Trane CenTraVac simplex centrifugal chiller (Symbio 800) Modbus register map
Updated 19 November 2026
Trane's CenTraVac is a large water-cooled centrifugal chiller; this map covers the single-compressor (simplex) models controlled by a Symbio 800, which serves BACnet and Modbus RTU/TCP from one points list. It covers the analog inputs (setpoints, water temperatures and flows, refrigerant and oil pressures, purge, starter/drive and energy values), BAS setpoints, binary status points, multi-state modes and the diagnostic flags.
This page lists 546 Modbus registers for the Trane CenTraVac simplex centrifugal chiller (Symbio 800) — 15 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Trane’s own free documentation (linked below) and checked against it.
- Manufacturer
- Trane
- Model
- CenTraVac simplex centrifugal chiller (Symbio 800)
- Equipment type
- Chiller
- Registers
- 546 (15 writable)
- Transport
- Modbus RTU, Modbus TCP
- Default unit ID
- Not stated
- Default serial
- 19200 baud, 8E1
- Documented addressing
- Modicon 3xxxx/4xxxx (drop the prefix, subtract 1)
- 32-bit word order
- ABCD high word first (big-endian)
- Also known as
- CVHE, CVHF, CVHG, CVHH, CVHL, CVHM, CVHS, CVGF, CVR, CVZA, CVXA, CenTraVac Simplex Symbio 800, CenTraVac simplex
Integration notes: Trane CenTraVac simplex centrifugal chiller (Symbio 800)
Read the analog inputs as pairs of input registers (float, high word first) and the binary/multi-state points as single registers. Write the BAS setpoints and command points in the 4xxxx holding range.
Minimum registers to map
Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.
| Register | Name | Type | Why | Access |
|---|---|---|---|---|
| IR 10 | Active Chilled Water Setpoint | FLOAT32 ABCD | Active chilled water setpoint | Read |
| IR 24 | Evaporator Leaving Water Temperature | FLOAT32 ABCD | Evaporator leaving water temperature | Read |
| IR 26 | Evaporator Entering Water Temperature | FLOAT32 ABCD | Evaporator entering water temperature | Read |
| IR 2010 | Running Mode | UINT16 | Running mode | Read |
| IR 3023 | Chiller Running State | UINT16 | Chiller running state | Read |
| IR 3028 | Diagnostic Present | UINT16 | Diagnostic present | Read |
| HR 10 | Chilled Water Setpoint | FLOAT32 ABCD | Chilled water setpoint (BAS) | Read/write |
| HR 2010 | Chiller Mode Command BAS | UINT16 | BAS chiller mode command | Read/write |
| HR 3014 | Chiller Auto Stop Command BAS | UINT16 | Chiller auto/stop command (BAS) | Read/write |
| HR 3011 | Reset Diagnostic | UINT16 | Reset diagnostic | Read/write |
Enable Modbus control & writes
On the Symbio 800 web interface go to Installation > Identification and Communications > Protocol Configuration and select Modbus RTU or Modbus TCP (per Trane's Symbio 800 integration guides).
Byte order & addressing
- Analog values are 32-bit floats in two consecutive registers, high word first.
- 0xFFFF in a binary or multi-state register and NaN in an analog register mean the value is invalid or not present.
Network setup
- The Modbus RTU address comes from the controller's rotary dials (1-247); address 000 disables Modbus RTU.
- Serial defaults are 19200 bps, even parity, 1 stop bit (set in the web interface's Protocol Configuration tab); wire RS-485 to the P1 link.
- Modbus TCP uses Ethernet port 1 (port 2 is reserved for the touch screen) and the IP address set on the IP Configuration tab; the rotary address is ignored for TCP and the Wi-Fi module is not supported for Modbus TCP.
Watch out for
- Points not supported by the unit's configuration are absent; confirm the configuration dependencies before mapping.
Trane CenTraVac simplex centrifugal chiller (Symbio 800) Modbus registers
Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.
| Table | Address | Name | Description | Type | Order | Scale | Units | Access | Values / bits |
|---|---|---|---|---|---|---|---|---|---|
| IR | 10doc 30011 | Active Chilled Water Setpoint | Temperature in the factory unit system (I-P or SI). | FLOAT32 | ABCD | Read | |||
| IR | 12doc 30013 | Chilled Water Setpoint Status | Temperature in the factory unit system (I-P or SI). | FLOAT32 | ABCD | Read | |||
| IR | 14doc 30015 | Active Base Loading Setpoint | Needs: Base Loading | FLOAT32 | ABCD | % | Read | ||
| IR | 16doc 30017 | Active Hot Water Setpoint | Temperature in the factory unit system (I-P or SI). Needs: Hot Water Control | FLOAT32 | ABCD | Read | |||
| IR | 18doc 30019 | Calculated Chiller Capacity | Cooling capacity in the factory unit system (I-P or SI). Needs: Evap Water Flow Sensing | FLOAT32 | ABCD | Read | |||
| IR | 20doc 30021 | Total Demand Distortion | Needs: Active Harmonic Dampening | FLOAT32 | ABCD | % | Read | ||
| IR | 22doc 30023 | Active Cool/Heat Setpoint Temperature | Temperature in the factory unit system (I-P or SI). | FLOAT32 | ABCD | Read | |||
| IR | 24doc 30025 | Evaporator Leaving Water Temperature | Temperature in the factory unit system (I-P or SI). | FLOAT32 | ABCD | Read | |||
| IR | 26doc 30027 | Evaporator Entering Water Temperature | Temperature in the factory unit system (I-P or SI). | FLOAT32 | ABCD | Read | |||
| IR | 28doc 30029 | Condenser Entering Water Temperature | Temperature in the factory unit system (I-P or SI). | FLOAT32 | ABCD | Read | |||
| IR | 30doc 30031 | Condenser Leaving Water Temperature | Temperature in the factory unit system (I-P or SI). | FLOAT32 | ABCD | Read | |||
| IR | 32doc 30033 | Evaporator Water Flow Rate | Water flow in the factory unit system (I-P or SI). Needs: Evap Water Flow Sensing | FLOAT32 | ABCD | Read | |||
| IR | 34doc 30035 | Evaporator Differential Water Pressure | Needs: Evap Water Flow Differential Pressure or Dual Pressure Sensors | FLOAT32 | ABCD | Read | |||
| IR | 36doc 30037 | Condenser Water Flow Rate | Water flow in the factory unit system (I-P or SI). Needs: Cond Water Flow Sensing | FLOAT32 | ABCD | Read | |||
| IR | 38doc 30039 | Condenser Differential Water Pressure | Needs: Cond Water Flow Differential Pressure or Dual Pressure Sensors | FLOAT32 | ABCD | Read | |||
| IR | 40doc 30041 | Heat Recovery Entering Water Temperature | Temperature in the factory unit system (I-P or SI). Needs: Heat Recovery | FLOAT32 | ABCD | Read | |||
| IR | 42doc 30043 | Heat Recovery Leaving Water Temperature | Temperature in the factory unit system (I-P or SI). Needs: Heat Recovery | FLOAT32 | ABCD | Read | |||
| IR | 44doc 30045 | AFD Last Diagnostic Code Ckt1 | Needs: Unit Mount AFD w/o THD filter Remote Mount Comm AFD (PF6000) | FLOAT32 | ABCD | Read | |||
| IR | 46doc 30047 | Unit Source ID (Last Diagnostic Code) | FLOAT32 | ABCD | Read | ||||
| IR | 48doc 30049 | Drive Input Voltage Calculated | Voltage. Needs: TR200 Modbus AFD Communicating AFD (AFD3) Communicating AFD (PF755) | FLOAT32 | ABCD | Read | |||
| IR | 50doc 30051 | Number of Circuits | FLOAT32 | ABCD | Read | ||||
| IR | 52doc 30053 | Number of Compressors Circuit 1 | FLOAT32 | ABCD | Read | ||||
| IR | 54doc 30055 | Number of Compressors Circuit 2 | FLOAT32 | ABCD | Read | ||||
| IR | 56doc 30057 | Refrigerant Monitor | Refrigerant concentration reading. Needs: Refrigerant Monitor | FLOAT32 | ABCD | Read | |||
| IR | 58doc 30059 | Evaporator Refrigerant Pressure Circuit 1 | Pressure in the factory unit system (I-P or SI). | FLOAT32 | ABCD | Read | |||
| IR | 60doc 30061 | Condenser Refrigerant Pressure Circuit 1 | Pressure in the factory unit system (I-P or SI). | FLOAT32 | ABCD | Read | |||
| IR | 62doc 30063 | Differential Refrigerant Pressure Circuit 1 | Differential pressure in the factory unit system (I-P or SI). | FLOAT32 | ABCD | Read | |||
| IR | 64doc 30065 | Low Side Oil Pressure - Compressor 1A | Needs: Not CVHS or CVGF CVR w/Oil Pressure Transducers or Oil Lite | FLOAT32 | ABCD | Read | |||
| IR | 66doc 30067 | High Side Oil Pressure - Compressor 1A | Needs: Not CVHS or CVGF CVR w/Oil Pressure Transducers or Oil Lite | FLOAT32 | ABCD | Read | |||
| IR | 68doc 30069 | Oil Differential Pressure Circuit 1 | Needs: Not CVHS or CVGF CVR w/Oil Pressure Transducers or Oil Lite | FLOAT32 | ABCD | Read | |||
| IR | 70doc 30071 | Oil Temperature - Compressor 1A | Temperature in the factory unit system (I-P or SI). Needs: Not CVHS | FLOAT32 | ABCD | Read | |||
| IR | 72doc 30073 | Evaporator Saturated Refrigerant Temperature Circuit 1 | Temperature in the factory unit system (I-P or SI). | FLOAT32 | ABCD | Read | |||
| IR | 74doc 30075 | Condenser Saturated Refrigerant Temperature Circuit 1 | Temperature in the factory unit system (I-P or SI). | FLOAT32 | ABCD | Read | |||
| IR | 76doc 30077 | Refrigerant Discharge Temperature - Compressor 1A | Temperature in the factory unit system (I-P or SI). Needs: Discharge Temperature Protection | FLOAT32 | ABCD | Read | |||
| IR | 78doc 30079 | Inlet Guide Vane 1 Percent Open Circuit 1 | FLOAT32 | ABCD | % | Read | |||
| IR | 80doc 30081 | Inlet Guide Vane 2 Percent Open Circuit 1 | Needs: Dual IGV2 | FLOAT32 | ABCD | % | Read | ||
| IR | 82doc 30083 | Purge Carbon Tank Temperature Circuit 1 | Temperature in the factory unit system (I-P or SI). Needs: Purge w/Carbon Tank | FLOAT32 | ABCD | Read | |||
| IR | 84doc 30085 | Purge Liquid Temperature Circuit 1 | Temperature in the factory unit system (I-P or SI). Needs: Purge | FLOAT32 | ABCD | Read | |||
| IR | 86doc 30087 | Purge Refrigerant Compressor Suction Temperature Circuit 1 | Temperature in the factory unit system (I-P or SI). Needs: Purge | FLOAT32 | ABCD | Read | |||
| IR | 88doc 30089 | Time Until Next Purge Run Circuit 1 (in seconds) | Needs: Purge | FLOAT32 | ABCD | s | Read | ||
| IR | 90doc 30091 | Purge Pumpout Chiller On % (7 Days) Circuit 1 | Needs: Purge | FLOAT32 | ABCD | % | Read | ||
| IR | 92doc 30093 | Purge Pumpout Chiller Off % (7 Days) Circuit 1 | Needs: Purge | FLOAT32 | ABCD | % | Read | ||
| IR | 94doc 30095 | Purge 24 Hour Pumpout Circuit 1 (in seconds) | Needs: Purge | FLOAT32 | ABCD | s | Read | ||
| IR | 96doc 30097 | Purge Pumpout - Life Circuit 1 (in seconds) | Needs: Purge | FLOAT32 | ABCD | s | Read | ||
| IR | 98doc 30099 | Refrigeration - Life Circuit 1 (in seconds) | Needs: Purge | FLOAT32 | ABCD | s | Read | ||
| IR | 100doc 30101 | Starts - Compressor 1A | FLOAT32 | ABCD | Read | ||||
| IR | 102doc 30103 | Run Time - Compressor 1A (in seconds) | FLOAT32 | ABCD | s | Read | |||
| IR | 104doc 30105 | Phase AB Voltage - Compressor 1A | Depends on starter/drive options; see the source configuration column. | FLOAT32 | ABCD | Read | |||
| IR | 106doc 30107 | Phase BC Voltage - Compressor 1A | Depends on starter/drive options; see the source configuration column. | FLOAT32 | ABCD | Read | |||
| IR | 108doc 30109 | Phase CA Voltage - Compressor 1A | Depends on starter/drive options; see the source configuration column. | FLOAT32 | ABCD | Read | |||
| IR | 110doc 30111 | Starter Average Phase Volt Circuit 1 | Depends on starter/drive options; see the source configuration column. | FLOAT32 | ABCD | Read | |||
| IR | 112doc 30113 | Line 1 Current - Compressor 1A | Depends on starter/drive options; see the source configuration column. | FLOAT32 | ABCD | Read | |||
| IR | 114doc 30115 | Line 2 Current - Compressor 1A | Depends on starter/drive options; see the source configuration column. | FLOAT32 | ABCD | Read | |||
| IR | 116doc 30117 | Line 3 Current - Compressor 1A | Depends on starter/drive options; see the source configuration column. | FLOAT32 | ABCD | Read | |||
| IR | 118doc 30119 | Average Line Current Circuit 1 | Depends on starter/drive options; see the source configuration column. | FLOAT32 | ABCD | Read | |||
| IR | 120doc 30121 | Line 1 Current RLA - Compressor 1A | Depends on starter/drive options; see the source configuration column. | FLOAT32 | ABCD | % | Read | ||
| IR | 122doc 30123 | Line 2 Current RLA - Compressor 1A | Depends on starter/drive options; see the source configuration column. | FLOAT32 | ABCD | % | Read | ||
| IR | 124doc 30125 | Line 3 Current RLA - Compressor 1A | Depends on starter/drive options; see the source configuration column. | FLOAT32 | ABCD | % | Read | ||
| IR | 126doc 30127 | Actual Running Capacity | Depends on starter/drive options; see the source configuration column. | FLOAT32 | ABCD | % | Read | ||
| IR | 128doc 30129 | Unit Power Consumption | Depends on starter/drive options; see the source configuration column. | FLOAT32 | ABCD | Read | |||
| IR | 130doc 30131 | Starter Load Power Factor - Compressor 1A | Depends on starter/drive options; see the source configuration column. | FLOAT32 | ABCD | Read | |||
| IR | 132doc 30133 | Inboard Bearing Temperature Circuit 1 | Temperature in the factory unit system (I-P or SI). Needs: Bearing Temp Sensors (Not CVHM) | FLOAT32 | ABCD | Read | |||
| IR | 134doc 30135 | Outboard Bearing Temperature Circuit 1 | Temperature in the factory unit system (I-P or SI). Needs: Bearing Temp Sensors | FLOAT32 | ABCD | Read | |||
| IR | 136doc 30137 | Motor Winding Temperature 1 Circuit 1 | Temperature in the factory unit system (I-P or SI). | FLOAT32 | ABCD | Read | |||
| IR | 138doc 30139 | Motor Winding Temperature 2 Circuit 1 | Temperature in the factory unit system (I-P or SI). | FLOAT32 | ABCD | Read | |||
| IR | 140doc 30141 | Motor Winding Temperature 3 Circuit 1 | Temperature in the factory unit system (I-P or SI). Needs: Not CVHS and CVHM | FLOAT32 | ABCD | Read | |||
| IR | 142doc 30143 | AFD Frequency Circuit 1 | Depends on starter/drive options; see the source configuration column. | FLOAT32 | ABCD | Read | |||
| IR | 144doc 30145 | AFD Transistor Temperature Circuit 1 | Depends on starter/drive options; see the source configuration column. | FLOAT32 | ABCD | Read | |||
| IR | 146doc 30147 | Drive Average Line Current Circuit 1 | Depends on starter/drive options; see the source configuration column. | FLOAT32 | ABCD | Read | |||
| IR | 148doc 30149 | Drive Current Line 1 Circuit 1 | Current. Needs: Unit Mount AFD (LF2) w/Line Side Items | FLOAT32 | ABCD | Read | |||
| IR | 150doc 30151 | Drive Current Line 2 Circuit 1 | Current. Needs: Unit Mount AFD (LF2) w/Line Side Items | FLOAT32 | ABCD | Read | |||
| IR | 152doc 30153 | Drive Current Line 3 Circuit 1 | Current. Needs: Unit Mount AFD (LF2) w/Line Side Items | FLOAT32 | ABCD | Read | |||
| IR | 154doc 30155 | Drive Line Frequency Circuit 1 | Depends on starter/drive options; see the source configuration column. | FLOAT32 | ABCD | Read | |||
| IR | 156doc 30157 | Drive Frequency Status | Depends on starter/drive options; see the source configuration column. | FLOAT32 | ABCD | Read | |||
| IR | 158doc 30159 | Drive Inverter Base Temperature Circuit 1 | Needs: Unit Mount AFD (LF2) w/Line Side Items Communicating AFD (AFD3) | FLOAT32 | ABCD | Read | |||
| IR | 160doc 30161 | Drive Rectifier Base Temperature Circuit 1 | Needs: Unit Mount AFD (LF2) w/Line Side Items Communicating AFD (AFD3) | FLOAT32 | ABCD | Read | |||
| IR | 162doc 30163 | Drive Output Power Circuit 1 | Depends on starter/drive options; see the source configuration column. | FLOAT32 | ABCD | Read | |||
| IR | 164doc 30165 | Drive Motor Current U RLA Circuit 1 | Depends on starter/drive options; see the source configuration column. | FLOAT32 | ABCD | % | Read | ||
| IR | 166doc 30167 | Drive Motor Current V RLA Circuit 1 | Depends on starter/drive options; see the source configuration column. | FLOAT32 | ABCD | % | Read | ||
| IR | 168doc 30169 | Drive Motor Current W RLA Circuit 1 | Depends on starter/drive options; see the source configuration column. | FLOAT32 | ABCD | % | Read | ||
| IR | 170doc 30171 | Drive Motor Current U Circuit 1 | Depends on starter/drive options; see the source configuration column. | FLOAT32 | ABCD | Read | |||
| IR | 172doc 30173 | Drive Motor Current V Circuit 1 | Depends on starter/drive options; see the source configuration column. | FLOAT32 | ABCD | Read | |||
| IR | 174doc 30175 | Drive Motor Current W Circuit 1 | Depends on starter/drive options; see the source configuration column. | FLOAT32 | ABCD | Read | |||
| IR | 176doc 30177 | Drive Motor Voltage UV Circuit 1 | Voltage. Needs: Communicating AFD (AFD3) | FLOAT32 | ABCD | Read | |||
| IR | 178doc 30179 | Drive Motor Voltage VW Circuit 1 | Voltage. Needs: Communicating AFD (AFD3) | FLOAT32 | ABCD | Read | |||
| IR | 180doc 30181 | Drive Motor Voltage WU Circuit 1 | Voltage. Needs: Communicating AFD (AFD3) | FLOAT32 | ABCD | Read | |||
| IR | 182doc 30183 | Drive Motor Average Voltage Circuit 1 | Depends on starter/drive options; see the source configuration column. | FLOAT32 | ABCD | Read | |||
| IR | 184doc 30185 | Drive Motor Average Current RLA Circuit 1 | Depends on starter/drive options; see the source configuration column. | FLOAT32 | ABCD | % | Read | ||
| IR | 186doc 30187 | Lube Differential Pressure | Differential pressure in the factory unit system (I-P or SI). Needs: CVHS | FLOAT32 | ABCD | Read | |||
| IR | 188doc 30189 | Lube Pump Suction Pressure | Pressure in the factory unit system (I-P or SI). Needs: CVHS | FLOAT32 | ABCD | Read | |||
| IR | 190doc 30191 | Lube Pump Discharge Pressure | Pressure in the factory unit system (I-P or SI). Needs: CVHS | FLOAT32 | ABCD | Read | |||
| IR | 192doc 30193 | Motor Coolant Temperature | Temperature in the factory unit system (I-P or SI). Needs: MTC Temp Sensor | FLOAT32 | ABCD | Read | |||
| IR | 194doc 30195 | AFD % RLA Ripple | Needs: Communicating AFD (AFD3) | FLOAT32 | ABCD | % | Read | ||
| IR | 196doc 30197 | AFD Inverter Module Temperature U | Temperature in the factory unit system (I-P or SI). Needs: Communicating AFD (AFD3) | FLOAT32 | ABCD | Read | |||
| IR | 198doc 30199 | AFD Inverter Module Temperature V | Temperature in the factory unit system (I-P or SI). Needs: Communicating AFD (AFD3) | FLOAT32 | ABCD | Read | |||
| IR | 200doc 30201 | AFD Inverter Module Temperature W | Temperature in the factory unit system (I-P or SI). Needs: Communicating AFD (AFD3) | FLOAT32 | ABCD | Read | |||
| IR | 202doc 30203 | Outboard Bearing Pad Temperature #1 Ckt1 | Temperature in the factory unit system (I-P or SI). Needs: CVHH | FLOAT32 | ABCD | Read | |||
| IR | 204doc 30205 | Outboard Bearing Pad Temperature #2 Ckt1 | Temperature in the factory unit system (I-P or SI). Needs: CVHH | FLOAT32 | ABCD | Read | |||
| IR | 206doc 30207 | Outboard Bearing Pad Temperature #3 Ckt1 | Temperature in the factory unit system (I-P or SI). Needs: CVHH | FLOAT32 | ABCD | Read | |||
| IR | 208doc 30209 | Condenser Control Output | Needs: Head Pressure Control | FLOAT32 | ABCD | % | Read | ||
| IR | 210doc 30211 | Restart Inhibit Time Remaining | FLOAT32 | ABCD | Read | ||||
| IR | 212doc 30213 | Chiller Design Capacity | Cooling capacity in the factory unit system (I-P or SI). | FLOAT32 | ABCD | Read | |||
| IR | 214doc 30215 | Entering Condenser Water Pressure | Pressure in the factory unit system (I-P or SI). Needs: Condenser Water Flow Differential Pressure Sensors | FLOAT32 | ABCD | Read | |||
| IR | 216doc 30217 | Entering Evaporator Water Pressure | Pressure in the factory unit system (I-P or SI). Needs: Evaporator Water Flow Differential Pressure Sensors | FLOAT32 | ABCD | Read | |||
| IR | 218doc 30219 | Leaving Condenser Water Pressure | Pressure in the factory unit system (I-P or SI). Needs: Condenser Water Flow Differential Pressure Sensors | FLOAT32 | ABCD | Read | |||
| IR | 220doc 30221 | Leaving Evaporator Water Pressure | Pressure in the factory unit system (I-P or SI). Needs: Evaporator Water Flow Differential Pressure Sensors | FLOAT32 | ABCD | Read | |||
| IR | 222doc 30223 | Condenser Approach Temperature Circuit 1 | Temperature difference, factory unit system (I-P or SI). | FLOAT32 | ABCD | Read | |||
| IR | 224doc 30225 | Evaporator Approach Temperature Circuit 1 | Temperature difference, factory unit system (I-P or SI). | FLOAT32 | ABCD | Read | |||
| IR | 226doc 30227 | Drive DC Bus Voltage Circuit 1 | Depends on starter/drive options; see the source configuration column. | FLOAT32 | ABCD | Read | |||
| IR | 228doc 30229 | Active Demand Limit Setpoint | FLOAT32 | ABCD | % | Read | |||
| IR | 230doc 30231 | Demand Limit Setpoint Status | Needs: Ice Building | FLOAT32 | ABCD | % | Read | ||
| IR | 232doc 30233 | Drive Heatsink Temperature Compressor 1A | Temperature in the factory unit system (I-P or SI). Needs: TR200 Modbus AFD | FLOAT32 | ABCD | Read | |||
| IR | 234doc 30235 | Heat Recovery Differential Water Pressure | Needs: Heat Recovery Water Flow Differential Pressure or Dual Pressure Sensors | FLOAT32 | ABCD | Read | |||
| IR | 236doc 30237 | Heat Recovery Water Flow Rate | Water flow in the factory unit system (I-P or SI). Needs: Heat Recovery Water Flow Sensing | FLOAT32 | ABCD | Read | |||
| IR | 238doc 30239 | Heat Recovery Calculated Capacity | Needs: Heat Recovery Water Flow Sensing | FLOAT32 | ABCD | Read | |||
| IR | 240doc 30241 | Heat Recovery Entering Water Pressure | Needs: Heat Recovery Water Flow Differential Pressure Sensors | FLOAT32 | ABCD | Read | |||
| IR | 242doc 30243 | Heat Recovery Leaving Water Pressure | Needs: Heat Recovery Water Flow Differential Pressure Sensors | FLOAT32 | ABCD | Read | |||
| IR | 244doc 30245 | Voltage L1-L2 | Voltage. Needs: Energy Meter | FLOAT32 | ABCD | Read | |||
| IR | 246doc 30247 | Voltage L2-L3 | Voltage. Needs: Energy Meter | FLOAT32 | ABCD | Read | |||
| IR | 248doc 30249 | Voltage L1-L3 | Voltage. Needs: Energy Meter | FLOAT32 | ABCD | Read | |||
| IR | 250doc 30251 | Chiller Average Line Voltage | Voltage. Needs: Energy Meter | FLOAT32 | ABCD | Read | |||
| IR | 252doc 30253 | Current L1 | Current. Needs: Energy Meter | FLOAT32 | ABCD | Read | |||
| IR | 254doc 30255 | Current L2 | Current. Needs: Energy Meter | FLOAT32 | ABCD | Read | |||
| IR | 256doc 30257 | Current L3 | Current. Needs: Energy Meter | FLOAT32 | ABCD | Read | |||
| IR | 258doc 30259 | Unit Average Line Current | Current. Needs: Energy Meter | FLOAT32 | ABCD | Read | |||
| IR | 260doc 30261 | Line Frequency | Needs: Energy Meter | FLOAT32 | ABCD | Read | |||
| IR | 262doc 30263 | Power Factor | Needs: Energy Meter | FLOAT32 | ABCD | Read | |||
| IR | 264doc 30265 | Unit Power Demand | Needs: Energy Meter | FLOAT32 | ABCD | Read | |||
| IR | 266doc 30267 | Energy Consumption | Depends on starter/drive options; see the source configuration column. | FLOAT32 | ABCD | Read | |||
| IR | 268doc 30269 | Energy Consumption Lifetime | Depends on starter/drive options; see the source configuration column. | FLOAT32 | ABCD | Read | |||
| IR | 270doc 30271 | Outdoor Air Temperature Local | Temperature in the factory unit system (I-P or SI). Needs: Outdoor Air Temperature | FLOAT32 | ABCD | Read | |||
| IR | 272doc 30273 | Heat Recovery Approach Temperature Circuit 1 | Temperature difference, factory unit system (I-P or SI). Needs: Heat Recovery | FLOAT32 | ABCD | Read | |||
| IR | 274doc 30275 | High Side Oil Gauge Pressure - Compressor 1A | Pressure in the factory unit system (I-P or SI). | FLOAT32 | ABCD | Read | |||
| IR | 276doc 30277 | Low Side Oil Gauge Pressure - Compressor 1A | Pressure in the factory unit system (I-P or SI). | FLOAT32 | ABCD | Read | |||
| IR | 278doc 30279 | Condenser Refrigerant Gauge Pressure Circuit 1 | Pressure in the factory unit system (I-P or SI). | FLOAT32 | ABCD | Read | |||
| IR | 280doc 30281 | Entering Condenser Water Gauge Pressure | Pressure in the factory unit system (I-P or SI). Needs: Condenser Water Flow Differential Pressure Sensors | FLOAT32 | ABCD | Read | |||
| IR | 282doc 30283 | Entering Evaporator Water Gauge Pressure | Pressure in the factory unit system (I-P or SI). Needs: Evaporator Water Flow Differential Pressure Sensors | FLOAT32 | ABCD | Read | |||
| IR | 284doc 30285 | Evaporator Refrigerant Gauge Pressure Circuit 1 | Pressure in the factory unit system (I-P or SI). | FLOAT32 | ABCD | Read | |||
| IR | 286doc 30287 | Heat Recovery Entering Water Gauge Pressure | Needs: Heat Recovery Water Flow Differential Pressure Sensors | FLOAT32 | ABCD | Read | |||
| IR | 288doc 30289 | Heat Recovery Leaving Water Gauge Pressure | Needs: Heat Recovery Water Flow Differential Pressure Sensors | FLOAT32 | ABCD | Read | |||
| IR | 290doc 30291 | Leaving Condenser Water Gauge Pressure | Pressure in the factory unit system (I-P or SI). Needs: Condenser Water Flow Differential Pressure Sensors | FLOAT32 | ABCD | Read | |||
| IR | 292doc 30293 | Leaving Evaporator Water Gauge Pressure | Pressure in the factory unit system (I-P or SI). Needs: Evaporator Water Flow Differential Pressure Sensors | FLOAT32 | ABCD | Read | |||
| IR | 294doc 30295 | Lube Pump Suction Gauge Pressure | Pressure in the factory unit system (I-P or SI). Needs: CVHS | FLOAT32 | ABCD | Read | |||
| IR | 296doc 30297 | Lube Pump Discharge Gauge Pressure | Pressure in the factory unit system (I-P or SI). Needs: CVHS | FLOAT32 | ABCD | Read | |||
| IR | 298doc 30299 | Active Cooling Differential to Start | Temperature difference, factory unit system (I-P or SI). | FLOAT32 | ABCD | Read | |||
| IR | 300doc 30301 | Active Cooling Differential to Stop | Temperature difference, factory unit system (I-P or SI). | FLOAT32 | ABCD | Read | |||
| IR | 302doc 30303 | Active Heating Differential to Start | Temperature difference, factory unit system (I-P or SI). Needs: Hot Water Control | FLOAT32 | ABCD | Read | |||
| IR | 304doc 30305 | Active Heating Differential to Stop | Temperature difference, factory unit system (I-P or SI). Needs: Hot Water Control | FLOAT32 | ABCD | Read | |||
| IR | 306doc 30307 | Calculated Heating Capacity | Needs: Cond Water Flow Sensing | FLOAT32 | ABCD | Read | |||
| IR | 308doc 30309 | Discharge Superheat Compressor 1A | Temperature difference, factory unit system (I-P or SI). Needs: Discharge Temperature Protection | FLOAT32 | ABCD | Read | |||
| IR | 2010doc 32011 | Running Mode | UINT16 | Read | 1 = Chiller Off; 2 = Chiller In Start Mode; 3 = Chiller In Run Mode; 4 = Chiller In Pre-Shutdown Mode; 5 = Chiller In Service Mode | ||||
| IR | 2011doc 32012 | Operating Mode | UINT16 | Read | 1 = Cool; 2 = Heat; 3 = Ice Making; 4 = Free Cooling | ||||
| IR | 2012doc 32013 | Chiller Setpoint Source | UINT16 | Read | 1 = BAS; 2 = External; 3 = Front Panel | ||||
| IR | 2013doc 32014 | Model Information [GEN2] | UINT16 | Read | 1 = CVHF; 2 = CVGF; 3 = CVHS; 11 = CDHF; 12 = CVR; 13 = CVHH; 14 = CDHH; 20 = CVHM; 38 = CVHE; 39 = CVHG; 40 = CVHL; 43 = CDHG; 72 = CVZA; 73 = CVXA | ||||
| IR | 2014doc 32015 | Cooling Type | UINT16 | Read | 1 = Water Cooled | ||||
| IR | 2015doc 32016 | Refrigerant Type | UINT16 | Read | 1 = R-11; 2 = R-12; 3 = R-22; 4 = R-123; 5 = R-134a; 8 = R-113; 9 = R-114; 10 = R-500; 11 = R-502; 13 = R-513A; 14 = R-1233zd(E); 15 = R-514A | ||||
| IR | 2016doc 32017 | Manufacturing Location | UINT16 | Read | 1 = Field Applied; 2 = La Crosse; 15 = Taicang | ||||
| IR | 3010doc 33011 | Base Loading Request Active | Needs: Base Loading | UINT16 | Read | 0 = Off; 1 = On | |||
| IR | 3011doc 33012 | Emergency Stop | UINT16 | Read | 0 = Auto; 1 = Emergency Stop - Manual Reset Required | ||||
| IR | 3012doc 33013 | Manual Override Exists | UINT16 | Read | 0 = Off; 1 = On | ||||
| IR | 3013doc 33014 | Base Loading Active | Needs: Base Loading | UINT16 | Read | 0 = Inactive; 1 = Active | |||
| IR | 3014doc 33015 | Run Enabled | UINT16 | Read | 0 = Run Not Enabled; 1 = Run Enabled | ||||
| IR | 3015doc 33016 | Local Setpoint Control | UINT16 | Read | 0 = Remote Control; 1 = Local Control | ||||
| IR | 3016doc 33017 | Maximum Capacity | UINT16 | Read | 0 = Off; 1 = On | ||||
| IR | 3017doc 33018 | Evaporator Leaving Water Temperature | UINT16 | Read | 0 = Not Limited; 1 = Limited | ||||
| IR | 3018doc 33019 | Head Relief Request | UINT16 | Read | 0 = Off; 1 = On | ||||
| IR | 3019doc 33020 | Hot Gas Bypass Active | Needs: Hot Gas Bypass | UINT16 | Read | 0 = Inactive; 1 = Active | |||
| IR | 3020doc 33021 | Purge Compressor Relay Circuit 1 | Needs: Purge | UINT16 | Read | 0 = Off; 1 = On | |||
| IR | 3021doc 33022 | Pump Out Relay Circuit 1 | Needs: Purge | UINT16 | Read | 0 = Off; 1 = On | |||
| IR | 3022doc 33023 | Purge Regenerating Valve Solenoid Circuit 1 | Needs: Purge w/Carbon Tank | UINT16 | Read | 0 = Off; 1 = On | |||
| IR | 3023doc 33024 | Chiller Running State | UINT16 | Read | 0 = Off; 1 = On | ||||
| IR | 3024doc 33025 | Evaporator Water Pump Request | UINT16 | Read | 0 = Off; 1 = On | ||||
| IR | 3025doc 33026 | Evaporator Water Flow Status | UINT16 | Read | 0 = No Flow; 1 = Flow | ||||
| IR | 3026doc 33027 | Condenser Water Pump Request | UINT16 | Read | 0 = Off; 1 = On | ||||
| IR | 3027doc 33028 | Condenser Water Flow Status | UINT16 | Read | 0 = No Flow; 1 = Flow | ||||
| IR | 3028doc 33029 | Diagnostic Present | UINT16 | Read | 0 = Normal; 1 = In Alarm | ||||
| IR | 3029doc 33030 | Diagnostic Shutdown Present | UINT16 | Read | 0 = Normal; 1 = In Alarm | ||||
| IR | 3030doc 33031 | Diagnostic: Manual Reset Required | UINT16 | Read | 0 = Normal; 1 = In Alarm | ||||
| IR | 3031doc 33032 | Diagnostic: Local Manual Reset Required | UINT16 | Read | 0 = Normal; 1 = In Alarm | ||||
| IR | 3032doc 33033 | Diagnostic Present: Information | UINT16 | Read | 0 = Normal; 1 = In Alarm | ||||
| IR | 3033doc 33034 | Diagnostic Present: Advisory | UINT16 | Read | 0 = Normal; 1 = In Alarm | ||||
| IR | 3034doc 33035 | Diagnostic Present: Critical | UINT16 | Read | 0 = Normal; 1 = In Alarm | ||||
| IR | 3035doc 33036 | Diagnostic Present: Service Required | UINT16 | Read | 0 = Normal; 1 = In Alarm | ||||
| IR | 3036doc 33037 | Compressor 1A Status | UINT16 | Read | 0 = Off; 1 = Running | ||||
| IR | 3037doc 33038 | Front Panel Auto Stop | UINT16 | Read | 0 = Stop; 1 = Auto | ||||
| IR | 3038doc 33039 | External Auto Stop Input Status | UINT16 | Read | 0 = Stop; 1 = Auto | ||||
| IR | 3039doc 33040 | Heat Recovery Water Flow Status | Needs: Heat Recovery Water Flow Switch | UINT16 | Read | 0 = No Flow; 1 = Flow | |||
| IR | 3040doc 33041 | AFD Shutdown Diagnostic Present Circuit 1 | UINT16 | Read | 0 = Normal; 1 = In Alarm | ||||
| IR | 4000doc 34001 | Diagnostic: AFD AD Calibration Error Circuit 1 | Diagnostic flag. Needs: Unit Mount AFD - AFDN,P (AFD3) | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4001doc 34002 | Diagnostic: AFD AHD Frequency Out of Range Circuit 1 | Diagnostic flag. Needs: Unit Mount AFD - AFDN,P (AFD3) | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4002doc 34003 | Diagnostic: AFD AHD Sync Signal Error Circuit 1 | Diagnostic flag. Needs: Unit Mount AFD - AFDN,P (AFD3) | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4003doc 34004 | Diagnostic: AFD Bump Failure Circuit 1 | Diagnostic flag. Needs: Unit Mount AFD - AFDN,P (AFD3) | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4004doc 34005 | Diagnostic: AFD Bus Over Voltage Circuit 1 | Depends on starter/drive options; see the source configuration column. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4005doc 34006 | Diagnostic: AFD Bus Ripple Too High Circuit 1 | Diagnostic flag. Needs: Unit Mount AFD - AFDN,P (AFD3) | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4006doc 34007 | Diagnostic: AFD Bus Under Voltage Circuit 1 | Depends on starter/drive options; see the source configuration column. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4007doc 34008 | Evaporator Leaving Water Temperature | Diagnostic flag. Needs: TR200 Modbus AFD (TR200) | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4008doc 34009 | Diagnostic: AFD Comm Loss: Main Processor Circuit 1 | Depends on starter/drive options; see the source configuration column. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4009doc 34010 | Diagnostic: AFD Control Board Memory Error Type 2 Circuit 1 | Diagnostic flag. Needs: Unit Mount AFD - AFDD,E,F (LF2) Remote Mount Comm AFD - (PF7000) | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4010doc 34011 | Diagnostic: AFD Current Sensor Self Test Failure Circuit 1 | Diagnostic flag. Needs: Unit Mount AFD - AFDN,P (AFD3) | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4011doc 34012 | Diagnostic: AFD Desaturation Detected Circuit 1 | Diagnostic flag. Needs: Unit Mount AFD - AFDN,P (AFD3) | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4012doc 34013 | Diagnostic: AFD DPI Communication Failure Circuit 1 | Diagnostic flag. Needs: Unit Mount AFD - AFDD,E,F (LF2) Remote Mount Comm AFD - (PF7000) | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4013doc 34014 | Diagnostic: AFD Drive Fault Circuit 1 | Diagnostic flag. Needs: MV Remote Mount Comm AFD | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4014doc 34015 | Diagnostic: AFD DSP Board ID Error Circuit 1 | Diagnostic flag. Needs: Unit Mount AFD - AFDN,P (AFD3) | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4015doc 34016 | Diagnostic: AFD DSP Board Initialization Failure Circuit 1 | Diagnostic flag. Needs: Unit Mount AFD - AFDN,P (AFD3) | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4016doc 34017 | Diagnostic: AFD DSP Board Low Voltage Failure Circuit 1 | Diagnostic flag. Needs: Unit Mount AFD - AFDN,P (AFD3) | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4017doc 34018 | Diagnostic: AFD DSP Board Over Temp Circuit 1 | Diagnostic flag. Needs: Unit Mount AFD - AFDN,P (AFD3) | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4018doc 34019 | Diagnostic: AFD Emergency Stop Fault Circuit 1 | Diagnostic flag. Needs: Unit Mount AFD - AFDN,P (AFD3) MV Remote Mount Comm AFD | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4019doc 34020 | Diagnostic: AFD Estimated Junction Over Temp Circuit 1 | Diagnostic flag. Needs: Unit Mount AFD - AFDN,P (AFD3) | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4020doc 34021 | Diagnostic: AFD Excessive AHD Inhibit Circuit 1 | Diagnostic flag. Needs: Unit Mount AFD - AFDN,P (AFD3) | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4021doc 34022 | Diagnostic: AFD External Fault Input Circuit 1 | Diagnostic flag. Needs: Unit Mount Comm AFD - AFDY (PF755) | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4022doc 34023 | Diagnostic: AFD Fatal Software Error Circuit 1 | Diagnostic flag. Needs: Unit Mount AFD - AFDD,E,F (LF2) Remote Mount Comm AFD - (PF7000) | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4023doc 34024 | Diagnostic: AFD Fault Circuit 1 | Diagnostic flag. Needs: TR200 Modbus AFD (TR200) | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4024doc 34025 | Diagnostic: AFD Gate Drive Board Over Temp Circuit 1 | Diagnostic flag. Needs: Unit Mount AFD - AFDN,P (AFD3) | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4025doc 34026 | Diagnostic: AFD Gate Drive Fault Circuit 1 | Diagnostic flag. Needs: Unit Mount AFD - AFDN,P (AFD3) | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4026doc 34027 | Diagnostic: AFD Gate Drive Low Voltage Failure Circuit 1 | Diagnostic flag. Needs: Unit Mount AFD - AFDN,P (AFD3) | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4027doc 34028 | Diagnostic: AFD Gate Drive Module Comm Loss Circuit 1 | Diagnostic flag. Needs: Unit Mount AFD - AFDN,P (AFD3) | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4028doc 34029 | Diagnostic: AFD Gate Kill Active Circuit 1 | Depends on starter/drive options; see the source configuration column. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4029doc 34030 | Diagnostic: AFD General Failure Circuit 1 | Diagnostic flag. Needs: TR200 Modbus AFD (TR200) | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4030doc 34031 | Diagnostic: AFD General Failure Circuit 1 | Depends on starter/drive options; see the source configuration column. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4031doc 34032 | Diagnostic: AFD Ground Fault Circuit 1 | Diagnostic flag. Needs: TR200 Modbus AFD (TR200) | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4032doc 34033 | Diagnostic: AFD Ground Fault Circuit 1 | Depends on starter/drive options; see the source configuration column. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4033doc 34034 | Diagnostic: AFD High Bus Voltage Circuit 1 | Diagnostic flag. Needs: Unit Mount AFD - AFDD,E,F (LF2) Remote Mount Comm AFD - (PF7000) | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4034doc 34035 | Diagnostic: AFD High Temperature Circuit 1 | Diagnostic flag. Needs: Unit Mount AFD - AFDD,E,F (LF2) Remote Mount Comm AFD - (PF7000) | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4035doc 34036 | Diagnostic: AFD I/O Board Failure Circuit 1 | Diagnostic flag. Needs: Unit Mount AFD - AFDD,E,F (LF2) Remote Mount Comm AFD - (PF7000) | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4036doc 34037 | Diagnostic: AFD IGBT Self Test Failure Circuit 1 | Diagnostic flag. Needs: Unit Mount AFD - AFDN,P (AFD3) | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4037doc 34038 | Diagnostic: AFD IMC 24V Detection Failure Circuit 1 | Diagnostic flag. Needs: Unit Mount AFD - AFDN,P (AFD3) | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4038doc 34039 | Diagnostic: AFD Input Transformer or Filter High Temp Circuit 1 | Diagnostic flag. Needs: Unit Mount Comm AFD - AFDY (PF755) | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4039doc 34040 | Diagnostic: AFD Instantaneous Current Overload Circuit 1 | Depends on starter/drive options; see the source configuration column. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4040doc 34041 | Diagnostic: AFD Interrupt Failure Circuit 1 | Diagnostic flag. Needs: Communicating AFD | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4041doc 34042 | Diagnostic: AFD Invalid Drive Command Circuit 1 | Diagnostic flag. Needs: Unit Mount AFD - AFDN,P (AFD3) | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4042doc 34043 | Diagnostic: AFD Inverter Heatsink Over Temp Circuit 1 | Diagnostic flag. Needs: Unit Mount AFD - AFDN,P (AFD3) MV Remote Mount Comm AFD | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4043doc 34044 | Diagnostic: AFD Loss of AHD Sync Signal Circuit 1 | Diagnostic flag. Needs: Unit Mount AFD - AFDN,P (AFD3) | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4044doc 34045 | Diagnostic: AFD Low Rotor Flux Feedback Circuit 1 | Diagnostic flag. Needs: Unit Mount AFD - AFDN,P (AFD3) Unit Mount Comm AFD - AFDY (PF755) | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4045doc 34046 | Diagnostic: AFD Mains Phase Loss Circuit 1 | Diagnostic flag. Needs: TR200 Modbus AFD (TR200) | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4046doc 34047 | Diagnostic: AFD Motor Current Overload Circuit 1 | Diagnostic flag. Needs: TR200 Modbus AFD (TR200) | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4047doc 34048 | Diagnostic: AFD Motor Current Overload Circuit 1 | Depends on starter/drive options; see the source configuration column. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4048doc 34049 | Diagnostic: AFD Motor Fault Circuit 1 | Needs: Unit Mount Comm AFD - AFDY (PF755) Remote Mount Comm AFD - VFDB (PF6000) | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4049doc 34050 | Diagnostic: AFD Motor Short Circuit 1 | Depends on starter/drive options; see the source configuration column. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4050doc 34051 | Diagnostic: AFD Non-Volatile Memory Failure Circuit 1 | Diagnostic flag. Needs: Unit Mount AFD - AFDN,P (AFD3) | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4051doc 34052 | Diagnostic: AFD Output Phase Loss Circuit 1 | Depends on starter/drive options; see the source configuration column. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4052doc 34053 | Diagnostic: AFD Over Temperature Circuit 1 | Needs: Unit Mount Comm AFD - AFDY (PF755) Remote Mount Comm AFD - VFDB (PF6000) | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4053doc 34054 | Diagnostic: AFD Overspeed Circuit 1 | Diagnostic flag. Needs: Unit Mount AFD - AFDN,P (AFD3) | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4054doc 34055 | Diagnostic: AFD Panel Interlock Fault Circuit 1 | Diagnostic flag. Needs: Unit Mount AFD - AFDN,P (AFD3) | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4055doc 34056 | Diagnostic: AFD Panel Interlock Warning Circuit 1 | Diagnostic flag. Needs: Unit Mount AFD - AFDN,P (AFD3) | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4056doc 34057 | Diagnostic: AFD Power Intfc Controller Board Failure Circuit 1 | Diagnostic flag. Needs: Unit Mount AFD - AFDD,E,F (LF2) Remote Mount Comm AFD - (PF7000) | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4057doc 34058 | Diagnostic: AFD Power Loss Circuit 1 | Depends on starter/drive options; see the source configuration column. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4058doc 34059 | Diagnostic: AFD Power Structure Board Failure Circuit 1 | Diagnostic flag. Needs: Unit Mount AFD - AFDD,E,F (LF2) Remote Mount Comm AFD - (PF7000) | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4059doc 34060 | Diagnostic: AFD Precharge Fault Circuit 1 | Needs: Unit Mount Comm AFD - AFDY (PF755) Remote Mount Comm AFD - VFDB (PF6000) | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4060doc 34061 | Diagnostic: AFD Rectifier Heatsink Over Temp Circuit 1 | Diagnostic flag. Needs: Unit Mount AFD - AFDN,P (AFD3) | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4061doc 34062 | Diagnostic: AFD RS485 Board Memory Error Type 2 Circuit 1 | Diagnostic flag. Needs: Unit Mount AFD - AFDD,E,F (LF2) Remote Mount Comm AFD - (PF7000) | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4062doc 34063 | Diagnostic: AFD Safe Stop Circuit 1 | Diagnostic flag. Needs: TR200 Modbus AFD (TR200) | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4063doc 34064 | Diagnostic: AFD Short Circuit Circuit 1 | Diagnostic flag. Needs: TR200 Modbus AFD (TR200) | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4064doc 34065 | Diagnostic: AFD Speed Configuration Mismatch Circuit 1 | Diagnostic flag. Needs: TR200 Modbus AFD (TR200) | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4065doc 34066 | Diagnostic: AFD Start Failure Circuit 1 | Diagnostic flag. Needs: Unit Mount AFD - AFDN,P (AFD3) | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4066doc 34067 | Diagnostic: AFD Temperature Sensor Warning Circuit 1 | Diagnostic flag. Needs: Unit Mount AFD - AFDN,P (AFD3) | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4067doc 34068 | Diagnostic: AFD Watchdog Timer Overflow Circuit 1 | Diagnostic flag. Needs: Unit Mount AFD - AFDN,P (AFD3) | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4068doc 34069 | Diagnostic: At Speed Input Opened Circuit 1 | Diagnostic flag. Needs: Non-comm AFD Solid State Starter | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4069doc 34070 | Diagnostic: At Speed Input Shorted Circuit 1 | Diagnostic flag. Needs: Non-comm AFD Solid State Starter | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4070doc 34071 | Diagnostic: Bearing Lube Flow First Stage Sensor Input | Diagnostic flag. Needs: CVHS | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4071doc 34072 | Diagnostic: Bearing Lube Flow Second Stage Sensor Input | Diagnostic flag. Needs: CVHS | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4072doc 34073 | Diagnostic: Brg Lube Flow Overdue First Stage Circuit 1 | Diagnostic flag. Needs: CVHS | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4073doc 34074 | Diagnostic: Brg Lube Flow Overdue Second Stage Circuit 1 | Diagnostic flag. Needs: CVHS | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4075doc 34076 | Diagnostic: Check Lube Filter Circuit 1 | Diagnostic flag. Needs: CVHS | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4076doc 34077 | Diagnostic: Check Oil Filter Circuit 1 | Diagnostic flag. Needs: Oil Pump | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4077doc 34078 | Diagnostic: Check Oil Heater Circuit 1 | Diagnostic flag. Needs: Oil Heater | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4078doc 34079 | Comm Loss: Adaptive Frequency Drive Circuit 1 | Diagnostic flag. Needs: Communicating AFD | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4079doc 34080 | Comm Loss: AFD Speed Signal VDC Output Circuit 1 | Diagnostic flag. Needs: Non-comm AFD | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4080doc 34081 | Comm Loss: Bearing Lube Flow First Stage | Diagnostic flag. Needs: CVHS | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4081doc 34082 | Comm Loss: Bearing Lube Flow Second Stage | Diagnostic flag. Needs: CVHS | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4082doc 34083 | Comm Loss: Compressor Motor % RLA Output Circuit 1 | Diagnostic flag. Needs: % RLA Output | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4083doc 34084 | Comm Loss: Cond Diff Water Pressure | Diagnostic flag. Needs: Cond Differential Pressure Flow Measurement | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4084doc 34085 | Comm Loss: Cond Head Press Cntrl Output | Diagnostic flag. Needs: Head Pressure Control | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4085doc 34086 | Comm Loss: Cond High Pressure Cutout | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4086doc 34087 | Comm Loss: Cond Lubrication Source Valve | Diagnostic flag. Needs: CVHS | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4087doc 34088 | Comm Loss: Cond Refrigerant Pressure | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4088doc 34089 | Comm Loss: Cond Rfgt Pressure Output | Diagnostic flag. Needs: Cond Refrigerant Pressure Output | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4089doc 34090 | Comm Loss: Cond Saturated Rfgt Temp | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4090doc 34091 | Comm Loss: Condenser Entering Water Pressure | Diagnostic flag. Needs: Cond Water Flow Measurement - Dual Pressure Sensor | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4091doc 34092 | Comm Loss: Condenser Entering Water Temp | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4092doc 34093 | Comm Loss: Condenser Leaving Water Pressure | Diagnostic flag. Needs: Cond Water Flow Measurement - Dual Pressure Sensor | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4093doc 34094 | Comm Loss: Condenser Leaving Water Temp | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4094doc 34095 | Comm Loss: Condenser Liquid Level Sensor | Diagnostic flag. Needs: Economizer Bypass | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4096doc 34097 | Comm Loss: Condenser Water Flow Switch | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4097doc 34098 | Comm Loss: Condenser Water Pump Relay | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4098doc 34099 | Comm Loss: Cprsr Discharge Rfgt Temp | Diagnostic flag. Needs: Compressor Discharge Temp Sensor | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4099doc 34100 | Comm Loss: Economizer Bypass Valve | Diagnostic flag. Needs: Economizer Bypass | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4102doc 34103 | Comm Loss: Emergency Stop | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4103doc 34104 | Comm Loss: Energy Meter Circuit 1 | Diagnostic flag. Needs: Energy Meter | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4104doc 34105 | Comm Loss: Evap Diff Water Pressure | Diagnostic flag. Needs: Evap Water Flow Measurement - Differential Pressure | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4105doc 34106 | Comm Loss: Evap Entering Water Temp | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4106doc 34107 | Comm Loss: Evap Leaving Water Temp | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4107doc 34108 | Comm Loss: Evap Lube Source Valve Relay | Diagnostic flag. Needs: CVHS | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4108doc 34109 | Comm Loss: Evap Saturated Rfgt Temp | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4109doc 34110 | Comm Loss: Evaporator Entering Water Pressure | Diagnostic flag. Needs: Evap Water Flow Measurement - Dual Pressure Sensor | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4110doc 34111 | Comm Loss: Evaporator Leaving Water Pressure | Diagnostic flag. Needs: Evap Water Flow Measurement - Dual Pressure Sensor | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4111doc 34112 | Comm Loss: Evaporator Water Flow Switch | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4112doc 34113 | Comm Loss: Evaporator Water Pump Relay | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4113doc 34114 | Comm Loss: Ext Base Loading Command | Diagnostic flag. Needs: Base Loading | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4114doc 34115 | Comm Loss: Ext Base Loading Setpoint | Diagnostic flag. Needs: Base Loading | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4115doc 34116 | Comm Loss: Ext Chilled/Hot Water Setpoint | Diagnostic flag. Needs: External Chilled Water Setpoint | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4116doc 34117 | Comm Loss: Ext Demand Limit Setpoint | Diagnostic flag. Needs: External Demand Limit | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4117doc 34118 | Comm Loss: External Auto/Stop | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4118doc 34119 | Comm Loss: External Free Cooling Command | Diagnostic flag. Needs: Free Cooling | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4119doc 34120 | Comm Loss: External Hot Water Command | Diagnostic flag. Needs: Hot Water Control | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4120doc 34121 | Comm Loss: External Ice Building Command | Diagnostic flag. Needs: Ice Building | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4121doc 34122 | Comm Loss: Free Cool Actrs Closed Input | Diagnostic flag. Needs: Free Cooling | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4122doc 34123 | Comm Loss: Free Cool Gas Line Actr Relay | Diagnostic flag. Needs: Free Cooling | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4123doc 34124 | Comm Loss: Free Cool Liq Line Actr Relay | Diagnostic flag. Needs: Free Cooling | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4124doc 34125 | Comm Loss: Free Cooling Auxiliary Relay | Diagnostic flag. Needs: Free Cooling | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4125doc 34126 | Comm Loss: Generator Fault Input | Diagnostic flag. Needs: Engine Generator Power Source | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4126doc 34127 | Comm Loss: Generator Speed Signal Output | Diagnostic flag. Needs: Engine Generator Power Source | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4127doc 34128 | Comm Loss: Generator Start/Stop Relay | Diagnostic flag. Needs: Engine Generator Power Source | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4128doc 34129 | Comm Loss: Generator Up To Speed Input | Diagnostic flag. Needs: Engine Generator Power Source | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4129doc 34130 | Comm Loss: Heat Recovery Differential Water Pressure | Diagnostic flag. Needs: Heat Recovery Water Flow Measurement - Differential Pressure | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4130doc 34131 | Comm Loss: Heat Recovery Entering Water Pressure | Diagnostic flag. Needs: Heat Recovery Water Flow Measurement - Dual Pressure Sensor | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4131doc 34132 | Comm Loss: Heat Recovery Entering Water Temp | Diagnostic flag. Needs: Heat Recovery | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4132doc 34133 | Comm Loss: Heat Recovery Leaving Water Pressure | Diagnostic flag. Needs: Heat Recovery Water Flow Measurement - Dual Pressure Sensor | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4133doc 34134 | Comm Loss: Heat Recovery Leaving Water Temp | Diagnostic flag. Needs: Heat Recovery | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4134doc 34135 | Comm Loss: Heat Recovery Water Flow Switch | Diagnostic flag. Needs: Heat Recovery Water Flow Switch | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4135doc 34136 | Comm Loss: High Lift Unload Valve Relay | Diagnostic flag. Needs: CVGF | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4136doc 34137 | Comm Loss: Hot Gas Bypass Actr Closed In | Diagnostic flag. Needs: Hot Gas Bypass | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4137doc 34138 | Comm Loss: Hot Gas Bypass Load Relay | Diagnostic flag. Needs: Hot Gas Bypass | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4138doc 34139 | Comm Loss: Hot Gas Bypass Unload Relay | Diagnostic flag. Needs: Hot Gas Bypass | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4139doc 34140 | Comm Loss: Ice Building Relay | Diagnostic flag. Needs: Ice Building | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4140doc 34141 | Comm Loss: IGV First Stage Actuator Circuit 1 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4141doc 34142 | Comm Loss: IGV Second Stage Actuator Circuit 1 | Diagnostic flag. Needs: Dual Actuators | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4142doc 34143 | Comm Loss: Inboard Bearing Temperature Circuit 1 | Diagnostic flag. Needs: Bearing Temp Sensor | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4143doc 34144 | Comm Loss: Lube Pump Discharge Pressure | Diagnostic flag. Needs: CVHS | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4144doc 34145 | Comm Loss: Lube Pump Suction Pressure | Diagnostic flag. Needs: CVHS | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4145doc 34146 | Comm Loss: Lube/Refrigerant Pump Relay | Diagnostic flag. Needs: CVHS | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4146doc 34147 | Comm Loss: Motor Coolant Temperature | Diagnostic flag. Needs: MTC Temperature Sensor | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4147doc 34148 | Comm Loss: Motor Temp/Overload | Diagnostic flag. Needs: "Lite" Motor Temp Protection | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4148doc 34149 | Comm Loss: Motor Temperature Cutout | Diagnostic flag. Needs: MTC Switch | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4149doc 34150 | Comm Loss: Motor Winding Temperature 1 Circuit 1 | Diagnostic flag. Needs: CVHE,F,G,H,L,M,S CVGF | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4150doc 34151 | Comm Loss: Motor Winding Temperature 2 Circuit 1 | Diagnostic flag. Needs: CVHE,F,G,H,L,M,S CVGF | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4151doc 34152 | Comm Loss: Motor Winding Temperature 3 Circuit 1 | Diagnostic flag. Needs: CVHE,F,G,H, L CVGF | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4152doc 34153 | Comm Loss: Oil Cooler Solenoid Circuit 1 | Diagnostic flag. Needs: CVHH Oil Cooler Solenoid Valve | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4153doc 34154 | Comm Loss: Oil Diff Pressure Switch Circuit 1 | Diagnostic flag. Needs: CVGF | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4154doc 34155 | Comm Loss: Oil Pressure Status Circuit 1 | Diagnostic flag. Needs: CVHE,F,G,H, L,M | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4155doc 34156 | Comm Loss: Oil Pump Discharge Pressure Circuit 1 | Diagnostic flag. Needs: CVHE,F,G,H, L,M | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4156doc 34157 | Comm Loss: Oil Tank Heater 4E1 Relay Circuit 1 | Diagnostic flag. Needs: CVHH CVGF | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4157doc 34158 | Comm Loss: Oil Tank Heater 4E2 Relay Circuit 1 | Diagnostic flag. Needs: CVHH CVGF | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4158doc 34159 | Comm Loss: Oil Tank Heater Relay Circuit 1 | Diagnostic flag. Needs: CVHE,F,G,H, L,M | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4159doc 34160 | Comm Loss: Oil Tank Pressure Circuit 1 | Diagnostic flag. Needs: CVHE,F,G,H, L,M | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4160doc 34161 | Comm Loss: Oil Tank Temperature Circuit 1 | Diagnostic flag. Needs: CVHE,F,G,H, L,M CVGF | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4161doc 34162 | Comm Loss: Oil Vent Line Circuit 1 | Diagnostic flag. Needs: CVHH | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4162doc 34163 | Comm Loss: Oil/Refrigerant Pump Relay Circuit 1 | Diagnostic flag. Needs: CVHE,F,G,H, L,M CVGF | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4163doc 34164 | Comm Loss: Outboard Bearing Pad Temp 1 Circuit 1 | Diagnostic flag. Needs: CVHH | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4164doc 34165 | Comm Loss: Outboard Bearing Pad Temp 2 Circuit 1 | Diagnostic flag. Needs: CVHH | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4165doc 34166 | Comm Loss: Outboard Bearing Pad Temp 3 Circuit 1 | Diagnostic flag. Needs: CVHH | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4166doc 34167 | Comm Loss: Outboard Bearing Temperature Circuit 1 | Diagnostic flag. Needs: Bearing Temp Sensor | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4167doc 34168 | Comm Loss: Outdoor Air Temperature | Diagnostic flag. Needs: Outdoor Air Temp Sensor | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4168doc 34169 | Comm Loss: Programmable Relay Board 1 | Diagnostic flag. Needs: Programmable Status Relays | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4169doc 34170 | Comm Loss: Programmable Relay Board 2 | Diagnostic flag. Needs: Programmable Status Relays | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4170doc 34171 | Comm Loss: Purge Alarm Relay Circuit 1 | Diagnostic flag. Needs: Purge | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4171doc 34172 | Comm Loss: Purge Carbon Tank Heater Rly Circuit 1 | Diagnostic flag. Needs: Purge w/Carbon Tank | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4172doc 34173 | Comm Loss: Purge Carbon Tank Temperature Circuit 1 | Diagnostic flag. Needs: Purge w/Carbon Tank | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4173doc 34174 | Comm Loss: Purge Condensing Unit Relay Circuit 1 | Diagnostic flag. Needs: Purge | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4174doc 34175 | Comm Loss: Purge Cprsr Suction Rfgt Temp Circuit 1 | Diagnostic flag. Needs: Purge | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4175doc 34176 | Comm Loss: Purge Exhaust Solenoid Output Circuit 1 | Diagnostic flag. Needs: Purge | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4176doc 34177 | Comm Loss: Purge Liquid Level Switch Circuit 1 | Diagnostic flag. Needs: Purge | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4177doc 34178 | Comm Loss: Purge Pumpout Relay Circuit 1 | Diagnostic flag. Needs: Purge | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4178doc 34179 | Comm Loss: Purge Pumpout Solenoid Output Circuit 1 | Diagnostic flag. Needs: Purge | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4179doc 34180 | Comm Loss: Purge Regen Solenoid Relay Circuit 1 | Diagnostic flag. Needs: Purge w/Carbon Tank | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4180doc 34181 | Comm Loss: Refrigerant Monitor Input | Diagnostic flag. Needs: Refrigerant Monitor | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4181doc 34182 | Comm Loss: Starter Circuit 1 | Diagnostic flag. Needs: EM Starters Solid State Starters Non-comm AFDs | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4182doc 34183 | Comm Loss: Starter Fault Circuit 1 | Diagnostic flag. Needs: Non-comm AFD Solid State Starter | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4183doc 34184 | Comm Loss: Vibration Sensor Input | Diagnostic flag. Needs: Vibration Sensor | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4184doc 34185 | Diagnostic: Compressor Did Not Accelerate: Shutdown Compressor 1A | Diagnostic flag. Needs: EM Starters Solid State Starters Non-comm AFDs | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4185doc 34186 | Diagnostic: Cond Saturated Refrigerant Temp Sensor | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4186doc 34187 | Diagnostic: Condenser Diff Water Pressure Xdcr | Diagnostic flag. Needs: Cond Water Flow Measurement - Differential Pressure | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4187doc 34188 | Diagnostic: Condenser Entering Water Pressure | Diagnostic flag. Needs: Cond Water Flow Measurement - Dual Pressure Sensor | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4188doc 34189 | Diagnostic: Condenser Entering Water Temp Sensor | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4189doc 34190 | Diagnostic: Condenser High Pressure Cutout | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4190doc 34191 | Diagnostic: Condenser Leaving Water Pressure | Diagnostic flag. Needs: Cond Water Flow Measurement - Dual Pressure Sensor | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4191doc 34192 | Diagnostic: Condenser Leaving Water Temp Sensor | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4192doc 34193 | Diagnostic: Condenser Liquid Level Sensor | Diagnostic flag. Needs: Economizer Bypass | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4193doc 34194 | Diagnostic: Condenser Refrigerant Pressure Xdcr | Diagnostic flag. Needs: Condenser Refrigerant Pressure Sensor | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4195doc 34196 | Diagnostic: Condenser Water Flow Lost | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4196doc 34197 | Diagnostic: Condenser Water Flow Overdue | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4197doc 34198 | Diagnostic: Cprsr Did Not Accelerate: Transition | Diagnostic flag. Needs: EM Starters Solid State Starters Non-comm AFDs | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4198doc 34199 | Diagnostic: Cprsr Discharge Refrigerant Temp Sensor | Diagnostic flag. Needs: Compressor Discharge Temp Sensor | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4199doc 34200 | Diagnostic: Differential Lube Pressure Overdue Circuit 1 | Diagnostic flag. Needs: CVHS | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4200doc 34201 | Diagnostic: Differential Oil Pressure Overdue Circuit 1 | Diagnostic flag. Needs: CVHE,F,G,H, L,M CVGF | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4202doc 34203 | Diagnostic: Emergency Stop | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4203doc 34204 | Diagnostic: Evap Rfgt Temp Deviate From Selection | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4204doc 34205 | Diagnostic: Evap Saturated Refrigerant Temp Sensor | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4205doc 34206 | Diagnostic: Evaporator Diff Water Pressure Xdcr | Diagnostic flag. Needs: Evap Water Flow Measurement - Differential Pressure | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4206doc 34207 | Diagnostic: Evaporator Entering Water Pressure | Diagnostic flag. Needs: Evap Flow Measurement - Dual Pressure Sensor | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4207doc 34208 | Diagnostic: Evaporator Entering Water Temp Sensor | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4208doc 34209 | Diagnostic: Evaporator Leaving Water Pressure | Diagnostic flag. Needs: Evap Flow Measurement - Dual Pressure Sensor | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4209doc 34210 | Diagnostic: Evaporator Leaving Water Temp Sensor | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4210doc 34211 | Diagnostic: Evaporator Water Flow Lost | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4211doc 34212 | Diagnostic: Evaporator Water Flow Overdue | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4212doc 34213 | Diagnostic: Excessive Loss of Communication | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4214doc 34215 | Diagnostic: Extended Compressor Surge Compressor 1A | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4215doc 34216 | Diagnostic: External Base Loading Setpoint | Diagnostic flag. Needs: Base Loading | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4216doc 34217 | Diagnostic: External Chilled/Hot Water Setpoint | Diagnostic flag. Needs: External Chilled Water Setpoint | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4217doc 34218 | Diagnostic: External Demand Limit Setpoint | Diagnostic flag. Needs: External Demand Limit Setpoint | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4218doc 34219 | Diagnostic: Free Cooling Actrs Not Open During FC | Diagnostic flag. Needs: Free Cooling | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4219doc 34220 | Diagnostic: Free Cooling Actuators Not Closed | Diagnostic flag. Needs: Free Cooling | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4220doc 34221 | Diagnostic: Free Cooling Actuators Not Open | Diagnostic flag. Needs: Free Cooling | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4221doc 34222 | Diagnostic: Free Cooling Actuators Unexpectedly Open | Diagnostic flag. Needs: Free Cooling | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4222doc 34223 | Diagnostic: Generator Fault Relay Open | Diagnostic flag. Needs: Engine Generator Power Source | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4223doc 34224 | Diagnostic: Generator Ready Signal Overdue | Diagnostic flag. Needs: Engine Generator Power Source | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4224doc 34225 | Diagnostic: Heat Recovery Diff Water Pressure | Diagnostic flag. Needs: Heat Recovery Water Flow Measurement - Differential Pressure | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4225doc 34226 | Diagnostic: Heat Recovery Entering Water Pressure | Diagnostic flag. Needs: Heat Recovery Water Flow Measurement - Dual Pressure Sensor | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4226doc 34227 | Diagnostic: Heat Recovery Entering Water Temp Sensor | Diagnostic flag. Needs: Heat Recovery | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4227doc 34228 | Diagnostic: Heat Recovery Leaving Water Pressure | Diagnostic flag. Needs: Heat Recovery Water Flow Measurement - Dual Pressure Sensor | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4228doc 34229 | Diagnostic: Heat Recovery Leaving Water Temp Sensor | Diagnostic flag. Needs: Heat Recovery | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4229doc 34230 | Diagnostic: High Condenser Pressure | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4230doc 34231 | Diagnostic: High Cprsr Rfgt Discharge Temperature | Diagnostic flag. Needs: Compressor Discharge Temp Sensor | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4231doc 34232 | Diagnostic: High Differential Refrigerant Pressure | Diagnostic flag. Needs: CVHE,F,G,H, L,M,S | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4232doc 34233 | Diagnostic: High Evaporator Refrigerant Temperature | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4233doc 34234 | Diagnostic: High Evaporator Water Temperature | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4234doc 34235 | Diagnostic: High Inboard Bearing Temperature Circuit 1 | Diagnostic flag. Needs: Bearing Temp Sensor | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4235doc 34236 | Diagnostic: High Motor Coolant Temperature Circuit 1 | Diagnostic flag. Needs: MTC Temperature Sensor | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4236doc 34237 | Diagnostic: High Motor Winding Temperature 1 Circuit 1 | Diagnostic flag. Needs: CVHE,F,G,H,S,M,L CVGF | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4237doc 34238 | Diagnostic: High Motor Winding Temperature 2 Circuit 1 | Diagnostic flag. Needs: CVHE,F,G,H,S,M,L CVGF | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4238doc 34239 | Diagnostic: High Motor Winding Temperature 3 Circuit 1 | Diagnostic flag. Needs: CVHE,F,G,H,L CVGF | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4239doc 34240 | Diagnostic: High Oil Temperature Circuit 1 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4240doc 34241 | Diagnostic: High Outboard Bearing Pad Temperature 1 Circuit 1 | Diagnostic flag. Needs: CVHH | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4241doc 34242 | Diagnostic: High Outboard Bearing Pad Temperature 2 Circuit 1 | Diagnostic flag. Needs: CVHH | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4242doc 34243 | Diagnostic: High Outboard Bearing Pad Temperature 3 Circuit 1 | Diagnostic flag. Needs: CVHH | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4243doc 34244 | Diagnostic: High Outboard Bearing Temp Circuit 1 | Diagnostic flag. Needs: Bearing Temp Sensor | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4244doc 34245 | Diagnostic: High Vacuum Lockout Circuit 1 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4245doc 34246 | Diagnostic: Hot Gas Bypass Valve Closure Overdue | Diagnostic flag. Needs: Hot Gas Bypass | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4246doc 34247 | Diagnostic: Hot Gas Bypass Valve Opening Overdue | Diagnostic flag. Needs: Hot Gas Bypass | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4247doc 34248 | Diagnostic: Hot Gas Bypass Valve Unexpectedly Open | Diagnostic flag. Needs: Hot Gas Bypass | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4248doc 34249 | Diagnostic: HPC/High AFD Heat Sink Water Pressure | Diagnostic flag. Needs: Unit Mount AFD - AFDD,E,F (LF2) Remote Mount Comm AFD - (PF7000) | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4249doc 34250 | Diagnostic: Inboard Bearing Temp Sensor Circuit 1 | Diagnostic flag. Needs: Bearing Temp Sensor | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4250doc 34251 | Diagnostic: Inverted Condenser Approach Temperature | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4251doc 34252 | Diagnostic: Inverted Condenser Water Temperature | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4252doc 34253 | Diagnostic: Inverted Evaporator Approach Temperature | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4253doc 34254 | Diagnostic: Inverted Evaporator Water Temperature | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4254doc 34255 | Diagnostic: Loss of Economizer Bypass Valve Control | Diagnostic flag. Needs: Economizer Bypass | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4255doc 34256 | Diagnostic: Low Bearing Lube Flow First Stage Circuit 1 | Diagnostic flag. Needs: CVHS | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4256doc 34257 | Diagnostic: Low Bearing Lube Flow Second Stage Circuit 1 | Diagnostic flag. Needs: CVHS | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4257doc 34258 | Diagnostic: Low Brg Lube Flow Lockout First Stage Circuit 1 | Diagnostic flag. Needs: CVHS | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4258doc 34259 | Diagnostic: Low Brg Lube Flow Lockout Second Stage Circuit 1 | Diagnostic flag. Needs: CVHS | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4259doc 34260 | Diagnostic: Low Differential Lube Pressure Circuit 1 | Diagnostic flag. Needs: CVHS | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4260doc 34261 | Diagnostic: Low Differential Oil Pressure Circuit 1 | Diagnostic flag. Needs: CVHE,F,G,H,L,M CVGF | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4261doc 34262 | Diagnostic: Low Evap Leaving Water Temp: Unit Off | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4262doc 34263 | Diagnostic: Low Evap Leaving Water Temp: Unit On | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4263doc 34264 | Diagnostic: Low Evaporator Refrigerant Temperature | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4264doc 34265 | Diagnostic: Low Evaporator Water Flow | Diagnostic flag. Needs: Water Flow Sensing | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4265doc 34266 | Diagnostic: Low Oil Temperature Circuit 1 | Diagnostic flag. Needs: CVHE,F,G,H, L CVGF | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4266doc 34267 | Diagnostic: Lube Pressure Sensor Calibration Circuit 1 | Diagnostic flag. Needs: CVHS | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4267doc 34268 | Diagnostic: Lube Pump Disch Pressure Xdcr Circuit 1 | Diagnostic flag. Needs: CVHS | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4268doc 34269 | Diagnostic: Lube Pump Override: Low Diff Press Circuit 1 | Diagnostic flag. Needs: CVHS | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4269doc 34270 | Diagnostic: Lube Pump Override: Low Flow 1st Stage Circuit 1 | Diagnostic flag. Needs: CVHS | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4270doc 34271 | Diagnostic: Lube Pump Override: Low Flow 2nd Stage Circuit 1 | Diagnostic flag. Needs: CVHS | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4271doc 34272 | Diagnostic: Lube Pump Suction Pressure Xdcr Circuit 1 | Diagnostic flag. Needs: CVHS | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4272doc 34273 | Diagnostic: Momentary Power Loss | Diagnostic flag. Needs: Momentary Power Loss | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4273doc 34274 | Diagnostic: Motor Coolant Temperature Sensor Circuit 1 | Diagnostic flag. Needs: MTC Temperature Sensor | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4274doc 34275 | Diagnostic: Motor Current Overload Circuit 1 | Diagnostic flag. Needs: EM Starters Solid State Starters Non-comm AFDs | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4275doc 34276 | Diagnostic: Motor Temperature Cutout Tripped Circuit 1 | Diagnostic flag. Needs: MTC Switch | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4276doc 34277 | Diagnostic: Motor Winding Temperature 1 Sensor Circuit 1 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4277doc 34278 | Diagnostic: Motor Winding Temperature 2 Sensor Circuit 1 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4278doc 34279 | Diagnostic: Motor Winding Temperature 3 Sensor Circuit 1 | Diagnostic flag. Needs: CVHE,F,G,H, L CVGF | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4279doc 34280 | Diagnostic: MP: Invalid Configuration | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4280doc 34281 | Diagnostic: MP: Reset Has Occurred | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4281doc 34282 | Diagnostic: Oil Pressure Sensor Calibration Circuit 1 | Diagnostic flag. Needs: CVHE,F,G,H,L,M | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4282doc 34283 | Diagnostic: Oil Pump Discharge Pressure Transducer Circuit 1 | Diagnostic flag. Needs: CVHE,F,G,H,L,M | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4283doc 34284 | Diagnostic: Oil Tank Pressure Transducer Circuit 1 | Diagnostic flag. Needs: CVHE,F,G,H,L,M | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4284doc 34285 | Diagnostic: Oil Tank Temperature Sensor Circuit 1 | Diagnostic flag. Needs: CVHE,F,G,H,L,M CVGF | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4285doc 34286 | Diagnostic: Outboard Bearing Pad Temp 1 Sensor Circuit 1 | Diagnostic flag. Needs: CVHH | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4286doc 34287 | Diagnostic: Outboard Bearing Pad Temp 2 Sensor Circuit 1 | Diagnostic flag. Needs: CVHH | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4287doc 34288 | Diagnostic: Outboard Bearing Pad Temp 3 Sensor Circuit 1 | Diagnostic flag. Needs: CVHH | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4288doc 34289 | Diagnostic: Outboard Bearing Temperature Sensor Circuit 1 | Diagnostic flag. Needs: Bearing Temp Sensor | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4289doc 34290 | Diagnostic: Outdoor Air Temperature Sensor | Diagnostic flag. Needs: Outdoor Air Temp Sensor | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4290doc 34291 | Diagnostic: Over Voltage Circuit 1 | Diagnostic flag. Needs: Line Voltage Sensing | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4291doc 34292 | Diagnostic: Phase Loss Circuit 1 | Diagnostic flag. Needs: EM Starters Solid State Starters Non-comm AFDs | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4292doc 34293 | Diagnostic: Phase Reversal Circuit 1 | Diagnostic flag. Needs: EM Starters Solid State Starters Non-comm AFDs | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4293doc 34294 | Diagnostic: Power Loss Circuit 1 | Diagnostic flag. Needs: EM Starters Solid State Starters Non-comm AFDs | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4294doc 34295 | Diagnostic: Purge Carbon Regen Temp Limit Exceeded Circuit 1 | Diagnostic flag. Needs: Purge w/Carbon Tank | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4295doc 34296 | Diagnostic: Purge Carbon Regen Temp Not Satisfied Circuit 1 | Diagnostic flag. Needs: Purge w/Carbon Tank | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4296doc 34297 | Diagnostic: Purge Carbon Regen Temperature Too Low Circuit 1 | Diagnostic flag. Needs: Purge w/Carbon Tank | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4297doc 34298 | Diagnostic: Purge Carbon Tank Temperature Sensor Circuit 1 | Diagnostic flag. Needs: Purge w/Carbon Tank | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4298doc 34299 | Diagnostic: Purge Cprsr Suction Rfgt Temp Sensor Circuit 1 | Diagnostic flag. Needs: Purge | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4299doc 34300 | Diagnostic: Purge Daily Pumpout Limit Exceeded Circuit 1 | Diagnostic flag. Needs: Purge | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4300doc 34301 | Diagnostic: Purge Liquid Level Too High Continuously Circuit 1 | Diagnostic flag. Needs: Purge | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4301doc 34302 | Diagnostic: Purge Liquid Level Too High Warning Circuit 1 | Diagnostic flag. Needs: Purge | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4302doc 34303 | Diagnostic: Purge Regen Cooldown Temp Too High Circuit 1 | Diagnostic flag. Needs: Purge w/Carbon Tank | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4303doc 34304 | Diagnostic: Refrigerant Monitor Input | Diagnostic flag. Needs: Refrigerant Monitor | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4304doc 34305 | Diagnostic: Restart Inhibit | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4305doc 34306 | Diagnostic: Severe Current Unbalance Circuit 1 | Diagnostic flag. Needs: Line Voltage Sensing | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4306doc 34307 | Diagnostic: Software Error 1001: Call Trane Service | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4307doc 34308 | Diagnostic: Software Error 1004: Call Trane Service | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4308doc 34309 | Diagnostic: Starter Comm Loss: Main Processor Circuit 1 | Diagnostic flag. Needs: EM Starters Solid State Starters Non-comm AFDs | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4309doc 34310 | Diagnostic: Starter Contactor Interrupt Failure Circuit 1 | Diagnostic flag. Needs: EM Starters Solid State Starters Non-comm AFDs | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4310doc 34311 | Diagnostic: Starter Did Not Fully Accelerate Circuit 1 | Diagnostic flag. Needs: EM Starters Solid State Starters Non-comm AFDs | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4311doc 34312 | Diagnostic: Starter Did Not Transition Circuit 1 | Diagnostic flag. Needs: EM Starters Solid State Starters Non-comm AFDs | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4312doc 34313 | Diagnostic: Starter Dry Run Test Circuit 1 | Diagnostic flag. Needs: EM Starters Solid State Starters Non-comm AFDs | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4313doc 34314 | Diagnostic: Starter Failed to Arm/Start Circuit 1 | Diagnostic flag. Needs: EM Starters Solid State Starters Non-comm AFDs | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4314doc 34315 | Diagnostic: Starter Fault Circuit 1 | Diagnostic flag. Needs: EM Starters Solid State Starters Non-comm AFDs | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4315doc 34316 | Diagnostic: Starter Fault Type I Circuit 1 | Diagnostic flag. Needs: EM Starters Solid State Starters Non-comm AFDs | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4316doc 34317 | Diagnostic: Starter Fault Type II Circuit 1 | Diagnostic flag. Needs: EM Starters Solid State Starters Non-comm AFDs | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4317doc 34318 | Diagnostic: Starter Fault Type III Circuit 1 | Diagnostic flag. Needs: EM Starters Solid State Starters Non-comm AFDs | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4318doc 34319 | Diagnostic: Starter Module Memory Error Type 1 Circuit 1 | Diagnostic flag. Needs: EM Starters Solid State Starters Non-comm AFDs | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4319doc 34320 | Diagnostic: Starter Module Memory Error Type 2 Circuit 1 | Diagnostic flag. Needs: EM Starters Solid State Starters Non-comm AFDs | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4320doc 34321 | Diagnostic: Transition Complete Input Opened Circuit 1 | Diagnostic flag. Needs: EM Starters Solid State Starters Non-comm AFDs | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4321doc 34322 | Diagnostic: Transition Complete Input Shorted Circuit 1 | Diagnostic flag. Needs: EM Starters Solid State Starters Non-comm AFDs | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4322doc 34323 | Diagnostic: Under Voltage Circuit 1 | Diagnostic flag. Needs: Line Voltage Sensing | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4323doc 34324 | Diagnostic: Unexpected Differential Lube Pressure Circuit 1 | Diagnostic flag. Needs: CVHS | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4324doc 34325 | Diagnostic: Unexpected Differential Oil Pressure Circuit 1 | Diagnostic flag. Needs: CVHE,F,G,H,L,M CVGF | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4325doc 34326 | Diagnostic: Unexpected Starter Shutdown Circuit 1 | Diagnostic flag. Needs: EM Starters Solid State Starters Non-comm AFDs | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4326doc 34327 | Diagnostic: Vibration Sensor Input | Diagnostic flag. Needs: Vibration Sensor | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4327doc 34328 | Comm Loss: Evap Refrigerant Pressure Circuit 1 | Diagnostic flag. Needs: Evap Pressure Sensor | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4328doc 34329 | Diagnostic: Evaporator Refrigerant Pressure Xdcr Circuit 1 | Diagnostic flag. Needs: Evap Pressure Sensor | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4329doc 34330 | Diagnostic: Inverted Heat Recovery Approach Temperature Circuit 1 | Diagnostic flag. Needs: Heat Recovery | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4330doc 34331 | Comm Loss: Sporlan Automatic Econ Valve Circuit 1 | Diagnostic flag. Needs: Sporlan Automatic Valve | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4331doc 34332 | Comm Loss: Sporlan Automatic Cond Valve Circuit 1 | Diagnostic flag. Needs: Sporlan Automatic Valve | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4332doc 34333 | Comm Loss: Trane IGV Cond Valve Circuit 1 | Diagnostic flag. Needs: Variable Orifice | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4333doc 34334 | Comm Loss: Trane IGV Econ Valve Circuit 1 | Diagnostic flag. Needs: Variable Orifice | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4334doc 34335 | Diagnostic: External Hot Water Setpoint | Diagnostic flag. Needs: External Hot Water Setpoint | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4335doc 34336 | Diagnostic: External Chilled Water Setpoint | Diagnostic flag. Needs: External Chilled Water Setpoint | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4336doc 34337 | Comm Loss: External Hot Wtr Setpoint | Diagnostic flag. Needs: External Hot Water Setpoint | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4337doc 34338 | Comm Loss: External Chilled Wtr Setpoint | Diagnostic flag. Needs: External Chilled Water Setpoint | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4338doc 34339 | Comm Loss: Motor Cooling Vent Valve Circuit 1 | Diagnostic flag. Needs: Booster Heat Pump | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4339doc 34340 | Diagnostic: Motor Cooling Vent Valve Position Error Circuit 1 | Diagnostic flag. Needs: Booster Heat Pump | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4340doc 34341 | Comm Loss: Oil Heat Exchanger Vent Valve Circuit 1 | Diagnostic flag. Needs: Booster Heat Pump | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4341doc 34342 | Diagnostic: Oil Heat Exchanger Vent Valve Position Error Circuit 1 | Diagnostic flag. Needs: Booster Heat Pump | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4342doc 34343 | Diagnostic: High Evaporator Refrigerant Temperature | Diagnostic flag. Needs: Booster Heat Pump | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4343doc 34344 | Diagnostic: Low Condenser Water Flow | Diagnostic flag. Needs: Hot Water Control | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4344doc 34345 | Diagnostic: Low Heat Recovery Water Flow | Diagnostic flag. Needs: Heat Recovery | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4345doc 34346 | Comm Loss: External Diagnostic Reset | Diagnostic flag. Needs: External Diagnostic Reset | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4346doc 34347 | Diagnostic: Economizer Refrigerant Pressure | Diagnostic flag. Needs: Variable Orifice | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4347doc 34348 | Diagnostic: Motor Cooling Pressure Sensor Circuit 1 | Diagnostic flag. Needs: Booster Heat Pump | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4348doc 34349 | Comm Loss: Motor Cooling Valve Circuit 1 | Diagnostic flag. Needs: Booster Heat Pump | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4349doc 34350 | Comm Loss: Motor Cooling Pressure Sensor Circuit 1 | Diagnostic flag. Needs: Booster Heat Pump | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| HR | 10doc 40011 | Chilled Water Setpoint | Temperature in the factory unit system (I-P or SI). | FLOAT32 | ABCD | Read/write | |||
| HR | 12doc 40013 | Demand Limit Setpoint | FLOAT32 | ABCD | % | Read/write | |||
| HR | 14doc 40015 | Hot Water Setpoint | Temperature in the factory unit system (I-P or SI). Needs: Hot Water Control | FLOAT32 | ABCD | Read/write | |||
| HR | 16doc 40017 | Base Loading Setpoint | Needs: Base Loading | FLOAT32 | ABCD | % | Read/write | ||
| HR | 18doc 40019 | BAS Cooling Differential to Start | Temperature difference, factory unit system (I-P or SI). | FLOAT32 | ABCD | Read/write | |||
| HR | 20doc 40021 | BAS Cooling Differential to Stop | Temperature difference, factory unit system (I-P or SI). | FLOAT32 | ABCD | Read/write | |||
| HR | 22doc 40023 | BAS Heating Differential to Start | Temperature difference, factory unit system (I-P or SI). Needs: Hot Water Control | FLOAT32 | ABCD | Read/write | |||
| HR | 24doc 40025 | BAS Heating Differential to Stop | Temperature difference, factory unit system (I-P or SI). Needs: Hot Water Control | FLOAT32 | ABCD | Read/write | |||
| HR | 2010doc 42011 | Chiller Mode Command BAS | UINT16 | Read/write | 1 = Cool; 2 = Heat; 3 = Ice Making; 4 = Free Cooling | ||||
| HR | 3010doc 43011 | Base Loading Request | Needs: Base Loading | UINT16 | Read/write | 0 = Off; 1 = On | |||
| HR | 3011doc 43012 | Reset Diagnostic | UINT16 | Read/write | 0 = Normal; 1 = Reset | ||||
| HR | 3012doc 43013 | Evaporator Water Pump Request BAS | UINT16 | Read/write | 0 = Auto; 1 = On | ||||
| HR | 3013doc 43014 | Condenser Water Pump Request BAS | UINT16 | Read/write | 0 = Auto; 1 = On | ||||
| HR | 3014doc 43015 | Chiller Auto Stop Command BAS | UINT16 | Read/write | 0 = Stop; 1 = Auto | ||||
| HR | 3015doc 43016 | Energy Consumption Reset | Depends on starter/drive options; see the source configuration column. | UINT16 | Read/write | 0 = Accumulating; 1 = Reset |
Notes on this map
- Register format table: analog points are 32-bit floats sent high word / high byte first (NaN = invalid); binary and multi-state points are unsigned 16-bit integers (0xFFFF = invalid).
- Values are sent in the unit system ordered from the factory (I-P is the usual default, SI optional); the list names only the quantity, so temperature/pressure/flow units are left blank here.
- Not every point exists on every unit: the controller builds its point set from the unit's configuration. Descriptions name the configuration a point depends on.
- Register numbers are printed in 5-digit Modicon form (3xxxx input registers, 4xxxx holding registers) and converted here to wire addresses (30011 = input register 10).
- Controller setup, serial defaults and the I-P/SI units statement come from the list's named reference document, Trane's Symbio 800 BACnet and Modbus integration guide BAS-SVP083B-EN (15 Nov 2024, https://elibrary.tranetechnologies.com/public/commercial-hvac/Literature/Integration/BAS-SVP083B-EN_11152024.pdf).
- The document carries separate Simplex and Duplex tables that reuse the same register numbers for different points; do not mix them.
- The 'Diagnostic Codes' pages (code number to text for the Last Diagnostic Code points) are not reproduced.
- Binary input 33018 is printed with the name 'Evaporator Leaving Water Temperature' and the states 'Not Limited / Limited'; copied as printed (it reports a capacity limit, not a temperature).
- Diagnostic input 34008 is also printed with the name 'Evaporator Leaving Water Temperature' (an alarm flag, 0 = Normal / 1 = In Alarm, TR200 AFD option); copied as printed.
- Duplex (two-compressor) CenTraVacs on Symbio 800 use the Duplex tables of the same list (see centravac-duplex-symbio-800); UC800 duplex units use a different map (centravac-duplex-uc800).
Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.
Questions about the Trane CenTraVac simplex centrifugal chiller (Symbio 800)
What Modbus registers does the Trane CenTraVac simplex centrifugal chiller (Symbio 800) have?
This map lists 546 registers: 531 input registers, 15 holding registers. 15 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.
Are the Trane CenTraVac simplex centrifugal chiller (Symbio 800) Modbus addresses 0-based or 1-based?
The manufacturer's document numbers registers Modicon 3xxxx/4xxxx (drop the prefix, subtract 1). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. The list prints Modicon register numbers: 3xxxx are input registers and 4xxxx holding registers, so 30011 is input register address 10 and 42011 is holding register address 2010.
What byte order does the Trane CenTraVac simplex centrifugal chiller (Symbio 800) use for 32-bit values?
Multi-register values in this map use ABCD (high word first (big-endian)). Set your client to this order for every 32/64-bit value in the table.
What are the minimum Modbus registers to integrate the Trane CenTraVac simplex centrifugal chiller (Symbio 800)?
Start with IR 10 Active Chilled Water Setpoint (Active chilled water setpoint); IR 24 Evaporator Leaving Water Temperature (Evaporator leaving water temperature); IR 26 Evaporator Entering Water Temperature (Evaporator entering water temperature); IR 2010 Running Mode (Running mode); IR 3023 Chiller Running State (Chiller running state); IR 3028 Diagnostic Present (Diagnostic present); HR 10 Chilled Water Setpoint (Chilled water setpoint (BAS)); HR 2010 Chiller Mode Command BAS (BAS chiller mode command); HR 3014 Chiller Auto Stop Command BAS (Chiller auto/stop command (BAS)); HR 3011 Reset Diagnostic (Reset diagnostic).
How do I enable Modbus control of the Trane CenTraVac simplex centrifugal chiller (Symbio 800)?
On the Symbio 800 web interface go to Installation > Identification and Communications > Protocol Configuration and select Modbus RTU or Modbus TCP (per Trane's Symbio 800 integration guides).
Where is the official Trane CenTraVac simplex centrifugal chiller (Symbio 800) Modbus documentation?
The source is Symbio 800 Integration Points List, BACnet/Modbus, CenTraVac (BAS-PTS009C-EN), revision 2025-12-12, published free by Trane at https://elibrary.tranetechnologies.com/public/commercial-hvac/Literature/Points%20List/BAS-PTS009C-EN_12122025.pdf.
More Trane Modbus register maps
- Chiller
Trane Agility water-cooled centrifugal chiller (Symbio 800)
Trane Agility water-cooled chillers with Symbio 800 controls, as listed in BAS-PTS007C-EN (6/30/2026).
Also known as: Agility, HDWA, Agility water-cooled chiller - Chiller
Trane Ascend ACR Series C air-cooled chiller (Symbio 800)
Trane Ascend model ACR Series C air-cooled chillers with the Symbio 800 controller, as listed in BAS-PTS021A-EN (11/15/2024).
Also known as: ACR, Ascend ACR, ACR Series C, Ascend air-cooled chiller ACR - Chiller
Trane Ascend ACS / ACX air-cooled scroll chiller and heat pump (Symbio 800)
Trane Ascend ACS air-cooled scroll chillers and ACX air-to-water heat pumps with the Symbio 800 controller, as listed in BAS-PTS011A-EN (11/15/2024).
Also known as: ACS, ACX, Ascend ACS, Ascend ACX, Ascend air-cooled chiller, Ascend air-to-water heat pump - Chiller
Trane CenTraVac CTV-Duplex water-cooled centrifugal chiller (UC800 native Modbus)
Trane Duplex CenTraVac (two-compressor) water-cooled centrifugal chillers with the Tracer UC800 controller, as listed in the Modbus section of BAS-PTS030A-EN (12/6/2024).
Also known as: CTV-Duplex, CTVD, CenTraVac Duplex, Duplex CenTraVac UC800 - Chiller
Trane CenTraVac duplex centrifugal chiller (Symbio 800)
Trane dual-compressor (duplex) CenTraVac water-cooled centrifugal chillers fitted with the Symbio 800 controller, as listed in the Duplex tables of BAS-PTS009C-EN (12/12/2025).
Also known as: CDHF, CDHG, CDHH, CenTraVac Duplex Symbio 800 - Chiller
Trane CGAM air-cooled scroll chiller (Symbio 800)
Trane CGAM air-cooled scroll chillers with the Symbio 800 controller, as listed in BAS-PTS019A-EN (11/15/2024).
Also known as: CGAM, Trane CGAM, CGAM air-cooled scroll chiller - Chiller
Trane RTAC air-cooled helical-rotary chiller (Symbio 800)
Trane RTAC air-cooled helical-rotary chillers with the Symbio 800 controller, as listed in BAS-PTS023A-EN (11/8/2024).
Also known as: RTAC, Series R RTAC - Chiller
Trane RTAC air-cooled helical-rotary chiller (UC800 native Modbus profile)
Trane RTAC air-cooled chillers on the Tracer UC800 controller using the UC800 native Modbus map in the Modbus section of BAS-PTS032A-EN (12/6/2024). Not the same register set as the Symbio 800 RTAC list (BAS-PTS023A-EN).
Also known as: RTAC UC800 native Modbus profile, Series R RTAC UC800 native Modbus, BAS-PTS032A-EN - Chiller
Trane Series R RTHD water-cooled helical-rotary chiller (Symbio 800)
Trane Series R model RTHD water-cooled helical-rotary chillers with the Symbio 800 controller, as listed in BAS-PTS015A-EN (11/15/2024).
Also known as: RTHD, Series R RTHD - Chiller
Trane Series R RTWD water-cooled helical-rotary chiller (Symbio 800)
Trane Series R model RTWD water-cooled helical-rotary chillers with the Symbio 800 controller, as listed in BAS-PTS017A-EN (11/15/2024).
Also known as: RTWD, Series R RTWD, RTUD - Chiller
Trane Sintesis RTAF air-cooled screw chiller (Symbio 800)
Trane Sintesis RTAF air-cooled helical-rotary chillers with the Symbio 800 controller, as listed in BAS-PTS013B-EN (4/7/2026).
Also known as: RTAF, Sintesis RTAF, Sintesis air-cooled chiller - Pump (data-centre coolant distribution unit)
Trane TCDU coolant distribution unit (data-centre liquid cooling)
Trane Coolant Distribution Unit (TCDU) for direct-to-chip liquid cooling, as documented in IOM DC-SVX001A-EN (April 2025).
Also known as: TCDU, Trane CDU, Trane Coolant Distribution Unit, DC-SVX001A - Sensor (refrigerant leak monitor for chiller plant rooms)
Trane TruSense RMWH refrigerant monitor (up to 16 points)
Trane TruSense RMWH multipoint photoacoustic refrigerant monitor with Modbus RTU selected, per IOM PART-SVX008A-EN (30 Sep 2025, preliminary).
Also known as: TruSense, RMWH, Trane refrigerant monitor, PART-SVX008A, RMWH-SVX001
Other chillers & heat pumps register maps
- Chiller
Daikin Applied Magnitude WMC-E magnetic-bearing centrifugal chiller (MicroTech controller)
Daikin Applied Magnitude WMC E-vintage water-cooled magnetic-bearing centrifugal chillers with the MicroTech unit controller and BACnet/Modbus communication module set to Modbus, per ED 19131-1.
Also known as: WMC-E, WMC E-Vintage, Magnitude WMC, Daikin WMC, ED 19131 - Chiller
Daikin Applied Pathfinder AWS air-cooled screw chiller (MicroTech controller)
Daikin Applied Pathfinder AWS air-cooled screw chillers with the MicroTech chiller unit controller and Modbus communication module, per ED 15121-13 (both application-version columns, 2507500204 and earlier / 2507500205 and later, mark the same data points).
Also known as: AWS, Pathfinder AWS, Daikin AWS, ED 15121 - Chiller
Daikin Applied ADS air-cooled global screw chiller (MicroTech controller)
Daikin Applied model ADS air-cooled global screw chillers with the MicroTech chiller unit controller and Modbus communication module, per ED 15121-13.
Also known as: ADS, Daikin ADS, Air-cooled Global Screw Chiller, ED 15121 - Chiller
Daikin Applied MicroTech II centrifugal chillers WSC/WDC/WPV/WMC/WCC/HSC/HDC/TSC (Modbus module)
McQuay/Daikin Applied water-cooled centrifugal chillers with the MicroTech II unit controller and Modbus Communication Module: WSC, WDC, WPV, WMC (magnetic bearing), WCC, HSC/HDC heat recovery and TSC Templifier, per ED 15063-2 (Dec 2005).
Also known as: WSC, WDC, WPV, WMC, WCC, HSC, HDC, TSC, McQuay centrifugal Modbus, MicroTech II chiller, ED 15063 - Chiller
Daikin Applied Trailblazer AMZ air-cooled scroll chiller (MicroTech controller)
Daikin Applied Trailblazer AMZ air-cooled scroll chillers with the MicroTech chiller unit controller and Modbus communication module, per ED 15121-13.
Also known as: AMZ, Trailblazer AMZ, Daikin AMZ, ED 15121 - Chiller (air-cooled chiller for data centres)
Vertiv Liebert HPC chiller with iCOM v4 (IntelliSlot Modbus)
Liebert HPC chillers on the iCOM v4 controller (iCOM_SC31 / iCOM_SC100 applications) with a Liebert IntelliSlot Modbus card.
Also known as: Liebert HPC, HPC chiller, Liebert HPC iCOM
All chillers & heat pumps Modbus register maps →
Source: Symbio 800 Integration Points List, BACnet/Modbus, CenTraVac · BAS-PTS009C-EN · rev. 2025-12-12. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.