  4. WTX water-cooled chiller with Turbocor compressors (pCO5+ BMS)

Chiller · Modbus register map

Aermec WTX water-cooled chiller with Turbocor compressors (pCO5+ BMS) Modbus register map

Updated 17 November 2026

Short answer

The WTX controller is a Carel pCO5+ that answers Modbus RTU through the AER485P1 card. This map lists the integer registers (chiller mode, compressor states, currents, voltages, demand and limits, run-hour counters, unit status) and the digital points (on/off, alarm reset, relay outputs and the full alarm list for up to four Turbocor compressors).

This page lists 293 Modbus registers for the Aermec WTX water-cooled chiller with Turbocor compressors (pCO5+ BMS) — 4 writable — with the table, 0-based wire address, data type, word order, scale, units and access of each, re-typed from Aermec’s own free documentation (linked below) and checked against it.

Manufacturer
Aermec
Model
WTX water-cooled chiller with Turbocor compressors (pCO5+ BMS)
Equipment type
Chiller
Registers
293 (4 writable)
Transport
Modbus RTU
Default unit ID
Not stated
Default serial
19200 baud, 8N2
Documented addressing
0-based (the number printed is the address on the wire)
Also known as
WTX, TBX
Source document
Manuale per creazione BMS - BMS manual, Connessione tramite Internet ModBus, WTX · 5009100_00 · rev. 2017-05
Download CSV all columns JSON Manufacturer PDF ↗

Integration notes: Aermec WTX water-cooled chiller with Turbocor compressors (pCO5+ BMS)

Integration in brief

Read coil 1 for unit on, coil 100 (sum of all alarms) and integer 5206 for unit status; write coil 10 to switch the plant from the BMS and coil 2 to reset alarms. Demand limit is integer 5012 (R/W).

Minimum registers to map

Addresses are 0-based wire addresses. Enough to monitor and run the unit; map more as the job needs.

RegisterNameTypeWhyAccess
CO 1On / Off UnitBITUnit on/off statusRead
CO 10On / Off plant by supervisorBITPlant on/off by BMSRead/write
CO 2Reset alarmsBITAlarm resetRead/write
HR 5206Units StatusUINT16Unit statusRead
HR 5012Cold demand limitUINT16Cooling demand limit %Read/write
HR 5025Total plant requestUINT16Total plant request %Read
HR 5002Chiller ModeUINT16Chiller modeRead/write
CO 100Sum of all alarmsBITSum of all alarmsRead

Enable Modbus control & writes

Fit the AER485P1 card (RS485) or AERNET (Ethernet) in the pCO5+ BMS slot; BMS card defaults are 19200 baud, no parity, 2 stop bits.

Byte order & addressing

Network setup

Watch out for

Aermec WTX water-cooled chiller with Turbocor compressors (pCO5+ BMS) Modbus registers

Address = 0-based wire address (the documented number is shown under it when it differs) · Order: ABCD = high word first, CDAB = low word first · Scale: engineering value = raw × scale.

293 of 293 shown
Aermec WTX water-cooled chiller with Turbocor compressors (pCO5+ BMS) Modbus register map
TableAddressNameDescriptionTypeOrderScaleUnitsAccessValues / bits
CO1On / Off Unit1 = unit on.BITRead
CO2Reset alarmsWrite 1 to reset.BITRead/write
CO4ID1 digital input0 = closed, 1 = open.BITRead
CO10On / Off plant by supervisorBMS on/off command.BITRead/write
CO13Compressor Alarm 1BITRead
CO14Compressor Alarm 2BITRead
CO30NO1 - Pump 1 evaporatorBITRead
CO31NO14 - Pump 2 evaporatorBITRead
CO32NO2 - Antifreeze resistanceBITRead
CO33NO4 - EEV valve suctionBITRead
CO34NO5 - Conservation ConsentBITRead
CO35NO7 - I / LOCK 1 - Turbocharger Consent 1BITRead
CO36Compressor 1 ONBITRead
CO37Compressor 2 ONBITRead
CO38NO12 - I / BLOCK 2 - Turbocharger Consent 2BITRead
CO42NO3 - Fan / condenser pumpBITRead
CO43Turbocharger Solenoid Inverter 1BITRead
CO44Turbocharger solenoid 2BITRead
CO45Solenoid turbocharger engine 1BITRead
CO46Solenoid turbocharger 2BITRead
CO49NO13 - I / BLOCK 3 - Turbocharger Consent 3BITRead
CO50NO15 - I / BLOCK 4 - Turbocharger Consent 4BITRead
CO51Compressor 3 ONBITRead
CO52Compressor 4 ONBITRead
CO53Turbocharger Solenoid Inverter 3BITRead
CO54Turbocharger solenoid inverter 4BITRead
CO55Solenoid turbocharger 3BITRead
CO56Turbocharged solenoid engine 4BITRead
CO78AL108 - Turbocor2 SCR phase1 = alarm active.BITRead
CO79AL109 - Turbocor2 Offline1 = alarm active.BITRead
CO80AL110 - Turbocor2 Startup failed1 = alarm active.BITRead
CO81AL111 - EVD Offline1 = alarm active.BITRead
CO82AL112 - EVD Probe S1 error1 = alarm active.BITRead
CO83AL113 - EVD Probe S2 Error1 = alarm active.BITRead
CO84AL114 - EVD Engine Error EEV1 = alarm active.BITRead
CO85AL115 - EVD Eeprom error1 = alarm active.BITRead
CO86AL116 - Low Liquid Level1 = alarm active.BITRead
CO87AL117 - High Liquid Level1 = alarm active.BITRead
CO88AL118 - Disconnected Modbus master (communication with Turbocor)1 = alarm active.BITRead
CO89AL119 - Thermal compressor 21 = alarm active.BITRead
CO90AL120 - EEV, Battery Low1 = alarm active.BITRead
CO93AL123 - Fuga Gas (ID16 Open)1 = alarm active.BITRead
CO100Sum of all alarmsBITRead
CO101AL001 - Digital input1 = alarm active.BITRead
CO102AL002 - Voltage or phase monitor1 = alarm active.BITRead
CO103AL003 - Evaporator Antifreeze1 = alarm active.BITRead
CO104AL004 - Compressor Thermal 11 = alarm active.BITRead
CO105AL005 - Plant Flow Switch1 = alarm active.BITRead
CO106AL006 - Digital input, EEV1 = alarm active.BITRead
CO107AL007 - Pressure High Pressure1 = alarm active.BITRead
CO108AL008 - High Pressure Transducer1 = alarm active.BITRead
CO109AL009 - Low Pressure Pressure Switch1 = alarm active.BITRead
CO110AL010 - Low Pressure Transducer1 = alarm active.BITRead
CO111AL011 - Low pressure1 = alarm active.BITRead
CO112AL012 - Fan heat / condenser pump1 = alarm active.BITRead
CO113AL013 - Heat pump 1 plant1 = alarm active.BITRead
CO114AL014 - Heat pump 2 plant1 = alarm active.BITRead
CO115AL015 - Maintenance of pump 1 plant1 = alarm active.BITRead
CO116AL016 - Maintenance of pump 2 plant1 = alarm active.BITRead
CO117AL017 - Compressor Maintenance 11 = alarm active.BITRead
CO118AL018 - Compressor Maintenance 21 = alarm active.BITRead
CO119AL019 - Probe U1 faulty or disconnected1 = alarm active.BITRead
CO120AL020 - Probe U2 faulty or disconnected1 = alarm active.BITRead
CO121AL021 - Probe U3 faulty or disconnected1 = alarm active.BITRead
CO122AL022 - Probe U4 faulty or disconnected1 = alarm active.BITRead
CO123AL023 - Probe U5 faulty or disconnected1 = alarm active.BITRead
CO124AL024 - Probe U6 faulty or disconnected1 = alarm active.BITRead
CO125AL025 - Probe U7 faulty or disconnected1 = alarm active.BITRead
CO126AL026 - Probe U8 faulty or disconnected1 = alarm active.BITRead
CO127AL027 - Probe U9 faulty or disconnected1 = alarm active.BITRead
CO128AL028 - Probe U10 faulty or disconnected1 = alarm active.BITRead
CO129AL029 - Turbocor1 High Temperature Gas Pressed1 = alarm active.BITRead
CO130AL030 - Turbocor2 High Pressure Gas Temperature1 = alarm active.BITRead
CO131AL031 - Turbocor1 Inverter temp.1 = alarm active.BITRead
CO132AL032 - Turbocor1 Discharge temp1 = alarm active.BITRead
CO133AL033 - Turbocor1 Suction press.1 = alarm active.BITRead
CO134AL034 - Turbocor1 Discharge press.1 = alarm active.BITRead
CO135AL035 - Turbocor1 Rotor Lock1 = alarm active.BITRead
CO136AL036 - Turbocor1 Phase current1 = alarm active.BITRead
CO137AL037 - Turbocor1 Cavity temp.1 = alarm active.BITRead
CO138AL038 - Turbocor1 overcurrent1 = alarm active.BITRead
CO139AL039 - Turbocor1 Compressor ratio1 = alarm active.BITRead
CO140AL040 - Turbocor1 DC Low Voltage1 = alarm active.BITRead
CO141AL041 - Turbocor1 SCR temp.1 = alarm active.BITRead
CO142AL042 - Turbocor1 System Locked out1 = alarm active.BITRead
CO143AL043 - Turbocor1 Calibration failed1 = alarm active.BITRead
CO144AL044 - Turbocor1 Startup failed1 = alarm active.BITRead
CO145AL045 - Turbocor1 Axial displacement1 = alarm active.BITRead
CO146AL046 - Turbocor1 Axial static load1 = alarm active.BITRead
CO147AL047 - Turbocor1 Front radial disp X1 = alarm active.BITRead
CO148AL048 - Turbocor1 Front radial disp Y1 = alarm active.BITRead
CO149AL049 - Turbocor1 Front radial load X1 = alarm active.BITRead
CO150AL050 - Turbocor1 Front radial load Y1 = alarm active.BITRead
CO151AL051 - Turbocor1 Back radial disp X1 = alarm active.BITRead
CO152AL052 - Turbocor1 Back radial disp Y1 = alarm active.BITRead
CO153AL053 - Turbocor1 Back radial load X1 = alarm active.BITRead
CO154AL054 - Turbocor1 Back radial load Y1 = alarm active.BITRead
CO155AL055 - Turbocor1 Single phase Overcurrent1 = alarm active.BITRead
CO156AL056 - Turbocor1 DC High voltage1 = alarm active.BITRead
CO157AL057 - Turbocor1 High current1 = alarm active.BITRead
CO158AL058 - Turbocor1 Sensors error1 = alarm active.BITRead
CO159AL059 - Turbocor1 IGBT error1 = alarm active.BITRead
CO160AL060 - Turbocor1 High winding temp.1 = alarm active.BITRead
CO161AL061 - Turbocor1 Bearing error1 = alarm active.BITRead
CO162AL062 - Turbocor1 Superheat1 = alarm active.BITRead
CO163AL063 - Turbocor1 Inverter error signal1 = alarm active.BITRead
CO164AL064 - Turbocor1 AVC data missing1 = alarm active.BITRead
CO165AL065 - Turbocor1 Motor Back EMF low1 = alarm active.BITRead
CO166AL066 - Turbocor1 EEprom error1 = alarm active.BITRead
CO167AL067 - Turbocor1 Generator mode1 = alarm active.BITRead
CO168AL068 - Turbocor1 SCR phase1 = alarm active.BITRead
CO169AL069 - Turbocor1 Offline1 = alarm active.BITRead
CO170AL070 - Turbocor1 Startup failed1 = alarm active.BITRead
CO171AL071 - Turbocor2 Inverter temp.1 = alarm active.BITRead
CO172AL072 - Turbocor2 Discharge temp.1 = alarm active.BITRead
CO173AL073 - Turbocor2 Suction Press.1 = alarm active.BITRead
CO174AL074 - Turbocor2 Discharge press.1 = alarm active.BITRead
CO175AL075 - Turbocor2 Rotor Lock1 = alarm active.BITRead
CO176AL076 - Turbocor2 Phase current1 = alarm active.BITRead
CO177AL077 - Turbocor2 Cavity temp.1 = alarm active.BITRead
CO178AL078 - Turbocor2 overcurrent1 = alarm active.BITRead
CO179AL079 - Turbocor2 Compressor ratio1 = alarm active.BITRead
CO180AL080 - Turbocor2 DC Low Voltage1 = alarm active.BITRead
CO181AL081 - Turbocor2 SCR temp.1 = alarm active.BITRead
CO182AL082 - Turbocor2 System Locked out1 = alarm active.BITRead
CO183AL083 - Turbocor2 Calibration failed1 = alarm active.BITRead
CO184AL084 - Turbocor2 Startup failed1 = alarm active.BITRead
CO185AL085 - Turbocor2 Axial displacement1 = alarm active.BITRead
CO186AL086 - Turbocor2 Axial static load1 = alarm active.BITRead
CO187AL087 - Turbocor2 Front radial disp X1 = alarm active.BITRead
CO188AL088 - Turbocor2 Front radial disp Y1 = alarm active.BITRead
CO189AL089 - Turbocor2 Front radial load X1 = alarm active.BITRead
CO190AL090 - Turbocor2 Front radial load Y1 = alarm active.BITRead
CO191AL091 - Turbocor2 Back radial disp X1 = alarm active.BITRead
CO192AL092 - Turbocor2 Back radial disp Y1 = alarm active.BITRead
CO193AL093 - Turbocor2 Back radial load X1 = alarm active.BITRead
CO194AL094 - Turbocor2 Back radial load Y1 = alarm active.BITRead
CO195AL095 - Turbocor2 Single phase Overcurrent1 = alarm active.BITRead
CO196AL096 - Turbocor2 DC High Voltage1 = alarm active.BITRead
CO197AL097 - Turbocor2 High current1 = alarm active.BITRead
CO198AL098 - Turbocor2 Sensors error1 = alarm active.BITRead
CO199AL099 - Turbocor2 IGBT error1 = alarm active.BITRead
CO200AL100 - Turbocor2 High winding temp1 = alarm active.BITRead
CO201AL101 - Turbocor2 Bearing error1 = alarm active.BITRead
CO202AL102 - Turbocor2 Superheat1 = alarm active.BITRead
CO203AL103 - Turbocor2 Inverter error signal1 = alarm active.BITRead
CO204AL104 - Turbocor2 AVC data missing1 = alarm active.BITRead
CO205AL105 - Turbocor2 Motor Back EMF low1 = alarm active.BITRead
CO206AL106 - Turbocor2 EEprom error1 = alarm active.BITRead
CO207AL107 - Turbocor2 Generator mode1 = alarm active.BITRead
CO225AL125 - Compressor Maintenance 31 = alarm active.BITRead
CO226AL126 - Compressor Maintenance 41 = alarm active.BITRead
CO227AL127 - Reset Parameters ... Reboot Card!1 = alarm active.BITRead
CO228AL128 - Turbocor3 High Temperature Gas Pressed1 = alarm active.BITRead
CO229AL129 - Turbocor4 High Temperature Gas Pressed1 = alarm active.BITRead
CO230Compressor Alarm 3BITRead
CO231Compressor Alarm 4BITRead
CO232AL130 - Compressor Thermal 31 = alarm active.BITRead
CO233AL131 - Compressor Thermal 41 = alarm active.BITRead
CO251AL151 - Turbocor3 Inverter temp.1 = alarm active.BITRead
CO252AL152 - Turbocor3 Discharge temp.1 = alarm active.BITRead
CO253AL153 - Turbocor3 Suction Press.1 = alarm active.BITRead
CO254AL154 - Turbocor3 Discharge press.1 = alarm active.BITRead
CO255AL155 - Turbocor3 Rotor Lock1 = alarm active.BITRead
CO256AL156 - Turbocor3 Phase current1 = alarm active.BITRead
CO257AL157 - Turbocor3 Cavity temp.1 = alarm active.BITRead
CO258AL158 - Turbocor3 overcurrent1 = alarm active.BITRead
CO259AL159 - Turbocor3 Compressor ratio1 = alarm active.BITRead
CO260AL160 - Turbocor3 DC Low Voltage1 = alarm active.BITRead
CO261AL161 - Turbocor3 SCR temp.1 = alarm active.BITRead
CO262AL162 - Turbocor3 System Locked out1 = alarm active.BITRead
CO263AL163 - Turbocor3 Calibration failed1 = alarm active.BITRead
CO264AL164 - Turbocor3 Startup failed1 = alarm active.BITRead
CO265AL165 - Turbocor3 Axial displacement1 = alarm active.BITRead
CO266AL166 - Turbocor3 Axial static load1 = alarm active.BITRead
CO267AL167 - Turbocor3 Front radial disp X1 = alarm active.BITRead
CO268AL168 - Turbocor3 Front radial disp Y1 = alarm active.BITRead
CO269AL169 - Turbocor3 Front radial load X1 = alarm active.BITRead
CO270AL170 - Turbocor3 Front radial load Y1 = alarm active.BITRead
CO271AL171 - Turbocor3 Back radial disp X1 = alarm active.BITRead
CO272AL172 - Turbocor3 Back radial disp Y1 = alarm active.BITRead
CO273AL173 - Turbocor3 Back radial load X1 = alarm active.BITRead
CO274AL174 - Turbocor3 Back radial load Y1 = alarm active.BITRead
CO275AL175 - Turbocor3 Single phase Overcurrent1 = alarm active.BITRead
CO276AL176 - Turbocor3 DC High Voltage1 = alarm active.BITRead
CO277AL177 - Turbocor3 High current1 = alarm active.BITRead
CO278AL178 - Turbocor3 Sensors error1 = alarm active.BITRead
CO279AL179 - Turbocor3 IGBT error1 = alarm active.BITRead
CO280AL180 - Turbocor3 High winding temp1 = alarm active.BITRead
CO281AL181 - Turbocor3 Bearing error1 = alarm active.BITRead
CO282AL182 - Turbocor3 Superheat1 = alarm active.BITRead
CO283AL183 - Turbocor3 Inverter error signal1 = alarm active.BITRead
CO284AL184 - Turbocor3 24Vdc fault1 = alarm active.BITRead
CO285AL185 - Turbocor3 Motor Back EMF low1 = alarm active.BITRead
CO286AL186 - Turbocor3 EEprom error1 = alarm active.BITRead
CO287AL187 - Turbocor3 Generator mode1 = alarm active.BITRead
CO288AL188 - Turbocor3 SCR phase1 = alarm active.BITRead
CO289AL189 - Turbocor3 Offline1 = alarm active.BITRead
CO290AL190 - Turbocor3 Startup failed1 = alarm active.BITRead
CO291AL191 - Turbocor4 Inverter temp.1 = alarm active.BITRead
CO292AL192 - Turbocor4 Discharge temp.1 = alarm active.BITRead
CO293AL193 - Turbocor4 Suction Press.1 = alarm active.BITRead
CO294AL194 - Turbocor4 Discharge press.1 = alarm active.BITRead
CO295AL195 - Turbocor4 Rotor Lock1 = alarm active.BITRead
CO296AL196 - Turbocor4 Phase current1 = alarm active.BITRead
CO297AL197 - Turbocor4 Cavity temp.1 = alarm active.BITRead
CO298AL198 - Turbocor4 overcurrent1 = alarm active.BITRead
CO299AL199 - Turbocor4 Compressor ratio1 = alarm active.BITRead
CO300AL200 - Turbocor4 DC Low Voltage1 = alarm active.BITRead
CO301AL201 - Turbocor4 SCR temp.1 = alarm active.BITRead
CO302AL202 - Turbocor4 System Locked out1 = alarm active.BITRead
CO303AL203 - Turbocor4 Calibration failed1 = alarm active.BITRead
CO304AL204 - Turbocor4 Startup failed1 = alarm active.BITRead
CO305AL205 - Turbocor4 Axial displacement1 = alarm active.BITRead
CO306AL206 - Turbocor4 Axial static load1 = alarm active.BITRead
CO307AL207 - Turbocor4 Front radial disp X1 = alarm active.BITRead
CO308AL208 - Turbocor4 Front radial disp Y1 = alarm active.BITRead
CO309AL209 - Turbocor4 Front radial load X1 = alarm active.BITRead
CO310AL210 - Turbocor4 Front radial load Y1 = alarm active.BITRead
CO311AL211 - Turbocor4 Back radial disp X1 = alarm active.BITRead
CO312AL212 - Turbocor4 Back radial disp Y1 = alarm active.BITRead
CO313AL213 - Turbocor4 Back radial load X1 = alarm active.BITRead
CO314AL214 - Turbocor4 Back radial load Y1 = alarm active.BITRead
CO315AL215 - Turbocor4 Single phase Overcurrent1 = alarm active.BITRead
CO316AL216 - Turbocor4 DC High Voltage1 = alarm active.BITRead
CO317AL217 - Turbocor4 High current1 = alarm active.BITRead
CO318AL218 - Turbocor4 Sensors error1 = alarm active.BITRead
CO319AL219 - Turbocor4 IGBT error1 = alarm active.BITRead
CO320AL220 - Turbocor4 High winding temp1 = alarm active.BITRead
CO321AL221 - Turbocor4 Bearing error1 = alarm active.BITRead
CO322AL222 - Turbocor4 Superheat1 = alarm active.BITRead
CO323AL223 - Turbocor4 Inverter error signal1 = alarm active.BITRead
CO324AL224 - Turbocor4 24Vdc fault1 = alarm active.BITRead
CO325AL225 - Turbocor4 Motor Back EMF low1 = alarm active.BITRead
CO326AL226 - Turbocor4 EEprom error1 = alarm active.BITRead
CO327AL227 - Turbocor4 Generator mode1 = alarm active.BITRead
CO328AL228 - Turbocor4 SCR phase1 = alarm active.BITRead
CO329AL229 - Turbocor4 Offline1 = alarm active.BITRead
CO330AL230 - Turbocor4 Startup failed1 = alarm active.BITRead
HR5002Chiller ModeUINT16Read/write0 = Comfort; 1 = Economy; 2 = From button
HR5004Compressor state 1UINT16Read0 = Off; 1 = Lockout; 2 = Resetting; 3 = Ramping up; 4 = Partially closed; 5 = Normal; 6 = Max flow; 7 = Min IGV; 8 = Interlock open; 9 = Fault waiting; 10 = High temp stop; 11 = Loading up
HR5005Compressor state 2UINT16Read0 = Off; 1 = Lockout; 2 = Resetting; 3 = Ramping up; 4 = Partially closed; 5 = Normal; 6 = Max flow; 7 = Min IGV; 8 = Interlock open; 9 = Fault waiting; 10 = High temp stop; 11 = Loading up
HR5008Pump pump 2 plant, top partThousands of hours; add the matching lower-part register.UINT16x1000 hRead
HR5009Pump counter 1 plant, top partThousands of hours; add the matching lower-part register.UINT16x1000 hRead
HR5010Pump pump 1 plant, lower partHours below 1000; add to the matching upper-part register.UINT16hRead
HR5011Pump pump 2 plant, lower partHours below 1000; add to the matching upper-part register.UINT16hRead
HR5012Cold demand limitUINT16%Read/write
HR5013Upper part counters, comp.1Thousands of hours; add the matching lower-part register.UINT16x1000 hRead
HR5014Lower part counters, comp.1Hours below 1000; add to the matching upper-part register.UINT16hRead
HR5015Upper part counters, comp.2Thousands of hours; add the matching lower-part register.UINT16x1000 hRead
HR5016Lower part counters, comp.2Hours below 1000; add to the matching upper-part register.UINT16hRead
HR5017Thermostatic requestUINT16%Read
HR5018Thermostatic demand limit (from multiplier U7 power limitation)UINT16%Read
HR5020Required Limit Turbocor 1UINT16%Read
HR5021Required Limit Turbocor 2UINT16%Read
HR5025Total plant requestUINT16%Read
HR5026Required power Compressor 1 (%)UINT16%Read
HR5027Required Power Compressor 2 (%)UINT16%Read
HR5028Speed fans condenser pumpUINT16%Read
HR5029EEV_A, liquid electronic valve opening A (stp)UINT16stepsRead
HR5030EEV_A, liquid electronic valve opening A (%)UINT16%Read
HR5031Current Compressor Power 1UINT16%Read
HR5032Current compressor power 2UINT16%Read
HR5033Compressor Current 1UINT16ARead
HR5034Compressor Current 2UINT16ARead
HR5035Compressor Voltage 1UINT16VRead
HR5036Compressor Voltage 2UINT16VRead
HR5048Upper part counters, comp.3Thousands of hours; add the matching lower-part register.UINT16x1000 hRead
HR5049Lower part counters, comp.3Hours below 1000; add to the matching upper-part register.UINT16hRead
HR5050Upper part counters, comp.4Thousands of hours; add the matching lower-part register.UINT16x1000 hRead
HR5051Lower part counters, comp.4Hours below 1000; add to the matching upper-part register.UINT16hRead
HR5052Software version Z (final part)UINT16Read
HR5071Configurator - Chiller SignalUINT16Read0 = TBX; 1 = WTX
HR5072WTX-Size ConfiguratorUINT16Read
HR5073WTX Configurator - EfficiencyUINT16Read
HR5074WTX Configurator - ExchangerUINT16Read
HR5075WTX Configurator - VersionUINT16Read
HR5076WTX Configurator - PowerUINT16Read
HR5102Compressor state 3UINT16Read0 = Off; 1 = Lockout; 2 = Resetting; 3 = Ramping up; 4 = Partially closed; 5 = Normal; 6 = Max flow; 7 = Min IGV; 8 = Interlock open; 9 = Fault waiting; 10 = High temp stop; 11 = Loading up
HR5103Compressor state 4UINT16Read0 = Off; 1 = Lockout; 2 = Resetting; 3 = Ramping up; 4 = Partially closed; 5 = Normal; 6 = Max flow; 7 = Min IGV; 8 = Interlock open; 9 = Fault waiting; 10 = High temp stop; 11 = Loading up
HR5106Required Limit Turbocor 3UINT16%Read
HR5107Required Limit Turbocor 4UINT16%Read
HR5108Required power Compressor 3 (%)UINT16%Read
HR5109Required power Compressor 4 (%)UINT16%Read
HR5110Current compressor power 3UINT16%Read
HR5111Current compressor power 4UINT16%Read
HR5112Compressor Current 3UINT16ARead
HR5113Compressor Current 4UINT16ARead
HR5114Compressor Voltage 3UINT16VRead
HR5115Compressor Voltage 4UINT16VRead
HR5206Units StatusValue 9 is cut off in the source.UINT16Read1 = On; 2 = Alarm; 3 = Reboot; 4 = Off BMS; 5 = Off scheduler; 6 = Off digital input; 7 = Off touch display; 8 = Not used
HR6240EEV_B, liquid electronic valve opening B (%)UINT16%Read
HR6241EEV_B, liquid electronic valve opening B (stp)UINT16stepsRead

Notes on this map

Check it against the live device. A register map tells you what the controller can expose; the unit in front of you may differ by firmware or options. Read a few registers and compare them with the unit’s own display; for a 32-bit value the float and byte-order decoder shows all four word orders at once, so a wrong word order or scale is obvious. New to this? Read what a register map is and why addresses are off by one.

Questions about the Aermec WTX water-cooled chiller with Turbocor compressors (pCO5+ BMS)

What Modbus registers does the Aermec WTX water-cooled chiller with Turbocor compressors (pCO5+ BMS) have?

This map lists 293 registers: 239 coils, 54 holding registers. 4 of them can be written. Registers vary with firmware, options and configuration, so confirm against the device.

Are the Aermec WTX water-cooled chiller with Turbocor compressors (pCO5+ BMS) Modbus addresses 0-based or 1-based?

The manufacturer's document numbers registers 0-based (the number printed is the address on the wire). Every address on this page is the 0-based wire address you put in the request; the documented number is shown under it where it differs. The manual states protocol addresses are base 0 and that addresses start from zero; its example reads address 1 with the frame 01 03 00 01. The BMS addresses in the tables go on the wire unchanged. Integer variables sit at 5001 + the Carel index (Carel 1 = 5002).

What are the minimum Modbus registers to integrate the Aermec WTX water-cooled chiller with Turbocor compressors (pCO5+ BMS)?

Start with CO 1 On / Off Unit (Unit on/off status); CO 10 On / Off plant by supervisor (Plant on/off by BMS); CO 2 Reset alarms (Alarm reset); HR 5206 Units Status (Unit status); HR 5012 Cold demand limit (Cooling demand limit %); HR 5025 Total plant request (Total plant request %); HR 5002 Chiller Mode (Chiller mode); CO 100 Sum of all alarms (Sum of all alarms).

How do I enable Modbus control of the Aermec WTX water-cooled chiller with Turbocor compressors (pCO5+ BMS)?

Fit the AER485P1 card (RS485) or AERNET (Ethernet) in the pCO5+ BMS slot; BMS card defaults are 19200 baud, no parity, 2 stop bits.

Where is the official Aermec WTX water-cooled chiller with Turbocor compressors (pCO5+ BMS) Modbus documentation?

The source is Manuale per creazione BMS - BMS manual, Connessione tramite Internet ModBus, WTX (5009100_00), revision 2017-05, published free by Aermec at https://www.aermec.com/download?id=6523.

More Aermec Modbus register maps

Other chillers & heat pumps register maps

All chillers & heat pumps Modbus register maps →

Source: Manuale per creazione BMS - BMS manual, Connessione tramite Internet ModBus, WTX · 5009100_00 · rev. 2017-05. Register numbers, types, scaling and units are reproduced as published; descriptions are our own.