Chiller · Modbus register map

Trane CenTraVac simplex centrifugal chiller (Symbio 800) Modbus register map

Updated 19 November 2026

Short answer

Trane's CenTraVac is a large water-cooled centrifugal chiller; this map covers the single-compressor (simplex) models controlled by a Symbio 800, which serves BACnet and Modbus RTU/TCP from one points list. It covers the analog inputs (setpoints, water temperatures and flows, refrigerant and oil pressures, purge, starter/drive and energy values), BAS setpoints, binary status points, multi-state modes and the diagnostic flags.

This page lists 546 Modbus registers for the Trane CenTraVac simplex centrifugal chiller (Symbio 800) — 15 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Trane’s own free documentation (linked below) and checked against it.

Manufacturer
Trane
Model
CenTraVac simplex centrifugal chiller (Symbio 800)
Equipment type
Chiller
Registers
546 (15 writable)
Transport
Modbus RTU, Modbus TCP
Default unit ID
Not stated
Default serial
19200 baud, 8E1
Documented addressing
Modicon 3xxxx/4xxxx (drop the prefix, subtract 1)
32-bit word order
ABCD high word first (big-endian)
Also known as
CVHE, CVHF, CVHG, CVHH, CVHL, CVHM, CVHS, CVGF, CVR, CVZA, CVXA, CenTraVac Simplex Symbio 800, CenTraVac simplex
Source document
Symbio 800 Integration Points List, BACnet/Modbus, CenTraVac · BAS-PTS009C-EN · rev. 2025-12-12
Download CSV all columns JSON Manufacturer PDF ↗

Integration notes: Trane CenTraVac simplex centrifugal chiller (Symbio 800)

Integration in brief

Read the analog inputs as pairs of input registers (float, high word first) and the binary/multi-state points as single registers. Write the BAS setpoints and command points in the 4xxxx holding range.

Minimum registers to map

Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.

RegisterNameTypeWhyAccess
IR 10Active Chilled Water SetpointFLOAT32 ABCDActive chilled water setpointRead
IR 24Evaporator Leaving Water TemperatureFLOAT32 ABCDEvaporator leaving water temperatureRead
IR 26Evaporator Entering Water TemperatureFLOAT32 ABCDEvaporator entering water temperatureRead
IR 2010Running ModeUINT16Running modeRead
IR 3023Chiller Running StateUINT16Chiller running stateRead
IR 3028Diagnostic PresentUINT16Diagnostic presentRead
HR 10Chilled Water SetpointFLOAT32 ABCDChilled water setpoint (BAS)Read/write
HR 2010Chiller Mode Command BASUINT16BAS chiller mode commandRead/write
HR 3014Chiller Auto Stop Command BASUINT16Chiller auto/stop command (BAS)Read/write
HR 3011Reset DiagnosticUINT16Reset diagnosticRead/write

Enable Modbus control & writes

On the Symbio 800 web interface go to Installation > Identification and Communications > Protocol Configuration and select Modbus RTU or Modbus TCP (per Trane's Symbio 800 integration guides).

Byte order & addressing

Network setup

Watch out for

Trane CenTraVac simplex centrifugal chiller (Symbio 800) Modbus registers

Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.

546 of 546 shown
Trane CenTraVac simplex centrifugal chiller (Symbio 800) Modbus register map
TableAddressNameDescriptionTypeOrderScaleUnitsAccessValues / bits
IR10doc 30011Active Chilled Water SetpointTemperature in the factory unit system (I-P or SI).FLOAT32ABCDRead
IR12doc 30013Chilled Water Setpoint StatusTemperature in the factory unit system (I-P or SI).FLOAT32ABCDRead
IR14doc 30015Active Base Loading SetpointNeeds: Base LoadingFLOAT32ABCD%Read
IR16doc 30017Active Hot Water SetpointTemperature in the factory unit system (I-P or SI). Needs: Hot Water ControlFLOAT32ABCDRead
IR18doc 30019Calculated Chiller CapacityCooling capacity in the factory unit system (I-P or SI). Needs: Evap Water Flow SensingFLOAT32ABCDRead
IR20doc 30021Total Demand DistortionNeeds: Active Harmonic DampeningFLOAT32ABCD%Read
IR22doc 30023Active Cool/Heat Setpoint TemperatureTemperature in the factory unit system (I-P or SI).FLOAT32ABCDRead
IR24doc 30025Evaporator Leaving Water TemperatureTemperature in the factory unit system (I-P or SI).FLOAT32ABCDRead
IR26doc 30027Evaporator Entering Water TemperatureTemperature in the factory unit system (I-P or SI).FLOAT32ABCDRead
IR28doc 30029Condenser Entering Water TemperatureTemperature in the factory unit system (I-P or SI).FLOAT32ABCDRead
IR30doc 30031Condenser Leaving Water TemperatureTemperature in the factory unit system (I-P or SI).FLOAT32ABCDRead
IR32doc 30033Evaporator Water Flow RateWater flow in the factory unit system (I-P or SI). Needs: Evap Water Flow SensingFLOAT32ABCDRead
IR34doc 30035Evaporator Differential Water PressureNeeds: Evap Water Flow Differential Pressure or Dual Pressure SensorsFLOAT32ABCDRead
IR36doc 30037Condenser Water Flow RateWater flow in the factory unit system (I-P or SI). Needs: Cond Water Flow SensingFLOAT32ABCDRead
IR38doc 30039Condenser Differential Water PressureNeeds: Cond Water Flow Differential Pressure or Dual Pressure SensorsFLOAT32ABCDRead
IR40doc 30041Heat Recovery Entering Water TemperatureTemperature in the factory unit system (I-P or SI). Needs: Heat RecoveryFLOAT32ABCDRead
IR42doc 30043Heat Recovery Leaving Water TemperatureTemperature in the factory unit system (I-P or SI). Needs: Heat RecoveryFLOAT32ABCDRead
IR44doc 30045AFD Last Diagnostic Code Ckt1Needs: Unit Mount AFD w/o THD filter Remote Mount Comm AFD (PF6000)FLOAT32ABCDRead
IR46doc 30047Unit Source ID (Last Diagnostic Code)FLOAT32ABCDRead
IR48doc 30049Drive Input Voltage CalculatedVoltage. Needs: TR200 Modbus AFD Communicating AFD (AFD3) Communicating AFD (PF755)FLOAT32ABCDRead
IR50doc 30051Number of CircuitsFLOAT32ABCDRead
IR52doc 30053Number of Compressors Circuit 1FLOAT32ABCDRead
IR54doc 30055Number of Compressors Circuit 2FLOAT32ABCDRead
IR56doc 30057Refrigerant MonitorRefrigerant concentration reading. Needs: Refrigerant MonitorFLOAT32ABCDRead
IR58doc 30059Evaporator Refrigerant Pressure Circuit 1Pressure in the factory unit system (I-P or SI).FLOAT32ABCDRead
IR60doc 30061Condenser Refrigerant Pressure Circuit 1Pressure in the factory unit system (I-P or SI).FLOAT32ABCDRead
IR62doc 30063Differential Refrigerant Pressure Circuit 1Differential pressure in the factory unit system (I-P or SI).FLOAT32ABCDRead
IR64doc 30065Low Side Oil Pressure - Compressor 1ANeeds: Not CVHS or CVGF CVR w/Oil Pressure Transducers or Oil LiteFLOAT32ABCDRead
IR66doc 30067High Side Oil Pressure - Compressor 1ANeeds: Not CVHS or CVGF CVR w/Oil Pressure Transducers or Oil LiteFLOAT32ABCDRead
IR68doc 30069Oil Differential Pressure Circuit 1Needs: Not CVHS or CVGF CVR w/Oil Pressure Transducers or Oil LiteFLOAT32ABCDRead
IR70doc 30071Oil Temperature - Compressor 1ATemperature in the factory unit system (I-P or SI). Needs: Not CVHSFLOAT32ABCDRead
IR72doc 30073Evaporator Saturated Refrigerant Temperature Circuit 1Temperature in the factory unit system (I-P or SI).FLOAT32ABCDRead
IR74doc 30075Condenser Saturated Refrigerant Temperature Circuit 1Temperature in the factory unit system (I-P or SI).FLOAT32ABCDRead
IR76doc 30077Refrigerant Discharge Temperature - Compressor 1ATemperature in the factory unit system (I-P or SI). Needs: Discharge Temperature ProtectionFLOAT32ABCDRead
IR78doc 30079Inlet Guide Vane 1 Percent Open Circuit 1FLOAT32ABCD%Read
IR80doc 30081Inlet Guide Vane 2 Percent Open Circuit 1Needs: Dual IGV2FLOAT32ABCD%Read
IR82doc 30083Purge Carbon Tank Temperature Circuit 1Temperature in the factory unit system (I-P or SI). Needs: Purge w/Carbon TankFLOAT32ABCDRead
IR84doc 30085Purge Liquid Temperature Circuit 1Temperature in the factory unit system (I-P or SI). Needs: PurgeFLOAT32ABCDRead
IR86doc 30087Purge Refrigerant Compressor Suction Temperature Circuit 1Temperature in the factory unit system (I-P or SI). Needs: PurgeFLOAT32ABCDRead
IR88doc 30089Time Until Next Purge Run Circuit 1 (in seconds)Needs: PurgeFLOAT32ABCDsRead
IR90doc 30091Purge Pumpout Chiller On % (7 Days) Circuit 1Needs: PurgeFLOAT32ABCD%Read
IR92doc 30093Purge Pumpout Chiller Off % (7 Days) Circuit 1Needs: PurgeFLOAT32ABCD%Read
IR94doc 30095Purge 24 Hour Pumpout Circuit 1 (in seconds)Needs: PurgeFLOAT32ABCDsRead
IR96doc 30097Purge Pumpout - Life Circuit 1 (in seconds)Needs: PurgeFLOAT32ABCDsRead
IR98doc 30099Refrigeration - Life Circuit 1 (in seconds)Needs: PurgeFLOAT32ABCDsRead
IR100doc 30101Starts - Compressor 1AFLOAT32ABCDRead
IR102doc 30103Run Time - Compressor 1A (in seconds)FLOAT32ABCDsRead
IR104doc 30105Phase AB Voltage - Compressor 1ADepends on starter/drive options; see the source configuration column.FLOAT32ABCDRead
IR106doc 30107Phase BC Voltage - Compressor 1ADepends on starter/drive options; see the source configuration column.FLOAT32ABCDRead
IR108doc 30109Phase CA Voltage - Compressor 1ADepends on starter/drive options; see the source configuration column.FLOAT32ABCDRead
IR110doc 30111Starter Average Phase Volt Circuit 1Depends on starter/drive options; see the source configuration column.FLOAT32ABCDRead
IR112doc 30113Line 1 Current - Compressor 1ADepends on starter/drive options; see the source configuration column.FLOAT32ABCDRead
IR114doc 30115Line 2 Current - Compressor 1ADepends on starter/drive options; see the source configuration column.FLOAT32ABCDRead
IR116doc 30117Line 3 Current - Compressor 1ADepends on starter/drive options; see the source configuration column.FLOAT32ABCDRead
IR118doc 30119Average Line Current Circuit 1Depends on starter/drive options; see the source configuration column.FLOAT32ABCDRead
IR120doc 30121Line 1 Current RLA - Compressor 1ADepends on starter/drive options; see the source configuration column.FLOAT32ABCD%Read
IR122doc 30123Line 2 Current RLA - Compressor 1ADepends on starter/drive options; see the source configuration column.FLOAT32ABCD%Read
IR124doc 30125Line 3 Current RLA - Compressor 1ADepends on starter/drive options; see the source configuration column.FLOAT32ABCD%Read
IR126doc 30127Actual Running CapacityDepends on starter/drive options; see the source configuration column.FLOAT32ABCD%Read
IR128doc 30129Unit Power ConsumptionDepends on starter/drive options; see the source configuration column.FLOAT32ABCDRead
IR130doc 30131Starter Load Power Factor - Compressor 1ADepends on starter/drive options; see the source configuration column.FLOAT32ABCDRead
IR132doc 30133Inboard Bearing Temperature Circuit 1Temperature in the factory unit system (I-P or SI). Needs: Bearing Temp Sensors (Not CVHM)FLOAT32ABCDRead
IR134doc 30135Outboard Bearing Temperature Circuit 1Temperature in the factory unit system (I-P or SI). Needs: Bearing Temp SensorsFLOAT32ABCDRead
IR136doc 30137Motor Winding Temperature 1 Circuit 1Temperature in the factory unit system (I-P or SI).FLOAT32ABCDRead
IR138doc 30139Motor Winding Temperature 2 Circuit 1Temperature in the factory unit system (I-P or SI).FLOAT32ABCDRead
IR140doc 30141Motor Winding Temperature 3 Circuit 1Temperature in the factory unit system (I-P or SI). Needs: Not CVHS and CVHMFLOAT32ABCDRead
IR142doc 30143AFD Frequency Circuit 1Depends on starter/drive options; see the source configuration column.FLOAT32ABCDRead
IR144doc 30145AFD Transistor Temperature Circuit 1Depends on starter/drive options; see the source configuration column.FLOAT32ABCDRead
IR146doc 30147Drive Average Line Current Circuit 1Depends on starter/drive options; see the source configuration column.FLOAT32ABCDRead
IR148doc 30149Drive Current Line 1 Circuit 1Current. Needs: Unit Mount AFD (LF2) w/Line Side ItemsFLOAT32ABCDRead
IR150doc 30151Drive Current Line 2 Circuit 1Current. Needs: Unit Mount AFD (LF2) w/Line Side ItemsFLOAT32ABCDRead
IR152doc 30153Drive Current Line 3 Circuit 1Current. Needs: Unit Mount AFD (LF2) w/Line Side ItemsFLOAT32ABCDRead
IR154doc 30155Drive Line Frequency Circuit 1Depends on starter/drive options; see the source configuration column.FLOAT32ABCDRead
IR156doc 30157Drive Frequency StatusDepends on starter/drive options; see the source configuration column.FLOAT32ABCDRead
IR158doc 30159Drive Inverter Base Temperature Circuit 1Needs: Unit Mount AFD (LF2) w/Line Side Items Communicating AFD (AFD3)FLOAT32ABCDRead
IR160doc 30161Drive Rectifier Base Temperature Circuit 1Needs: Unit Mount AFD (LF2) w/Line Side Items Communicating AFD (AFD3)FLOAT32ABCDRead
IR162doc 30163Drive Output Power Circuit 1Depends on starter/drive options; see the source configuration column.FLOAT32ABCDRead
IR164doc 30165Drive Motor Current U RLA Circuit 1Depends on starter/drive options; see the source configuration column.FLOAT32ABCD%Read
IR166doc 30167Drive Motor Current V RLA Circuit 1Depends on starter/drive options; see the source configuration column.FLOAT32ABCD%Read
IR168doc 30169Drive Motor Current W RLA Circuit 1Depends on starter/drive options; see the source configuration column.FLOAT32ABCD%Read
IR170doc 30171Drive Motor Current U Circuit 1Depends on starter/drive options; see the source configuration column.FLOAT32ABCDRead
IR172doc 30173Drive Motor Current V Circuit 1Depends on starter/drive options; see the source configuration column.FLOAT32ABCDRead
IR174doc 30175Drive Motor Current W Circuit 1Depends on starter/drive options; see the source configuration column.FLOAT32ABCDRead
IR176doc 30177Drive Motor Voltage UV Circuit 1Voltage. Needs: Communicating AFD (AFD3)FLOAT32ABCDRead
IR178doc 30179Drive Motor Voltage VW Circuit 1Voltage. Needs: Communicating AFD (AFD3)FLOAT32ABCDRead
IR180doc 30181Drive Motor Voltage WU Circuit 1Voltage. Needs: Communicating AFD (AFD3)FLOAT32ABCDRead
IR182doc 30183Drive Motor Average Voltage Circuit 1Depends on starter/drive options; see the source configuration column.FLOAT32ABCDRead
IR184doc 30185Drive Motor Average Current RLA Circuit 1Depends on starter/drive options; see the source configuration column.FLOAT32ABCD%Read
IR186doc 30187Lube Differential PressureDifferential pressure in the factory unit system (I-P or SI). Needs: CVHSFLOAT32ABCDRead
IR188doc 30189Lube Pump Suction PressurePressure in the factory unit system (I-P or SI). Needs: CVHSFLOAT32ABCDRead
IR190doc 30191Lube Pump Discharge PressurePressure in the factory unit system (I-P or SI). Needs: CVHSFLOAT32ABCDRead
IR192doc 30193Motor Coolant TemperatureTemperature in the factory unit system (I-P or SI). Needs: MTC Temp SensorFLOAT32ABCDRead
IR194doc 30195AFD % RLA RippleNeeds: Communicating AFD (AFD3)FLOAT32ABCD%Read
IR196doc 30197AFD Inverter Module Temperature UTemperature in the factory unit system (I-P or SI). Needs: Communicating AFD (AFD3)FLOAT32ABCDRead
IR198doc 30199AFD Inverter Module Temperature VTemperature in the factory unit system (I-P or SI). Needs: Communicating AFD (AFD3)FLOAT32ABCDRead
IR200doc 30201AFD Inverter Module Temperature WTemperature in the factory unit system (I-P or SI). Needs: Communicating AFD (AFD3)FLOAT32ABCDRead
IR202doc 30203Outboard Bearing Pad Temperature #1 Ckt1Temperature in the factory unit system (I-P or SI). Needs: CVHHFLOAT32ABCDRead
IR204doc 30205Outboard Bearing Pad Temperature #2 Ckt1Temperature in the factory unit system (I-P or SI). Needs: CVHHFLOAT32ABCDRead
IR206doc 30207Outboard Bearing Pad Temperature #3 Ckt1Temperature in the factory unit system (I-P or SI). Needs: CVHHFLOAT32ABCDRead
IR208doc 30209Condenser Control OutputNeeds: Head Pressure ControlFLOAT32ABCD%Read
IR210doc 30211Restart Inhibit Time RemainingFLOAT32ABCDRead
IR212doc 30213Chiller Design CapacityCooling capacity in the factory unit system (I-P or SI).FLOAT32ABCDRead
IR214doc 30215Entering Condenser Water PressurePressure in the factory unit system (I-P or SI). Needs: Condenser Water Flow Differential Pressure SensorsFLOAT32ABCDRead
IR216doc 30217Entering Evaporator Water PressurePressure in the factory unit system (I-P or SI). Needs: Evaporator Water Flow Differential Pressure SensorsFLOAT32ABCDRead
IR218doc 30219Leaving Condenser Water PressurePressure in the factory unit system (I-P or SI). Needs: Condenser Water Flow Differential Pressure SensorsFLOAT32ABCDRead
IR220doc 30221Leaving Evaporator Water PressurePressure in the factory unit system (I-P or SI). Needs: Evaporator Water Flow Differential Pressure SensorsFLOAT32ABCDRead
IR222doc 30223Condenser Approach Temperature Circuit 1Temperature difference, factory unit system (I-P or SI).FLOAT32ABCDRead
IR224doc 30225Evaporator Approach Temperature Circuit 1Temperature difference, factory unit system (I-P or SI).FLOAT32ABCDRead
IR226doc 30227Drive DC Bus Voltage Circuit 1Depends on starter/drive options; see the source configuration column.FLOAT32ABCDRead
IR228doc 30229Active Demand Limit SetpointFLOAT32ABCD%Read
IR230doc 30231Demand Limit Setpoint StatusNeeds: Ice BuildingFLOAT32ABCD%Read
IR232doc 30233Drive Heatsink Temperature Compressor 1ATemperature in the factory unit system (I-P or SI). Needs: TR200 Modbus AFDFLOAT32ABCDRead
IR234doc 30235Heat Recovery Differential Water PressureNeeds: Heat Recovery Water Flow Differential Pressure or Dual Pressure SensorsFLOAT32ABCDRead
IR236doc 30237Heat Recovery Water Flow RateWater flow in the factory unit system (I-P or SI). Needs: Heat Recovery Water Flow SensingFLOAT32ABCDRead
IR238doc 30239Heat Recovery Calculated CapacityNeeds: Heat Recovery Water Flow SensingFLOAT32ABCDRead
IR240doc 30241Heat Recovery Entering Water PressureNeeds: Heat Recovery Water Flow Differential Pressure SensorsFLOAT32ABCDRead
IR242doc 30243Heat Recovery Leaving Water PressureNeeds: Heat Recovery Water Flow Differential Pressure SensorsFLOAT32ABCDRead
IR244doc 30245Voltage L1-L2Voltage. Needs: Energy MeterFLOAT32ABCDRead
IR246doc 30247Voltage L2-L3Voltage. Needs: Energy MeterFLOAT32ABCDRead
IR248doc 30249Voltage L1-L3Voltage. Needs: Energy MeterFLOAT32ABCDRead
IR250doc 30251Chiller Average Line VoltageVoltage. Needs: Energy MeterFLOAT32ABCDRead
IR252doc 30253Current L1Current. Needs: Energy MeterFLOAT32ABCDRead
IR254doc 30255Current L2Current. Needs: Energy MeterFLOAT32ABCDRead
IR256doc 30257Current L3Current. Needs: Energy MeterFLOAT32ABCDRead
IR258doc 30259Unit Average Line CurrentCurrent. Needs: Energy MeterFLOAT32ABCDRead
IR260doc 30261Line FrequencyNeeds: Energy MeterFLOAT32ABCDRead
IR262doc 30263Power FactorNeeds: Energy MeterFLOAT32ABCDRead
IR264doc 30265Unit Power DemandNeeds: Energy MeterFLOAT32ABCDRead
IR266doc 30267Energy ConsumptionDepends on starter/drive options; see the source configuration column.FLOAT32ABCDRead
IR268doc 30269Energy Consumption LifetimeDepends on starter/drive options; see the source configuration column.FLOAT32ABCDRead
IR270doc 30271Outdoor Air Temperature LocalTemperature in the factory unit system (I-P or SI). Needs: Outdoor Air TemperatureFLOAT32ABCDRead
IR272doc 30273Heat Recovery Approach Temperature Circuit 1Temperature difference, factory unit system (I-P or SI). Needs: Heat RecoveryFLOAT32ABCDRead
IR274doc 30275High Side Oil Gauge Pressure - Compressor 1APressure in the factory unit system (I-P or SI).FLOAT32ABCDRead
IR276doc 30277Low Side Oil Gauge Pressure - Compressor 1APressure in the factory unit system (I-P or SI).FLOAT32ABCDRead
IR278doc 30279Condenser Refrigerant Gauge Pressure Circuit 1Pressure in the factory unit system (I-P or SI).FLOAT32ABCDRead
IR280doc 30281Entering Condenser Water Gauge PressurePressure in the factory unit system (I-P or SI). Needs: Condenser Water Flow Differential Pressure SensorsFLOAT32ABCDRead
IR282doc 30283Entering Evaporator Water Gauge PressurePressure in the factory unit system (I-P or SI). Needs: Evaporator Water Flow Differential Pressure SensorsFLOAT32ABCDRead
IR284doc 30285Evaporator Refrigerant Gauge Pressure Circuit 1Pressure in the factory unit system (I-P or SI).FLOAT32ABCDRead
IR286doc 30287Heat Recovery Entering Water Gauge PressureNeeds: Heat Recovery Water Flow Differential Pressure SensorsFLOAT32ABCDRead
IR288doc 30289Heat Recovery Leaving Water Gauge PressureNeeds: Heat Recovery Water Flow Differential Pressure SensorsFLOAT32ABCDRead
IR290doc 30291Leaving Condenser Water Gauge PressurePressure in the factory unit system (I-P or SI). Needs: Condenser Water Flow Differential Pressure SensorsFLOAT32ABCDRead
IR292doc 30293Leaving Evaporator Water Gauge PressurePressure in the factory unit system (I-P or SI). Needs: Evaporator Water Flow Differential Pressure SensorsFLOAT32ABCDRead
IR294doc 30295Lube Pump Suction Gauge PressurePressure in the factory unit system (I-P or SI). Needs: CVHSFLOAT32ABCDRead
IR296doc 30297Lube Pump Discharge Gauge PressurePressure in the factory unit system (I-P or SI). Needs: CVHSFLOAT32ABCDRead
IR298doc 30299Active Cooling Differential to StartTemperature difference, factory unit system (I-P or SI).FLOAT32ABCDRead
IR300doc 30301Active Cooling Differential to StopTemperature difference, factory unit system (I-P or SI).FLOAT32ABCDRead
IR302doc 30303Active Heating Differential to StartTemperature difference, factory unit system (I-P or SI). Needs: Hot Water ControlFLOAT32ABCDRead
IR304doc 30305Active Heating Differential to StopTemperature difference, factory unit system (I-P or SI). Needs: Hot Water ControlFLOAT32ABCDRead
IR306doc 30307Calculated Heating CapacityNeeds: Cond Water Flow SensingFLOAT32ABCDRead
IR308doc 30309Discharge Superheat Compressor 1ATemperature difference, factory unit system (I-P or SI). Needs: Discharge Temperature ProtectionFLOAT32ABCDRead
IR2010doc 32011Running ModeUINT16Read1 = Chiller Off; 2 = Chiller In Start Mode; 3 = Chiller In Run Mode; 4 = Chiller In Pre-Shutdown Mode; 5 = Chiller In Service Mode
IR2011doc 32012Operating ModeUINT16Read1 = Cool; 2 = Heat; 3 = Ice Making; 4 = Free Cooling
IR2012doc 32013Chiller Setpoint SourceUINT16Read1 = BAS; 2 = External; 3 = Front Panel
IR2013doc 32014Model Information [GEN2]UINT16Read1 = CVHF; 2 = CVGF; 3 = CVHS; 11 = CDHF; 12 = CVR; 13 = CVHH; 14 = CDHH; 20 = CVHM; 38 = CVHE; 39 = CVHG; 40 = CVHL; 43 = CDHG; 72 = CVZA; 73 = CVXA
IR2014doc 32015Cooling TypeUINT16Read1 = Water Cooled
IR2015doc 32016Refrigerant TypeUINT16Read1 = R-11; 2 = R-12; 3 = R-22; 4 = R-123; 5 = R-134a; 8 = R-113; 9 = R-114; 10 = R-500; 11 = R-502; 13 = R-513A; 14 = R-1233zd(E); 15 = R-514A
IR2016doc 32017Manufacturing LocationUINT16Read1 = Field Applied; 2 = La Crosse; 15 = Taicang
IR3010doc 33011Base Loading Request ActiveNeeds: Base LoadingUINT16Read0 = Off; 1 = On
IR3011doc 33012Emergency StopUINT16Read0 = Auto; 1 = Emergency Stop - Manual Reset Required
IR3012doc 33013Manual Override ExistsUINT16Read0 = Off; 1 = On
IR3013doc 33014Base Loading ActiveNeeds: Base LoadingUINT16Read0 = Inactive; 1 = Active
IR3014doc 33015Run EnabledUINT16Read0 = Run Not Enabled; 1 = Run Enabled
IR3015doc 33016Local Setpoint ControlUINT16Read0 = Remote Control; 1 = Local Control
IR3016doc 33017Maximum CapacityUINT16Read0 = Off; 1 = On
IR3017doc 33018Evaporator Leaving Water TemperatureUINT16Read0 = Not Limited; 1 = Limited
IR3018doc 33019Head Relief RequestUINT16Read0 = Off; 1 = On
IR3019doc 33020Hot Gas Bypass ActiveNeeds: Hot Gas BypassUINT16Read0 = Inactive; 1 = Active
IR3020doc 33021Purge Compressor Relay Circuit 1Needs: PurgeUINT16Read0 = Off; 1 = On
IR3021doc 33022Pump Out Relay Circuit 1Needs: PurgeUINT16Read0 = Off; 1 = On
IR3022doc 33023Purge Regenerating Valve Solenoid Circuit 1Needs: Purge w/Carbon TankUINT16Read0 = Off; 1 = On
IR3023doc 33024Chiller Running StateUINT16Read0 = Off; 1 = On
IR3024doc 33025Evaporator Water Pump RequestUINT16Read0 = Off; 1 = On
IR3025doc 33026Evaporator Water Flow StatusUINT16Read0 = No Flow; 1 = Flow
IR3026doc 33027Condenser Water Pump RequestUINT16Read0 = Off; 1 = On
IR3027doc 33028Condenser Water Flow StatusUINT16Read0 = No Flow; 1 = Flow
IR3028doc 33029Diagnostic PresentUINT16Read0 = Normal; 1 = In Alarm
IR3029doc 33030Diagnostic Shutdown PresentUINT16Read0 = Normal; 1 = In Alarm
IR3030doc 33031Diagnostic: Manual Reset RequiredUINT16Read0 = Normal; 1 = In Alarm
IR3031doc 33032Diagnostic: Local Manual Reset RequiredUINT16Read0 = Normal; 1 = In Alarm
IR3032doc 33033Diagnostic Present: InformationUINT16Read0 = Normal; 1 = In Alarm
IR3033doc 33034Diagnostic Present: AdvisoryUINT16Read0 = Normal; 1 = In Alarm
IR3034doc 33035Diagnostic Present: CriticalUINT16Read0 = Normal; 1 = In Alarm
IR3035doc 33036Diagnostic Present: Service RequiredUINT16Read0 = Normal; 1 = In Alarm
IR3036doc 33037Compressor 1A StatusUINT16Read0 = Off; 1 = Running
IR3037doc 33038Front Panel Auto StopUINT16Read0 = Stop; 1 = Auto
IR3038doc 33039External Auto Stop Input StatusUINT16Read0 = Stop; 1 = Auto
IR3039doc 33040Heat Recovery Water Flow StatusNeeds: Heat Recovery Water Flow SwitchUINT16Read0 = No Flow; 1 = Flow
IR3040doc 33041AFD Shutdown Diagnostic Present Circuit 1UINT16Read0 = Normal; 1 = In Alarm
IR4000doc 34001Diagnostic: AFD AD Calibration Error Circuit 1Diagnostic flag. Needs: Unit Mount AFD - AFDN,P (AFD3)UINT16Read0 = Normal; 1 = In Alarm
IR4001doc 34002Diagnostic: AFD AHD Frequency Out of Range Circuit 1Diagnostic flag. Needs: Unit Mount AFD - AFDN,P (AFD3)UINT16Read0 = Normal; 1 = In Alarm
IR4002doc 34003Diagnostic: AFD AHD Sync Signal Error Circuit 1Diagnostic flag. Needs: Unit Mount AFD - AFDN,P (AFD3)UINT16Read0 = Normal; 1 = In Alarm
IR4003doc 34004Diagnostic: AFD Bump Failure Circuit 1Diagnostic flag. Needs: Unit Mount AFD - AFDN,P (AFD3)UINT16Read0 = Normal; 1 = In Alarm
IR4004doc 34005Diagnostic: AFD Bus Over Voltage Circuit 1Depends on starter/drive options; see the source configuration column.UINT16Read0 = Normal; 1 = In Alarm
IR4005doc 34006Diagnostic: AFD Bus Ripple Too High Circuit 1Diagnostic flag. Needs: Unit Mount AFD - AFDN,P (AFD3)UINT16Read0 = Normal; 1 = In Alarm
IR4006doc 34007Diagnostic: AFD Bus Under Voltage Circuit 1Depends on starter/drive options; see the source configuration column.UINT16Read0 = Normal; 1 = In Alarm
IR4007doc 34008Evaporator Leaving Water TemperatureDiagnostic flag. Needs: TR200 Modbus AFD (TR200)UINT16Read0 = Normal; 1 = In Alarm
IR4008doc 34009Diagnostic: AFD Comm Loss: Main Processor Circuit 1Depends on starter/drive options; see the source configuration column.UINT16Read0 = Normal; 1 = In Alarm
IR4009doc 34010Diagnostic: AFD Control Board Memory Error Type 2 Circuit 1Diagnostic flag. Needs: Unit Mount AFD - AFDD,E,F (LF2) Remote Mount Comm AFD - (PF7000)UINT16Read0 = Normal; 1 = In Alarm
IR4010doc 34011Diagnostic: AFD Current Sensor Self Test Failure Circuit 1Diagnostic flag. Needs: Unit Mount AFD - AFDN,P (AFD3)UINT16Read0 = Normal; 1 = In Alarm
IR4011doc 34012Diagnostic: AFD Desaturation Detected Circuit 1Diagnostic flag. Needs: Unit Mount AFD - AFDN,P (AFD3)UINT16Read0 = Normal; 1 = In Alarm
IR4012doc 34013Diagnostic: AFD DPI Communication Failure Circuit 1Diagnostic flag. Needs: Unit Mount AFD - AFDD,E,F (LF2) Remote Mount Comm AFD - (PF7000)UINT16Read0 = Normal; 1 = In Alarm
IR4013doc 34014Diagnostic: AFD Drive Fault Circuit 1Diagnostic flag. Needs: MV Remote Mount Comm AFDUINT16Read0 = Normal; 1 = In Alarm
IR4014doc 34015Diagnostic: AFD DSP Board ID Error Circuit 1Diagnostic flag. Needs: Unit Mount AFD - AFDN,P (AFD3)UINT16Read0 = Normal; 1 = In Alarm
IR4015doc 34016Diagnostic: AFD DSP Board Initialization Failure Circuit 1Diagnostic flag. Needs: Unit Mount AFD - AFDN,P (AFD3)UINT16Read0 = Normal; 1 = In Alarm
IR4016doc 34017Diagnostic: AFD DSP Board Low Voltage Failure Circuit 1Diagnostic flag. Needs: Unit Mount AFD - AFDN,P (AFD3)UINT16Read0 = Normal; 1 = In Alarm
IR4017doc 34018Diagnostic: AFD DSP Board Over Temp Circuit 1Diagnostic flag. Needs: Unit Mount AFD - AFDN,P (AFD3)UINT16Read0 = Normal; 1 = In Alarm
IR4018doc 34019Diagnostic: AFD Emergency Stop Fault Circuit 1Diagnostic flag. Needs: Unit Mount AFD - AFDN,P (AFD3) MV Remote Mount Comm AFDUINT16Read0 = Normal; 1 = In Alarm
IR4019doc 34020Diagnostic: AFD Estimated Junction Over Temp Circuit 1Diagnostic flag. Needs: Unit Mount AFD - AFDN,P (AFD3)UINT16Read0 = Normal; 1 = In Alarm
IR4020doc 34021Diagnostic: AFD Excessive AHD Inhibit Circuit 1Diagnostic flag. Needs: Unit Mount AFD - AFDN,P (AFD3)UINT16Read0 = Normal; 1 = In Alarm
IR4021doc 34022Diagnostic: AFD External Fault Input Circuit 1Diagnostic flag. Needs: Unit Mount Comm AFD - AFDY (PF755)UINT16Read0 = Normal; 1 = In Alarm
IR4022doc 34023Diagnostic: AFD Fatal Software Error Circuit 1Diagnostic flag. Needs: Unit Mount AFD - AFDD,E,F (LF2) Remote Mount Comm AFD - (PF7000)UINT16Read0 = Normal; 1 = In Alarm
IR4023doc 34024Diagnostic: AFD Fault Circuit 1Diagnostic flag. Needs: TR200 Modbus AFD (TR200)UINT16Read0 = Normal; 1 = In Alarm
IR4024doc 34025Diagnostic: AFD Gate Drive Board Over Temp Circuit 1Diagnostic flag. Needs: Unit Mount AFD - AFDN,P (AFD3)UINT16Read0 = Normal; 1 = In Alarm
IR4025doc 34026Diagnostic: AFD Gate Drive Fault Circuit 1Diagnostic flag. Needs: Unit Mount AFD - AFDN,P (AFD3)UINT16Read0 = Normal; 1 = In Alarm
IR4026doc 34027Diagnostic: AFD Gate Drive Low Voltage Failure Circuit 1Diagnostic flag. Needs: Unit Mount AFD - AFDN,P (AFD3)UINT16Read0 = Normal; 1 = In Alarm
IR4027doc 34028Diagnostic: AFD Gate Drive Module Comm Loss Circuit 1Diagnostic flag. Needs: Unit Mount AFD - AFDN,P (AFD3)UINT16Read0 = Normal; 1 = In Alarm
IR4028doc 34029Diagnostic: AFD Gate Kill Active Circuit 1Depends on starter/drive options; see the source configuration column.UINT16Read0 = Normal; 1 = In Alarm
IR4029doc 34030Diagnostic: AFD General Failure Circuit 1Diagnostic flag. Needs: TR200 Modbus AFD (TR200)UINT16Read0 = Normal; 1 = In Alarm
IR4030doc 34031Diagnostic: AFD General Failure Circuit 1Depends on starter/drive options; see the source configuration column.UINT16Read0 = Normal; 1 = In Alarm
IR4031doc 34032Diagnostic: AFD Ground Fault Circuit 1Diagnostic flag. Needs: TR200 Modbus AFD (TR200)UINT16Read0 = Normal; 1 = In Alarm
IR4032doc 34033Diagnostic: AFD Ground Fault Circuit 1Depends on starter/drive options; see the source configuration column.UINT16Read0 = Normal; 1 = In Alarm
IR4033doc 34034Diagnostic: AFD High Bus Voltage Circuit 1Diagnostic flag. Needs: Unit Mount AFD - AFDD,E,F (LF2) Remote Mount Comm AFD - (PF7000)UINT16Read0 = Normal; 1 = In Alarm
IR4034doc 34035Diagnostic: AFD High Temperature Circuit 1Diagnostic flag. Needs: Unit Mount AFD - AFDD,E,F (LF2) Remote Mount Comm AFD - (PF7000)UINT16Read0 = Normal; 1 = In Alarm
IR4035doc 34036Diagnostic: AFD I/O Board Failure Circuit 1Diagnostic flag. Needs: Unit Mount AFD - AFDD,E,F (LF2) Remote Mount Comm AFD - (PF7000)UINT16Read0 = Normal; 1 = In Alarm
IR4036doc 34037Diagnostic: AFD IGBT Self Test Failure Circuit 1Diagnostic flag. Needs: Unit Mount AFD - AFDN,P (AFD3)UINT16Read0 = Normal; 1 = In Alarm
IR4037doc 34038Diagnostic: AFD IMC 24V Detection Failure Circuit 1Diagnostic flag. Needs: Unit Mount AFD - AFDN,P (AFD3)UINT16Read0 = Normal; 1 = In Alarm
IR4038doc 34039Diagnostic: AFD Input Transformer or Filter High Temp Circuit 1Diagnostic flag. Needs: Unit Mount Comm AFD - AFDY (PF755)UINT16Read0 = Normal; 1 = In Alarm
IR4039doc 34040Diagnostic: AFD Instantaneous Current Overload Circuit 1Depends on starter/drive options; see the source configuration column.UINT16Read0 = Normal; 1 = In Alarm
IR4040doc 34041Diagnostic: AFD Interrupt Failure Circuit 1Diagnostic flag. Needs: Communicating AFDUINT16Read0 = Normal; 1 = In Alarm
IR4041doc 34042Diagnostic: AFD Invalid Drive Command Circuit 1Diagnostic flag. Needs: Unit Mount AFD - AFDN,P (AFD3)UINT16Read0 = Normal; 1 = In Alarm
IR4042doc 34043Diagnostic: AFD Inverter Heatsink Over Temp Circuit 1Diagnostic flag. Needs: Unit Mount AFD - AFDN,P (AFD3) MV Remote Mount Comm AFDUINT16Read0 = Normal; 1 = In Alarm
IR4043doc 34044Diagnostic: AFD Loss of AHD Sync Signal Circuit 1Diagnostic flag. Needs: Unit Mount AFD - AFDN,P (AFD3)UINT16Read0 = Normal; 1 = In Alarm
IR4044doc 34045Diagnostic: AFD Low Rotor Flux Feedback Circuit 1Diagnostic flag. Needs: Unit Mount AFD - AFDN,P (AFD3) Unit Mount Comm AFD - AFDY (PF755)UINT16Read0 = Normal; 1 = In Alarm
IR4045doc 34046Diagnostic: AFD Mains Phase Loss Circuit 1Diagnostic flag. Needs: TR200 Modbus AFD (TR200)UINT16Read0 = Normal; 1 = In Alarm
IR4046doc 34047Diagnostic: AFD Motor Current Overload Circuit 1Diagnostic flag. Needs: TR200 Modbus AFD (TR200)UINT16Read0 = Normal; 1 = In Alarm
IR4047doc 34048Diagnostic: AFD Motor Current Overload Circuit 1Depends on starter/drive options; see the source configuration column.UINT16Read0 = Normal; 1 = In Alarm
IR4048doc 34049Diagnostic: AFD Motor Fault Circuit 1Needs: Unit Mount Comm AFD - AFDY (PF755) Remote Mount Comm AFD - VFDB (PF6000)UINT16Read0 = Normal; 1 = In Alarm
IR4049doc 34050Diagnostic: AFD Motor Short Circuit 1Depends on starter/drive options; see the source configuration column.UINT16Read0 = Normal; 1 = In Alarm
IR4050doc 34051Diagnostic: AFD Non-Volatile Memory Failure Circuit 1Diagnostic flag. Needs: Unit Mount AFD - AFDN,P (AFD3)UINT16Read0 = Normal; 1 = In Alarm
IR4051doc 34052Diagnostic: AFD Output Phase Loss Circuit 1Depends on starter/drive options; see the source configuration column.UINT16Read0 = Normal; 1 = In Alarm
IR4052doc 34053Diagnostic: AFD Over Temperature Circuit 1Needs: Unit Mount Comm AFD - AFDY (PF755) Remote Mount Comm AFD - VFDB (PF6000)UINT16Read0 = Normal; 1 = In Alarm
IR4053doc 34054Diagnostic: AFD Overspeed Circuit 1Diagnostic flag. Needs: Unit Mount AFD - AFDN,P (AFD3)UINT16Read0 = Normal; 1 = In Alarm
IR4054doc 34055Diagnostic: AFD Panel Interlock Fault Circuit 1Diagnostic flag. Needs: Unit Mount AFD - AFDN,P (AFD3)UINT16Read0 = Normal; 1 = In Alarm
IR4055doc 34056Diagnostic: AFD Panel Interlock Warning Circuit 1Diagnostic flag. Needs: Unit Mount AFD - AFDN,P (AFD3)UINT16Read0 = Normal; 1 = In Alarm
IR4056doc 34057Diagnostic: AFD Power Intfc Controller Board Failure Circuit 1Diagnostic flag. Needs: Unit Mount AFD - AFDD,E,F (LF2) Remote Mount Comm AFD - (PF7000)UINT16Read0 = Normal; 1 = In Alarm
IR4057doc 34058Diagnostic: AFD Power Loss Circuit 1Depends on starter/drive options; see the source configuration column.UINT16Read0 = Normal; 1 = In Alarm
IR4058doc 34059Diagnostic: AFD Power Structure Board Failure Circuit 1Diagnostic flag. Needs: Unit Mount AFD - AFDD,E,F (LF2) Remote Mount Comm AFD - (PF7000)UINT16Read0 = Normal; 1 = In Alarm
IR4059doc 34060Diagnostic: AFD Precharge Fault Circuit 1Needs: Unit Mount Comm AFD - AFDY (PF755) Remote Mount Comm AFD - VFDB (PF6000)UINT16Read0 = Normal; 1 = In Alarm
IR4060doc 34061Diagnostic: AFD Rectifier Heatsink Over Temp Circuit 1Diagnostic flag. Needs: Unit Mount AFD - AFDN,P (AFD3)UINT16Read0 = Normal; 1 = In Alarm
IR4061doc 34062Diagnostic: AFD RS485 Board Memory Error Type 2 Circuit 1Diagnostic flag. Needs: Unit Mount AFD - AFDD,E,F (LF2) Remote Mount Comm AFD - (PF7000)UINT16Read0 = Normal; 1 = In Alarm
IR4062doc 34063Diagnostic: AFD Safe Stop Circuit 1Diagnostic flag. Needs: TR200 Modbus AFD (TR200)UINT16Read0 = Normal; 1 = In Alarm
IR4063doc 34064Diagnostic: AFD Short Circuit Circuit 1Diagnostic flag. Needs: TR200 Modbus AFD (TR200)UINT16Read0 = Normal; 1 = In Alarm
IR4064doc 34065Diagnostic: AFD Speed Configuration Mismatch Circuit 1Diagnostic flag. Needs: TR200 Modbus AFD (TR200)UINT16Read0 = Normal; 1 = In Alarm
IR4065doc 34066Diagnostic: AFD Start Failure Circuit 1Diagnostic flag. Needs: Unit Mount AFD - AFDN,P (AFD3)UINT16Read0 = Normal; 1 = In Alarm
IR4066doc 34067Diagnostic: AFD Temperature Sensor Warning Circuit 1Diagnostic flag. Needs: Unit Mount AFD - AFDN,P (AFD3)UINT16Read0 = Normal; 1 = In Alarm
IR4067doc 34068Diagnostic: AFD Watchdog Timer Overflow Circuit 1Diagnostic flag. Needs: Unit Mount AFD - AFDN,P (AFD3)UINT16Read0 = Normal; 1 = In Alarm
IR4068doc 34069Diagnostic: At Speed Input Opened Circuit 1Diagnostic flag. Needs: Non-comm AFD Solid State StarterUINT16Read0 = Normal; 1 = In Alarm
IR4069doc 34070Diagnostic: At Speed Input Shorted Circuit 1Diagnostic flag. Needs: Non-comm AFD Solid State StarterUINT16Read0 = Normal; 1 = In Alarm
IR4070doc 34071Diagnostic: Bearing Lube Flow First Stage Sensor InputDiagnostic flag. Needs: CVHSUINT16Read0 = Normal; 1 = In Alarm
IR4071doc 34072Diagnostic: Bearing Lube Flow Second Stage Sensor InputDiagnostic flag. Needs: CVHSUINT16Read0 = Normal; 1 = In Alarm
IR4072doc 34073Diagnostic: Brg Lube Flow Overdue First Stage Circuit 1Diagnostic flag. Needs: CVHSUINT16Read0 = Normal; 1 = In Alarm
IR4073doc 34074Diagnostic: Brg Lube Flow Overdue Second Stage Circuit 1Diagnostic flag. Needs: CVHSUINT16Read0 = Normal; 1 = In Alarm
IR4075doc 34076Diagnostic: Check Lube Filter Circuit 1Diagnostic flag. Needs: CVHSUINT16Read0 = Normal; 1 = In Alarm
IR4076doc 34077Diagnostic: Check Oil Filter Circuit 1Diagnostic flag. Needs: Oil PumpUINT16Read0 = Normal; 1 = In Alarm
IR4077doc 34078Diagnostic: Check Oil Heater Circuit 1Diagnostic flag. Needs: Oil HeaterUINT16Read0 = Normal; 1 = In Alarm
IR4078doc 34079Comm Loss: Adaptive Frequency Drive Circuit 1Diagnostic flag. Needs: Communicating AFDUINT16Read0 = Normal; 1 = In Alarm
IR4079doc 34080Comm Loss: AFD Speed Signal VDC Output Circuit 1Diagnostic flag. Needs: Non-comm AFDUINT16Read0 = Normal; 1 = In Alarm
IR4080doc 34081Comm Loss: Bearing Lube Flow First StageDiagnostic flag. Needs: CVHSUINT16Read0 = Normal; 1 = In Alarm
IR4081doc 34082Comm Loss: Bearing Lube Flow Second StageDiagnostic flag. Needs: CVHSUINT16Read0 = Normal; 1 = In Alarm
IR4082doc 34083Comm Loss: Compressor Motor % RLA Output Circuit 1Diagnostic flag. Needs: % RLA OutputUINT16Read0 = Normal; 1 = In Alarm
IR4083doc 34084Comm Loss: Cond Diff Water PressureDiagnostic flag. Needs: Cond Differential Pressure Flow MeasurementUINT16Read0 = Normal; 1 = In Alarm
IR4084doc 34085Comm Loss: Cond Head Press Cntrl OutputDiagnostic flag. Needs: Head Pressure ControlUINT16Read0 = Normal; 1 = In Alarm
IR4085doc 34086Comm Loss: Cond High Pressure CutoutDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4086doc 34087Comm Loss: Cond Lubrication Source ValveDiagnostic flag. Needs: CVHSUINT16Read0 = Normal; 1 = In Alarm
IR4087doc 34088Comm Loss: Cond Refrigerant PressureDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4088doc 34089Comm Loss: Cond Rfgt Pressure OutputDiagnostic flag. Needs: Cond Refrigerant Pressure OutputUINT16Read0 = Normal; 1 = In Alarm
IR4089doc 34090Comm Loss: Cond Saturated Rfgt TempDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4090doc 34091Comm Loss: Condenser Entering Water PressureDiagnostic flag. Needs: Cond Water Flow Measurement - Dual Pressure SensorUINT16Read0 = Normal; 1 = In Alarm
IR4091doc 34092Comm Loss: Condenser Entering Water TempDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4092doc 34093Comm Loss: Condenser Leaving Water PressureDiagnostic flag. Needs: Cond Water Flow Measurement - Dual Pressure SensorUINT16Read0 = Normal; 1 = In Alarm
IR4093doc 34094Comm Loss: Condenser Leaving Water TempDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4094doc 34095Comm Loss: Condenser Liquid Level SensorDiagnostic flag. Needs: Economizer BypassUINT16Read0 = Normal; 1 = In Alarm
IR4096doc 34097Comm Loss: Condenser Water Flow SwitchDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4097doc 34098Comm Loss: Condenser Water Pump RelayDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4098doc 34099Comm Loss: Cprsr Discharge Rfgt TempDiagnostic flag. Needs: Compressor Discharge Temp SensorUINT16Read0 = Normal; 1 = In Alarm
IR4099doc 34100Comm Loss: Economizer Bypass ValveDiagnostic flag. Needs: Economizer BypassUINT16Read0 = Normal; 1 = In Alarm
IR4102doc 34103Comm Loss: Emergency StopDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4103doc 34104Comm Loss: Energy Meter Circuit 1Diagnostic flag. Needs: Energy MeterUINT16Read0 = Normal; 1 = In Alarm
IR4104doc 34105Comm Loss: Evap Diff Water PressureDiagnostic flag. Needs: Evap Water Flow Measurement - Differential PressureUINT16Read0 = Normal; 1 = In Alarm
IR4105doc 34106Comm Loss: Evap Entering Water TempDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4106doc 34107Comm Loss: Evap Leaving Water TempDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4107doc 34108Comm Loss: Evap Lube Source Valve RelayDiagnostic flag. Needs: CVHSUINT16Read0 = Normal; 1 = In Alarm
IR4108doc 34109Comm Loss: Evap Saturated Rfgt TempDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4109doc 34110Comm Loss: Evaporator Entering Water PressureDiagnostic flag. Needs: Evap Water Flow Measurement - Dual Pressure SensorUINT16Read0 = Normal; 1 = In Alarm
IR4110doc 34111Comm Loss: Evaporator Leaving Water PressureDiagnostic flag. Needs: Evap Water Flow Measurement - Dual Pressure SensorUINT16Read0 = Normal; 1 = In Alarm
IR4111doc 34112Comm Loss: Evaporator Water Flow SwitchDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4112doc 34113Comm Loss: Evaporator Water Pump RelayDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4113doc 34114Comm Loss: Ext Base Loading CommandDiagnostic flag. Needs: Base LoadingUINT16Read0 = Normal; 1 = In Alarm
IR4114doc 34115Comm Loss: Ext Base Loading SetpointDiagnostic flag. Needs: Base LoadingUINT16Read0 = Normal; 1 = In Alarm
IR4115doc 34116Comm Loss: Ext Chilled/Hot Water SetpointDiagnostic flag. Needs: External Chilled Water SetpointUINT16Read0 = Normal; 1 = In Alarm
IR4116doc 34117Comm Loss: Ext Demand Limit SetpointDiagnostic flag. Needs: External Demand LimitUINT16Read0 = Normal; 1 = In Alarm
IR4117doc 34118Comm Loss: External Auto/StopDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4118doc 34119Comm Loss: External Free Cooling CommandDiagnostic flag. Needs: Free CoolingUINT16Read0 = Normal; 1 = In Alarm
IR4119doc 34120Comm Loss: External Hot Water CommandDiagnostic flag. Needs: Hot Water ControlUINT16Read0 = Normal; 1 = In Alarm
IR4120doc 34121Comm Loss: External Ice Building CommandDiagnostic flag. Needs: Ice BuildingUINT16Read0 = Normal; 1 = In Alarm
IR4121doc 34122Comm Loss: Free Cool Actrs Closed InputDiagnostic flag. Needs: Free CoolingUINT16Read0 = Normal; 1 = In Alarm
IR4122doc 34123Comm Loss: Free Cool Gas Line Actr RelayDiagnostic flag. Needs: Free CoolingUINT16Read0 = Normal; 1 = In Alarm
IR4123doc 34124Comm Loss: Free Cool Liq Line Actr RelayDiagnostic flag. Needs: Free CoolingUINT16Read0 = Normal; 1 = In Alarm
IR4124doc 34125Comm Loss: Free Cooling Auxiliary RelayDiagnostic flag. Needs: Free CoolingUINT16Read0 = Normal; 1 = In Alarm
IR4125doc 34126Comm Loss: Generator Fault InputDiagnostic flag. Needs: Engine Generator Power SourceUINT16Read0 = Normal; 1 = In Alarm
IR4126doc 34127Comm Loss: Generator Speed Signal OutputDiagnostic flag. Needs: Engine Generator Power SourceUINT16Read0 = Normal; 1 = In Alarm
IR4127doc 34128Comm Loss: Generator Start/Stop RelayDiagnostic flag. Needs: Engine Generator Power SourceUINT16Read0 = Normal; 1 = In Alarm
IR4128doc 34129Comm Loss: Generator Up To Speed InputDiagnostic flag. Needs: Engine Generator Power SourceUINT16Read0 = Normal; 1 = In Alarm
IR4129doc 34130Comm Loss: Heat Recovery Differential Water PressureDiagnostic flag. Needs: Heat Recovery Water Flow Measurement - Differential PressureUINT16Read0 = Normal; 1 = In Alarm
IR4130doc 34131Comm Loss: Heat Recovery Entering Water PressureDiagnostic flag. Needs: Heat Recovery Water Flow Measurement - Dual Pressure SensorUINT16Read0 = Normal; 1 = In Alarm
IR4131doc 34132Comm Loss: Heat Recovery Entering Water TempDiagnostic flag. Needs: Heat RecoveryUINT16Read0 = Normal; 1 = In Alarm
IR4132doc 34133Comm Loss: Heat Recovery Leaving Water PressureDiagnostic flag. Needs: Heat Recovery Water Flow Measurement - Dual Pressure SensorUINT16Read0 = Normal; 1 = In Alarm
IR4133doc 34134Comm Loss: Heat Recovery Leaving Water TempDiagnostic flag. Needs: Heat RecoveryUINT16Read0 = Normal; 1 = In Alarm
IR4134doc 34135Comm Loss: Heat Recovery Water Flow SwitchDiagnostic flag. Needs: Heat Recovery Water Flow SwitchUINT16Read0 = Normal; 1 = In Alarm
IR4135doc 34136Comm Loss: High Lift Unload Valve RelayDiagnostic flag. Needs: CVGFUINT16Read0 = Normal; 1 = In Alarm
IR4136doc 34137Comm Loss: Hot Gas Bypass Actr Closed InDiagnostic flag. Needs: Hot Gas BypassUINT16Read0 = Normal; 1 = In Alarm
IR4137doc 34138Comm Loss: Hot Gas Bypass Load RelayDiagnostic flag. Needs: Hot Gas BypassUINT16Read0 = Normal; 1 = In Alarm
IR4138doc 34139Comm Loss: Hot Gas Bypass Unload RelayDiagnostic flag. Needs: Hot Gas BypassUINT16Read0 = Normal; 1 = In Alarm
IR4139doc 34140Comm Loss: Ice Building RelayDiagnostic flag. Needs: Ice BuildingUINT16Read0 = Normal; 1 = In Alarm
IR4140doc 34141Comm Loss: IGV First Stage Actuator Circuit 1Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4141doc 34142Comm Loss: IGV Second Stage Actuator Circuit 1Diagnostic flag. Needs: Dual ActuatorsUINT16Read0 = Normal; 1 = In Alarm
IR4142doc 34143Comm Loss: Inboard Bearing Temperature Circuit 1Diagnostic flag. Needs: Bearing Temp SensorUINT16Read0 = Normal; 1 = In Alarm
IR4143doc 34144Comm Loss: Lube Pump Discharge PressureDiagnostic flag. Needs: CVHSUINT16Read0 = Normal; 1 = In Alarm
IR4144doc 34145Comm Loss: Lube Pump Suction PressureDiagnostic flag. Needs: CVHSUINT16Read0 = Normal; 1 = In Alarm
IR4145doc 34146Comm Loss: Lube/Refrigerant Pump RelayDiagnostic flag. Needs: CVHSUINT16Read0 = Normal; 1 = In Alarm
IR4146doc 34147Comm Loss: Motor Coolant TemperatureDiagnostic flag. Needs: MTC Temperature SensorUINT16Read0 = Normal; 1 = In Alarm
IR4147doc 34148Comm Loss: Motor Temp/OverloadDiagnostic flag. Needs: "Lite" Motor Temp ProtectionUINT16Read0 = Normal; 1 = In Alarm
IR4148doc 34149Comm Loss: Motor Temperature CutoutDiagnostic flag. Needs: MTC SwitchUINT16Read0 = Normal; 1 = In Alarm
IR4149doc 34150Comm Loss: Motor Winding Temperature 1 Circuit 1Diagnostic flag. Needs: CVHE,F,G,H,L,M,S CVGFUINT16Read0 = Normal; 1 = In Alarm
IR4150doc 34151Comm Loss: Motor Winding Temperature 2 Circuit 1Diagnostic flag. Needs: CVHE,F,G,H,L,M,S CVGFUINT16Read0 = Normal; 1 = In Alarm
IR4151doc 34152Comm Loss: Motor Winding Temperature 3 Circuit 1Diagnostic flag. Needs: CVHE,F,G,H, L CVGFUINT16Read0 = Normal; 1 = In Alarm
IR4152doc 34153Comm Loss: Oil Cooler Solenoid Circuit 1Diagnostic flag. Needs: CVHH Oil Cooler Solenoid ValveUINT16Read0 = Normal; 1 = In Alarm
IR4153doc 34154Comm Loss: Oil Diff Pressure Switch Circuit 1Diagnostic flag. Needs: CVGFUINT16Read0 = Normal; 1 = In Alarm
IR4154doc 34155Comm Loss: Oil Pressure Status Circuit 1Diagnostic flag. Needs: CVHE,F,G,H, L,MUINT16Read0 = Normal; 1 = In Alarm
IR4155doc 34156Comm Loss: Oil Pump Discharge Pressure Circuit 1Diagnostic flag. Needs: CVHE,F,G,H, L,MUINT16Read0 = Normal; 1 = In Alarm
IR4156doc 34157Comm Loss: Oil Tank Heater 4E1 Relay Circuit 1Diagnostic flag. Needs: CVHH CVGFUINT16Read0 = Normal; 1 = In Alarm
IR4157doc 34158Comm Loss: Oil Tank Heater 4E2 Relay Circuit 1Diagnostic flag. Needs: CVHH CVGFUINT16Read0 = Normal; 1 = In Alarm
IR4158doc 34159Comm Loss: Oil Tank Heater Relay Circuit 1Diagnostic flag. Needs: CVHE,F,G,H, L,MUINT16Read0 = Normal; 1 = In Alarm
IR4159doc 34160Comm Loss: Oil Tank Pressure Circuit 1Diagnostic flag. Needs: CVHE,F,G,H, L,MUINT16Read0 = Normal; 1 = In Alarm
IR4160doc 34161Comm Loss: Oil Tank Temperature Circuit 1Diagnostic flag. Needs: CVHE,F,G,H, L,M CVGFUINT16Read0 = Normal; 1 = In Alarm
IR4161doc 34162Comm Loss: Oil Vent Line Circuit 1Diagnostic flag. Needs: CVHHUINT16Read0 = Normal; 1 = In Alarm
IR4162doc 34163Comm Loss: Oil/Refrigerant Pump Relay Circuit 1Diagnostic flag. Needs: CVHE,F,G,H, L,M CVGFUINT16Read0 = Normal; 1 = In Alarm
IR4163doc 34164Comm Loss: Outboard Bearing Pad Temp 1 Circuit 1Diagnostic flag. Needs: CVHHUINT16Read0 = Normal; 1 = In Alarm
IR4164doc 34165Comm Loss: Outboard Bearing Pad Temp 2 Circuit 1Diagnostic flag. Needs: CVHHUINT16Read0 = Normal; 1 = In Alarm
IR4165doc 34166Comm Loss: Outboard Bearing Pad Temp 3 Circuit 1Diagnostic flag. Needs: CVHHUINT16Read0 = Normal; 1 = In Alarm
IR4166doc 34167Comm Loss: Outboard Bearing Temperature Circuit 1Diagnostic flag. Needs: Bearing Temp SensorUINT16Read0 = Normal; 1 = In Alarm
IR4167doc 34168Comm Loss: Outdoor Air TemperatureDiagnostic flag. Needs: Outdoor Air Temp SensorUINT16Read0 = Normal; 1 = In Alarm
IR4168doc 34169Comm Loss: Programmable Relay Board 1Diagnostic flag. Needs: Programmable Status RelaysUINT16Read0 = Normal; 1 = In Alarm
IR4169doc 34170Comm Loss: Programmable Relay Board 2Diagnostic flag. Needs: Programmable Status RelaysUINT16Read0 = Normal; 1 = In Alarm
IR4170doc 34171Comm Loss: Purge Alarm Relay Circuit 1Diagnostic flag. Needs: PurgeUINT16Read0 = Normal; 1 = In Alarm
IR4171doc 34172Comm Loss: Purge Carbon Tank Heater Rly Circuit 1Diagnostic flag. Needs: Purge w/Carbon TankUINT16Read0 = Normal; 1 = In Alarm
IR4172doc 34173Comm Loss: Purge Carbon Tank Temperature Circuit 1Diagnostic flag. Needs: Purge w/Carbon TankUINT16Read0 = Normal; 1 = In Alarm
IR4173doc 34174Comm Loss: Purge Condensing Unit Relay Circuit 1Diagnostic flag. Needs: PurgeUINT16Read0 = Normal; 1 = In Alarm
IR4174doc 34175Comm Loss: Purge Cprsr Suction Rfgt Temp Circuit 1Diagnostic flag. Needs: PurgeUINT16Read0 = Normal; 1 = In Alarm
IR4175doc 34176Comm Loss: Purge Exhaust Solenoid Output Circuit 1Diagnostic flag. Needs: PurgeUINT16Read0 = Normal; 1 = In Alarm
IR4176doc 34177Comm Loss: Purge Liquid Level Switch Circuit 1Diagnostic flag. Needs: PurgeUINT16Read0 = Normal; 1 = In Alarm
IR4177doc 34178Comm Loss: Purge Pumpout Relay Circuit 1Diagnostic flag. Needs: PurgeUINT16Read0 = Normal; 1 = In Alarm
IR4178doc 34179Comm Loss: Purge Pumpout Solenoid Output Circuit 1Diagnostic flag. Needs: PurgeUINT16Read0 = Normal; 1 = In Alarm
IR4179doc 34180Comm Loss: Purge Regen Solenoid Relay Circuit 1Diagnostic flag. Needs: Purge w/Carbon TankUINT16Read0 = Normal; 1 = In Alarm
IR4180doc 34181Comm Loss: Refrigerant Monitor InputDiagnostic flag. Needs: Refrigerant MonitorUINT16Read0 = Normal; 1 = In Alarm
IR4181doc 34182Comm Loss: Starter Circuit 1Diagnostic flag. Needs: EM Starters Solid State Starters Non-comm AFDsUINT16Read0 = Normal; 1 = In Alarm
IR4182doc 34183Comm Loss: Starter Fault Circuit 1Diagnostic flag. Needs: Non-comm AFD Solid State StarterUINT16Read0 = Normal; 1 = In Alarm
IR4183doc 34184Comm Loss: Vibration Sensor InputDiagnostic flag. Needs: Vibration SensorUINT16Read0 = Normal; 1 = In Alarm
IR4184doc 34185Diagnostic: Compressor Did Not Accelerate: Shutdown Compressor 1ADiagnostic flag. Needs: EM Starters Solid State Starters Non-comm AFDsUINT16Read0 = Normal; 1 = In Alarm
IR4185doc 34186Diagnostic: Cond Saturated Refrigerant Temp SensorDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4186doc 34187Diagnostic: Condenser Diff Water Pressure XdcrDiagnostic flag. Needs: Cond Water Flow Measurement - Differential PressureUINT16Read0 = Normal; 1 = In Alarm
IR4187doc 34188Diagnostic: Condenser Entering Water PressureDiagnostic flag. Needs: Cond Water Flow Measurement - Dual Pressure SensorUINT16Read0 = Normal; 1 = In Alarm
IR4188doc 34189Diagnostic: Condenser Entering Water Temp SensorDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4189doc 34190Diagnostic: Condenser High Pressure CutoutDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4190doc 34191Diagnostic: Condenser Leaving Water PressureDiagnostic flag. Needs: Cond Water Flow Measurement - Dual Pressure SensorUINT16Read0 = Normal; 1 = In Alarm
IR4191doc 34192Diagnostic: Condenser Leaving Water Temp SensorDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4192doc 34193Diagnostic: Condenser Liquid Level SensorDiagnostic flag. Needs: Economizer BypassUINT16Read0 = Normal; 1 = In Alarm
IR4193doc 34194Diagnostic: Condenser Refrigerant Pressure XdcrDiagnostic flag. Needs: Condenser Refrigerant Pressure SensorUINT16Read0 = Normal; 1 = In Alarm
IR4195doc 34196Diagnostic: Condenser Water Flow LostDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4196doc 34197Diagnostic: Condenser Water Flow OverdueDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4197doc 34198Diagnostic: Cprsr Did Not Accelerate: TransitionDiagnostic flag. Needs: EM Starters Solid State Starters Non-comm AFDsUINT16Read0 = Normal; 1 = In Alarm
IR4198doc 34199Diagnostic: Cprsr Discharge Refrigerant Temp SensorDiagnostic flag. Needs: Compressor Discharge Temp SensorUINT16Read0 = Normal; 1 = In Alarm
IR4199doc 34200Diagnostic: Differential Lube Pressure Overdue Circuit 1Diagnostic flag. Needs: CVHSUINT16Read0 = Normal; 1 = In Alarm
IR4200doc 34201Diagnostic: Differential Oil Pressure Overdue Circuit 1Diagnostic flag. Needs: CVHE,F,G,H, L,M CVGFUINT16Read0 = Normal; 1 = In Alarm
IR4202doc 34203Diagnostic: Emergency StopDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4203doc 34204Diagnostic: Evap Rfgt Temp Deviate From SelectionDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4204doc 34205Diagnostic: Evap Saturated Refrigerant Temp SensorDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4205doc 34206Diagnostic: Evaporator Diff Water Pressure XdcrDiagnostic flag. Needs: Evap Water Flow Measurement - Differential PressureUINT16Read0 = Normal; 1 = In Alarm
IR4206doc 34207Diagnostic: Evaporator Entering Water PressureDiagnostic flag. Needs: Evap Flow Measurement - Dual Pressure SensorUINT16Read0 = Normal; 1 = In Alarm
IR4207doc 34208Diagnostic: Evaporator Entering Water Temp SensorDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4208doc 34209Diagnostic: Evaporator Leaving Water PressureDiagnostic flag. Needs: Evap Flow Measurement - Dual Pressure SensorUINT16Read0 = Normal; 1 = In Alarm
IR4209doc 34210Diagnostic: Evaporator Leaving Water Temp SensorDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4210doc 34211Diagnostic: Evaporator Water Flow LostDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4211doc 34212Diagnostic: Evaporator Water Flow OverdueDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4212doc 34213Diagnostic: Excessive Loss of CommunicationDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4214doc 34215Diagnostic: Extended Compressor Surge Compressor 1ADiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4215doc 34216Diagnostic: External Base Loading SetpointDiagnostic flag. Needs: Base LoadingUINT16Read0 = Normal; 1 = In Alarm
IR4216doc 34217Diagnostic: External Chilled/Hot Water SetpointDiagnostic flag. Needs: External Chilled Water SetpointUINT16Read0 = Normal; 1 = In Alarm
IR4217doc 34218Diagnostic: External Demand Limit SetpointDiagnostic flag. Needs: External Demand Limit SetpointUINT16Read0 = Normal; 1 = In Alarm
IR4218doc 34219Diagnostic: Free Cooling Actrs Not Open During FCDiagnostic flag. Needs: Free CoolingUINT16Read0 = Normal; 1 = In Alarm
IR4219doc 34220Diagnostic: Free Cooling Actuators Not ClosedDiagnostic flag. Needs: Free CoolingUINT16Read0 = Normal; 1 = In Alarm
IR4220doc 34221Diagnostic: Free Cooling Actuators Not OpenDiagnostic flag. Needs: Free CoolingUINT16Read0 = Normal; 1 = In Alarm
IR4221doc 34222Diagnostic: Free Cooling Actuators Unexpectedly OpenDiagnostic flag. Needs: Free CoolingUINT16Read0 = Normal; 1 = In Alarm
IR4222doc 34223Diagnostic: Generator Fault Relay OpenDiagnostic flag. Needs: Engine Generator Power SourceUINT16Read0 = Normal; 1 = In Alarm
IR4223doc 34224Diagnostic: Generator Ready Signal OverdueDiagnostic flag. Needs: Engine Generator Power SourceUINT16Read0 = Normal; 1 = In Alarm
IR4224doc 34225Diagnostic: Heat Recovery Diff Water PressureDiagnostic flag. Needs: Heat Recovery Water Flow Measurement - Differential PressureUINT16Read0 = Normal; 1 = In Alarm
IR4225doc 34226Diagnostic: Heat Recovery Entering Water PressureDiagnostic flag. Needs: Heat Recovery Water Flow Measurement - Dual Pressure SensorUINT16Read0 = Normal; 1 = In Alarm
IR4226doc 34227Diagnostic: Heat Recovery Entering Water Temp SensorDiagnostic flag. Needs: Heat RecoveryUINT16Read0 = Normal; 1 = In Alarm
IR4227doc 34228Diagnostic: Heat Recovery Leaving Water PressureDiagnostic flag. Needs: Heat Recovery Water Flow Measurement - Dual Pressure SensorUINT16Read0 = Normal; 1 = In Alarm
IR4228doc 34229Diagnostic: Heat Recovery Leaving Water Temp SensorDiagnostic flag. Needs: Heat RecoveryUINT16Read0 = Normal; 1 = In Alarm
IR4229doc 34230Diagnostic: High Condenser PressureDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4230doc 34231Diagnostic: High Cprsr Rfgt Discharge TemperatureDiagnostic flag. Needs: Compressor Discharge Temp SensorUINT16Read0 = Normal; 1 = In Alarm
IR4231doc 34232Diagnostic: High Differential Refrigerant PressureDiagnostic flag. Needs: CVHE,F,G,H, L,M,SUINT16Read0 = Normal; 1 = In Alarm
IR4232doc 34233Diagnostic: High Evaporator Refrigerant TemperatureDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4233doc 34234Diagnostic: High Evaporator Water TemperatureDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4234doc 34235Diagnostic: High Inboard Bearing Temperature Circuit 1Diagnostic flag. Needs: Bearing Temp SensorUINT16Read0 = Normal; 1 = In Alarm
IR4235doc 34236Diagnostic: High Motor Coolant Temperature Circuit 1Diagnostic flag. Needs: MTC Temperature SensorUINT16Read0 = Normal; 1 = In Alarm
IR4236doc 34237Diagnostic: High Motor Winding Temperature 1 Circuit 1Diagnostic flag. Needs: CVHE,F,G,H,S,M,L CVGFUINT16Read0 = Normal; 1 = In Alarm
IR4237doc 34238Diagnostic: High Motor Winding Temperature 2 Circuit 1Diagnostic flag. Needs: CVHE,F,G,H,S,M,L CVGFUINT16Read0 = Normal; 1 = In Alarm
IR4238doc 34239Diagnostic: High Motor Winding Temperature 3 Circuit 1Diagnostic flag. Needs: CVHE,F,G,H,L CVGFUINT16Read0 = Normal; 1 = In Alarm
IR4239doc 34240Diagnostic: High Oil Temperature Circuit 1Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4240doc 34241Diagnostic: High Outboard Bearing Pad Temperature 1 Circuit 1Diagnostic flag. Needs: CVHHUINT16Read0 = Normal; 1 = In Alarm
IR4241doc 34242Diagnostic: High Outboard Bearing Pad Temperature 2 Circuit 1Diagnostic flag. Needs: CVHHUINT16Read0 = Normal; 1 = In Alarm
IR4242doc 34243Diagnostic: High Outboard Bearing Pad Temperature 3 Circuit 1Diagnostic flag. Needs: CVHHUINT16Read0 = Normal; 1 = In Alarm
IR4243doc 34244Diagnostic: High Outboard Bearing Temp Circuit 1Diagnostic flag. Needs: Bearing Temp SensorUINT16Read0 = Normal; 1 = In Alarm
IR4244doc 34245Diagnostic: High Vacuum Lockout Circuit 1Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4245doc 34246Diagnostic: Hot Gas Bypass Valve Closure OverdueDiagnostic flag. Needs: Hot Gas BypassUINT16Read0 = Normal; 1 = In Alarm
IR4246doc 34247Diagnostic: Hot Gas Bypass Valve Opening OverdueDiagnostic flag. Needs: Hot Gas BypassUINT16Read0 = Normal; 1 = In Alarm
IR4247doc 34248Diagnostic: Hot Gas Bypass Valve Unexpectedly OpenDiagnostic flag. Needs: Hot Gas BypassUINT16Read0 = Normal; 1 = In Alarm
IR4248doc 34249Diagnostic: HPC/High AFD Heat Sink Water PressureDiagnostic flag. Needs: Unit Mount AFD - AFDD,E,F (LF2) Remote Mount Comm AFD - (PF7000)UINT16Read0 = Normal; 1 = In Alarm
IR4249doc 34250Diagnostic: Inboard Bearing Temp Sensor Circuit 1Diagnostic flag. Needs: Bearing Temp SensorUINT16Read0 = Normal; 1 = In Alarm
IR4250doc 34251Diagnostic: Inverted Condenser Approach TemperatureDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4251doc 34252Diagnostic: Inverted Condenser Water TemperatureDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4252doc 34253Diagnostic: Inverted Evaporator Approach TemperatureDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4253doc 34254Diagnostic: Inverted Evaporator Water TemperatureDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4254doc 34255Diagnostic: Loss of Economizer Bypass Valve ControlDiagnostic flag. Needs: Economizer BypassUINT16Read0 = Normal; 1 = In Alarm
IR4255doc 34256Diagnostic: Low Bearing Lube Flow First Stage Circuit 1Diagnostic flag. Needs: CVHSUINT16Read0 = Normal; 1 = In Alarm
IR4256doc 34257Diagnostic: Low Bearing Lube Flow Second Stage Circuit 1Diagnostic flag. Needs: CVHSUINT16Read0 = Normal; 1 = In Alarm
IR4257doc 34258Diagnostic: Low Brg Lube Flow Lockout First Stage Circuit 1Diagnostic flag. Needs: CVHSUINT16Read0 = Normal; 1 = In Alarm
IR4258doc 34259Diagnostic: Low Brg Lube Flow Lockout Second Stage Circuit 1Diagnostic flag. Needs: CVHSUINT16Read0 = Normal; 1 = In Alarm
IR4259doc 34260Diagnostic: Low Differential Lube Pressure Circuit 1Diagnostic flag. Needs: CVHSUINT16Read0 = Normal; 1 = In Alarm
IR4260doc 34261Diagnostic: Low Differential Oil Pressure Circuit 1Diagnostic flag. Needs: CVHE,F,G,H,L,M CVGFUINT16Read0 = Normal; 1 = In Alarm
IR4261doc 34262Diagnostic: Low Evap Leaving Water Temp: Unit OffDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4262doc 34263Diagnostic: Low Evap Leaving Water Temp: Unit OnDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4263doc 34264Diagnostic: Low Evaporator Refrigerant TemperatureDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4264doc 34265Diagnostic: Low Evaporator Water FlowDiagnostic flag. Needs: Water Flow SensingUINT16Read0 = Normal; 1 = In Alarm
IR4265doc 34266Diagnostic: Low Oil Temperature Circuit 1Diagnostic flag. Needs: CVHE,F,G,H, L CVGFUINT16Read0 = Normal; 1 = In Alarm
IR4266doc 34267Diagnostic: Lube Pressure Sensor Calibration Circuit 1Diagnostic flag. Needs: CVHSUINT16Read0 = Normal; 1 = In Alarm
IR4267doc 34268Diagnostic: Lube Pump Disch Pressure Xdcr Circuit 1Diagnostic flag. Needs: CVHSUINT16Read0 = Normal; 1 = In Alarm
IR4268doc 34269Diagnostic: Lube Pump Override: Low Diff Press Circuit 1Diagnostic flag. Needs: CVHSUINT16Read0 = Normal; 1 = In Alarm
IR4269doc 34270Diagnostic: Lube Pump Override: Low Flow 1st Stage Circuit 1Diagnostic flag. Needs: CVHSUINT16Read0 = Normal; 1 = In Alarm
IR4270doc 34271Diagnostic: Lube Pump Override: Low Flow 2nd Stage Circuit 1Diagnostic flag. Needs: CVHSUINT16Read0 = Normal; 1 = In Alarm
IR4271doc 34272Diagnostic: Lube Pump Suction Pressure Xdcr Circuit 1Diagnostic flag. Needs: CVHSUINT16Read0 = Normal; 1 = In Alarm
IR4272doc 34273Diagnostic: Momentary Power LossDiagnostic flag. Needs: Momentary Power LossUINT16Read0 = Normal; 1 = In Alarm
IR4273doc 34274Diagnostic: Motor Coolant Temperature Sensor Circuit 1Diagnostic flag. Needs: MTC Temperature SensorUINT16Read0 = Normal; 1 = In Alarm
IR4274doc 34275Diagnostic: Motor Current Overload Circuit 1Diagnostic flag. Needs: EM Starters Solid State Starters Non-comm AFDsUINT16Read0 = Normal; 1 = In Alarm
IR4275doc 34276Diagnostic: Motor Temperature Cutout Tripped Circuit 1Diagnostic flag. Needs: MTC SwitchUINT16Read0 = Normal; 1 = In Alarm
IR4276doc 34277Diagnostic: Motor Winding Temperature 1 Sensor Circuit 1Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4277doc 34278Diagnostic: Motor Winding Temperature 2 Sensor Circuit 1Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4278doc 34279Diagnostic: Motor Winding Temperature 3 Sensor Circuit 1Diagnostic flag. Needs: CVHE,F,G,H, L CVGFUINT16Read0 = Normal; 1 = In Alarm
IR4279doc 34280Diagnostic: MP: Invalid ConfigurationDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4280doc 34281Diagnostic: MP: Reset Has OccurredDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4281doc 34282Diagnostic: Oil Pressure Sensor Calibration Circuit 1Diagnostic flag. Needs: CVHE,F,G,H,L,MUINT16Read0 = Normal; 1 = In Alarm
IR4282doc 34283Diagnostic: Oil Pump Discharge Pressure Transducer Circuit 1Diagnostic flag. Needs: CVHE,F,G,H,L,MUINT16Read0 = Normal; 1 = In Alarm
IR4283doc 34284Diagnostic: Oil Tank Pressure Transducer Circuit 1Diagnostic flag. Needs: CVHE,F,G,H,L,MUINT16Read0 = Normal; 1 = In Alarm
IR4284doc 34285Diagnostic: Oil Tank Temperature Sensor Circuit 1Diagnostic flag. Needs: CVHE,F,G,H,L,M CVGFUINT16Read0 = Normal; 1 = In Alarm
IR4285doc 34286Diagnostic: Outboard Bearing Pad Temp 1 Sensor Circuit 1Diagnostic flag. Needs: CVHHUINT16Read0 = Normal; 1 = In Alarm
IR4286doc 34287Diagnostic: Outboard Bearing Pad Temp 2 Sensor Circuit 1Diagnostic flag. Needs: CVHHUINT16Read0 = Normal; 1 = In Alarm
IR4287doc 34288Diagnostic: Outboard Bearing Pad Temp 3 Sensor Circuit 1Diagnostic flag. Needs: CVHHUINT16Read0 = Normal; 1 = In Alarm
IR4288doc 34289Diagnostic: Outboard Bearing Temperature Sensor Circuit 1Diagnostic flag. Needs: Bearing Temp SensorUINT16Read0 = Normal; 1 = In Alarm
IR4289doc 34290Diagnostic: Outdoor Air Temperature SensorDiagnostic flag. Needs: Outdoor Air Temp SensorUINT16Read0 = Normal; 1 = In Alarm
IR4290doc 34291Diagnostic: Over Voltage Circuit 1Diagnostic flag. Needs: Line Voltage SensingUINT16Read0 = Normal; 1 = In Alarm
IR4291doc 34292Diagnostic: Phase Loss Circuit 1Diagnostic flag. Needs: EM Starters Solid State Starters Non-comm AFDsUINT16Read0 = Normal; 1 = In Alarm
IR4292doc 34293Diagnostic: Phase Reversal Circuit 1Diagnostic flag. Needs: EM Starters Solid State Starters Non-comm AFDsUINT16Read0 = Normal; 1 = In Alarm
IR4293doc 34294Diagnostic: Power Loss Circuit 1Diagnostic flag. Needs: EM Starters Solid State Starters Non-comm AFDsUINT16Read0 = Normal; 1 = In Alarm
IR4294doc 34295Diagnostic: Purge Carbon Regen Temp Limit Exceeded Circuit 1Diagnostic flag. Needs: Purge w/Carbon TankUINT16Read0 = Normal; 1 = In Alarm
IR4295doc 34296Diagnostic: Purge Carbon Regen Temp Not Satisfied Circuit 1Diagnostic flag. Needs: Purge w/Carbon TankUINT16Read0 = Normal; 1 = In Alarm
IR4296doc 34297Diagnostic: Purge Carbon Regen Temperature Too Low Circuit 1Diagnostic flag. Needs: Purge w/Carbon TankUINT16Read0 = Normal; 1 = In Alarm
IR4297doc 34298Diagnostic: Purge Carbon Tank Temperature Sensor Circuit 1Diagnostic flag. Needs: Purge w/Carbon TankUINT16Read0 = Normal; 1 = In Alarm
IR4298doc 34299Diagnostic: Purge Cprsr Suction Rfgt Temp Sensor Circuit 1Diagnostic flag. Needs: PurgeUINT16Read0 = Normal; 1 = In Alarm
IR4299doc 34300Diagnostic: Purge Daily Pumpout Limit Exceeded Circuit 1Diagnostic flag. Needs: PurgeUINT16Read0 = Normal; 1 = In Alarm
IR4300doc 34301Diagnostic: Purge Liquid Level Too High Continuously Circuit 1Diagnostic flag. Needs: PurgeUINT16Read0 = Normal; 1 = In Alarm
IR4301doc 34302Diagnostic: Purge Liquid Level Too High Warning Circuit 1Diagnostic flag. Needs: PurgeUINT16Read0 = Normal; 1 = In Alarm
IR4302doc 34303Diagnostic: Purge Regen Cooldown Temp Too High Circuit 1Diagnostic flag. Needs: Purge w/Carbon TankUINT16Read0 = Normal; 1 = In Alarm
IR4303doc 34304Diagnostic: Refrigerant Monitor InputDiagnostic flag. Needs: Refrigerant MonitorUINT16Read0 = Normal; 1 = In Alarm
IR4304doc 34305Diagnostic: Restart InhibitDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4305doc 34306Diagnostic: Severe Current Unbalance Circuit 1Diagnostic flag. Needs: Line Voltage SensingUINT16Read0 = Normal; 1 = In Alarm
IR4306doc 34307Diagnostic: Software Error 1001: Call Trane ServiceDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4307doc 34308Diagnostic: Software Error 1004: Call Trane ServiceDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4308doc 34309Diagnostic: Starter Comm Loss: Main Processor Circuit 1Diagnostic flag. Needs: EM Starters Solid State Starters Non-comm AFDsUINT16Read0 = Normal; 1 = In Alarm
IR4309doc 34310Diagnostic: Starter Contactor Interrupt Failure Circuit 1Diagnostic flag. Needs: EM Starters Solid State Starters Non-comm AFDsUINT16Read0 = Normal; 1 = In Alarm
IR4310doc 34311Diagnostic: Starter Did Not Fully Accelerate Circuit 1Diagnostic flag. Needs: EM Starters Solid State Starters Non-comm AFDsUINT16Read0 = Normal; 1 = In Alarm
IR4311doc 34312Diagnostic: Starter Did Not Transition Circuit 1Diagnostic flag. Needs: EM Starters Solid State Starters Non-comm AFDsUINT16Read0 = Normal; 1 = In Alarm
IR4312doc 34313Diagnostic: Starter Dry Run Test Circuit 1Diagnostic flag. Needs: EM Starters Solid State Starters Non-comm AFDsUINT16Read0 = Normal; 1 = In Alarm
IR4313doc 34314Diagnostic: Starter Failed to Arm/Start Circuit 1Diagnostic flag. Needs: EM Starters Solid State Starters Non-comm AFDsUINT16Read0 = Normal; 1 = In Alarm
IR4314doc 34315Diagnostic: Starter Fault Circuit 1Diagnostic flag. Needs: EM Starters Solid State Starters Non-comm AFDsUINT16Read0 = Normal; 1 = In Alarm
IR4315doc 34316Diagnostic: Starter Fault Type I Circuit 1Diagnostic flag. Needs: EM Starters Solid State Starters Non-comm AFDsUINT16Read0 = Normal; 1 = In Alarm
IR4316doc 34317Diagnostic: Starter Fault Type II Circuit 1Diagnostic flag. Needs: EM Starters Solid State Starters Non-comm AFDsUINT16Read0 = Normal; 1 = In Alarm
IR4317doc 34318Diagnostic: Starter Fault Type III Circuit 1Diagnostic flag. Needs: EM Starters Solid State Starters Non-comm AFDsUINT16Read0 = Normal; 1 = In Alarm
IR4318doc 34319Diagnostic: Starter Module Memory Error Type 1 Circuit 1Diagnostic flag. Needs: EM Starters Solid State Starters Non-comm AFDsUINT16Read0 = Normal; 1 = In Alarm
IR4319doc 34320Diagnostic: Starter Module Memory Error Type 2 Circuit 1Diagnostic flag. Needs: EM Starters Solid State Starters Non-comm AFDsUINT16Read0 = Normal; 1 = In Alarm
IR4320doc 34321Diagnostic: Transition Complete Input Opened Circuit 1Diagnostic flag. Needs: EM Starters Solid State Starters Non-comm AFDsUINT16Read0 = Normal; 1 = In Alarm
IR4321doc 34322Diagnostic: Transition Complete Input Shorted Circuit 1Diagnostic flag. Needs: EM Starters Solid State Starters Non-comm AFDsUINT16Read0 = Normal; 1 = In Alarm
IR4322doc 34323Diagnostic: Under Voltage Circuit 1Diagnostic flag. Needs: Line Voltage SensingUINT16Read0 = Normal; 1 = In Alarm
IR4323doc 34324Diagnostic: Unexpected Differential Lube Pressure Circuit 1Diagnostic flag. Needs: CVHSUINT16Read0 = Normal; 1 = In Alarm
IR4324doc 34325Diagnostic: Unexpected Differential Oil Pressure Circuit 1Diagnostic flag. Needs: CVHE,F,G,H,L,M CVGFUINT16Read0 = Normal; 1 = In Alarm
IR4325doc 34326Diagnostic: Unexpected Starter Shutdown Circuit 1Diagnostic flag. Needs: EM Starters Solid State Starters Non-comm AFDsUINT16Read0 = Normal; 1 = In Alarm
IR4326doc 34327Diagnostic: Vibration Sensor InputDiagnostic flag. Needs: Vibration SensorUINT16Read0 = Normal; 1 = In Alarm
IR4327doc 34328Comm Loss: Evap Refrigerant Pressure Circuit 1Diagnostic flag. Needs: Evap Pressure SensorUINT16Read0 = Normal; 1 = In Alarm
IR4328doc 34329Diagnostic: Evaporator Refrigerant Pressure Xdcr Circuit 1Diagnostic flag. Needs: Evap Pressure SensorUINT16Read0 = Normal; 1 = In Alarm
IR4329doc 34330Diagnostic: Inverted Heat Recovery Approach Temperature Circuit 1Diagnostic flag. Needs: Heat RecoveryUINT16Read0 = Normal; 1 = In Alarm
IR4330doc 34331Comm Loss: Sporlan Automatic Econ Valve Circuit 1Diagnostic flag. Needs: Sporlan Automatic ValveUINT16Read0 = Normal; 1 = In Alarm
IR4331doc 34332Comm Loss: Sporlan Automatic Cond Valve Circuit 1Diagnostic flag. Needs: Sporlan Automatic ValveUINT16Read0 = Normal; 1 = In Alarm
IR4332doc 34333Comm Loss: Trane IGV Cond Valve Circuit 1Diagnostic flag. Needs: Variable OrificeUINT16Read0 = Normal; 1 = In Alarm
IR4333doc 34334Comm Loss: Trane IGV Econ Valve Circuit 1Diagnostic flag. Needs: Variable OrificeUINT16Read0 = Normal; 1 = In Alarm
IR4334doc 34335Diagnostic: External Hot Water SetpointDiagnostic flag. Needs: External Hot Water SetpointUINT16Read0 = Normal; 1 = In Alarm
IR4335doc 34336Diagnostic: External Chilled Water SetpointDiagnostic flag. Needs: External Chilled Water SetpointUINT16Read0 = Normal; 1 = In Alarm
IR4336doc 34337Comm Loss: External Hot Wtr SetpointDiagnostic flag. Needs: External Hot Water SetpointUINT16Read0 = Normal; 1 = In Alarm
IR4337doc 34338Comm Loss: External Chilled Wtr SetpointDiagnostic flag. Needs: External Chilled Water SetpointUINT16Read0 = Normal; 1 = In Alarm
IR4338doc 34339Comm Loss: Motor Cooling Vent Valve Circuit 1Diagnostic flag. Needs: Booster Heat PumpUINT16Read0 = Normal; 1 = In Alarm
IR4339doc 34340Diagnostic: Motor Cooling Vent Valve Position Error Circuit 1Diagnostic flag. Needs: Booster Heat PumpUINT16Read0 = Normal; 1 = In Alarm
IR4340doc 34341Comm Loss: Oil Heat Exchanger Vent Valve Circuit 1Diagnostic flag. Needs: Booster Heat PumpUINT16Read0 = Normal; 1 = In Alarm
IR4341doc 34342Diagnostic: Oil Heat Exchanger Vent Valve Position Error Circuit 1Diagnostic flag. Needs: Booster Heat PumpUINT16Read0 = Normal; 1 = In Alarm
IR4342doc 34343Diagnostic: High Evaporator Refrigerant TemperatureDiagnostic flag. Needs: Booster Heat PumpUINT16Read0 = Normal; 1 = In Alarm
IR4343doc 34344Diagnostic: Low Condenser Water FlowDiagnostic flag. Needs: Hot Water ControlUINT16Read0 = Normal; 1 = In Alarm
IR4344doc 34345Diagnostic: Low Heat Recovery Water FlowDiagnostic flag. Needs: Heat RecoveryUINT16Read0 = Normal; 1 = In Alarm
IR4345doc 34346Comm Loss: External Diagnostic ResetDiagnostic flag. Needs: External Diagnostic ResetUINT16Read0 = Normal; 1 = In Alarm
IR4346doc 34347Diagnostic: Economizer Refrigerant PressureDiagnostic flag. Needs: Variable OrificeUINT16Read0 = Normal; 1 = In Alarm
IR4347doc 34348Diagnostic: Motor Cooling Pressure Sensor Circuit 1Diagnostic flag. Needs: Booster Heat PumpUINT16Read0 = Normal; 1 = In Alarm
IR4348doc 34349Comm Loss: Motor Cooling Valve Circuit 1Diagnostic flag. Needs: Booster Heat PumpUINT16Read0 = Normal; 1 = In Alarm
IR4349doc 34350Comm Loss: Motor Cooling Pressure Sensor Circuit 1Diagnostic flag. Needs: Booster Heat PumpUINT16Read0 = Normal; 1 = In Alarm
HR10doc 40011Chilled Water SetpointTemperature in the factory unit system (I-P or SI).FLOAT32ABCDRead/write
HR12doc 40013Demand Limit SetpointFLOAT32ABCD%Read/write
HR14doc 40015Hot Water SetpointTemperature in the factory unit system (I-P or SI). Needs: Hot Water ControlFLOAT32ABCDRead/write
HR16doc 40017Base Loading SetpointNeeds: Base LoadingFLOAT32ABCD%Read/write
HR18doc 40019BAS Cooling Differential to StartTemperature difference, factory unit system (I-P or SI).FLOAT32ABCDRead/write
HR20doc 40021BAS Cooling Differential to StopTemperature difference, factory unit system (I-P or SI).FLOAT32ABCDRead/write
HR22doc 40023BAS Heating Differential to StartTemperature difference, factory unit system (I-P or SI). Needs: Hot Water ControlFLOAT32ABCDRead/write
HR24doc 40025BAS Heating Differential to StopTemperature difference, factory unit system (I-P or SI). Needs: Hot Water ControlFLOAT32ABCDRead/write
HR2010doc 42011Chiller Mode Command BASUINT16Read/write1 = Cool; 2 = Heat; 3 = Ice Making; 4 = Free Cooling
HR3010doc 43011Base Loading RequestNeeds: Base LoadingUINT16Read/write0 = Off; 1 = On
HR3011doc 43012Reset DiagnosticUINT16Read/write0 = Normal; 1 = Reset
HR3012doc 43013Evaporator Water Pump Request BASUINT16Read/write0 = Auto; 1 = On
HR3013doc 43014Condenser Water Pump Request BASUINT16Read/write0 = Auto; 1 = On
HR3014doc 43015Chiller Auto Stop Command BASUINT16Read/write0 = Stop; 1 = Auto
HR3015doc 43016Energy Consumption ResetDepends on starter/drive options; see the source configuration column.UINT16Read/write0 = Accumulating; 1 = Reset

Notes on this map

Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.

Questions about the Trane CenTraVac simplex centrifugal chiller (Symbio 800)

What Modbus registers does the Trane CenTraVac simplex centrifugal chiller (Symbio 800) have?

This map lists 546 registers: 531 input registers, 15 holding registers. 15 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.

Are the Trane CenTraVac simplex centrifugal chiller (Symbio 800) Modbus addresses 0-based or 1-based?

The manufacturer's document numbers registers Modicon 3xxxx/4xxxx (drop the prefix, subtract 1). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. The list prints Modicon register numbers: 3xxxx are input registers and 4xxxx holding registers, so 30011 is input register address 10 and 42011 is holding register address 2010.

What byte order does the Trane CenTraVac simplex centrifugal chiller (Symbio 800) use for 32-bit values?

Multi-register values in this map use ABCD (high word first (big-endian)). Set your client to this order for every 32/64-bit value in the table.

What are the minimum Modbus registers to integrate the Trane CenTraVac simplex centrifugal chiller (Symbio 800)?

Start with IR 10 Active Chilled Water Setpoint (Active chilled water setpoint); IR 24 Evaporator Leaving Water Temperature (Evaporator leaving water temperature); IR 26 Evaporator Entering Water Temperature (Evaporator entering water temperature); IR 2010 Running Mode (Running mode); IR 3023 Chiller Running State (Chiller running state); IR 3028 Diagnostic Present (Diagnostic present); HR 10 Chilled Water Setpoint (Chilled water setpoint (BAS)); HR 2010 Chiller Mode Command BAS (BAS chiller mode command); HR 3014 Chiller Auto Stop Command BAS (Chiller auto/stop command (BAS)); HR 3011 Reset Diagnostic (Reset diagnostic).

How do I enable Modbus control of the Trane CenTraVac simplex centrifugal chiller (Symbio 800)?

On the Symbio 800 web interface go to Installation > Identification and Communications > Protocol Configuration and select Modbus RTU or Modbus TCP (per Trane's Symbio 800 integration guides).

Where is the official Trane CenTraVac simplex centrifugal chiller (Symbio 800) Modbus documentation?

The source is Symbio 800 Integration Points List, BACnet/Modbus, CenTraVac (BAS-PTS009C-EN), revision 2025-12-12, published free by Trane at https://elibrary.tranetechnologies.com/public/commercial-hvac/Literature/Points%20List/BAS-PTS009C-EN_12122025.pdf.

More Trane Modbus register maps

Other chillers & heat pumps register maps

All chillers & heat pumps Modbus register maps →

Source: Symbio 800 Integration Points List, BACnet/Modbus, CenTraVac · BAS-PTS009C-EN · rev. 2025-12-12. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.