- Home
- Modbus register maps
- Trane
- Series R RTWD water-cooled helical-rotary chiller (Symbio 800)
Chiller · Modbus register map
Trane Series R RTWD water-cooled helical-rotary chiller (Symbio 800) Modbus register map
Updated 19 November 2026
Trane's Series R RTWD is a water-cooled helical-rotary (screw) chiller. Its Symbio 800 controller serves BACnet and Modbus RTU/TCP from one points list. This map covers the analog inputs (setpoints, water and refrigerant temperatures and pressures, starts and running time, starter values), BAS setpoints, binary status points, multi-state modes and the diagnostic flags.
This page lists 673 Modbus registers for the Trane Series R RTWD water-cooled helical-rotary chiller (Symbio 800) — 8 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Trane’s own free documentation (linked below) and checked against it.
- Manufacturer
- Trane
- Model
- Series R RTWD water-cooled helical-rotary chiller (Symbio 800)
- Equipment type
- Chiller
- Registers
- 673 (8 writable)
- Transport
- Modbus RTU, Modbus TCP
- Default unit ID
- Not stated
- Documented addressing
- Modicon 3xxxx/4xxxx (drop the prefix, subtract 1)
- 32-bit word order
- ABCD high word first (big-endian)
- Also known as
- RTWD, Series R RTWD, RTUD
Integration notes: Trane Series R RTWD water-cooled helical-rotary chiller (Symbio 800)
Read the analog inputs as pairs of input registers (float, high word first) and the binary/multi-state points as single registers. Write the BAS setpoints and command points in the 4xxxx holding range.
Minimum registers to map
Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.
| Register | Name | Type | Why | Access |
|---|---|---|---|---|
| IR 10 | Active Cool/Heat Setpoint Temperature | FLOAT32 ABCD | Active cool/heat setpoint | Read |
| IR 16 | Evaporator Leaving Water Temperature | FLOAT32 ABCD | Evaporator leaving water temperature | Read |
| IR 14 | Evaporator Entering Water Temperature | FLOAT32 ABCD | Evaporator entering water temperature | Read |
| IR 28 | Actual Running Capacity | FLOAT32 ABCD | Actual running capacity | Read |
| IR 2010 | Running Mode | UINT16 | Running mode | Read |
| IR 3010 | Run Enable | UINT16 | Run enable | Read |
| IR 3018 | Diagnostic Present | UINT16 | Diagnostic present | Read |
| HR 10 | Chilled Water Setpoint | FLOAT32 ABCD | Chilled water setpoint (BAS) | Read/write |
| HR 2010 | Chiller Mode Command BAS | UINT16 | BAS chiller mode command | Read/write |
Enable Modbus control & writes
On the Symbio 800 web interface go to Installation > Identification and Communications > Protocol Configuration and select Modbus RTU or Modbus TCP (per Trane's Symbio 800 integration guides).
Byte order & addressing
- Analog values are 32-bit floats occupying two registers; read both registers in one request.
- 0xFFFF in a binary or multi-state register and NaN in an analog register mean the value is invalid or not present.
Network setup
- The Modbus RTU address comes from the controller's rotary dials (1-247); address 000 disables Modbus RTU.
- Modbus TCP uses Ethernet port 2; the rotary address is ignored for TCP.
Watch out for
- Points not supported by the unit's configuration are absent; confirm the configuration dependencies before mapping.
Trane Series R RTWD water-cooled helical-rotary chiller (Symbio 800) Modbus registers
Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.
| Table | Address | Name | Description | Type | Order | Scale | Units | Access | Values / bits |
|---|---|---|---|---|---|---|---|---|---|
| IR | 10doc 30011 | Active Cool/Heat Setpoint Temperature | Temperature in the factory unit system (I-P or SI). | FLOAT32 | ABCD | Read | |||
| IR | 12doc 30013 | Active Demand Limit Setpoint | FLOAT32 | ABCD | % | Read | |||
| IR | 14doc 30015 | Evaporator Entering Water Temperature | Temperature in the factory unit system (I-P or SI). | FLOAT32 | ABCD | Read | |||
| IR | 16doc 30017 | Evaporator Leaving Water Temperature | Temperature in the factory unit system (I-P or SI). | FLOAT32 | ABCD | Read | |||
| IR | 18doc 30019 | Outdoor Air Temperature | Temperature in the factory unit system (I-P or SI). | FLOAT32 | ABCD | Read | |||
| IR | 20doc 30021 | Number of Circuits | FLOAT32 | ABCD | Read | ||||
| IR | 24doc 30025 | Number of Compressors, Circuit 1 | FLOAT32 | ABCD | Read | ||||
| IR | 26doc 30027 | Number of Compressors, Circuit 2 | FLOAT32 | ABCD | Read | ||||
| IR | 28doc 30029 | Actual Running Capacity | FLOAT32 | ABCD | % | Read | |||
| IR | 30doc 30031 | Evaporator Refrigerant Absolute Pressure Circuit 1 | Pressure in the factory unit system (I-P or SI). | FLOAT32 | ABCD | Read | |||
| IR | 32doc 30033 | Condenser Refrigerant Absolute Pressure Circuit 1 | Pressure in the factory unit system (I-P or SI). | FLOAT32 | ABCD | Read | |||
| IR | 34doc 30035 | Differential Refrigerant Pressure Ckt1 | Pressure in the factory unit system (I-P or SI). | FLOAT32 | ABCD | Read | |||
| IR | 36doc 30037 | Evaporator Shell Refrigerant Pressure Ckt1 | Pressure in the factory unit system (I-P or SI). Needs: Evaporator Isolation Valves | FLOAT32 | ABCD | Read | |||
| IR | 38doc 30039 | Evaporator Saturated Rfgt Temp Ckt1 | Temperature in the factory unit system (I-P or SI). | FLOAT32 | ABCD | Read | |||
| IR | 40doc 30041 | Condenser Saturated Rfgt Temp Ckt1 | Temperature in the factory unit system (I-P or SI). | FLOAT32 | ABCD | Read | |||
| IR | 42doc 30043 | Discharge Temperature Cprsr1A | Temperature in the factory unit system (I-P or SI). | FLOAT32 | ABCD | Read | |||
| IR | 44doc 30045 | Oil Absolute Pressure Cprsr1A | Pressure in the factory unit system (I-P or SI). Needs: Compressor 1A | FLOAT32 | ABCD | Read | |||
| IR | 46doc 30047 | Starts Cprsr1A | Needs: Compressor 1A | FLOAT32 | ABCD | Read | |||
| IR | 48doc 30049 | Running Time Cprsr1A | Needs: Compressor 1A | FLOAT32 | ABCD | Read | |||
| IR | 50doc 30051 | Evaporator Refrigerant Absolute Pressure Circuit 2 | Pressure in the factory unit system (I-P or SI). | FLOAT32 | ABCD | Read | |||
| IR | 52doc 30053 | Condenser Refrigerant Absolute Pressure Circuit 2 | Pressure in the factory unit system (I-P or SI). | FLOAT32 | ABCD | Read | |||
| IR | 54doc 30055 | Differential Refrigerant Pressure Ckt2 | Pressure in the factory unit system (I-P or SI). | FLOAT32 | ABCD | Read | |||
| IR | 56doc 30057 | Evaporator Shell Refrigerant Pressure Ckt2 | Pressure in the factory unit system (I-P or SI). Needs: Evaporator Isolation Valves | FLOAT32 | ABCD | Read | |||
| IR | 58doc 30059 | Evaporator Saturated Rfgt Temp Ckt2 | Temperature in the factory unit system (I-P or SI). | FLOAT32 | ABCD | Read | |||
| IR | 60doc 30061 | Condenser Saturated Rfgt Temp Ckt2 | Temperature in the factory unit system (I-P or SI). | FLOAT32 | ABCD | Read | |||
| IR | 62doc 30063 | Compressor Suction Temperature | Temperature in the factory unit system (I-P or SI). Needs: RTSF | FLOAT32 | ABCD | Read | |||
| IR | 64doc 30065 | Discharge Temperature Cprsr2A | Temperature in the factory unit system (I-P or SI). Needs: Compressor 2A | FLOAT32 | ABCD | Read | |||
| IR | 66doc 30067 | Oil Absolute Pressure Cprsr2A | Pressure in the factory unit system (I-P or SI). Needs: Compressor 2A | FLOAT32 | ABCD | Read | |||
| IR | 68doc 30069 | Discharge Temperature Cprsr1B | Temperature in the factory unit system (I-P or SI). Needs: Compressor 1B | FLOAT32 | ABCD | Read | |||
| IR | 70doc 30071 | Oil Absolute Pressure Cprsr1B | Pressure in the factory unit system (I-P or SI). Needs: Compressor 1B | FLOAT32 | ABCD | Read | |||
| IR | 72doc 30073 | Starts Cprsr1B | Needs: Compressor 1B | FLOAT32 | ABCD | Read | |||
| IR | 74doc 30075 | Running Time Cprsr1B | Needs: Compressor 1B | FLOAT32 | ABCD | Read | |||
| IR | 76doc 30077 | Starts Cprsr2A | Needs: Compressor 2A | FLOAT32 | ABCD | Read | |||
| IR | 78doc 30079 | Running Time Cprsr2A | Needs: Compressor 2A | FLOAT32 | ABCD | Read | |||
| IR | 80doc 30081 | Discharge Temperature Cprsr2B | Temperature in the factory unit system (I-P or SI). Needs: Compressor 2B | FLOAT32 | ABCD | Read | |||
| IR | 82doc 30083 | Oil Absolute Pressure Cprsr2B | Pressure in the factory unit system (I-P or SI). Needs: Compressor 2B | FLOAT32 | ABCD | Read | |||
| IR | 84doc 30085 | Starts Cprsr2B | Needs: Compressor 2B | FLOAT32 | ABCD | Read | |||
| IR | 86doc 30087 | Running Time Cprsr2B | Needs: Compressor 2B | FLOAT32 | ABCD | Read | |||
| IR | 88doc 30089 | Motor Voltage AB Starter 1A | Voltage. Needs: Line Voltage Sensing | FLOAT32 | ABCD | Read | |||
| IR | 90doc 30091 | Motor Voltage AB Starter 1B | Voltage. Needs: Line Voltage Sensing | FLOAT32 | ABCD | Read | |||
| IR | 92doc 30093 | Motor Voltage AB Starter 2A | Voltage. Needs: Line Voltage Sensing | FLOAT32 | ABCD | Read | |||
| IR | 94doc 30095 | Motor Voltage AB Starter 2B | Voltage. Needs: Line Voltage Sensing | FLOAT32 | ABCD | Read | |||
| IR | 96doc 30097 | Oil Temperature Circuit 1 | Temperature in the factory unit system (I-P or SI). Needs: Oil Cooler | FLOAT32 | ABCD | Read | |||
| IR | 98doc 30099 | Oil Temperature Circuit 2 | Temperature in the factory unit system (I-P or SI). Needs: Oil Cooler | FLOAT32 | ABCD | Read | |||
| IR | 100doc 30101 | Condenser Entering Water Temperature | Temperature in the factory unit system (I-P or SI). | FLOAT32 | ABCD | Read | |||
| IR | 102doc 30103 | Condenser Leaving Water Temperature | Temperature in the factory unit system (I-P or SI). | FLOAT32 | ABCD | Read | |||
| IR | 104doc 30105 | Unit Power Consumption | Electrical power. Needs: Energy Meter | FLOAT32 | ABCD | Read | |||
| IR | 106doc 30107 | Energy Consumption NonReset | Electrical energy. Needs: Energy Meter | FLOAT32 | ABCD | Read | |||
| IR | 108doc 30109 | Energy Consumption Resettable | Electrical energy. Needs: Energy Meter | FLOAT32 | ABCD | Read | |||
| IR | 110doc 30111 | Motor Current L1 Starter 1A | Current. Needs: Starter 1A | FLOAT32 | ABCD | Read | |||
| IR | 112doc 30113 | Motor Current L2 Starter 1A | Current. Needs: Starter 1A | FLOAT32 | ABCD | Read | |||
| IR | 114doc 30115 | Motor Current L3 Starter 1A | Current. Needs: Starter 1A | FLOAT32 | ABCD | Read | |||
| IR | 116doc 30117 | Motor Current L1 % RLA Starter 1A | Needs: Starter 1A | FLOAT32 | ABCD | % | Read | ||
| IR | 118doc 30119 | Motor Current L2 % RLA Starter 1A | Needs: Starter 1A | FLOAT32 | ABCD | % | Read | ||
| IR | 120doc 30121 | Motor Current L3 % RLA Starter 1A | Needs: Starter 1A | FLOAT32 | ABCD | % | Read | ||
| IR | 122doc 30123 | Motor Current L1 Starter 2A | Current. Needs: Starter 2A | FLOAT32 | ABCD | Read | |||
| IR | 124doc 30125 | Motor Current L2 Starter 2A | Current. Needs: Starter 2A | FLOAT32 | ABCD | Read | |||
| IR | 126doc 30127 | Motor Current L3 Starter 2A | Current. Needs: Starter 2A | FLOAT32 | ABCD | Read | |||
| IR | 128doc 30129 | Motor Current L1 % RLA Starter 2A | Needs: Starter 2A | FLOAT32 | ABCD | % | Read | ||
| IR | 130doc 30131 | Motor Current L2 % RLA Starter 2A | Needs: Starter 2A | FLOAT32 | ABCD | % | Read | ||
| IR | 132doc 30133 | Motor Current L3 % RLA Starter 2A | Needs: Starter 2A | FLOAT32 | ABCD | % | Read | ||
| IR | 134doc 30135 | Motor Current L1 Starter 1B | Current. Needs: Starter 1B | FLOAT32 | ABCD | Read | |||
| IR | 136doc 30137 | Motor Current L2 Starter 1B | Current. Needs: Starter 1B | FLOAT32 | ABCD | Read | |||
| IR | 138doc 30139 | Motor Current L3 Starter 1B | Current. Needs: Starter 1B | FLOAT32 | ABCD | Read | |||
| IR | 140doc 30141 | Motor Current L1 % RLA Starter 1B | Needs: Starter 1B | FLOAT32 | ABCD | % | Read | ||
| IR | 142doc 30143 | Motor Current L2 % RLA Starter 1B | Needs: Starter 1B | FLOAT32 | ABCD | % | Read | ||
| IR | 144doc 30145 | Motor Current L3 % RLA Starter 1B | Needs: Starter 1B | FLOAT32 | ABCD | % | Read | ||
| IR | 146doc 30147 | Motor Current L1 Starter 2B | Current. Needs: Starter 2B | FLOAT32 | ABCD | Read | |||
| IR | 148doc 30149 | Motor Current L2 Starter 2B | Current. Needs: Starter 2B | FLOAT32 | ABCD | Read | |||
| IR | 150doc 30151 | Motor Current L3 Starter 2B | Current. Needs: Starter 2B | FLOAT32 | ABCD | Read | |||
| IR | 152doc 30153 | Motor Current L1 % RLA Starter 2B | Needs: Starter 2B | FLOAT32 | ABCD | % | Read | ||
| IR | 154doc 30155 | Motor Current L2 % RLA Starter 2B | Needs: Starter 2B | FLOAT32 | ABCD | % | Read | ||
| IR | 156doc 30157 | Motor Current L3 % RLA Starter 2B | Needs: Starter 2B | FLOAT32 | ABCD | % | Read | ||
| IR | 158doc 30159 | Motor Current A Cprsr1A | Current. Needs: GP4 w/Modbus AFD (TR200) | FLOAT32 | ABCD | Read | |||
| IR | 160doc 30161 | Motor Current B Cprsr1A | Current. Needs: GP4 w/Modbus AFD (TR200) | FLOAT32 | ABCD | Read | |||
| IR | 162doc 30163 | Motor Current C Cprsr1A | Current. Needs: GP4 w/Modbus AFD (TR200) | FLOAT32 | ABCD | Read | |||
| IR | 164doc 30165 | Motor % RLA A Cprsr1A | Needs: GP4 w/Modbus AFD (TR200) | FLOAT32 | ABCD | % | Read | ||
| IR | 166doc 30167 | Motor % RLA B Cprsr1A | Needs: GP4 w/Modbus AFD (TR200) | FLOAT32 | ABCD | % | Read | ||
| IR | 168doc 30169 | Motor % RLA C Cprsr1A | Needs: GP4 w/Modbus AFD (TR200) | FLOAT32 | ABCD | % | Read | ||
| IR | 170doc 30171 | Motor Current A Cprsr2A | Current. Needs: GP4 w/Modbus AFD (TR200) | FLOAT32 | ABCD | Read | |||
| IR | 172doc 30173 | Motor Current B Cprsr2A | Current. Needs: GP4 w/Modbus AFD (TR200) | FLOAT32 | ABCD | Read | |||
| IR | 174doc 30175 | Motor Current C Cprsr2A | Current. Needs: GP4 w/Modbus AFD (TR200) | FLOAT32 | ABCD | Read | |||
| IR | 176doc 30177 | Motor % RLA A Cprsr2A | Needs: GP4 w/Modbus AFD (TR200) | FLOAT32 | ABCD | % | Read | ||
| IR | 178doc 30179 | Motor % RLA B Cprsr2A | Needs: GP4 w/Modbus AFD (TR200) | FLOAT32 | ABCD | % | Read | ||
| IR | 180doc 30181 | Motor % RLA C Cprsr2A | Needs: GP4 w/Modbus AFD (TR200) | FLOAT32 | ABCD | % | Read | ||
| IR | 182doc 30183 | Average Motor Current % RLA AFD 1A | Needs: Modbus AFD (TR200) | FLOAT32 | ABCD | % | Read | ||
| IR | 184doc 30185 | Average Motor Current % RLA AFD 2A | Needs: Modbus AFD (TR200) | FLOAT32 | ABCD | % | Read | ||
| IR | 186doc 30187 | Unit Source ID (Last Diagnostic Code) | FLOAT32 | ABCD | Read | ||||
| IR | 188doc 30189 | Chiller Design Capacity | Cooling capacity in the factory unit system (I-P or SI). | FLOAT32 | ABCD | Read | |||
| IR | 190doc 30191 | Active Chilled Water Setpoint | Temperature in the factory unit system (I-P or SI). | FLOAT32 | ABCD | Read | |||
| IR | 192doc 30193 | Active Hot Water Setpoint | Temperature in the factory unit system (I-P or SI). Needs: Hot Water Control | FLOAT32 | ABCD | Read | |||
| IR | 194doc 30195 | Unit Load Command | FLOAT32 | ABCD | % | Read | |||
| IR | 196doc 30197 | Air Flow Percentage Circuit 1 | Needs: RTUD | FLOAT32 | ABCD | % | Read | ||
| IR | 198doc 30199 | Air Flow Percentage Circuit 2 | Needs: RTUD | FLOAT32 | ABCD | % | Read | ||
| IR | 200doc 30201 | Evaporator Refrigerant Pressure Circuit 1 | Pressure in the factory unit system (I-P or SI). | FLOAT32 | ABCD | Read | |||
| IR | 202doc 30203 | Condenser Refrigerant Pressure Circuit 1 | Pressure in the factory unit system (I-P or SI). | FLOAT32 | ABCD | Read | |||
| IR | 204doc 30205 | Evaporator Refrigerant Pressure Circuit 2 | Pressure in the factory unit system (I-P or SI). | FLOAT32 | ABCD | Read | |||
| IR | 206doc 30207 | Condenser Refrigerant Pressure Circuit 2 | Pressure in the factory unit system (I-P or SI). | FLOAT32 | ABCD | Read | |||
| IR | 208doc 30209 | Condenser Control Output | Needs: Head Pressure Control | FLOAT32 | ABCD | % | Read | ||
| IR | 210doc 30211 | Oil Pressure Cprsr1A | Pressure in the factory unit system (I-P or SI). Needs: Compressor 1A | FLOAT32 | ABCD | Read | |||
| IR | 212doc 30213 | Oil Pressure Cprsr2A | Pressure in the factory unit system (I-P or SI). Needs: Compressor 2A | FLOAT32 | ABCD | Read | |||
| IR | 214doc 30215 | Oil Pressure Cprsr1B | Pressure in the factory unit system (I-P or SI). Needs: Compressor 1B | FLOAT32 | ABCD | Read | |||
| IR | 216doc 30217 | Oil Pressure Cprsr2B | Pressure in the factory unit system (I-P or SI). Needs: Compressor 2B | FLOAT32 | ABCD | Read | |||
| IR | 218doc 30219 | Evaporator Approach Temperature Circuit 1 | Temperature difference, factory unit system (I-P or SI). | FLOAT32 | ABCD | Read | |||
| IR | 220doc 30221 | Evaporator Approach Temperature Circuit 2 | Temperature difference, factory unit system (I-P or SI). | FLOAT32 | ABCD | Read | |||
| IR | 222doc 30223 | Condenser Approach Temperature Circuit 1 | Temperature difference, factory unit system (I-P or SI). | FLOAT32 | ABCD | Read | |||
| IR | 224doc 30225 | Condenser Approach Temperature Circuit 2 | Temperature difference, factory unit system (I-P or SI). | FLOAT32 | ABCD | Read | |||
| IR | 226doc 30227 | Average Line Current Circuit 1 | Current. Needs: Two Energy Meters | FLOAT32 | ABCD | Read | |||
| IR | 228doc 30229 | Average Line Current Circuit 2 | Current. Needs: Two Energy Meters | FLOAT32 | ABCD | Read | |||
| IR | 230doc 30231 | Average Line Voltage Circuit 1 | Voltage. Needs: Two Energy Meters | FLOAT32 | ABCD | Read | |||
| IR | 232doc 30233 | Average Line Voltage Circuit 2 | Voltage. Needs: Two Energy Meters | FLOAT32 | ABCD | Read | |||
| IR | 234doc 30235 | Line Current L1 Circuit 1 | Current. Needs: Two Energy Meters | FLOAT32 | ABCD | Read | |||
| IR | 236doc 30237 | Line Current L2 Circuit 1 | Current. Needs: Two Energy Meters | FLOAT32 | ABCD | Read | |||
| IR | 238doc 30239 | Line Current L3 Circuit 1 | Current. Needs: Two Energy Meters | FLOAT32 | ABCD | Read | |||
| IR | 240doc 30241 | Line Current L1 Circuit 2 | Current. Needs: Two Energy Meters | FLOAT32 | ABCD | Read | |||
| IR | 242doc 30243 | Line Current L2 Circuit 2 | Current. Needs: Two Energy Meters | FLOAT32 | ABCD | Read | |||
| IR | 244doc 30245 | Line Current L3 Circuit 2 | Current. Needs: Two Energy Meters | FLOAT32 | ABCD | Read | |||
| IR | 246doc 30247 | Voltage L1-L2 Circuit 1 | Voltage. Needs: Two Energy Meters | FLOAT32 | ABCD | Read | |||
| IR | 248doc 30249 | Voltage L2-L3 Circuit 1 | Voltage. Needs: Two Energy Meters | FLOAT32 | ABCD | Read | |||
| IR | 250doc 30251 | Voltage L1-L3 Circuit 1 | Voltage. Needs: Two Energy Meters | FLOAT32 | ABCD | Read | |||
| IR | 252doc 30253 | Voltage L1-L2 Circuit 2 | Voltage. Needs: Two Energy Meters | FLOAT32 | ABCD | Read | |||
| IR | 254doc 30255 | Voltage L2-L1 Circuit 2 | Voltage. Needs: Two Energy Meters | FLOAT32 | ABCD | Read | |||
| IR | 256doc 30257 | Voltage L1-L3 Circuit 2 | Voltage. Needs: Two Energy Meters | FLOAT32 | ABCD | Read | |||
| IR | 258doc 30259 | Line Frequency Circuit 1 | Needs: Two Energy Meters | FLOAT32 | ABCD | Read | |||
| IR | 260doc 30261 | Line Frequency Circuit 2 | Needs: Two Energy Meters | FLOAT32 | ABCD | Read | |||
| IR | 262doc 30263 | Power Factor Circuit 1 | Needs: Two Energy Meters | FLOAT32 | ABCD | Read | |||
| IR | 264doc 30265 | Power Factor Circuit 2 | Needs: Two Energy Meters | FLOAT32 | ABCD | Read | |||
| IR | 266doc 30267 | Power Demand Circuit 1 | Electrical power. Needs: Two Energy Meters | FLOAT32 | ABCD | Read | |||
| IR | 268doc 30269 | Power Demand Circuit 2 | Electrical power. Needs: Two Energy Meters | FLOAT32 | ABCD | Read | |||
| IR | 270doc 30271 | Power Factor | Needs: One Energy Meter | FLOAT32 | ABCD | Read | |||
| IR | 272doc 30273 | Current L1 | Current. Needs: One Energy Meter | FLOAT32 | ABCD | Read | |||
| IR | 274doc 30275 | Current L2 | Current. Needs: One Energy Meter | FLOAT32 | ABCD | Read | |||
| IR | 276doc 30277 | Current L3 | Current. Needs: One Energy Meter | FLOAT32 | ABCD | Read | |||
| IR | 278doc 30279 | Average Current | Current. Needs: One Energy Meter | FLOAT32 | ABCD | Read | |||
| IR | 280doc 30281 | Voltage L1-L2 | Voltage. Needs: One Energy Meter | FLOAT32 | ABCD | Read | |||
| IR | 282doc 30283 | Voltage L2-L3 | Voltage. Needs: One Energy Meter | FLOAT32 | ABCD | Read | |||
| IR | 284doc 30285 | Voltage L1-L3 | Voltage. Needs: One Energy Meter | FLOAT32 | ABCD | Read | |||
| IR | 286doc 30287 | Average Voltage L-L | Voltage. Needs: One Energy Meter | FLOAT32 | ABCD | Read | |||
| IR | 288doc 30289 | Line Frequency | Needs: One Energy Meter | FLOAT32 | ABCD | Read | |||
| IR | 290doc 30291 | Unit Power Demand | Electrical power. Needs: Power Monitor | FLOAT32 | ABCD | Read | |||
| IR | 292doc 30293 | Active Cooling Differential to Start | Temperature difference, factory unit system (I-P or SI). | FLOAT32 | ABCD | Read | |||
| IR | 294doc 30295 | Active Cooling Differential to Stop | Temperature difference, factory unit system (I-P or SI). | FLOAT32 | ABCD | Read | |||
| IR | 296doc 30297 | Active Heating Differential to Start | Temperature difference, factory unit system (I-P or SI). Needs: Hot Water Control | FLOAT32 | ABCD | Read | |||
| IR | 298doc 30299 | Active Heating Differential to Stop | Temperature difference, factory unit system (I-P or SI). Needs: Hot Water Control | FLOAT32 | ABCD | Read | |||
| IR | 2010doc 32011 | Running Mode | UINT16 | Read | 1 = Chiller Off; 2 = Chiller In Start Mode; 3 = Chiller In Run Mode; 4 = Chiller In Pre-Shutdown Mode; 5 = Chiller In Service Mode | ||||
| IR | 2011doc 32012 | Operating Mode | UINT16 | Read | 1 = Cool; 2 = Heat; 3 = Ice Making; 4 = Free Cooling | ||||
| IR | 2013doc 32014 | Refrigerant Type | UINT16 | Read | 5 = R-134a; 13 = R-513A; 16 = R-1234ze(E); 18 = R-515B | ||||
| IR | 2014doc 32015 | Manufacturing Location | UINT16 | Read | 3 = Pueblo; 4 = Charmes | ||||
| IR | 2015doc 32016 | Cooling Type | UINT16 | Read | 1 = Water Cooled; 2 = Air Cooled | ||||
| IR | 2016doc 32017 | Model Information [GEN2] | UINT16 | Read | 17 = RTWF; 30 = RTSF; 41 = RTWF XSE; 45 = RTWD; 46 = RTUD | ||||
| IR | 3010doc 33011 | Run Enable | UINT16 | Read | 0 = Run Not Enabled; 1 = Run Enabled | ||||
| IR | 3011doc 33012 | Local Setpoint Control | UINT16 | Read | 0 = Remote Control; 1 = Local Control | ||||
| IR | 3012doc 33013 | Limit Mode Relay Status | UINT16 | Read | 0 = Off; 1 = On | ||||
| IR | 3013doc 33014 | Chiller Running State | UINT16 | Read | 0 = Off; 1 = On | ||||
| IR | 3014doc 33015 | Maximum Capacity | UINT16 | Read | 0 = Off; 1 = On | ||||
| IR | 3015doc 33016 | Manual Override Exists | UINT16 | Read | 0 = Off; 1 = On | ||||
| IR | 3016doc 33017 | Emergency Stop | UINT16 | Read | 0 = Auto; 1 = Emergency Stop - Manual Reset Required | ||||
| IR | 3017doc 33018 | Evaporator Water Flow Status | UINT16 | Read | 0 = No Flow; 1 = Flow | ||||
| IR | 3018doc 33019 | Diagnostic Present | UINT16 | Read | 0 = Normal; 1 = In Alarm | ||||
| IR | 3019doc 33020 | Diagnostic Shutdown Present | UINT16 | Read | 0 = Normal; 1 = In Alarm | ||||
| IR | 3020doc 33021 | Diagnostic: Manual Reset Required | UINT16 | Read | 0 = Normal; 1 = In Alarm | ||||
| IR | 3021doc 33022 | Diagnostic: Local Manual Reset Required | UINT16 | Read | 0 = Normal; 1 = In Alarm | ||||
| IR | 3022doc 33023 | Diagnostic Present: Information | UINT16 | Read | 0 = Normal; 1 = In Alarm | ||||
| IR | 3023doc 33024 | Diagnostic Present: Advisory | UINT16 | Read | 0 = Normal; 1 = In Alarm | ||||
| IR | 3024doc 33025 | Diagnostic Present: Critical | UINT16 | Read | 0 = Normal; 1 = In Alarm | ||||
| IR | 3025doc 33026 | Diagnostic Present: Service Required | UINT16 | Read | 0 = Normal; 1 = In Alarm | ||||
| IR | 3026doc 33027 | Compressor 1A Running Status | UINT16 | Read | 0 = Stop; 1 = Auto | ||||
| IR | 3027doc 33028 | Compressor 1B Running Status | Needs: Compressor 1B | UINT16 | Read | 0 = Stop; 1 = Auto | |||
| IR | 3028doc 33029 | Compressor 2A Running Status | Needs: Compressor 2A | UINT16 | Read | 0 = Stop; 1 = Auto | |||
| IR | 3029doc 33030 | Compressor 2B Running Status | Needs: Compressor 2B | UINT16 | Read | 0 = Stop; 1 = Auto | |||
| IR | 3030doc 33031 | External Auto Stop | UINT16 | Read | 0 = Stop; 1 = Auto | ||||
| IR | 3031doc 33032 | Condenser Water Pump Command | UINT16 | Read | 0 = Inactive; 1 = Active | ||||
| IR | 3032doc 33033 | Evaporator Water Pump Command | UINT16 | Read | 0 = Off; 1 = On | ||||
| IR | 3033doc 33034 | Condenser Water Flow Status | UINT16 | Read | 0 = Inactive; 1 = Active | ||||
| IR | 3034doc 33035 | Front Panel Auto Stop Status | UINT16 | Read | 0 = Stop; 1 = Auto | ||||
| IR | 3035doc 33036 | Circuit Manual Reset Indicator (CMR) Ckt1 | UINT16 | Read | 0 = Inactive; 1 = Active | ||||
| IR | 3036doc 33037 | Circuit Manual Reset Indicator (CMR) Ckt2 | Needs: Circuit 2 | UINT16 | Read | 0 = Inactive; 1 = Active | |||
| IR | 3037doc 33038 | Circuit Auto Reset Indicator (CAR) Ckt1 | UINT16 | Read | 0 = Inactive; 1 = Active | ||||
| IR | 3038doc 33039 | Circuit Auto Reset Indicator (CAR) Ckt2 | Needs: Circuit 2 | UINT16 | Read | 0 = Inactive; 1 = Active | |||
| IR | 3039doc 33040 | Head Pressure Relief Request | UINT16 | Read | 0 = Normal; 1 = Locked Out | ||||
| IR | 3040doc 33041 | Alarm - General Latching Unit | UINT16 | Read | 0 = Normal; 1 = In Alarm | ||||
| IR | 3041doc 33042 | Alarm - General Non Latching Unit | UINT16 | Read | 0 = Normal; 1 = In Alarm | ||||
| IR | 3042doc 33043 | Alarm - General Latching Ckt1 | UINT16 | Read | 0 = Normal; 1 = In Alarm | ||||
| IR | 3043doc 33044 | Alarm - General Latching Ckt2 | Needs: Circuit 2 | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 3044doc 33045 | Alarm - General Non Latching Ckt1 | UINT16 | Read | 0 = Normal; 1 = In Alarm | ||||
| IR | 3045doc 33046 | Alarm - General Non Latching Ckt2 | Needs: Circuit 2 | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 3046doc 33047 | Noise Reduction Request Active | Needs: Noise Reduction | UINT16 | Read | 0 = Off; 1 = On | |||
| IR | 4000doc 34001 | Comm Loss: %RLA Indication Output (Vdc) | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4001doc 34002 | Comm Loss: AFD 1A | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4002doc 34003 | Comm Loss: AFD 2A | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4003doc 34004 | Comm Loss: AFD Fault Input 1A | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4004doc 34005 | Comm Loss: AFD Fault Input 1B | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4005doc 34006 | Comm Loss: AFD Fault Input 2A | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4006doc 34007 | Comm Loss: AFD Fault Input 2B | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4007doc 34008 | Comm Loss: AFD Run Command 1A | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4008doc 34009 | Comm Loss: AFD Run Command 2A | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4009doc 34010 | Comm Loss: AFD Speed Command 1A | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4010doc 34011 | Comm Loss: AFD Speed Command 1B | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4011doc 34012 | Comm Loss: AFD Speed Command 2A | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4012doc 34013 | Comm Loss: AFD Speed Command 2B | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4013doc 34014 | Comm Loss: AOC Inlet Oil Temperature 1A | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4014doc 34015 | Comm Loss: AOC Inlet Oil Temperature 2A | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4015doc 34016 | Comm Loss: Auxiliary Setpoint Command | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4016doc 34017 | Comm Loss: Chiller Bypass Valve Output | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4017doc 34018 | Comm Loss: Cond Head Press Cntrl Output | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4018doc 34019 | Comm Loss: Cond Rfgt Liquid Level Ckt1 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4019doc 34020 | Comm Loss: Cond Rfgt Liquid Level Ckt2 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4020doc 34021 | Comm Loss: Cond Water Pump Analog Output | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4021doc 34022 | Comm Loss: Condenser Entering Water Temp | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4022doc 34023 | Comm Loss: Condenser Leaving Water Temp | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4023doc 34024 | Comm Loss: Condenser Rfgt Pressure Ckt2 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4024doc 34025 | Comm Loss: Condenser Rfgt Pressure Ckt1 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4025doc 34026 | Comm Loss: Condenser Rfgt Pressure Output | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4026doc 34027 | Comm Loss: Condenser Water Flow Switch | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4027doc 34028 | Comm Loss: Condenser Water Pump Relay | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4028doc 34029 | Comm Loss: Cprsr Disch Rfgt Temp 1A | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4029doc 34030 | Comm Loss: Cprsr Disch Rfgt Temp 1B | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4030doc 34031 | Comm Loss: Cprsr Disch Rfgt Temp 2A | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4031doc 34032 | Comm Loss: Cprsr Disch Rfgt Temp 2B | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4032doc 34033 | Comm Loss: Electronic Expansion Valve Ckt1 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4033doc 34034 | Comm Loss: Electronic Expansion Valve Ckt2 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4034doc 34035 | Comm Loss: Emergency Stop Feedback Input | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4035doc 34036 | Comm Loss: Energy Meter Pulse Input | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4036doc 34037 | Comm Loss: Evap Entering Water Pressure | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4037doc 34038 | Comm Loss: Evap Entering Water Temp | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4038doc 34039 | Comm Loss: Evap Iso Valve Close Switch Ckt1 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4039doc 34040 | Comm Loss: Evap Iso Valve Close Switch Ckt2 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4040doc 34041 | Comm Loss: Evap Iso Valve Open Switch Ckt1 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4041doc 34042 | Comm Loss: Evap Iso Valve Open Switch Ckt2 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4042doc 34043 | Comm Loss: Evap Isolation Valve Relay Ckt1 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4043doc 34044 | Comm Loss: Evap Isolation Valve Relay Ckt2 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4044doc 34045 | Comm Loss: Evap Leaving Water Pressure | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4045doc 34046 | Comm Loss: Evap Leaving Water Temp | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4046doc 34047 | Comm Loss: Evap Oil Return Level Ckt1 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4047doc 34048 | Comm Loss: Evap Oil Return Level Ckt2 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4048doc 34049 | Comm Loss: Evap Pump Inv1 Fault Input | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4049doc 34050 | Comm Loss: Evap Pump Inv1 Run Command | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4050doc 34051 | Comm Loss: Evap Rfgt Liquid Level Ckt1 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4051doc 34052 | Comm Loss: Evap Rfgt Liquid Level Ckt2 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4052doc 34053 | Comm Loss: Evap Rfgt Pool Temp Ckt1 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4053doc 34054 | Comm Loss: Evap Rfgt Pool Temp Ckt2 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4054doc 34055 | Comm Loss: Evap Shell Rfgt Pressure Ckt1 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4055doc 34056 | Comm Loss: Evap Shell Rfgt Pressure Ckt2 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4056doc 34057 | Comm Loss: Evap Water Pump Analog Output | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4057doc 34058 | Comm Loss: Evap Water Pump Inv Freq Input | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4058doc 34059 | Comm Loss: Evaporator Pump 1 Fault Input | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4059doc 34060 | Comm Loss: Evaporator Pump 2 Fault Input | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4060doc 34061 | Comm Loss: Evaporator Water Flow Switch | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4061doc 34062 | Comm Loss: Evaporator Water Pump 1 Relay | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4062doc 34063 | Comm Loss: Evaporator Water Pump 2 Relay | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4063doc 34064 | Comm Loss: Ext Chilled/Hot Water Setpoint | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4064doc 34065 | Comm Loss: Ext Demand Limit Setpoint | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4065doc 34066 | Comm Loss: Ext Noise Reduction Request | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4066doc 34067 | Comm Loss: External Auto/Stop | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4067doc 34068 | Comm Loss: External Ckt2 Lockout | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4068doc 34069 | Comm Loss: External Ckt1 Lockout | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4069doc 34070 | Comm Loss: External Hot Water Command | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4070doc 34071 | Comm Loss: External Ice Building Command | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4071doc 34072 | Comm Loss: Fan Control Relays, Ckt1 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4072doc 34073 | Comm Loss: Fan Control Relays, Ckt2 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4073doc 34074 | Comm Loss: Fan Inverter Fault Ckt1 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4074doc 34075 | Comm Loss: Fan Inverter Fault Ckt2 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4075doc 34076 | Comm Loss: Fan Inverter Speed Command Ckt1 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4076doc 34077 | Comm Loss: Fan Inverter Speed Command Ckt2 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4077doc 34078 | Comm Loss: High Pressure Cutout Sw 1A | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4078doc 34079 | Comm Loss: High Pressure Cutout Sw 1B | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4079doc 34080 | Comm Loss: High Pressure Cutout Sw 2A | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4080doc 34081 | Comm Loss: High Pressure Cutout Sw 2B | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4081doc 34082 | Comm Loss: High Pressure Cutout Switch Ckt2 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4082doc 34083 | Comm Loss: High Pressure Cutout Switch Ckt1 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4083doc 34084 | Comm Loss: HR Entering Water Temp Sensor | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4084doc 34085 | Comm Loss: HR Leaving Water Temp Sensor | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4085doc 34086 | Comm Loss: Ice Building Status Relay | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4086doc 34087 | Comm Loss: Liquid Line Pressure Ckt1 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4087doc 34088 | Comm Loss: Liquid Line Pressure Ckt2 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4088doc 34089 | Comm Loss: Liquid Line Temperature Ckt1 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4089doc 34090 | Comm Loss: Liquid Line Temperature Ckt2 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4090doc 34091 | Comm Loss: Motor RLA Input 1A | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4091doc 34092 | Comm Loss: Motor RLA Input 1B | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4092doc 34093 | Comm Loss: Motor RLA Input 2A | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4093doc 34094 | Comm Loss: Motor RLA Input 2B | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4094doc 34095 | Comm Loss: Motor Winding Tstat Cprsr1A | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4095doc 34096 | Comm Loss: Motor Winding Tstat Cprsr2A | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4096doc 34097 | Comm Loss: Noise Reduction Request Relay Ckt1 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4097doc 34098 | Comm Loss: Noise Reduction Request Relay Ckt2 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4098doc 34099 | Comm Loss: Off-cycle Freeze Prot Relay | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4099doc 34100 | Comm Loss: Oil Heater Relay 1A | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4100doc 34101 | Comm Loss: Oil Heater Relay 2A | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4101doc 34102 | Comm Loss: Oil Loss Level Sensor Input Ckt1 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4102doc 34103 | Comm Loss: Oil Loss Level Sensor Input Ckt2 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4103doc 34104 | Comm Loss: Oil Pressure 1A | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4104doc 34105 | Comm Loss: Oil Pressure 1B | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4105doc 34106 | Comm Loss: Oil Pressure 2A | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4106doc 34107 | Comm Loss: Oil Pressure 2B | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4107doc 34108 | Comm Loss: Oil Return Gas Pump Drain Ckt1 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4108doc 34109 | Comm Loss: Oil Return Gas Pump Drain Ckt2 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4109doc 34110 | Comm Loss: Oil Return Gas Pump Fill Ckt1 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4110doc 34111 | Comm Loss: Oil Return Gas Pump Fill Ckt2 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4111doc 34112 | Comm Loss: Oil Return Purge Valve Ckt1 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4112doc 34113 | Comm Loss: Oil Return Purge Valve Ckt2 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4113doc 34114 | Comm Loss: Oil Temp, Ckt 1 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4114doc 34115 | Comm Loss: Oil Temp, Ckt 2 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4115doc 34116 | Comm Loss: Outdoor Air Temperature | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4116doc 34117 | Comm Loss: Programmable Relay Board 1 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4117doc 34118 | Comm Loss: Programmable Relay Board 2 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4118doc 34119 | Comm Loss: Reversing Valve | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4119doc 34120 | Comm Loss: Slide Valve Load 1A | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4120doc 34121 | Comm Loss: Slide Valve Load 1B | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4121doc 34122 | Comm Loss: Slide Valve Load 2A | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4122doc 34123 | Comm Loss: Slide Valve Load 2B | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4123doc 34124 | Comm Loss: Slide Valve Unload 1A | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4124doc 34125 | Comm Loss: Slide Valve Unload 1B | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4125doc 34126 | Comm Loss: Slide Valve Unload 2A | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4126doc 34127 | Comm Loss: Slide Valve Unload 2B | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4127doc 34128 | Comm Loss: Starter 1A | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4128doc 34129 | Comm Loss: Starter 1B | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4129doc 34130 | Comm Loss: Starter 2A | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4130doc 34131 | Comm Loss: Starter 2B | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4131doc 34132 | Comm Loss: Step Load 1A | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4132doc 34133 | Comm Loss: Step Load 1B | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4133doc 34134 | Comm Loss: Step Load 2A | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4134doc 34135 | Comm Loss: Step Load 2B | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4135doc 34136 | Comm Loss: Suction Rfgt Pressure Ckt2 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4136doc 34137 | Comm Loss: Suction Rfgt Pressure Ckt1 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4137doc 34138 | Comm Loss: Suction Rfgt Pressure 1A | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4138doc 34139 | Comm Loss: Suction Rfgt Pressure 1B | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4139doc 34140 | Comm Loss: Suction Rfgt Pressure 2A | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4140doc 34141 | Comm Loss: Suction Rfgt Pressure 2B | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4141doc 34142 | Comm Loss: Suction Temperature | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4142doc 34143 | Comm Loss: Water System Diff Pressure | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4143doc 34144 | Comm Loss: Winding Temp 1, Cprsr1A | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4144doc 34145 | Comm Loss: Winding Temp 1, Cprsr2A | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4145doc 34146 | Comm Loss: Winding Temp 2, Cprsr1A | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4146doc 34147 | Diagnostic: AFD %RLA Feedback 1A | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4147doc 34148 | Diagnostic: AFD %RLA Feedback 1B | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4148doc 34149 | Diagnostic: AFD %RLA Feedback 2A | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4149doc 34150 | Diagnostic: AFD %RLA Feedback 2B | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4150doc 34151 | Diagnostic: AFD Bump Complete 1A | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4151doc 34152 | Diagnostic: AFD Bump Complete 2A | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4152doc 34153 | Diagnostic: AFD Bump Current High 1A | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4153doc 34154 | Diagnostic: AFD Bump Current High 2A | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4154doc 34155 | Diagnostic: AFD Comm Loss – 1A | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4155doc 34156 | Diagnostic: AFD Comm Loss – 1B | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4156doc 34157 | Diagnostic: AFD Comm Loss – 2A | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4157doc 34158 | Diagnostic: AFD Comm Loss – 2B | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4158doc 34159 | Diagnostic: AFD Failure to Arm or Start 1A | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4159doc 34160 | Diagnostic: AFD Failure to Arm or Start 1B | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4160doc 34161 | Diagnostic: AFD Failure to Arm or Start 2A | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4161doc 34162 | Diagnostic: AFD Failure to Arm or Start 2B | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4162doc 34163 | Diagnostic: AFD Fault 1A | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4163doc 34164 | Diagnostic: AFD Fault 1B | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4164doc 34165 | Diagnostic: AFD Fault 2A | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4165doc 34166 | Diagnostic: AFD Fault 2B | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4166doc 34167 | Diagnostic: AFD Fault Mains 1A | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4167doc 34168 | Diagnostic: AFD Fault Mains 2A | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4168doc 34169 | Diagnostic: AFD Harmonic Filter Over Temperature 1A | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4169doc 34170 | Diagnostic: AFD Harmonic Filter Over Temperature 2A | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4170doc 34171 | Diagnostic: AFD High Pressure Cutout 1A | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4171doc 34172 | Diagnostic: AFD High Pressure Cutout 2A | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4172doc 34173 | Diagnostic: AFD Interrupt Failure 1A | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4173doc 34174 | Diagnostic: AFD Interrupt Failure 2A | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4174doc 34175 | Diagnostic: AFD Motor Current Overload 1A | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4175doc 34176 | Diagnostic: AFD Motor Current Overload 1B | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4176doc 34177 | Diagnostic: AFD Motor Current Overload 2A | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4177doc 34178 | Diagnostic: AFD Motor Current Overload 2B | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4178doc 34179 | Diagnostic: AFD Motor Fault 1A | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4179doc 34180 | Diagnostic: AFD Motor Fault 2A | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4180doc 34181 | Diagnostic: AFD Motor Speed Too High 1A | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4181doc 34182 | Diagnostic: AFD Motor Speed Too High 2A | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4182doc 34183 | Diagnostic: AFD Motor Speed Too Low 1A | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4183doc 34184 | Diagnostic: AFD Motor Speed Too Low 2A | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4184doc 34185 | Diagnostic: AFD Pump Out Speed Low 1A | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4185doc 34186 | Diagnostic: AFD Pump Out Speed Low 2A | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4186doc 34187 | Diagnostic: AFD Unexpected Shutdown 1A | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4187doc 34188 | Diagnostic: AFD Unexpected Shutdown 2A | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4188doc 34189 | Diagnostic: AFD Unhandled Fault 1A | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4189doc 34190 | Diagnostic: AFD Unhandled Fault 2A | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4190doc 34191 | Diagnostic: AOC Inlet Oil Temperature Sensor 1A | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4191doc 34192 | Diagnostic: AOC Inlet Oil Temperature Sensor 2A | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4192doc 34193 | Diagnostic: Check Clock | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4193doc 34194 | Diagnostic: Chiller Service Recommended | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4194doc 34195 | Diagnostic: Comm Loss: Winding Temp 2, Cprsr2A | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4195doc 34196 | Diagnostic: Cond Rfgt Liquid Level Sensor Ckt1 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4196doc 34197 | Diagnostic: Cond Rfgt Liquid Level Sensor Ckt2 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4197doc 34198 | Diagnostic: Condenser Entering Water Temp Sensor | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4198doc 34199 | Diagnostic: Condenser Leaving Water Temp Sensor | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4199doc 34200 | Diagnostic: Condenser Rfgt Pressure Sensor Ckt2 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4200doc 34201 | Diagnostic: Condenser Rfgt Pressure Sensor Ckt1 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4201doc 34202 | Diagnostic: Condenser Water Flow Lost | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4202doc 34203 | Diagnostic: Condenser Water Flow Overdue | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4203doc 34204 | Diagnostic: Cprsr Did Not Accel: Shutdown 1A | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4204doc 34205 | Diagnostic: Cprsr Did Not Accel: Shutdown 1B | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4205doc 34206 | Diagnostic: Cprsr Did Not Accel: Shutdown 2A | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4206doc 34207 | Diagnostic: Cprsr Did Not Accel: Shutdown 2B | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4207doc 34208 | Diagnostic: Cprsr Did Not Accel: Transition 1A | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4208doc 34209 | Diagnostic: Cprsr Did Not Accel: Transition 1B | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4209doc 34210 | Diagnostic: Cprsr Did Not Accel: Transition 2A | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4210doc 34211 | Diagnostic: Cprsr Did Not Accel: Transition 2B | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4211doc 34212 | Diagnostic: Cprsr Disch Rfgt Temp Sensor 1A | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4212doc 34213 | Diagnostic: Cprsr Disch Rfgt Temp Sensor 1B | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4213doc 34214 | Diagnostic: Cprsr Disch Rfgt Temp Sensor 2A | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4214doc 34215 | Diagnostic: Cprsr Disch Rfgt Temp Sensor 2B | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4215doc 34216 | Diagnostic: Emergency Stop Feedback Input | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4216doc 34217 | Diagnostic: Evap Iso Valve Illegal Switch State Ckt1 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4217doc 34218 | Diagnostic: Evap Iso Valve Illegal Switch State Ckt2 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4218doc 34219 | Diagnostic: Evap Isolation Valve Closed Switch Failure Ckt1 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4219doc 34220 | Diagnostic: Evap Isolation Valve Closed Switch Failure Ckt2 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4220doc 34221 | Diagnostic: Evap Isolation Valve Failed To Close Ckt1 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4221doc 34222 | Diagnostic: Evap Isolation Valve Failed To Close Ckt2 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4222doc 34223 | Diagnostic: Evap Isolation Valve Failed To Open Ckt1 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4223doc 34224 | Diagnostic: Evap Isolation Valve Failed To Open Ckt2 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4224doc 34225 | Diagnostic: Evap Isolation Valve Open Switch Failure Ckt1 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4225doc 34226 | Diagnostic: Evap Isolation Valve Open Switch Failure Ckt2 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4226doc 34227 | Diagnostic: Evap Pump 1 Starts Run time Written | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4227doc 34228 | Diagnostic: Evap Pump 2 Starts Run time Written | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4228doc 34229 | Diagnostic: Evap Rfgt Pool Temp Sensor Ckt1 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4229doc 34230 | Diagnostic: Evap Rfgt Pool Temp Sensor Ckt2 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4230doc 34231 | Diagnostic: Evap Rfgt Pool Temp Sensor Error Ckt1 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4231doc 34232 | Diagnostic: Evap Rfgt Pool Temp Sensor Error Ckt2 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4232doc 34233 | Diagnostic: Evap Spillover Liquid Level Sensor Ckt1 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4233doc 34234 | Diagnostic: Evap Spillover Liquid Level Sensor Ckt2 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4234doc 34235 | Diagnostic: Evap Water Pump 1 Svc Recommended | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4235doc 34236 | Diagnostic: Evap Water Pump 2 Svc Recommended | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4236doc 34237 | Diagnostic: Evaporator Approach Error Ckt2 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4237doc 34238 | Diagnostic: Evaporator Approach Error Ckt1 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4238doc 34239 | Diagnostic: Evaporator Entering Water Pressure | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4239doc 34240 | Diagnostic: Evaporator Entering Water Temp Sensor | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4240doc 34241 | Diagnostic: Evaporator Leaving Water Pressure | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4241doc 34242 | Diagnostic: Evaporator Leaving Water Temp Sensor | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4242doc 34243 | Diagnostic: Evaporator Oil Return Level Sensor, Ckt1 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4243doc 34244 | Diagnostic: Evaporator Oil Return Level Sensor, Ckt2 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4244doc 34245 | Diagnostic: Evaporator Pump 1 Fault | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4245doc 34246 | Diagnostic: Evaporator Pump 2 Fault | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4246doc 34247 | Diagnostic: Evaporator Shell Rfgt Pressure Sensor Ckt1 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4247doc 34248 | Diagnostic: Evaporator Shell Rfgt Pressure Sensor Ckt2 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4248doc 34249 | Diagnostic: Evaporator Water Flow Lost | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4249doc 34250 | Diagnostic: Evaporator Water Flow Lost Pump1 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4250doc 34251 | Diagnostic: Evaporator Water Flow Lost Pump2 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4251doc 34252 | Diagnostic: Evaporator Water Flow Overdue | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4252doc 34253 | Diagnostic: Evaporator Water Flow Overdue Pump1 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4253doc 34254 | Diagnostic: Evaporator Water Flow Overdue Pump2 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4254doc 34255 | Diagnostic: Excessive Condenser Pressure Ckt2 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4255doc 34256 | Diagnostic: Excessive Condenser Pressure Ckt1 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4256doc 34257 | Diagnostic: External Chilled/Hot Water Setpoint | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4257doc 34258 | Diagnostic: External Demand Limit Setpoint | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4258doc 34259 | Diagnostic: EXV Pressure Equalization Failed Ckt1 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4259doc 34260 | Diagnostic: EXV Pressure Equalization Failed Ckt2 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4260doc 34261 | Diagnostic: Fan Inverter Fault Ckt1 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4261doc 34262 | Diagnostic: Fan Inverter Fault Ckt2 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4262doc 34263 | Diagnostic: Heat Recovery Entering Water Temp Sensor | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4263doc 34264 | Diagnostic: Heat Recovery Leaving Water Temp Sensor | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4264doc 34265 | Diagnostic: GP4Vvi High Cprsr Rfgt Discharge Temp 1A | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4265doc 34266 | Diagnostic: High Cprsr Rfgt Discharge Temp 1A | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4266doc 34267 | Diagnostic: High Cprsr Rfgt Discharge Temp 1B | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4267doc 34268 | Diagnostic: GP4Vvi High Cprsr Rfgt Discharge Temp 2A | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4268doc 34269 | Diagnostic: High Cprsr Rfgt Discharge Temp 2A | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4269doc 34270 | Diagnostic: High Cprsr Rfgt Discharge Temp 2B | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4270doc 34271 | Diagnostic: High Differential Refrigerant Pressure | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4271doc 34272 | Diagnostic: High Differential Rfgt Pressure 1A | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4272doc 34273 | Diagnostic: High Differential Rfgt Pressure 1B | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4273doc 34274 | Diagnostic: High Differential Rfgt Pressure 2A | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4274doc 34275 | Diagnostic: High Differential Rfgt Pressure 2B | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4275doc 34276 | Diagnostic: High Evap Shell Rfgt Pressure Ckt1 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4276doc 34277 | Diagnostic: High Evap Shell Rfgt Pressure Ckt2 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4277doc 34278 | Diagnostic: High Evaporator Water Temperature | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4278doc 34279 | Diagnostic: High Motor Winding Temperature 1A | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4279doc 34280 | Diagnostic: High Motor Winding Temperature 2A | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4280doc 34281 | Diagnostic: High Motor Winding Temperature Cprsr1A | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4281doc 34282 | Diagnostic: High Motor Winding Temperature Cprsr2A | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4282doc 34283 | Diagnostic: High Oil Temperature Ckt1 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4283doc 34284 | Diagnostic: High Oil Temperature Ckt2 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4284doc 34285 | Diagnostic: High Pressure Cutout Ckt2 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4285doc 34286 | Diagnostic: High Pressure Cutout Ckt1 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4286doc 34287 | Diagnostic: High Pressure Cutout 1A | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4287doc 34288 | Diagnostic: High Pressure Cutout 1B | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4288doc 34289 | Diagnostic: High Pressure Cutout 2A | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4289doc 34290 | Diagnostic: High Pressure Cutout 2B | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4290doc 34291 | Diagnostic: High Refrigerant Pressure Ratio | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4291doc 34292 | Diagnostic: High Refrigerant Pressure Ratio 1A | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4292doc 34293 | Diagnostic: High Refrigerant Pressure Ratio 1B | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4293doc 34294 | Diagnostic: High Refrigerant Pressure Ratio 2A | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4294doc 34295 | Diagnostic: High Refrigerant Pressure Ratio 2B | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4295doc 34296 | Diagnostic: Inverted Evaporator Water Temperature | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4296doc 34297 | Diagnostic: Liquid Line Pressure Sensor Ckt1 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4297doc 34298 | Diagnostic: Liquid Line Pressure Sensor Ckt2 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4298doc 34299 | Diagnostic: Liquid Line Temp Sensor Ckt1 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4299doc 34300 | Diagnostic: Liquid Line Temp Sensor Ckt2 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4300doc 34301 | Diagnostic: Loss of Oil for Compressor (Running) Ckt1 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4301doc 34302 | Diagnostic: Loss of Oil for Compressor (Running) Ckt2 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4302doc 34303 | Diagnostic: Loss of Oil for Compressor (Stopped) Ckt1 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4303doc 34304 | Diagnostic: Loss of Oil for Compressor (Stopped) Ckt2 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4304doc 34305 | Diagnostic: Low Condenser Rfgt Temp Ckt 1: Unit Off | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4305doc 34306 | Diagnostic: Low Condenser Rfgt Temp Ckt 2: Unit Off | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4306doc 34307 | Diagnostic: Low Differential Rfgt Pressure 1A | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4307doc 34308 | Diagnostic: Low Differential Rfgt Pressure 1B | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4308doc 34309 | Diagnostic: Low Differential Rfgt Pressure 2A | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4309doc 34310 | Diagnostic: Low Differential Rfgt Pressure 2B | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4310doc 34311 | Diagnostic: Low Discharge Superheat 1A | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4311doc 34312 | Diagnostic: Low Discharge Superheat 1B | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4312doc 34313 | Diagnostic: Low Discharge Superheat 2A | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4313doc 34314 | Diagnostic: Low Discharge Superheat 2B | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4314doc 34315 | Diagnostic: Low Evaporator Oil Return Level Ckt1 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4315doc 34316 | Diagnostic: Low Evaporator Oil Return Level Ckt2 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4316doc 34317 | Diagnostic: Low Evaporator Refrigerant Pressure Ckt1 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4317doc 34318 | Diagnostic: Low Evaporator Refrigerant Pressure Ckt2 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4318doc 34319 | Diagnostic: Low Evaporator Rfgt Temp Ckt 1: Unit Off | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4319doc 34320 | Diagnostic: Low Evaporator Rfgt Temp Ckt 2: Unit Off | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4320doc 34321 | Diagnostic: Low Evaporator Water Temp (Unit Off) | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4321doc 34322 | Diagnostic: Low Evaporator Water Temp (Unit On) | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4322doc 34323 | Diagnostic: Low Oil Flow 1A | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4323doc 34324 | Diagnostic: Low Oil Flow 1B | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4324doc 34325 | Diagnostic: Low Oil Flow 2A | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4325doc 34326 | Diagnostic: Low Oil Flow 2B | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4326doc 34327 | Diagnostic: Low Refrigerant Temperature Ckt2 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4327doc 34328 | Diagnostic: Low Refrigerant Temperature Ckt1 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4328doc 34329 | Diagnostic: Mfr Maintenance Recommended 1A | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4329doc 34330 | Diagnostic: Mfr Maintenance Recommended 1B | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4330doc 34331 | Diagnostic: Mfr Maintenance Recommended 2A | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4331doc 34332 | Diagnostic: Mfr Maintenance Recommended 2B | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4332doc 34333 | Diagnostic: Momentary Power Loss 1A | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4333doc 34334 | Diagnostic: Momentary Power Loss 1B | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4334doc 34335 | Diagnostic: Momentary Power Loss 2A | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4335doc 34336 | Diagnostic: Momentary Power Loss 2B | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4336doc 34337 | Diagnostic: Motor Current Overload 1A | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4337doc 34338 | Diagnostic: Motor Current Overload 1B | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4338doc 34339 | Diagnostic: Motor Current Overload 2A | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4339doc 34340 | Diagnostic: Motor Current Overload 2B | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4340doc 34341 | Diagnostic: Motor Winding Temp Sensor Cprsr1A | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4341doc 34342 | Diagnostic: Motor Winding Temp Sensor Cprsr2A | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4342doc 34343 | Diagnostic: MP: Invalid Configuration | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4343doc 34344 | Diagnostic: MP: Non-Volatile Block Test Error | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4344doc 34345 | Diagnostic: MP: Reset Has Occurred | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4345doc 34346 | Diagnostic: Need Cprsr 1A To Run For Oil Flow | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4346doc 34347 | Diagnostic: No Differential Rfgt Pressure 1A | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4347doc 34348 | Diagnostic: No Differential Rfgt Pressure 1B | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4348doc 34349 | Diagnostic: No Differential Rfgt Pressure 2A | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4349doc 34350 | Diagnostic: No Differential Rfgt Pressure 2B | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4350doc 34351 | Diagnostic: Oil Analysis Recommended Ckt1 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4351doc 34352 | Diagnostic: Oil Analysis Recommended Ckt2 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4352doc 34353 | Diagnostic: Oil Filter Change Recommended Cprsr1A | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4353doc 34354 | Diagnostic: Oil Filter Change Recommended Cprsr2A | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4354doc 34355 | Diagnostic: Oil Flow Protection Fault 1A | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4355doc 34356 | Diagnostic: Oil Flow Protection Fault 1B | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4356doc 34357 | Diagnostic: Oil Flow Protection Fault 2A | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4357doc 34358 | Diagnostic: Oil Flow Protection Fault 2B | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4358doc 34359 | Diagnostic: Oil Pressure Sensor 1A | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4359doc 34360 | Diagnostic: Oil Pressure Sensor 1B | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4360doc 34361 | Diagnostic: Oil Pressure Sensor 2A | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4361doc 34362 | Diagnostic: Oil Pressure Sensor 2B | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4362doc 34363 | Diagnostic: Oil Temperature Sensor, Circuit 1 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4363doc 34364 | Diagnostic: Oil Temperature Sensor, Circuit 2 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4364doc 34365 | Diagnostic: Outdoor Air Temperature Sensor | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4365doc 34366 | Diagnostic: Over Voltage | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4366doc 34367 | Diagnostic: Over Voltage 1A | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4367doc 34368 | Diagnostic: Over Voltage 2A | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4368doc 34369 | Diagnostic: Phase Loss 1A | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4369doc 34370 | Diagnostic: Phase Loss 1B | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4370doc 34371 | Diagnostic: Phase Loss 2A | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4371doc 34372 | Diagnostic: Phase Loss 2B | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4372doc 34373 | Diagnostic: Phase Reversal 1A | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4373doc 34374 | Diagnostic: Phase Reversal 1B | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4374doc 34375 | Diagnostic: Phase Reversal 2A | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4375doc 34376 | Diagnostic: Phase Reversal 2B | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4376doc 34377 | Diagnostic: Power Loss 1A | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4377doc 34378 | Diagnostic: Power Loss 1B | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4378doc 34379 | Diagnostic: Power Loss 2A | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4379doc 34380 | Diagnostic: Power Loss 2B | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4380doc 34381 | Diagnostic: Pumpdown Terminated Ckt1 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4381doc 34382 | Diagnostic: Pumpdown Terminated Ckt2 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4382doc 34383 | Diagnostic: Pumpdown Terminated By Time Ckt2 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4383doc 34384 | Diagnostic: Pumpdown Terminated By Time Ckt1 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4384doc 34385 | Diagnostic: Refrigerant Charge Loss Detected Ckt1 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4385doc 34386 | Diagnostic: Refrigerant Charge Loss Detected Ckt2 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4386doc 34387 | Diagnostic: Restart Inhibit Invoked 1A | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4387doc 34388 | Diagnostic: Restart Inhibit Invoked 1B | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4388doc 34389 | Diagnostic: Restart Inhibit Invoked 2A | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4389doc 34390 | Diagnostic: Restart Inhibit Invoked 2B | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4390doc 34391 | Diagnostic: Severe Current Imbalance 1A | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4391doc 34392 | Diagnostic: Severe Current Imbalance 1B | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4392doc 34393 | Diagnostic: Severe Current Imbalance 2A | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4393doc 34394 | Diagnostic: Severe Current Imbalance 2B | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4394doc 34395 | Diagnostic: Software Error 1001: Call Trane Service | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4395doc 34396 | Diagnostic: Software Error 1002: Call Trane Service | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4396doc 34397 | Diagnostic: Software Error 1003: Call Trane Service | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4397doc 34398 | Diagnostic: Starter Comm Loss: Main Processor 1A | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4398doc 34399 | Diagnostic: Starter Comm Loss: Main Processor 1B | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4399doc 34400 | Diagnostic: Starter Comm Loss: Main Processor 2A | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4400doc 34401 | Diagnostic: Starter Comm Loss: Main Processor 2B | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4401doc 34402 | Diagnostic: Starter Contactor Interrupt Failure 1A | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4402doc 34403 | Diagnostic: Starter Contactor Interrupt Failure 1B | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4403doc 34404 | Diagnostic: Starter Contactor Interrupt Failure 2A | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4404doc 34405 | Diagnostic: Starter Contactor Interrupt Failure 2B | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4405doc 34406 | Diagnostic: Starter Did Not Fully Accelerate 1B | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4406doc 34407 | Diagnostic: Starter Did Not Fully Accelerate 1A | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4407doc 34408 | Diagnostic: Starter Did Not Fully Accelerate 2B | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4408doc 34409 | Diagnostic: Starter Did Not Transition 1A | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4409doc 34410 | Diagnostic: Starter Did Not Transition 1B | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4410doc 34411 | Diagnostic: Starter Did Not Transition 2A | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4411doc 34412 | Diagnostic: Starter Did Not Transition 2B | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4412doc 34413 | Diagnostic: Starter Dry Run Test 1A | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4413doc 34414 | Diagnostic: Starter Dry Run Test 1B | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4414doc 34415 | Diagnostic: Starter Dry Run Test 2A | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4415doc 34416 | Diagnostic: Starter Dry Run Test 2B | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4416doc 34417 | Diagnostic: Starter Failed to Arm/Start 1A | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4417doc 34418 | Diagnostic: Starter Failed to Arm/Start 1B | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4418doc 34419 | Diagnostic: Starter Failed to Arm/Start 2A | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4419doc 34420 | Diagnostic: Starter Failed to Arm/Start 2B | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4420doc 34421 | Diagnostic: Starter Fault Type I 1A | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4421doc 34422 | Diagnostic: Starter Fault Type I 1B | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4422doc 34423 | Diagnostic: Starter Fault Type I 2A | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4423doc 34424 | Diagnostic: Starter Fault Type I 2B | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4424doc 34425 | Diagnostic: Starter Fault Type II 1A | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4425doc 34426 | Diagnostic: Starter Fault Type II 1B | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4426doc 34427 | Diagnostic: Starter Fault Type II 2A | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4427doc 34428 | Diagnostic: Starter Fault Type II 2B | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4428doc 34429 | Diagnostic: Starter Fault Type III 1A | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4429doc 34430 | Diagnostic: Starter Fault Type III 1B | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4430doc 34431 | Diagnostic: Starter Fault Type III 2A | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4431doc 34432 | Diagnostic: Starter Fault Type III 2B | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4432doc 34433 | Diagnostic: Starter Module Memory Error Type 1 1A | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4433doc 34434 | Diagnostic: Starter Module Memory Error Type 1 1B | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4434doc 34435 | Diagnostic: Starter Module Memory Error Type 1 2A | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4435doc 34436 | Diagnostic: Starter Module Memory Error Type 1 2B | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4436doc 34437 | Diagnostic: Starter Module Memory Error Type 2 1A | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4437doc 34438 | Diagnostic: Starter Module Memory Error Type 2 1B | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4438doc 34439 | Diagnostic: Starter Module Memory Error Type 2 2A | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4439doc 34440 | Diagnostic: Starter Module Memory Error Type 2 2B | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4440doc 34441 | Diagnostic: Starts/Hours Modified 1A | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4441doc 34442 | Diagnostic: Starts/Hours Modified 1B | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4442doc 34443 | Diagnostic: Starts/Hours Modified 2A | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4443doc 34444 | Diagnostic: Starts/Hours Modified 2B | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4444doc 34445 | Diagnostic: Suction Pressure Transducer Ckt2 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4445doc 34446 | Diagnostic: Suction Pressure Transducer Ckt1 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4446doc 34447 | Diagnostic: Suction Refrigerant Pressure Sensor 1A | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4447doc 34448 | Diagnostic: Suction Refrigerant Pressure Sensor 1B | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4448doc 34449 | Diagnostic: Suction Refrigerant Pressure Sensor 2A | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4449doc 34450 | Diagnostic: Suction Refrigerant Pressure Sensor 2B | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4450doc 34451 | Diagnostic: Suction Temperature Sensor | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4451doc 34452 | Diagnostic: Transition Complete Input Opened 1A | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4452doc 34453 | Diagnostic: Transition Complete Input Opened 1B | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4453doc 34454 | Diagnostic: Transition Complete Input Opened 2A | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4454doc 34455 | Diagnostic: Transition Complete Input Opened 2B | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4455doc 34456 | Diagnostic: Transition Complete Input Shorted 1A | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4456doc 34457 | Diagnostic: Transition Complete Input Shorted 1B | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4457doc 34458 | Diagnostic: Transition Complete Input Shorted 2A | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4458doc 34459 | Diagnostic: Transition Complete Input Shorted 2B | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4459doc 34460 | Diagnostic: Under Voltage | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4460doc 34461 | Diagnostic: Under Voltage 1A | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4461doc 34462 | Diagnostic: Under Voltage 2A | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4462doc 34463 | Diagnostic: Unexpected Starter Shutdown 1A | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4463doc 34464 | Diagnostic: Unexpected Starter Shutdown 1B | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4464doc 34465 | Diagnostic: Unexpected Starter Shutdown 2A | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4465doc 34466 | Diagnostic: Unexpected Starter Shutdown 2B | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4466doc 34467 | Diagnostic: Very Low Discharge Superheat 1A | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4467doc 34468 | Diagnostic: Very Low Discharge Superheat 2A | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4468doc 34469 | Diagnostic: Very Low Evap Rfgt Pressure 1A | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4469doc 34470 | Diagnostic: Very Low Evap Rfgt Pressure 1B | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4470doc 34471 | Diagnostic: Very Low Evap Rfgt Pressure 2A | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4471doc 34472 | Diagnostic: Very Low Evap Rfgt Pressure 2B | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4472doc 34473 | Diagnostic: Water System Differential Pressure | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4473doc 34474 | Diagnostic: Energy Meter Write Value Failure | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4474doc 34475 | Diagnostic: Write Command Failure Energy Meter 1 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4475doc 34476 | Diagnostic: Write Command Failure Energy Meter 2 | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4476doc 34477 | Diagnostic: High Evaporator Pressure | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| IR | 4477doc 34478 | Comm Loss: Starter Panel High Temperature Limit | Diagnostic flag. | UINT16 | Read | 0 = Normal; 1 = In Alarm | |||
| HR | 10doc 40011 | Chilled Water Setpoint | Temperature in the factory unit system (I-P or SI). | FLOAT32 | ABCD | Read/write | |||
| HR | 12doc 40013 | Demand Limit Setpoint | FLOAT32 | ABCD | % | Read/write | |||
| HR | 14doc 40015 | Hot Water Setpoint | Temperature in the factory unit system (I-P or SI). Needs: Hot Water Control | FLOAT32 | ABCD | Read/write | |||
| HR | 16doc 40017 | BAS Cooling Differential to Start | Temperature difference, factory unit system (I-P or SI). | FLOAT32 | ABCD | Read/write | |||
| HR | 18doc 40019 | BAS Cooling Differential to Stop | Temperature difference, factory unit system (I-P or SI). | FLOAT32 | ABCD | Read/write | |||
| HR | 20doc 40021 | BAS Heating Differential to Start | Temperature difference, factory unit system (I-P or SI). Needs: Hot Water Control | FLOAT32 | ABCD | Read/write | |||
| HR | 22doc 40023 | BAS Heating Differential to Stop | Temperature difference, factory unit system (I-P or SI). Needs: Hot Water Control | FLOAT32 | ABCD | Read/write | |||
| HR | 2010doc 42011 | Chiller Mode Command BAS | UINT16 | Read/write | 1 = Cool; 2 = Heat; 3 = Ice Making; 4 = Free Cooling |
Notes on this map
- Register format table: analog points are 32-bit floats sent high word / high byte first (NaN = invalid); binary and multi-state points are unsigned 16-bit integers (0xFFFF = invalid).
- Values are sent in the unit system ordered from the factory (I-P is the usual default, SI optional); the list names only the quantity, so temperature/pressure/flow units are left blank here.
- Not every point exists on every unit: the controller builds its point set from the unit's configuration. Descriptions name the configuration a point depends on.
- Register numbers are printed in 5-digit Modicon form (3xxxx input registers, 4xxxx holding registers) and converted here to wire addresses (30011 = input register 10).
- Controller setup and the I-P/SI units statement come from Trane's Symbio 800 integration guide BAS-SVP047B-EN (Sept 2023, https://elibrary.tranetechnologies.com/public/commercial-hvac/Literature/Integration/BAS-SVP047B-EN_09092023.pdf), which describes the same Symbio 800 controller.
- Left out: the Modbus Binary Values page (BAS commands such as Chiller Auto Stop Command BAS and Reset Diagnostic). The list prints them with 33011-33022, the same numbers as the binary inputs, so their real holding-register numbers are not stated.
- Running time values are described in the list as seconds; units are left blank because the units column says 'No Units'.
- The list skips 30023.
Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.
Questions about the Trane Series R RTWD water-cooled helical-rotary chiller (Symbio 800)
What Modbus registers does the Trane Series R RTWD water-cooled helical-rotary chiller (Symbio 800) have?
This map lists 673 registers: 665 input registers, 8 holding registers. 8 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.
Are the Trane Series R RTWD water-cooled helical-rotary chiller (Symbio 800) Modbus addresses 0-based or 1-based?
The manufacturer's document numbers registers Modicon 3xxxx/4xxxx (drop the prefix, subtract 1). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. The list prints Modicon register numbers: 3xxxx are input registers and 4xxxx holding registers, so 30011 is input register address 10 and 42011 is holding register address 2010.
What byte order does the Trane Series R RTWD water-cooled helical-rotary chiller (Symbio 800) use for 32-bit values?
Multi-register values in this map use ABCD (high word first (big-endian)). Set your client to this order for every 32/64-bit value in the table.
What are the minimum Modbus registers to integrate the Trane Series R RTWD water-cooled helical-rotary chiller (Symbio 800)?
Start with IR 10 Active Cool/Heat Setpoint Temperature (Active cool/heat setpoint); IR 16 Evaporator Leaving Water Temperature (Evaporator leaving water temperature); IR 14 Evaporator Entering Water Temperature (Evaporator entering water temperature); IR 28 Actual Running Capacity (Actual running capacity); IR 2010 Running Mode (Running mode); IR 3010 Run Enable (Run enable); IR 3018 Diagnostic Present (Diagnostic present); HR 10 Chilled Water Setpoint (Chilled water setpoint (BAS)); HR 2010 Chiller Mode Command BAS (BAS chiller mode command).
How do I enable Modbus control of the Trane Series R RTWD water-cooled helical-rotary chiller (Symbio 800)?
On the Symbio 800 web interface go to Installation > Identification and Communications > Protocol Configuration and select Modbus RTU or Modbus TCP (per Trane's Symbio 800 integration guides).
Where is the official Trane Series R RTWD water-cooled helical-rotary chiller (Symbio 800) Modbus documentation?
The source is Symbio 800 Integration Points List, BACnet/Modbus, Series R Model RTWD (BAS-PTS017A-EN), revision 2024-11-15, published free by Trane at https://elibrary.tranetechnologies.com/public/commercial-hvac/Literature/Points%20List/BAS-PTS017A-EN_11152024.pdf.
More Trane Modbus register maps
- Chiller
Trane Agility water-cooled centrifugal chiller (Symbio 800)
Trane Agility water-cooled chillers with Symbio 800 controls, as listed in BAS-PTS007C-EN (6/30/2026).
Also known as: Agility, HDWA, Agility water-cooled chiller - Chiller
Trane Ascend ACR Series C air-cooled chiller (Symbio 800)
Trane Ascend model ACR Series C air-cooled chillers with the Symbio 800 controller, as listed in BAS-PTS021A-EN (11/15/2024).
Also known as: ACR, Ascend ACR, ACR Series C, Ascend air-cooled chiller ACR - Chiller
Trane Ascend ACS / ACX air-cooled scroll chiller and heat pump (Symbio 800)
Trane Ascend ACS air-cooled scroll chillers and ACX air-to-water heat pumps with the Symbio 800 controller, as listed in BAS-PTS011A-EN (11/15/2024).
Also known as: ACS, ACX, Ascend ACS, Ascend ACX, Ascend air-cooled chiller, Ascend air-to-water heat pump - Chiller
Trane CenTraVac CTV-Duplex water-cooled centrifugal chiller (UC800 native Modbus)
Trane Duplex CenTraVac (two-compressor) water-cooled centrifugal chillers with the Tracer UC800 controller, as listed in the Modbus section of BAS-PTS030A-EN (12/6/2024).
Also known as: CTV-Duplex, CTVD, CenTraVac Duplex, Duplex CenTraVac UC800 - Chiller
Trane CenTraVac duplex centrifugal chiller (Symbio 800)
Trane dual-compressor (duplex) CenTraVac water-cooled centrifugal chillers fitted with the Symbio 800 controller, as listed in the Duplex tables of BAS-PTS009C-EN (12/12/2025).
Also known as: CDHF, CDHG, CDHH, CenTraVac Duplex Symbio 800 - Chiller
Trane CenTraVac simplex centrifugal chiller (Symbio 800)
Trane single-compressor (simplex) CenTraVac water-cooled centrifugal chillers fitted with the Symbio 800 controller, as listed in the Simplex tables of BAS-PTS009C-EN (12/12/2025).
Also known as: CVHE, CVHF, CVHG, CVHH, CVHL, CVHM, CVHS, CVGF, CVR, CVZA, CVXA, CenTraVac Simplex Symbio 800, CenTraVac simplex - Chiller
Trane CGAM air-cooled scroll chiller (Symbio 800)
Trane CGAM air-cooled scroll chillers with the Symbio 800 controller, as listed in BAS-PTS019A-EN (11/15/2024).
Also known as: CGAM, Trane CGAM, CGAM air-cooled scroll chiller - Chiller
Trane RTAC air-cooled helical-rotary chiller (Symbio 800)
Trane RTAC air-cooled helical-rotary chillers with the Symbio 800 controller, as listed in BAS-PTS023A-EN (11/8/2024).
Also known as: RTAC, Series R RTAC - Chiller
Trane RTAC air-cooled helical-rotary chiller (UC800 native Modbus profile)
Trane RTAC air-cooled chillers on the Tracer UC800 controller using the UC800 native Modbus map in the Modbus section of BAS-PTS032A-EN (12/6/2024). Not the same register set as the Symbio 800 RTAC list (BAS-PTS023A-EN).
Also known as: RTAC UC800 native Modbus profile, Series R RTAC UC800 native Modbus, BAS-PTS032A-EN - Chiller
Trane Series R RTHD water-cooled helical-rotary chiller (Symbio 800)
Trane Series R model RTHD water-cooled helical-rotary chillers with the Symbio 800 controller, as listed in BAS-PTS015A-EN (11/15/2024).
Also known as: RTHD, Series R RTHD - Chiller
Trane Sintesis RTAF air-cooled screw chiller (Symbio 800)
Trane Sintesis RTAF air-cooled helical-rotary chillers with the Symbio 800 controller, as listed in BAS-PTS013B-EN (4/7/2026).
Also known as: RTAF, Sintesis RTAF, Sintesis air-cooled chiller - Pump (data-centre coolant distribution unit)
Trane TCDU coolant distribution unit (data-centre liquid cooling)
Trane Coolant Distribution Unit (TCDU) for direct-to-chip liquid cooling, as documented in IOM DC-SVX001A-EN (April 2025).
Also known as: TCDU, Trane CDU, Trane Coolant Distribution Unit, DC-SVX001A - Sensor (refrigerant leak monitor for chiller plant rooms)
Trane TruSense RMWH refrigerant monitor (up to 16 points)
Trane TruSense RMWH multipoint photoacoustic refrigerant monitor with Modbus RTU selected, per IOM PART-SVX008A-EN (30 Sep 2025, preliminary).
Also known as: TruSense, RMWH, Trane refrigerant monitor, PART-SVX008A, RMWH-SVX001
Other chillers & heat pumps register maps
- Chiller (air-cooled)
Daikin Applied EWAT-B / EWAFT-B / EWAT-C / EWAFT-C air-cooled inverter chillers (Microtech 4, ARES software)
EWA(F)T-B and -C air-cooled chillers (F = free-cooling) with a Microtech 4 controller running ARES software, per D-EIGOC00207-24_05EN.
Also known as: EWAT-B, EWAFT-B, EWAT-C, EWAFT-C, EWA(F)T-B-C, EWAT~B, EWAFT~B, Daikin EWAT, ARES - Chiller
Daikin Applied MicroTech II scroll and screw chillers AGZ/ACZ/WGZ/AGS/WGS (Modbus module)
McQuay/Daikin Applied AGZ air-cooled and WGZ water-cooled global scroll chillers, ACZ scroll condensing units, and AGS/WGS global screw chillers with the MicroTech II controller and Modbus Communication Module, per ED 15063-2 (Dec 2005).
Also known as: AGZ-A, AGZ-B, ACZ-A, ACZ-B, WGZ, AGS-B, AGS-C, WGS, AGZ, ACZ, AGS, McQuay global scroll Modbus, McQuay global screw Modbus, ED 15063 - Chiller (refrigerant chiller for Liebert XD rack cooling)
Vertiv Liebert XDC refrigerant chiller for XD systems with iCOM v4 (IntelliSlot Modbus)
Liebert XDC units (the compressorised refrigerant chiller that feeds Liebert XD rack and ceiling cooling modules) on the iCOM v4 controller with a Liebert IntelliSlot Modbus card.
Also known as: Liebert XDC, XDC, Liebert XD chiller - Chiller (water-cooled, magnetic-bearing centrifugal)
Daikin Applied Magnitude WME magnetic-bearing chiller (MicroTech, Modbus)
Magnitude WME C- and D-vintage and WME-C QUAD chillers with the MicroTech unit controller and Modbus communication module, per ED 19111-4.
Also known as: WME-C, WME-D, WME-C QUAD, Magnitude WME, Daikin WME - Chiller
Daikin Applied Trailblazer AGZ-D / AGZ-E air-cooled scroll chiller (MicroTech controller)
Daikin Applied Trailblazer AGZ-D and AGZ-E air-cooled scroll chillers with the MicroTech chiller unit controller and Modbus communication module, per ED 15121-13.
Also known as: AGZ-D, AGZ-E, AGZ D-Vintage, AGZ E-Vintage, ED 15121, Trailblazer AGZ-D, Trailblazer AGZ-E - Chiller (water-cooled)
Daikin Applied EWWD-VZ / EWWH-VZ / EWWS-VZ water-cooled inverter screw chillers (Microtech, Adam software)
EWWD-VZ, EWWH-VZ and EWWS-VZ water-cooled inverter screw chillers with Microtech III or Microtech 4 controller running Adam software, per D-EIGOC00201-22_03EN.
Also known as: EWWD-VZ, EWWH-VZ, EWWS-VZ, EWWD(H)(S)_VZ, EWWD~VZ, EWWH~VZ, Daikin EWWD VZ, Adam
All chillers & heat pumps Modbus register maps →
Source: Symbio 800 Integration Points List, BACnet/Modbus, Series R Model RTWD · BAS-PTS017A-EN · rev. 2024-11-15. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.