- RTAC air-cooled helical-rotary chiller (UC800 native Modbus profile)
Chiller · Modbus register map
Trane RTAC air-cooled helical-rotary chiller (UC800 native Modbus profile) Modbus register map
Updated 19 November 2026
Trane's RTAC is an air-cooled helical-rotary (screw) chiller. On the Tracer UC800 controller it offers a compact native Modbus map in which every point is one 16-bit register with a fixed SI scaling per register type (temperatures in 0.01 °C, pressures in 0.1 kPa absolute, percent in 0.005 % steps). The map covers BAS commands, water and refrigerant temperatures and pressures, oil values, starter currents and voltages, AFD values and status flags.
This page lists 87 Modbus registers for the Trane RTAC air-cooled helical-rotary chiller (UC800 native Modbus profile) — 5 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Trane’s own free documentation (linked below) and checked against it.
- Manufacturer
- Trane
- Model
- RTAC air-cooled helical-rotary chiller (UC800 native Modbus profile)
- Equipment type
- Chiller
- Registers
- 87 (5 writable)
- Transport
- Modbus RTU, Modbus TCP
- Default unit ID
- Not stated
- Documented addressing
- Modicon 3xxxx/4xxxx (drop the prefix, subtract 1)
- Also known as
- RTAC UC800 native Modbus profile, Series R RTAC UC800 native Modbus, BAS-PTS032A-EN
Integration notes: Trane RTAC air-cooled helical-rotary chiller (UC800 native Modbus profile)
Write 40001 (auto/stop), 40002 (mode) and 40003 (chilled-water setpoint, 0.01 °C) and poll the 3xxxx input registers with function 04. Every value is a single register; apply the per-type scale from the object-format table.
Minimum registers to map
Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.
| Register | Name | Type | Why | Access |
|---|---|---|---|---|
| IR 85 | Chiller Running Indicator | UINT16 | Chiller running indicator | Read |
| IR 96 | Chiller Running Status | UINT16 | Chiller running status | Read |
| IR 33 | Evaporator Leaving Water Temp | INT16 | Evaporator leaving water temperature | Read |
| IR 2 | Active Chilled Water Setpoint | INT16 | Active chilled water setpoint | Read |
| IR 4 | Actual Running Capacity | INT16 | Actual running capacity | Read |
| IR 93 | Alarm Present | UINT16 | Alarm present | Read |
| HR 0 | BAS Chiller Auto Stop Command | UINT16 | Chiller auto/stop command | Read/write |
| HR 1 | BAS Chiller Mode Command | UINT16 | Chiller mode command | Read/write |
| HR 2 | Chilled Water Setpoint | INT16 | Chilled water setpoint (BAS) | Read/write |
| HR 7 | Remote Diagnostic Reset Command | UINT16 | Diagnostic reset | Read/write |
Enable Modbus control & writes
The points list does not describe setup; it names BAS-SVP083*-EN as its reference integration guide for selecting Modbus on the controller.
Byte order & addressing
- Percent registers count in 0.005 % steps (20,000 = 100 %).
- Temperatures are signed hundredths of a degree Celsius; pressures are tenths of a kPa absolute (subtract atmospheric pressure, also published at 30014, for gauge).
Network setup
- Unit address, baud and TCP settings are set in the controller's protocol configuration; the list gives no defaults.
Watch out for
- Mode command 40002 accepts only 0 = Cool and 2 = Ice on this chiller.
Trane RTAC air-cooled helical-rotary chiller (UC800 native Modbus profile) Modbus registers
Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.
| Table | Address | Name | Description | Type | Order | Scale | Units | Access | Values / bits |
|---|---|---|---|---|---|---|---|---|---|
| IR | 0doc 30001 | Software Type | UINT16 | Read | |||||
| IR | 1doc 30002 | Software Revision | UINT16 | Read | |||||
| IR | 2doc 30003 | Active Chilled Water Setpoint | 0.01 °C per count. | INT16 | × 0.01 | °C | Read | ||
| IR | 3doc 30004 | Active Current Limit Setpoint | Percent type: 20,000 = 100 %. | INT16 | × 0.005 | % | Read | ||
| IR | 4doc 30005 | Actual Running Capacity | Percent type: 20,000 = 100 %. | INT16 | × 0.005 | % | Read | ||
| IR | 5doc 30006 | Evaporator Refrigerant Pressure - Ckt1 | Absolute pressure, 0.1 kPa per count. | UINT16 | × 0.1 | kPa | Read | ||
| IR | 6doc 30007 | Evaporator Refrigerant Pressure - Ckt 2 | Absolute pressure, 0.1 kPa per count. | UINT16 | × 0.1 | kPa | Read | ||
| IR | 7doc 30008 | Evaporator Saturated Refrigerant Temperature- Ckt 1 | 0.01 °C per count. | INT16 | × 0.01 | °C | Read | ||
| IR | 8doc 30009 | Evaporator Saturated Refrigerant Temperature- Ckt 2 | 0.01 °C per count. | INT16 | × 0.01 | °C | Read | ||
| IR | 9doc 30010 | Condenser Refrigerant Pressure - Ckt 1 | Absolute pressure, 0.1 kPa per count. | UINT16 | × 0.1 | kPa | Read | ||
| IR | 10doc 30011 | Condenser Refrigerant Pressure - Ckt 2 | Absolute pressure, 0.1 kPa per count. | UINT16 | × 0.1 | kPa | Read | ||
| IR | 11doc 30012 | Condenser Saturated Refrigerant Temperature - Ckt 1 | 0.01 °C per count. | INT16 | × 0.01 | °C | Read | ||
| IR | 12doc 30013 | Condenser Saturated Refrigerant Temperature - Ckt 2 | 0.01 °C per count. | INT16 | × 0.01 | °C | Read | ||
| IR | 13doc 30014 | Local Atmospheric Pressure | Absolute pressure, 0.1 kPa per count. | UINT16 | × 0.1 | kPa | Read | ||
| IR | 30doc 30031 | Airflow Percentage- Circuit 1 | Percent type: 20,000 = 100 %. | INT16 | × 0.005 | % | Read | ||
| IR | 31doc 30032 | Airflow Percentage- Circuit 2 | Percent type: 20,000 = 100 %. | INT16 | × 0.005 | % | Read | ||
| IR | 32doc 30033 | Evaporator Entering Water Temp | 0.01 °C per count. | INT16 | × 0.01 | °C | Read | ||
| IR | 33doc 30034 | Evaporator Leaving Water Temp | 0.01 °C per count. | INT16 | × 0.01 | °C | Read | ||
| IR | 34doc 30035 | High Side Oil Pressure - Compressor 1A | Absolute pressure, 0.1 kPa per count. | UINT16 | × 0.1 | kPa | Read | ||
| IR | 35doc 30036 | High Side Oil Pressure - Compressor 1B | Absolute pressure, 0.1 kPa per count. | UINT16 | × 0.1 | kPa | Read | ||
| IR | 36doc 30037 | High Side Oil Pressure - Compressor 2A | Absolute pressure, 0.1 kPa per count. | UINT16 | × 0.1 | kPa | Read | ||
| IR | 37doc 30038 | High Side Oil Pressure - Compressor 2B | Absolute pressure, 0.1 kPa per count. | UINT16 | × 0.1 | kPa | Read | ||
| IR | 38doc 30039 | Oil Temp - Compressor 1A | 0.01 °C per count. | INT16 | × 0.01 | °C | Read | ||
| IR | 39doc 30040 | Oil Temp - Compressor 1B | 0.01 °C per count. | INT16 | × 0.01 | °C | Read | ||
| IR | 40doc 30041 | Oil Temp - Compressor 2A | 0.01 °C per count. | INT16 | × 0.01 | °C | Read | ||
| IR | 41doc 30042 | Oil Temp - Compressor 2B | 0.01 °C per count. | INT16 | × 0.01 | °C | Read | ||
| IR | 42doc 30043 | Outdoor Air Temperature | 0.01 °C per count. | INT16 | × 0.01 | °C | Read | ||
| IR | 43doc 30044 | Motor Voltage AB Starter 1A | UINT16 | V | Read | ||||
| IR | 44doc 30045 | Motor Voltage AB Starter 1B | UINT16 | V | Read | ||||
| IR | 45doc 30046 | Motor Voltage AB Starter 2A | UINT16 | V | Read | ||||
| IR | 46doc 30047 | Motor Current L1 Starter 1A | UINT16 | A | Read | ||||
| IR | 47doc 30048 | Motor Current L2 Starter 1A | UINT16 | A | Read | ||||
| IR | 48doc 30049 | Motor Current L3 Starter 1A | UINT16 | A | Read | ||||
| IR | 49doc 30050 | Motor Current L1 Starter 1B | UINT16 | A | Read | ||||
| IR | 50doc 30051 | Motor Current L2 Starter 1B | UINT16 | A | Read | ||||
| IR | 51doc 30052 | Motor Current L3 Starter 1B | UINT16 | A | Read | ||||
| IR | 52doc 30053 | Motor Current L1 Starter 2A | UINT16 | A | Read | ||||
| IR | 53doc 30054 | Motor Current L2 Starter 2A | UINT16 | A | Read | ||||
| IR | 54doc 30055 | Motor Current L3 Starter 2A | UINT16 | A | Read | ||||
| IR | 55doc 30056 | Motor Current L1 Starter 2B | UINT16 | A | Read | ||||
| IR | 56doc 30057 | Motor Current L2 Starter 2B | UINT16 | A | Read | ||||
| IR | 57doc 30058 | Motor Current L3 Starter 2B | UINT16 | A | Read | ||||
| IR | 58doc 30059 | Motor Current L1 % RLA Starter 1A | Percent type: 20,000 = 100 %. | INT16 | × 0.005 | % | Read | ||
| IR | 59doc 30060 | Motor Current L2 % RLA Starter 1A | Percent type: 20,000 = 100 %. | INT16 | × 0.005 | % | Read | ||
| IR | 60doc 30061 | Motor Current L3 % RLA Starter 1A | Percent type: 20,000 = 100 %. | INT16 | × 0.005 | % | Read | ||
| IR | 61doc 30062 | Motor Current L1 % RLA Starter 1B | Percent type: 20,000 = 100 %. | INT16 | × 0.005 | % | Read | ||
| IR | 62doc 30063 | Motor Current L2 % RLA Starter 1B | Percent type: 20,000 = 100 %. | INT16 | × 0.005 | % | Read | ||
| IR | 63doc 30064 | Motor Current L3 % RLA Starter 1B | Percent type: 20,000 = 100 %. | INT16 | × 0.005 | % | Read | ||
| IR | 64doc 30065 | Motor Current L1 % RLA Starter 2A | Percent type: 20,000 = 100 %. | INT16 | × 0.005 | % | Read | ||
| IR | 65doc 30066 | Motor Current L2 % RLA Starter 2A | Percent type: 20,000 = 100 %. | INT16 | × 0.005 | % | Read | ||
| IR | 66doc 30067 | Motor Current L3 % RLA Starter 2A | Percent type: 20,000 = 100 %. | INT16 | × 0.005 | % | Read | ||
| IR | 67doc 30068 | Motor Current L1 % RLA Starter 2B | Percent type: 20,000 = 100 %. | INT16 | × 0.005 | % | Read | ||
| IR | 68doc 30069 | Motor Current L2 % RLA Starter 2B | Percent type: 20,000 = 100 %. | INT16 | × 0.005 | % | Read | ||
| IR | 69doc 30070 | Motor Current L3 % RLA Starter 2B | Percent type: 20,000 = 100 %. | INT16 | × 0.005 | % | Read | ||
| IR | 74doc 30075 | Output Power AFD 1A | UINT16 | kW | Read | ||||
| IR | 75doc 30076 | Output Power AFD 2A | UINT16 | kW | Read | ||||
| IR | 76doc 30077 | Discharge Temperature Cprsr 1A | 0.01 °C per count. | INT16 | × 0.01 | °C | Read | ||
| IR | 77doc 30078 | Discharge Temperature Cprsr 2A | 0.01 °C per count. | INT16 | × 0.01 | °C | Read | ||
| IR | 78doc 30079 | Frequency Command Cprsr 1A | UINT16 | × 0.1 | Hz | Read | |||
| IR | 79doc 30080 | Frequency Command Cprsr 2A | UINT16 | × 0.1 | Hz | Read | |||
| IR | 80doc 30081 | Average Motor Current % RLA AFD 1A | Percent type: 20,000 = 100 %. | INT16 | × 0.005 | % | Read | ||
| IR | 81doc 30082 | Average Motor Current % RLA AFD 2A | Percent type: 20,000 = 100 %. | INT16 | × 0.005 | % | Read | ||
| IR | 82doc 30083 | Run Enabled | UINT16 | Read | 0 = False/Off/No/Disabled/Stop; 1 = True/On/Yes/Enabled/Auto | ||||
| IR | 83doc 30084 | Local Setpoint Control | UINT16 | Read | 0 = False/Off/No/Disabled/Stop; 1 = True/On/Yes/Enabled/Auto | ||||
| IR | 84doc 30085 | Chiller Limit Mode Indicator | UINT16 | Read | 0 = False/Off/No/Disabled/Stop; 1 = True/On/Yes/Enabled/Auto | ||||
| IR | 85doc 30086 | Chiller Running Indicator | UINT16 | Read | 0 = False/Off/No/Disabled/Stop; 1 = True/On/Yes/Enabled/Auto | ||||
| IR | 86doc 30087 | Maximum Capacity | UINT16 | Read | 0 = False/Off/No/Disabled/Stop; 1 = True/On/Yes/Enabled/Auto | ||||
| IR | 87doc 30088 | Compressor 1A Running | UINT16 | Read | 0 = False/Off/No/Disabled/Stop; 1 = True/On/Yes/Enabled/Auto | ||||
| IR | 88doc 30089 | Compressor 1B Running | UINT16 | Read | 0 = False/Off/No/Disabled/Stop; 1 = True/On/Yes/Enabled/Auto | ||||
| IR | 89doc 30090 | Compressor 2A Running | UINT16 | Read | 0 = False/Off/No/Disabled/Stop; 1 = True/On/Yes/Enabled/Auto | ||||
| IR | 90doc 30091 | Compressor 2B Running | UINT16 | Read | 0 = False/Off/No/Disabled/Stop; 1 = True/On/Yes/Enabled/Auto | ||||
| IR | 91doc 30092 | Evaporator Water Pump Command | UINT16 | Read | 0 = False/Off/No/Disabled/Stop; 1 = True/On/Yes/Enabled/Auto | ||||
| IR | 92doc 30093 | Evaporator Water Flow Status | UINT16 | Read | 0 = False/Off/No/Disabled/Stop; 1 = True/On/Yes/Enabled/Auto | ||||
| IR | 93doc 30094 | Alarm Present | UINT16 | Read | 0 = False/Off/No/Disabled/Stop; 1 = True/On/Yes/Enabled/Auto | ||||
| IR | 94doc 30095 | Shutdown Alarm Present | UINT16 | Read | 0 = False/Off/No/Disabled/Stop; 1 = True/On/Yes/Enabled/Auto | ||||
| IR | 96doc 30097 | Chiller Running Status | UINT16 | Read | 0 = Not running; 1 = Starting; 2 = Running; 3 = Stopping | ||||
| IR | 97doc 30098 | Operating Mode | UINT16 | Read | 0 = Cool; 2 = Ice | ||||
| IR | 98doc 30099 | Refrigerant Type | UINT16 | Read | 4 = R134a; 14 = R513A | ||||
| IR | 99doc 30100 | Model Information | UINT16 | Read | 0 = RTA | ||||
| IR | 100doc 30101 | Cooling Type | UINT16 | Read | 1 = Air Cooled | ||||
| IR | 101doc 30102 | Manufacturing Location | UINT16 | Read | 2 = Pueblo; 3 = Charmes; 13 = Curitiba; 14 = Taicang | ||||
| IR | 102doc 30103 | Last Diagnostic Code | UINT16 | Read | |||||
| HR | 0doc 40001 | BAS Chiller Auto Stop Command | UINT16 | Read/write | 0 = Stop; 1 = Auto | ||||
| HR | 1doc 40002 | BAS Chiller Mode Command | UINT16 | Read/write | 0 = Cool; 2 = Ice | ||||
| HR | 2doc 40003 | Chilled Water Setpoint | 0.01 °C per count. | INT16 | × 0.01 | °C | Read/write | ||
| HR | 3doc 40004 | Current Limit Setpoint | Percent type: 20,000 = 100 %. | INT16 | × 0.005 | % | Read/write | ||
| HR | 7doc 40008 | Remote Diagnostic Reset Command | UINT16 | Read/write | 0 = False (no reset); 1 = True (can reset) |
Notes on this map
- The object-format table gives one encoding per register type: Binary/Enumeration/Current/Voltage/Power/Frequency/Pressure are unsigned 16-bit; Percent, Percent_1, Power Factor, Differential Pressure and Temperature are signed 16-bit. Scales: Temperature 0.01 °C, Pressure 0.1 kPa absolute, Percent 0.005 % (20,000 = 100 %), Percent_1 1 %, Frequency 0.1 Hz, Power kW, Current A, Voltage V. Rows typed 'Temp' are read as Temperature.
- Values are always SI in this native map; there is no I-P switch in the list.
- Left out: compressor starts and run time (30015-30030), typed Count (u32) and Time (u32) over two registers; the list does not state the word order.
- Left out: Number of Circuits / Compressors (30071-30073), typed Count (u32) but printed as single registers, and Chiller Design Capacity (30074), typed 'Number', which the format table does not define.
- This RTAC also appears in the library under its Symbio 800 points list (rtac-symbio-800, BAS-PTS023A-EN); that list uses 32-bit float registers and different numbers. Use this map only for the UC800 native Modbus profile.
- The points list does not name the Modbus transport (RTU or TCP); it refers to BAS-SVP083*-EN for protocol setup, so confirm the transport in the controller configuration.
- Software Type and Software Revision (30001, 30002) are typed 'NA', which the format table does not list; they are shown as plain unsigned 16-bit values (the table's 'None' type).
Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.
Questions about the Trane RTAC air-cooled helical-rotary chiller (UC800 native Modbus profile)
What Modbus registers does the Trane RTAC air-cooled helical-rotary chiller (UC800 native Modbus profile) have?
This map lists 87 registers: 82 input registers, 5 holding registers. 5 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.
Are the Trane RTAC air-cooled helical-rotary chiller (UC800 native Modbus profile) Modbus addresses 0-based or 1-based?
The manufacturer's document numbers registers Modicon 3xxxx/4xxxx (drop the prefix, subtract 1). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. The list prints Modicon register numbers: 4xxxx are holding registers and 3xxxx input registers, so 40001 is holding register address 0 and 30034 is input register address 33.
What are the minimum Modbus registers to integrate the Trane RTAC air-cooled helical-rotary chiller (UC800 native Modbus profile)?
Start with IR 85 Chiller Running Indicator (Chiller running indicator); IR 96 Chiller Running Status (Chiller running status); IR 33 Evaporator Leaving Water Temp (Evaporator leaving water temperature); IR 2 Active Chilled Water Setpoint (Active chilled water setpoint); IR 4 Actual Running Capacity (Actual running capacity); IR 93 Alarm Present (Alarm present); HR 0 BAS Chiller Auto Stop Command (Chiller auto/stop command); HR 1 BAS Chiller Mode Command (Chiller mode command); HR 2 Chilled Water Setpoint (Chilled water setpoint (BAS)); HR 7 Remote Diagnostic Reset Command (Diagnostic reset).
How do I enable Modbus control of the Trane RTAC air-cooled helical-rotary chiller (UC800 native Modbus profile)?
The points list does not describe setup; it names BAS-SVP083*-EN as its reference integration guide for selecting Modbus on the controller.
Where is the official Trane RTAC air-cooled helical-rotary chiller (UC800 native Modbus profile) Modbus documentation?
The source is Symbio 800 Integration Points List, BACnet/Modbus, RTAC (UC800) (BAS-PTS032A-EN), revision 2024-12-06, published free by Trane at https://elibrary.tranetechnologies.com/public/commercial-hvac/Literature/Points%20List/BAS-PTS032A-EN_12062024.pdf.
More Trane Modbus register maps
- Chiller
Trane Agility water-cooled centrifugal chiller (Symbio 800)
Trane Agility water-cooled chillers with Symbio 800 controls, as listed in BAS-PTS007C-EN (6/30/2026).
Also known as: Agility, HDWA, Agility water-cooled chiller - Chiller
Trane Ascend ACR Series C air-cooled chiller (Symbio 800)
Trane Ascend model ACR Series C air-cooled chillers with the Symbio 800 controller, as listed in BAS-PTS021A-EN (11/15/2024).
Also known as: ACR, Ascend ACR, ACR Series C, Ascend air-cooled chiller ACR - Chiller
Trane Ascend ACS / ACX air-cooled scroll chiller and heat pump (Symbio 800)
Trane Ascend ACS air-cooled scroll chillers and ACX air-to-water heat pumps with the Symbio 800 controller, as listed in BAS-PTS011A-EN (11/15/2024).
Also known as: ACS, ACX, Ascend ACS, Ascend ACX, Ascend air-cooled chiller, Ascend air-to-water heat pump - Chiller
Trane CenTraVac CTV-Duplex water-cooled centrifugal chiller (UC800 native Modbus)
Trane Duplex CenTraVac (two-compressor) water-cooled centrifugal chillers with the Tracer UC800 controller, as listed in the Modbus section of BAS-PTS030A-EN (12/6/2024).
Also known as: CTV-Duplex, CTVD, CenTraVac Duplex, Duplex CenTraVac UC800 - Chiller
Trane CenTraVac duplex centrifugal chiller (Symbio 800)
Trane dual-compressor (duplex) CenTraVac water-cooled centrifugal chillers fitted with the Symbio 800 controller, as listed in the Duplex tables of BAS-PTS009C-EN (12/12/2025).
Also known as: CDHF, CDHG, CDHH, CenTraVac Duplex Symbio 800 - Chiller
Trane CenTraVac simplex centrifugal chiller (Symbio 800)
Trane single-compressor (simplex) CenTraVac water-cooled centrifugal chillers fitted with the Symbio 800 controller, as listed in the Simplex tables of BAS-PTS009C-EN (12/12/2025).
Also known as: CVHE, CVHF, CVHG, CVHH, CVHL, CVHM, CVHS, CVGF, CVR, CVZA, CVXA, CenTraVac Simplex Symbio 800, CenTraVac simplex - Chiller
Trane CGAM air-cooled scroll chiller (Symbio 800)
Trane CGAM air-cooled scroll chillers with the Symbio 800 controller, as listed in BAS-PTS019A-EN (11/15/2024).
Also known as: CGAM, Trane CGAM, CGAM air-cooled scroll chiller - Chiller
Trane RTAC air-cooled helical-rotary chiller (Symbio 800)
Trane RTAC air-cooled helical-rotary chillers with the Symbio 800 controller, as listed in BAS-PTS023A-EN (11/8/2024).
Also known as: RTAC, Series R RTAC - Chiller
Trane Series R RTHD water-cooled helical-rotary chiller (Symbio 800)
Trane Series R model RTHD water-cooled helical-rotary chillers with the Symbio 800 controller, as listed in BAS-PTS015A-EN (11/15/2024).
Also known as: RTHD, Series R RTHD - Chiller
Trane Series R RTWD water-cooled helical-rotary chiller (Symbio 800)
Trane Series R model RTWD water-cooled helical-rotary chillers with the Symbio 800 controller, as listed in BAS-PTS017A-EN (11/15/2024).
Also known as: RTWD, Series R RTWD, RTUD - Chiller
Trane Sintesis RTAF air-cooled screw chiller (Symbio 800)
Trane Sintesis RTAF air-cooled helical-rotary chillers with the Symbio 800 controller, as listed in BAS-PTS013B-EN (4/7/2026).
Also known as: RTAF, Sintesis RTAF, Sintesis air-cooled chiller - Pump (data-centre coolant distribution unit)
Trane TCDU coolant distribution unit (data-centre liquid cooling)
Trane Coolant Distribution Unit (TCDU) for direct-to-chip liquid cooling, as documented in IOM DC-SVX001A-EN (April 2025).
Also known as: TCDU, Trane CDU, Trane Coolant Distribution Unit, DC-SVX001A - Sensor (refrigerant leak monitor for chiller plant rooms)
Trane TruSense RMWH refrigerant monitor (up to 16 points)
Trane TruSense RMWH multipoint photoacoustic refrigerant monitor with Modbus RTU selected, per IOM PART-SVX008A-EN (30 Sep 2025, preliminary).
Also known as: TruSense, RMWH, Trane refrigerant monitor, PART-SVX008A, RMWH-SVX001
Other chillers & heat pumps register maps
- Chiller
Aermec WTX water-cooled chiller with Turbocor compressors (pCO5+ BMS)
Aermec WTX oil-free (Danfoss Turbocor) water-cooled chillers with the pCO5+ controller, via the AER485P1 RS485 card or AERNET; BMS manual for WTX 5009100_00 (1705).
Also known as: WTX, TBX - Chiller
Daikin Applied Magnitude WMT magnetic-bearing centrifugal chiller (MicroTech controller)
Daikin Applied Magnitude WMT water-cooled magnetic-bearing centrifugal chillers with the MicroTech unit controller and BACnet/Modbus communication module set to Modbus, per ED 19131-1.
Also known as: WMT, Magnitude WMT, Daikin WMT, ED 19131 - Chiller
Daikin Applied Trailblazer AGZ-F air-cooled scroll chiller (MicroTech controller)
Daikin Applied Trailblazer AGZ F-vintage air-cooled scroll chillers with the MicroTech unit controller and BACnet/Modbus communication module set to Modbus, per ED 19131-1 (application 1.2.0 and later).
Also known as: AGZ-F, AGZ F-Vintage, Trailblazer AGZ, Trailblazer AGZ-F, ED 19131 - Chiller
Daikin Applied Magnitude WMC-E magnetic-bearing centrifugal chiller (MicroTech controller)
Daikin Applied Magnitude WMC E-vintage water-cooled magnetic-bearing centrifugal chillers with the MicroTech unit controller and BACnet/Modbus communication module set to Modbus, per ED 19131-1.
Also known as: WMC-E, WMC E-Vintage, Magnitude WMC, Daikin WMC, ED 19131 - Chiller
Daikin Applied Pathfinder AWS air-cooled screw chiller (MicroTech controller)
Daikin Applied Pathfinder AWS air-cooled screw chillers with the MicroTech chiller unit controller and Modbus communication module, per ED 15121-13 (both application-version columns, 2507500204 and earlier / 2507500205 and later, mark the same data points).
Also known as: AWS, Pathfinder AWS, Daikin AWS, ED 15121 - Chiller
Daikin Applied ADS air-cooled global screw chiller (MicroTech controller)
Daikin Applied model ADS air-cooled global screw chillers with the MicroTech chiller unit controller and Modbus communication module, per ED 15121-13.
Also known as: ADS, Daikin ADS, Air-cooled Global Screw Chiller, ED 15121
All chillers & heat pumps Modbus register maps →
Source: Symbio 800 Integration Points List, BACnet/Modbus, RTAC (UC800) · BAS-PTS032A-EN · rev. 2024-12-06. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.