Chiller · Modbus register map
Trane CenTraVac CTV-Duplex water-cooled centrifugal chiller (UC800 native Modbus) Modbus register map
Updated 19 November 2026
Trane's Duplex CenTraVac is a two-circuit water-cooled centrifugal chiller. Its Tracer UC800 controller has a native Modbus map in which every point is one 16-bit register with a fixed SI scaling per register type (temperatures in 0.01 °C, pressures in 0.1 kPa, percent in 0.005 % steps). This map covers the BAS command registers and the input registers for water and refrigerant temperatures, pressures, starter and AFD values, bearing and winding temperatures and status enums.
This page lists 192 Modbus registers for the Trane CenTraVac CTV-Duplex water-cooled centrifugal chiller (UC800 native Modbus) — 12 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Trane’s own free documentation (linked below) and checked against it.
- Manufacturer
- Trane
- Model
- CenTraVac CTV-Duplex water-cooled centrifugal chiller (UC800 native Modbus)
- Equipment type
- Chiller
- Registers
- 192 (12 writable)
- Transport
- Modbus RTU, Modbus TCP
- Default unit ID
- Not stated
- Documented addressing
- Modicon 3xxxx/4xxxx (drop the prefix, subtract 1)
- Also known as
- CTV-Duplex, CTVD, CenTraVac Duplex, Duplex CenTraVac UC800
Integration notes: Trane CenTraVac CTV-Duplex water-cooled centrifugal chiller (UC800 native Modbus)
Write 40001 (auto/stop), 40002 (mode) and 40003 (chilled-water setpoint, 0.01 °C) and poll the 3xxxx input registers with function 04. Every value is a single register; apply the per-type scale from the object-format table.
Minimum registers to map
Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.
| Register | Name | Type | Why | Access |
|---|---|---|---|---|
| IR 2 | Chiller Running | UINT16 | Chiller running | Read |
| IR 25 | Chiller Running Status | UINT16 | Chiller running status | Read |
| IR 10 | Evap Leaving Water Temp | INT16 | Evaporator leaving water temperature | Read |
| IR 9 | Active Cool/Heat Setpoint Temperature | INT16 | Active cool/heat setpoint | Read |
| IR 46 | Alarm Present | UINT16 | Alarm present | Read |
| HR 0 | BAS Chiller Auto Stop Command | UINT16 | Chiller auto/stop command | Read/write |
| HR 1 | BAS Chiller Mode Command | UINT16 | Chiller mode command | Read/write |
| HR 2 | BAS Chilled Water Setpoint | INT16 | Chilled water setpoint (BAS) | Read/write |
| HR 7 | BAS Diagnostic Reset | UINT16 | Diagnostic reset | Read/write |
Enable Modbus control & writes
The points list does not describe setup; it names BAS-SVP083*-EN as its reference integration guide for enabling Modbus on the controller.
Byte order & addressing
- Percent registers count in 0.005 % steps (20,000 = 100 %), not 0.1 %.
- Temperatures are signed hundredths of a degree Celsius; pressures are tenths of a kPa.
Network setup
- Unit address, baud and TCP settings are set in the controller's protocol configuration; the list itself gives no defaults.
Watch out for
- Points not supported by the unit's configuration are absent or invalid; the list applies to Duplex (two-compressor) machines.
Trane CenTraVac CTV-Duplex water-cooled centrifugal chiller (UC800 native Modbus) Modbus registers
Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.
| Table | Address | Name | Description | Type | Order | Scale | Units | Access | Values / bits |
|---|---|---|---|---|---|---|---|---|---|
| IR | 0doc 30001 | Software Type | UINT16 | Read | 458 = CTVD | ||||
| IR | 1doc 30002 | Software Revision | UINT16 | Read | |||||
| IR | 2doc 30003 | Chiller Running | UINT16 | Read | 0 = False/Off/No/Disabled/Stop; 1 = True/On/Yes/Enabled/Auto | ||||
| IR | 3doc 30004 | Unit Average Line Current | Percent type: 20,000 = 100 %. | INT16 | × 0.005 | % | Read | ||
| IR | 4doc 30005 | Active Current Limit Setpoint | Percent type: 20,000 = 100 %. | INT16 | × 0.005 | % | Read | ||
| IR | 5doc 30006 | Active Base Loading Setpt | Percent type: 20,000 = 100 %. | INT16 | × 0.005 | % | Read | ||
| IR | 6doc 30007 | Unit Power Consumption | UINT16 | kW | Read | ||||
| IR | 7doc 30008 | Calculated Chiller Capacity | UINT16 | kW | Read | ||||
| IR | 8doc 30009 | Approx Unit Heating Power | UINT16 | kW | Read | ||||
| IR | 9doc 30010 | Active Cool/Heat Setpoint Temperature | 0.01 °C per count. | INT16 | × 0.01 | °C | Read | ||
| IR | 10doc 30011 | Evap Leaving Water Temp | 0.01 °C per count. | INT16 | × 0.01 | °C | Read | ||
| IR | 11doc 30012 | Evap Entering Water Temp | 0.01 °C per count. | INT16 | × 0.01 | °C | Read | ||
| IR | 12doc 30013 | Cond Entering Water Temp | 0.01 °C per count. | INT16 | × 0.01 | °C | Read | ||
| IR | 13doc 30014 | Cond Leaving Water Temp | 0.01 °C per count. | INT16 | × 0.01 | °C | Read | ||
| IR | 14doc 30015 | Evaporator Pump Control | UINT16 | Read | 0 = False/Off/No/Disabled/Stop; 1 = True/On/Yes/Enabled/Auto | ||||
| IR | 15doc 30016 | Evaporator Water Flow | UINT16 | Read | 0 = False/Off/No/Disabled/Stop; 1 = True/On/Yes/Enabled/Auto | ||||
| IR | 16doc 30017 | Approx Evap Water Flow | UINT16 | L/min | Read | ||||
| IR | 17doc 30018 | Evap Differential Wtr Press | Absolute pressure, 0.1 kPa per count. | UINT16 | × 0.1 | kPa | Read | ||
| IR | 18doc 30019 | Condenser Pump Control | UINT16 | Read | 0 = False/Off/No/Disabled/Stop; 1 = True/On/Yes/Enabled/Auto | ||||
| IR | 19doc 30020 | Condenser Water Flow | UINT16 | Read | 0 = False/Off/No/Disabled/Stop; 1 = True/On/Yes/Enabled/Auto | ||||
| IR | 20doc 30021 | Approx Cond Water Flow | UINT16 | L/min | Read | ||||
| IR | 21doc 30022 | Cond Differential Wtr Press | Absolute pressure, 0.1 kPa per count. | UINT16 | × 0.1 | kPa | Read | ||
| IR | 22doc 30023 | Second Condenser Entering Water Temperature | 0.01 °C per count. | INT16 | × 0.01 | °C | Read | ||
| IR | 23doc 30024 | Second Condenser Leaving Water Temperature | 0.01 °C per count. | INT16 | × 0.01 | °C | Read | ||
| IR | 24doc 30025 | Last Diagnostic Code | UINT16 | Read | |||||
| IR | 25doc 30026 | Chiller Running Status | UINT16 | Read | 0 = Off/Idle (Auto); 1 = Starting; 2 = Running; 3 = Stopping | ||||
| IR | 26doc 30027 | Chiller Control Mode | UINT16 | Read | 0 = Cool; 1 = Heat; 2 = Ice; 3 = Free Cool | ||||
| IR | 27doc 30028 | Setpoint Source | UINT16 | Read | 0 = BAS+External+Loc al; 1 = External+Local; 2 = Local | ||||
| IR | 28doc 30029 | Active Chilled Water Setpoint Source | UINT16 | Read | 0 = Front Panel; 1 = External; 2 = Ice Machine; 3 = BAS | ||||
| IR | 29doc 30030 | Active Current Limit Setpoint Source | UINT16 | Read | 0 = Front Panel; 1 = External; 2 = Ice Machiine; 3 = BAS | ||||
| IR | 30doc 30031 | Active Base Loading Setpoint Source | UINT16 | Read | 0 = Front Panel; 1 = External; 2 = Ice Machiine; 3 = BAS | ||||
| IR | 31doc 30032 | Active Hot Water Setpoint Source | UINT16 | Read | 0 = Front Panel; 1 = External; 2 = Ice Machiine; 3 = BAS | ||||
| IR | 32doc 30033 | Front Panel Auto/Stop | UINT16 | Read | 0 = False/Off/No/Disabled/Stop; 1 = True/On/Yes/Enabled/Auto | ||||
| IR | 33doc 30034 | Front Panel Chiller Control Mode | UINT16 | Read | 0 = Cool; 1 = Heat; 2 = Ice; 3 = Free Cool | ||||
| IR | 34doc 30035 | Front Panel Chilled Water Setpt | 0.01 °C per count. | INT16 | × 0.01 | °C | Read | ||
| IR | 35doc 30036 | Front Panel Current Limit Setpoint | Percent type: 20,000 = 100 %. | INT16 | × 0.005 | % | Read | ||
| IR | 36doc 30037 | Front Panel Hot Water Setpt | 0.01 °C per count. | INT16 | × 0.01 | °C | Read | ||
| IR | 37doc 30038 | Front Panel Base Loading Setpt | Percent type: 20,000 = 100 %. | INT16 | × 0.005 | % | Read | ||
| IR | 38doc 30039 | Front Panel Base Loading Command | UINT16 | Read | 0 = False/Off/No/Disabled/Stop; 1 = True/On/Yes/Enabled/Auto | ||||
| IR | 39doc 30040 | External Auto Stop | UINT16 | Read | 0 = False/Off/No/Disabled/Stop; 1 = True/On/Yes/Enabled/Auto | ||||
| IR | 40doc 30041 | Ext Chilled Wtr Setpt | 0.01 °C per count. | INT16 | × 0.01 | °C | Read | ||
| IR | 41doc 30042 | Ext Current Limit Setpt | Percent type: 20,000 = 100 %. | INT16 | × 0.005 | % | Read | ||
| IR | 42doc 30043 | External Base Loading Setpoint | Percent type: 20,000 = 100 %. | INT16 | × 0.005 | % | Read | ||
| IR | 43doc 30044 | Emergency Stop | UINT16 | Read | 0 = False/Off/No/Disabled/Stop; 1 = True/On/Yes/Enabled/Auto | ||||
| IR | 44doc 30045 | Manual Override Exists | UINT16 | Read | 0 = False/Off/No/Disabled/Stop; 1 = True/On/Yes/Enabled/Auto | ||||
| IR | 45doc 30046 | Base Loading | UINT16 | Read | 0 = False/Off/No/Disabled/Stop; 1 = True/On/Yes/Enabled/Auto | ||||
| IR | 46doc 30047 | Alarm Present | UINT16 | Read | 0 = False/Off/No/Disabled/Stop; 1 = True/On/Yes/Enabled/Auto | ||||
| IR | 47doc 30048 | Run Enabled | UINT16 | Read | 0 = False/Off/No/Disabled/Stop; 1 = True/On/Yes/Enabled/Auto | ||||
| IR | 48doc 30049 | Local Setpoint Control | UINT16 | Read | 0 = False/Off/No/Disabled/Stop; 1 = True/On/Yes/Enabled/Auto | ||||
| IR | 49doc 30050 | Maximum Capacity Relay | UINT16 | Read | 0 = False/Off/No/Disabled/Stop; 1 = True/On/Yes/Enabled/Auto | ||||
| IR | 50doc 30051 | Limit Mode Relay Status | UINT16 | Read | 0 = False/Off/No/Disabled/Stop; 1 = True/On/Yes/Enabled/Auto | ||||
| IR | 51doc 30052 | Head Relief Request Relay | UINT16 | Read | 0 = False/Off/No/Disabled/Stop; 1 = True/On/Yes/Enabled/Auto | ||||
| IR | 53doc 30054 | Refrigerant Monitor | UINT16 | ppm | Read | ||||
| IR | 54doc 30055 | Compressor Running Ckt1 | UINT16 | Read | 0 = False/Off/No/Disabled/Stop; 1 = True/On/Yes/Enabled/Auto | ||||
| IR | 55doc 30056 | Evaporator Refrigerant Pressure Ckt1 | Absolute pressure, 0.1 kPa per count. | UINT16 | × 0.1 | kPa | Read | ||
| IR | 56doc 30057 | Condenser Refrigerant Pressure Ckt1 | Absolute pressure, 0.1 kPa per count. | UINT16 | × 0.1 | kPa | Read | ||
| IR | 57doc 30058 | Differential Refrigerant Pressure Ckt1 | Pressure type (0.1 kPa per count); the same point is repeated signed at 30187-30190. | UINT16 | × 0.1 | kPa | Read | ||
| IR | 58doc 30059 | Oil Tank Pressure Ckt1 | Absolute pressure, 0.1 kPa per count. | UINT16 | × 0.1 | kPa | Read | ||
| IR | 59doc 30060 | Oil Pump Discharge Pressure Ckt1 | Absolute pressure, 0.1 kPa per count. | UINT16 | × 0.1 | kPa | Read | ||
| IR | 60doc 30061 | Oil Differential Pressure Ckt1 | Pressure type (0.1 kPa per count); the same point is repeated signed at 30187-30190. | UINT16 | × 0.1 | kPa | Read | ||
| IR | 61doc 30062 | Oil Tank Temperature Ckt1 | 0.01 °C per count. | INT16 | × 0.01 | °C | Read | ||
| IR | 62doc 30063 | Evaporator Saturated Rfgt Temp Ckt1 | 0.01 °C per count. | INT16 | × 0.01 | °C | Read | ||
| IR | 63doc 30064 | Condenser Saturated Rfgt Temp Ckt1 | 0.01 °C per count. | INT16 | × 0.01 | °C | Read | ||
| IR | 64doc 30065 | Compressor Rfgt Discharge Temp Ckt1 | 0.01 °C per count. | INT16 | × 0.01 | °C | Read | ||
| IR | 65doc 30066 | IGV 1 Percent Open Ckt1 | Percent type: 20,000 = 100 %. | INT16 | × 0.005 | % | Read | ||
| IR | 66doc 30067 | IGV 2 Percent Open Ckt1 | Percent type: 20,000 = 100 %. | INT16 | × 0.005 | % | Read | ||
| IR | 67doc 30068 | Purge Compressor Relay Ckt1 | UINT16 | Read | 0 = False/Off/No/Disabled/Stop; 1 = True/On/Yes/Enabled/Auto | ||||
| IR | 68doc 30069 | Pumpout Relay Ckt1 | UINT16 | Read | 0 = False/Off/No/Disabled/Stop; 1 = True/On/Yes/Enabled/Auto | ||||
| IR | 69doc 30070 | Purge Regen Valve Solenoid Ckt1 | UINT16 | Read | 0 = False/Off/No/Disabled/Stop; 1 = True/On/Yes/Enabled/Auto | ||||
| IR | 70doc 30071 | Purge Carbon Tank Temp Ckt1 | 0.01 °C per count. | INT16 | × 0.01 | °C | Read | ||
| IR | 71doc 30072 | Purge Liquid Temperature Ckt1 | 0.01 °C per count. | INT16 | × 0.01 | °C | Read | ||
| IR | 72doc 30073 | Purge Rfgt Compressor Suction Temp Ckt1 | 0.01 °C per count. | INT16 | × 0.01 | °C | Read | ||
| IR | 89doc 30090 | Starter Voltage Phase AB Ckt1 | UINT16 | V | Read | ||||
| IR | 90doc 30091 | Starter Voltage Phase BC Ckt1 | UINT16 | V | Read | ||||
| IR | 91doc 30092 | Starter Voltage Phase CA Ckt1 | UINT16 | V | Read | ||||
| IR | 92doc 30093 | Starter Average Phase Voltage Ckt1 | UINT16 | V | Read | ||||
| IR | 93doc 30094 | Starter Current L1 Ckt1 | UINT16 | A | Read | ||||
| IR | 94doc 30095 | Starter Current L2 Ckt1 | UINT16 | A | Read | ||||
| IR | 95doc 30096 | Starter Current L3 Ckt1 | UINT16 | A | Read | ||||
| IR | 96doc 30097 | Average Line Current Ckt1 | UINT16 | A | Read | ||||
| IR | 97doc 30098 | Starter Current L1 % RLA Ckt1 | Percent type: 20,000 = 100 %. | INT16 | × 0.005 | % | Read | ||
| IR | 98doc 30099 | Starter Current L2 % RLA Ckt1 | Percent type: 20,000 = 100 %. | INT16 | × 0.005 | % | Read | ||
| IR | 99doc 30100 | Starter Current L3 % RLA Ckt1 | Percent type: 20,000 = 100 %. | INT16 | × 0.005 | % | Read | ||
| IR | 100doc 30101 | Average Line Current % RLA Ckt1 | Percent type: 20,000 = 100 %. | INT16 | × 0.005 | % | Read | ||
| IR | 101doc 30102 | Starter Power Consumption Ckt1 | UINT16 | kW | Read | ||||
| IR | 102doc 30103 | Starter Load Power Factor Ckt1 | Power factor type: 200 = 1. | INT16 | × 0.005 | Read | |||
| IR | 103doc 30104 | Inboard Bearing Temperature Ckt1 | 0.01 °C per count. | INT16 | × 0.01 | °C | Read | ||
| IR | 104doc 30105 | Outboard Bearing Temperature Ckt1 | 0.01 °C per count. | INT16 | × 0.01 | °C | Read | ||
| IR | 105doc 30106 | Motor Winding Temp 1 Ckt1 | 0.01 °C per count. | INT16 | × 0.01 | °C | Read | ||
| IR | 106doc 30107 | Motor Winding Temp 2 Ckt1 | 0.01 °C per count. | INT16 | × 0.01 | °C | Read | ||
| IR | 107doc 30108 | Motor Winding Temp 3 Ckt1 | 0.01 °C per count. | INT16 | × 0.01 | °C | Read | ||
| IR | 108doc 30109 | Frequency Ckt1 | UINT16 | × 0.1 | Hz | Read | |||
| IR | 109doc 30110 | AFD Transistor Temperature Ckt1 | 0.01 °C per count. | INT16 | × 0.01 | °C | Read | ||
| IR | 110doc 30111 | Compressor Running Ckt2 | UINT16 | Read | 0 = False/Off/No/Disabled/Stop; 1 = True/On/Yes/Enabled/Auto | ||||
| IR | 111doc 30112 | Evaporator Refrigerant Pressure Ckt2 | Absolute pressure, 0.1 kPa per count. | UINT16 | × 0.1 | kPa | Read | ||
| IR | 112doc 30113 | Condenser Refrigerant Pressure Ckt2 | Absolute pressure, 0.1 kPa per count. | UINT16 | × 0.1 | kPa | Read | ||
| IR | 113doc 30114 | Differential Refrigerant Pressure Ckt2 | Pressure type (0.1 kPa per count); the same point is repeated signed at 30187-30190. | UINT16 | × 0.1 | kPa | Read | ||
| IR | 114doc 30115 | Oil Tank Pressure Ckt2 | Absolute pressure, 0.1 kPa per count. | UINT16 | × 0.1 | kPa | Read | ||
| IR | 115doc 30116 | Oil Pump Discharge Pressure Ckt2 | Absolute pressure, 0.1 kPa per count. | UINT16 | × 0.1 | kPa | Read | ||
| IR | 116doc 30117 | Oil Differential Pressure Ckt2 | Pressure type (0.1 kPa per count); the same point is repeated signed at 30187-30190. | UINT16 | × 0.1 | kPa | Read | ||
| IR | 117doc 30118 | Oil Tank Temperature Ckt2 | 0.01 °C per count. | INT16 | × 0.01 | °C | Read | ||
| IR | 118doc 30119 | Evaporator Saturated Rfgt Temp Ckt2 | 0.01 °C per count. | INT16 | × 0.01 | °C | Read | ||
| IR | 119doc 30120 | Condenser Saturated Rfgt Temp Ckt2 | 0.01 °C per count. | INT16 | × 0.01 | °C | Read | ||
| IR | 120doc 30121 | Compressor Rfgt Discharge Temp Ckt2 | 0.01 °C per count. | INT16 | × 0.01 | °C | Read | ||
| IR | 121doc 30122 | IGV 1 Percent Open Ckt2 | Percent type: 20,000 = 100 %. | INT16 | × 0.005 | % | Read | ||
| IR | 122doc 30123 | IGV 2 Percent Open Ckt2 | Percent type: 20,000 = 100 %. | INT16 | × 0.005 | % | Read | ||
| IR | 123doc 30124 | Purge Compressor Relay Ckt2 | UINT16 | Read | 0 = False/Off/No/Disabled/Stop; 1 = True/On/Yes/Enabled/Auto | ||||
| IR | 124doc 30125 | Pumpout Relay Ckt2 | UINT16 | Read | 0 = False/Off/No/Disabled/Stop; 1 = True/On/Yes/Enabled/Auto | ||||
| IR | 125doc 30126 | Purge Regen Valve Solenoid Ckt2 | UINT16 | Read | 0 = False/Off/No/Disabled/Stop; 1 = True/On/Yes/Enabled/Auto | ||||
| IR | 126doc 30127 | Purge Carbon Tank Temp Ckt2 | 0.01 °C per count. | INT16 | × 0.01 | °C | Read | ||
| IR | 127doc 30128 | Purge Liquid Temperature Ckt2 | 0.01 °C per count. | INT16 | × 0.01 | °C | Read | ||
| IR | 128doc 30129 | Purge Rfgt Compressor Suction Temp Ckt2 | 0.01 °C per count. | INT16 | × 0.01 | °C | Read | ||
| IR | 145doc 30146 | Starter Voltage Phase AB Ckt2 | UINT16 | V | Read | ||||
| IR | 146doc 30147 | Starter Voltage Phase BC Ckt2 | UINT16 | V | Read | ||||
| IR | 147doc 30148 | Starter Voltage Phase CA Ckt2 | UINT16 | V | Read | ||||
| IR | 148doc 30149 | Starter Average Phase Voltage Ckt2 | UINT16 | V | Read | ||||
| IR | 149doc 30150 | Starter Current L1 Ckt2 | UINT16 | A | Read | ||||
| IR | 150doc 30151 | Starter Current L2 Ckt2 | UINT16 | A | Read | ||||
| IR | 151doc 30152 | Starter Current L3 Ckt2 | UINT16 | A | Read | ||||
| IR | 152doc 30153 | Average Line Current Ckt2 | UINT16 | A | Read | ||||
| IR | 153doc 30154 | Starter Current L1 % RLA Ckt2 | Percent type: 20,000 = 100 %. | INT16 | × 0.005 | % | Read | ||
| IR | 154doc 30155 | Starter Current L2 % RLA Ckt2 | Percent type: 20,000 = 100 %. | INT16 | × 0.005 | % | Read | ||
| IR | 155doc 30156 | Starter Current L3 % RLA Ckt2 | Percent type: 20,000 = 100 %. | INT16 | × 0.005 | % | Read | ||
| IR | 156doc 30157 | Average Line Current % RLA Ckts | Percent type: 20,000 = 100 %. | INT16 | × 0.005 | % | Read | ||
| IR | 157doc 30158 | Starter Power Consumption Ckt2 | UINT16 | kW | Read | ||||
| IR | 158doc 30159 | Starter Load Power Factor Ckt2 | Power factor type: 200 = 1. | INT16 | × 0.005 | Read | |||
| IR | 159doc 30160 | Inboard Bearing Temperature Ckt2 | 0.01 °C per count. | INT16 | × 0.01 | °C | Read | ||
| IR | 160doc 30161 | Outboard Bearing Temperature Ckt2 | 0.01 °C per count. | INT16 | × 0.01 | °C | Read | ||
| IR | 161doc 30162 | Motor Winding Temperature 1 Ckt2 | 0.01 °C per count. | INT16 | × 0.01 | °C | Read | ||
| IR | 162doc 30163 | Motor Winding Temperature 2 Ckt2 | 0.01 °C per count. | INT16 | × 0.01 | °C | Read | ||
| IR | 163doc 30164 | Motor Winding Temperature 3 Ckt2 | 0.01 °C per count. | INT16 | × 0.01 | °C | Read | ||
| IR | 164doc 30165 | Frequency Ckt2 | UINT16 | × 0.1 | Hz | Read | |||
| IR | 165doc 30166 | AFD Transistor Temperature Ckt2 | 0.01 °C per count. | INT16 | × 0.01 | °C | Read | ||
| IR | 166doc 30167 | AFD Input Frequency Ckt1 | UINT16 | × 0.1 | Hz | Read | |||
| IR | 167doc 30168 | AFD Average Input Current Ckt1 | UINT16 | A | Read | ||||
| IR | 168doc 30169 | AFD Output Voltage Ckt1 | UINT16 | V | Read | ||||
| IR | 169doc 30170 | AFD Input Current L1 Ckt1 | UINT16 | A | Read | ||||
| IR | 170doc 30171 | AFD Input Current L2 Ckt1 | UINT16 | A | Read | ||||
| IR | 171doc 30172 | AFD Input Current L3 Ckt1 | UINT16 | A | Read | ||||
| IR | 173doc 30174 | AFD Inverter Base Temperature Ckt1 | 0.01 °C per count. | INT16 | × 0.01 | °C | Read | ||
| IR | 174doc 30175 | AFD Rectifier Base Temperature Ckt1 | 0.01 °C per count. | INT16 | × 0.01 | °C | Read | ||
| IR | 175doc 30176 | AFD Output Power Ckt1 | UINT16 | kW | Read | ||||
| IR | 176doc 30177 | AFD Input Frequency Ckt2 | UINT16 | × 0.1 | Hz | Read | |||
| IR | 177doc 30178 | AFD Average Input Current Ckt2 | UINT16 | A | Read | ||||
| IR | 178doc 30179 | AFD Output Voltage Ckt2 | UINT16 | V | Read | ||||
| IR | 179doc 30180 | AFD Input Current L1 Ckt2 | UINT16 | A | Read | ||||
| IR | 180doc 30181 | AFD Input Current L2 Ckt2 | UINT16 | A | Read | ||||
| IR | 181doc 30182 | AFD Input Current L2 Ckt2 | UINT16 | A | Read | ||||
| IR | 183doc 30184 | AFD Inverter Base Temperature Ckt2 | 0.01 °C per count. | INT16 | × 0.01 | °C | Read | ||
| IR | 184doc 30185 | AFD Rectifier Base Temperature Ckt2 | 0.01 °C per count. | INT16 | × 0.01 | °C | Read | ||
| IR | 185doc 30186 | AFD Output Power Ckt2 | UINT16 | kW | Read | ||||
| IR | 186doc 30187 | Differential Refrigerant Pressure Ckt1 | Differential pressure, 0.1 kPa per count. | INT16 | × 0.1 | kPa | Read | ||
| IR | 187doc 30188 | Differential Refrigerant Pressure Ckt2 | Differential pressure, 0.1 kPa per count. | INT16 | × 0.1 | kPa | Read | ||
| IR | 188doc 30189 | Oil Differential Pressure Ckt1 | Differential pressure, 0.1 kPa per count. | INT16 | × 0.1 | kPa | Read | ||
| IR | 189doc 30190 | Oil Differential Pressure Ckt2 | Differential pressure, 0.1 kPa per count. | INT16 | × 0.1 | kPa | Read | ||
| IR | 190doc 30191 | AFD Motor Voltage U Ckt1 | UINT16 | V | Read | ||||
| IR | 191doc 30192 | AFD Motor Voltage VCkt1 | UINT16 | V | Read | ||||
| IR | 192doc 30193 | AFD Motor Voltage WCkt1 | UINT16 | V | Read | ||||
| IR | 193doc 30194 | AFD IGBT Temperature U Ckt1 | 0.01 °C per count. | INT16 | × 0.01 | °C | Read | ||
| IR | 194doc 30195 | AFD IGBT Temperature V Ckt1 | 0.01 °C per count. | INT16 | × 0.01 | °C | Read | ||
| IR | 195doc 30196 | AFD IGBT Temperature W Ckt1 | 0.01 °C per count. | INT16 | × 0.01 | °C | Read | ||
| IR | 196doc 30197 | AFD Percent RLA Ripple Ckt1 | Percent type: 20,000 = 100 %. | INT16 | × 0.005 | % | Read | ||
| IR | 197doc 30198 | DC Bus Voltage Ckt1 | UINT16 | V | Read | ||||
| IR | 198doc 30199 | AFD Motor Voltage U Ckt2 | UINT16 | V | Read | ||||
| IR | 199doc 30200 | AFD Motor Voltage V Ckt2 | UINT16 | V | Read | ||||
| IR | 200doc 30201 | AFD Motor Voltage W Ckt2 | UINT16 | V | Read | ||||
| IR | 201doc 30202 | AFD IGBT Temperature U Ckt2 | 0.01 °C per count. | INT16 | × 0.01 | °C | Read | ||
| IR | 202doc 30203 | AFD IGBT Temperature V Ckt2 | 0.01 °C per count. | INT16 | × 0.01 | °C | Read | ||
| IR | 203doc 30204 | AFD IGBT Temperature W Ckt2 | 0.01 °C per count. | INT16 | × 0.01 | °C | Read | ||
| IR | 204doc 30205 | AFD Percent RLA Ripple Ckt2 | Percent type: 20,000 = 100 %. | INT16 | × 0.005 | % | Read | ||
| IR | 205doc 30206 | DC Bus Voltage Ckt2 | UINT16 | V | Read | ||||
| IR | 206doc 30207 | Outboard Bearing Pad Temperature 1 Ckt1 | 0.01 °C per count. | INT16 | × 0.01 | °C | Read | ||
| IR | 207doc 30208 | Outboard Bearing Pad Temperature 2 Ckt1 | 0.01 °C per count. | INT16 | × 0.01 | °C | Read | ||
| IR | 208doc 30209 | Outboard Bearing Pad Temperature 3 Ckt1 | 0.01 °C per count. | INT16 | × 0.01 | °C | Read | ||
| IR | 209doc 30210 | Outboard Bearing Pad Temperature 1 Ckt2 | 0.01 °C per count. | INT16 | × 0.01 | °C | Read | ||
| IR | 210doc 30211 | Outboard Bearing Pad Temperature 2 Ckt2 | 0.01 °C per count. | INT16 | × 0.01 | °C | Read | ||
| IR | 211doc 30212 | Outboard Bearing Pad Temperature 3 Ckt2 | 0.01 °C per count. | INT16 | × 0.01 | °C | Read | ||
| IR | 212doc 30213 | Refrigerant Type | UINT16 | Read | 0 = R11; 1 = R12; 2 = R22; 3 = R123; 4 = R134a; 5 = R407C; 6 = R410A; 7 = R113; 8 = R114; 9 = R500; 10 = R502; 11 = R404A; 12 = R513A; 13 = R1233zd(E); 14 = R514A; 15 = R1234ze-(E) | ||||
| IR | 214doc 30215 | Frequency Command Ckt1 | UINT16 | × 0.1 | Hz | Read | |||
| IR | 215doc 30216 | Frequency Command Ckt2 | UINT16 | × 0.1 | Hz | Read | |||
| HR | 0doc 40001 | BAS Chiller Auto Stop Command | UINT16 | Read/write | 0 = False/Off/No/Disabled/Stop; 1 = True/On/Yes/Enabled/Auto | ||||
| HR | 1doc 40002 | BAS Chiller Mode Command | UINT16 | Read/write | 0 = Cool; 1 = Heat; 2 = Ice; 3 = Free Cool | ||||
| HR | 2doc 40003 | BAS Chilled Water Setpoint | 0.01 °C per count. | INT16 | × 0.01 | °C | Read/write | ||
| HR | 3doc 40004 | BAS Current Limit Setpoint | Percent type: 20,000 = 100 %. | INT16 | × 0.005 | % | Read/write | ||
| HR | 4doc 40005 | BAS Hot Water Setpoint | 0.01 °C per count. | INT16 | × 0.01 | °C | Read/write | ||
| HR | 5doc 40006 | BAS Base Loading Setpoint | Percent type: 20,000 = 100 %. | INT16 | × 0.005 | % | Read/write | ||
| HR | 6doc 40007 | BAS Base Loading Enable | UINT16 | Read/write | 0 = False/Off/No/Disabled/Stop; 1 = True/On/Yes/Enabled/Auto | ||||
| HR | 7doc 40008 | BAS Diagnostic Reset | UINT16 | Read/write | 0 = False/Off/No/Disabled/Stop; 1 = True/On/Yes/Enabled/Auto | ||||
| HR | 8doc 40009 | Evaporator Pump Override | UINT16 | Read/write | 0 = False/Off/No/Disabled/Stop; 1 = True/On/Yes/Enabled/Auto | ||||
| HR | 9doc 40010 | Condenser Pump Override | UINT16 | Read/write | 0 = False/Off/No/Disabled/Stop; 1 = True/On/Yes/Enabled/Auto | ||||
| HR | 10doc 40011 | Circuit Lockout Ckt1 | UINT16 | Read/write | 0 = Auto; 1 = Locked | ||||
| HR | 11doc 40012 | Circuit Lockout Ckt2 | UINT16 | Read/write | 0 = Auto; 1 = Locked |
Notes on this map
- The object-format table gives one fixed encoding per register type: Binary/Enumeration/Current/Voltage/Power/Concentration/Frequency/Flow/Pressure are unsigned 16-bit; Percent, Power Factor, Differential Pressure and Temperature are signed 16-bit. Scales: Temperature 0.01 °C, Pressure and Differential Pressure 0.1 kPa (printed as absolute for both), Percent 0.005 % (20,000 = 100 %), Power Factor 0.005, Frequency 0.1 Hz, Flow water L/min, Flow air L/s, Power kW, Current A, Voltage V.
- Values are always SI in this native map; there is no I-P switch in the list.
- Left out: all Time Interval points (purge timers, pumpout counters, refrigeration life, compressor running time). They are 32-bit (u32) over two registers and the list does not state the word order.
- Left out: Compressor Starts Ckt1/Ckt2 (30086, 30142). Their type 'Count' is not defined in the object-format table and they span two registers.
- Left out: Circuit Available Ckt1/Ckt2 (30217, 30218), printed with no register type.
- Differential refrigerant pressure and oil differential pressure appear twice: 30058/30061 (Ckt1) and 30114/30117 (Ckt2) use the Pressure type, and 30187-30190 repeat them with the signed Differential Pressure type.
- Last Diagnostic Code (30025) points to the diagnostic list in the BACnet part of the document; codes are not reproduced.
- BAS-PTS029A-EN (CTV-Simplex UC800) carries a Modbus section that is essentially the same Duplex table (Software Type 458 = CTVD), so no separate Simplex map is made from it.
- The points list does not name the Modbus transport (RTU or TCP); it refers to BAS-SVP083*-EN for protocol setup, so confirm the transport in the controller configuration.
- 30181 and 30182 are both printed as 'AFD Input Current L2 Ckt2'; the names are kept as printed.
Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.
Questions about the Trane CenTraVac CTV-Duplex water-cooled centrifugal chiller (UC800 native Modbus)
What Modbus registers does the Trane CenTraVac CTV-Duplex water-cooled centrifugal chiller (UC800 native Modbus) have?
This map lists 192 registers: 180 input registers, 12 holding registers. 12 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.
Are the Trane CenTraVac CTV-Duplex water-cooled centrifugal chiller (UC800 native Modbus) Modbus addresses 0-based or 1-based?
The manufacturer's document numbers registers Modicon 3xxxx/4xxxx (drop the prefix, subtract 1). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. The list prints Modicon register numbers: 4xxxx are holding registers and 3xxxx input registers, so 40001 is holding register address 0 and 30010 is input register address 9.
What are the minimum Modbus registers to integrate the Trane CenTraVac CTV-Duplex water-cooled centrifugal chiller (UC800 native Modbus)?
Start with IR 2 Chiller Running (Chiller running); IR 25 Chiller Running Status (Chiller running status); IR 10 Evap Leaving Water Temp (Evaporator leaving water temperature); IR 9 Active Cool/Heat Setpoint Temperature (Active cool/heat setpoint); IR 46 Alarm Present (Alarm present); HR 0 BAS Chiller Auto Stop Command (Chiller auto/stop command); HR 1 BAS Chiller Mode Command (Chiller mode command); HR 2 BAS Chilled Water Setpoint (Chilled water setpoint (BAS)); HR 7 BAS Diagnostic Reset (Diagnostic reset).
How do I enable Modbus control of the Trane CenTraVac CTV-Duplex water-cooled centrifugal chiller (UC800 native Modbus)?
The points list does not describe setup; it names BAS-SVP083*-EN as its reference integration guide for enabling Modbus on the controller.
Where is the official Trane CenTraVac CTV-Duplex water-cooled centrifugal chiller (UC800 native Modbus) Modbus documentation?
The source is Symbio 800 Integration Points List, BACnet/Modbus, CTV-Duplex (UC800) (BAS-PTS030A-EN), revision 2024-12-06, published free by Trane at https://elibrary.tranetechnologies.com/public/commercial-hvac/Literature/Points%20List/BAS-PTS030A-EN_12062024.pdf.
More Trane Modbus register maps
- Chiller
Trane Agility water-cooled centrifugal chiller (Symbio 800)
Trane Agility water-cooled chillers with Symbio 800 controls, as listed in BAS-PTS007C-EN (6/30/2026).
Also known as: Agility, HDWA, Agility water-cooled chiller - Chiller
Trane Ascend ACR Series C air-cooled chiller (Symbio 800)
Trane Ascend model ACR Series C air-cooled chillers with the Symbio 800 controller, as listed in BAS-PTS021A-EN (11/15/2024).
Also known as: ACR, Ascend ACR, ACR Series C, Ascend air-cooled chiller ACR - Chiller
Trane Ascend ACS / ACX air-cooled scroll chiller and heat pump (Symbio 800)
Trane Ascend ACS air-cooled scroll chillers and ACX air-to-water heat pumps with the Symbio 800 controller, as listed in BAS-PTS011A-EN (11/15/2024).
Also known as: ACS, ACX, Ascend ACS, Ascend ACX, Ascend air-cooled chiller, Ascend air-to-water heat pump - Chiller
Trane CenTraVac duplex centrifugal chiller (Symbio 800)
Trane dual-compressor (duplex) CenTraVac water-cooled centrifugal chillers fitted with the Symbio 800 controller, as listed in the Duplex tables of BAS-PTS009C-EN (12/12/2025).
Also known as: CDHF, CDHG, CDHH, CenTraVac Duplex Symbio 800 - Chiller
Trane CenTraVac simplex centrifugal chiller (Symbio 800)
Trane single-compressor (simplex) CenTraVac water-cooled centrifugal chillers fitted with the Symbio 800 controller, as listed in the Simplex tables of BAS-PTS009C-EN (12/12/2025).
Also known as: CVHE, CVHF, CVHG, CVHH, CVHL, CVHM, CVHS, CVGF, CVR, CVZA, CVXA, CenTraVac Simplex Symbio 800, CenTraVac simplex - Chiller
Trane CGAM air-cooled scroll chiller (Symbio 800)
Trane CGAM air-cooled scroll chillers with the Symbio 800 controller, as listed in BAS-PTS019A-EN (11/15/2024).
Also known as: CGAM, Trane CGAM, CGAM air-cooled scroll chiller - Chiller
Trane RTAC air-cooled helical-rotary chiller (Symbio 800)
Trane RTAC air-cooled helical-rotary chillers with the Symbio 800 controller, as listed in BAS-PTS023A-EN (11/8/2024).
Also known as: RTAC, Series R RTAC - Chiller
Trane RTAC air-cooled helical-rotary chiller (UC800 native Modbus profile)
Trane RTAC air-cooled chillers on the Tracer UC800 controller using the UC800 native Modbus map in the Modbus section of BAS-PTS032A-EN (12/6/2024). Not the same register set as the Symbio 800 RTAC list (BAS-PTS023A-EN).
Also known as: RTAC UC800 native Modbus profile, Series R RTAC UC800 native Modbus, BAS-PTS032A-EN - Chiller
Trane Series R RTHD water-cooled helical-rotary chiller (Symbio 800)
Trane Series R model RTHD water-cooled helical-rotary chillers with the Symbio 800 controller, as listed in BAS-PTS015A-EN (11/15/2024).
Also known as: RTHD, Series R RTHD - Chiller
Trane Series R RTWD water-cooled helical-rotary chiller (Symbio 800)
Trane Series R model RTWD water-cooled helical-rotary chillers with the Symbio 800 controller, as listed in BAS-PTS017A-EN (11/15/2024).
Also known as: RTWD, Series R RTWD, RTUD - Chiller
Trane Sintesis RTAF air-cooled screw chiller (Symbio 800)
Trane Sintesis RTAF air-cooled helical-rotary chillers with the Symbio 800 controller, as listed in BAS-PTS013B-EN (4/7/2026).
Also known as: RTAF, Sintesis RTAF, Sintesis air-cooled chiller - Pump (data-centre coolant distribution unit)
Trane TCDU coolant distribution unit (data-centre liquid cooling)
Trane Coolant Distribution Unit (TCDU) for direct-to-chip liquid cooling, as documented in IOM DC-SVX001A-EN (April 2025).
Also known as: TCDU, Trane CDU, Trane Coolant Distribution Unit, DC-SVX001A - Sensor (refrigerant leak monitor for chiller plant rooms)
Trane TruSense RMWH refrigerant monitor (up to 16 points)
Trane TruSense RMWH multipoint photoacoustic refrigerant monitor with Modbus RTU selected, per IOM PART-SVX008A-EN (30 Sep 2025, preliminary).
Also known as: TruSense, RMWH, Trane refrigerant monitor, PART-SVX008A, RMWH-SVX001
Other chillers & heat pumps register maps
- Chiller (air-cooled)
Daikin Applied EWAT-B / EWAFT-B / EWAT-C / EWAFT-C air-cooled inverter chillers (Microtech 4, ARES software)
EWA(F)T-B and -C air-cooled chillers (F = free-cooling) with a Microtech 4 controller running ARES software, per D-EIGOC00207-24_05EN.
Also known as: EWAT-B, EWAFT-B, EWAT-C, EWAFT-C, EWA(F)T-B-C, EWAT~B, EWAFT~B, Daikin EWAT, ARES - Chiller
Daikin Applied MicroTech II scroll and screw chillers AGZ/ACZ/WGZ/AGS/WGS (Modbus module)
McQuay/Daikin Applied AGZ air-cooled and WGZ water-cooled global scroll chillers, ACZ scroll condensing units, and AGS/WGS global screw chillers with the MicroTech II controller and Modbus Communication Module, per ED 15063-2 (Dec 2005).
Also known as: AGZ-A, AGZ-B, ACZ-A, ACZ-B, WGZ, AGS-B, AGS-C, WGS, AGZ, ACZ, AGS, McQuay global scroll Modbus, McQuay global screw Modbus, ED 15063 - Chiller (refrigerant chiller for Liebert XD rack cooling)
Vertiv Liebert XDC refrigerant chiller for XD systems with iCOM v4 (IntelliSlot Modbus)
Liebert XDC units (the compressorised refrigerant chiller that feeds Liebert XD rack and ceiling cooling modules) on the iCOM v4 controller with a Liebert IntelliSlot Modbus card.
Also known as: Liebert XDC, XDC, Liebert XD chiller - Chiller (water-cooled, magnetic-bearing centrifugal)
Daikin Applied Magnitude WME magnetic-bearing chiller (MicroTech, Modbus)
Magnitude WME C- and D-vintage and WME-C QUAD chillers with the MicroTech unit controller and Modbus communication module, per ED 19111-4.
Also known as: WME-C, WME-D, WME-C QUAD, Magnitude WME, Daikin WME - Chiller
Daikin Applied Trailblazer AGZ-D / AGZ-E air-cooled scroll chiller (MicroTech controller)
Daikin Applied Trailblazer AGZ-D and AGZ-E air-cooled scroll chillers with the MicroTech chiller unit controller and Modbus communication module, per ED 15121-13.
Also known as: AGZ-D, AGZ-E, AGZ D-Vintage, AGZ E-Vintage, ED 15121, Trailblazer AGZ-D, Trailblazer AGZ-E - Chiller (water-cooled)
Daikin Applied EWWD-VZ / EWWH-VZ / EWWS-VZ water-cooled inverter screw chillers (Microtech, Adam software)
EWWD-VZ, EWWH-VZ and EWWS-VZ water-cooled inverter screw chillers with Microtech III or Microtech 4 controller running Adam software, per D-EIGOC00201-22_03EN.
Also known as: EWWD-VZ, EWWH-VZ, EWWS-VZ, EWWD(H)(S)_VZ, EWWD~VZ, EWWH~VZ, Daikin EWWD VZ, Adam
All chillers & heat pumps Modbus register maps →
Source: Symbio 800 Integration Points List, BACnet/Modbus, CTV-Duplex (UC800) · BAS-PTS030A-EN · rev. 2024-12-06. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.