Sensor (refrigerant leak monitor for chiller plant rooms) · Modbus register map

Trane TruSense RMWH refrigerant monitor (up to 16 points) Modbus register map

Updated 19 November 2026

Short answer

Wall-mounted sample-draw refrigerant monitor for chiller and equipment rooms that checks up to 16 points for leaks of the common HVAC refrigerants. Over Modbus RTU it exposes 16-bit holding registers: unit status, an acknowledge and reset command, per-channel gas type, ppm reading and alarm flags, and calibration dates.

This page lists 76 Modbus registers for the Trane TruSense RMWH refrigerant monitor (up to 16 points) — 2 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Trane’s own free documentation (linked below) and checked against it.

Manufacturer
Trane
Model
TruSense RMWH refrigerant monitor (up to 16 points)
Equipment type
Sensor (refrigerant leak monitor for chiller plant rooms)
Registers
76 (2 writable)
Transport
Modbus RTU
Default unit ID
Not stated
Documented addressing
Modicon 3xxxx/4xxxx (drop the prefix, subtract 1)
Also known as
TruSense, RMWH, Trane refrigerant monitor, PART-SVX008A, RMWH-SVX001
Source document
Installation, Operation, and Maintenance: TruSense RMWH Refrigerant Monitor · PART-SVX008A-EN · rev. 2025-09-30
Download CSV all columns JSON Manufacturer PDF ↗

Integration notes: Trane TruSense RMWH refrigerant monitor (up to 16 points)

Integration in brief

Select MODBUS on the Outputs > Digital tab, set the device address and baud rate, then poll holding registers 40007-40073. Each channel uses four registers: gas number, ppm, status flags, reserved.

Minimum registers to map

Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.

RegisterNameTypeWhyAccess
HR 6Unit statusBITMAP16Unit status flagsRead
HR 10Channel 1 gas concentrationUINT16Channel 1 refrigerant ppmRead
HR 11Channel 1 statusBITMAP16Channel 1 alarm flagsRead
HR 9Channel 1 gas numberUINT16Channel 1 gas typeRead
HR 14Channel 2 gas concentrationUINT16Channel 2 refrigerant ppmRead
HR 7ACK buttonUINT16Acknowledge alarmsWrite

Enable Modbus control & writes

Digital output is None by default. During initial setup (or later on the Outputs screen) open the Digital tab, select MODBUS, press Edit, enter the Device Address, choose a baud rate, set the RS485 Termination check box as needed, and press Done.

Byte order & addressing

Network setup

Watch out for

Trane TruSense RMWH refrigerant monitor (up to 16 points) Modbus registers

Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.

76 of 76 shown
Trane TruSense RMWH refrigerant monitor (up to 16 points) Modbus register map
TableAddressNameDescriptionTypeOrderScaleUnitsAccessValues / bits
HR0doc 40001Product IDTwo ASCII characters, reads "CG".UINT16Read
HR1doc 40002Firmware version 1Major version in the high byte, minor in the low byte.UINT16Read
HR2doc 40003Firmware version 2Build number (two bytes).UINT16Read
HR6doc 40007Unit statusPacked unit status flags.BITMAP16Readbit 0 = Warm-up pending; bit 1 = Operating (normal mode); bit 2 = Calibration in progress; bit 3 = Fault reported; bit 4 = Alarm (caution/warning/alarm level reached)
HR7doc 40008ACK buttonWrite 1 to acknowledge alarms.UINT16Write
HR8doc 40009RESET buttonHigh byte = action, low byte = channel (0-15) or 255 for all.UINT16Write
HR9doc 40010Channel 1 gas numberRefrigerant the channel is set to measure.UINT16Read0 = R-11; 1 = R-12; 2 = R-22; 3 = R-123; 4 = R-134A; 5 = R-401A; 6 = R-404A; 7 = R-407A; 8 = R-407C; 9 = R-407F; 10 = R-410A; 11 = R-422A; 12 = R-422D; 13 = R-427A; 14 = R-507; 15 = R-513A; 16 = R-514A; 17 = R-1233zd(E); 18 = R-1234yf; 19 = R-1234ze
HR10doc 40011Channel 1 gas concentrationUINT16ppmRead
HR11doc 40012Channel 1 statusPacked channel alarm flags.BITMAP16Readbit 0 = Caution level reached; bit 1 = Warning level reached; bit 2 = Alarm level reached; bit 3 = Beacon (caution/warning/alarm set); bit 4 = Horn (configured level set and not acknowledged); bit 5 = New (level set and not acknowledged); bit 6 = Hold (acknowledged latching alarm now below threshold); bit 7 = Fault reported
HR13doc 40014Channel 2 gas numberRefrigerant the channel is set to measure.UINT16Read0 = R-11; 1 = R-12; 2 = R-22; 3 = R-123; 4 = R-134A; 5 = R-401A; 6 = R-404A; 7 = R-407A; 8 = R-407C; 9 = R-407F; 10 = R-410A; 11 = R-422A; 12 = R-422D; 13 = R-427A; 14 = R-507; 15 = R-513A; 16 = R-514A; 17 = R-1233zd(E); 18 = R-1234yf; 19 = R-1234ze
HR14doc 40015Channel 2 gas concentrationUINT16ppmRead
HR15doc 40016Channel 2 statusPacked channel alarm flags.BITMAP16Readbit 0 = Caution level reached; bit 1 = Warning level reached; bit 2 = Alarm level reached; bit 3 = Beacon (caution/warning/alarm set); bit 4 = Horn (configured level set and not acknowledged); bit 5 = New (level set and not acknowledged); bit 6 = Hold (acknowledged latching alarm now below threshold); bit 7 = Fault reported
HR17doc 40018Channel 3 gas numberRefrigerant the channel is set to measure.UINT16Read0 = R-11; 1 = R-12; 2 = R-22; 3 = R-123; 4 = R-134A; 5 = R-401A; 6 = R-404A; 7 = R-407A; 8 = R-407C; 9 = R-407F; 10 = R-410A; 11 = R-422A; 12 = R-422D; 13 = R-427A; 14 = R-507; 15 = R-513A; 16 = R-514A; 17 = R-1233zd(E); 18 = R-1234yf; 19 = R-1234ze
HR18doc 40019Channel 3 gas concentrationUINT16ppmRead
HR19doc 40020Channel 3 statusPacked channel alarm flags.BITMAP16Readbit 0 = Caution level reached; bit 1 = Warning level reached; bit 2 = Alarm level reached; bit 3 = Beacon (caution/warning/alarm set); bit 4 = Horn (configured level set and not acknowledged); bit 5 = New (level set and not acknowledged); bit 6 = Hold (acknowledged latching alarm now below threshold); bit 7 = Fault reported
HR21doc 40022Channel 4 gas numberRefrigerant the channel is set to measure.UINT16Read0 = R-11; 1 = R-12; 2 = R-22; 3 = R-123; 4 = R-134A; 5 = R-401A; 6 = R-404A; 7 = R-407A; 8 = R-407C; 9 = R-407F; 10 = R-410A; 11 = R-422A; 12 = R-422D; 13 = R-427A; 14 = R-507; 15 = R-513A; 16 = R-514A; 17 = R-1233zd(E); 18 = R-1234yf; 19 = R-1234ze
HR22doc 40023Channel 4 gas concentrationUINT16ppmRead
HR23doc 40024Channel 4 statusPacked channel alarm flags.BITMAP16Readbit 0 = Caution level reached; bit 1 = Warning level reached; bit 2 = Alarm level reached; bit 3 = Beacon (caution/warning/alarm set); bit 4 = Horn (configured level set and not acknowledged); bit 5 = New (level set and not acknowledged); bit 6 = Hold (acknowledged latching alarm now below threshold); bit 7 = Fault reported
HR25doc 40026Channel 5 gas numberRefrigerant the channel is set to measure.UINT16Read0 = R-11; 1 = R-12; 2 = R-22; 3 = R-123; 4 = R-134A; 5 = R-401A; 6 = R-404A; 7 = R-407A; 8 = R-407C; 9 = R-407F; 10 = R-410A; 11 = R-422A; 12 = R-422D; 13 = R-427A; 14 = R-507; 15 = R-513A; 16 = R-514A; 17 = R-1233zd(E); 18 = R-1234yf; 19 = R-1234ze
HR26doc 40027Channel 5 gas concentrationUINT16ppmRead
HR27doc 40028Channel 5 statusPacked channel alarm flags.BITMAP16Readbit 0 = Caution level reached; bit 1 = Warning level reached; bit 2 = Alarm level reached; bit 3 = Beacon (caution/warning/alarm set); bit 4 = Horn (configured level set and not acknowledged); bit 5 = New (level set and not acknowledged); bit 6 = Hold (acknowledged latching alarm now below threshold); bit 7 = Fault reported
HR29doc 40030Channel 6 gas numberRefrigerant the channel is set to measure.UINT16Read0 = R-11; 1 = R-12; 2 = R-22; 3 = R-123; 4 = R-134A; 5 = R-401A; 6 = R-404A; 7 = R-407A; 8 = R-407C; 9 = R-407F; 10 = R-410A; 11 = R-422A; 12 = R-422D; 13 = R-427A; 14 = R-507; 15 = R-513A; 16 = R-514A; 17 = R-1233zd(E); 18 = R-1234yf; 19 = R-1234ze
HR30doc 40031Channel 6 gas concentrationUINT16ppmRead
HR31doc 40032Channel 6 statusPacked channel alarm flags.BITMAP16Readbit 0 = Caution level reached; bit 1 = Warning level reached; bit 2 = Alarm level reached; bit 3 = Beacon (caution/warning/alarm set); bit 4 = Horn (configured level set and not acknowledged); bit 5 = New (level set and not acknowledged); bit 6 = Hold (acknowledged latching alarm now below threshold); bit 7 = Fault reported
HR33doc 40034Channel 7 gas numberRefrigerant the channel is set to measure.UINT16Read0 = R-11; 1 = R-12; 2 = R-22; 3 = R-123; 4 = R-134A; 5 = R-401A; 6 = R-404A; 7 = R-407A; 8 = R-407C; 9 = R-407F; 10 = R-410A; 11 = R-422A; 12 = R-422D; 13 = R-427A; 14 = R-507; 15 = R-513A; 16 = R-514A; 17 = R-1233zd(E); 18 = R-1234yf; 19 = R-1234ze
HR34doc 40035Channel 7 gas concentrationUINT16ppmRead
HR35doc 40036Channel 7 statusPacked channel alarm flags.BITMAP16Readbit 0 = Caution level reached; bit 1 = Warning level reached; bit 2 = Alarm level reached; bit 3 = Beacon (caution/warning/alarm set); bit 4 = Horn (configured level set and not acknowledged); bit 5 = New (level set and not acknowledged); bit 6 = Hold (acknowledged latching alarm now below threshold); bit 7 = Fault reported
HR37doc 40038Channel 8 gas numberRefrigerant the channel is set to measure.UINT16Read0 = R-11; 1 = R-12; 2 = R-22; 3 = R-123; 4 = R-134A; 5 = R-401A; 6 = R-404A; 7 = R-407A; 8 = R-407C; 9 = R-407F; 10 = R-410A; 11 = R-422A; 12 = R-422D; 13 = R-427A; 14 = R-507; 15 = R-513A; 16 = R-514A; 17 = R-1233zd(E); 18 = R-1234yf; 19 = R-1234ze
HR38doc 40039Channel 8 gas concentrationUINT16ppmRead
HR39doc 40040Channel 8 statusPacked channel alarm flags.BITMAP16Readbit 0 = Caution level reached; bit 1 = Warning level reached; bit 2 = Alarm level reached; bit 3 = Beacon (caution/warning/alarm set); bit 4 = Horn (configured level set and not acknowledged); bit 5 = New (level set and not acknowledged); bit 6 = Hold (acknowledged latching alarm now below threshold); bit 7 = Fault reported
HR41doc 40042Channel 9 gas numberRefrigerant the channel is set to measure.UINT16Read0 = R-11; 1 = R-12; 2 = R-22; 3 = R-123; 4 = R-134A; 5 = R-401A; 6 = R-404A; 7 = R-407A; 8 = R-407C; 9 = R-407F; 10 = R-410A; 11 = R-422A; 12 = R-422D; 13 = R-427A; 14 = R-507; 15 = R-513A; 16 = R-514A; 17 = R-1233zd(E); 18 = R-1234yf; 19 = R-1234ze
HR42doc 40043Channel 9 gas concentrationUINT16ppmRead
HR43doc 40044Channel 9 statusPacked channel alarm flags.BITMAP16Readbit 0 = Caution level reached; bit 1 = Warning level reached; bit 2 = Alarm level reached; bit 3 = Beacon (caution/warning/alarm set); bit 4 = Horn (configured level set and not acknowledged); bit 5 = New (level set and not acknowledged); bit 6 = Hold (acknowledged latching alarm now below threshold); bit 7 = Fault reported
HR45doc 40046Channel 10 gas numberRefrigerant the channel is set to measure.UINT16Read0 = R-11; 1 = R-12; 2 = R-22; 3 = R-123; 4 = R-134A; 5 = R-401A; 6 = R-404A; 7 = R-407A; 8 = R-407C; 9 = R-407F; 10 = R-410A; 11 = R-422A; 12 = R-422D; 13 = R-427A; 14 = R-507; 15 = R-513A; 16 = R-514A; 17 = R-1233zd(E); 18 = R-1234yf; 19 = R-1234ze
HR46doc 40047Channel 10 gas concentrationUINT16ppmRead
HR47doc 40048Channel 10 statusPacked channel alarm flags.BITMAP16Readbit 0 = Caution level reached; bit 1 = Warning level reached; bit 2 = Alarm level reached; bit 3 = Beacon (caution/warning/alarm set); bit 4 = Horn (configured level set and not acknowledged); bit 5 = New (level set and not acknowledged); bit 6 = Hold (acknowledged latching alarm now below threshold); bit 7 = Fault reported
HR49doc 40050Channel 11 gas numberRefrigerant the channel is set to measure.UINT16Read0 = R-11; 1 = R-12; 2 = R-22; 3 = R-123; 4 = R-134A; 5 = R-401A; 6 = R-404A; 7 = R-407A; 8 = R-407C; 9 = R-407F; 10 = R-410A; 11 = R-422A; 12 = R-422D; 13 = R-427A; 14 = R-507; 15 = R-513A; 16 = R-514A; 17 = R-1233zd(E); 18 = R-1234yf; 19 = R-1234ze
HR50doc 40051Channel 11 gas concentrationUINT16ppmRead
HR51doc 40052Channel 11 statusPacked channel alarm flags.BITMAP16Readbit 0 = Caution level reached; bit 1 = Warning level reached; bit 2 = Alarm level reached; bit 3 = Beacon (caution/warning/alarm set); bit 4 = Horn (configured level set and not acknowledged); bit 5 = New (level set and not acknowledged); bit 6 = Hold (acknowledged latching alarm now below threshold); bit 7 = Fault reported
HR53doc 40054Channel 12 gas numberRefrigerant the channel is set to measure.UINT16Read0 = R-11; 1 = R-12; 2 = R-22; 3 = R-123; 4 = R-134A; 5 = R-401A; 6 = R-404A; 7 = R-407A; 8 = R-407C; 9 = R-407F; 10 = R-410A; 11 = R-422A; 12 = R-422D; 13 = R-427A; 14 = R-507; 15 = R-513A; 16 = R-514A; 17 = R-1233zd(E); 18 = R-1234yf; 19 = R-1234ze
HR54doc 40055Channel 12 gas concentrationUINT16ppmRead
HR55doc 40056Channel 12 statusPacked channel alarm flags.BITMAP16Readbit 0 = Caution level reached; bit 1 = Warning level reached; bit 2 = Alarm level reached; bit 3 = Beacon (caution/warning/alarm set); bit 4 = Horn (configured level set and not acknowledged); bit 5 = New (level set and not acknowledged); bit 6 = Hold (acknowledged latching alarm now below threshold); bit 7 = Fault reported
HR57doc 40058Channel 13 gas numberRefrigerant the channel is set to measure.UINT16Read0 = R-11; 1 = R-12; 2 = R-22; 3 = R-123; 4 = R-134A; 5 = R-401A; 6 = R-404A; 7 = R-407A; 8 = R-407C; 9 = R-407F; 10 = R-410A; 11 = R-422A; 12 = R-422D; 13 = R-427A; 14 = R-507; 15 = R-513A; 16 = R-514A; 17 = R-1233zd(E); 18 = R-1234yf; 19 = R-1234ze
HR58doc 40059Channel 13 gas concentrationUINT16ppmRead
HR59doc 40060Channel 13 statusPacked channel alarm flags.BITMAP16Readbit 0 = Caution level reached; bit 1 = Warning level reached; bit 2 = Alarm level reached; bit 3 = Beacon (caution/warning/alarm set); bit 4 = Horn (configured level set and not acknowledged); bit 5 = New (level set and not acknowledged); bit 6 = Hold (acknowledged latching alarm now below threshold); bit 7 = Fault reported
HR61doc 40062Channel 14 gas numberRefrigerant the channel is set to measure.UINT16Read0 = R-11; 1 = R-12; 2 = R-22; 3 = R-123; 4 = R-134A; 5 = R-401A; 6 = R-404A; 7 = R-407A; 8 = R-407C; 9 = R-407F; 10 = R-410A; 11 = R-422A; 12 = R-422D; 13 = R-427A; 14 = R-507; 15 = R-513A; 16 = R-514A; 17 = R-1233zd(E); 18 = R-1234yf; 19 = R-1234ze
HR62doc 40063Channel 14 gas concentrationUINT16ppmRead
HR63doc 40064Channel 14 statusPacked channel alarm flags.BITMAP16Readbit 0 = Caution level reached; bit 1 = Warning level reached; bit 2 = Alarm level reached; bit 3 = Beacon (caution/warning/alarm set); bit 4 = Horn (configured level set and not acknowledged); bit 5 = New (level set and not acknowledged); bit 6 = Hold (acknowledged latching alarm now below threshold); bit 7 = Fault reported
HR65doc 40066Channel 15 gas numberRefrigerant the channel is set to measure.UINT16Read0 = R-11; 1 = R-12; 2 = R-22; 3 = R-123; 4 = R-134A; 5 = R-401A; 6 = R-404A; 7 = R-407A; 8 = R-407C; 9 = R-407F; 10 = R-410A; 11 = R-422A; 12 = R-422D; 13 = R-427A; 14 = R-507; 15 = R-513A; 16 = R-514A; 17 = R-1233zd(E); 18 = R-1234yf; 19 = R-1234ze
HR66doc 40067Channel 15 gas concentrationUINT16ppmRead
HR67doc 40068Channel 15 statusPacked channel alarm flags.BITMAP16Readbit 0 = Caution level reached; bit 1 = Warning level reached; bit 2 = Alarm level reached; bit 3 = Beacon (caution/warning/alarm set); bit 4 = Horn (configured level set and not acknowledged); bit 5 = New (level set and not acknowledged); bit 6 = Hold (acknowledged latching alarm now below threshold); bit 7 = Fault reported
HR69doc 40070Channel 16 gas numberRefrigerant the channel is set to measure.UINT16Read0 = R-11; 1 = R-12; 2 = R-22; 3 = R-123; 4 = R-134A; 5 = R-401A; 6 = R-404A; 7 = R-407A; 8 = R-407C; 9 = R-407F; 10 = R-410A; 11 = R-422A; 12 = R-422D; 13 = R-427A; 14 = R-507; 15 = R-513A; 16 = R-514A; 17 = R-1233zd(E); 18 = R-1234yf; 19 = R-1234ze
HR70doc 40071Channel 16 gas concentrationUINT16ppmRead
HR71doc 40072Channel 16 statusPacked channel alarm flags.BITMAP16Readbit 0 = Caution level reached; bit 1 = Warning level reached; bit 2 = Alarm level reached; bit 3 = Beacon (caution/warning/alarm set); bit 4 = Horn (configured level set and not acknowledged); bit 5 = New (level set and not acknowledged); bit 6 = Hold (acknowledged latching alarm now below threshold); bit 7 = Fault reported
HR89doc 40090Next calibration timeDays since 1 Jan 1970.UINT16dRead
HR90doc 40091Zero calibration timeDays since 1 Jan 1970.UINT16dRead
HR91doc 40092Span calibration time #00 (R-11)Days since 1 Jan 1970 of the last span calibration for this gas.UINT16dRead
HR92doc 40093Span calibration time #01 (R-12)Days since 1 Jan 1970 of the last span calibration for this gas.UINT16dRead
HR93doc 40094Span calibration time #02 (R-22)Days since 1 Jan 1970 of the last span calibration for this gas.UINT16dRead
HR94doc 40095Span calibration time #03 (R-123)Days since 1 Jan 1970 of the last span calibration for this gas.UINT16dRead
HR95doc 40096Span calibration time #04 (R-134A)Days since 1 Jan 1970 of the last span calibration for this gas.UINT16dRead
HR96doc 40097Span calibration time #05 (R-401A)Days since 1 Jan 1970 of the last span calibration for this gas.UINT16dRead
HR97doc 40098Span calibration time #06 (R-404A)Days since 1 Jan 1970 of the last span calibration for this gas.UINT16dRead
HR98doc 40099Span calibration time #07 (R-407A)Days since 1 Jan 1970 of the last span calibration for this gas.UINT16dRead
HR99doc 40100Span calibration time #08 (R-407C)Days since 1 Jan 1970 of the last span calibration for this gas.UINT16dRead
HR100doc 40101Span calibration time #09 (R-407F)Days since 1 Jan 1970 of the last span calibration for this gas.UINT16dRead
HR101doc 40102Span calibration time #10 (R-410A)Days since 1 Jan 1970 of the last span calibration for this gas.UINT16dRead
HR102doc 40103Span calibration time #11 (R-422A)Days since 1 Jan 1970 of the last span calibration for this gas.UINT16dRead
HR103doc 40104Span calibration time #12 (R-422D)Days since 1 Jan 1970 of the last span calibration for this gas.UINT16dRead
HR104doc 40105Span calibration time #13 (R-427A)Days since 1 Jan 1970 of the last span calibration for this gas.UINT16dRead
HR105doc 40106Span calibration time #14 (R-507)Days since 1 Jan 1970 of the last span calibration for this gas.UINT16dRead
HR106doc 40107Span calibration time #15 (R-513A)Days since 1 Jan 1970 of the last span calibration for this gas.UINT16dRead
HR107doc 40108Span calibration time #16 (R-514A)Days since 1 Jan 1970 of the last span calibration for this gas.UINT16dRead
HR108doc 40109Span calibration time #17 (R-1233zd(E))Days since 1 Jan 1970 of the last span calibration for this gas.UINT16dRead
HR109doc 40110Span calibration time #18 (R-1234yf)Days since 1 Jan 1970 of the last span calibration for this gas.UINT16dRead
HR110doc 40111Span calibration time #19 (R-1234ze)Days since 1 Jan 1970 of the last span calibration for this gas.UINT16dRead

Notes on this map

Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.

Questions about the Trane TruSense RMWH refrigerant monitor (up to 16 points)

What Modbus registers does the Trane TruSense RMWH refrigerant monitor (up to 16 points) have?

This map lists 76 registers: 76 holding registers. 2 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.

Are the Trane TruSense RMWH refrigerant monitor (up to 16 points) Modbus addresses 0-based or 1-based?

The manufacturer's document numbers registers Modicon 3xxxx/4xxxx (drop the prefix, subtract 1). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. The register table's 'Index' column prints Modicon holding registers from 40001, so 40001 is wire address 0 and channel 1 gas concentration 40011 is wire address 10.

What are the minimum Modbus registers to integrate the Trane TruSense RMWH refrigerant monitor (up to 16 points)?

Start with HR 6 Unit status (Unit status flags); HR 10 Channel 1 gas concentration (Channel 1 refrigerant ppm); HR 11 Channel 1 status (Channel 1 alarm flags); HR 9 Channel 1 gas number (Channel 1 gas type); HR 14 Channel 2 gas concentration (Channel 2 refrigerant ppm); HR 7 ACK button (Acknowledge alarms).

How do I enable Modbus control of the Trane TruSense RMWH refrigerant monitor (up to 16 points)?

Digital output is None by default. During initial setup (or later on the Outputs screen) open the Digital tab, select MODBUS, press Edit, enter the Device Address, choose a baud rate, set the RS485 Termination check box as needed, and press Done.

Where is the official Trane TruSense RMWH refrigerant monitor (up to 16 points) Modbus documentation?

The source is Installation, Operation, and Maintenance: TruSense RMWH Refrigerant Monitor (PART-SVX008A-EN), revision 2025-09-30, published free by Trane at https://elibrary.tranetechnologies.com/public/commercial-hvac/Literature/Installation%20Operation%20and%20Maintenance/PART-SVX008A-EN_09302025.pdf.

More Trane Modbus register maps

Other chillers & heat pumps register maps

All chillers & heat pumps Modbus register maps →

Source: Installation, Operation, and Maintenance: TruSense RMWH Refrigerant Monitor · PART-SVX008A-EN · rev. 2025-09-30. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.