Chiller · Modbus register map

Trane RTAC air-cooled helical-rotary chiller (UC800 native Modbus profile) Modbus register map

Updated 19 November 2026

Short answer

Trane's RTAC is an air-cooled helical-rotary (screw) chiller. On the Tracer UC800 controller it offers a compact native Modbus map in which every point is one 16-bit register with a fixed SI scaling per register type (temperatures in 0.01 °C, pressures in 0.1 kPa absolute, percent in 0.005 % steps). The map covers BAS commands, water and refrigerant temperatures and pressures, oil values, starter currents and voltages, AFD values and status flags.

This page lists 87 Modbus registers for the Trane RTAC air-cooled helical-rotary chiller (UC800 native Modbus profile) — 5 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Trane’s own free documentation (linked below) and checked against it.

Manufacturer
Trane
Model
RTAC air-cooled helical-rotary chiller (UC800 native Modbus profile)
Equipment type
Chiller
Registers
87 (5 writable)
Transport
Modbus RTU, Modbus TCP
Default unit ID
Not stated
Documented addressing
Modicon 3xxxx/4xxxx (drop the prefix, subtract 1)
Also known as
RTAC UC800 native Modbus profile, Series R RTAC UC800 native Modbus, BAS-PTS032A-EN
Source document
Symbio 800 Integration Points List, BACnet/Modbus, RTAC (UC800) · BAS-PTS032A-EN · rev. 2024-12-06
Download CSV all columns JSON Manufacturer PDF ↗

Integration notes: Trane RTAC air-cooled helical-rotary chiller (UC800 native Modbus profile)

Integration in brief

Write 40001 (auto/stop), 40002 (mode) and 40003 (chilled-water setpoint, 0.01 °C) and poll the 3xxxx input registers with function 04. Every value is a single register; apply the per-type scale from the object-format table.

Minimum registers to map

Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.

RegisterNameTypeWhyAccess
IR 85Chiller Running IndicatorUINT16Chiller running indicatorRead
IR 96Chiller Running StatusUINT16Chiller running statusRead
IR 33Evaporator Leaving Water TempINT16Evaporator leaving water temperatureRead
IR 2Active Chilled Water SetpointINT16Active chilled water setpointRead
IR 4Actual Running CapacityINT16Actual running capacityRead
IR 93Alarm PresentUINT16Alarm presentRead
HR 0BAS Chiller Auto Stop CommandUINT16Chiller auto/stop commandRead/write
HR 1BAS Chiller Mode CommandUINT16Chiller mode commandRead/write
HR 2Chilled Water SetpointINT16Chilled water setpoint (BAS)Read/write
HR 7Remote Diagnostic Reset CommandUINT16Diagnostic resetRead/write

Enable Modbus control & writes

The points list does not describe setup; it names BAS-SVP083*-EN as its reference integration guide for selecting Modbus on the controller.

Byte order & addressing

Network setup

Watch out for

Trane RTAC air-cooled helical-rotary chiller (UC800 native Modbus profile) Modbus registers

Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.

87 of 87 shown
Trane RTAC air-cooled helical-rotary chiller (UC800 native Modbus profile) Modbus register map
TableAddressNameDescriptionTypeOrderScaleUnitsAccessValues / bits
IR0doc 30001Software TypeUINT16Read
IR1doc 30002Software RevisionUINT16Read
IR2doc 30003Active Chilled Water Setpoint0.01 °C per count.INT16× 0.01°CRead
IR3doc 30004Active Current Limit SetpointPercent type: 20,000 = 100 %.INT16× 0.005%Read
IR4doc 30005Actual Running CapacityPercent type: 20,000 = 100 %.INT16× 0.005%Read
IR5doc 30006Evaporator Refrigerant Pressure - Ckt1Absolute pressure, 0.1 kPa per count.UINT16× 0.1kPaRead
IR6doc 30007Evaporator Refrigerant Pressure - Ckt 2Absolute pressure, 0.1 kPa per count.UINT16× 0.1kPaRead
IR7doc 30008Evaporator Saturated Refrigerant Temperature- Ckt 10.01 °C per count.INT16× 0.01°CRead
IR8doc 30009Evaporator Saturated Refrigerant Temperature- Ckt 20.01 °C per count.INT16× 0.01°CRead
IR9doc 30010Condenser Refrigerant Pressure - Ckt 1Absolute pressure, 0.1 kPa per count.UINT16× 0.1kPaRead
IR10doc 30011Condenser Refrigerant Pressure - Ckt 2Absolute pressure, 0.1 kPa per count.UINT16× 0.1kPaRead
IR11doc 30012Condenser Saturated Refrigerant Temperature - Ckt 10.01 °C per count.INT16× 0.01°CRead
IR12doc 30013Condenser Saturated Refrigerant Temperature - Ckt 20.01 °C per count.INT16× 0.01°CRead
IR13doc 30014Local Atmospheric PressureAbsolute pressure, 0.1 kPa per count.UINT16× 0.1kPaRead
IR30doc 30031Airflow Percentage- Circuit 1Percent type: 20,000 = 100 %.INT16× 0.005%Read
IR31doc 30032Airflow Percentage- Circuit 2Percent type: 20,000 = 100 %.INT16× 0.005%Read
IR32doc 30033Evaporator Entering Water Temp0.01 °C per count.INT16× 0.01°CRead
IR33doc 30034Evaporator Leaving Water Temp0.01 °C per count.INT16× 0.01°CRead
IR34doc 30035High Side Oil Pressure - Compressor 1AAbsolute pressure, 0.1 kPa per count.UINT16× 0.1kPaRead
IR35doc 30036High Side Oil Pressure - Compressor 1BAbsolute pressure, 0.1 kPa per count.UINT16× 0.1kPaRead
IR36doc 30037High Side Oil Pressure - Compressor 2AAbsolute pressure, 0.1 kPa per count.UINT16× 0.1kPaRead
IR37doc 30038High Side Oil Pressure - Compressor 2BAbsolute pressure, 0.1 kPa per count.UINT16× 0.1kPaRead
IR38doc 30039Oil Temp - Compressor 1A0.01 °C per count.INT16× 0.01°CRead
IR39doc 30040Oil Temp - Compressor 1B0.01 °C per count.INT16× 0.01°CRead
IR40doc 30041Oil Temp - Compressor 2A0.01 °C per count.INT16× 0.01°CRead
IR41doc 30042Oil Temp - Compressor 2B0.01 °C per count.INT16× 0.01°CRead
IR42doc 30043Outdoor Air Temperature0.01 °C per count.INT16× 0.01°CRead
IR43doc 30044Motor Voltage AB Starter 1AUINT16VRead
IR44doc 30045Motor Voltage AB Starter 1BUINT16VRead
IR45doc 30046Motor Voltage AB Starter 2AUINT16VRead
IR46doc 30047Motor Current L1 Starter 1AUINT16ARead
IR47doc 30048Motor Current L2 Starter 1AUINT16ARead
IR48doc 30049Motor Current L3 Starter 1AUINT16ARead
IR49doc 30050Motor Current L1 Starter 1BUINT16ARead
IR50doc 30051Motor Current L2 Starter 1BUINT16ARead
IR51doc 30052Motor Current L3 Starter 1BUINT16ARead
IR52doc 30053Motor Current L1 Starter 2AUINT16ARead
IR53doc 30054Motor Current L2 Starter 2AUINT16ARead
IR54doc 30055Motor Current L3 Starter 2AUINT16ARead
IR55doc 30056Motor Current L1 Starter 2BUINT16ARead
IR56doc 30057Motor Current L2 Starter 2BUINT16ARead
IR57doc 30058Motor Current L3 Starter 2BUINT16ARead
IR58doc 30059Motor Current L1 % RLA Starter 1APercent type: 20,000 = 100 %.INT16× 0.005%Read
IR59doc 30060Motor Current L2 % RLA Starter 1APercent type: 20,000 = 100 %.INT16× 0.005%Read
IR60doc 30061Motor Current L3 % RLA Starter 1APercent type: 20,000 = 100 %.INT16× 0.005%Read
IR61doc 30062Motor Current L1 % RLA Starter 1BPercent type: 20,000 = 100 %.INT16× 0.005%Read
IR62doc 30063Motor Current L2 % RLA Starter 1BPercent type: 20,000 = 100 %.INT16× 0.005%Read
IR63doc 30064Motor Current L3 % RLA Starter 1BPercent type: 20,000 = 100 %.INT16× 0.005%Read
IR64doc 30065Motor Current L1 % RLA Starter 2APercent type: 20,000 = 100 %.INT16× 0.005%Read
IR65doc 30066Motor Current L2 % RLA Starter 2APercent type: 20,000 = 100 %.INT16× 0.005%Read
IR66doc 30067Motor Current L3 % RLA Starter 2APercent type: 20,000 = 100 %.INT16× 0.005%Read
IR67doc 30068Motor Current L1 % RLA Starter 2BPercent type: 20,000 = 100 %.INT16× 0.005%Read
IR68doc 30069Motor Current L2 % RLA Starter 2BPercent type: 20,000 = 100 %.INT16× 0.005%Read
IR69doc 30070Motor Current L3 % RLA Starter 2BPercent type: 20,000 = 100 %.INT16× 0.005%Read
IR74doc 30075Output Power AFD 1AUINT16kWRead
IR75doc 30076Output Power AFD 2AUINT16kWRead
IR76doc 30077Discharge Temperature Cprsr 1A0.01 °C per count.INT16× 0.01°CRead
IR77doc 30078Discharge Temperature Cprsr 2A0.01 °C per count.INT16× 0.01°CRead
IR78doc 30079Frequency Command Cprsr 1AUINT16× 0.1HzRead
IR79doc 30080Frequency Command Cprsr 2AUINT16× 0.1HzRead
IR80doc 30081Average Motor Current % RLA AFD 1APercent type: 20,000 = 100 %.INT16× 0.005%Read
IR81doc 30082Average Motor Current % RLA AFD 2APercent type: 20,000 = 100 %.INT16× 0.005%Read
IR82doc 30083Run EnabledUINT16Read0 = False/Off/No/Disabled/Stop; 1 = True/On/Yes/Enabled/Auto
IR83doc 30084Local Setpoint ControlUINT16Read0 = False/Off/No/Disabled/Stop; 1 = True/On/Yes/Enabled/Auto
IR84doc 30085Chiller Limit Mode IndicatorUINT16Read0 = False/Off/No/Disabled/Stop; 1 = True/On/Yes/Enabled/Auto
IR85doc 30086Chiller Running IndicatorUINT16Read0 = False/Off/No/Disabled/Stop; 1 = True/On/Yes/Enabled/Auto
IR86doc 30087Maximum CapacityUINT16Read0 = False/Off/No/Disabled/Stop; 1 = True/On/Yes/Enabled/Auto
IR87doc 30088Compressor 1A RunningUINT16Read0 = False/Off/No/Disabled/Stop; 1 = True/On/Yes/Enabled/Auto
IR88doc 30089Compressor 1B RunningUINT16Read0 = False/Off/No/Disabled/Stop; 1 = True/On/Yes/Enabled/Auto
IR89doc 30090Compressor 2A RunningUINT16Read0 = False/Off/No/Disabled/Stop; 1 = True/On/Yes/Enabled/Auto
IR90doc 30091Compressor 2B RunningUINT16Read0 = False/Off/No/Disabled/Stop; 1 = True/On/Yes/Enabled/Auto
IR91doc 30092Evaporator Water Pump CommandUINT16Read0 = False/Off/No/Disabled/Stop; 1 = True/On/Yes/Enabled/Auto
IR92doc 30093Evaporator Water Flow StatusUINT16Read0 = False/Off/No/Disabled/Stop; 1 = True/On/Yes/Enabled/Auto
IR93doc 30094Alarm PresentUINT16Read0 = False/Off/No/Disabled/Stop; 1 = True/On/Yes/Enabled/Auto
IR94doc 30095Shutdown Alarm PresentUINT16Read0 = False/Off/No/Disabled/Stop; 1 = True/On/Yes/Enabled/Auto
IR96doc 30097Chiller Running StatusUINT16Read0 = Not running; 1 = Starting; 2 = Running; 3 = Stopping
IR97doc 30098Operating ModeUINT16Read0 = Cool; 2 = Ice
IR98doc 30099Refrigerant TypeUINT16Read4 = R134a; 14 = R513A
IR99doc 30100Model InformationUINT16Read0 = RTA
IR100doc 30101Cooling TypeUINT16Read1 = Air Cooled
IR101doc 30102Manufacturing LocationUINT16Read2 = Pueblo; 3 = Charmes; 13 = Curitiba; 14 = Taicang
IR102doc 30103Last Diagnostic CodeUINT16Read
HR0doc 40001BAS Chiller Auto Stop CommandUINT16Read/write0 = Stop; 1 = Auto
HR1doc 40002BAS Chiller Mode CommandUINT16Read/write0 = Cool; 2 = Ice
HR2doc 40003Chilled Water Setpoint0.01 °C per count.INT16× 0.01°CRead/write
HR3doc 40004Current Limit SetpointPercent type: 20,000 = 100 %.INT16× 0.005%Read/write
HR7doc 40008Remote Diagnostic Reset CommandUINT16Read/write0 = False (no reset); 1 = True (can reset)

Notes on this map

Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.

Questions about the Trane RTAC air-cooled helical-rotary chiller (UC800 native Modbus profile)

What Modbus registers does the Trane RTAC air-cooled helical-rotary chiller (UC800 native Modbus profile) have?

This map lists 87 registers: 82 input registers, 5 holding registers. 5 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.

Are the Trane RTAC air-cooled helical-rotary chiller (UC800 native Modbus profile) Modbus addresses 0-based or 1-based?

The manufacturer's document numbers registers Modicon 3xxxx/4xxxx (drop the prefix, subtract 1). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. The list prints Modicon register numbers: 4xxxx are holding registers and 3xxxx input registers, so 40001 is holding register address 0 and 30034 is input register address 33.

What are the minimum Modbus registers to integrate the Trane RTAC air-cooled helical-rotary chiller (UC800 native Modbus profile)?

Start with IR 85 Chiller Running Indicator (Chiller running indicator); IR 96 Chiller Running Status (Chiller running status); IR 33 Evaporator Leaving Water Temp (Evaporator leaving water temperature); IR 2 Active Chilled Water Setpoint (Active chilled water setpoint); IR 4 Actual Running Capacity (Actual running capacity); IR 93 Alarm Present (Alarm present); HR 0 BAS Chiller Auto Stop Command (Chiller auto/stop command); HR 1 BAS Chiller Mode Command (Chiller mode command); HR 2 Chilled Water Setpoint (Chilled water setpoint (BAS)); HR 7 Remote Diagnostic Reset Command (Diagnostic reset).

How do I enable Modbus control of the Trane RTAC air-cooled helical-rotary chiller (UC800 native Modbus profile)?

The points list does not describe setup; it names BAS-SVP083*-EN as its reference integration guide for selecting Modbus on the controller.

Where is the official Trane RTAC air-cooled helical-rotary chiller (UC800 native Modbus profile) Modbus documentation?

The source is Symbio 800 Integration Points List, BACnet/Modbus, RTAC (UC800) (BAS-PTS032A-EN), revision 2024-12-06, published free by Trane at https://elibrary.tranetechnologies.com/public/commercial-hvac/Literature/Points%20List/BAS-PTS032A-EN_12062024.pdf.

More Trane Modbus register maps

Other chillers & heat pumps register maps

All chillers & heat pumps Modbus register maps →

Source: Symbio 800 Integration Points List, BACnet/Modbus, RTAC (UC800) · BAS-PTS032A-EN · rev. 2024-12-06. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.