- WTX water-cooled chiller with Turbocor compressors (pCO5+ BMS)
Chiller · Modbus register map
Aermec WTX water-cooled chiller with Turbocor compressors (pCO5+ BMS) Modbus register map
Updated 17 November 2026
The WTX controller is a Carel pCO5+ that answers Modbus RTU through the AER485P1 card. This map lists the integer registers (chiller mode, compressor states, currents, voltages, demand and limits, run-hour counters, unit status) and the digital points (on/off, alarm reset, relay outputs and the full alarm list for up to four Turbocor compressors).
This page lists 293 Modbus registers for the Aermec WTX water-cooled chiller with Turbocor compressors (pCO5+ BMS) — 4 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Aermec’s own free documentation (linked below) and checked against it.
- Manufacturer
- Aermec
- Model
- WTX water-cooled chiller with Turbocor compressors (pCO5+ BMS)
- Equipment type
- Chiller
- Registers
- 293 (4 writable)
- Transport
- Modbus RTU
- Default unit ID
- Not stated
- Default serial
- 19200 baud, 8N2
- Documented addressing
- 0-based (the number printed is the address on the wire)
- Also known as
- WTX, TBX
Integration notes: Aermec WTX water-cooled chiller with Turbocor compressors (pCO5+ BMS)
Read coil 1 for unit on, coil 100 (sum of all alarms) and integer 5206 for unit status; write coil 10 to switch the plant from the BMS and coil 2 to reset alarms. Demand limit is integer 5012 (R/W).
Minimum registers to map
Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.
| Register | Name | Type | Why | Access |
|---|---|---|---|---|
| CO 1 | On / Off Unit | BIT | Unit on/off status | Read |
| CO 10 | On / Off plant by supervisor | BIT | Plant on/off by BMS | Read/write |
| CO 2 | Reset alarms | BIT | Alarm reset | Read/write |
| HR 5206 | Units Status | UINT16 | Unit status | Read |
| HR 5012 | Cold demand limit | UINT16 | Cooling demand limit % | Read/write |
| HR 5025 | Total plant request | UINT16 | Total plant request % | Read |
| HR 5002 | Chiller Mode | UINT16 | Chiller mode | Read/write |
| CO 100 | Sum of all alarms | BIT | Sum of all alarms | Read |
Enable Modbus control & writes
Fit the AER485P1 card (RS485) or AERNET (Ethernet) in the pCO5+ BMS slot; BMS card defaults are 19200 baud, no parity, 2 stop bits.
Byte order & addressing
- Addresses are protocol (base 0) addresses; do not subtract 1.
- Integers live at 5001 + Carel index; digitals and analogues use the plain index.
Network setup
- Set the BMS address and serial settings on the pCO5+ to match the master (default 19200 baud, 8N2 as listed).
Watch out for
- Without a stated scale, verify any analogue value you add against the unit display before using it.
Aermec WTX water-cooled chiller with Turbocor compressors (pCO5+ BMS) Modbus registers
Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.
| Table | Address | Name | Description | Type | Order | Scale | Units | Access | Values / bits |
|---|---|---|---|---|---|---|---|---|---|
| CO | 1 | On / Off Unit | 1 = unit on. | BIT | Read | ||||
| CO | 2 | Reset alarms | Write 1 to reset. | BIT | Read/write | ||||
| CO | 4 | ID1 digital input | 0 = closed, 1 = open. | BIT | Read | ||||
| CO | 10 | On / Off plant by supervisor | BMS on/off command. | BIT | Read/write | ||||
| CO | 13 | Compressor Alarm 1 | BIT | Read | |||||
| CO | 14 | Compressor Alarm 2 | BIT | Read | |||||
| CO | 30 | NO1 - Pump 1 evaporator | BIT | Read | |||||
| CO | 31 | NO14 - Pump 2 evaporator | BIT | Read | |||||
| CO | 32 | NO2 - Antifreeze resistance | BIT | Read | |||||
| CO | 33 | NO4 - EEV valve suction | BIT | Read | |||||
| CO | 34 | NO5 - Conservation Consent | BIT | Read | |||||
| CO | 35 | NO7 - I / LOCK 1 - Turbocharger Consent 1 | BIT | Read | |||||
| CO | 36 | Compressor 1 ON | BIT | Read | |||||
| CO | 37 | Compressor 2 ON | BIT | Read | |||||
| CO | 38 | NO12 - I / BLOCK 2 - Turbocharger Consent 2 | BIT | Read | |||||
| CO | 42 | NO3 - Fan / condenser pump | BIT | Read | |||||
| CO | 43 | Turbocharger Solenoid Inverter 1 | BIT | Read | |||||
| CO | 44 | Turbocharger solenoid 2 | BIT | Read | |||||
| CO | 45 | Solenoid turbocharger engine 1 | BIT | Read | |||||
| CO | 46 | Solenoid turbocharger 2 | BIT | Read | |||||
| CO | 49 | NO13 - I / BLOCK 3 - Turbocharger Consent 3 | BIT | Read | |||||
| CO | 50 | NO15 - I / BLOCK 4 - Turbocharger Consent 4 | BIT | Read | |||||
| CO | 51 | Compressor 3 ON | BIT | Read | |||||
| CO | 52 | Compressor 4 ON | BIT | Read | |||||
| CO | 53 | Turbocharger Solenoid Inverter 3 | BIT | Read | |||||
| CO | 54 | Turbocharger solenoid inverter 4 | BIT | Read | |||||
| CO | 55 | Solenoid turbocharger 3 | BIT | Read | |||||
| CO | 56 | Turbocharged solenoid engine 4 | BIT | Read | |||||
| CO | 78 | AL108 - Turbocor2 SCR phase | 1 = alarm active. | BIT | Read | ||||
| CO | 79 | AL109 - Turbocor2 Offline | 1 = alarm active. | BIT | Read | ||||
| CO | 80 | AL110 - Turbocor2 Startup failed | 1 = alarm active. | BIT | Read | ||||
| CO | 81 | AL111 - EVD Offline | 1 = alarm active. | BIT | Read | ||||
| CO | 82 | AL112 - EVD Probe S1 error | 1 = alarm active. | BIT | Read | ||||
| CO | 83 | AL113 - EVD Probe S2 Error | 1 = alarm active. | BIT | Read | ||||
| CO | 84 | AL114 - EVD Engine Error EEV | 1 = alarm active. | BIT | Read | ||||
| CO | 85 | AL115 - EVD Eeprom error | 1 = alarm active. | BIT | Read | ||||
| CO | 86 | AL116 - Low Liquid Level | 1 = alarm active. | BIT | Read | ||||
| CO | 87 | AL117 - High Liquid Level | 1 = alarm active. | BIT | Read | ||||
| CO | 88 | AL118 - Disconnected Modbus master (communication with Turbocor) | 1 = alarm active. | BIT | Read | ||||
| CO | 89 | AL119 - Thermal compressor 2 | 1 = alarm active. | BIT | Read | ||||
| CO | 90 | AL120 - EEV, Battery Low | 1 = alarm active. | BIT | Read | ||||
| CO | 93 | AL123 - Fuga Gas (ID16 Open) | 1 = alarm active. | BIT | Read | ||||
| CO | 100 | Sum of all alarms | BIT | Read | |||||
| CO | 101 | AL001 - Digital input | 1 = alarm active. | BIT | Read | ||||
| CO | 102 | AL002 - Voltage or phase monitor | 1 = alarm active. | BIT | Read | ||||
| CO | 103 | AL003 - Evaporator Antifreeze | 1 = alarm active. | BIT | Read | ||||
| CO | 104 | AL004 - Compressor Thermal 1 | 1 = alarm active. | BIT | Read | ||||
| CO | 105 | AL005 - Plant Flow Switch | 1 = alarm active. | BIT | Read | ||||
| CO | 106 | AL006 - Digital input, EEV | 1 = alarm active. | BIT | Read | ||||
| CO | 107 | AL007 - Pressure High Pressure | 1 = alarm active. | BIT | Read | ||||
| CO | 108 | AL008 - High Pressure Transducer | 1 = alarm active. | BIT | Read | ||||
| CO | 109 | AL009 - Low Pressure Pressure Switch | 1 = alarm active. | BIT | Read | ||||
| CO | 110 | AL010 - Low Pressure Transducer | 1 = alarm active. | BIT | Read | ||||
| CO | 111 | AL011 - Low pressure | 1 = alarm active. | BIT | Read | ||||
| CO | 112 | AL012 - Fan heat / condenser pump | 1 = alarm active. | BIT | Read | ||||
| CO | 113 | AL013 - Heat pump 1 plant | 1 = alarm active. | BIT | Read | ||||
| CO | 114 | AL014 - Heat pump 2 plant | 1 = alarm active. | BIT | Read | ||||
| CO | 115 | AL015 - Maintenance of pump 1 plant | 1 = alarm active. | BIT | Read | ||||
| CO | 116 | AL016 - Maintenance of pump 2 plant | 1 = alarm active. | BIT | Read | ||||
| CO | 117 | AL017 - Compressor Maintenance 1 | 1 = alarm active. | BIT | Read | ||||
| CO | 118 | AL018 - Compressor Maintenance 2 | 1 = alarm active. | BIT | Read | ||||
| CO | 119 | AL019 - Probe U1 faulty or disconnected | 1 = alarm active. | BIT | Read | ||||
| CO | 120 | AL020 - Probe U2 faulty or disconnected | 1 = alarm active. | BIT | Read | ||||
| CO | 121 | AL021 - Probe U3 faulty or disconnected | 1 = alarm active. | BIT | Read | ||||
| CO | 122 | AL022 - Probe U4 faulty or disconnected | 1 = alarm active. | BIT | Read | ||||
| CO | 123 | AL023 - Probe U5 faulty or disconnected | 1 = alarm active. | BIT | Read | ||||
| CO | 124 | AL024 - Probe U6 faulty or disconnected | 1 = alarm active. | BIT | Read | ||||
| CO | 125 | AL025 - Probe U7 faulty or disconnected | 1 = alarm active. | BIT | Read | ||||
| CO | 126 | AL026 - Probe U8 faulty or disconnected | 1 = alarm active. | BIT | Read | ||||
| CO | 127 | AL027 - Probe U9 faulty or disconnected | 1 = alarm active. | BIT | Read | ||||
| CO | 128 | AL028 - Probe U10 faulty or disconnected | 1 = alarm active. | BIT | Read | ||||
| CO | 129 | AL029 - Turbocor1 High Temperature Gas Pressed | 1 = alarm active. | BIT | Read | ||||
| CO | 130 | AL030 - Turbocor2 High Pressure Gas Temperature | 1 = alarm active. | BIT | Read | ||||
| CO | 131 | AL031 - Turbocor1 Inverter temp. | 1 = alarm active. | BIT | Read | ||||
| CO | 132 | AL032 - Turbocor1 Discharge temp | 1 = alarm active. | BIT | Read | ||||
| CO | 133 | AL033 - Turbocor1 Suction press. | 1 = alarm active. | BIT | Read | ||||
| CO | 134 | AL034 - Turbocor1 Discharge press. | 1 = alarm active. | BIT | Read | ||||
| CO | 135 | AL035 - Turbocor1 Rotor Lock | 1 = alarm active. | BIT | Read | ||||
| CO | 136 | AL036 - Turbocor1 Phase current | 1 = alarm active. | BIT | Read | ||||
| CO | 137 | AL037 - Turbocor1 Cavity temp. | 1 = alarm active. | BIT | Read | ||||
| CO | 138 | AL038 - Turbocor1 overcurrent | 1 = alarm active. | BIT | Read | ||||
| CO | 139 | AL039 - Turbocor1 Compressor ratio | 1 = alarm active. | BIT | Read | ||||
| CO | 140 | AL040 - Turbocor1 DC Low Voltage | 1 = alarm active. | BIT | Read | ||||
| CO | 141 | AL041 - Turbocor1 SCR temp. | 1 = alarm active. | BIT | Read | ||||
| CO | 142 | AL042 - Turbocor1 System Locked out | 1 = alarm active. | BIT | Read | ||||
| CO | 143 | AL043 - Turbocor1 Calibration failed | 1 = alarm active. | BIT | Read | ||||
| CO | 144 | AL044 - Turbocor1 Startup failed | 1 = alarm active. | BIT | Read | ||||
| CO | 145 | AL045 - Turbocor1 Axial displacement | 1 = alarm active. | BIT | Read | ||||
| CO | 146 | AL046 - Turbocor1 Axial static load | 1 = alarm active. | BIT | Read | ||||
| CO | 147 | AL047 - Turbocor1 Front radial disp X | 1 = alarm active. | BIT | Read | ||||
| CO | 148 | AL048 - Turbocor1 Front radial disp Y | 1 = alarm active. | BIT | Read | ||||
| CO | 149 | AL049 - Turbocor1 Front radial load X | 1 = alarm active. | BIT | Read | ||||
| CO | 150 | AL050 - Turbocor1 Front radial load Y | 1 = alarm active. | BIT | Read | ||||
| CO | 151 | AL051 - Turbocor1 Back radial disp X | 1 = alarm active. | BIT | Read | ||||
| CO | 152 | AL052 - Turbocor1 Back radial disp Y | 1 = alarm active. | BIT | Read | ||||
| CO | 153 | AL053 - Turbocor1 Back radial load X | 1 = alarm active. | BIT | Read | ||||
| CO | 154 | AL054 - Turbocor1 Back radial load Y | 1 = alarm active. | BIT | Read | ||||
| CO | 155 | AL055 - Turbocor1 Single phase Overcurrent | 1 = alarm active. | BIT | Read | ||||
| CO | 156 | AL056 - Turbocor1 DC High voltage | 1 = alarm active. | BIT | Read | ||||
| CO | 157 | AL057 - Turbocor1 High current | 1 = alarm active. | BIT | Read | ||||
| CO | 158 | AL058 - Turbocor1 Sensors error | 1 = alarm active. | BIT | Read | ||||
| CO | 159 | AL059 - Turbocor1 IGBT error | 1 = alarm active. | BIT | Read | ||||
| CO | 160 | AL060 - Turbocor1 High winding temp. | 1 = alarm active. | BIT | Read | ||||
| CO | 161 | AL061 - Turbocor1 Bearing error | 1 = alarm active. | BIT | Read | ||||
| CO | 162 | AL062 - Turbocor1 Superheat | 1 = alarm active. | BIT | Read | ||||
| CO | 163 | AL063 - Turbocor1 Inverter error signal | 1 = alarm active. | BIT | Read | ||||
| CO | 164 | AL064 - Turbocor1 AVC data missing | 1 = alarm active. | BIT | Read | ||||
| CO | 165 | AL065 - Turbocor1 Motor Back EMF low | 1 = alarm active. | BIT | Read | ||||
| CO | 166 | AL066 - Turbocor1 EEprom error | 1 = alarm active. | BIT | Read | ||||
| CO | 167 | AL067 - Turbocor1 Generator mode | 1 = alarm active. | BIT | Read | ||||
| CO | 168 | AL068 - Turbocor1 SCR phase | 1 = alarm active. | BIT | Read | ||||
| CO | 169 | AL069 - Turbocor1 Offline | 1 = alarm active. | BIT | Read | ||||
| CO | 170 | AL070 - Turbocor1 Startup failed | 1 = alarm active. | BIT | Read | ||||
| CO | 171 | AL071 - Turbocor2 Inverter temp. | 1 = alarm active. | BIT | Read | ||||
| CO | 172 | AL072 - Turbocor2 Discharge temp. | 1 = alarm active. | BIT | Read | ||||
| CO | 173 | AL073 - Turbocor2 Suction Press. | 1 = alarm active. | BIT | Read | ||||
| CO | 174 | AL074 - Turbocor2 Discharge press. | 1 = alarm active. | BIT | Read | ||||
| CO | 175 | AL075 - Turbocor2 Rotor Lock | 1 = alarm active. | BIT | Read | ||||
| CO | 176 | AL076 - Turbocor2 Phase current | 1 = alarm active. | BIT | Read | ||||
| CO | 177 | AL077 - Turbocor2 Cavity temp. | 1 = alarm active. | BIT | Read | ||||
| CO | 178 | AL078 - Turbocor2 overcurrent | 1 = alarm active. | BIT | Read | ||||
| CO | 179 | AL079 - Turbocor2 Compressor ratio | 1 = alarm active. | BIT | Read | ||||
| CO | 180 | AL080 - Turbocor2 DC Low Voltage | 1 = alarm active. | BIT | Read | ||||
| CO | 181 | AL081 - Turbocor2 SCR temp. | 1 = alarm active. | BIT | Read | ||||
| CO | 182 | AL082 - Turbocor2 System Locked out | 1 = alarm active. | BIT | Read | ||||
| CO | 183 | AL083 - Turbocor2 Calibration failed | 1 = alarm active. | BIT | Read | ||||
| CO | 184 | AL084 - Turbocor2 Startup failed | 1 = alarm active. | BIT | Read | ||||
| CO | 185 | AL085 - Turbocor2 Axial displacement | 1 = alarm active. | BIT | Read | ||||
| CO | 186 | AL086 - Turbocor2 Axial static load | 1 = alarm active. | BIT | Read | ||||
| CO | 187 | AL087 - Turbocor2 Front radial disp X | 1 = alarm active. | BIT | Read | ||||
| CO | 188 | AL088 - Turbocor2 Front radial disp Y | 1 = alarm active. | BIT | Read | ||||
| CO | 189 | AL089 - Turbocor2 Front radial load X | 1 = alarm active. | BIT | Read | ||||
| CO | 190 | AL090 - Turbocor2 Front radial load Y | 1 = alarm active. | BIT | Read | ||||
| CO | 191 | AL091 - Turbocor2 Back radial disp X | 1 = alarm active. | BIT | Read | ||||
| CO | 192 | AL092 - Turbocor2 Back radial disp Y | 1 = alarm active. | BIT | Read | ||||
| CO | 193 | AL093 - Turbocor2 Back radial load X | 1 = alarm active. | BIT | Read | ||||
| CO | 194 | AL094 - Turbocor2 Back radial load Y | 1 = alarm active. | BIT | Read | ||||
| CO | 195 | AL095 - Turbocor2 Single phase Overcurrent | 1 = alarm active. | BIT | Read | ||||
| CO | 196 | AL096 - Turbocor2 DC High Voltage | 1 = alarm active. | BIT | Read | ||||
| CO | 197 | AL097 - Turbocor2 High current | 1 = alarm active. | BIT | Read | ||||
| CO | 198 | AL098 - Turbocor2 Sensors error | 1 = alarm active. | BIT | Read | ||||
| CO | 199 | AL099 - Turbocor2 IGBT error | 1 = alarm active. | BIT | Read | ||||
| CO | 200 | AL100 - Turbocor2 High winding temp | 1 = alarm active. | BIT | Read | ||||
| CO | 201 | AL101 - Turbocor2 Bearing error | 1 = alarm active. | BIT | Read | ||||
| CO | 202 | AL102 - Turbocor2 Superheat | 1 = alarm active. | BIT | Read | ||||
| CO | 203 | AL103 - Turbocor2 Inverter error signal | 1 = alarm active. | BIT | Read | ||||
| CO | 204 | AL104 - Turbocor2 AVC data missing | 1 = alarm active. | BIT | Read | ||||
| CO | 205 | AL105 - Turbocor2 Motor Back EMF low | 1 = alarm active. | BIT | Read | ||||
| CO | 206 | AL106 - Turbocor2 EEprom error | 1 = alarm active. | BIT | Read | ||||
| CO | 207 | AL107 - Turbocor2 Generator mode | 1 = alarm active. | BIT | Read | ||||
| CO | 225 | AL125 - Compressor Maintenance 3 | 1 = alarm active. | BIT | Read | ||||
| CO | 226 | AL126 - Compressor Maintenance 4 | 1 = alarm active. | BIT | Read | ||||
| CO | 227 | AL127 - Reset Parameters ... Reboot Card! | 1 = alarm active. | BIT | Read | ||||
| CO | 228 | AL128 - Turbocor3 High Temperature Gas Pressed | 1 = alarm active. | BIT | Read | ||||
| CO | 229 | AL129 - Turbocor4 High Temperature Gas Pressed | 1 = alarm active. | BIT | Read | ||||
| CO | 230 | Compressor Alarm 3 | BIT | Read | |||||
| CO | 231 | Compressor Alarm 4 | BIT | Read | |||||
| CO | 232 | AL130 - Compressor Thermal 3 | 1 = alarm active. | BIT | Read | ||||
| CO | 233 | AL131 - Compressor Thermal 4 | 1 = alarm active. | BIT | Read | ||||
| CO | 251 | AL151 - Turbocor3 Inverter temp. | 1 = alarm active. | BIT | Read | ||||
| CO | 252 | AL152 - Turbocor3 Discharge temp. | 1 = alarm active. | BIT | Read | ||||
| CO | 253 | AL153 - Turbocor3 Suction Press. | 1 = alarm active. | BIT | Read | ||||
| CO | 254 | AL154 - Turbocor3 Discharge press. | 1 = alarm active. | BIT | Read | ||||
| CO | 255 | AL155 - Turbocor3 Rotor Lock | 1 = alarm active. | BIT | Read | ||||
| CO | 256 | AL156 - Turbocor3 Phase current | 1 = alarm active. | BIT | Read | ||||
| CO | 257 | AL157 - Turbocor3 Cavity temp. | 1 = alarm active. | BIT | Read | ||||
| CO | 258 | AL158 - Turbocor3 overcurrent | 1 = alarm active. | BIT | Read | ||||
| CO | 259 | AL159 - Turbocor3 Compressor ratio | 1 = alarm active. | BIT | Read | ||||
| CO | 260 | AL160 - Turbocor3 DC Low Voltage | 1 = alarm active. | BIT | Read | ||||
| CO | 261 | AL161 - Turbocor3 SCR temp. | 1 = alarm active. | BIT | Read | ||||
| CO | 262 | AL162 - Turbocor3 System Locked out | 1 = alarm active. | BIT | Read | ||||
| CO | 263 | AL163 - Turbocor3 Calibration failed | 1 = alarm active. | BIT | Read | ||||
| CO | 264 | AL164 - Turbocor3 Startup failed | 1 = alarm active. | BIT | Read | ||||
| CO | 265 | AL165 - Turbocor3 Axial displacement | 1 = alarm active. | BIT | Read | ||||
| CO | 266 | AL166 - Turbocor3 Axial static load | 1 = alarm active. | BIT | Read | ||||
| CO | 267 | AL167 - Turbocor3 Front radial disp X | 1 = alarm active. | BIT | Read | ||||
| CO | 268 | AL168 - Turbocor3 Front radial disp Y | 1 = alarm active. | BIT | Read | ||||
| CO | 269 | AL169 - Turbocor3 Front radial load X | 1 = alarm active. | BIT | Read | ||||
| CO | 270 | AL170 - Turbocor3 Front radial load Y | 1 = alarm active. | BIT | Read | ||||
| CO | 271 | AL171 - Turbocor3 Back radial disp X | 1 = alarm active. | BIT | Read | ||||
| CO | 272 | AL172 - Turbocor3 Back radial disp Y | 1 = alarm active. | BIT | Read | ||||
| CO | 273 | AL173 - Turbocor3 Back radial load X | 1 = alarm active. | BIT | Read | ||||
| CO | 274 | AL174 - Turbocor3 Back radial load Y | 1 = alarm active. | BIT | Read | ||||
| CO | 275 | AL175 - Turbocor3 Single phase Overcurrent | 1 = alarm active. | BIT | Read | ||||
| CO | 276 | AL176 - Turbocor3 DC High Voltage | 1 = alarm active. | BIT | Read | ||||
| CO | 277 | AL177 - Turbocor3 High current | 1 = alarm active. | BIT | Read | ||||
| CO | 278 | AL178 - Turbocor3 Sensors error | 1 = alarm active. | BIT | Read | ||||
| CO | 279 | AL179 - Turbocor3 IGBT error | 1 = alarm active. | BIT | Read | ||||
| CO | 280 | AL180 - Turbocor3 High winding temp | 1 = alarm active. | BIT | Read | ||||
| CO | 281 | AL181 - Turbocor3 Bearing error | 1 = alarm active. | BIT | Read | ||||
| CO | 282 | AL182 - Turbocor3 Superheat | 1 = alarm active. | BIT | Read | ||||
| CO | 283 | AL183 - Turbocor3 Inverter error signal | 1 = alarm active. | BIT | Read | ||||
| CO | 284 | AL184 - Turbocor3 24Vdc fault | 1 = alarm active. | BIT | Read | ||||
| CO | 285 | AL185 - Turbocor3 Motor Back EMF low | 1 = alarm active. | BIT | Read | ||||
| CO | 286 | AL186 - Turbocor3 EEprom error | 1 = alarm active. | BIT | Read | ||||
| CO | 287 | AL187 - Turbocor3 Generator mode | 1 = alarm active. | BIT | Read | ||||
| CO | 288 | AL188 - Turbocor3 SCR phase | 1 = alarm active. | BIT | Read | ||||
| CO | 289 | AL189 - Turbocor3 Offline | 1 = alarm active. | BIT | Read | ||||
| CO | 290 | AL190 - Turbocor3 Startup failed | 1 = alarm active. | BIT | Read | ||||
| CO | 291 | AL191 - Turbocor4 Inverter temp. | 1 = alarm active. | BIT | Read | ||||
| CO | 292 | AL192 - Turbocor4 Discharge temp. | 1 = alarm active. | BIT | Read | ||||
| CO | 293 | AL193 - Turbocor4 Suction Press. | 1 = alarm active. | BIT | Read | ||||
| CO | 294 | AL194 - Turbocor4 Discharge press. | 1 = alarm active. | BIT | Read | ||||
| CO | 295 | AL195 - Turbocor4 Rotor Lock | 1 = alarm active. | BIT | Read | ||||
| CO | 296 | AL196 - Turbocor4 Phase current | 1 = alarm active. | BIT | Read | ||||
| CO | 297 | AL197 - Turbocor4 Cavity temp. | 1 = alarm active. | BIT | Read | ||||
| CO | 298 | AL198 - Turbocor4 overcurrent | 1 = alarm active. | BIT | Read | ||||
| CO | 299 | AL199 - Turbocor4 Compressor ratio | 1 = alarm active. | BIT | Read | ||||
| CO | 300 | AL200 - Turbocor4 DC Low Voltage | 1 = alarm active. | BIT | Read | ||||
| CO | 301 | AL201 - Turbocor4 SCR temp. | 1 = alarm active. | BIT | Read | ||||
| CO | 302 | AL202 - Turbocor4 System Locked out | 1 = alarm active. | BIT | Read | ||||
| CO | 303 | AL203 - Turbocor4 Calibration failed | 1 = alarm active. | BIT | Read | ||||
| CO | 304 | AL204 - Turbocor4 Startup failed | 1 = alarm active. | BIT | Read | ||||
| CO | 305 | AL205 - Turbocor4 Axial displacement | 1 = alarm active. | BIT | Read | ||||
| CO | 306 | AL206 - Turbocor4 Axial static load | 1 = alarm active. | BIT | Read | ||||
| CO | 307 | AL207 - Turbocor4 Front radial disp X | 1 = alarm active. | BIT | Read | ||||
| CO | 308 | AL208 - Turbocor4 Front radial disp Y | 1 = alarm active. | BIT | Read | ||||
| CO | 309 | AL209 - Turbocor4 Front radial load X | 1 = alarm active. | BIT | Read | ||||
| CO | 310 | AL210 - Turbocor4 Front radial load Y | 1 = alarm active. | BIT | Read | ||||
| CO | 311 | AL211 - Turbocor4 Back radial disp X | 1 = alarm active. | BIT | Read | ||||
| CO | 312 | AL212 - Turbocor4 Back radial disp Y | 1 = alarm active. | BIT | Read | ||||
| CO | 313 | AL213 - Turbocor4 Back radial load X | 1 = alarm active. | BIT | Read | ||||
| CO | 314 | AL214 - Turbocor4 Back radial load Y | 1 = alarm active. | BIT | Read | ||||
| CO | 315 | AL215 - Turbocor4 Single phase Overcurrent | 1 = alarm active. | BIT | Read | ||||
| CO | 316 | AL216 - Turbocor4 DC High Voltage | 1 = alarm active. | BIT | Read | ||||
| CO | 317 | AL217 - Turbocor4 High current | 1 = alarm active. | BIT | Read | ||||
| CO | 318 | AL218 - Turbocor4 Sensors error | 1 = alarm active. | BIT | Read | ||||
| CO | 319 | AL219 - Turbocor4 IGBT error | 1 = alarm active. | BIT | Read | ||||
| CO | 320 | AL220 - Turbocor4 High winding temp | 1 = alarm active. | BIT | Read | ||||
| CO | 321 | AL221 - Turbocor4 Bearing error | 1 = alarm active. | BIT | Read | ||||
| CO | 322 | AL222 - Turbocor4 Superheat | 1 = alarm active. | BIT | Read | ||||
| CO | 323 | AL223 - Turbocor4 Inverter error signal | 1 = alarm active. | BIT | Read | ||||
| CO | 324 | AL224 - Turbocor4 24Vdc fault | 1 = alarm active. | BIT | Read | ||||
| CO | 325 | AL225 - Turbocor4 Motor Back EMF low | 1 = alarm active. | BIT | Read | ||||
| CO | 326 | AL226 - Turbocor4 EEprom error | 1 = alarm active. | BIT | Read | ||||
| CO | 327 | AL227 - Turbocor4 Generator mode | 1 = alarm active. | BIT | Read | ||||
| CO | 328 | AL228 - Turbocor4 SCR phase | 1 = alarm active. | BIT | Read | ||||
| CO | 329 | AL229 - Turbocor4 Offline | 1 = alarm active. | BIT | Read | ||||
| CO | 330 | AL230 - Turbocor4 Startup failed | 1 = alarm active. | BIT | Read | ||||
| HR | 5002 | Chiller Mode | UINT16 | Read/write | 0 = Comfort; 1 = Economy; 2 = From button | ||||
| HR | 5004 | Compressor state 1 | UINT16 | Read | 0 = Off; 1 = Lockout; 2 = Resetting; 3 = Ramping up; 4 = Partially closed; 5 = Normal; 6 = Max flow; 7 = Min IGV; 8 = Interlock open; 9 = Fault waiting; 10 = High temp stop; 11 = Loading up | ||||
| HR | 5005 | Compressor state 2 | UINT16 | Read | 0 = Off; 1 = Lockout; 2 = Resetting; 3 = Ramping up; 4 = Partially closed; 5 = Normal; 6 = Max flow; 7 = Min IGV; 8 = Interlock open; 9 = Fault waiting; 10 = High temp stop; 11 = Loading up | ||||
| HR | 5008 | Pump pump 2 plant, top part | Thousands of hours; add the matching lower-part register. | UINT16 | x1000 h | Read | |||
| HR | 5009 | Pump counter 1 plant, top part | Thousands of hours; add the matching lower-part register. | UINT16 | x1000 h | Read | |||
| HR | 5010 | Pump pump 1 plant, lower part | Hours below 1000; add to the matching upper-part register. | UINT16 | h | Read | |||
| HR | 5011 | Pump pump 2 plant, lower part | Hours below 1000; add to the matching upper-part register. | UINT16 | h | Read | |||
| HR | 5012 | Cold demand limit | UINT16 | % | Read/write | ||||
| HR | 5013 | Upper part counters, comp.1 | Thousands of hours; add the matching lower-part register. | UINT16 | x1000 h | Read | |||
| HR | 5014 | Lower part counters, comp.1 | Hours below 1000; add to the matching upper-part register. | UINT16 | h | Read | |||
| HR | 5015 | Upper part counters, comp.2 | Thousands of hours; add the matching lower-part register. | UINT16 | x1000 h | Read | |||
| HR | 5016 | Lower part counters, comp.2 | Hours below 1000; add to the matching upper-part register. | UINT16 | h | Read | |||
| HR | 5017 | Thermostatic request | UINT16 | % | Read | ||||
| HR | 5018 | Thermostatic demand limit (from multiplier U7 power limitation) | UINT16 | % | Read | ||||
| HR | 5020 | Required Limit Turbocor 1 | UINT16 | % | Read | ||||
| HR | 5021 | Required Limit Turbocor 2 | UINT16 | % | Read | ||||
| HR | 5025 | Total plant request | UINT16 | % | Read | ||||
| HR | 5026 | Required power Compressor 1 (%) | UINT16 | % | Read | ||||
| HR | 5027 | Required Power Compressor 2 (%) | UINT16 | % | Read | ||||
| HR | 5028 | Speed fans condenser pump | UINT16 | % | Read | ||||
| HR | 5029 | EEV_A, liquid electronic valve opening A (stp) | UINT16 | steps | Read | ||||
| HR | 5030 | EEV_A, liquid electronic valve opening A (%) | UINT16 | % | Read | ||||
| HR | 5031 | Current Compressor Power 1 | UINT16 | % | Read | ||||
| HR | 5032 | Current compressor power 2 | UINT16 | % | Read | ||||
| HR | 5033 | Compressor Current 1 | UINT16 | A | Read | ||||
| HR | 5034 | Compressor Current 2 | UINT16 | A | Read | ||||
| HR | 5035 | Compressor Voltage 1 | UINT16 | V | Read | ||||
| HR | 5036 | Compressor Voltage 2 | UINT16 | V | Read | ||||
| HR | 5048 | Upper part counters, comp.3 | Thousands of hours; add the matching lower-part register. | UINT16 | x1000 h | Read | |||
| HR | 5049 | Lower part counters, comp.3 | Hours below 1000; add to the matching upper-part register. | UINT16 | h | Read | |||
| HR | 5050 | Upper part counters, comp.4 | Thousands of hours; add the matching lower-part register. | UINT16 | x1000 h | Read | |||
| HR | 5051 | Lower part counters, comp.4 | Hours below 1000; add to the matching upper-part register. | UINT16 | h | Read | |||
| HR | 5052 | Software version Z (final part) | UINT16 | Read | |||||
| HR | 5071 | Configurator - Chiller Signal | UINT16 | Read | 0 = TBX; 1 = WTX | ||||
| HR | 5072 | WTX-Size Configurator | UINT16 | Read | |||||
| HR | 5073 | WTX Configurator - Efficiency | UINT16 | Read | |||||
| HR | 5074 | WTX Configurator - Exchanger | UINT16 | Read | |||||
| HR | 5075 | WTX Configurator - Version | UINT16 | Read | |||||
| HR | 5076 | WTX Configurator - Power | UINT16 | Read | |||||
| HR | 5102 | Compressor state 3 | UINT16 | Read | 0 = Off; 1 = Lockout; 2 = Resetting; 3 = Ramping up; 4 = Partially closed; 5 = Normal; 6 = Max flow; 7 = Min IGV; 8 = Interlock open; 9 = Fault waiting; 10 = High temp stop; 11 = Loading up | ||||
| HR | 5103 | Compressor state 4 | UINT16 | Read | 0 = Off; 1 = Lockout; 2 = Resetting; 3 = Ramping up; 4 = Partially closed; 5 = Normal; 6 = Max flow; 7 = Min IGV; 8 = Interlock open; 9 = Fault waiting; 10 = High temp stop; 11 = Loading up | ||||
| HR | 5106 | Required Limit Turbocor 3 | UINT16 | % | Read | ||||
| HR | 5107 | Required Limit Turbocor 4 | UINT16 | % | Read | ||||
| HR | 5108 | Required power Compressor 3 (%) | UINT16 | % | Read | ||||
| HR | 5109 | Required power Compressor 4 (%) | UINT16 | % | Read | ||||
| HR | 5110 | Current compressor power 3 | UINT16 | % | Read | ||||
| HR | 5111 | Current compressor power 4 | UINT16 | % | Read | ||||
| HR | 5112 | Compressor Current 3 | UINT16 | A | Read | ||||
| HR | 5113 | Compressor Current 4 | UINT16 | A | Read | ||||
| HR | 5114 | Compressor Voltage 3 | UINT16 | V | Read | ||||
| HR | 5115 | Compressor Voltage 4 | UINT16 | V | Read | ||||
| HR | 5206 | Units Status | Value 9 is cut off in the source. | UINT16 | Read | 1 = On; 2 = Alarm; 3 = Reboot; 4 = Off BMS; 5 = Off scheduler; 6 = Off digital input; 7 = Off touch display; 8 = Not used | |||
| HR | 6240 | EEV_B, liquid electronic valve opening B (%) | UINT16 | % | Read | ||||
| HR | 6241 | EEV_B, liquid electronic valve opening B (stp) | UINT16 | steps | Read |
Notes on this map
- Left out: all analogue variables (temperatures, pressures, setpoints, addresses 1-205). The manual lists ranges like -999.9 to 999.9 but never states the register scale, so the raw-to-value factor is not settled.
- Also left out: compressor speed, minimum and maximum speed registers (5006/5007, 5037-5040, 5104/5105, 5116-5119), because the '[0 ... 48000] / 10 RPM' wording does not make clear whether the register holds rpm or rpm/10; and 5003 (Aermec internal use).
- Run-hour counters come in two parts: an upper register in thousands of hours and a lower register in hours (0-999).
- Digital points are read with function 1 and written with function 5, so they are listed as coils; integer variables use functions 3 and 6.
Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.
Questions about the Aermec WTX water-cooled chiller with Turbocor compressors (pCO5+ BMS)
What Modbus registers does the Aermec WTX water-cooled chiller with Turbocor compressors (pCO5+ BMS) have?
This map lists 293 registers: 239 coils, 54 holding registers. 4 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.
Are the Aermec WTX water-cooled chiller with Turbocor compressors (pCO5+ BMS) Modbus addresses 0-based or 1-based?
The manufacturer's document numbers registers 0-based (the number printed is the address on the wire). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. The manual states protocol addresses are base 0 and that addresses start from zero; its example reads address 1 with the frame 01 03 00 01. The BMS addresses in the tables go on the wire unchanged. Integer variables sit at 5001 + the Carel index (Carel 1 = 5002).
What are the minimum Modbus registers to integrate the Aermec WTX water-cooled chiller with Turbocor compressors (pCO5+ BMS)?
Start with CO 1 On / Off Unit (Unit on/off status); CO 10 On / Off plant by supervisor (Plant on/off by BMS); CO 2 Reset alarms (Alarm reset); HR 5206 Units Status (Unit status); HR 5012 Cold demand limit (Cooling demand limit %); HR 5025 Total plant request (Total plant request %); HR 5002 Chiller Mode (Chiller mode); CO 100 Sum of all alarms (Sum of all alarms).
How do I enable Modbus control of the Aermec WTX water-cooled chiller with Turbocor compressors (pCO5+ BMS)?
Fit the AER485P1 card (RS485) or AERNET (Ethernet) in the pCO5+ BMS slot; BMS card defaults are 19200 baud, no parity, 2 stop bits.
Where is the official Aermec WTX water-cooled chiller with Turbocor compressors (pCO5+ BMS) Modbus documentation?
The source is Manuale per creazione BMS - BMS manual, Connessione tramite Internet ModBus, WTX (5009100_00), revision 2017-05, published free by Aermec at https://www.aermec.com/download?id=6523.
More Aermec Modbus register maps
- Split AC unit (VRF / split AC gateway built in)
Aermec LCG series DC inverter air conditioners (built-in Modbus)
Aermec LCG series DC inverter units whose indoor-unit controller has the built-in Modbus RTU interface; Modbus Protocol user manual LCG 5385758_02 (24.01).
Also known as: LCG - Split AC unit (VRF / split AC gateway built in)
Aermec LPG series DC inverter air conditioners (built-in Modbus)
Aermec LPG series DC inverter units whose indoor-unit controller has the built-in Modbus RTU interface; ModBus Protocol LPG series 5385759_02 (EN 25.05).
Also known as: LPG
Other chillers & heat pumps register maps
- Chiller
Daikin Applied Magnitude WMT magnetic-bearing centrifugal chiller (MicroTech controller)
Daikin Applied Magnitude WMT water-cooled magnetic-bearing centrifugal chillers with the MicroTech unit controller and BACnet/Modbus communication module set to Modbus, per ED 19131-1.
Also known as: WMT, Magnitude WMT, Daikin WMT, ED 19131 - Chiller
Daikin Applied Trailblazer AGZ-F air-cooled scroll chiller (MicroTech controller)
Daikin Applied Trailblazer AGZ F-vintage air-cooled scroll chillers with the MicroTech unit controller and BACnet/Modbus communication module set to Modbus, per ED 19131-1 (application 1.2.0 and later).
Also known as: AGZ-F, AGZ F-Vintage, Trailblazer AGZ, Trailblazer AGZ-F, ED 19131 - Chiller
Trane CenTraVac simplex centrifugal chiller (Symbio 800)
Trane single-compressor (simplex) CenTraVac water-cooled centrifugal chillers fitted with the Symbio 800 controller, as listed in the Simplex tables of BAS-PTS009C-EN (12/12/2025).
Also known as: CVHE, CVHF, CVHG, CVHH, CVHL, CVHM, CVHS, CVGF, CVR, CVZA, CVXA, CenTraVac Simplex Symbio 800, CenTraVac simplex - Sensor (refrigerant leak monitor for chiller plant rooms)
Trane TruSense RMWH refrigerant monitor (up to 16 points)
Trane TruSense RMWH multipoint photoacoustic refrigerant monitor with Modbus RTU selected, per IOM PART-SVX008A-EN (30 Sep 2025, preliminary).
Also known as: TruSense, RMWH, Trane refrigerant monitor, PART-SVX008A, RMWH-SVX001 - Chiller
Daikin Applied Magnitude WMC-E magnetic-bearing centrifugal chiller (MicroTech controller)
Daikin Applied Magnitude WMC E-vintage water-cooled magnetic-bearing centrifugal chillers with the MicroTech unit controller and BACnet/Modbus communication module set to Modbus, per ED 19131-1.
Also known as: WMC-E, WMC E-Vintage, Magnitude WMC, Daikin WMC, ED 19131 - Chiller
Daikin Applied Pathfinder AWS air-cooled screw chiller (MicroTech controller)
Daikin Applied Pathfinder AWS air-cooled screw chillers with the MicroTech chiller unit controller and Modbus communication module, per ED 15121-13 (both application-version columns, 2507500204 and earlier / 2507500205 and later, mark the same data points).
Also known as: AWS, Pathfinder AWS, Daikin AWS, ED 15121
All chillers & heat pumps Modbus register maps →
Source: Manuale per creazione BMS - BMS manual, Connessione tramite Internet ModBus, WTX · 5009100_00 · rev. 2017-05. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.