Sensor (refrigerant leak monitor for chiller plant rooms) · Modbus register map
Trane TruSense RMWH refrigerant monitor (up to 16 points) Modbus register map
Updated 19 November 2026
Wall-mounted sample-draw refrigerant monitor for chiller and equipment rooms that checks up to 16 points for leaks of the common HVAC refrigerants. Over Modbus RTU it exposes 16-bit holding registers: unit status, an acknowledge and reset command, per-channel gas type, ppm reading and alarm flags, and calibration dates.
This page lists 76 Modbus registers for the Trane TruSense RMWH refrigerant monitor (up to 16 points) — 2 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Trane’s own free documentation (linked below) and checked against it.
- Manufacturer
- Trane
- Model
- TruSense RMWH refrigerant monitor (up to 16 points)
- Registers
- 76 (2 writable)
- Transport
- Modbus RTU
- Default unit ID
- Not stated
- Documented addressing
- Modicon 3xxxx/4xxxx (drop the prefix, subtract 1)
- Also known as
- TruSense, RMWH, Trane refrigerant monitor, PART-SVX008A, RMWH-SVX001
Integration notes: Trane TruSense RMWH refrigerant monitor (up to 16 points)
Select MODBUS on the Outputs > Digital tab, set the device address and baud rate, then poll holding registers 40007-40073. Each channel uses four registers: gas number, ppm, status flags, reserved.
Minimum registers to map
Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.
| Register | Name | Type | Why | Access |
|---|---|---|---|---|
| HR 6 | Unit status | BITMAP16 | Unit status flags | Read |
| HR 10 | Channel 1 gas concentration | UINT16 | Channel 1 refrigerant ppm | Read |
| HR 11 | Channel 1 status | BITMAP16 | Channel 1 alarm flags | Read |
| HR 9 | Channel 1 gas number | UINT16 | Channel 1 gas type | Read |
| HR 14 | Channel 2 gas concentration | UINT16 | Channel 2 refrigerant ppm | Read |
| HR 7 | ACK button | UINT16 | Acknowledge alarms | Write |
Enable Modbus control & writes
Digital output is None by default. During initial setup (or later on the Outputs screen) open the Digital tab, select MODBUS, press Edit, enter the Device Address, choose a baud rate, set the RS485 Termination check box as needed, and press Done.
Byte order & addressing
- Channel n starts at register 40010 + 4 x (n - 1).
- The reset command packs the action in the high byte and the channel (0-15, or 255 for all) in the low byte.
Network setup
- RS-485 Modbus RTU only; set address and baud on the touchscreen.
- The Modbus setup screen has an RS485 Termination check box for the built-in terminator.
Watch out for
- Modbus is off until MODBUS is chosen on the Digital tab (factory default is None).
- Calibration dates are day counts since 1970, not Unix seconds.
Trane TruSense RMWH refrigerant monitor (up to 16 points) Modbus registers
Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.
| Table | Address | Name | Description | Type | Order | Scale | Units | Access | Values / bits |
|---|---|---|---|---|---|---|---|---|---|
| HR | 0doc 40001 | Product ID | Two ASCII characters, reads "CG". | UINT16 | Read | ||||
| HR | 1doc 40002 | Firmware version 1 | Major version in the high byte, minor in the low byte. | UINT16 | Read | ||||
| HR | 2doc 40003 | Firmware version 2 | Build number (two bytes). | UINT16 | Read | ||||
| HR | 6doc 40007 | Unit status | Packed unit status flags. | BITMAP16 | Read | bit 0 = Warm-up pending; bit 1 = Operating (normal mode); bit 2 = Calibration in progress; bit 3 = Fault reported; bit 4 = Alarm (caution/warning/alarm level reached) | |||
| HR | 7doc 40008 | ACK button | Write 1 to acknowledge alarms. | UINT16 | Write | ||||
| HR | 8doc 40009 | RESET button | High byte = action, low byte = channel (0-15) or 255 for all. | UINT16 | Write | ||||
| HR | 9doc 40010 | Channel 1 gas number | Refrigerant the channel is set to measure. | UINT16 | Read | 0 = R-11; 1 = R-12; 2 = R-22; 3 = R-123; 4 = R-134A; 5 = R-401A; 6 = R-404A; 7 = R-407A; 8 = R-407C; 9 = R-407F; 10 = R-410A; 11 = R-422A; 12 = R-422D; 13 = R-427A; 14 = R-507; 15 = R-513A; 16 = R-514A; 17 = R-1233zd(E); 18 = R-1234yf; 19 = R-1234ze | |||
| HR | 10doc 40011 | Channel 1 gas concentration | UINT16 | ppm | Read | ||||
| HR | 11doc 40012 | Channel 1 status | Packed channel alarm flags. | BITMAP16 | Read | bit 0 = Caution level reached; bit 1 = Warning level reached; bit 2 = Alarm level reached; bit 3 = Beacon (caution/warning/alarm set); bit 4 = Horn (configured level set and not acknowledged); bit 5 = New (level set and not acknowledged); bit 6 = Hold (acknowledged latching alarm now below threshold); bit 7 = Fault reported | |||
| HR | 13doc 40014 | Channel 2 gas number | Refrigerant the channel is set to measure. | UINT16 | Read | 0 = R-11; 1 = R-12; 2 = R-22; 3 = R-123; 4 = R-134A; 5 = R-401A; 6 = R-404A; 7 = R-407A; 8 = R-407C; 9 = R-407F; 10 = R-410A; 11 = R-422A; 12 = R-422D; 13 = R-427A; 14 = R-507; 15 = R-513A; 16 = R-514A; 17 = R-1233zd(E); 18 = R-1234yf; 19 = R-1234ze | |||
| HR | 14doc 40015 | Channel 2 gas concentration | UINT16 | ppm | Read | ||||
| HR | 15doc 40016 | Channel 2 status | Packed channel alarm flags. | BITMAP16 | Read | bit 0 = Caution level reached; bit 1 = Warning level reached; bit 2 = Alarm level reached; bit 3 = Beacon (caution/warning/alarm set); bit 4 = Horn (configured level set and not acknowledged); bit 5 = New (level set and not acknowledged); bit 6 = Hold (acknowledged latching alarm now below threshold); bit 7 = Fault reported | |||
| HR | 17doc 40018 | Channel 3 gas number | Refrigerant the channel is set to measure. | UINT16 | Read | 0 = R-11; 1 = R-12; 2 = R-22; 3 = R-123; 4 = R-134A; 5 = R-401A; 6 = R-404A; 7 = R-407A; 8 = R-407C; 9 = R-407F; 10 = R-410A; 11 = R-422A; 12 = R-422D; 13 = R-427A; 14 = R-507; 15 = R-513A; 16 = R-514A; 17 = R-1233zd(E); 18 = R-1234yf; 19 = R-1234ze | |||
| HR | 18doc 40019 | Channel 3 gas concentration | UINT16 | ppm | Read | ||||
| HR | 19doc 40020 | Channel 3 status | Packed channel alarm flags. | BITMAP16 | Read | bit 0 = Caution level reached; bit 1 = Warning level reached; bit 2 = Alarm level reached; bit 3 = Beacon (caution/warning/alarm set); bit 4 = Horn (configured level set and not acknowledged); bit 5 = New (level set and not acknowledged); bit 6 = Hold (acknowledged latching alarm now below threshold); bit 7 = Fault reported | |||
| HR | 21doc 40022 | Channel 4 gas number | Refrigerant the channel is set to measure. | UINT16 | Read | 0 = R-11; 1 = R-12; 2 = R-22; 3 = R-123; 4 = R-134A; 5 = R-401A; 6 = R-404A; 7 = R-407A; 8 = R-407C; 9 = R-407F; 10 = R-410A; 11 = R-422A; 12 = R-422D; 13 = R-427A; 14 = R-507; 15 = R-513A; 16 = R-514A; 17 = R-1233zd(E); 18 = R-1234yf; 19 = R-1234ze | |||
| HR | 22doc 40023 | Channel 4 gas concentration | UINT16 | ppm | Read | ||||
| HR | 23doc 40024 | Channel 4 status | Packed channel alarm flags. | BITMAP16 | Read | bit 0 = Caution level reached; bit 1 = Warning level reached; bit 2 = Alarm level reached; bit 3 = Beacon (caution/warning/alarm set); bit 4 = Horn (configured level set and not acknowledged); bit 5 = New (level set and not acknowledged); bit 6 = Hold (acknowledged latching alarm now below threshold); bit 7 = Fault reported | |||
| HR | 25doc 40026 | Channel 5 gas number | Refrigerant the channel is set to measure. | UINT16 | Read | 0 = R-11; 1 = R-12; 2 = R-22; 3 = R-123; 4 = R-134A; 5 = R-401A; 6 = R-404A; 7 = R-407A; 8 = R-407C; 9 = R-407F; 10 = R-410A; 11 = R-422A; 12 = R-422D; 13 = R-427A; 14 = R-507; 15 = R-513A; 16 = R-514A; 17 = R-1233zd(E); 18 = R-1234yf; 19 = R-1234ze | |||
| HR | 26doc 40027 | Channel 5 gas concentration | UINT16 | ppm | Read | ||||
| HR | 27doc 40028 | Channel 5 status | Packed channel alarm flags. | BITMAP16 | Read | bit 0 = Caution level reached; bit 1 = Warning level reached; bit 2 = Alarm level reached; bit 3 = Beacon (caution/warning/alarm set); bit 4 = Horn (configured level set and not acknowledged); bit 5 = New (level set and not acknowledged); bit 6 = Hold (acknowledged latching alarm now below threshold); bit 7 = Fault reported | |||
| HR | 29doc 40030 | Channel 6 gas number | Refrigerant the channel is set to measure. | UINT16 | Read | 0 = R-11; 1 = R-12; 2 = R-22; 3 = R-123; 4 = R-134A; 5 = R-401A; 6 = R-404A; 7 = R-407A; 8 = R-407C; 9 = R-407F; 10 = R-410A; 11 = R-422A; 12 = R-422D; 13 = R-427A; 14 = R-507; 15 = R-513A; 16 = R-514A; 17 = R-1233zd(E); 18 = R-1234yf; 19 = R-1234ze | |||
| HR | 30doc 40031 | Channel 6 gas concentration | UINT16 | ppm | Read | ||||
| HR | 31doc 40032 | Channel 6 status | Packed channel alarm flags. | BITMAP16 | Read | bit 0 = Caution level reached; bit 1 = Warning level reached; bit 2 = Alarm level reached; bit 3 = Beacon (caution/warning/alarm set); bit 4 = Horn (configured level set and not acknowledged); bit 5 = New (level set and not acknowledged); bit 6 = Hold (acknowledged latching alarm now below threshold); bit 7 = Fault reported | |||
| HR | 33doc 40034 | Channel 7 gas number | Refrigerant the channel is set to measure. | UINT16 | Read | 0 = R-11; 1 = R-12; 2 = R-22; 3 = R-123; 4 = R-134A; 5 = R-401A; 6 = R-404A; 7 = R-407A; 8 = R-407C; 9 = R-407F; 10 = R-410A; 11 = R-422A; 12 = R-422D; 13 = R-427A; 14 = R-507; 15 = R-513A; 16 = R-514A; 17 = R-1233zd(E); 18 = R-1234yf; 19 = R-1234ze | |||
| HR | 34doc 40035 | Channel 7 gas concentration | UINT16 | ppm | Read | ||||
| HR | 35doc 40036 | Channel 7 status | Packed channel alarm flags. | BITMAP16 | Read | bit 0 = Caution level reached; bit 1 = Warning level reached; bit 2 = Alarm level reached; bit 3 = Beacon (caution/warning/alarm set); bit 4 = Horn (configured level set and not acknowledged); bit 5 = New (level set and not acknowledged); bit 6 = Hold (acknowledged latching alarm now below threshold); bit 7 = Fault reported | |||
| HR | 37doc 40038 | Channel 8 gas number | Refrigerant the channel is set to measure. | UINT16 | Read | 0 = R-11; 1 = R-12; 2 = R-22; 3 = R-123; 4 = R-134A; 5 = R-401A; 6 = R-404A; 7 = R-407A; 8 = R-407C; 9 = R-407F; 10 = R-410A; 11 = R-422A; 12 = R-422D; 13 = R-427A; 14 = R-507; 15 = R-513A; 16 = R-514A; 17 = R-1233zd(E); 18 = R-1234yf; 19 = R-1234ze | |||
| HR | 38doc 40039 | Channel 8 gas concentration | UINT16 | ppm | Read | ||||
| HR | 39doc 40040 | Channel 8 status | Packed channel alarm flags. | BITMAP16 | Read | bit 0 = Caution level reached; bit 1 = Warning level reached; bit 2 = Alarm level reached; bit 3 = Beacon (caution/warning/alarm set); bit 4 = Horn (configured level set and not acknowledged); bit 5 = New (level set and not acknowledged); bit 6 = Hold (acknowledged latching alarm now below threshold); bit 7 = Fault reported | |||
| HR | 41doc 40042 | Channel 9 gas number | Refrigerant the channel is set to measure. | UINT16 | Read | 0 = R-11; 1 = R-12; 2 = R-22; 3 = R-123; 4 = R-134A; 5 = R-401A; 6 = R-404A; 7 = R-407A; 8 = R-407C; 9 = R-407F; 10 = R-410A; 11 = R-422A; 12 = R-422D; 13 = R-427A; 14 = R-507; 15 = R-513A; 16 = R-514A; 17 = R-1233zd(E); 18 = R-1234yf; 19 = R-1234ze | |||
| HR | 42doc 40043 | Channel 9 gas concentration | UINT16 | ppm | Read | ||||
| HR | 43doc 40044 | Channel 9 status | Packed channel alarm flags. | BITMAP16 | Read | bit 0 = Caution level reached; bit 1 = Warning level reached; bit 2 = Alarm level reached; bit 3 = Beacon (caution/warning/alarm set); bit 4 = Horn (configured level set and not acknowledged); bit 5 = New (level set and not acknowledged); bit 6 = Hold (acknowledged latching alarm now below threshold); bit 7 = Fault reported | |||
| HR | 45doc 40046 | Channel 10 gas number | Refrigerant the channel is set to measure. | UINT16 | Read | 0 = R-11; 1 = R-12; 2 = R-22; 3 = R-123; 4 = R-134A; 5 = R-401A; 6 = R-404A; 7 = R-407A; 8 = R-407C; 9 = R-407F; 10 = R-410A; 11 = R-422A; 12 = R-422D; 13 = R-427A; 14 = R-507; 15 = R-513A; 16 = R-514A; 17 = R-1233zd(E); 18 = R-1234yf; 19 = R-1234ze | |||
| HR | 46doc 40047 | Channel 10 gas concentration | UINT16 | ppm | Read | ||||
| HR | 47doc 40048 | Channel 10 status | Packed channel alarm flags. | BITMAP16 | Read | bit 0 = Caution level reached; bit 1 = Warning level reached; bit 2 = Alarm level reached; bit 3 = Beacon (caution/warning/alarm set); bit 4 = Horn (configured level set and not acknowledged); bit 5 = New (level set and not acknowledged); bit 6 = Hold (acknowledged latching alarm now below threshold); bit 7 = Fault reported | |||
| HR | 49doc 40050 | Channel 11 gas number | Refrigerant the channel is set to measure. | UINT16 | Read | 0 = R-11; 1 = R-12; 2 = R-22; 3 = R-123; 4 = R-134A; 5 = R-401A; 6 = R-404A; 7 = R-407A; 8 = R-407C; 9 = R-407F; 10 = R-410A; 11 = R-422A; 12 = R-422D; 13 = R-427A; 14 = R-507; 15 = R-513A; 16 = R-514A; 17 = R-1233zd(E); 18 = R-1234yf; 19 = R-1234ze | |||
| HR | 50doc 40051 | Channel 11 gas concentration | UINT16 | ppm | Read | ||||
| HR | 51doc 40052 | Channel 11 status | Packed channel alarm flags. | BITMAP16 | Read | bit 0 = Caution level reached; bit 1 = Warning level reached; bit 2 = Alarm level reached; bit 3 = Beacon (caution/warning/alarm set); bit 4 = Horn (configured level set and not acknowledged); bit 5 = New (level set and not acknowledged); bit 6 = Hold (acknowledged latching alarm now below threshold); bit 7 = Fault reported | |||
| HR | 53doc 40054 | Channel 12 gas number | Refrigerant the channel is set to measure. | UINT16 | Read | 0 = R-11; 1 = R-12; 2 = R-22; 3 = R-123; 4 = R-134A; 5 = R-401A; 6 = R-404A; 7 = R-407A; 8 = R-407C; 9 = R-407F; 10 = R-410A; 11 = R-422A; 12 = R-422D; 13 = R-427A; 14 = R-507; 15 = R-513A; 16 = R-514A; 17 = R-1233zd(E); 18 = R-1234yf; 19 = R-1234ze | |||
| HR | 54doc 40055 | Channel 12 gas concentration | UINT16 | ppm | Read | ||||
| HR | 55doc 40056 | Channel 12 status | Packed channel alarm flags. | BITMAP16 | Read | bit 0 = Caution level reached; bit 1 = Warning level reached; bit 2 = Alarm level reached; bit 3 = Beacon (caution/warning/alarm set); bit 4 = Horn (configured level set and not acknowledged); bit 5 = New (level set and not acknowledged); bit 6 = Hold (acknowledged latching alarm now below threshold); bit 7 = Fault reported | |||
| HR | 57doc 40058 | Channel 13 gas number | Refrigerant the channel is set to measure. | UINT16 | Read | 0 = R-11; 1 = R-12; 2 = R-22; 3 = R-123; 4 = R-134A; 5 = R-401A; 6 = R-404A; 7 = R-407A; 8 = R-407C; 9 = R-407F; 10 = R-410A; 11 = R-422A; 12 = R-422D; 13 = R-427A; 14 = R-507; 15 = R-513A; 16 = R-514A; 17 = R-1233zd(E); 18 = R-1234yf; 19 = R-1234ze | |||
| HR | 58doc 40059 | Channel 13 gas concentration | UINT16 | ppm | Read | ||||
| HR | 59doc 40060 | Channel 13 status | Packed channel alarm flags. | BITMAP16 | Read | bit 0 = Caution level reached; bit 1 = Warning level reached; bit 2 = Alarm level reached; bit 3 = Beacon (caution/warning/alarm set); bit 4 = Horn (configured level set and not acknowledged); bit 5 = New (level set and not acknowledged); bit 6 = Hold (acknowledged latching alarm now below threshold); bit 7 = Fault reported | |||
| HR | 61doc 40062 | Channel 14 gas number | Refrigerant the channel is set to measure. | UINT16 | Read | 0 = R-11; 1 = R-12; 2 = R-22; 3 = R-123; 4 = R-134A; 5 = R-401A; 6 = R-404A; 7 = R-407A; 8 = R-407C; 9 = R-407F; 10 = R-410A; 11 = R-422A; 12 = R-422D; 13 = R-427A; 14 = R-507; 15 = R-513A; 16 = R-514A; 17 = R-1233zd(E); 18 = R-1234yf; 19 = R-1234ze | |||
| HR | 62doc 40063 | Channel 14 gas concentration | UINT16 | ppm | Read | ||||
| HR | 63doc 40064 | Channel 14 status | Packed channel alarm flags. | BITMAP16 | Read | bit 0 = Caution level reached; bit 1 = Warning level reached; bit 2 = Alarm level reached; bit 3 = Beacon (caution/warning/alarm set); bit 4 = Horn (configured level set and not acknowledged); bit 5 = New (level set and not acknowledged); bit 6 = Hold (acknowledged latching alarm now below threshold); bit 7 = Fault reported | |||
| HR | 65doc 40066 | Channel 15 gas number | Refrigerant the channel is set to measure. | UINT16 | Read | 0 = R-11; 1 = R-12; 2 = R-22; 3 = R-123; 4 = R-134A; 5 = R-401A; 6 = R-404A; 7 = R-407A; 8 = R-407C; 9 = R-407F; 10 = R-410A; 11 = R-422A; 12 = R-422D; 13 = R-427A; 14 = R-507; 15 = R-513A; 16 = R-514A; 17 = R-1233zd(E); 18 = R-1234yf; 19 = R-1234ze | |||
| HR | 66doc 40067 | Channel 15 gas concentration | UINT16 | ppm | Read | ||||
| HR | 67doc 40068 | Channel 15 status | Packed channel alarm flags. | BITMAP16 | Read | bit 0 = Caution level reached; bit 1 = Warning level reached; bit 2 = Alarm level reached; bit 3 = Beacon (caution/warning/alarm set); bit 4 = Horn (configured level set and not acknowledged); bit 5 = New (level set and not acknowledged); bit 6 = Hold (acknowledged latching alarm now below threshold); bit 7 = Fault reported | |||
| HR | 69doc 40070 | Channel 16 gas number | Refrigerant the channel is set to measure. | UINT16 | Read | 0 = R-11; 1 = R-12; 2 = R-22; 3 = R-123; 4 = R-134A; 5 = R-401A; 6 = R-404A; 7 = R-407A; 8 = R-407C; 9 = R-407F; 10 = R-410A; 11 = R-422A; 12 = R-422D; 13 = R-427A; 14 = R-507; 15 = R-513A; 16 = R-514A; 17 = R-1233zd(E); 18 = R-1234yf; 19 = R-1234ze | |||
| HR | 70doc 40071 | Channel 16 gas concentration | UINT16 | ppm | Read | ||||
| HR | 71doc 40072 | Channel 16 status | Packed channel alarm flags. | BITMAP16 | Read | bit 0 = Caution level reached; bit 1 = Warning level reached; bit 2 = Alarm level reached; bit 3 = Beacon (caution/warning/alarm set); bit 4 = Horn (configured level set and not acknowledged); bit 5 = New (level set and not acknowledged); bit 6 = Hold (acknowledged latching alarm now below threshold); bit 7 = Fault reported | |||
| HR | 89doc 40090 | Next calibration time | Days since 1 Jan 1970. | UINT16 | d | Read | |||
| HR | 90doc 40091 | Zero calibration time | Days since 1 Jan 1970. | UINT16 | d | Read | |||
| HR | 91doc 40092 | Span calibration time #00 (R-11) | Days since 1 Jan 1970 of the last span calibration for this gas. | UINT16 | d | Read | |||
| HR | 92doc 40093 | Span calibration time #01 (R-12) | Days since 1 Jan 1970 of the last span calibration for this gas. | UINT16 | d | Read | |||
| HR | 93doc 40094 | Span calibration time #02 (R-22) | Days since 1 Jan 1970 of the last span calibration for this gas. | UINT16 | d | Read | |||
| HR | 94doc 40095 | Span calibration time #03 (R-123) | Days since 1 Jan 1970 of the last span calibration for this gas. | UINT16 | d | Read | |||
| HR | 95doc 40096 | Span calibration time #04 (R-134A) | Days since 1 Jan 1970 of the last span calibration for this gas. | UINT16 | d | Read | |||
| HR | 96doc 40097 | Span calibration time #05 (R-401A) | Days since 1 Jan 1970 of the last span calibration for this gas. | UINT16 | d | Read | |||
| HR | 97doc 40098 | Span calibration time #06 (R-404A) | Days since 1 Jan 1970 of the last span calibration for this gas. | UINT16 | d | Read | |||
| HR | 98doc 40099 | Span calibration time #07 (R-407A) | Days since 1 Jan 1970 of the last span calibration for this gas. | UINT16 | d | Read | |||
| HR | 99doc 40100 | Span calibration time #08 (R-407C) | Days since 1 Jan 1970 of the last span calibration for this gas. | UINT16 | d | Read | |||
| HR | 100doc 40101 | Span calibration time #09 (R-407F) | Days since 1 Jan 1970 of the last span calibration for this gas. | UINT16 | d | Read | |||
| HR | 101doc 40102 | Span calibration time #10 (R-410A) | Days since 1 Jan 1970 of the last span calibration for this gas. | UINT16 | d | Read | |||
| HR | 102doc 40103 | Span calibration time #11 (R-422A) | Days since 1 Jan 1970 of the last span calibration for this gas. | UINT16 | d | Read | |||
| HR | 103doc 40104 | Span calibration time #12 (R-422D) | Days since 1 Jan 1970 of the last span calibration for this gas. | UINT16 | d | Read | |||
| HR | 104doc 40105 | Span calibration time #13 (R-427A) | Days since 1 Jan 1970 of the last span calibration for this gas. | UINT16 | d | Read | |||
| HR | 105doc 40106 | Span calibration time #14 (R-507) | Days since 1 Jan 1970 of the last span calibration for this gas. | UINT16 | d | Read | |||
| HR | 106doc 40107 | Span calibration time #15 (R-513A) | Days since 1 Jan 1970 of the last span calibration for this gas. | UINT16 | d | Read | |||
| HR | 107doc 40108 | Span calibration time #16 (R-514A) | Days since 1 Jan 1970 of the last span calibration for this gas. | UINT16 | d | Read | |||
| HR | 108doc 40109 | Span calibration time #17 (R-1233zd(E)) | Days since 1 Jan 1970 of the last span calibration for this gas. | UINT16 | d | Read | |||
| HR | 109doc 40110 | Span calibration time #18 (R-1234yf) | Days since 1 Jan 1970 of the last span calibration for this gas. | UINT16 | d | Read | |||
| HR | 110doc 40111 | Span calibration time #19 (R-1234ze) | Days since 1 Jan 1970 of the last span calibration for this gas. | UINT16 | d | Read |
Notes on this map
- The register list gives no data type or multiplier; every register is one 16-bit word, typed here as unsigned. Concentrations are listed in ppm as printed (the specifications give a 0-1000 ppm range and 1 ppm resolution).
- RESET button actions (40009): high byte 0 + channel number (0-15) resets that channel's alarms, 0/255 resets all channel alarms; 1 + channel resets that channel's faults, 1/255 all channel faults; 2/255 resets common faults; 3/255 resets all alarms and faults.
- Each channel also has a 'Reserved' register that reads 0 (40013, 40017 ... 40073); these and Reserved 40004-40006 are left out.
- The document is marked 'Preliminary' and supersedes RMWH-SVX001D-EN.
- Baud rate and device address are chosen on the touchscreen; the manual does not list the defaults, the baud choices or parity.
- The table's 'Index' column starts at 40001 in 5-digit Modicon form; the manual gives no separate offset statement, so 40001 is taken as wire address 0.
Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.
Questions about the Trane TruSense RMWH refrigerant monitor (up to 16 points)
What Modbus registers does the Trane TruSense RMWH refrigerant monitor (up to 16 points) have?
This map lists 76 registers: 76 holding registers. 2 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.
Are the Trane TruSense RMWH refrigerant monitor (up to 16 points) Modbus addresses 0-based or 1-based?
The manufacturer's document numbers registers Modicon 3xxxx/4xxxx (drop the prefix, subtract 1). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. The register table's 'Index' column prints Modicon holding registers from 40001, so 40001 is wire address 0 and channel 1 gas concentration 40011 is wire address 10.
What are the minimum Modbus registers to integrate the Trane TruSense RMWH refrigerant monitor (up to 16 points)?
Start with HR 6 Unit status (Unit status flags); HR 10 Channel 1 gas concentration (Channel 1 refrigerant ppm); HR 11 Channel 1 status (Channel 1 alarm flags); HR 9 Channel 1 gas number (Channel 1 gas type); HR 14 Channel 2 gas concentration (Channel 2 refrigerant ppm); HR 7 ACK button (Acknowledge alarms).
How do I enable Modbus control of the Trane TruSense RMWH refrigerant monitor (up to 16 points)?
Digital output is None by default. During initial setup (or later on the Outputs screen) open the Digital tab, select MODBUS, press Edit, enter the Device Address, choose a baud rate, set the RS485 Termination check box as needed, and press Done.
Where is the official Trane TruSense RMWH refrigerant monitor (up to 16 points) Modbus documentation?
The source is Installation, Operation, and Maintenance: TruSense RMWH Refrigerant Monitor (PART-SVX008A-EN), revision 2025-09-30, published free by Trane at https://elibrary.tranetechnologies.com/public/commercial-hvac/Literature/Installation%20Operation%20and%20Maintenance/PART-SVX008A-EN_09302025.pdf.
More Trane Modbus register maps
- Chiller
Trane Agility water-cooled centrifugal chiller (Symbio 800)
Trane Agility water-cooled chillers with Symbio 800 controls, as listed in BAS-PTS007C-EN (6/30/2026).
Also known as: Agility, HDWA, Agility water-cooled chiller - Chiller
Trane Ascend ACR Series C air-cooled chiller (Symbio 800)
Trane Ascend model ACR Series C air-cooled chillers with the Symbio 800 controller, as listed in BAS-PTS021A-EN (11/15/2024).
Also known as: ACR, Ascend ACR, ACR Series C, Ascend air-cooled chiller ACR - Chiller
Trane Ascend ACS / ACX air-cooled scroll chiller and heat pump (Symbio 800)
Trane Ascend ACS air-cooled scroll chillers and ACX air-to-water heat pumps with the Symbio 800 controller, as listed in BAS-PTS011A-EN (11/15/2024).
Also known as: ACS, ACX, Ascend ACS, Ascend ACX, Ascend air-cooled chiller, Ascend air-to-water heat pump - Chiller
Trane CenTraVac CTV-Duplex water-cooled centrifugal chiller (UC800 native Modbus)
Trane Duplex CenTraVac (two-compressor) water-cooled centrifugal chillers with the Tracer UC800 controller, as listed in the Modbus section of BAS-PTS030A-EN (12/6/2024).
Also known as: CTV-Duplex, CTVD, CenTraVac Duplex, Duplex CenTraVac UC800 - Chiller
Trane CenTraVac duplex centrifugal chiller (Symbio 800)
Trane dual-compressor (duplex) CenTraVac water-cooled centrifugal chillers fitted with the Symbio 800 controller, as listed in the Duplex tables of BAS-PTS009C-EN (12/12/2025).
Also known as: CDHF, CDHG, CDHH, CenTraVac Duplex Symbio 800 - Chiller
Trane CenTraVac simplex centrifugal chiller (Symbio 800)
Trane single-compressor (simplex) CenTraVac water-cooled centrifugal chillers fitted with the Symbio 800 controller, as listed in the Simplex tables of BAS-PTS009C-EN (12/12/2025).
Also known as: CVHE, CVHF, CVHG, CVHH, CVHL, CVHM, CVHS, CVGF, CVR, CVZA, CVXA, CenTraVac Simplex Symbio 800, CenTraVac simplex - Chiller
Trane CGAM air-cooled scroll chiller (Symbio 800)
Trane CGAM air-cooled scroll chillers with the Symbio 800 controller, as listed in BAS-PTS019A-EN (11/15/2024).
Also known as: CGAM, Trane CGAM, CGAM air-cooled scroll chiller - Chiller
Trane RTAC air-cooled helical-rotary chiller (Symbio 800)
Trane RTAC air-cooled helical-rotary chillers with the Symbio 800 controller, as listed in BAS-PTS023A-EN (11/8/2024).
Also known as: RTAC, Series R RTAC - Chiller
Trane RTAC air-cooled helical-rotary chiller (UC800 native Modbus profile)
Trane RTAC air-cooled chillers on the Tracer UC800 controller using the UC800 native Modbus map in the Modbus section of BAS-PTS032A-EN (12/6/2024). Not the same register set as the Symbio 800 RTAC list (BAS-PTS023A-EN).
Also known as: RTAC UC800 native Modbus profile, Series R RTAC UC800 native Modbus, BAS-PTS032A-EN - Chiller
Trane Series R RTHD water-cooled helical-rotary chiller (Symbio 800)
Trane Series R model RTHD water-cooled helical-rotary chillers with the Symbio 800 controller, as listed in BAS-PTS015A-EN (11/15/2024).
Also known as: RTHD, Series R RTHD - Chiller
Trane Series R RTWD water-cooled helical-rotary chiller (Symbio 800)
Trane Series R model RTWD water-cooled helical-rotary chillers with the Symbio 800 controller, as listed in BAS-PTS017A-EN (11/15/2024).
Also known as: RTWD, Series R RTWD, RTUD - Chiller
Trane Sintesis RTAF air-cooled screw chiller (Symbio 800)
Trane Sintesis RTAF air-cooled helical-rotary chillers with the Symbio 800 controller, as listed in BAS-PTS013B-EN (4/7/2026).
Also known as: RTAF, Sintesis RTAF, Sintesis air-cooled chiller - Pump (data-centre coolant distribution unit)
Trane TCDU coolant distribution unit (data-centre liquid cooling)
Trane Coolant Distribution Unit (TCDU) for direct-to-chip liquid cooling, as documented in IOM DC-SVX001A-EN (April 2025).
Also known as: TCDU, Trane CDU, Trane Coolant Distribution Unit, DC-SVX001A
Other chillers & heat pumps register maps
- Chiller
Daikin Applied Magnitude WMC-E magnetic-bearing centrifugal chiller (MicroTech controller)
Daikin Applied Magnitude WMC E-vintage water-cooled magnetic-bearing centrifugal chillers with the MicroTech unit controller and BACnet/Modbus communication module set to Modbus, per ED 19131-1.
Also known as: WMC-E, WMC E-Vintage, Magnitude WMC, Daikin WMC, ED 19131 - Chiller
Daikin Applied Pathfinder AWS air-cooled screw chiller (MicroTech controller)
Daikin Applied Pathfinder AWS air-cooled screw chillers with the MicroTech chiller unit controller and Modbus communication module, per ED 15121-13 (both application-version columns, 2507500204 and earlier / 2507500205 and later, mark the same data points).
Also known as: AWS, Pathfinder AWS, Daikin AWS, ED 15121 - Chiller
Daikin Applied ADS air-cooled global screw chiller (MicroTech controller)
Daikin Applied model ADS air-cooled global screw chillers with the MicroTech chiller unit controller and Modbus communication module, per ED 15121-13.
Also known as: ADS, Daikin ADS, Air-cooled Global Screw Chiller, ED 15121 - Chiller
Daikin Applied MicroTech II centrifugal chillers WSC/WDC/WPV/WMC/WCC/HSC/HDC/TSC (Modbus module)
McQuay/Daikin Applied water-cooled centrifugal chillers with the MicroTech II unit controller and Modbus Communication Module: WSC, WDC, WPV, WMC (magnetic bearing), WCC, HSC/HDC heat recovery and TSC Templifier, per ED 15063-2 (Dec 2005).
Also known as: WSC, WDC, WPV, WMC, WCC, HSC, HDC, TSC, McQuay centrifugal Modbus, MicroTech II chiller, ED 15063 - Chiller
Daikin Applied Trailblazer AMZ air-cooled scroll chiller (MicroTech controller)
Daikin Applied Trailblazer AMZ air-cooled scroll chillers with the MicroTech chiller unit controller and Modbus communication module, per ED 15121-13.
Also known as: AMZ, Trailblazer AMZ, Daikin AMZ, ED 15121 - Chiller (air-cooled chiller for data centres)
Vertiv Liebert HPC chiller with iCOM v4 (IntelliSlot Modbus)
Liebert HPC chillers on the iCOM v4 controller (iCOM_SC31 / iCOM_SC100 applications) with a Liebert IntelliSlot Modbus card.
Also known as: Liebert HPC, HPC chiller, Liebert HPC iCOM
All chillers & heat pumps Modbus register maps →
Source: Installation, Operation, and Maintenance: TruSense RMWH Refrigerant Monitor · PART-SVX008A-EN · rev. 2025-09-30. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.