Chiller · Modbus register map

Trane Series R RTWD water-cooled helical-rotary chiller (Symbio 800) Modbus register map

Updated 19 November 2026

Short answer

Trane's Series R RTWD is a water-cooled helical-rotary (screw) chiller. Its Symbio 800 controller serves BACnet and Modbus RTU/TCP from one points list. This map covers the analog inputs (setpoints, water and refrigerant temperatures and pressures, starts and running time, starter values), BAS setpoints, binary status points, multi-state modes and the diagnostic flags.

This page lists 673 Modbus registers for the Trane Series R RTWD water-cooled helical-rotary chiller (Symbio 800) — 8 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Trane’s own free documentation (linked below) and checked against it.

Manufacturer
Trane
Model
Series R RTWD water-cooled helical-rotary chiller (Symbio 800)
Equipment type
Chiller
Registers
673 (8 writable)
Transport
Modbus RTU, Modbus TCP
Default unit ID
Not stated
Documented addressing
Modicon 3xxxx/4xxxx (drop the prefix, subtract 1)
32-bit word order
ABCD high word first (big-endian)
Also known as
RTWD, Series R RTWD, RTUD
Source document
Symbio 800 Integration Points List, BACnet/Modbus, Series R Model RTWD · BAS-PTS017A-EN · rev. 2024-11-15
Download CSV all columns JSON Manufacturer PDF ↗

Integration notes: Trane Series R RTWD water-cooled helical-rotary chiller (Symbio 800)

Integration in brief

Read the analog inputs as pairs of input registers (float, high word first) and the binary/multi-state points as single registers. Write the BAS setpoints and command points in the 4xxxx holding range.

Minimum registers to map

Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.

RegisterNameTypeWhyAccess
IR 10Active Cool/Heat Setpoint TemperatureFLOAT32 ABCDActive cool/heat setpointRead
IR 16Evaporator Leaving Water TemperatureFLOAT32 ABCDEvaporator leaving water temperatureRead
IR 14Evaporator Entering Water TemperatureFLOAT32 ABCDEvaporator entering water temperatureRead
IR 28Actual Running CapacityFLOAT32 ABCDActual running capacityRead
IR 2010Running ModeUINT16Running modeRead
IR 3010Run EnableUINT16Run enableRead
IR 3018Diagnostic PresentUINT16Diagnostic presentRead
HR 10Chilled Water SetpointFLOAT32 ABCDChilled water setpoint (BAS)Read/write
HR 2010Chiller Mode Command BASUINT16BAS chiller mode commandRead/write

Enable Modbus control & writes

On the Symbio 800 web interface go to Installation > Identification and Communications > Protocol Configuration and select Modbus RTU or Modbus TCP (per Trane's Symbio 800 integration guides).

Byte order & addressing

Network setup

Watch out for

Trane Series R RTWD water-cooled helical-rotary chiller (Symbio 800) Modbus registers

Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.

673 of 673 shown
Trane Series R RTWD water-cooled helical-rotary chiller (Symbio 800) Modbus register map
TableAddressNameDescriptionTypeOrderScaleUnitsAccessValues / bits
IR10doc 30011Active Cool/Heat Setpoint TemperatureTemperature in the factory unit system (I-P or SI).FLOAT32ABCDRead
IR12doc 30013Active Demand Limit SetpointFLOAT32ABCD%Read
IR14doc 30015Evaporator Entering Water TemperatureTemperature in the factory unit system (I-P or SI).FLOAT32ABCDRead
IR16doc 30017Evaporator Leaving Water TemperatureTemperature in the factory unit system (I-P or SI).FLOAT32ABCDRead
IR18doc 30019Outdoor Air TemperatureTemperature in the factory unit system (I-P or SI).FLOAT32ABCDRead
IR20doc 30021Number of CircuitsFLOAT32ABCDRead
IR24doc 30025Number of Compressors, Circuit 1FLOAT32ABCDRead
IR26doc 30027Number of Compressors, Circuit 2FLOAT32ABCDRead
IR28doc 30029Actual Running CapacityFLOAT32ABCD%Read
IR30doc 30031Evaporator Refrigerant Absolute Pressure Circuit 1Pressure in the factory unit system (I-P or SI).FLOAT32ABCDRead
IR32doc 30033Condenser Refrigerant Absolute Pressure Circuit 1Pressure in the factory unit system (I-P or SI).FLOAT32ABCDRead
IR34doc 30035Differential Refrigerant Pressure Ckt1Pressure in the factory unit system (I-P or SI).FLOAT32ABCDRead
IR36doc 30037Evaporator Shell Refrigerant Pressure Ckt1Pressure in the factory unit system (I-P or SI). Needs: Evaporator Isolation ValvesFLOAT32ABCDRead
IR38doc 30039Evaporator Saturated Rfgt Temp Ckt1Temperature in the factory unit system (I-P or SI).FLOAT32ABCDRead
IR40doc 30041Condenser Saturated Rfgt Temp Ckt1Temperature in the factory unit system (I-P or SI).FLOAT32ABCDRead
IR42doc 30043Discharge Temperature Cprsr1ATemperature in the factory unit system (I-P or SI).FLOAT32ABCDRead
IR44doc 30045Oil Absolute Pressure Cprsr1APressure in the factory unit system (I-P or SI). Needs: Compressor 1AFLOAT32ABCDRead
IR46doc 30047Starts Cprsr1ANeeds: Compressor 1AFLOAT32ABCDRead
IR48doc 30049Running Time Cprsr1ANeeds: Compressor 1AFLOAT32ABCDRead
IR50doc 30051Evaporator Refrigerant Absolute Pressure Circuit 2Pressure in the factory unit system (I-P or SI).FLOAT32ABCDRead
IR52doc 30053Condenser Refrigerant Absolute Pressure Circuit 2Pressure in the factory unit system (I-P or SI).FLOAT32ABCDRead
IR54doc 30055Differential Refrigerant Pressure Ckt2Pressure in the factory unit system (I-P or SI).FLOAT32ABCDRead
IR56doc 30057Evaporator Shell Refrigerant Pressure Ckt2Pressure in the factory unit system (I-P or SI). Needs: Evaporator Isolation ValvesFLOAT32ABCDRead
IR58doc 30059Evaporator Saturated Rfgt Temp Ckt2Temperature in the factory unit system (I-P or SI).FLOAT32ABCDRead
IR60doc 30061Condenser Saturated Rfgt Temp Ckt2Temperature in the factory unit system (I-P or SI).FLOAT32ABCDRead
IR62doc 30063Compressor Suction TemperatureTemperature in the factory unit system (I-P or SI). Needs: RTSFFLOAT32ABCDRead
IR64doc 30065Discharge Temperature Cprsr2ATemperature in the factory unit system (I-P or SI). Needs: Compressor 2AFLOAT32ABCDRead
IR66doc 30067Oil Absolute Pressure Cprsr2APressure in the factory unit system (I-P or SI). Needs: Compressor 2AFLOAT32ABCDRead
IR68doc 30069Discharge Temperature Cprsr1BTemperature in the factory unit system (I-P or SI). Needs: Compressor 1BFLOAT32ABCDRead
IR70doc 30071Oil Absolute Pressure Cprsr1BPressure in the factory unit system (I-P or SI). Needs: Compressor 1BFLOAT32ABCDRead
IR72doc 30073Starts Cprsr1BNeeds: Compressor 1BFLOAT32ABCDRead
IR74doc 30075Running Time Cprsr1BNeeds: Compressor 1BFLOAT32ABCDRead
IR76doc 30077Starts Cprsr2ANeeds: Compressor 2AFLOAT32ABCDRead
IR78doc 30079Running Time Cprsr2ANeeds: Compressor 2AFLOAT32ABCDRead
IR80doc 30081Discharge Temperature Cprsr2BTemperature in the factory unit system (I-P or SI). Needs: Compressor 2BFLOAT32ABCDRead
IR82doc 30083Oil Absolute Pressure Cprsr2BPressure in the factory unit system (I-P or SI). Needs: Compressor 2BFLOAT32ABCDRead
IR84doc 30085Starts Cprsr2BNeeds: Compressor 2BFLOAT32ABCDRead
IR86doc 30087Running Time Cprsr2BNeeds: Compressor 2BFLOAT32ABCDRead
IR88doc 30089Motor Voltage AB Starter 1AVoltage. Needs: Line Voltage SensingFLOAT32ABCDRead
IR90doc 30091Motor Voltage AB Starter 1BVoltage. Needs: Line Voltage SensingFLOAT32ABCDRead
IR92doc 30093Motor Voltage AB Starter 2AVoltage. Needs: Line Voltage SensingFLOAT32ABCDRead
IR94doc 30095Motor Voltage AB Starter 2BVoltage. Needs: Line Voltage SensingFLOAT32ABCDRead
IR96doc 30097Oil Temperature Circuit 1Temperature in the factory unit system (I-P or SI). Needs: Oil CoolerFLOAT32ABCDRead
IR98doc 30099Oil Temperature Circuit 2Temperature in the factory unit system (I-P or SI). Needs: Oil CoolerFLOAT32ABCDRead
IR100doc 30101Condenser Entering Water TemperatureTemperature in the factory unit system (I-P or SI).FLOAT32ABCDRead
IR102doc 30103Condenser Leaving Water TemperatureTemperature in the factory unit system (I-P or SI).FLOAT32ABCDRead
IR104doc 30105Unit Power ConsumptionElectrical power. Needs: Energy MeterFLOAT32ABCDRead
IR106doc 30107Energy Consumption NonResetElectrical energy. Needs: Energy MeterFLOAT32ABCDRead
IR108doc 30109Energy Consumption ResettableElectrical energy. Needs: Energy MeterFLOAT32ABCDRead
IR110doc 30111Motor Current L1 Starter 1ACurrent. Needs: Starter 1AFLOAT32ABCDRead
IR112doc 30113Motor Current L2 Starter 1ACurrent. Needs: Starter 1AFLOAT32ABCDRead
IR114doc 30115Motor Current L3 Starter 1ACurrent. Needs: Starter 1AFLOAT32ABCDRead
IR116doc 30117Motor Current L1 % RLA Starter 1ANeeds: Starter 1AFLOAT32ABCD%Read
IR118doc 30119Motor Current L2 % RLA Starter 1ANeeds: Starter 1AFLOAT32ABCD%Read
IR120doc 30121Motor Current L3 % RLA Starter 1ANeeds: Starter 1AFLOAT32ABCD%Read
IR122doc 30123Motor Current L1 Starter 2ACurrent. Needs: Starter 2AFLOAT32ABCDRead
IR124doc 30125Motor Current L2 Starter 2ACurrent. Needs: Starter 2AFLOAT32ABCDRead
IR126doc 30127Motor Current L3 Starter 2ACurrent. Needs: Starter 2AFLOAT32ABCDRead
IR128doc 30129Motor Current L1 % RLA Starter 2ANeeds: Starter 2AFLOAT32ABCD%Read
IR130doc 30131Motor Current L2 % RLA Starter 2ANeeds: Starter 2AFLOAT32ABCD%Read
IR132doc 30133Motor Current L3 % RLA Starter 2ANeeds: Starter 2AFLOAT32ABCD%Read
IR134doc 30135Motor Current L1 Starter 1BCurrent. Needs: Starter 1BFLOAT32ABCDRead
IR136doc 30137Motor Current L2 Starter 1BCurrent. Needs: Starter 1BFLOAT32ABCDRead
IR138doc 30139Motor Current L3 Starter 1BCurrent. Needs: Starter 1BFLOAT32ABCDRead
IR140doc 30141Motor Current L1 % RLA Starter 1BNeeds: Starter 1BFLOAT32ABCD%Read
IR142doc 30143Motor Current L2 % RLA Starter 1BNeeds: Starter 1BFLOAT32ABCD%Read
IR144doc 30145Motor Current L3 % RLA Starter 1BNeeds: Starter 1BFLOAT32ABCD%Read
IR146doc 30147Motor Current L1 Starter 2BCurrent. Needs: Starter 2BFLOAT32ABCDRead
IR148doc 30149Motor Current L2 Starter 2BCurrent. Needs: Starter 2BFLOAT32ABCDRead
IR150doc 30151Motor Current L3 Starter 2BCurrent. Needs: Starter 2BFLOAT32ABCDRead
IR152doc 30153Motor Current L1 % RLA Starter 2BNeeds: Starter 2BFLOAT32ABCD%Read
IR154doc 30155Motor Current L2 % RLA Starter 2BNeeds: Starter 2BFLOAT32ABCD%Read
IR156doc 30157Motor Current L3 % RLA Starter 2BNeeds: Starter 2BFLOAT32ABCD%Read
IR158doc 30159Motor Current A Cprsr1ACurrent. Needs: GP4 w/Modbus AFD (TR200)FLOAT32ABCDRead
IR160doc 30161Motor Current B Cprsr1ACurrent. Needs: GP4 w/Modbus AFD (TR200)FLOAT32ABCDRead
IR162doc 30163Motor Current C Cprsr1ACurrent. Needs: GP4 w/Modbus AFD (TR200)FLOAT32ABCDRead
IR164doc 30165Motor % RLA A Cprsr1ANeeds: GP4 w/Modbus AFD (TR200)FLOAT32ABCD%Read
IR166doc 30167Motor % RLA B Cprsr1ANeeds: GP4 w/Modbus AFD (TR200)FLOAT32ABCD%Read
IR168doc 30169Motor % RLA C Cprsr1ANeeds: GP4 w/Modbus AFD (TR200)FLOAT32ABCD%Read
IR170doc 30171Motor Current A Cprsr2ACurrent. Needs: GP4 w/Modbus AFD (TR200)FLOAT32ABCDRead
IR172doc 30173Motor Current B Cprsr2ACurrent. Needs: GP4 w/Modbus AFD (TR200)FLOAT32ABCDRead
IR174doc 30175Motor Current C Cprsr2ACurrent. Needs: GP4 w/Modbus AFD (TR200)FLOAT32ABCDRead
IR176doc 30177Motor % RLA A Cprsr2ANeeds: GP4 w/Modbus AFD (TR200)FLOAT32ABCD%Read
IR178doc 30179Motor % RLA B Cprsr2ANeeds: GP4 w/Modbus AFD (TR200)FLOAT32ABCD%Read
IR180doc 30181Motor % RLA C Cprsr2ANeeds: GP4 w/Modbus AFD (TR200)FLOAT32ABCD%Read
IR182doc 30183Average Motor Current % RLA AFD 1ANeeds: Modbus AFD (TR200)FLOAT32ABCD%Read
IR184doc 30185Average Motor Current % RLA AFD 2ANeeds: Modbus AFD (TR200)FLOAT32ABCD%Read
IR186doc 30187Unit Source ID (Last Diagnostic Code)FLOAT32ABCDRead
IR188doc 30189Chiller Design CapacityCooling capacity in the factory unit system (I-P or SI).FLOAT32ABCDRead
IR190doc 30191Active Chilled Water SetpointTemperature in the factory unit system (I-P or SI).FLOAT32ABCDRead
IR192doc 30193Active Hot Water SetpointTemperature in the factory unit system (I-P or SI). Needs: Hot Water ControlFLOAT32ABCDRead
IR194doc 30195Unit Load CommandFLOAT32ABCD%Read
IR196doc 30197Air Flow Percentage Circuit 1Needs: RTUDFLOAT32ABCD%Read
IR198doc 30199Air Flow Percentage Circuit 2Needs: RTUDFLOAT32ABCD%Read
IR200doc 30201Evaporator Refrigerant Pressure Circuit 1Pressure in the factory unit system (I-P or SI).FLOAT32ABCDRead
IR202doc 30203Condenser Refrigerant Pressure Circuit 1Pressure in the factory unit system (I-P or SI).FLOAT32ABCDRead
IR204doc 30205Evaporator Refrigerant Pressure Circuit 2Pressure in the factory unit system (I-P or SI).FLOAT32ABCDRead
IR206doc 30207Condenser Refrigerant Pressure Circuit 2Pressure in the factory unit system (I-P or SI).FLOAT32ABCDRead
IR208doc 30209Condenser Control OutputNeeds: Head Pressure ControlFLOAT32ABCD%Read
IR210doc 30211Oil Pressure Cprsr1APressure in the factory unit system (I-P or SI). Needs: Compressor 1AFLOAT32ABCDRead
IR212doc 30213Oil Pressure Cprsr2APressure in the factory unit system (I-P or SI). Needs: Compressor 2AFLOAT32ABCDRead
IR214doc 30215Oil Pressure Cprsr1BPressure in the factory unit system (I-P or SI). Needs: Compressor 1BFLOAT32ABCDRead
IR216doc 30217Oil Pressure Cprsr2BPressure in the factory unit system (I-P or SI). Needs: Compressor 2BFLOAT32ABCDRead
IR218doc 30219Evaporator Approach Temperature Circuit 1Temperature difference, factory unit system (I-P or SI).FLOAT32ABCDRead
IR220doc 30221Evaporator Approach Temperature Circuit 2Temperature difference, factory unit system (I-P or SI).FLOAT32ABCDRead
IR222doc 30223Condenser Approach Temperature Circuit 1Temperature difference, factory unit system (I-P or SI).FLOAT32ABCDRead
IR224doc 30225Condenser Approach Temperature Circuit 2Temperature difference, factory unit system (I-P or SI).FLOAT32ABCDRead
IR226doc 30227Average Line Current Circuit 1Current. Needs: Two Energy MetersFLOAT32ABCDRead
IR228doc 30229Average Line Current Circuit 2Current. Needs: Two Energy MetersFLOAT32ABCDRead
IR230doc 30231Average Line Voltage Circuit 1Voltage. Needs: Two Energy MetersFLOAT32ABCDRead
IR232doc 30233Average Line Voltage Circuit 2Voltage. Needs: Two Energy MetersFLOAT32ABCDRead
IR234doc 30235Line Current L1 Circuit 1Current. Needs: Two Energy MetersFLOAT32ABCDRead
IR236doc 30237Line Current L2 Circuit 1Current. Needs: Two Energy MetersFLOAT32ABCDRead
IR238doc 30239Line Current L3 Circuit 1Current. Needs: Two Energy MetersFLOAT32ABCDRead
IR240doc 30241Line Current L1 Circuit 2Current. Needs: Two Energy MetersFLOAT32ABCDRead
IR242doc 30243Line Current L2 Circuit 2Current. Needs: Two Energy MetersFLOAT32ABCDRead
IR244doc 30245Line Current L3 Circuit 2Current. Needs: Two Energy MetersFLOAT32ABCDRead
IR246doc 30247Voltage L1-L2 Circuit 1Voltage. Needs: Two Energy MetersFLOAT32ABCDRead
IR248doc 30249Voltage L2-L3 Circuit 1Voltage. Needs: Two Energy MetersFLOAT32ABCDRead
IR250doc 30251Voltage L1-L3 Circuit 1Voltage. Needs: Two Energy MetersFLOAT32ABCDRead
IR252doc 30253Voltage L1-L2 Circuit 2Voltage. Needs: Two Energy MetersFLOAT32ABCDRead
IR254doc 30255Voltage L2-L1 Circuit 2Voltage. Needs: Two Energy MetersFLOAT32ABCDRead
IR256doc 30257Voltage L1-L3 Circuit 2Voltage. Needs: Two Energy MetersFLOAT32ABCDRead
IR258doc 30259Line Frequency Circuit 1Needs: Two Energy MetersFLOAT32ABCDRead
IR260doc 30261Line Frequency Circuit 2Needs: Two Energy MetersFLOAT32ABCDRead
IR262doc 30263Power Factor Circuit 1Needs: Two Energy MetersFLOAT32ABCDRead
IR264doc 30265Power Factor Circuit 2Needs: Two Energy MetersFLOAT32ABCDRead
IR266doc 30267Power Demand Circuit 1Electrical power. Needs: Two Energy MetersFLOAT32ABCDRead
IR268doc 30269Power Demand Circuit 2Electrical power. Needs: Two Energy MetersFLOAT32ABCDRead
IR270doc 30271Power FactorNeeds: One Energy MeterFLOAT32ABCDRead
IR272doc 30273Current L1Current. Needs: One Energy MeterFLOAT32ABCDRead
IR274doc 30275Current L2Current. Needs: One Energy MeterFLOAT32ABCDRead
IR276doc 30277Current L3Current. Needs: One Energy MeterFLOAT32ABCDRead
IR278doc 30279Average CurrentCurrent. Needs: One Energy MeterFLOAT32ABCDRead
IR280doc 30281Voltage L1-L2Voltage. Needs: One Energy MeterFLOAT32ABCDRead
IR282doc 30283Voltage L2-L3Voltage. Needs: One Energy MeterFLOAT32ABCDRead
IR284doc 30285Voltage L1-L3Voltage. Needs: One Energy MeterFLOAT32ABCDRead
IR286doc 30287Average Voltage L-LVoltage. Needs: One Energy MeterFLOAT32ABCDRead
IR288doc 30289Line FrequencyNeeds: One Energy MeterFLOAT32ABCDRead
IR290doc 30291Unit Power DemandElectrical power. Needs: Power MonitorFLOAT32ABCDRead
IR292doc 30293Active Cooling Differential to StartTemperature difference, factory unit system (I-P or SI).FLOAT32ABCDRead
IR294doc 30295Active Cooling Differential to StopTemperature difference, factory unit system (I-P or SI).FLOAT32ABCDRead
IR296doc 30297Active Heating Differential to StartTemperature difference, factory unit system (I-P or SI). Needs: Hot Water ControlFLOAT32ABCDRead
IR298doc 30299Active Heating Differential to StopTemperature difference, factory unit system (I-P or SI). Needs: Hot Water ControlFLOAT32ABCDRead
IR2010doc 32011Running ModeUINT16Read1 = Chiller Off; 2 = Chiller In Start Mode; 3 = Chiller In Run Mode; 4 = Chiller In Pre-Shutdown Mode; 5 = Chiller In Service Mode
IR2011doc 32012Operating ModeUINT16Read1 = Cool; 2 = Heat; 3 = Ice Making; 4 = Free Cooling
IR2013doc 32014Refrigerant TypeUINT16Read5 = R-134a; 13 = R-513A; 16 = R-1234ze(E); 18 = R-515B
IR2014doc 32015Manufacturing LocationUINT16Read3 = Pueblo; 4 = Charmes
IR2015doc 32016Cooling TypeUINT16Read1 = Water Cooled; 2 = Air Cooled
IR2016doc 32017Model Information [GEN2]UINT16Read17 = RTWF; 30 = RTSF; 41 = RTWF XSE; 45 = RTWD; 46 = RTUD
IR3010doc 33011Run EnableUINT16Read0 = Run Not Enabled; 1 = Run Enabled
IR3011doc 33012Local Setpoint ControlUINT16Read0 = Remote Control; 1 = Local Control
IR3012doc 33013Limit Mode Relay StatusUINT16Read0 = Off; 1 = On
IR3013doc 33014Chiller Running StateUINT16Read0 = Off; 1 = On
IR3014doc 33015Maximum CapacityUINT16Read0 = Off; 1 = On
IR3015doc 33016Manual Override ExistsUINT16Read0 = Off; 1 = On
IR3016doc 33017Emergency StopUINT16Read0 = Auto; 1 = Emergency Stop - Manual Reset Required
IR3017doc 33018Evaporator Water Flow StatusUINT16Read0 = No Flow; 1 = Flow
IR3018doc 33019Diagnostic PresentUINT16Read0 = Normal; 1 = In Alarm
IR3019doc 33020Diagnostic Shutdown PresentUINT16Read0 = Normal; 1 = In Alarm
IR3020doc 33021Diagnostic: Manual Reset RequiredUINT16Read0 = Normal; 1 = In Alarm
IR3021doc 33022Diagnostic: Local Manual Reset RequiredUINT16Read0 = Normal; 1 = In Alarm
IR3022doc 33023Diagnostic Present: InformationUINT16Read0 = Normal; 1 = In Alarm
IR3023doc 33024Diagnostic Present: AdvisoryUINT16Read0 = Normal; 1 = In Alarm
IR3024doc 33025Diagnostic Present: CriticalUINT16Read0 = Normal; 1 = In Alarm
IR3025doc 33026Diagnostic Present: Service RequiredUINT16Read0 = Normal; 1 = In Alarm
IR3026doc 33027Compressor 1A Running StatusUINT16Read0 = Stop; 1 = Auto
IR3027doc 33028Compressor 1B Running StatusNeeds: Compressor 1BUINT16Read0 = Stop; 1 = Auto
IR3028doc 33029Compressor 2A Running StatusNeeds: Compressor 2AUINT16Read0 = Stop; 1 = Auto
IR3029doc 33030Compressor 2B Running StatusNeeds: Compressor 2BUINT16Read0 = Stop; 1 = Auto
IR3030doc 33031External Auto StopUINT16Read0 = Stop; 1 = Auto
IR3031doc 33032Condenser Water Pump CommandUINT16Read0 = Inactive; 1 = Active
IR3032doc 33033Evaporator Water Pump CommandUINT16Read0 = Off; 1 = On
IR3033doc 33034Condenser Water Flow StatusUINT16Read0 = Inactive; 1 = Active
IR3034doc 33035Front Panel Auto Stop StatusUINT16Read0 = Stop; 1 = Auto
IR3035doc 33036Circuit Manual Reset Indicator (CMR) Ckt1UINT16Read0 = Inactive; 1 = Active
IR3036doc 33037Circuit Manual Reset Indicator (CMR) Ckt2Needs: Circuit 2UINT16Read0 = Inactive; 1 = Active
IR3037doc 33038Circuit Auto Reset Indicator (CAR) Ckt1UINT16Read0 = Inactive; 1 = Active
IR3038doc 33039Circuit Auto Reset Indicator (CAR) Ckt2Needs: Circuit 2UINT16Read0 = Inactive; 1 = Active
IR3039doc 33040Head Pressure Relief RequestUINT16Read0 = Normal; 1 = Locked Out
IR3040doc 33041Alarm - General Latching UnitUINT16Read0 = Normal; 1 = In Alarm
IR3041doc 33042Alarm - General Non Latching UnitUINT16Read0 = Normal; 1 = In Alarm
IR3042doc 33043Alarm - General Latching Ckt1UINT16Read0 = Normal; 1 = In Alarm
IR3043doc 33044Alarm - General Latching Ckt2Needs: Circuit 2UINT16Read0 = Normal; 1 = In Alarm
IR3044doc 33045Alarm - General Non Latching Ckt1UINT16Read0 = Normal; 1 = In Alarm
IR3045doc 33046Alarm - General Non Latching Ckt2Needs: Circuit 2UINT16Read0 = Normal; 1 = In Alarm
IR3046doc 33047Noise Reduction Request ActiveNeeds: Noise ReductionUINT16Read0 = Off; 1 = On
IR4000doc 34001Comm Loss: %RLA Indication Output (Vdc)Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4001doc 34002Comm Loss: AFD 1ADiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4002doc 34003Comm Loss: AFD 2ADiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4003doc 34004Comm Loss: AFD Fault Input 1ADiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4004doc 34005Comm Loss: AFD Fault Input 1BDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4005doc 34006Comm Loss: AFD Fault Input 2ADiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4006doc 34007Comm Loss: AFD Fault Input 2BDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4007doc 34008Comm Loss: AFD Run Command 1ADiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4008doc 34009Comm Loss: AFD Run Command 2ADiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4009doc 34010Comm Loss: AFD Speed Command 1ADiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4010doc 34011Comm Loss: AFD Speed Command 1BDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4011doc 34012Comm Loss: AFD Speed Command 2ADiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4012doc 34013Comm Loss: AFD Speed Command 2BDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4013doc 34014Comm Loss: AOC Inlet Oil Temperature 1ADiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4014doc 34015Comm Loss: AOC Inlet Oil Temperature 2ADiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4015doc 34016Comm Loss: Auxiliary Setpoint CommandDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4016doc 34017Comm Loss: Chiller Bypass Valve OutputDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4017doc 34018Comm Loss: Cond Head Press Cntrl OutputDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4018doc 34019Comm Loss: Cond Rfgt Liquid Level Ckt1Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4019doc 34020Comm Loss: Cond Rfgt Liquid Level Ckt2Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4020doc 34021Comm Loss: Cond Water Pump Analog OutputDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4021doc 34022Comm Loss: Condenser Entering Water TempDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4022doc 34023Comm Loss: Condenser Leaving Water TempDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4023doc 34024Comm Loss: Condenser Rfgt Pressure Ckt2Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4024doc 34025Comm Loss: Condenser Rfgt Pressure Ckt1Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4025doc 34026Comm Loss: Condenser Rfgt Pressure OutputDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4026doc 34027Comm Loss: Condenser Water Flow SwitchDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4027doc 34028Comm Loss: Condenser Water Pump RelayDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4028doc 34029Comm Loss: Cprsr Disch Rfgt Temp 1ADiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4029doc 34030Comm Loss: Cprsr Disch Rfgt Temp 1BDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4030doc 34031Comm Loss: Cprsr Disch Rfgt Temp 2ADiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4031doc 34032Comm Loss: Cprsr Disch Rfgt Temp 2BDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4032doc 34033Comm Loss: Electronic Expansion Valve Ckt1Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4033doc 34034Comm Loss: Electronic Expansion Valve Ckt2Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4034doc 34035Comm Loss: Emergency Stop Feedback InputDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4035doc 34036Comm Loss: Energy Meter Pulse InputDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4036doc 34037Comm Loss: Evap Entering Water PressureDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4037doc 34038Comm Loss: Evap Entering Water TempDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4038doc 34039Comm Loss: Evap Iso Valve Close Switch Ckt1Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4039doc 34040Comm Loss: Evap Iso Valve Close Switch Ckt2Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4040doc 34041Comm Loss: Evap Iso Valve Open Switch Ckt1Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4041doc 34042Comm Loss: Evap Iso Valve Open Switch Ckt2Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4042doc 34043Comm Loss: Evap Isolation Valve Relay Ckt1Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4043doc 34044Comm Loss: Evap Isolation Valve Relay Ckt2Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4044doc 34045Comm Loss: Evap Leaving Water PressureDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4045doc 34046Comm Loss: Evap Leaving Water TempDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4046doc 34047Comm Loss: Evap Oil Return Level Ckt1Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4047doc 34048Comm Loss: Evap Oil Return Level Ckt2Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4048doc 34049Comm Loss: Evap Pump Inv1 Fault InputDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4049doc 34050Comm Loss: Evap Pump Inv1 Run CommandDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4050doc 34051Comm Loss: Evap Rfgt Liquid Level Ckt1Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4051doc 34052Comm Loss: Evap Rfgt Liquid Level Ckt2Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4052doc 34053Comm Loss: Evap Rfgt Pool Temp Ckt1Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4053doc 34054Comm Loss: Evap Rfgt Pool Temp Ckt2Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4054doc 34055Comm Loss: Evap Shell Rfgt Pressure Ckt1Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4055doc 34056Comm Loss: Evap Shell Rfgt Pressure Ckt2Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4056doc 34057Comm Loss: Evap Water Pump Analog OutputDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4057doc 34058Comm Loss: Evap Water Pump Inv Freq InputDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4058doc 34059Comm Loss: Evaporator Pump 1 Fault InputDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4059doc 34060Comm Loss: Evaporator Pump 2 Fault InputDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4060doc 34061Comm Loss: Evaporator Water Flow SwitchDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4061doc 34062Comm Loss: Evaporator Water Pump 1 RelayDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4062doc 34063Comm Loss: Evaporator Water Pump 2 RelayDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4063doc 34064Comm Loss: Ext Chilled/Hot Water SetpointDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4064doc 34065Comm Loss: Ext Demand Limit SetpointDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4065doc 34066Comm Loss: Ext Noise Reduction RequestDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4066doc 34067Comm Loss: External Auto/StopDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4067doc 34068Comm Loss: External Ckt2 LockoutDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4068doc 34069Comm Loss: External Ckt1 LockoutDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4069doc 34070Comm Loss: External Hot Water CommandDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4070doc 34071Comm Loss: External Ice Building CommandDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4071doc 34072Comm Loss: Fan Control Relays, Ckt1Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4072doc 34073Comm Loss: Fan Control Relays, Ckt2Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4073doc 34074Comm Loss: Fan Inverter Fault Ckt1Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4074doc 34075Comm Loss: Fan Inverter Fault Ckt2Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4075doc 34076Comm Loss: Fan Inverter Speed Command Ckt1Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4076doc 34077Comm Loss: Fan Inverter Speed Command Ckt2Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4077doc 34078Comm Loss: High Pressure Cutout Sw 1ADiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4078doc 34079Comm Loss: High Pressure Cutout Sw 1BDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4079doc 34080Comm Loss: High Pressure Cutout Sw 2ADiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4080doc 34081Comm Loss: High Pressure Cutout Sw 2BDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4081doc 34082Comm Loss: High Pressure Cutout Switch Ckt2Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4082doc 34083Comm Loss: High Pressure Cutout Switch Ckt1Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4083doc 34084Comm Loss: HR Entering Water Temp SensorDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4084doc 34085Comm Loss: HR Leaving Water Temp SensorDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4085doc 34086Comm Loss: Ice Building Status RelayDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4086doc 34087Comm Loss: Liquid Line Pressure Ckt1Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4087doc 34088Comm Loss: Liquid Line Pressure Ckt2Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4088doc 34089Comm Loss: Liquid Line Temperature Ckt1Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4089doc 34090Comm Loss: Liquid Line Temperature Ckt2Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4090doc 34091Comm Loss: Motor RLA Input 1ADiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4091doc 34092Comm Loss: Motor RLA Input 1BDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4092doc 34093Comm Loss: Motor RLA Input 2ADiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4093doc 34094Comm Loss: Motor RLA Input 2BDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4094doc 34095Comm Loss: Motor Winding Tstat Cprsr1ADiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4095doc 34096Comm Loss: Motor Winding Tstat Cprsr2ADiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4096doc 34097Comm Loss: Noise Reduction Request Relay Ckt1Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4097doc 34098Comm Loss: Noise Reduction Request Relay Ckt2Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4098doc 34099Comm Loss: Off-cycle Freeze Prot RelayDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4099doc 34100Comm Loss: Oil Heater Relay 1ADiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4100doc 34101Comm Loss: Oil Heater Relay 2ADiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4101doc 34102Comm Loss: Oil Loss Level Sensor Input Ckt1Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4102doc 34103Comm Loss: Oil Loss Level Sensor Input Ckt2Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4103doc 34104Comm Loss: Oil Pressure 1ADiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4104doc 34105Comm Loss: Oil Pressure 1BDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4105doc 34106Comm Loss: Oil Pressure 2ADiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4106doc 34107Comm Loss: Oil Pressure 2BDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4107doc 34108Comm Loss: Oil Return Gas Pump Drain Ckt1Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4108doc 34109Comm Loss: Oil Return Gas Pump Drain Ckt2Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4109doc 34110Comm Loss: Oil Return Gas Pump Fill Ckt1Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4110doc 34111Comm Loss: Oil Return Gas Pump Fill Ckt2Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4111doc 34112Comm Loss: Oil Return Purge Valve Ckt1Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4112doc 34113Comm Loss: Oil Return Purge Valve Ckt2Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4113doc 34114Comm Loss: Oil Temp, Ckt 1Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4114doc 34115Comm Loss: Oil Temp, Ckt 2Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4115doc 34116Comm Loss: Outdoor Air TemperatureDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4116doc 34117Comm Loss: Programmable Relay Board 1Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4117doc 34118Comm Loss: Programmable Relay Board 2Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4118doc 34119Comm Loss: Reversing ValveDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4119doc 34120Comm Loss: Slide Valve Load 1ADiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4120doc 34121Comm Loss: Slide Valve Load 1BDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4121doc 34122Comm Loss: Slide Valve Load 2ADiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4122doc 34123Comm Loss: Slide Valve Load 2BDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4123doc 34124Comm Loss: Slide Valve Unload 1ADiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4124doc 34125Comm Loss: Slide Valve Unload 1BDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4125doc 34126Comm Loss: Slide Valve Unload 2ADiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4126doc 34127Comm Loss: Slide Valve Unload 2BDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4127doc 34128Comm Loss: Starter 1ADiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4128doc 34129Comm Loss: Starter 1BDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4129doc 34130Comm Loss: Starter 2ADiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4130doc 34131Comm Loss: Starter 2BDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4131doc 34132Comm Loss: Step Load 1ADiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4132doc 34133Comm Loss: Step Load 1BDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4133doc 34134Comm Loss: Step Load 2ADiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4134doc 34135Comm Loss: Step Load 2BDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4135doc 34136Comm Loss: Suction Rfgt Pressure Ckt2Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4136doc 34137Comm Loss: Suction Rfgt Pressure Ckt1Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4137doc 34138Comm Loss: Suction Rfgt Pressure 1ADiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4138doc 34139Comm Loss: Suction Rfgt Pressure 1BDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4139doc 34140Comm Loss: Suction Rfgt Pressure 2ADiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4140doc 34141Comm Loss: Suction Rfgt Pressure 2BDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4141doc 34142Comm Loss: Suction TemperatureDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4142doc 34143Comm Loss: Water System Diff PressureDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4143doc 34144Comm Loss: Winding Temp 1, Cprsr1ADiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4144doc 34145Comm Loss: Winding Temp 1, Cprsr2ADiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4145doc 34146Comm Loss: Winding Temp 2, Cprsr1ADiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4146doc 34147Diagnostic: AFD %RLA Feedback 1ADiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4147doc 34148Diagnostic: AFD %RLA Feedback 1BDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4148doc 34149Diagnostic: AFD %RLA Feedback 2ADiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4149doc 34150Diagnostic: AFD %RLA Feedback 2BDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4150doc 34151Diagnostic: AFD Bump Complete 1ADiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4151doc 34152Diagnostic: AFD Bump Complete 2ADiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4152doc 34153Diagnostic: AFD Bump Current High 1ADiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4153doc 34154Diagnostic: AFD Bump Current High 2ADiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4154doc 34155Diagnostic: AFD Comm Loss – 1ADiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4155doc 34156Diagnostic: AFD Comm Loss – 1BDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4156doc 34157Diagnostic: AFD Comm Loss – 2ADiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4157doc 34158Diagnostic: AFD Comm Loss – 2BDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4158doc 34159Diagnostic: AFD Failure to Arm or Start 1ADiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4159doc 34160Diagnostic: AFD Failure to Arm or Start 1BDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4160doc 34161Diagnostic: AFD Failure to Arm or Start 2ADiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4161doc 34162Diagnostic: AFD Failure to Arm or Start 2BDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4162doc 34163Diagnostic: AFD Fault 1ADiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4163doc 34164Diagnostic: AFD Fault 1BDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4164doc 34165Diagnostic: AFD Fault 2ADiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4165doc 34166Diagnostic: AFD Fault 2BDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4166doc 34167Diagnostic: AFD Fault Mains 1ADiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4167doc 34168Diagnostic: AFD Fault Mains 2ADiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4168doc 34169Diagnostic: AFD Harmonic Filter Over Temperature 1ADiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4169doc 34170Diagnostic: AFD Harmonic Filter Over Temperature 2ADiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4170doc 34171Diagnostic: AFD High Pressure Cutout 1ADiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4171doc 34172Diagnostic: AFD High Pressure Cutout 2ADiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4172doc 34173Diagnostic: AFD Interrupt Failure 1ADiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4173doc 34174Diagnostic: AFD Interrupt Failure 2ADiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4174doc 34175Diagnostic: AFD Motor Current Overload 1ADiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4175doc 34176Diagnostic: AFD Motor Current Overload 1BDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4176doc 34177Diagnostic: AFD Motor Current Overload 2ADiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4177doc 34178Diagnostic: AFD Motor Current Overload 2BDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4178doc 34179Diagnostic: AFD Motor Fault 1ADiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4179doc 34180Diagnostic: AFD Motor Fault 2ADiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4180doc 34181Diagnostic: AFD Motor Speed Too High 1ADiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4181doc 34182Diagnostic: AFD Motor Speed Too High 2ADiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4182doc 34183Diagnostic: AFD Motor Speed Too Low 1ADiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4183doc 34184Diagnostic: AFD Motor Speed Too Low 2ADiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4184doc 34185Diagnostic: AFD Pump Out Speed Low 1ADiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4185doc 34186Diagnostic: AFD Pump Out Speed Low 2ADiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4186doc 34187Diagnostic: AFD Unexpected Shutdown 1ADiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4187doc 34188Diagnostic: AFD Unexpected Shutdown 2ADiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4188doc 34189Diagnostic: AFD Unhandled Fault 1ADiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4189doc 34190Diagnostic: AFD Unhandled Fault 2ADiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4190doc 34191Diagnostic: AOC Inlet Oil Temperature Sensor 1ADiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4191doc 34192Diagnostic: AOC Inlet Oil Temperature Sensor 2ADiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4192doc 34193Diagnostic: Check ClockDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4193doc 34194Diagnostic: Chiller Service RecommendedDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4194doc 34195Diagnostic: Comm Loss: Winding Temp 2, Cprsr2ADiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4195doc 34196Diagnostic: Cond Rfgt Liquid Level Sensor Ckt1Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4196doc 34197Diagnostic: Cond Rfgt Liquid Level Sensor Ckt2Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4197doc 34198Diagnostic: Condenser Entering Water Temp SensorDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4198doc 34199Diagnostic: Condenser Leaving Water Temp SensorDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4199doc 34200Diagnostic: Condenser Rfgt Pressure Sensor Ckt2Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4200doc 34201Diagnostic: Condenser Rfgt Pressure Sensor Ckt1Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4201doc 34202Diagnostic: Condenser Water Flow LostDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4202doc 34203Diagnostic: Condenser Water Flow OverdueDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4203doc 34204Diagnostic: Cprsr Did Not Accel: Shutdown 1ADiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4204doc 34205Diagnostic: Cprsr Did Not Accel: Shutdown 1BDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4205doc 34206Diagnostic: Cprsr Did Not Accel: Shutdown 2ADiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4206doc 34207Diagnostic: Cprsr Did Not Accel: Shutdown 2BDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4207doc 34208Diagnostic: Cprsr Did Not Accel: Transition 1ADiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4208doc 34209Diagnostic: Cprsr Did Not Accel: Transition 1BDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4209doc 34210Diagnostic: Cprsr Did Not Accel: Transition 2ADiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4210doc 34211Diagnostic: Cprsr Did Not Accel: Transition 2BDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4211doc 34212Diagnostic: Cprsr Disch Rfgt Temp Sensor 1ADiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4212doc 34213Diagnostic: Cprsr Disch Rfgt Temp Sensor 1BDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4213doc 34214Diagnostic: Cprsr Disch Rfgt Temp Sensor 2ADiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4214doc 34215Diagnostic: Cprsr Disch Rfgt Temp Sensor 2BDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4215doc 34216Diagnostic: Emergency Stop Feedback InputDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4216doc 34217Diagnostic: Evap Iso Valve Illegal Switch State Ckt1Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4217doc 34218Diagnostic: Evap Iso Valve Illegal Switch State Ckt2Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4218doc 34219Diagnostic: Evap Isolation Valve Closed Switch Failure Ckt1Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4219doc 34220Diagnostic: Evap Isolation Valve Closed Switch Failure Ckt2Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4220doc 34221Diagnostic: Evap Isolation Valve Failed To Close Ckt1Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4221doc 34222Diagnostic: Evap Isolation Valve Failed To Close Ckt2Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4222doc 34223Diagnostic: Evap Isolation Valve Failed To Open Ckt1Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4223doc 34224Diagnostic: Evap Isolation Valve Failed To Open Ckt2Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4224doc 34225Diagnostic: Evap Isolation Valve Open Switch Failure Ckt1Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4225doc 34226Diagnostic: Evap Isolation Valve Open Switch Failure Ckt2Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4226doc 34227Diagnostic: Evap Pump 1 Starts Run time WrittenDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4227doc 34228Diagnostic: Evap Pump 2 Starts Run time WrittenDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4228doc 34229Diagnostic: Evap Rfgt Pool Temp Sensor Ckt1Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4229doc 34230Diagnostic: Evap Rfgt Pool Temp Sensor Ckt2Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4230doc 34231Diagnostic: Evap Rfgt Pool Temp Sensor Error Ckt1Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4231doc 34232Diagnostic: Evap Rfgt Pool Temp Sensor Error Ckt2Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4232doc 34233Diagnostic: Evap Spillover Liquid Level Sensor Ckt1Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4233doc 34234Diagnostic: Evap Spillover Liquid Level Sensor Ckt2Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4234doc 34235Diagnostic: Evap Water Pump 1 Svc RecommendedDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4235doc 34236Diagnostic: Evap Water Pump 2 Svc RecommendedDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4236doc 34237Diagnostic: Evaporator Approach Error Ckt2Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4237doc 34238Diagnostic: Evaporator Approach Error Ckt1Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4238doc 34239Diagnostic: Evaporator Entering Water PressureDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4239doc 34240Diagnostic: Evaporator Entering Water Temp SensorDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4240doc 34241Diagnostic: Evaporator Leaving Water PressureDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4241doc 34242Diagnostic: Evaporator Leaving Water Temp SensorDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4242doc 34243Diagnostic: Evaporator Oil Return Level Sensor, Ckt1Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4243doc 34244Diagnostic: Evaporator Oil Return Level Sensor, Ckt2Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4244doc 34245Diagnostic: Evaporator Pump 1 FaultDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4245doc 34246Diagnostic: Evaporator Pump 2 FaultDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4246doc 34247Diagnostic: Evaporator Shell Rfgt Pressure Sensor Ckt1Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4247doc 34248Diagnostic: Evaporator Shell Rfgt Pressure Sensor Ckt2Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4248doc 34249Diagnostic: Evaporator Water Flow LostDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4249doc 34250Diagnostic: Evaporator Water Flow Lost Pump1Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4250doc 34251Diagnostic: Evaporator Water Flow Lost Pump2Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4251doc 34252Diagnostic: Evaporator Water Flow OverdueDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4252doc 34253Diagnostic: Evaporator Water Flow Overdue Pump1Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4253doc 34254Diagnostic: Evaporator Water Flow Overdue Pump2Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4254doc 34255Diagnostic: Excessive Condenser Pressure Ckt2Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4255doc 34256Diagnostic: Excessive Condenser Pressure Ckt1Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4256doc 34257Diagnostic: External Chilled/Hot Water SetpointDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4257doc 34258Diagnostic: External Demand Limit SetpointDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4258doc 34259Diagnostic: EXV Pressure Equalization Failed Ckt1Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4259doc 34260Diagnostic: EXV Pressure Equalization Failed Ckt2Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4260doc 34261Diagnostic: Fan Inverter Fault Ckt1Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4261doc 34262Diagnostic: Fan Inverter Fault Ckt2Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4262doc 34263Diagnostic: Heat Recovery Entering Water Temp SensorDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4263doc 34264Diagnostic: Heat Recovery Leaving Water Temp SensorDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4264doc 34265Diagnostic: GP4Vvi High Cprsr Rfgt Discharge Temp 1ADiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4265doc 34266Diagnostic: High Cprsr Rfgt Discharge Temp 1ADiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4266doc 34267Diagnostic: High Cprsr Rfgt Discharge Temp 1BDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4267doc 34268Diagnostic: GP4Vvi High Cprsr Rfgt Discharge Temp 2ADiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4268doc 34269Diagnostic: High Cprsr Rfgt Discharge Temp 2ADiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4269doc 34270Diagnostic: High Cprsr Rfgt Discharge Temp 2BDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4270doc 34271Diagnostic: High Differential Refrigerant PressureDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4271doc 34272Diagnostic: High Differential Rfgt Pressure 1ADiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4272doc 34273Diagnostic: High Differential Rfgt Pressure 1BDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4273doc 34274Diagnostic: High Differential Rfgt Pressure 2ADiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4274doc 34275Diagnostic: High Differential Rfgt Pressure 2BDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4275doc 34276Diagnostic: High Evap Shell Rfgt Pressure Ckt1Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4276doc 34277Diagnostic: High Evap Shell Rfgt Pressure Ckt2Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4277doc 34278Diagnostic: High Evaporator Water TemperatureDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4278doc 34279Diagnostic: High Motor Winding Temperature 1ADiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4279doc 34280Diagnostic: High Motor Winding Temperature 2ADiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4280doc 34281Diagnostic: High Motor Winding Temperature Cprsr1ADiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4281doc 34282Diagnostic: High Motor Winding Temperature Cprsr2ADiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4282doc 34283Diagnostic: High Oil Temperature Ckt1Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4283doc 34284Diagnostic: High Oil Temperature Ckt2Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4284doc 34285Diagnostic: High Pressure Cutout Ckt2Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4285doc 34286Diagnostic: High Pressure Cutout Ckt1Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4286doc 34287Diagnostic: High Pressure Cutout 1ADiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4287doc 34288Diagnostic: High Pressure Cutout 1BDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4288doc 34289Diagnostic: High Pressure Cutout 2ADiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4289doc 34290Diagnostic: High Pressure Cutout 2BDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4290doc 34291Diagnostic: High Refrigerant Pressure RatioDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4291doc 34292Diagnostic: High Refrigerant Pressure Ratio 1ADiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4292doc 34293Diagnostic: High Refrigerant Pressure Ratio 1BDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4293doc 34294Diagnostic: High Refrigerant Pressure Ratio 2ADiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4294doc 34295Diagnostic: High Refrigerant Pressure Ratio 2BDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4295doc 34296Diagnostic: Inverted Evaporator Water TemperatureDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4296doc 34297Diagnostic: Liquid Line Pressure Sensor Ckt1Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4297doc 34298Diagnostic: Liquid Line Pressure Sensor Ckt2Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4298doc 34299Diagnostic: Liquid Line Temp Sensor Ckt1Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4299doc 34300Diagnostic: Liquid Line Temp Sensor Ckt2Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4300doc 34301Diagnostic: Loss of Oil for Compressor (Running) Ckt1Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4301doc 34302Diagnostic: Loss of Oil for Compressor (Running) Ckt2Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4302doc 34303Diagnostic: Loss of Oil for Compressor (Stopped) Ckt1Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4303doc 34304Diagnostic: Loss of Oil for Compressor (Stopped) Ckt2Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4304doc 34305Diagnostic: Low Condenser Rfgt Temp Ckt 1: Unit OffDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4305doc 34306Diagnostic: Low Condenser Rfgt Temp Ckt 2: Unit OffDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4306doc 34307Diagnostic: Low Differential Rfgt Pressure 1ADiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4307doc 34308Diagnostic: Low Differential Rfgt Pressure 1BDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4308doc 34309Diagnostic: Low Differential Rfgt Pressure 2ADiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4309doc 34310Diagnostic: Low Differential Rfgt Pressure 2BDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4310doc 34311Diagnostic: Low Discharge Superheat 1ADiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4311doc 34312Diagnostic: Low Discharge Superheat 1BDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4312doc 34313Diagnostic: Low Discharge Superheat 2ADiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4313doc 34314Diagnostic: Low Discharge Superheat 2BDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4314doc 34315Diagnostic: Low Evaporator Oil Return Level Ckt1Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4315doc 34316Diagnostic: Low Evaporator Oil Return Level Ckt2Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4316doc 34317Diagnostic: Low Evaporator Refrigerant Pressure Ckt1Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4317doc 34318Diagnostic: Low Evaporator Refrigerant Pressure Ckt2Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4318doc 34319Diagnostic: Low Evaporator Rfgt Temp Ckt 1: Unit OffDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4319doc 34320Diagnostic: Low Evaporator Rfgt Temp Ckt 2: Unit OffDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4320doc 34321Diagnostic: Low Evaporator Water Temp (Unit Off)Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4321doc 34322Diagnostic: Low Evaporator Water Temp (Unit On)Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4322doc 34323Diagnostic: Low Oil Flow 1ADiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4323doc 34324Diagnostic: Low Oil Flow 1BDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4324doc 34325Diagnostic: Low Oil Flow 2ADiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4325doc 34326Diagnostic: Low Oil Flow 2BDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4326doc 34327Diagnostic: Low Refrigerant Temperature Ckt2Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4327doc 34328Diagnostic: Low Refrigerant Temperature Ckt1Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4328doc 34329Diagnostic: Mfr Maintenance Recommended 1ADiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4329doc 34330Diagnostic: Mfr Maintenance Recommended 1BDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4330doc 34331Diagnostic: Mfr Maintenance Recommended 2ADiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4331doc 34332Diagnostic: Mfr Maintenance Recommended 2BDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4332doc 34333Diagnostic: Momentary Power Loss 1ADiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4333doc 34334Diagnostic: Momentary Power Loss 1BDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4334doc 34335Diagnostic: Momentary Power Loss 2ADiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4335doc 34336Diagnostic: Momentary Power Loss 2BDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4336doc 34337Diagnostic: Motor Current Overload 1ADiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4337doc 34338Diagnostic: Motor Current Overload 1BDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4338doc 34339Diagnostic: Motor Current Overload 2ADiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4339doc 34340Diagnostic: Motor Current Overload 2BDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4340doc 34341Diagnostic: Motor Winding Temp Sensor Cprsr1ADiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4341doc 34342Diagnostic: Motor Winding Temp Sensor Cprsr2ADiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4342doc 34343Diagnostic: MP: Invalid ConfigurationDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4343doc 34344Diagnostic: MP: Non-Volatile Block Test ErrorDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4344doc 34345Diagnostic: MP: Reset Has OccurredDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4345doc 34346Diagnostic: Need Cprsr 1A To Run For Oil FlowDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4346doc 34347Diagnostic: No Differential Rfgt Pressure 1ADiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4347doc 34348Diagnostic: No Differential Rfgt Pressure 1BDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4348doc 34349Diagnostic: No Differential Rfgt Pressure 2ADiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4349doc 34350Diagnostic: No Differential Rfgt Pressure 2BDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4350doc 34351Diagnostic: Oil Analysis Recommended Ckt1Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4351doc 34352Diagnostic: Oil Analysis Recommended Ckt2Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4352doc 34353Diagnostic: Oil Filter Change Recommended Cprsr1ADiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4353doc 34354Diagnostic: Oil Filter Change Recommended Cprsr2ADiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4354doc 34355Diagnostic: Oil Flow Protection Fault 1ADiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4355doc 34356Diagnostic: Oil Flow Protection Fault 1BDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4356doc 34357Diagnostic: Oil Flow Protection Fault 2ADiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4357doc 34358Diagnostic: Oil Flow Protection Fault 2BDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4358doc 34359Diagnostic: Oil Pressure Sensor 1ADiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4359doc 34360Diagnostic: Oil Pressure Sensor 1BDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4360doc 34361Diagnostic: Oil Pressure Sensor 2ADiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4361doc 34362Diagnostic: Oil Pressure Sensor 2BDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4362doc 34363Diagnostic: Oil Temperature Sensor, Circuit 1Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4363doc 34364Diagnostic: Oil Temperature Sensor, Circuit 2Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4364doc 34365Diagnostic: Outdoor Air Temperature SensorDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4365doc 34366Diagnostic: Over VoltageDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4366doc 34367Diagnostic: Over Voltage 1ADiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4367doc 34368Diagnostic: Over Voltage 2ADiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4368doc 34369Diagnostic: Phase Loss 1ADiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4369doc 34370Diagnostic: Phase Loss 1BDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4370doc 34371Diagnostic: Phase Loss 2ADiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4371doc 34372Diagnostic: Phase Loss 2BDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4372doc 34373Diagnostic: Phase Reversal 1ADiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4373doc 34374Diagnostic: Phase Reversal 1BDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4374doc 34375Diagnostic: Phase Reversal 2ADiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4375doc 34376Diagnostic: Phase Reversal 2BDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4376doc 34377Diagnostic: Power Loss 1ADiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4377doc 34378Diagnostic: Power Loss 1BDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4378doc 34379Diagnostic: Power Loss 2ADiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4379doc 34380Diagnostic: Power Loss 2BDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4380doc 34381Diagnostic: Pumpdown Terminated Ckt1Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4381doc 34382Diagnostic: Pumpdown Terminated Ckt2Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4382doc 34383Diagnostic: Pumpdown Terminated By Time Ckt2Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4383doc 34384Diagnostic: Pumpdown Terminated By Time Ckt1Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4384doc 34385Diagnostic: Refrigerant Charge Loss Detected Ckt1Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4385doc 34386Diagnostic: Refrigerant Charge Loss Detected Ckt2Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4386doc 34387Diagnostic: Restart Inhibit Invoked 1ADiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4387doc 34388Diagnostic: Restart Inhibit Invoked 1BDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4388doc 34389Diagnostic: Restart Inhibit Invoked 2ADiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4389doc 34390Diagnostic: Restart Inhibit Invoked 2BDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4390doc 34391Diagnostic: Severe Current Imbalance 1ADiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4391doc 34392Diagnostic: Severe Current Imbalance 1BDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4392doc 34393Diagnostic: Severe Current Imbalance 2ADiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4393doc 34394Diagnostic: Severe Current Imbalance 2BDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4394doc 34395Diagnostic: Software Error 1001: Call Trane ServiceDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4395doc 34396Diagnostic: Software Error 1002: Call Trane ServiceDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4396doc 34397Diagnostic: Software Error 1003: Call Trane ServiceDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4397doc 34398Diagnostic: Starter Comm Loss: Main Processor 1ADiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4398doc 34399Diagnostic: Starter Comm Loss: Main Processor 1BDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4399doc 34400Diagnostic: Starter Comm Loss: Main Processor 2ADiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4400doc 34401Diagnostic: Starter Comm Loss: Main Processor 2BDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4401doc 34402Diagnostic: Starter Contactor Interrupt Failure 1ADiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4402doc 34403Diagnostic: Starter Contactor Interrupt Failure 1BDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4403doc 34404Diagnostic: Starter Contactor Interrupt Failure 2ADiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4404doc 34405Diagnostic: Starter Contactor Interrupt Failure 2BDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4405doc 34406Diagnostic: Starter Did Not Fully Accelerate 1BDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4406doc 34407Diagnostic: Starter Did Not Fully Accelerate 1ADiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4407doc 34408Diagnostic: Starter Did Not Fully Accelerate 2BDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4408doc 34409Diagnostic: Starter Did Not Transition 1ADiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4409doc 34410Diagnostic: Starter Did Not Transition 1BDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4410doc 34411Diagnostic: Starter Did Not Transition 2ADiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4411doc 34412Diagnostic: Starter Did Not Transition 2BDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4412doc 34413Diagnostic: Starter Dry Run Test 1ADiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4413doc 34414Diagnostic: Starter Dry Run Test 1BDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4414doc 34415Diagnostic: Starter Dry Run Test 2ADiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4415doc 34416Diagnostic: Starter Dry Run Test 2BDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4416doc 34417Diagnostic: Starter Failed to Arm/Start 1ADiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4417doc 34418Diagnostic: Starter Failed to Arm/Start 1BDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4418doc 34419Diagnostic: Starter Failed to Arm/Start 2ADiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4419doc 34420Diagnostic: Starter Failed to Arm/Start 2BDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4420doc 34421Diagnostic: Starter Fault Type I 1ADiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4421doc 34422Diagnostic: Starter Fault Type I 1BDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4422doc 34423Diagnostic: Starter Fault Type I 2ADiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4423doc 34424Diagnostic: Starter Fault Type I 2BDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4424doc 34425Diagnostic: Starter Fault Type II 1ADiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4425doc 34426Diagnostic: Starter Fault Type II 1BDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4426doc 34427Diagnostic: Starter Fault Type II 2ADiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4427doc 34428Diagnostic: Starter Fault Type II 2BDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4428doc 34429Diagnostic: Starter Fault Type III 1ADiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4429doc 34430Diagnostic: Starter Fault Type III 1BDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4430doc 34431Diagnostic: Starter Fault Type III 2ADiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4431doc 34432Diagnostic: Starter Fault Type III 2BDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4432doc 34433Diagnostic: Starter Module Memory Error Type 1 1ADiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4433doc 34434Diagnostic: Starter Module Memory Error Type 1 1BDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4434doc 34435Diagnostic: Starter Module Memory Error Type 1 2ADiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4435doc 34436Diagnostic: Starter Module Memory Error Type 1 2BDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4436doc 34437Diagnostic: Starter Module Memory Error Type 2 1ADiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4437doc 34438Diagnostic: Starter Module Memory Error Type 2 1BDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4438doc 34439Diagnostic: Starter Module Memory Error Type 2 2ADiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4439doc 34440Diagnostic: Starter Module Memory Error Type 2 2BDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4440doc 34441Diagnostic: Starts/Hours Modified 1ADiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4441doc 34442Diagnostic: Starts/Hours Modified 1BDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4442doc 34443Diagnostic: Starts/Hours Modified 2ADiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4443doc 34444Diagnostic: Starts/Hours Modified 2BDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4444doc 34445Diagnostic: Suction Pressure Transducer Ckt2Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4445doc 34446Diagnostic: Suction Pressure Transducer Ckt1Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4446doc 34447Diagnostic: Suction Refrigerant Pressure Sensor 1ADiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4447doc 34448Diagnostic: Suction Refrigerant Pressure Sensor 1BDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4448doc 34449Diagnostic: Suction Refrigerant Pressure Sensor 2ADiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4449doc 34450Diagnostic: Suction Refrigerant Pressure Sensor 2BDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4450doc 34451Diagnostic: Suction Temperature SensorDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4451doc 34452Diagnostic: Transition Complete Input Opened 1ADiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4452doc 34453Diagnostic: Transition Complete Input Opened 1BDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4453doc 34454Diagnostic: Transition Complete Input Opened 2ADiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4454doc 34455Diagnostic: Transition Complete Input Opened 2BDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4455doc 34456Diagnostic: Transition Complete Input Shorted 1ADiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4456doc 34457Diagnostic: Transition Complete Input Shorted 1BDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4457doc 34458Diagnostic: Transition Complete Input Shorted 2ADiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4458doc 34459Diagnostic: Transition Complete Input Shorted 2BDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4459doc 34460Diagnostic: Under VoltageDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4460doc 34461Diagnostic: Under Voltage 1ADiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4461doc 34462Diagnostic: Under Voltage 2ADiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4462doc 34463Diagnostic: Unexpected Starter Shutdown 1ADiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4463doc 34464Diagnostic: Unexpected Starter Shutdown 1BDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4464doc 34465Diagnostic: Unexpected Starter Shutdown 2ADiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4465doc 34466Diagnostic: Unexpected Starter Shutdown 2BDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4466doc 34467Diagnostic: Very Low Discharge Superheat 1ADiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4467doc 34468Diagnostic: Very Low Discharge Superheat 2ADiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4468doc 34469Diagnostic: Very Low Evap Rfgt Pressure 1ADiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4469doc 34470Diagnostic: Very Low Evap Rfgt Pressure 1BDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4470doc 34471Diagnostic: Very Low Evap Rfgt Pressure 2ADiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4471doc 34472Diagnostic: Very Low Evap Rfgt Pressure 2BDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4472doc 34473Diagnostic: Water System Differential PressureDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4473doc 34474Diagnostic: Energy Meter Write Value FailureDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4474doc 34475Diagnostic: Write Command Failure Energy Meter 1Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4475doc 34476Diagnostic: Write Command Failure Energy Meter 2Diagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4476doc 34477Diagnostic: High Evaporator PressureDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
IR4477doc 34478Comm Loss: Starter Panel High Temperature LimitDiagnostic flag.UINT16Read0 = Normal; 1 = In Alarm
HR10doc 40011Chilled Water SetpointTemperature in the factory unit system (I-P or SI).FLOAT32ABCDRead/write
HR12doc 40013Demand Limit SetpointFLOAT32ABCD%Read/write
HR14doc 40015Hot Water SetpointTemperature in the factory unit system (I-P or SI). Needs: Hot Water ControlFLOAT32ABCDRead/write
HR16doc 40017BAS Cooling Differential to StartTemperature difference, factory unit system (I-P or SI).FLOAT32ABCDRead/write
HR18doc 40019BAS Cooling Differential to StopTemperature difference, factory unit system (I-P or SI).FLOAT32ABCDRead/write
HR20doc 40021BAS Heating Differential to StartTemperature difference, factory unit system (I-P or SI). Needs: Hot Water ControlFLOAT32ABCDRead/write
HR22doc 40023BAS Heating Differential to StopTemperature difference, factory unit system (I-P or SI). Needs: Hot Water ControlFLOAT32ABCDRead/write
HR2010doc 42011Chiller Mode Command BASUINT16Read/write1 = Cool; 2 = Heat; 3 = Ice Making; 4 = Free Cooling

Notes on this map

Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.

Questions about the Trane Series R RTWD water-cooled helical-rotary chiller (Symbio 800)

What Modbus registers does the Trane Series R RTWD water-cooled helical-rotary chiller (Symbio 800) have?

This map lists 673 registers: 665 input registers, 8 holding registers. 8 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.

Are the Trane Series R RTWD water-cooled helical-rotary chiller (Symbio 800) Modbus addresses 0-based or 1-based?

The manufacturer's document numbers registers Modicon 3xxxx/4xxxx (drop the prefix, subtract 1). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. The list prints Modicon register numbers: 3xxxx are input registers and 4xxxx holding registers, so 30011 is input register address 10 and 42011 is holding register address 2010.

What byte order does the Trane Series R RTWD water-cooled helical-rotary chiller (Symbio 800) use for 32-bit values?

Multi-register values in this map use ABCD (high word first (big-endian)). Set your client to this order for every 32/64-bit value in the table.

What are the minimum Modbus registers to integrate the Trane Series R RTWD water-cooled helical-rotary chiller (Symbio 800)?

Start with IR 10 Active Cool/Heat Setpoint Temperature (Active cool/heat setpoint); IR 16 Evaporator Leaving Water Temperature (Evaporator leaving water temperature); IR 14 Evaporator Entering Water Temperature (Evaporator entering water temperature); IR 28 Actual Running Capacity (Actual running capacity); IR 2010 Running Mode (Running mode); IR 3010 Run Enable (Run enable); IR 3018 Diagnostic Present (Diagnostic present); HR 10 Chilled Water Setpoint (Chilled water setpoint (BAS)); HR 2010 Chiller Mode Command BAS (BAS chiller mode command).

How do I enable Modbus control of the Trane Series R RTWD water-cooled helical-rotary chiller (Symbio 800)?

On the Symbio 800 web interface go to Installation > Identification and Communications > Protocol Configuration and select Modbus RTU or Modbus TCP (per Trane's Symbio 800 integration guides).

Where is the official Trane Series R RTWD water-cooled helical-rotary chiller (Symbio 800) Modbus documentation?

The source is Symbio 800 Integration Points List, BACnet/Modbus, Series R Model RTWD (BAS-PTS017A-EN), revision 2024-11-15, published free by Trane at https://elibrary.tranetechnologies.com/public/commercial-hvac/Literature/Points%20List/BAS-PTS017A-EN_11152024.pdf.