Chiller · Modbus register map
Trane Agility water-cooled centrifugal chiller (Symbio 800) Modbus register map
Updated 17 November 2026
Trane's Agility is a compact water-cooled centrifugal chiller with an adaptive-frequency drive. Its Symbio 800 controller serves BACnet and Modbus RTU/TCP from one points list. This map covers the analog inputs (setpoints, drive values, flows, temperatures, pressures, energy meter), BAS setpoints, binary status and diagnostic flags and the multi-state mode points.
This page lists 412 Modbus registers for the Trane Agility water-cooled centrifugal chiller (Symbio 800) — 17 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Trane’s own free documentation (linked below) and checked against it.
- Manufacturer
- Trane
- Model
- Agility water-cooled centrifugal chiller (Symbio 800)
- Equipment type
- Chiller
- Registers
- 412 (17 writable)
- Transport
- Modbus RTU, Modbus TCP
- Default unit ID
- Not stated
- Default serial
- 19200 baud, 8E1
- Documented addressing
- Modicon 3xxxx/4xxxx (drop the prefix, subtract 1)
- 32-bit word order
- ABCD high word first (big-endian)
- Also known as
- Agility, HDWA, Agility water-cooled chiller
Integration notes: Trane Agility water-cooled centrifugal chiller (Symbio 800)
Read the analog inputs as pairs of input registers (float, high word first) and the binary/multi-state points as single registers. Write the BAS setpoints and command points in the 4xxxx holding range.
Minimum registers to map
Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.
| Register | Name | Type | Why | Access |
|---|---|---|---|---|
| IR 10 | Active Chilled Water Setpoint | FLOAT32 ABCD | Active chilled water setpoint | Read |
| IR 22 | Chilled Water Setpoint Status | FLOAT32 ABCD | Chilled water setpoint status | Read |
| IR 48 | Drive Speed Status Percent | FLOAT32 ABCD | Drive speed % | Read |
| IR 3019 | Chiller Running State | UINT16 | Chiller running state | Read |
| IR 3010 | Diagnostic Present | UINT16 | Diagnostic present | Read |
| HR 10 | Chilled Water Setpoint | FLOAT32 ABCD | Chilled water setpoint (BAS) | Read/write |
| HR 2010 | Chiller Mode Command BAS | UINT16 | Chiller mode command | Read/write |
| HR 3010 | Base Loading Request | UINT16 | Base loading request | Read/write |
Enable Modbus control & writes
On the Symbio 800 web interface (USB connection) go to Installation > Identification and Communications > Protocol Configuration and select Modbus RTU or Modbus TCP; for TCP set the IP address on the IP Configuration tab.
Byte order & addressing
- Analog values are 32-bit floats in two consecutive registers, high word first.
- 0xFFFF in a binary or multi-state register and NaN in an analog register mean the value is invalid.
Network setup
- The Modbus RTU address comes from the controller's rotary dials (001-247); 000 disables Modbus RTU. A change takes effect without a power cycle.
- Modbus TCP uses Ethernet port 1 (port 2 is reserved for the optional touch screen); the rotary address is not used for TCP and the Wi-Fi module does not support Modbus TCP.
Watch out for
- Points not supported by the unit's configuration are absent; confirm the configuration dependencies before mapping.
Trane Agility water-cooled centrifugal chiller (Symbio 800) Modbus registers
Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.
| Table | Address | Name | Description | Type | Order | Scale | Units | Access | Values / bits |
|---|---|---|---|---|---|---|---|---|---|
| IR | 10doc 30011 | Active Chilled Water Setpoint | Temperature in the unit system set at the factory (I-P or SI). | FLOAT32 | ABCD | Read | |||
| IR | 12doc 30013 | Active Base Loading Setpoint | Needs: Base Loading | FLOAT32 | ABCD | % | Read | ||
| IR | 14doc 30015 | Active Cool/Heat Setpoint Temperature | Temperature in the unit system set at the factory (I-P or SI). | FLOAT32 | ABCD | Read | |||
| IR | 16doc 30017 | Active Hot Water Setpoint | Temperature in the unit system set at the factory (I-P or SI). Needs: Hot Water Control | FLOAT32 | ABCD | Read | |||
| IR | 18doc 30019 | Active Demand Limit Setpoint | FLOAT32 | ABCD | % | Read | |||
| IR | 20doc 30021 | Demand Limit Setpoint Status | Needs: Ice Building | FLOAT32 | ABCD | % | Read | ||
| IR | 22doc 30023 | Chilled Water Setpoint Status | Temperature in the unit system set at the factory (I-P or SI). | FLOAT32 | ABCD | Read | |||
| IR | 24doc 30025 | Drive Motor Average Current RLA Circuit 1 | FLOAT32 | ABCD | % | Read | |||
| IR | 26doc 30027 | Drive Motor Voltage | Voltage. | FLOAT32 | ABCD | Read | |||
| IR | 28doc 30029 | Drive DC Bus Voltage Circuit 1 | Voltage. | FLOAT32 | ABCD | Read | |||
| IR | 30doc 30031 | AFD Frequency Circuit 1 | FLOAT32 | ABCD | Read | ||||
| IR | 32doc 30033 | AFD Transistor Temperature Circuit 1 | Temperature in the unit system set at the factory (I-P or SI). | FLOAT32 | ABCD | Read | |||
| IR | 34doc 30035 | Drive Motor Current U Circuit 1 | Current. | FLOAT32 | ABCD | Read | |||
| IR | 36doc 30037 | Drive Motor Current U RLA Circuit 1 | FLOAT32 | ABCD | % | Read | |||
| IR | 38doc 30039 | Drive Motor Current V Circuit 1 | Current. | FLOAT32 | ABCD | Read | |||
| IR | 40doc 30041 | Drive Motor Current V RLA Circuit 1 | FLOAT32 | ABCD | % | Read | |||
| IR | 42doc 30043 | Drive Motor Current W Circuit 1 | Current. | FLOAT32 | ABCD | Read | |||
| IR | 44doc 30045 | Drive Motor Current W RLA Circuit 1 | FLOAT32 | ABCD | % | Read | |||
| IR | 46doc 30047 | Drive Output Power Circuit 1 | Electrical power. | FLOAT32 | ABCD | Read | |||
| IR | 48doc 30049 | Drive Speed Status Percent | FLOAT32 | ABCD | % | Read | |||
| IR | 50doc 30051 | Condenser Water Flow Rate | Flow in the factory unit system (I-P or SI). Needs: Cond Water Flow Measurement | FLOAT32 | ABCD | Read | |||
| IR | 52doc 30053 | Evaporator Water Flow Rate | Flow in the factory unit system (I-P or SI). Needs: Evap Water Flow Measurement | FLOAT32 | ABCD | Read | |||
| IR | 54doc 30055 | Calculated Chiller Capacity | Cooling capacity in the factory unit system (I-P or SI). Needs: Evap Water Flow Measurement | FLOAT32 | ABCD | Read | |||
| IR | 56doc 30057 | Compressor Bearing Temperature 1 - Compressor 1A | Temperature in the unit system set at the factory (I-P or SI). | FLOAT32 | ABCD | Read | |||
| IR | 58doc 30059 | Compressor Bearing Temperature 2 - Compressor 1A | Temperature in the unit system set at the factory (I-P or SI). | FLOAT32 | ABCD | Read | |||
| IR | 60doc 30061 | Refrigerant Discharge Temperature - Compressor 1A | Temperature in the unit system set at the factory (I-P or SI). | FLOAT32 | ABCD | Read | |||
| IR | 62doc 30063 | Run Time - Compressor 1A (in seconds) | FLOAT32 | ABCD | s | Read | |||
| IR | 64doc 30065 | Starts - Compressor 1A | FLOAT32 | ABCD | Read | ||||
| IR | 66doc 30067 | Condenser Differential Water Pressure | Needs: Cond Water Flow Measurement Differential Pressure or Dual Pressure Sensors | FLOAT32 | ABCD | Read | |||
| IR | 68doc 30069 | Condenser Entering Water Temperature | Temperature in the unit system set at the factory (I-P or SI). | FLOAT32 | ABCD | Read | |||
| IR | 70doc 30071 | Condenser Leaving Water Temperature | Temperature in the unit system set at the factory (I-P or SI). | FLOAT32 | ABCD | Read | |||
| IR | 72doc 30073 | Condenser Refrigerant Pressure Circuit 1 | Pressure in the factory unit system (I-P or SI). | FLOAT32 | ABCD | Read | |||
| IR | 74doc 30075 | Condenser Saturated Refrigerant Temperature Circuit 1 | Temperature in the unit system set at the factory (I-P or SI). | FLOAT32 | ABCD | Read | |||
| IR | 76doc 30077 | Differential Refrigerant Pressure Circuit 1 | Pressure in the factory unit system (I-P or SI). | FLOAT32 | ABCD | Read | |||
| IR | 78doc 30079 | Evaporator Differential Water Pressure | Needs: Evap Water Flow Measurement Differential Pressure or Dual Pressure Sensors | FLOAT32 | ABCD | Read | |||
| IR | 80doc 30081 | Evaporator Entering Water Temperature | Temperature in the unit system set at the factory (I-P or SI). | FLOAT32 | ABCD | Read | |||
| IR | 82doc 30083 | Evaporator Leaving Water Temperature | Temperature in the unit system set at the factory (I-P or SI). | FLOAT32 | ABCD | Read | |||
| IR | 84doc 30085 | Evaporator Refrigerant Pressure Circuit 1 | Pressure in the factory unit system (I-P or SI). | FLOAT32 | ABCD | Read | |||
| IR | 86doc 30087 | Evaporator Saturated Refrigerant Temperature Circuit 1 | Temperature in the unit system set at the factory (I-P or SI). | FLOAT32 | ABCD | Read | |||
| IR | 88doc 30089 | Entering Condenser Water Pressure | Needs: Cond Water Flow Measurement Differential Pressure or Dual Pressure Sensors | FLOAT32 | ABCD | Read | |||
| IR | 90doc 30091 | Leaving Condenser Water Pressure | Needs: Cond Water Flow Measurement Differential Pressure or Dual Pressure Sensors | FLOAT32 | ABCD | Read | |||
| IR | 92doc 30093 | Entering Evaporator Water Pressure | Needs: Evap Water Flow Measurement Differential Pressure or Dual Pressure Sensors | FLOAT32 | ABCD | Read | |||
| IR | 94doc 30095 | Leaving Evaporator Water Pressure | Needs: Evap Water Flow Measurement Differential Pressure or Dual Pressure Sensors | FLOAT32 | ABCD | Read | |||
| IR | 96doc 30097 | Inlet Guide Vane 1 Percent Open Circuit 1 | FLOAT32 | ABCD | % | Read | |||
| IR | 98doc 30099 | Motor Winding Temperature 1 Circuit 1 | Temperature in the unit system set at the factory (I-P or SI). | FLOAT32 | ABCD | Read | |||
| IR | 100doc 30101 | Motor Winding Temperature 2 Circuit 1 | Temperature in the unit system set at the factory (I-P or SI). | FLOAT32 | ABCD | Read | |||
| IR | 102doc 30103 | Motor Winding Temperature 3 Circuit 1 | Temperature in the unit system set at the factory (I-P or SI). | FLOAT32 | ABCD | Read | |||
| IR | 104doc 30105 | Number of Circuits | FLOAT32 | ABCD | Read | ||||
| IR | 106doc 30107 | Number of Compressors Circuit 1 | FLOAT32 | ABCD | Read | ||||
| IR | 108doc 30109 | Number of Compressors Circuit 2 | FLOAT32 | ABCD | Read | ||||
| IR | 110doc 30111 | Refrigerant Monitor | Needs: Refrigerant Monitor | FLOAT32 | ABCD | Read | |||
| IR | 112doc 30113 | Unit Power Consumption | Electrical power. | FLOAT32 | ABCD | Read | |||
| IR | 114doc 30115 | Drive Input Voltage Calculated 1A | Voltage. | FLOAT32 | ABCD | Read | |||
| IR | 116doc 30117 | Actual Running Capacity | FLOAT32 | ABCD | % | Read | |||
| IR | 118doc 30119 | Unit Source ID | FLOAT32 | ABCD | Read | ||||
| IR | 120doc 30121 | Chiller Design Capacity | Cooling capacity in the factory unit system (I-P or SI). | FLOAT32 | ABCD | Read | |||
| IR | 122doc 30123 | Outdoor Air Temperature | Temperature in the unit system set at the factory (I-P or SI). Needs: Outdoor Air Temp | FLOAT32 | ABCD | Read | |||
| IR | 124doc 30125 | Energy Consumption Lifetime | Electrical energy. | FLOAT32 | ABCD | Read | |||
| IR | 126doc 30127 | Energy Consumption | Electrical energy. | FLOAT32 | ABCD | Read | |||
| IR | 128doc 30129 | Unit Power Demand | Electrical power. | FLOAT32 | ABCD | Read | |||
| IR | 130doc 30131 | Voltage L1-L2 | Voltage. Needs: Energy Meter | FLOAT32 | ABCD | Read | |||
| IR | 132doc 30133 | Voltage L2-L3 | Voltage. Needs: Energy Meter | FLOAT32 | ABCD | Read | |||
| IR | 134doc 30135 | Voltage L1-L3 | Voltage. Needs: Energy Meter | FLOAT32 | ABCD | Read | |||
| IR | 136doc 30137 | Current L1 | Current. Needs: Energy Meter | FLOAT32 | ABCD | Read | |||
| IR | 138doc 30139 | Current L2 | Current. Needs: Energy Meter | FLOAT32 | ABCD | Read | |||
| IR | 140doc 30141 | Current L3 | Current. Needs: Energy Meter | FLOAT32 | ABCD | Read | |||
| IR | 142doc 30143 | Line Frequency | Needs: Energy Meter | FLOAT32 | ABCD | Read | |||
| IR | 144doc 30145 | Power Factor | Needs: Energy Meter | FLOAT32 | ABCD | Read | |||
| IR | 146doc 30147 | Condenser Control Output | Needs: Condenser Control Output | FLOAT32 | ABCD | % | Read | ||
| IR | 148doc 30149 | Average Voltage L-L | Voltage. Needs: Energy Meter | FLOAT32 | ABCD | Read | |||
| IR | 150doc 30151 | Average Current | Current. Needs: Energy Meter | FLOAT32 | ABCD | Read | |||
| IR | 152doc 30153 | Condenser Approach Temperature Circuit 1 | Temperature difference, factory unit system (I-P or SI). | FLOAT32 | ABCD | Read | |||
| IR | 154doc 30155 | Evaporator Approach Temperature Circuit 1 | Temperature difference, factory unit system (I-P or SI). | FLOAT32 | ABCD | Read | |||
| IR | 180doc 30181 | Drive Motor Current U RLA Circuit 2 | Needs: Circuit 2 | FLOAT32 | ABCD | % | Read | ||
| IR | 182doc 30183 | Drive Motor Current V Circuit 2 | Current. Needs: Circuit 2 | FLOAT32 | ABCD | Read | |||
| IR | 184doc 30185 | Drive Motor Current V RLA Circuit 2 | Needs: Circuit 2 | FLOAT32 | ABCD | % | Read | ||
| IR | 186doc 30187 | Drive Motor Current W Circuit 2 | Current. Needs: Circuit 2 | FLOAT32 | ABCD | Read | |||
| IR | 188doc 30189 | Drive Motor Current W RLA Circuit 2 | Needs: Circuit 2 | FLOAT32 | ABCD | % | Read | ||
| IR | 190doc 30191 | Drive Output Power Circuit 2 | Electrical power. Needs: Circuit 2 | FLOAT32 | ABCD | Read | |||
| IR | 192doc 30193 | Drive Speed Status Percent Circuit 2 | Needs: Circuit 2 | FLOAT32 | ABCD | % | Read | ||
| IR | 194doc 30195 | Compressor Bearing Temperature 1 - Compressor 2A | Temperature in the unit system set at the factory (I-P or SI). Needs: Circuit 2 | FLOAT32 | ABCD | Read | |||
| IR | 196doc 30197 | Compressor Bearing Temperature 2 - Compressor 2A | Temperature in the unit system set at the factory (I-P or SI). Needs: Circuit 2 | FLOAT32 | ABCD | Read | |||
| IR | 198doc 30199 | Refrigerant Discharge Temperature - Compressor 2A | Temperature in the unit system set at the factory (I-P or SI). Needs: Circuit 2 | FLOAT32 | ABCD | Read | |||
| IR | 200doc 30201 | Run Time - Compressor 2A | Needs: Circuit 2 | FLOAT32 | ABCD | Read | |||
| IR | 202doc 30203 | Starts - Compressor 2A | Needs: Circuit 2 | FLOAT32 | ABCD | Read | |||
| IR | 204doc 30205 | Condenser Refrigerant Pressure Circuit 2 | Pressure in the factory unit system (I-P or SI). Needs: Circuit 2 | FLOAT32 | ABCD | Read | |||
| IR | 206doc 30207 | Condenser Saturated Refrigerant Temperature Circuit 2 | Temperature in the unit system set at the factory (I-P or SI). Needs: Circuit 2 | FLOAT32 | ABCD | Read | |||
| IR | 208doc 30209 | Differential Refrigerant Pressure Circuit 2 | Pressure in the factory unit system (I-P or SI). Needs: Circuit 2 | FLOAT32 | ABCD | Read | |||
| IR | 210doc 30211 | Evaporator Refrigerant Pressure Circuit 2 | Pressure in the factory unit system (I-P or SI). Needs: Circuit 2 | FLOAT32 | ABCD | Read | |||
| IR | 212doc 30213 | Evaporator Saturated Refrigerant Temperature Circuit 2 | Temperature in the unit system set at the factory (I-P or SI). Needs: Circuit 2 | FLOAT32 | ABCD | Read | |||
| IR | 214doc 30215 | Inlet Guide Vane 1 Percent Open Circuit 2 | Needs: Circuit 2 | FLOAT32 | ABCD | % | Read | ||
| IR | 216doc 30217 | Motor Winding Temperature 1 Circuit 2 | Temperature in the unit system set at the factory (I-P or SI). Needs: Circuit 2 | FLOAT32 | ABCD | Read | |||
| IR | 218doc 30219 | Motor Winding Temperature 2 Circuit 2 | Temperature in the unit system set at the factory (I-P or SI). Needs: Circuit 2 | FLOAT32 | ABCD | Read | |||
| IR | 220doc 30221 | Motor Winding Temperature 3 Circuit 2 | Temperature in the unit system set at the factory (I-P or SI). Needs: Circuit 2 | FLOAT32 | ABCD | Read | |||
| IR | 222doc 30223 | Drive Input Voltage Calculated 2A | Voltage. Needs: Circuit 2 | FLOAT32 | ABCD | Read | |||
| IR | 240doc 30241 | Condenser Approach Temperature Circuit 2 | Temperature difference, factory unit system (I-P or SI). Needs: Circuit 2 | FLOAT32 | ABCD | Read | |||
| IR | 242doc 30243 | Evaporator Approach Temperature Circuit 2 | Temperature difference, factory unit system (I-P or SI). Needs: Circuit 2 | FLOAT32 | ABCD | Read | |||
| IR | 244doc 30245 | Condenser Refrigerant Gauge Pressure Circuit 2 | Pressure in the factory unit system (I-P or SI). Needs: Circuit 2 | FLOAT32 | ABCD | Read | |||
| IR | 246doc 30247 | Evaporator Refrigerant Gauge Pressure Circuit 2 | Pressure in the factory unit system (I-P or SI). Needs: Circuit 2 | FLOAT32 | ABCD | Read | |||
| IR | 248doc 30249 | Active Cooling Differential to Start | Temperature difference, factory unit system (I-P or SI). | FLOAT32 | ABCD | Read | |||
| IR | 250doc 30251 | Active Cooling Differential to Stop | Temperature difference, factory unit system (I-P or SI). | FLOAT32 | ABCD | Read | |||
| IR | 252doc 30253 | Active Heating Differential to Start | Temperature difference, factory unit system (I-P or SI). Needs: Hot Water Control | FLOAT32 | ABCD | Read | |||
| IR | 254doc 30255 | Active Heating Differential to Stop | Temperature difference, factory unit system (I-P or SI). Needs: Hot Water Control | FLOAT32 | ABCD | Read | |||
| IR | 256doc 30257 | Discharge Superheat Compressor 1A | Temperature difference, factory unit system (I-P or SI). | FLOAT32 | ABCD | Read | |||
| IR | 258doc 30259 | Discharge Superheat Compressor 2A | Temperature difference, factory unit system (I-P or SI). Needs: Circuit 2 | FLOAT32 | ABCD | Read | |||
| IR | 2010doc 32011 | Operating Mode | UINT16 | Read | 1 = Cool; 2 = Heat; 3 = Ice Making; 4 = Free Cooling | ||||
| IR | 2011doc 32012 | Running Mode | UINT16 | Read | 1 = Chiller Off; 2 = Chiller In Start Mode; 3 = Chiller In Run Mode; 4 = Chiller In Pre-Shutdown Mode; 5 = Chiller In Service Mode | ||||
| IR | 2012doc 32013 | Manufacturing Location | UINT16 | Read | 2 = La Crosse | ||||
| IR | 2013doc 32014 | Chiller Setpoint Source | UINT16 | Read | 1 = BAS; 2 = External; 3 = Front Panel | ||||
| IR | 2014doc 32015 | Refrigerant Type | UINT16 | Read | 5 = R-134a; 13 = R-513A; 16 = R-1234ze(E); 18 = R-515B | ||||
| IR | 2015doc 32016 | Cooling Type | UINT16 | Read | 1 = Water Cooled | ||||
| IR | 2016doc 32017 | Model Information [GEN2] | UINT16 | Read | 25 = HDWA; 66 = HDDA | ||||
| IR | 3010doc 33011 | Diagnostic Present | UINT16 | Read | 0 = Normal; 1 = In Alarm | ||||
| IR | 3011doc 33012 | Diagnostic Shutdown Present | UINT16 | Read | 0 = Normal; 1 = In Alarm | ||||
| IR | 3012doc 33013 | Diagnostic: Manual Reset Required | UINT16 | Read | 0 = Normal; 1 = In Alarm | ||||
| IR | 3013doc 33014 | Diagnostic: Local Manual Reset Required | UINT16 | Read | 0 = Normal; 1 = In Alarm | ||||
| IR | 3014doc 33015 | Diagnostic Present: Information | UINT16 | Read | 0 = Normal; 1 = In Alarm | ||||
| IR | 3015doc 33016 | Diagnostic Present: Advisory | UINT16 | Read | 0 = Normal; 1 = In Alarm | ||||
| IR | 3016doc 33017 | Diagnostic Present: Critical | UINT16 | Read | 0 = Normal; 1 = In Alarm | ||||
| IR | 3017doc 33018 | Diagnostic Present: Service Required | UINT16 | Read | 0 = Normal; 1 = In Alarm | ||||
| IR | 3018doc 33019 | Base Loading Active | Needs: Base Loading | UINT16 | Read | 0 = Inactive; 1 = Active | |||
| IR | 3019doc 33020 | Chiller Running State | UINT16 | Read | 0 = Off; 1 = On | ||||
| IR | 3020doc 33021 | Condenser Water Flow Status | UINT16 | Read | 0 = No Flow; 1 = Flow | ||||
| IR | 3021doc 33022 | Condenser Water Pump Request | UINT16 | Read | 0 = Off; 1 = On | ||||
| IR | 3022doc 33023 | Emergency Stop | UINT16 | Read | 0 = Auto; 1 = Emergency Stop - Manual Reset Required | ||||
| IR | 3023doc 33024 | Evaporator Water Flow Status | UINT16 | Read | 0 = No Flow; 1 = Flow | ||||
| IR | 3024doc 33025 | Evaporator Water Pump Request | UINT16 | Read | 0 = Off; 1 = On | ||||
| IR | 3025doc 33026 | Base Loading Request Active | Needs: Base Loading | UINT16 | Read | 0 = Off; 1 = On | |||
| IR | 3026doc 33027 | Head Relief Request | UINT16 | Read | 0 = Off; 1 = On | ||||
| IR | 3027doc 33028 | Limit Mode Relay Status | UINT16 | Read | 0 = Off; 1 = On | ||||
| IR | 3028doc 33029 | Local Setpoint Control | UINT16 | Read | 0 = Remote Control; 1 = Local Control | ||||
| IR | 3029doc 33030 | Manual Override Exists | UINT16 | Read | 0 = Off; 1 = On | ||||
| IR | 3030doc 33031 | Maximum Capacity | UINT16 | Read | 0 = Off; 1 = On | ||||
| IR | 3031doc 33032 | Run Enabled | UINT16 | Read | 0 = Run Not Enabled; 1 = Run Enabled | ||||
| IR | 3032doc 33033 | Compressor 1A Status | UINT16 | Read | 0 = Off; 1 = Running | ||||
| IR | 3033doc 33034 | Front Panel Auto Stop | UINT16 | Read | 0 = Stop; 1 = Auto | ||||
| IR | 3034doc 33035 | External Auto Stop Input Status | UINT16 | Read | 0 = Stop; 1 = Auto | ||||
| IR | 3035doc 33036 | Compressor 2A Status | Needs: Circuit 2 | UINT16 | Read | 0 = Off; 1 = Running | |||
| IR | 4000doc 34001 | Comm Loss: Ext Base Loading Command | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4001doc 34002 | Comm Loss: Ext Base Loading Setpoint | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4002doc 34003 | Diagnostic: External Base Loading Setpoint | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4003doc 34004 | Comm Loss: Energy Meter | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4004doc 34005 | Comm Loss: Outdoor Air Temperature | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4005doc 34006 | Diagnostic: Energy Meter Write Command Failure | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4006doc 34007 | Diagnostic: Outdoor Air Temperature Sensor | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4007doc 34008 | Diagnostic: Software Error 1001: Call Trane Service | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4008doc 34009 | Diagnostic: Software Error 1002: Call Trane Service | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4009doc 34010 | Diagnostic: Software Error 1003: Call Trane Service | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4010doc 34011 | Comm Loss: Condenser Liquid Level Sensor Circuit 1 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4011doc 34012 | Comm Loss: Condenser Rfgt Pressure Circuit 1 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4012doc 34013 | Comm Loss: Drive Cooling Supply Temperature Circuit 1 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4013doc 34014 | Comm Loss: Drive Cooling Valve Circuit 1 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4014doc 34015 | Comm Loss: Evaporator Refrigerant Pressure Circuit 1 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4015doc 34016 | Diagnostic: Condenser Liquid Level Sensor Circuit 1 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4016doc 34017 | Diagnostic: Condenser Refrigerant Pressure Sensor Circuit 1 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4017doc 34018 | Diagnostic: Drive Cooling Supply Temperature Sensor Circuit 1 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4018doc 34019 | Diagnostic: Evaporator Refrigerant Pressure Sensor Circuit 1 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4019doc 34020 | Diagnostic: High Condenser Liquid Level Circuit 1 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4020doc 34021 | Diagnostic: Low Condenser Liquid Level Circuit 1 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4021doc 34022 | Diagnostic: Inverted Condenser Approach Temperature | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4022doc 34023 | Diagnostic: Inverted Evaporator Approach Temperature | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4023doc 34024 | Diagnostic: Loss of Drive Cooling Control Circuit 1 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4024doc 34025 | Diagnostic: Loss of Evaporator EXV Control Circuit 1 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4025doc 34026 | Diagnostic: Low Evaporator Refrigerant Temperature Circuit 1 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4026doc 34027 | Comm Loss: Cprsr Discharge Rfgt Temp Circuit 1 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4027doc 34028 | Comm Loss: Economizer Valve Circuit 1 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4028doc 34029 | Comm Loss: Economizer Pressure Circuit 1 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4029doc 34030 | Comm Loss: Economizer Temperature Circuit 1 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4030doc 34031 | Comm Loss: IGV First Stage Actuator Circuit 1 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4031doc 34032 | Comm Loss: Interstage Bypass Valve Circuit 1 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4032doc 34033 | Diagnostic: Compressor Refrigerant Discharge Temperature Sensor Circuit 1 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4033doc 34034 | Diagnostic: Economizer Pressure Sensor Circuit 1 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4034doc 34035 | Diagnostic: Economizer Temperature Sensor Circuit 1 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4035doc 34036 | Diagnostic: Extended Compressor Surge Circuit 1 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4036doc 34037 | Diagnostic: Condenser Water Flow Lost | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4037doc 34038 | Diagnostic: Condenser Water Flow Overdue | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4038doc 34039 | Diagnostic: High Condenser Pressure Circuit 1 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4039doc 34040 | Comm Loss: Condenser Entering Water Pressure | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4040doc 34041 | Comm Loss: Condenser Entering Water Temp | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4041doc 34042 | Comm Loss: Condenser Leaving Water Pressure | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4042doc 34043 | Comm Loss: Condenser Leaving Water Temp | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4043doc 34044 | Comm Loss: Condenser Water Flow Measurement Sensor | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4044doc 34045 | Comm Loss: Condenser Water Flow Switch | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4045doc 34046 | Comm Loss: Condenser Water Pump Relay | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4046doc 34047 | Diagnostic: Condenser Entering Water Pressure | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4047doc 34048 | Diagnostic: Condenser Entering Water Temp Sensor | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4048doc 34049 | Diagnostic: Condenser Leaving Water Pressure | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4049doc 34050 | Diagnostic: Condenser Leaving Water Temp Sensor | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4050doc 34051 | Diagnostic: Condenser Water Flow Measurement Sensor | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4051doc 34052 | Diagnostic: Inverted Condenser Water Temperature | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4052doc 34053 | Diagnostic: Evaporator Water Flow Lost | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4053doc 34054 | Diagnostic: Evaporator Water Flow Overdue | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4054doc 34055 | Diagnostic: High Evaporator Refrigerant Pressure | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4055doc 34056 | Diagnostic: High Evaporator Water Temperature | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4056doc 34057 | Diagnostic: Low Evaporator Water Flow | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4057doc 34058 | Comm Loss: Evap Entering Water Temp | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4058doc 34059 | Comm Loss: Evap Leaving Water Temp | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4059doc 34060 | Comm Loss: Evaporator Entering Water Pressure | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4060doc 34061 | Comm Loss: Evaporator Leaving Water Pressure | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4061doc 34062 | Comm Loss: Evaporator Water Flow Measurement Sensor | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4062doc 34063 | Comm Loss: Evaporator Water Flow Switch | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4063doc 34064 | Comm Loss: Evaporator Water Pump Relay | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4064doc 34065 | Diagnostic: Evaporator Entering Water Pressure | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4065doc 34066 | Diagnostic: Evaporator Entering Water Temp Sensor | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4066doc 34067 | Diagnostic: Evaporator Leaving Water Pressure | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4067doc 34068 | Diagnostic: Evaporator Leaving Water Temp Sensor | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4068doc 34069 | Diagnostic: Evaporator Water Flow Measurement Sensor | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4069doc 34070 | Diagnostic: Inverted Evaporator Water Temperature | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4070doc 34071 | Diagnostic: Low Evap Leaving Water Temp: Unit Off | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4071doc 34072 | Diagnostic: Low Evap Leaving Water Temp: Unit On | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4072doc 34073 | Comm Loss: Evaporator EXV Circuit 1 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4073doc 34074 | Comm Loss: Chiller % Capacity Output | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4074doc 34075 | Comm Loss: Condenser Rfgt Pressure Output | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4075doc 34076 | Comm Loss: Emergency Stop | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4076doc 34077 | Comm Loss: Ext Chilled/Hot Water Setpoint | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4077doc 34078 | Comm Loss: Ext Demand Limit Setpoint | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4078doc 34079 | Comm Loss: External Auto/Stop | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4079doc 34080 | Comm Loss: External Hot Water Command | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4080doc 34081 | Comm Loss: Programmable Relay Board 1 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4081doc 34082 | Comm Loss: Programmable Relay Board 2 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4082doc 34083 | Diagnostic: Emergency Stop | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4083doc 34084 | Diagnostic: External Chilled/Hot Water Setpoint | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4084doc 34085 | Diagnostic: External Demand Limit Setpoint | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4085doc 34086 | Comm Loss: Refrigerant Monitor Input | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4086doc 34087 | Diagnostic: Refrigerant Monitor Input | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4087doc 34088 | Comm Loss: External Ice Building Command | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4088doc 34089 | Comm Loss: Ice Building Status Relay | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4089doc 34090 | Diagnostic: MBC Bearing Temperature 1 Circuit 1 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4090doc 34091 | Diagnostic: MBC Bearing Temperature 2 Circuit 1 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4091doc 34092 | Diagnostic: MBC Failed Centering Circuit 1 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4092doc 34093 | Comm Loss: MBC Cooling Valve Circuit 1 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4093doc 34094 | Comm Loss: Magnetic Bearing Controller Circuit 1 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4094doc 34095 | Comm Loss: UPS Fault Circuit 1 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4095doc 34096 | Diagnostic: Loss of MBC Cooling Control Circuit 1 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4096doc 34097 | Diagnostic: MBC Not Centered Circuit 1 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4097doc 34098 | Diagnostic: MBC Not Ready To Rotate Circuit 1 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4098doc 34099 | Diagnostic: MBC Over Voltage Circuit 1 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4099doc 34100 | Diagnostic: MBC Parameter Table Not Set Circuit 1 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4100doc 34101 | Diagnostic: MBC Rotor Elongation Circuit 1 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4101doc 34102 | Diagnostic: MBC Rotor Unbalance Alarm Circuit 1 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4102doc 34103 | Diagnostic: MBC: Shutdown Request Circuit 1 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4103doc 34104 | Diagnostic: MBC Under Voltage Circuit 1 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4104doc 34105 | Diagnostic: MBC Overspeed Circuit 1 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4105doc 34106 | Diagnostic: MBC PCB Temperature Circuit 1 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4106doc 34107 | Diagnostic: MBC Rotation Detected Without Levitation Circuit 1 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4107doc 34108 | Diagnostic: MBC Speed Sensor Circuit 1 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4108doc 34109 | Diagnostic: UPS Fault Circuit 1 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4109doc 34110 | Comm Loss: Motor Cooling Valve Circuit 1 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4110doc 34111 | Comm Loss: Motor Winding Temperature 1 Circuit 1 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4111doc 34112 | Comm Loss: Motor Winding Temperature 2 Circuit 1 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4112doc 34113 | Comm Loss: Motor Winding Temperature 3 Circuit 1 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4113doc 34114 | Diagnostic: High Compressor Refrigerant Discharge Temperature Circuit 1 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4114doc 34115 | Diagnostic: High Motor Winding Temperature 1 Circuit 1 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4115doc 34116 | Diagnostic: High Motor Winding Temperature 2 Circuit 1 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4116doc 34117 | Diagnostic: High Motor Winding Temperature 3 Circuit 1 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4117doc 34118 | Diagnostic: High Vacuum Lockout Circuit 1 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4118doc 34119 | Diagnostic: Loss of Motor Cooling Control Circuit 1 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4119doc 34120 | Diagnostic: Motor Winding Temperature 1 Sensor Circuit 1 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4120doc 34121 | Diagnostic: Motor Winding Temperature 2 Sensor Circuit 1 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4121doc 34122 | Diagnostic: Motor Winding Temperature 3 Sensor Circuit 1 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4122doc 34123 | Diagnostic: MP: Invalid Configuration | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4123doc 34124 | Diagnostic: MP: Reset Has Occurred | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4124doc 34125 | Diagnostic: AFD Comm Loss: Main Processor Circuit 1 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4125doc 34126 | Diagnostic: AFD Failure to Arm or Start Circuit 1 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4126doc 34127 | Diagnostic: AFD Fault Circuit 1 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4127doc 34128 | Diagnostic: AFD Ground Fault Circuit 1 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4128doc 34129 | Diagnostic: AFD Interrupt Failure Circuit 1 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4129doc 34130 | Diagnostic: AFD Mains Failure Circuit 1 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4130doc 34131 | Diagnostic: AFD Motor Current Overload Circuit 1 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4131doc 34132 | Diagnostic: AFD Safe Stop Circuit 1 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4132doc 34133 | Diagnostic: AFD Short Circuit Circuit 1 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4133doc 34134 | Diagnostic: AFD Speed Configuration Mismatch Circuit 1 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4134doc 34135 | Comm Loss: Adaptive Frequency Drive Circuit 1 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4135doc 34136 | Diagnostic: Unexpected Starter Shutdown Circuit 1 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4136doc 34137 | Diagnostic: Software Error 1005: Call Trane Service | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4137doc 34138 | Comm Loss: Starter Panel High Temp Limit Compressor 1A | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4138doc 34139 | Diagnostic: Starter Panel High Temp Limit Compressor 1A | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4139doc 34140 | Comm Loss: Subcooled Liquid Temp Circuit 1 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4140doc 34141 | Comm Loss: External Ckt Lockout Circuit 1 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4141doc 34142 | Diagnostic: Subcooled Liquid Temperature Sensor Circuit 1 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4142doc 34143 | Diagnostic: Evaporator Saturated Refrigerant Temp Sensor Circuit 1 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4143doc 34144 | Comm Loss: Evap Saturated Rfgt Temp Circuit 1 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4144doc 34145 | Diagnostic: Low Suction Refrigerant Pressure Circuit 1 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4145doc 34146 | Diagnostic: High Differential Refrigerant Pressure Circuit 1 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4146doc 34147 | Diagnostic: High Refrigerant Pressure Ratio Circuit 1 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4147doc 34148 | Diagnostic: Starts/Hours Modified Compressor 1A | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4148doc 34149 | Diagnostic: Starts/Hours Modified Compressor 2A | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4149doc 34150 | Diagnostic: High Evaporator Refrigerant Temperature Circuit 1 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4150doc 34151 | Comm Loss: Off-cycle Freeze Protection Relay Circuit 1 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4151doc 34152 | Comm Loss: Condenser Head Pressure Cntrl Output Circuit 1 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4152doc 34153 | Comm Loss: Ext Noise Reduction Request Circuit 1 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4153doc 34154 | Diagnostic: MBC Failed Clearance Check Circuit 1 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4154doc 34155 | Diagnostic: Check Clock | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4155doc 34156 | Diagnostic: MP: Non-Volatile Block Test Error | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4156doc 34157 | Diagnostic: Under Voltage Circuit 1 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4157doc 34158 | Diagnostic: Over Voltage Circuit 1 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4158doc 34159 | Compressor 2A Status | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4159doc 34160 | Comm Loss: Condenser Liquid Level Sensor Circuit 2 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4160doc 34161 | Comm Loss: Condenser Rfgt Pressure Circuit 2 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4161doc 34162 | Comm Loss: Drive Cooling Supply Temperature Circuit 2 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4162doc 34163 | Comm Loss: Drive Cooling Supply Temperature Circuit 2 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4163doc 34164 | Comm Loss: Drive Cooling Valve Circuit 2 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4164doc 34165 | Comm Loss: Evaporator Refrigerant Pressure Circuit 2 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4165doc 34166 | Diagnostic: Condenser Liquid Level Sensor Circuit 2 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4166doc 34167 | Diagnostic: Condenser Refrigerant Pressure Sensor Circuit 2 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4167doc 34168 | Diagnostic: Drive Cooling Supply Temperature Sensor Circuit 2 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4168doc 34169 | Diagnostic: Evaporator Refrigerant Pressure Sensor Circuit 2 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4169doc 34170 | Diagnostic: High Condenser Liquid Level Circuit 2 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4170doc 34171 | Diagnostic: Low Condenser Liquid Level Circuit 2 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4171doc 34172 | Diagnostic: Loss of Drive Cooling Control Circuit 2 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4172doc 34173 | Diagnostic: Loss of Evaporator EXV Control Circuit 2 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4173doc 34174 | Diagnostic: Low Evaporator Refrigerant Temperature Circuit 2 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4174doc 34175 | Comm Loss: Cprsr Discharge Rfgt Temp Circuit 2 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4175doc 34176 | Comm Loss: Economizer Valve Circuit 2 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4176doc 34177 | Comm Loss: Economizer Pressure Circuit 2 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4177doc 34178 | Comm Loss: Economizer Temperature Circuit 2 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4178doc 34179 | Comm Loss: IGV First Stage Actuator Circuit 2 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4179doc 34180 | Comm Loss: Interstage Bypass Valve Circuit 2 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4180doc 34181 | Diagnostic: Compressor Refrigerant Discharge Temperature Sensor Circuit 2 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4181doc 34182 | Diagnostic: Economizer Pressure Sensor Circuit 2 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4182doc 34183 | Diagnostic: Economizer Temperature Sensor Circuit 2 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4183doc 34184 | Diagnostic: Extended Compressor Surge Circuit 2 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4184doc 34185 | Diagnostic: High Condenser Pressure Circuit 2 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4185doc 34186 | Comm Loss: Evaporator EXV Circuit 2 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4186doc 34187 | Diagnostic: MBC Bearing Temperature 1 Circuit 2 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4187doc 34188 | Diagnostic: MBC Bearing Temperature 2 Circuit 2 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4188doc 34189 | Diagnostic: MBC Failed Centering Circuit 2 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4189doc 34190 | Comm Loss: MBC Cooling Valve Circuit 2 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4190doc 34191 | Comm Loss: Magnetic Bearing Controller Circuit 2 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4191doc 34192 | Comm Loss: UPS Fault Circuit 2 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4192doc 34193 | Diagnostic: Loss of MBC Cooling Control Circuit 2 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4193doc 34194 | Diagnostic: MBC Not Centered Circuit 2 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4194doc 34195 | Diagnostic: MBC Not Ready To Rotate Circuit 2 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4195doc 34196 | Diagnostic: MBC Over Voltage Circuit 2 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4196doc 34197 | Diagnostic: MBC Parameter Table Not Set Circuit 2 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4197doc 34198 | Diagnostic: MBC Rotor Elongation Circuit 2 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4198doc 34199 | Diagnostic: MBC Rotor Unbalance Alarm Circuit 2 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4199doc 34200 | Diagnostic: MBC: Shutdown Request Circuit 2 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4200doc 34201 | Diagnostic: MBC Under Voltage Circuit 2 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4201doc 34202 | Diagnostic: MBC Overspeed Circuit 2 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4202doc 34203 | Diagnostic: MBC PCB Temperature Circuit 2 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4203doc 34204 | Diagnostic: MBC Rotation Detected Without Levitation Circuit 2 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4204doc 34205 | Diagnostic: MBC Speed Sensor Circuit 2 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4205doc 34206 | Diagnostic: UPS Fault Circuit 2 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4206doc 34207 | Comm Loss: Motor Cooling Valve Circuit 2 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4207doc 34208 | Comm Loss: Motor Winding Temperature 1 Circuit 2 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4208doc 34209 | Comm Loss: Motor Winding Temperature 2 Circuit 2 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4209doc 34210 | Comm Loss: Motor Winding Temperature 3 Circuit 2 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4210doc 34211 | Diagnostic: High Compressor Refrigerant Discharge Temperature Circuit 2 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4211doc 34212 | Diagnostic: High Motor Winding Temperature 1 Circuit 2 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4212doc 34213 | Diagnostic: High Motor Winding Temperature 2 Circuit 2 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4213doc 34214 | Diagnostic: High Motor Winding Temperature 3 Circuit 2 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4214doc 34215 | Diagnostic: High Vacuum Lockout Circuit 2 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4215doc 34216 | Diagnostic: Loss of Motor Cooling Control Circuit 2 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4216doc 34217 | Diagnostic: Motor Winding Temperature 1 Sensor Circuit 2 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4217doc 34218 | Diagnostic: Motor Winding Temperature 2 Sensor Circuit 2 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4218doc 34219 | Diagnostic: Motor Winding Temperature 3 Sensor Circuit 2 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4219doc 34220 | Diagnostic: AFD Comm Loss: Main Processor Circuit 2 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4220doc 34221 | Diagnostic: AFD Failure to Arm or Start Circuit 2 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4221doc 34222 | Diagnostic: AFD Fault Circuit 2 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4222doc 34223 | Diagnostic: AFD Ground Fault Circuit 2 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4223doc 34224 | Diagnostic: AFD Interrupt Failure Circuit 2 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4224doc 34225 | Diagnostic: AFD Mains Failure Circuit 2 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4225doc 34226 | Diagnostic: AFD Motor Current Overload Circuit 2 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4226doc 34227 | Diagnostic: AFD Safe Stop Circuit 2 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4227doc 34228 | Diagnostic: AFD Short Circuit Circuit 2 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4228doc 34229 | Diagnostic: AFD Speed Configuration Mismatch Circuit 2 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4229doc 34230 | Comm Loss: Adaptive Frequency Drive Circuit 2 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4230doc 34231 | Diagnostic: Unexpected Starter Shutdown Circuit 2 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4231doc 34232 | Comm Loss: Starter Panel High Temp Limit Compressor 2A | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4232doc 34233 | Diagnostic: Starter Panel High Temp Limit Compressor 2A | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4233doc 34234 | Comm Loss: Subcooled Liquid Temp Circuit 2 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4234doc 34235 | Comm Loss: External Ckt Lockout Circuit 2 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4235doc 34236 | Diagnostic: Subcooled Liquid Temperature Sensor Circuit 2 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4236doc 34237 | Diagnostic: Evaporator Saturated Refrigerant Temp Sensor Circuit 2 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4237doc 34238 | Comm Loss: Evap Saturated Rfgt Temp Circuit 2 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4238doc 34239 | Diagnostic: Low Suction Refrigerant Pressure Circuit 2 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4239doc 34240 | Diagnostic: High Differential Refrigerant Pressure Circuit 2 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4240doc 34241 | Diagnostic: High Refrigerant Pressure Ratio Circuit 2 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4241doc 34242 | Diagnostic: High Evaporator Refrigerant Temperature Circuit 2 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4242doc 34243 | Comm Loss: Off-cycle Freeze Protection Relay Circuit 2 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4243doc 34244 | Comm Loss: Condenser Head Pressure Cntrl Output Circuit 2 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4244doc 34245 | Comm Loss: Ext Noise Reduction Request Circuit 2 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4245doc 34246 | Diagnostic: MBC Failed Clearance Check Circuit 2 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4246doc 34247 | Diagnostic: Under Voltage Circuit 2 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4247doc 34248 | Diagnostic: Over Voltage Circuit 2 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4248doc 34249 | Comm Loss: IGV Second Stage Actuator Circuit 1 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4249doc 34250 | Comm Loss: IGV Second Stage Actuator Circuit 2 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4250doc 34251 | Comm Loss: Condenser Liquid Line Temperature Circuit 1 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4251doc 34252 | Diagnostic: Condenser Liquid Line Temperature Sensor Circuit 1 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4252doc 34253 | Comm Loss: Condenser Liquid Line Temperature Circuit 2 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4253doc 34254 | Diagnostic: Condenser Liquid Line Temperature Sensor Circuit 2 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4254doc 34255 | Diagnostic: High Evaporator Refrigerant Pressure Circuit 2 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4255doc 34256 | Diagnostic: Inverted Condenser Approach Temperature Circuit 2 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4256doc 34257 | Diagnostic: Inverted Evaporator Approach Temperature Circuit 2 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| HR | 10doc 40011 | Chilled Water Setpoint | Temperature in the unit system set at the factory (I-P or SI). | FLOAT32 | ABCD | Read/write | |||
| HR | 12doc 40013 | Demand Limit Setpoint | FLOAT32 | ABCD | % | Read/write | |||
| HR | 14doc 40015 | Hot Water Setpoint | Temperature in the unit system set at the factory (I-P or SI). Needs: Hot Water Control | FLOAT32 | ABCD | Read/write | |||
| HR | 16doc 40017 | Base Loading Setpoint | Needs: Base Loading | FLOAT32 | ABCD | % | Read/write | ||
| HR | 18doc 40019 | BAS Cooling Differential to Start | Temperature difference, factory unit system (I-P or SI). | FLOAT32 | ABCD | Read/write | |||
| HR | 20doc 40021 | BAS Cooling Differential to Stop | Temperature difference, factory unit system (I-P or SI). | FLOAT32 | ABCD | Read/write | |||
| HR | 22doc 40023 | BAS Heating Differential to Start | Temperature difference, factory unit system (I-P or SI). Needs: Hot Water Control | FLOAT32 | ABCD | Read/write | |||
| HR | 24doc 40025 | BAS Heating Differential to Stop | Temperature difference, factory unit system (I-P or SI). Needs: Hot Water Control | FLOAT32 | ABCD | Read/write | |||
| HR | 2010doc 42011 | Chiller Mode Command BAS | UINT16 | Read/write | 1 = Cool; 2 = Heat; 3 = Ice Making; 4 = Free Cooling | ||||
| HR | 3010doc 43011 | Base Loading Request | Needs: Base Loading | UINT16 | Read/write | 0 = Off; 1 = On | |||
| HR | 3011doc 43012 | Reset Diagnostic | UINT16 | Read/write | 0 = Normal; 1 = Reset | ||||
| HR | 3012doc 43013 | Chiller Auto Stop Command BAS | UINT16 | Read/write | 0 = Stop; 1 = Auto | ||||
| HR | 3013doc 43014 | Energy Consumption Reset | UINT16 | Read/write | 0 = Accumulating; 1 = Reset | ||||
| HR | 3014doc 43015 | Evaporator Water Pump Request BAS | UINT16 | Read/write | 1 = On | ||||
| HR | 3015doc 43016 | Condenser Water Pump Request BAS | UINT16 | Read/write | 1 = On | ||||
| HR | 3016doc 43017 | Circuit 1 Lockout BAS | UINT16 | Read/write | 1 = On | ||||
| HR | 3017doc 43018 | Circuit 2 Lockout BAS | Needs: Circuit 2 | UINT16 | Read/write | 1 = On |
Notes on this map
- Register format table: analog points are 32-bit floats sent high word / high byte first (NaN = invalid); binary and multi-state points are unsigned 16-bit integers (0xFFFF = invalid).
- Values are sent in the unit system ordered from the factory (I-P is the usual default, SI optional); the list names only the quantity, so temperature/pressure/flow units are left blank here.
- Not every point exists on every unit: the controller builds its point set from the unit's configuration. Descriptions name the configuration a point depends on.
- Register numbers are printed in 5-digit Modicon form (3xxxx input registers, 4xxxx holding registers) and converted here to wire addresses (30011 = input register 10).
- Agility integration guide BAS-SVP047B-EN (Sept 2023, https://elibrary.tranetechnologies.com/public/commercial-hvac/Literature/Integration/BAS-SVP047B-EN_09092023.pdf) gives the same register format and the Modbus RTU/TCP setup steps used in the integration block.
- Left out: AI-10173 to AI-10184 (registers 30157-30168). The list numbers these 32-bit floats one register apart, which cannot be right for two-register values, so their true addresses are unclear.
Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.
Questions about the Trane Agility water-cooled centrifugal chiller (Symbio 800)
What Modbus registers does the Trane Agility water-cooled centrifugal chiller (Symbio 800) have?
This map lists 412 registers: 395 input registers, 17 holding registers. 17 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.
Are the Trane Agility water-cooled centrifugal chiller (Symbio 800) Modbus addresses 0-based or 1-based?
The manufacturer's document numbers registers Modicon 3xxxx/4xxxx (drop the prefix, subtract 1). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. The list prints Modicon register numbers: 3xxxx are input registers and 4xxxx holding registers, so 30011 is input register address 10 and 42011 is holding register address 2010.
What byte order does the Trane Agility water-cooled centrifugal chiller (Symbio 800) use for 32-bit values?
Multi-register values in this map use ABCD (high word first (big-endian)). Set your client to this order for every 32/64-bit value in the table.
What are the minimum Modbus registers to integrate the Trane Agility water-cooled centrifugal chiller (Symbio 800)?
Start with IR 10 Active Chilled Water Setpoint (Active chilled water setpoint); IR 22 Chilled Water Setpoint Status (Chilled water setpoint status); IR 48 Drive Speed Status Percent (Drive speed %); IR 3019 Chiller Running State (Chiller running state); IR 3010 Diagnostic Present (Diagnostic present); HR 10 Chilled Water Setpoint (Chilled water setpoint (BAS)); HR 2010 Chiller Mode Command BAS (Chiller mode command); HR 3010 Base Loading Request (Base loading request).
How do I enable Modbus control of the Trane Agility water-cooled centrifugal chiller (Symbio 800)?
On the Symbio 800 web interface (USB connection) go to Installation > Identification and Communications > Protocol Configuration and select Modbus RTU or Modbus TCP; for TCP set the IP address on the IP Configuration tab.
Where is the official Trane Agility water-cooled centrifugal chiller (Symbio 800) Modbus documentation?
The source is Symbio 800 Integration Points List, BACnet/Modbus, Agility Water-Cooled Chillers (BAS-PTS007C-EN), revision 2026-06-30, published free by Trane at https://elibrary.tranetechnologies.com/public/commercial-hvac/Literature/Points%20List/BAS-PTS007C-EN_06302026.pdf.
More Trane Modbus register maps
- Chiller
Trane Ascend ACR Series C air-cooled chiller (Symbio 800)
Trane Ascend model ACR Series C air-cooled chillers with the Symbio 800 controller, as listed in BAS-PTS021A-EN (11/15/2024).
Also known as: ACR, Ascend ACR, ACR Series C, Ascend air-cooled chiller ACR - Chiller
Trane Ascend ACS / ACX air-cooled scroll chiller and heat pump (Symbio 800)
Trane Ascend ACS air-cooled scroll chillers and ACX air-to-water heat pumps with the Symbio 800 controller, as listed in BAS-PTS011A-EN (11/15/2024).
Also known as: ACS, ACX, Ascend ACS, Ascend ACX, Ascend air-cooled chiller, Ascend air-to-water heat pump - Chiller
Trane CenTraVac CTV-Duplex water-cooled centrifugal chiller (UC800 native Modbus)
Trane Duplex CenTraVac (two-compressor) water-cooled centrifugal chillers with the Tracer UC800 controller, as listed in the Modbus section of BAS-PTS030A-EN (12/6/2024).
Also known as: CTV-Duplex, CTVD, CenTraVac Duplex, Duplex CenTraVac UC800 - Chiller
Trane CenTraVac duplex centrifugal chiller (Symbio 800)
Trane dual-compressor (duplex) CenTraVac water-cooled centrifugal chillers fitted with the Symbio 800 controller, as listed in the Duplex tables of BAS-PTS009C-EN (12/12/2025).
Also known as: CDHF, CDHG, CDHH, CenTraVac Duplex Symbio 800 - Chiller
Trane CenTraVac simplex centrifugal chiller (Symbio 800)
Trane single-compressor (simplex) CenTraVac water-cooled centrifugal chillers fitted with the Symbio 800 controller, as listed in the Simplex tables of BAS-PTS009C-EN (12/12/2025).
Also known as: CVHE, CVHF, CVHG, CVHH, CVHL, CVHM, CVHS, CVGF, CVR, CVZA, CVXA, CenTraVac Simplex Symbio 800, CenTraVac simplex - Chiller
Trane CGAM air-cooled scroll chiller (Symbio 800)
Trane CGAM air-cooled scroll chillers with the Symbio 800 controller, as listed in BAS-PTS019A-EN (11/15/2024).
Also known as: CGAM, Trane CGAM, CGAM air-cooled scroll chiller - Chiller
Trane RTAC air-cooled helical-rotary chiller (Symbio 800)
Trane RTAC air-cooled helical-rotary chillers with the Symbio 800 controller, as listed in BAS-PTS023A-EN (11/8/2024).
Also known as: RTAC, Series R RTAC - Chiller
Trane RTAC air-cooled helical-rotary chiller (UC800 native Modbus profile)
Trane RTAC air-cooled chillers on the Tracer UC800 controller using the UC800 native Modbus map in the Modbus section of BAS-PTS032A-EN (12/6/2024). Not the same register set as the Symbio 800 RTAC list (BAS-PTS023A-EN).
Also known as: RTAC UC800 native Modbus profile, Series R RTAC UC800 native Modbus, BAS-PTS032A-EN - Chiller
Trane Series R RTHD water-cooled helical-rotary chiller (Symbio 800)
Trane Series R model RTHD water-cooled helical-rotary chillers with the Symbio 800 controller, as listed in BAS-PTS015A-EN (11/15/2024).
Also known as: RTHD, Series R RTHD - Chiller
Trane Series R RTWD water-cooled helical-rotary chiller (Symbio 800)
Trane Series R model RTWD water-cooled helical-rotary chillers with the Symbio 800 controller, as listed in BAS-PTS017A-EN (11/15/2024).
Also known as: RTWD, Series R RTWD, RTUD - Chiller
Trane Sintesis RTAF air-cooled screw chiller (Symbio 800)
Trane Sintesis RTAF air-cooled helical-rotary chillers with the Symbio 800 controller, as listed in BAS-PTS013B-EN (4/7/2026).
Also known as: RTAF, Sintesis RTAF, Sintesis air-cooled chiller - Pump (data-centre coolant distribution unit)
Trane TCDU coolant distribution unit (data-centre liquid cooling)
Trane Coolant Distribution Unit (TCDU) for direct-to-chip liquid cooling, as documented in IOM DC-SVX001A-EN (April 2025).
Also known as: TCDU, Trane CDU, Trane Coolant Distribution Unit, DC-SVX001A - Sensor (refrigerant leak monitor for chiller plant rooms)
Trane TruSense RMWH refrigerant monitor (up to 16 points)
Trane TruSense RMWH multipoint photoacoustic refrigerant monitor with Modbus RTU selected, per IOM PART-SVX008A-EN (30 Sep 2025, preliminary).
Also known as: TruSense, RMWH, Trane refrigerant monitor, PART-SVX008A, RMWH-SVX001
Other chillers & heat pumps register maps
- Chiller (refrigerant chiller for Liebert XD rack cooling)
Vertiv Liebert XDC refrigerant chiller for XD systems with iCOM v4 (IntelliSlot Modbus)
Liebert XDC units (the compressorised refrigerant chiller that feeds Liebert XD rack and ceiling cooling modules) on the iCOM v4 controller with a Liebert IntelliSlot Modbus card.
Also known as: Liebert XDC, XDC, Liebert XD chiller - Chiller (water-cooled, magnetic-bearing centrifugal)
Daikin Applied Magnitude WME magnetic-bearing chiller (MicroTech, Modbus)
Magnitude WME C- and D-vintage and WME-C QUAD chillers with the MicroTech unit controller and Modbus communication module, per ED 19111-4.
Also known as: WME-C, WME-D, WME-C QUAD, Magnitude WME, Daikin WME - Chiller
Daikin Applied Trailblazer AGZ-D / AGZ-E air-cooled scroll chiller (MicroTech controller)
Daikin Applied Trailblazer AGZ-D and AGZ-E air-cooled scroll chillers with the MicroTech chiller unit controller and Modbus communication module, per ED 15121-13.
Also known as: AGZ-D, AGZ-E, AGZ D-Vintage, AGZ E-Vintage, ED 15121, Trailblazer AGZ-D, Trailblazer AGZ-E - Chiller (water-cooled)
Daikin Applied EWWD-VZ / EWWH-VZ / EWWS-VZ water-cooled inverter screw chillers (Microtech, Adam software)
EWWD-VZ, EWWH-VZ and EWWS-VZ water-cooled inverter screw chillers with Microtech III or Microtech 4 controller running Adam software, per D-EIGOC00201-22_03EN.
Also known as: EWWD-VZ, EWWH-VZ, EWWS-VZ, EWWD(H)(S)_VZ, EWWD~VZ, EWWH~VZ, Daikin EWWD VZ, Adam - Chiller
Daikin Applied Navigator WWV / TWV water-cooled screw chiller (MicroTech controller)
Daikin Applied Navigator WWV and TWV water-cooled screw chillers with the MicroTech chiller unit controller and Modbus communication module, per ED 15121-13.
Also known as: WWV, TWV, Navigator WWV, Navigator TWV, Daikin Navigator, ED 15121 - Chiller
Aermec WTX water-cooled chiller with Turbocor compressors (pCO5+ BMS)
Aermec WTX oil-free (Danfoss Turbocor) water-cooled chillers with the pCO5+ controller, via the AER485P1 RS485 card or AERNET; BMS manual for WTX 5009100_00 (1705).
Also known as: WTX, TBX
All chillers & heat pumps Modbus register maps →
Source: Symbio 800 Integration Points List, BACnet/Modbus, Agility Water-Cooled Chillers · BAS-PTS007C-EN · rev. 2026-06-30. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.