1ATemperature in the unit system set at the factory (I-P or SI).FLOAT32ABCDRead
IR62doc 30063Run Time - Compressor 1A (in seconds)FLOAT32ABCDsRead
IR64doc 30065Starts - Compressor 1AFLOAT32ABCDRead
IR66doc 30067Condenser Differential Water PressureNeeds: Cond Water Flow Measurement Differential Pressure or Dual Pressure SensorsFLOAT32ABCDRead
IR68doc 30069Condenser Entering Water TemperatureTemperature in the unit system set at the factory (I-P or SI).FLOAT32ABCDRead
IR70doc 30071Condenser Leaving Water TemperatureTemperature in the unit system set at the factory (I-P or SI).FLOAT32ABCDRead
IR72doc 30073Condenser Refrigerant Pressure Circuit 1Pressure in the factory unit system (I-P or SI).FLOAT32ABCDRead
IR74doc 30075Condenser Saturated Refrigerant Temperature Circuit 1Temperature in the unit system set at the factory (I-P or SI).FLOAT32ABCDRead
IR76doc 30077Differential Refrigerant Pressure Circuit 1Pressure in the factory unit system (I-P or SI).FLOAT32ABCDRead
IR78doc 30079Evaporator Differential Water PressureNeeds: Evap Water Flow Measurement Differential Pressure or Dual Pressure SensorsFLOAT32ABCDRead
IR80doc 30081Evaporator Entering Water TemperatureTemperature in the unit system set at the factory (I-P or SI).FLOAT32ABCDRead
IR82doc 30083Evaporator Leaving Water TemperatureTemperature in the unit system set at the factory (I-P or SI).FLOAT32ABCDRead
IR84doc 30085Evaporator Refrigerant Pressure Circuit 1Pressure in the factory unit system (I-P or SI).FLOAT32ABCDRead
IR86doc 30087Evaporator Saturated Refrigerant Temperature Circuit 1Temperature in the unit system set at the factory (I-P or SI).FLOAT32ABCDRead
IR88doc 30089Entering Condenser Water PressureNeeds: Cond Water Flow Measurement Differential Pressure or Dual Pressure SensorsFLOAT32ABCDRead
IR90doc 30091Leaving Condenser Water PressureNeeds: Cond Water Flow Measurement Differential Pressure or Dual Pressure SensorsFLOAT32ABCDRead
IR92doc 30093Entering Evaporator Water PressureNeeds: Evap Water Flow Measurement Differential Pressure or Dual Pressure SensorsFLOAT32ABCDRead
IR94doc 30095Leaving Evaporator Water PressureNeeds: Evap Water Flow Measurement Differential Pressure or Dual Pressure SensorsFLOAT32ABCDRead
IR96doc 30097Inlet Guide Vane 1 Percent Open Circuit 1FLOAT32ABCD%Read
IR98doc 30099Motor Winding Temperature 1 Circuit 1Temperature in the unit system set at the factory (I-P or SI).FLOAT32ABCDRead
IR100doc 30101Motor Winding Temperature 2 Circuit 1Temperature in the unit system set at the factory (I-P or SI).FLOAT32ABCDRead
IR102doc 30103Motor Winding Temperature 3 Circuit 1Temperature in the unit system set at the factory (I-P or SI).FLOAT32ABCDRead
IR104doc 30105Number of CircuitsFLOAT32ABCDRead
IR106doc 30107Number of Compressors Circuit 1FLOAT32ABCDRead
IR108doc 30109Number of Compressors Circuit 2FLOAT32ABCDRead
IR110doc 30111Refrigerant MonitorNeeds: Refrigerant MonitorFLOAT32ABCDRead
IR112doc 30113Unit Power ConsumptionElectrical power.FLOAT32ABCDRead
IR114doc 30115Drive Input Voltage Calculated 1AVoltage.FLOAT32ABCDRead
IR116doc 30117Actual Running CapacityFLOAT32ABCD%Read
IR118doc 30119Unit Source IDFLOAT32ABCDRead
IR120doc 30121Chiller Design CapacityCooling capacity in the factory unit system (I-P or SI).FLOAT32ABCDRead
IR122doc 30123Outdoor Air TemperatureTemperature in the unit system set at the factory (I-P or SI). Needs: Outdoor Air TempFLOAT32ABCDRead
IR124doc 30125Energy Consumption LifetimeElectrical energy.FLOAT32ABCDRead
IR126doc 30127Energy ConsumptionElectrical energy.FLOAT32ABCDRead
IR128doc 30129Unit Power DemandElectrical power.FLOAT32ABCDRead
IR130doc 30131Voltage L1-L2Voltage. Needs: Energy MeterFLOAT32ABCDRead
IR132doc 30133Voltage L2-L3Voltage. Needs: Energy MeterFLOAT32ABCDRead
IR134doc 30135Voltage L1-L3Voltage. Needs: Energy MeterFLOAT32ABCDRead
IR136doc 30137Current L1Current. Needs: Energy MeterFLOAT32ABCDRead
IR138doc 30139Current L2Current. Needs: Energy MeterFLOAT32ABCDRead
IR140doc 30141Current L3Current. Needs: Energy MeterFLOAT32ABCDRead
IR142doc 30143Line FrequencyNeeds: Energy MeterFLOAT32ABCDRead
IR144doc 30145Power FactorNeeds: Energy MeterFLOAT32ABCDRead
IR146doc 30147Condenser Control OutputNeeds: Condenser Control OutputFLOAT32ABCD%Read
IR148doc 30149Average Voltage L-LVoltage. Needs: Energy MeterFLOAT32ABCDRead
IR150doc 30151Average CurrentCurrent. Needs: Energy MeterFLOAT32ABCDRead
IR152doc 30153Condenser Approach Temperature Circuit 1Temperature difference, factory unit system (I-P or SI).FLOAT32ABCDRead
IR154doc 30155Evaporator Approach Temperature Circuit 1Temperature difference, factory unit system (I-P or SI).FLOAT32ABCDRead
IR180doc 30181Drive Motor Current U RLA Circuit 2Needs: Circuit 2FLOAT32ABCD%Read
IR182doc 30183Drive Motor Current V Circuit 2Current. Needs: Circuit 2FLOAT32ABCDRead
IR184doc 30185Drive Motor Current V RLA Circuit 2Needs: Circuit 2FLOAT32ABCD%Read
IR186doc 30187Drive Motor Current W Circuit 2Current. Needs: Circuit 2FLOAT32ABCDRead
IR188doc 30189Drive Motor Current W RLA Circuit 2Needs: Circuit 2FLOAT32ABCD%Read
IR190doc 30191Drive Output Power Circuit 2Electrical power. Needs: Circuit 2FLOAT32ABCDRead
IR192doc 30193Drive Speed Status Percent Circuit 2Needs: Circuit 2FLOAT32ABCD%Read
IR194doc 30195Compressor Bearing Temperature 1 - Compressor 2ATemperature in the unit system set at the factory (I-P or SI). Needs: Circuit 2FLOAT32ABCDRead
IR196doc 30197Compressor Bearing Temperature 2 - Compressor 2ATemperature in the unit system set at the factory (I-P or SI). Needs: Circuit 2FLOAT32ABCDRead
IR198doc 30199Refrigerant Discharge Temperature - Compressor 2ATemperature in the unit system set at the factory (I-P or SI). Needs: Circuit 2FLOAT32ABCDRead
IR200doc 30201Run Time - Compressor 2ANeeds: Circuit 2FLOAT32ABCDRead
IR202doc 30203Starts - Compressor 2ANeeds: Circuit 2FLOAT32ABCDRead
IR204doc 30205Condenser Refrigerant Pressure Circuit 2Pressure in the factory unit system (I-P or SI). Needs: Circuit 2FLOAT32ABCDRead
IR206doc 30207Condenser Saturated Refrigerant Temperature Circuit 2Temperature in the unit system set at the factory (I-P or SI). Needs: Circuit 2FLOAT32ABCDRead
IR208doc 30209Differential Refrigerant Pressure Circuit 2Pressure in the factory unit system (I-P or SI). Needs: Circuit 2FLOAT32ABCDRead
IR210doc 30211Evaporator Refrigerant Pressure Circuit 2Pressure in the factory unit system (I-P or SI). Needs: Circuit 2FLOAT32ABCDRead
IR212doc 30213Evaporator Saturated Refrigerant Temperature Circuit 2Temperature in the unit system set at the factory (I-P or SI). Needs: Circuit 2FLOAT32ABCDRead
IR214doc 30215Inlet Guide Vane 1 Percent Open Circuit 2Needs: Circuit 2FLOAT32ABCD%Read
IR216doc 30217Motor Winding Temperature 1 Circuit 2Temperature in the unit system set at the factory (I-P or SI). Needs: Circuit 2FLOAT32ABCDRead
IR218doc 30219Motor Winding Temperature 2 Circuit 2Temperature in the unit system set at the factory (I-P or SI). Needs: Circuit 2FLOAT32ABCDRead
IR220doc 30221Motor Winding Temperature 3 Circuit 2Temperature in the unit system set at the factory (I-P or SI). Needs: Circuit 2FLOAT32ABCDRead
IR222doc 30223Drive Input Voltage Calculated 2AVoltage. Needs: Circuit 2FLOAT32ABCDRead
IR240doc 30241Condenser Approach Temperature Circuit 2Temperature difference, factory unit system (I-P or SI). Needs: Circuit 2FLOAT32ABCDRead
IR242doc 30243Evaporator Approach Temperature Circuit 2Temperature difference, factory unit system (I-P or SI). Needs: Circuit 2FLOAT32ABCDRead
IR244doc 30245Condenser Refrigerant Gauge Pressure Circuit 2Pressure in the factory unit system (I-P or SI). Needs: Circuit 2FLOAT32ABCDRead
IR246doc 30247Evaporator Refrigerant Gauge Pressure Circuit 2Pressure in the factory unit system (I-P or SI). Needs: Circuit 2FLOAT32ABCDRead
IR248doc 30249Active Cooling Differential to StartTemperature difference, factory unit system (I-P or SI).FLOAT32ABCDRead
IR250doc 30251Active Cooling Differential to StopTemperature difference, factory unit system (I-P or SI).FLOAT32ABCDRead
IR252doc 30253Active Heating Differential to StartTemperature difference, factory unit system (I-P or SI). Needs: Hot Water ControlFLOAT32ABCDRead
IR254doc 30255Active Heating Differential to StopTemperature difference, factory unit system (I-P or SI). Needs: Hot Water ControlFLOAT32ABCDRead
IR256doc 30257Discharge Superheat Compressor 1ATemperature difference, factory unit system (I-P or SI).FLOAT32ABCDRead
IR258doc 30259Discharge Superheat Compressor 2ATemperature difference, factory unit system (I-P or SI). Needs: Circuit 2FLOAT32ABCDRead
IR2010doc 32011Operating ModeUINT16Read1 = Cool; 2 = Heat; 3 = Ice Making; 4 = Free Cooling
IR2011doc 32012Running ModeUINT16Read1 = Chiller Off; 2 = Chiller In Start Mode; 3 = Chiller In Run Mode; 4 = Chiller In Pre-Shutdown Mode; 5 = Chiller In Service Mode
IR2012doc 32013Manufacturing LocationUINT16Read2 = La Crosse
IR2013doc 32014Chiller Setpoint SourceUINT16Read1 = BAS; 2 = External; 3 = Front Panel
IR2014doc 32015Refrigerant TypeUINT16Read5 = R-134a; 13 = R-513A; 16 = R-1234ze(E); 18 = R-515B
IR2015doc 32016Cooling TypeUINT16Read1 = Water Cooled
IR2016doc 32017Model Information [GEN2]UINT16Read25 = HDWA; 66 = HDDA
IR3010doc 33011Diagnostic PresentUINT16Read0 = Normal; 1 = In Alarm
IR3011doc 33012Diagnostic Shutdown PresentUINT16Read0 = Normal; 1 = In Alarm
IR3012doc 33013Diagnostic: Manual Reset RequiredUINT16Read0 = Normal; 1 = In Alarm
IR3013doc 33014Diagnostic: Local Manual Reset RequiredUINT16Read0 = Normal; 1 = In Alarm
IR3014doc 33015Diagnostic Present: InformationUINT16Read0 = Normal; 1 = In Alarm
IR3015doc 33016Diagnostic Present: AdvisoryUINT16Read0 = Normal; 1 = In Alarm
IR3016doc 33017Diagnostic Present: CriticalUINT16Read0 = Normal; 1 = In Alarm
IR3017doc 33018Diagnostic Present: Service RequiredUINT16Read0 = Normal; 1 = In Alarm
IR3018doc 33019Base Loading ActiveNeeds: Base LoadingUINT16Read0 = Inactive; 1 = Active
IR3019doc 33020Chiller Running StateUINT16Read0 = Off; 1 = On
IR3020doc 33021Condenser Water Flow StatusUINT16Read0 = No Flow; 1 = Flow
IR3021doc 33022Condenser Water Pump RequestUINT16Read0 = Off; 1 = On
IR3022doc 33023Emergency StopUINT16Read0 = Auto; 1 = Emergency Stop - Manual Reset Required
IR3023doc 33024Evaporator Water Flow StatusUINT16Read0 = No Flow; 1 = Flow
IR3024doc 33025Evaporator Water Pump RequestUINT16Read0 = Off; 1 = On
IR3025doc 33026Base Loading Request ActiveNeeds: Base LoadingUINT16Read0 = Off; 1 = On
IR3026doc 33027Head Relief RequestUINT16Read0 = Off; 1 = On
IR3027doc 33028Limit Mode Relay StatusUINT16Read0 = Off; 1 = On
IR3028doc 33029Local Setpoint ControlUINT16Read0 = Remote Control; 1 = Local Control
IR3029doc 33030Manual Override ExistsUINT16Read0 = Off; 1 = On
IR3030doc 33031Maximum CapacityUINT16Read0 = Off; 1 = On
IR3031doc 33032Run EnabledUINT16Read0 = Run Not Enabled; 1 = Run Enabled
IR3032doc 33033Compressor 1A StatusUINT16Read0 = Off; 1 = Running
IR3033doc 33034Front Panel Auto StopUINT16Read0 = Stop; 1 = Auto
IR3034doc 33035External Auto Stop Input StatusUINT16Read0 = Stop; 1 = Auto
IR3035doc 33036Compressor 2A StatusNeeds: Circuit 2UINT16Read0 = Off; 1 = Running
IR4000doc 34001Comm Loss: Ext Base Loading CommandDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4001doc 34002Comm Loss: Ext Base Loading SetpointDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4002doc 34003Diagnostic: External Base Loading SetpointDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4003doc 34004Comm Loss: Energy MeterDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4004doc 34005Comm Loss: Outdoor Air TemperatureDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4005doc 34006Diagnostic: Energy Meter Write Command FailureDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4006doc 34007Diagnostic: Outdoor Air Temperature SensorDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4007doc 34008Diagnostic: Software Error 1001: Call Trane ServiceDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4008doc 34009Diagnostic: Software Error 1002: Call Trane ServiceDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4009doc 34010Diagnostic: Software Error 1003: Call Trane ServiceDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4010doc 34011Comm Loss: Condenser Liquid Level Sensor Circuit 1Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4011doc 34012Comm Loss: Condenser Rfgt Pressure Circuit 1Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4012doc 34013Comm Loss: Drive Cooling Supply Temperature Circuit 1Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4013doc 34014Comm Loss: Drive Cooling Valve Circuit 1Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4014doc 34015Comm Loss: Evaporator Refrigerant Pressure Circuit 1Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4015doc 34016Diagnostic: Condenser Liquid Level Sensor Circuit 1Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4016doc 34017Diagnostic: Condenser Refrigerant Pressure Sensor Circuit 1Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4017doc 34018Diagnostic: Drive Cooling Supply Temperature Sensor Circuit 1Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4018doc 34019Diagnostic: Evaporator Refrigerant Pressure Sensor Circuit 1Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4019doc 34020Diagnostic: High Condenser Liquid Level Circuit 1Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4020doc 34021Diagnostic: Low Condenser Liquid Level Circuit 1Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4021doc 34022Diagnostic: Inverted Condenser Approach TemperatureDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4022doc 34023Diagnostic: Inverted Evaporator Approach TemperatureDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4023doc 34024Diagnostic: Loss of Drive Cooling Control Circuit 1Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4024doc 34025Diagnostic: Loss of Evaporator EXV Control Circuit 1Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4025doc 34026Diagnostic: Low Evaporator Refrigerant Temperature Circuit 1Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4026doc 34027Comm Loss: Cprsr Discharge Rfgt Temp Circuit 1Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4027doc 34028Comm Loss: Economizer Valve Circuit 1Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4028doc 34029Comm Loss: Economizer Pressure Circuit 1Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4029doc 34030Comm Loss: Economizer Temperature Circuit 1Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4030doc 34031Comm Loss: IGV First Stage Actuator Circuit 1Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4031doc 34032Comm Loss: Interstage Bypass Valve Circuit 1Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4032doc 34033Diagnostic: Compressor Refrigerant Discharge Temperature Sensor Circuit 1Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4033doc 34034Diagnostic: Economizer Pressure Sensor Circuit 1Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4034doc 34035Diagnostic: Economizer Temperature Sensor Circuit 1Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4035doc 34036Diagnostic: Extended Compressor Surge Circuit 1Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4036doc 34037Diagnostic: Condenser Water Flow LostDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4037doc 34038Diagnostic: Condenser Water Flow OverdueDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4038doc 34039Diagnostic: High Condenser Pressure Circuit 1Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4039doc 34040Comm Loss: Condenser Entering Water PressureDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4040doc 34041Comm Loss: Condenser Entering Water TempDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4041doc 34042Comm Loss: Condenser Leaving Water PressureDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4042doc 34043Comm Loss: Condenser Leaving Water TempDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4043doc 34044Comm Loss: Condenser Water Flow Measurement SensorDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4044doc 34045Comm Loss: Condenser Water Flow SwitchDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4045doc 34046Comm Loss: Condenser Water Pump RelayDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4046doc 34047Diagnostic: Condenser Entering Water PressureDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4047doc 34048Diagnostic: Condenser Entering Water Temp SensorDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4048doc 34049Diagnostic: Condenser Leaving Water PressureDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4049doc 34050Diagnostic: Condenser Leaving Water Temp SensorDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4050doc 34051Diagnostic: Condenser Water Flow Measurement SensorDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4051doc 34052Diagnostic: Inverted Condenser Water TemperatureDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4052doc 34053Diagnostic: Evaporator Water Flow LostDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4053doc 34054Diagnostic: Evaporator Water Flow OverdueDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4054doc 34055Diagnostic: High Evaporator Refrigerant PressureDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4055doc 34056Diagnostic: High Evaporator Water TemperatureDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4056doc 34057Diagnostic: Low Evaporator Water FlowDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4057doc 34058Comm Loss: Evap Entering Water TempDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4058doc 34059Comm Loss: Evap Leaving Water TempDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4059doc 34060Comm Loss: Evaporator Entering Water PressureDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4060doc 34061Comm Loss: Evaporator Leaving Water PressureDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4061doc 34062Comm Loss: Evaporator Water Flow Measurement SensorDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4062doc 34063Comm Loss: Evaporator Water Flow SwitchDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4063doc 34064Comm Loss: Evaporator Water Pump RelayDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4064doc 34065Diagnostic: Evaporator Entering Water PressureDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4065doc 34066Diagnostic: Evaporator Entering Water Temp SensorDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4066doc 34067Diagnostic: Evaporator Leaving Water PressureDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4067doc 34068Diagnostic: Evaporator Leaving Water Temp SensorDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4068doc 34069Diagnostic: Evaporator Water Flow Measurement SensorDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4069doc 34070Diagnostic: Inverted Evaporator Water TemperatureDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4070doc 34071Diagnostic: Low Evap Leaving Water Temp: Unit OffDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4071doc 34072Diagnostic: Low Evap Leaving Water Temp: Unit OnDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4072doc 34073Comm Loss: Evaporator EXV Circuit 1Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4073doc 34074Comm Loss: Chiller % Capacity OutputDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4074doc 34075Comm Loss: Condenser Rfgt Pressure OutputDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4075doc 34076Comm Loss: Emergency StopDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4076doc 34077Comm Loss: Ext Chilled/Hot Water SetpointDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4077doc 34078Comm Loss: Ext Demand Limit SetpointDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4078doc 34079Comm Loss: External Auto/StopDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4079doc 34080Comm Loss: External Hot Water CommandDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4080doc 34081Comm Loss: Programmable Relay Board 1Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4081doc 34082Comm Loss: Programmable Relay Board 2Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4082doc 34083Diagnostic: Emergency StopDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4083doc 34084Diagnostic: External Chilled/Hot Water SetpointDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4084doc 34085Diagnostic: External Demand Limit SetpointDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4085doc 34086Comm Loss: Refrigerant Monitor InputDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4086doc 34087Diagnostic: Refrigerant Monitor InputDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4087doc 34088Comm Loss: External Ice Building CommandDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4088doc 34089Comm Loss: Ice Building Status RelayDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4089doc 34090Diagnostic: MBC Bearing Temperature 1 Circuit 1Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4090doc 34091Diagnostic: MBC Bearing Temperature 2 Circuit 1Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4091doc 34092Diagnostic: MBC Failed Centering Circuit 1Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4092doc 34093Comm Loss: MBC Cooling Valve Circuit 1Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4093doc 34094Comm Loss: Magnetic Bearing Controller Circuit 1Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4094doc 34095Comm Loss: UPS Fault Circuit 1Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4095doc 34096Diagnostic: Loss of MBC Cooling Control Circuit 1Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4096doc 34097Diagnostic: MBC Not Centered Circuit 1Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4097doc 34098Diagnostic: MBC Not Ready To Rotate Circuit 1Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4098doc 34099Diagnostic: MBC Over Voltage Circuit 1Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4099doc 34100Diagnostic: MBC Parameter Table Not Set Circuit 1Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4100doc 34101Diagnostic: MBC Rotor Elongation Circuit 1Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4101doc 34102Diagnostic: MBC Rotor Unbalance Alarm Circuit 1Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4102doc 34103Diagnostic: MBC: Shutdown Request Circuit 1Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4103doc 34104Diagnostic: MBC Under Voltage Circuit 1Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4104doc 34105Diagnostic: MBC Overspeed Circuit 1Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4105doc 34106Diagnostic: MBC PCB Temperature Circuit 1Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4106doc 34107Diagnostic: MBC Rotation Detected Without Levitation Circuit 1Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4107doc 34108Diagnostic: MBC Speed Sensor Circuit 1Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4108doc 34109Diagnostic: UPS Fault Circuit 1Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4109doc 34110Comm Loss: Motor Cooling Valve Circuit 1Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4110doc 34111Comm Loss: Motor Winding Temperature 1 Circuit 1Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4111doc 34112Comm Loss: Motor Winding Temperature 2 Circuit 1Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4112doc 34113Comm Loss: Motor Winding Temperature 3 Circuit 1Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4113doc 34114Diagnostic: High Compressor Refrigerant Discharge Temperature Circuit 1Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4114doc 34115Diagnostic: High Motor Winding Temperature 1 Circuit 1Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4115doc 34116Diagnostic: High Motor Winding Temperature 2 Circuit 1Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4116doc 34117Diagnostic: High Motor Winding Temperature 3 Circuit 1Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4117doc 34118Diagnostic: High Vacuum Lockout Circuit 1Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4118doc 34119Diagnostic: Loss of Motor Cooling Control Circuit 1Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4119doc 34120Diagnostic: Motor Winding Temperature 1 Sensor Circuit 1Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4120doc 34121Diagnostic: Motor Winding Temperature 2 Sensor Circuit 1Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4121doc 34122Diagnostic: Motor Winding Temperature 3 Sensor Circuit 1Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4122doc 34123Diagnostic: MP: Invalid ConfigurationDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4123doc 34124Diagnostic: MP: Reset Has OccurredDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4124doc 34125Diagnostic: AFD Comm Loss: Main Processor Circuit 1Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4125doc 34126Diagnostic: AFD Failure to Arm or Start Circuit 1Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4126doc 34127Diagnostic: AFD Fault Circuit 1Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4127doc 34128Diagnostic: AFD Ground Fault Circuit 1Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4128doc 34129Diagnostic: AFD Interrupt Failure Circuit 1Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4129doc 34130Diagnostic: AFD Mains Failure Circuit 1Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4130doc 34131Diagnostic: AFD Motor Current Overload Circuit 1Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4131doc 34132Diagnostic: AFD Safe Stop Circuit 1Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4132doc 34133Diagnostic: AFD Short Circuit Circuit 1Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4133doc 34134Diagnostic: AFD Speed Configuration Mismatch Circuit 1Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4134doc 34135Comm Loss: Adaptive Frequency Drive Circuit 1Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4135doc 34136Diagnostic: Unexpected Starter Shutdown Circuit 1Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4136doc 34137Diagnostic: Software Error 1005: Call Trane ServiceDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4137doc 34138Comm Loss: Starter Panel High Temp Limit Compressor 1ADiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4138doc 34139Diagnostic: Starter Panel High Temp Limit Compressor 1ADiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4139doc 34140Comm Loss: Subcooled Liquid Temp Circuit 1Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4140doc 34141Comm Loss: External Ckt Lockout Circuit 1Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4141doc 34142Diagnostic: Subcooled Liquid Temperature Sensor Circuit 1Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4142doc 34143Diagnostic: Evaporator Saturated Refrigerant Temp Sensor Circuit 1Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4143doc 34144Comm Loss: Evap Saturated Rfgt Temp Circuit 1Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4144doc 34145Diagnostic: Low Suction Refrigerant Pressure Circuit 1Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4145doc 34146Diagnostic: High Differential Refrigerant Pressure Circuit 1Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4146doc 34147Diagnostic: High Refrigerant Pressure Ratio Circuit 1Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4147doc 34148Diagnostic: Starts/Hours Modified Compressor 1ADiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4148doc 34149Diagnostic: Starts/Hours Modified Compressor 2ADiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4149doc 34150Diagnostic: High Evaporator Refrigerant Temperature Circuit 1Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4150doc 34151Comm Loss: Off-cycle Freeze Protection Relay Circuit 1Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4151doc 34152Comm Loss: Condenser Head Pressure Cntrl Output Circuit 1Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4152doc 34153Comm Loss: Ext Noise Reduction Request Circuit 1Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4153doc 34154Diagnostic: MBC Failed Clearance Check Circuit 1Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4154doc 34155Diagnostic: Check ClockDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4155doc 34156Diagnostic: MP: Non-Volatile Block Test ErrorDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4156doc 34157Diagnostic: Under Voltage Circuit 1Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4157doc 34158Diagnostic: Over Voltage Circuit 1Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4158doc 34159Compressor 2A StatusDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4159doc 34160Comm Loss: Condenser Liquid Level Sensor Circuit 2Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4160doc 34161Comm Loss: Condenser Rfgt Pressure Circuit 2Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4161doc 34162Comm Loss: Drive Cooling Supply Temperature Circuit 2Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4162doc 34163Comm Loss: Drive Cooling Supply Temperature Circuit 2Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4163doc 34164Comm Loss: Drive Cooling Valve Circuit 2Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4164doc 34165Comm Loss: Evaporator Refrigerant Pressure Circuit 2Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4165doc 34166Diagnostic: Condenser Liquid Level Sensor Circuit 2Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4166doc 34167Diagnostic: Condenser Refrigerant Pressure Sensor Circuit 2Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4167doc 34168Diagnostic: Drive Cooling Supply Temperature Sensor Circuit 2Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4168doc 34169Diagnostic: Evaporator Refrigerant Pressure Sensor Circuit 2Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4169doc 34170Diagnostic: High Condenser Liquid Level Circuit 2Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4170doc 34171Diagnostic: Low Condenser Liquid Level Circuit 2Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4171doc 34172Diagnostic: Loss of Drive Cooling Control Circuit 2Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4172doc 34173Diagnostic: Loss of Evaporator EXV Control Circuit 2Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4173doc 34174Diagnostic: Low Evaporator Refrigerant Temperature Circuit 2Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4174doc 34175Comm Loss: Cprsr Discharge Rfgt Temp Circuit 2Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4175doc 34176Comm Loss: Economizer Valve Circuit 2Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4176doc 34177Comm Loss: Economizer Pressure Circuit 2Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4177doc 34178Comm Loss: Economizer Temperature Circuit 2Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4178doc 34179Comm Loss: IGV First Stage Actuator Circuit 2Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4179doc 34180Comm Loss: Interstage Bypass Valve Circuit 2Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4180doc 34181Diagnostic: Compressor Refrigerant Discharge Temperature Sensor Circuit 2Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4181doc 34182Diagnostic: Economizer Pressure Sensor Circuit 2Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4182doc 34183Diagnostic: Economizer Temperature Sensor Circuit 2Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4183doc 34184Diagnostic: Extended Compressor Surge Circuit 2Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4184doc 34185Diagnostic: High Condenser Pressure Circuit 2Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4185doc 34186Comm Loss: Evaporator EXV Circuit 2Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4186doc 34187Diagnostic: MBC Bearing Temperature 1 Circuit 2Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4187doc 34188Diagnostic: MBC Bearing Temperature 2 Circuit 2Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4188doc 34189Diagnostic: MBC Failed Centering Circuit 2Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4189doc 34190Comm Loss: MBC Cooling Valve Circuit 2Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4190doc 34191Comm Loss: Magnetic Bearing Controller Circuit 2Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4191doc 34192Comm Loss: UPS Fault Circuit 2Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4192doc 34193Diagnostic: Loss of MBC Cooling Control Circuit 2Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4193doc 34194Diagnostic: MBC Not Centered Circuit 2Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4194doc 34195Diagnostic: MBC Not Ready To Rotate Circuit 2Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4195doc 34196Diagnostic: MBC Over Voltage Circuit 2Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4196doc 34197Diagnostic: MBC Parameter Table Not Set Circuit 2Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4197doc 34198Diagnostic: MBC Rotor Elongation Circuit 2Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4198doc 34199Diagnostic: MBC Rotor Unbalance Alarm Circuit 2Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4199doc 34200Diagnostic: MBC: Shutdown Request Circuit 2Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4200doc 34201Diagnostic: MBC Under Voltage Circuit 2Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4201doc 34202Diagnostic: MBC Overspeed Circuit 2Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4202doc 34203Diagnostic: MBC PCB Temperature Circuit 2Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4203doc 34204Diagnostic: MBC Rotation Detected Without Levitation Circuit 2Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4204doc 34205Diagnostic: MBC Speed Sensor Circuit 2Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4205doc 34206Diagnostic: UPS Fault Circuit 2Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4206doc 34207Comm Loss: Motor Cooling Valve Circuit 2Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4207doc 34208Comm Loss: Motor Winding Temperature 1 Circuit 2Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4208doc 34209Comm Loss: Motor Winding Temperature 2 Circuit 2Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4209doc 34210Comm Loss: Motor Winding Temperature 3 Circuit 2Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4210doc 34211Diagnostic: High Compressor Refrigerant Discharge Temperature Circuit 2Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4211doc 34212Diagnostic: High Motor Winding Temperature 1 Circuit 2Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4212doc 34213Diagnostic: High Motor Winding Temperature 2 Circuit 2Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4213doc 34214Diagnostic: High Motor Winding Temperature 3 Circuit 2Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4214doc 34215Diagnostic: High Vacuum Lockout Circuit 2Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4215doc 34216Diagnostic: Loss of Motor Cooling Control Circuit 2Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4216doc 34217Diagnostic: Motor Winding Temperature 1 Sensor Circuit 2Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4217doc 34218Diagnostic: Motor Winding Temperature 2 Sensor Circuit 2Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4218doc 34219Diagnostic: Motor Winding Temperature 3 Sensor Circuit 2Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4219doc 34220Diagnostic: AFD Comm Loss: Main Processor Circuit 2Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4220doc 34221Diagnostic: AFD Failure to Arm or Start Circuit 2Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4221doc 34222Diagnostic: AFD Fault Circuit 2Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4222doc 34223Diagnostic: AFD Ground Fault Circuit 2Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4223doc 34224Diagnostic: AFD Interrupt Failure Circuit 2Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4224doc 34225Diagnostic: AFD Mains Failure Circuit 2Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4225doc 34226Diagnostic: AFD Motor Current Overload Circuit 2Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4226doc 34227Diagnostic: AFD Safe Stop Circuit 2Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4227doc 34228Diagnostic: AFD Short Circuit Circuit 2Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4228doc 34229Diagnostic: AFD Speed Configuration Mismatch Circuit 2Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4229doc 34230Comm Loss: Adaptive Frequency Drive Circuit 2Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4230doc 34231Diagnostic: Unexpected Starter Shutdown Circuit 2Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4231doc 34232Comm Loss: Starter Panel High Temp Limit Compressor 2ADiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4232doc 34233Diagnostic: Starter Panel High Temp Limit Compressor 2ADiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4233doc 34234Comm Loss: Subcooled Liquid Temp Circuit 2Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4234doc 34235Comm Loss: External Ckt Lockout Circuit 2Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4235doc 34236Diagnostic: Subcooled Liquid Temperature Sensor Circuit 2Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4236doc 34237Diagnostic: Evaporator Saturated Refrigerant Temp Sensor Circuit 2Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4237doc 34238Comm Loss: Evap Saturated Rfgt Temp Circuit 2Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4238doc 34239Diagnostic: Low Suction Refrigerant Pressure Circuit 2Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4239doc 34240Diagnostic: High Differential Refrigerant Pressure Circuit 2Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4240doc 34241Diagnostic: High Refrigerant Pressure Ratio Circuit 2Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4241doc 34242Diagnostic: High Evaporator Refrigerant Temperature Circuit 2Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4242doc 34243Comm Loss: Off-cycle Freeze Protection Relay Circuit 2Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4243doc 34244Comm Loss: Condenser Head Pressure Cntrl Output Circuit 2Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4244doc 34245Comm Loss: Ext Noise Reduction Request Circuit 2Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4245doc 34246Diagnostic: MBC Failed Clearance Check Circuit 2Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4246doc 34247Diagnostic: Under Voltage Circuit 2Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4247doc 34248Diagnostic: Over Voltage Circuit 2Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4248doc 34249Comm Loss: IGV Second Stage Actuator Circuit 1Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4249doc 34250Comm Loss: IGV Second Stage Actuator Circuit 2Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4250doc 34251Comm Loss: Condenser Liquid Line Temperature Circuit 1Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4251doc 34252Diagnostic: Condenser Liquid Line Temperature Sensor Circuit 1Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4252doc 34253Comm Loss: Condenser Liquid Line Temperature Circuit 2Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4253doc 34254Diagnostic: Condenser Liquid Line Temperature Sensor Circuit 2Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4254doc 34255Diagnostic: High Evaporator Refrigerant Pressure Circuit 2Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4255doc 34256Diagnostic: Inverted Condenser Approach Temperature Circuit 2Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4256doc 34257Diagnostic: Inverted Evaporator Approach Temperature Circuit 2Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
HR10doc 40011Chilled Water SetpointTemperature in the unit system set at the factory (I-P or SI).FLOAT32ABCDRead/write
HR12doc 40013Demand Limit SetpointFLOAT32ABCD%Read/write
HR14doc 40015Hot Water SetpointTemperature in the unit system set at the factory (I-P or SI). Needs: Hot Water ControlFLOAT32ABCDRead/write
HR16doc 40017Base Loading SetpointNeeds: Base LoadingFLOAT32ABCD%Read/write
HR18doc 40019BAS Cooling Differential to StartTemperature difference, factory unit system (I-P or SI).FLOAT32ABCDRead/write
HR20doc 40021BAS Cooling Differential to StopTemperature difference, factory unit system (I-P or SI).FLOAT32ABCDRead/write
HR22doc 40023BAS Heating Differential to StartTemperature difference, factory unit system (I-P or SI). Needs: Hot Water ControlFLOAT32ABCDRead/write
HR24doc 40025BAS Heating Differential to StopTemperature difference, factory unit system (I-P or SI). Needs: Hot Water ControlFLOAT32ABCDRead/write
HR2010doc 42011Chiller Mode Command BASUINT16Read/write1 = Cool; 2 = Heat; 3 = Ice Making; 4 = Free Cooling
HR3010doc 43011Base Loading RequestNeeds: Base LoadingUINT16Read/write0 = Off; 1 = On
HR3011doc 43012Reset DiagnosticUINT16Read/write0 = Normal; 1 = Reset
HR3012doc 43013Chiller Auto Stop Command BASUINT16Read/write0 = Stop; 1 = Auto
HR3013doc 43014Energy Consumption ResetUINT16Read/write0 = Accumulating; 1 = Reset
HR3014doc 43015Evaporator Water Pump Request BASUINT16Read/write1 = On
HR3015doc 43016Condenser Water Pump Request BASUINT16Read/write1 = On
HR3016doc 43017Circuit 1 Lockout BASUINT16Read/write1 = On
HR3017doc 43018Circuit 2 Lockout BASNeeds: Circuit 2UINT16Read/write1 = On

Notes on this map

Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.

Questions about the Trane Agility water-cooled centrifugal chiller (Symbio 800)

What Modbus registers does the Trane Agility water-cooled centrifugal chiller (Symbio 800) have?

This map lists 412 registers: 395 input registers, 17 holding registers. 17 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.

Are the Trane Agility water-cooled centrifugal chiller (Symbio 800) Modbus addresses 0-based or 1-based?

The manufacturer's document numbers registers Modicon 3xxxx/4xxxx (drop the prefix, subtract 1). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. The list prints Modicon register numbers: 3xxxx are input registers and 4xxxx holding registers, so 30011 is input register address 10 and 42011 is holding register address 2010.

What byte order does the Trane Agility water-cooled centrifugal chiller (Symbio 800) use for 32-bit values?

Multi-register values in this map use ABCD (high word first (big-endian)). Set your client to this order for every 32/64-bit value in the table.

What are the minimum Modbus registers to integrate the Trane Agility water-cooled centrifugal chiller (Symbio 800)?

Start with IR 10 Active Chilled Water Setpoint (Active chilled water setpoint); IR 22 Chilled Water Setpoint Status (Chilled water setpoint status); IR 48 Drive Speed Status Percent (Drive speed %); IR 3019 Chiller Running State (Chiller running state); IR 3010 Diagnostic Present (Diagnostic present); HR 10 Chilled Water Setpoint (Chilled water setpoint (BAS)); HR 2010 Chiller Mode Command BAS (Chiller mode command); HR 3010 Base Loading Request (Base loading request).

How do I enable Modbus control of the Trane Agility water-cooled centrifugal chiller (Symbio 800)?

On the Symbio 800 web interface (USB connection) go to Installation > Identification and Communications > Protocol Configuration and select Modbus RTU or Modbus TCP; for TCP set the IP address on the IP Configuration tab.

Where is the official Trane Agility water-cooled centrifugal chiller (Symbio 800) Modbus documentation?

The source is Symbio 800 Integration Points List, BACnet/Modbus, Agility Water-Cooled Chillers (BAS-PTS007C-EN), revision 2026-06-30, published free by Trane at https://elibrary.tranetechnologies.com/public/commercial-hvac/Literature/Points%20List/BAS-PTS007C-EN_06302026.pdf.

More Trane Modbus register maps

Other chillers & heat pumps register maps

All chillers & heat pumps Modbus register maps →

Source: Symbio 800 Integration Points List, BACnet/Modbus, Agility Water-Cooled Chillers · BAS-PTS007C-EN · rev. 2026-06-30. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.