Trane CenTraVac CTV-Duplex water-cooled centrifugal chiller (UC800 native Modbus) Modbus register map

Updated 19 November 2026

Short answer

Trane's Duplex CenTraVac is a two-circuit water-cooled centrifugal chiller. Its Tracer UC800 controller has a native Modbus map in which every point is one 16-bit register with a fixed SI scaling per register type (temperatures in 0.01 °C, pressures in 0.1 kPa, percent in 0.005 % steps). This map covers the BAS command registers and the input registers for water and refrigerant temperatures, pressures, starter and AFD values, bearing and winding temperatures and status enums.

This page lists 192 Modbus registers for the Trane CenTraVac CTV-Duplex water-cooled centrifugal chiller (UC800 native Modbus) — 12 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Trane’s own free documentation (linked below) and checked against it.

Manufacturer
Trane
Model
CenTraVac CTV-Duplex water-cooled centrifugal chiller (UC800 native Modbus)
Equipment type
Chiller
Registers
192 (12 writable)
Transport
Modbus RTU, Modbus TCP
Default unit ID
Not stated
Documented addressing
Modicon 3xxxx/4xxxx (drop the prefix, subtract 1)
Also known as
CTV-Duplex, CTVD, CenTraVac Duplex, Duplex CenTraVac UC800
Source document
Symbio 800 Integration Points List, BACnet/Modbus, CTV-Duplex (UC800) · BAS-PTS030A-EN · rev. 2024-12-06
Download CSV all columns JSON Manufacturer PDF ↗

Integration notes: Trane CenTraVac CTV-Duplex water-cooled centrifugal chiller (UC800 native Modbus)

Integration in brief

Write 40001 (auto/stop), 40002 (mode) and 40003 (chilled-water setpoint, 0.01 °C) and poll the 3xxxx input registers with function 04. Every value is a single register; apply the per-type scale from the object-format table.

Minimum registers to map

Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.

RegisterNameTypeWhyAccess
IR 2Chiller RunningUINT16Chiller runningRead
IR 25Chiller Running StatusUINT16Chiller running statusRead
IR 10Evap Leaving Water TempINT16Evaporator leaving water temperatureRead
IR 9Active Cool/Heat Setpoint TemperatureINT16Active cool/heat setpointRead
IR 46Alarm PresentUINT16Alarm presentRead
HR 0BAS Chiller Auto Stop CommandUINT16Chiller auto/stop commandRead/write
HR 1BAS Chiller Mode CommandUINT16Chiller mode commandRead/write
HR 2BAS Chilled Water SetpointINT16Chilled water setpoint (BAS)Read/write
HR 7BAS Diagnostic ResetUINT16Diagnostic resetRead/write

Enable Modbus control & writes

The points list does not describe setup; it names BAS-SVP083*-EN as its reference integration guide for enabling Modbus on the controller.

Byte order & addressing

Network setup

Watch out for

Trane CenTraVac CTV-Duplex water-cooled centrifugal chiller (UC800 native Modbus) Modbus registers

Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.

192 of 192 shown
Trane CenTraVac CTV-Duplex water-cooled centrifugal chiller (UC800 native Modbus) Modbus register map
TableAddressNameDescriptionTypeOrderScaleUnitsAccessValues / bits
IR0doc 30001Software TypeUINT16Read458 = CTVD
IR1doc 30002Software RevisionUINT16Read
IR2doc 30003Chiller RunningUINT16Read0 = False/Off/No/Disabled/Stop; 1 = True/On/Yes/Enabled/Auto
IR3doc 30004Unit Average Line CurrentPercent type: 20,000 = 100 %.INT16× 0.005%Read
IR4doc 30005Active Current Limit SetpointPercent type: 20,000 = 100 %.INT16× 0.005%Read
IR5doc 30006Active Base Loading SetptPercent type: 20,000 = 100 %.INT16× 0.005%Read
IR6doc 30007Unit Power ConsumptionUINT16kWRead
IR7doc 30008Calculated Chiller CapacityUINT16kWRead
IR8doc 30009Approx Unit Heating PowerUINT16kWRead
IR9doc 30010Active Cool/Heat Setpoint Temperature0.01 °C per count.INT16× 0.01°CRead
IR10doc 30011Evap Leaving Water Temp0.01 °C per count.INT16× 0.01°CRead
IR11doc 30012Evap Entering Water Temp0.01 °C per count.INT16× 0.01°CRead
IR12doc 30013Cond Entering Water Temp0.01 °C per count.INT16× 0.01°CRead
IR13doc 30014Cond Leaving Water Temp0.01 °C per count.INT16× 0.01°CRead
IR14doc 30015Evaporator Pump ControlUINT16Read0 = False/Off/No/Disabled/Stop; 1 = True/On/Yes/Enabled/Auto
IR15doc 30016Evaporator Water FlowUINT16Read0 = False/Off/No/Disabled/Stop; 1 = True/On/Yes/Enabled/Auto
IR16doc 30017Approx Evap Water FlowUINT16L/minRead
IR17doc 30018Evap Differential Wtr PressAbsolute pressure, 0.1 kPa per count.UINT16× 0.1kPaRead
IR18doc 30019Condenser Pump ControlUINT16Read0 = False/Off/No/Disabled/Stop; 1 = True/On/Yes/Enabled/Auto
IR19doc 30020Condenser Water FlowUINT16Read0 = False/Off/No/Disabled/Stop; 1 = True/On/Yes/Enabled/Auto
IR20doc 30021Approx Cond Water FlowUINT16L/minRead
IR21doc 30022Cond Differential Wtr PressAbsolute pressure, 0.1 kPa per count.UINT16× 0.1kPaRead
IR22doc 30023Second Condenser Entering Water Temperature0.01 °C per count.INT16× 0.01°CRead
IR23doc 30024Second Condenser Leaving Water Temperature0.01 °C per count.INT16× 0.01°CRead
IR24doc 30025Last Diagnostic CodeUINT16Read
IR25doc 30026Chiller Running StatusUINT16Read0 = Off/Idle (Auto); 1 = Starting; 2 = Running; 3 = Stopping
IR26doc 30027Chiller Control ModeUINT16Read0 = Cool; 1 = Heat; 2 = Ice; 3 = Free Cool
IR27doc 30028Setpoint SourceUINT16Read0 = BAS+External+Loc al; 1 = External+Local; 2 = Local
IR28doc 30029Active Chilled Water Setpoint SourceUINT16Read0 = Front Panel; 1 = External; 2 = Ice Machine; 3 = BAS
IR29doc 30030Active Current Limit Setpoint SourceUINT16Read0 = Front Panel; 1 = External; 2 = Ice Machiine; 3 = BAS
IR30doc 30031Active Base Loading Setpoint SourceUINT16Read0 = Front Panel; 1 = External; 2 = Ice Machiine; 3 = BAS
IR31doc 30032Active Hot Water Setpoint SourceUINT16Read0 = Front Panel; 1 = External; 2 = Ice Machiine; 3 = BAS
IR32doc 30033Front Panel Auto/StopUINT16Read0 = False/Off/No/Disabled/Stop; 1 = True/On/Yes/Enabled/Auto
IR33doc 30034Front Panel Chiller Control ModeUINT16Read0 = Cool; 1 = Heat; 2 = Ice; 3 = Free Cool
IR34doc 30035Front Panel Chilled Water Setpt0.01 °C per count.INT16× 0.01°CRead
IR35doc 30036Front Panel Current Limit SetpointPercent type: 20,000 = 100 %.INT16× 0.005%Read
IR36doc 30037Front Panel Hot Water Setpt0.01 °C per count.INT16× 0.01°CRead
IR37doc 30038Front Panel Base Loading SetptPercent type: 20,000 = 100 %.INT16× 0.005%Read
IR38doc 30039Front Panel Base Loading CommandUINT16Read0 = False/Off/No/Disabled/Stop; 1 = True/On/Yes/Enabled/Auto
IR39doc 30040External Auto StopUINT16Read0 = False/Off/No/Disabled/Stop; 1 = True/On/Yes/Enabled/Auto
IR40doc 30041Ext Chilled Wtr Setpt0.01 °C per count.INT16× 0.01°CRead
IR41doc 30042Ext Current Limit SetptPercent type: 20,000 = 100 %.INT16× 0.005%Read
IR42doc 30043External Base Loading SetpointPercent type: 20,000 = 100 %.INT16× 0.005%Read
IR43doc 30044Emergency StopUINT16Read0 = False/Off/No/Disabled/Stop; 1 = True/On/Yes/Enabled/Auto
IR44doc 30045Manual Override ExistsUINT16Read0 = False/Off/No/Disabled/Stop; 1 = True/On/Yes/Enabled/Auto
IR45doc 30046Base LoadingUINT16Read0 = False/Off/No/Disabled/Stop; 1 = True/On/Yes/Enabled/Auto
IR46doc 30047Alarm PresentUINT16Read0 = False/Off/No/Disabled/Stop; 1 = True/On/Yes/Enabled/Auto
IR47doc 30048Run EnabledUINT16Read0 = False/Off/No/Disabled/Stop; 1 = True/On/Yes/Enabled/Auto
IR48doc 30049Local Setpoint ControlUINT16Read0 = False/Off/No/Disabled/Stop; 1 = True/On/Yes/Enabled/Auto
IR49doc 30050Maximum Capacity RelayUINT16Read0 = False/Off/No/Disabled/Stop; 1 = True/On/Yes/Enabled/Auto
IR50doc 30051Limit Mode Relay StatusUINT16Read0 = False/Off/No/Disabled/Stop; 1 = True/On/Yes/Enabled/Auto
IR51doc 30052Head Relief Request RelayUINT16Read0 = False/Off/No/Disabled/Stop; 1 = True/On/Yes/Enabled/Auto
IR53doc 30054Refrigerant MonitorUINT16ppmRead
IR54doc 30055Compressor Running Ckt1UINT16Read0 = False/Off/No/Disabled/Stop; 1 = True/On/Yes/Enabled/Auto
IR55doc 30056Evaporator Refrigerant Pressure Ckt1Absolute pressure, 0.1 kPa per count.UINT16× 0.1kPaRead
IR56doc 30057Condenser Refrigerant Pressure Ckt1Absolute pressure, 0.1 kPa per count.UINT16× 0.1kPaRead
IR57doc 30058Differential Refrigerant Pressure Ckt1Pressure type (0.1 kPa per count); the same point is repeated signed at 30187-30190.UINT16× 0.1kPaRead
IR58doc 30059Oil Tank Pressure Ckt1Absolute pressure, 0.1 kPa per count.UINT16× 0.1kPaRead
IR59doc 30060Oil Pump Discharge Pressure Ckt1Absolute pressure, 0.1 kPa per count.UINT16× 0.1kPaRead
IR60doc 30061Oil Differential Pressure Ckt1Pressure type (0.1 kPa per count); the same point is repeated signed at 30187-30190.UINT16× 0.1kPaRead
IR61doc 30062Oil Tank Temperature Ckt10.01 °C per count.INT16× 0.01°CRead
IR62doc 30063Evaporator Saturated Rfgt Temp Ckt10.01 °C per count.INT16× 0.01°CRead
IR63doc 30064Condenser Saturated Rfgt Temp Ckt10.01 °C per count.INT16× 0.01°CRead
IR64doc 30065Compressor Rfgt Discharge Temp Ckt10.01 °C per count.INT16× 0.01°CRead
IR65doc 30066IGV 1 Percent Open Ckt1Percent type: 20,000 = 100 %.INT16× 0.005%Read
IR66doc 30067IGV 2 Percent Open Ckt1Percent type: 20,000 = 100 %.INT16× 0.005%Read
IR67doc 30068Purge Compressor Relay Ckt1UINT16Read0 = False/Off/No/Disabled/Stop; 1 = True/On/Yes/Enabled/Auto
IR68doc 30069Pumpout Relay Ckt1UINT16Read0 = False/Off/No/Disabled/Stop; 1 = True/On/Yes/Enabled/Auto
IR69doc 30070Purge Regen Valve Solenoid Ckt1UINT16Read0 = False/Off/No/Disabled/Stop; 1 = True/On/Yes/Enabled/Auto
IR70doc 30071Purge Carbon Tank Temp Ckt10.01 °C per count.INT16× 0.01°CRead
IR71doc 30072Purge Liquid Temperature Ckt10.01 °C per count.INT16× 0.01°CRead
IR72doc 30073Purge Rfgt Compressor Suction Temp Ckt10.01 °C per count.INT16× 0.01°CRead
IR89doc 30090Starter Voltage Phase AB Ckt1UINT16VRead
IR90doc 30091Starter Voltage Phase BC Ckt1UINT16VRead
IR91doc 30092Starter Voltage Phase CA Ckt1UINT16VRead
IR92doc 30093Starter Average Phase Voltage Ckt1UINT16VRead
IR93doc 30094Starter Current L1 Ckt1UINT16ARead
IR94doc 30095Starter Current L2 Ckt1UINT16ARead
IR95doc 30096Starter Current L3 Ckt1UINT16ARead
IR96doc 30097Average Line Current Ckt1UINT16ARead
IR97doc 30098Starter Current L1 % RLA Ckt1Percent type: 20,000 = 100 %.INT16× 0.005%Read
IR98doc 30099Starter Current L2 % RLA Ckt1Percent type: 20,000 = 100 %.INT16× 0.005%Read
IR99doc 30100Starter Current L3 % RLA Ckt1Percent type: 20,000 = 100 %.INT16× 0.005%Read
IR100doc 30101Average Line Current % RLA Ckt1Percent type: 20,000 = 100 %.INT16× 0.005%Read
IR101doc 30102Starter Power Consumption Ckt1UINT16kWRead
IR102doc 30103Starter Load Power Factor Ckt1Power factor type: 200 = 1.INT16× 0.005Read
IR103doc 30104Inboard Bearing Temperature Ckt10.01 °C per count.INT16× 0.01°CRead
IR104doc 30105Outboard Bearing Temperature Ckt10.01 °C per count.INT16× 0.01°CRead
IR105doc 30106Motor Winding Temp 1 Ckt10.01 °C per count.INT16× 0.01°CRead
IR106doc 30107Motor Winding Temp 2 Ckt10.01 °C per count.INT16× 0.01°CRead
IR107doc 30108Motor Winding Temp 3 Ckt10.01 °C per count.INT16× 0.01°CRead
IR108doc 30109Frequency Ckt1UINT16× 0.1HzRead
IR109doc 30110AFD Transistor Temperature Ckt10.01 °C per count.INT16× 0.01°CRead
IR110doc 30111Compressor Running Ckt2UINT16Read0 = False/Off/No/Disabled/Stop; 1 = True/On/Yes/Enabled/Auto
IR111doc 30112Evaporator Refrigerant Pressure Ckt2Absolute pressure, 0.1 kPa per count.UINT16× 0.1kPaRead
IR112doc 30113Condenser Refrigerant Pressure Ckt2Absolute pressure, 0.1 kPa per count.UINT16× 0.1kPaRead
IR113doc 30114Differential Refrigerant Pressure Ckt2Pressure type (0.1 kPa per count); the same point is repeated signed at 30187-30190.UINT16× 0.1kPaRead
IR114doc 30115Oil Tank Pressure Ckt2Absolute pressure, 0.1 kPa per count.UINT16× 0.1kPaRead
IR115doc 30116Oil Pump Discharge Pressure Ckt2Absolute pressure, 0.1 kPa per count.UINT16× 0.1kPaRead
IR116doc 30117Oil Differential Pressure Ckt2Pressure type (0.1 kPa per count); the same point is repeated signed at 30187-30190.UINT16× 0.1kPaRead
IR117doc 30118Oil Tank Temperature Ckt20.01 °C per count.INT16× 0.01°CRead
IR118doc 30119Evaporator Saturated Rfgt Temp Ckt20.01 °C per count.INT16× 0.01°CRead
IR119doc 30120Condenser Saturated Rfgt Temp Ckt20.01 °C per count.INT16× 0.01°CRead
IR120doc 30121Compressor Rfgt Discharge Temp Ckt20.01 °C per count.INT16× 0.01°CRead
IR121doc 30122IGV 1 Percent Open Ckt2Percent type: 20,000 = 100 %.INT16× 0.005%Read
IR122doc 30123IGV 2 Percent Open Ckt2Percent type: 20,000 = 100 %.INT16× 0.005%Read
IR123doc 30124Purge Compressor Relay Ckt2UINT16Read0 = False/Off/No/Disabled/Stop; 1 = True/On/Yes/Enabled/Auto
IR124doc 30125Pumpout Relay Ckt2UINT16Read0 = False/Off/No/Disabled/Stop; 1 = True/On/Yes/Enabled/Auto
IR125doc 30126Purge Regen Valve Solenoid Ckt2UINT16Read0 = False/Off/No/Disabled/Stop; 1 = True/On/Yes/Enabled/Auto
IR126doc 30127Purge Carbon Tank Temp Ckt20.01 °C per count.INT16× 0.01°CRead
IR127doc 30128Purge Liquid Temperature Ckt20.01 °C per count.INT16× 0.01°CRead
IR128doc 30129Purge Rfgt Compressor Suction Temp Ckt20.01 °C per count.INT16× 0.01°CRead
IR145doc 30146Starter Voltage Phase AB Ckt2UINT16VRead
IR146doc 30147Starter Voltage Phase BC Ckt2UINT16VRead
IR147doc 30148Starter Voltage Phase CA Ckt2UINT16VRead
IR148doc 30149Starter Average Phase Voltage Ckt2UINT16VRead
IR149doc 30150Starter Current L1 Ckt2UINT16ARead
IR150doc 30151Starter Current L2 Ckt2UINT16ARead
IR151doc 30152Starter Current L3 Ckt2UINT16ARead
IR152doc 30153Average Line Current Ckt2UINT16ARead
IR153doc 30154Starter Current L1 % RLA Ckt2Percent type: 20,000 = 100 %.INT16× 0.005%Read
IR154doc 30155Starter Current L2 % RLA Ckt2Percent type: 20,000 = 100 %.INT16× 0.005%Read
IR155doc 30156Starter Current L3 % RLA Ckt2Percent type: 20,000 = 100 %.INT16× 0.005%Read
IR156doc 30157Average Line Current % RLA CktsPercent type: 20,000 = 100 %.INT16× 0.005%Read
IR157doc 30158Starter Power Consumption Ckt2UINT16kWRead
IR158doc 30159Starter Load Power Factor Ckt2Power factor type: 200 = 1.INT16× 0.005Read
IR159doc 30160Inboard Bearing Temperature Ckt20.01 °C per count.INT16× 0.01°CRead
IR160doc 30161Outboard Bearing Temperature Ckt20.01 °C per count.INT16× 0.01°CRead
IR161doc 30162Motor Winding Temperature 1 Ckt20.01 °C per count.INT16× 0.01°CRead
IR162doc 30163Motor Winding Temperature 2 Ckt20.01 °C per count.INT16× 0.01°CRead
IR163doc 30164Motor Winding Temperature 3 Ckt20.01 °C per count.INT16× 0.01°CRead
IR164doc 30165Frequency Ckt2UINT16× 0.1HzRead
IR165doc 30166AFD Transistor Temperature Ckt20.01 °C per count.INT16× 0.01°CRead
IR166doc 30167AFD Input Frequency Ckt1UINT16× 0.1HzRead
IR167doc 30168AFD Average Input Current Ckt1UINT16ARead
IR168doc 30169AFD Output Voltage Ckt1UINT16VRead
IR169doc 30170AFD Input Current L1 Ckt1UINT16ARead
IR170doc 30171AFD Input Current L2 Ckt1UINT16ARead
IR171doc 30172AFD Input Current L3 Ckt1UINT16ARead
IR173doc 30174AFD Inverter Base Temperature Ckt10.01 °C per count.INT16× 0.01°CRead
IR174doc 30175AFD Rectifier Base Temperature Ckt10.01 °C per count.INT16× 0.01°CRead
IR175doc 30176AFD Output Power Ckt1UINT16kWRead
IR176doc 30177AFD Input Frequency Ckt2UINT16× 0.1HzRead
IR177doc 30178AFD Average Input Current Ckt2UINT16ARead
IR178doc 30179AFD Output Voltage Ckt2UINT16VRead
IR179doc 30180AFD Input Current L1 Ckt2UINT16ARead
IR180doc 30181AFD Input Current L2 Ckt2UINT16ARead
IR181doc 30182AFD Input Current L2 Ckt2UINT16ARead
IR183doc 30184AFD Inverter Base Temperature Ckt20.01 °C per count.INT16× 0.01°CRead
IR184doc 30185AFD Rectifier Base Temperature Ckt20.01 °C per count.INT16× 0.01°CRead
IR185doc 30186AFD Output Power Ckt2UINT16kWRead
IR186doc 30187Differential Refrigerant Pressure Ckt1Differential pressure, 0.1 kPa per count.INT16× 0.1kPaRead
IR187doc 30188Differential Refrigerant Pressure Ckt2Differential pressure, 0.1 kPa per count.INT16× 0.1kPaRead
IR188doc 30189Oil Differential Pressure Ckt1Differential pressure, 0.1 kPa per count.INT16× 0.1kPaRead
IR189doc 30190Oil Differential Pressure Ckt2Differential pressure, 0.1 kPa per count.INT16× 0.1kPaRead
IR190doc 30191AFD Motor Voltage U Ckt1UINT16VRead
IR191doc 30192AFD Motor Voltage VCkt1UINT16VRead
IR192doc 30193AFD Motor Voltage WCkt1UINT16VRead
IR193doc 30194AFD IGBT Temperature U Ckt10.01 °C per count.INT16× 0.01°CRead
IR194doc 30195AFD IGBT Temperature V Ckt10.01 °C per count.INT16× 0.01°CRead
IR195doc 30196AFD IGBT Temperature W Ckt10.01 °C per count.INT16× 0.01°CRead
IR196doc 30197AFD Percent RLA Ripple Ckt1Percent type: 20,000 = 100 %.INT16× 0.005%Read
IR197doc 30198DC Bus Voltage Ckt1UINT16VRead
IR198doc 30199AFD Motor Voltage U Ckt2UINT16VRead
IR199doc 30200AFD Motor Voltage V Ckt2UINT16VRead
IR200doc 30201AFD Motor Voltage W Ckt2UINT16VRead
IR201doc 30202AFD IGBT Temperature U Ckt20.01 °C per count.INT16× 0.01°CRead
IR202doc 30203AFD IGBT Temperature V Ckt20.01 °C per count.INT16× 0.01°CRead
IR203doc 30204AFD IGBT Temperature W Ckt20.01 °C per count.INT16× 0.01°CRead
IR204doc 30205AFD Percent RLA Ripple Ckt2Percent type: 20,000 = 100 %.INT16× 0.005%Read
IR205doc 30206DC Bus Voltage Ckt2UINT16VRead
IR206doc 30207Outboard Bearing Pad Temperature 1 Ckt10.01 °C per count.INT16× 0.01°CRead
IR207doc 30208Outboard Bearing Pad Temperature 2 Ckt10.01 °C per count.INT16× 0.01°CRead
IR208doc 30209Outboard Bearing Pad Temperature 3 Ckt10.01 °C per count.INT16× 0.01°CRead
IR209doc 30210Outboard Bearing Pad Temperature 1 Ckt20.01 °C per count.INT16× 0.01°CRead
IR210doc 30211Outboard Bearing Pad Temperature 2 Ckt20.01 °C per count.INT16× 0.01°CRead
IR211doc 30212Outboard Bearing Pad Temperature 3 Ckt20.01 °C per count.INT16× 0.01°CRead
IR212doc 30213Refrigerant TypeUINT16Read0 = R11; 1 = R12; 2 = R22; 3 = R123; 4 = R134a; 5 = R407C; 6 = R410A; 7 = R113; 8 = R114; 9 = R500; 10 = R502; 11 = R404A; 12 = R513A; 13 = R1233zd(E); 14 = R514A; 15 = R1234ze-(E)
IR214doc 30215Frequency Command Ckt1UINT16× 0.1HzRead
IR215doc 30216Frequency Command Ckt2UINT16× 0.1HzRead
HR0doc 40001BAS Chiller Auto Stop CommandUINT16Read/write0 = False/Off/No/Disabled/Stop; 1 = True/On/Yes/Enabled/Auto
HR1doc 40002BAS Chiller Mode CommandUINT16Read/write0 = Cool; 1 = Heat; 2 = Ice; 3 = Free Cool
HR2doc 40003BAS Chilled Water Setpoint0.01 °C per count.INT16× 0.01°CRead/write
HR3doc 40004BAS Current Limit SetpointPercent type: 20,000 = 100 %.INT16× 0.005%Read/write
HR4doc 40005BAS Hot Water Setpoint0.01 °C per count.INT16× 0.01°CRead/write
HR5doc 40006BAS Base Loading SetpointPercent type: 20,000 = 100 %.INT16× 0.005%Read/write
HR6doc 40007BAS Base Loading EnableUINT16Read/write0 = False/Off/No/Disabled/Stop; 1 = True/On/Yes/Enabled/Auto
HR7doc 40008BAS Diagnostic ResetUINT16Read/write0 = False/Off/No/Disabled/Stop; 1 = True/On/Yes/Enabled/Auto
HR8doc 40009Evaporator Pump OverrideUINT16Read/write0 = False/Off/No/Disabled/Stop; 1 = True/On/Yes/Enabled/Auto
HR9doc 40010Condenser Pump OverrideUINT16Read/write0 = False/Off/No/Disabled/Stop; 1 = True/On/Yes/Enabled/Auto
HR10doc 40011Circuit Lockout Ckt1UINT16Read/write0 = Auto; 1 = Locked
HR11doc 40012Circuit Lockout Ckt2UINT16Read/write0 = Auto; 1 = Locked

Notes on this map

Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.

Questions about the Trane CenTraVac CTV-Duplex water-cooled centrifugal chiller (UC800 native Modbus)

What Modbus registers does the Trane CenTraVac CTV-Duplex water-cooled centrifugal chiller (UC800 native Modbus) have?

This map lists 192 registers: 180 input registers, 12 holding registers. 12 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.

Are the Trane CenTraVac CTV-Duplex water-cooled centrifugal chiller (UC800 native Modbus) Modbus addresses 0-based or 1-based?

The manufacturer's document numbers registers Modicon 3xxxx/4xxxx (drop the prefix, subtract 1). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. The list prints Modicon register numbers: 4xxxx are holding registers and 3xxxx input registers, so 40001 is holding register address 0 and 30010 is input register address 9.

What are the minimum Modbus registers to integrate the Trane CenTraVac CTV-Duplex water-cooled centrifugal chiller (UC800 native Modbus)?

Start with IR 2 Chiller Running (Chiller running); IR 25 Chiller Running Status (Chiller running status); IR 10 Evap Leaving Water Temp (Evaporator leaving water temperature); IR 9 Active Cool/Heat Setpoint Temperature (Active cool/heat setpoint); IR 46 Alarm Present (Alarm present); HR 0 BAS Chiller Auto Stop Command (Chiller auto/stop command); HR 1 BAS Chiller Mode Command (Chiller mode command); HR 2 BAS Chilled Water Setpoint (Chilled water setpoint (BAS)); HR 7 BAS Diagnostic Reset (Diagnostic reset).

How do I enable Modbus control of the Trane CenTraVac CTV-Duplex water-cooled centrifugal chiller (UC800 native Modbus)?

The points list does not describe setup; it names BAS-SVP083*-EN as its reference integration guide for enabling Modbus on the controller.

Where is the official Trane CenTraVac CTV-Duplex water-cooled centrifugal chiller (UC800 native Modbus) Modbus documentation?

The source is Symbio 800 Integration Points List, BACnet/Modbus, CTV-Duplex (UC800) (BAS-PTS030A-EN), revision 2024-12-06, published free by Trane at https://elibrary.tranetechnologies.com/public/commercial-hvac/Literature/Points%20List/BAS-PTS030A-EN_12062024.pdf.